Академический Документы
Профессиональный Документы
Культура Документы
Model
FR-D700
p
x p a n d e d line-u K
E 0 -11K an
d 15
FR-D72 1K and 15K
0-1
FR-D74
•Features 1
(1) Safety stop function (1) 150%/1Hz high starting torque by General (2) Brake resistor can be connected •Outline
7
The FR-D700 series is compliant to the EU Provided by the user (present) FR-D700
-purpose magnetic flux vector control A brake transistor is built-in to the 0.4K or more.
dimension
drawings
Machinery Directive without the addition of General-purpose magnetic flux vector control and auto Connecting an optional brake resistor increases
Safety function
previously required external devices. is equipped regeneration capability. •Terminal connection
•Magnetic contactor (MC)
* tuning function are available.
Operation of an external Emergency Stop Emergency stop Emergency stop It is useful for deceleration time reduction of a machine with diagram
•Emergency stop wiring It ensures operation that requires high starting torque, such 11
device results in a highly reliable as transfer machine including conveyer, hoist, lift, etc., a large inertia, such as fan, and operation of lift, etc. •Terminal specification
immediate shutoff of the D700's output to explanation
washing machine, and agitators.
the motor. •High torque of 150%/1Hz and 200%/3Hz (3.7K or less) is
This safety stop function conforms to the realized (when the slip compensation function is valid). •Operation panel 13
following standards. •Auto tuning •Parameter unit
Only one MC is recommended
For conventional model... instead of two. Many kinds of motors can be optimally controlled with
EN ISO 13849-1 Category 3 / PLd Two MCs were necessary Although MC is not required Mitsubishi original "non-rotation" auto tuning function. (R1
for the safety stop function. constants tuning)
EN62061 / IEC61508 SIL2 •High cost
•Maintenance of two MCs was •Cost reduction
•Parameter list 16
necessary •Maintenance of one MC
•Installation space was necessary •Installation space is reduced
With spring clamp terminals*, the wiring became easier and more secure. (example: (example: automated storage)
(example: conveyer) industrial washing machine)
*: Main circuit terminal is screw terminal.
•Option and 24
•Wiring is completed only
Easy wiring •Spring structure in terminal contact
Highly reliable (3) Enhanced function peripheral devices
•The design life of the capacitors has been extended to 10 years output when the life span is near. applications with variable load
control enables tension control by dancer roll.
by the adoption of a capacitor endures 5000 hours at 105˚C torque characteristic such as
surrounding air temperature*1,*2. *4: If any one of main circuit capacitor, control circuit capacitor, inrush current restriction fan and pump.
(example: air-conditioning fan)
•Traverse
Traverse function
*1: Surrounding air temperature : annual average 40˚C (free from corrosive gas, flammable gas,
circuit or cooling fan reaches the output level, an alarm is output. Capacity of the main function for wind-up drum of spinning machine
circuit capacitor can be measured by setting parameter at a stop and turning the power
oil mist, dust and dirt) Since the design life is a calculated value, it is not a guaranteed and wiredrawing machine prevents unevenness and
from off to on. Measuring the capacity enables alarm to be output.
value.
*2: Output current : 80% of the inverter rated current
The cooling fan outputs alarm by using fan speed detection. deformation at thread winding.
Features
(1) Quick setup with the setting dial (1) Easy replacement of cooling fan (2) Combed shaped wiring cover
Setting dial is the feature of Mitsubishi inverters. A cooling fan is provided on top Since a cover can be fitted
•Displayed numbers can be jumped by turning the setting dial quickly, and numbers can of the inverter of all capacities after wiring, wiring work is
Specifications
Standard
be changed one by one by turning it slowly, enabling speedy parameter setting. requiring a cooling fan (1.5K or easily done.
•The nonslip setting dial is easier to turn. more).
A cooling fan can be easily
replaced without disconnecting
Dimension
Drawings
Outline
(2) Easy setting from (3) Enclosure surface operation panel main circuit wires.
Terminal Specification
Optional enclosure surface operation panel (FR-PA07) can be
Terminal Connection
Explanation
Diagram
connected. In addition, an operation panel for the FR-E500 series
Connecting a personal computer and the inverter via RS-485
can be connected.
communication enables setting with wizard (interactive) function of
The operation panel of the inverter can not be removed.
the FR Configurator (inverter setup software). A parameter unit connection cable (FR-CB20 ) is
(1) RoHS Directive compliant (3) EMC Directive compliant noise filter
Operation panel
Parameter unit
In addition, a parameter setting can be converted from the separately necessary.
Parameter
equipment sold in the market after July 1, 2006 do not contain lead, cadmium, mercury,
List
An optional parameter unit (FR-PU07) can be connected as well. hexavalent chromium, polybrominated biphenyl (PBB) and polybrominated diphenyl ether
(PBDE) flame retardants.
A parameter unit connection cable (FR-CB20 ) is separately necessary.
Complies with UL, cUL, EC Directives
<G> mark indicating RoHS Directive compliance is printed on the package.
Setting wizard function (example: acceleration/deceleration time setting) (4)
•Setting such as direct input method with a numeric
(2) Filterpack FR-BFP2 (option) (CE marking) as a standard model.
Protective
Functions
keypad, operation status indication, and help
function are usable.
Eight languages can be displayed. Power factor improving DC reactor, zero phase reactor, and
•Parameter setting values of maximum of three capacitative filter (radio noise filter), are frequently-used units for
inverters can be stored. an air conditioning application. The filterpack combines those
Options
three units are available as an option.
Acceleration/deceleration
7 Lineup
pattern setting
Instructions
(5) Enhanced communication function
Acceleration/deceleration The lineup of three phase 200V/400V class goes to 15K.
time setting • Mitsubishi inverter protocol and Modbus-RTU
•For a use in harsh environment, special unit with board coating is also available. Please contact our sales representative.
Communication speed of RS-485 has been improved
•For the FR-D700 series, North American (NA), EU (EC), and Chinese (CHT) specifications also are supported.
FR-D700 Series
Difference List
(communication at 38.4kbps is available)
Specification
*: This catalog explains based on the Japanese specifications.
"Multi command mode" has been added to Mitsubishi inverter protocol Consult our sales office for specifications of each country.
Parameter list display (data processing time of the inverter has been reduced to 1/4)
Supports Modbus-RTU
F R-D 740 -0. 4K
International
FA Center
Warranty
4 Compact and space saving Symbol Voltage Symbol Number of Power Phases Symbol Inverter Capacity
1 100V class None Three-phase input
(1) Easily replaceable compact body (2) Side by side installation saves space 2 200V class S Single-phase input 0.1K to 15K
Indicate capacity
"kW".
4 400V class Single-phase input
W
Installation size is the same as that of the FR-S500 series which is Space can be saved by side by side no clearance installation*. (double voltage output)
the smallest model of the Mitsubishi inverter. *: Use the inverter at the surrounding air temperature of 40˚C or less.
Power
Inverter Model 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Supply
Three phase
FR-D720- K
200V
128mm Three phase
FR-D740- K
400V
Single phase
FR-D720S- K
200V *
FR-D740-0.4K FR-S540E-0.4K Single phase
FR-D710W- K
100V *
*: Output of the single-phase 200V and single-phase 100V input models is three-phase 200V. :Available models :Not available
3 4
Standard specifications
Rating
z Three-phase 200V power supply
Model FR-D720-
K 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Model FR-D720-
-NA 008 014 025 042 070 100 165 238 318 — —
Applicable motor capacity (kW)∗1 0.1 0.2 0.4 0.75 1.5 2.2 3.7 5.5 7.5 11 15
Rated capacity (kVA)∗2 0.3 0.6 1.0 1.7 2.8 4.0 6.6 9.5 12.7 17.9 23.1
Rated current (A) 0.8 1.4 2.5 4.2 7.0 10.0 16.5 23.8 31.8 45.0 58.0
Output
Permissible AC voltage
170 to 264V 50Hz/60Hz
fluctuation
Permissible frequency fluctuation ±5%
Power supply capacity (kVA)∗6 0.4 0.7 1.2 2.1 4.0 5.5 9.0 12.0 17.0 20.0 27.0
Protective structure (JEM1030) Enclosed type (IP20).
Cooling system Self-cooling Forced air cooling
Approximate mass (kg) 0.5 0.5 0.8 1.0 1.4 1.4 1.8 3.6 3.6 6.5 6.5
Power supply capacity (kVA)∗6 1.5 2.5 4.5 5.5 9.5 12.0 17.0 20.0 28.0
the pulse voltage value of the inverter output side voltage remains unchanged at about 2 that of the power supply.
∗5 The braking torque indicated is a short-duration average torque (which varies with motor loss) when the motor alone is decelerated from 60Hz in the shortest
time and is not a continuous regenerative torque. When the motor is decelerated from the frequency higher than the base frequency, the average
deceleration torque will reduce. Since the inverter does not contain a brake resistor, use the optional brake resistor when regenerative energy is large. A
brake unit (FR-BU2) may also be used.
∗6 The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).
5
z Single-phase 200V power supply
Model FR-D720S-
K 0.1 0.2 0.4 0.75 1.5 2.2
Features
Model FR-D720S-
-NA 008 014 025 042 070 100
Model FR-D720S-
-EC 008 014 025 042 070 100
Model FR-D720S-
K-CHT 0.1 0.2 0.4 0.75 1.5 2.2
Specifications
Applicable motor capacity (kW)∗1 0.1 0.2 0.4 0.75 1.5 2.2
Standard
Rated capacity (kVA)∗2 0.3 0.6 1.0 1.7 2.8 4.0
Rated current (A) 0.8 1.4 2.5 4.2 7.0 10.0
Output
Dimension
Drawings
Outline
Regenerative braking torque∗5 150% 100% 50% 20%
Rated input AC voltage/frequency Single-phase 200 to 240V 50Hz/60Hz
Power supply
Terminal Specification
Terminal Connection
Explanation
Diagram
Power supply capacity (kVA)∗6 0.5 0.9 1.5 2.3 4.0 5.2
Protective structure (JEM1030) Enclosed type (IP20).
Cooling system Self-cooling Forced air cooling
Operation panel
Approximate mass (kg) 0.5 0.5 0.9 1.1 1.5 2.0
Parameter unit
z Single-phase 100V power supply
Model FR-D710W-
K 0.1 0.2 0.4 0.75
Model FR-D710W-
-NA 008 014 025 042
Parameter
List
Applicable motor capacity (kW)∗1 0.1 0.2 0.4 0.75
Rated capacity (kVA)∗2 0.3 0.6 1.0 1.7
Rated current (A) 0.8 1.4 2.5 4.2
Output
Protective
Functions
Overload current rating∗3
(inverse-time characteristics)
Voltage Three-phase 200 to 230V∗7, ∗8
Regenerative braking torque∗5 150% 100%
Rated input AC voltage/frequency Single-phase 100 to 115V 50Hz/60Hz
Power supply
Options
Permissible AC voltage fluctuation 90 to 132V 50Hz/60Hz
Permissible frequency fluctuation ±5%
Instructions
Protective structure (JEM1030) Enclosed type (IP20).
Cooling system Self-cooling
Approximate mass (kg) 0.6 0.7 0.9 1.4
∗1 The applicable motor capacity indicated is the maximum capacity applicable for use of the Mitsubishi 4-pole standard motor.
FR-D700 Series
Difference List
Specification
∗2 The rated output capacity indicated assumes that the output voltage is 230V.
∗3 The % value of the overload current rating indicated is the ratio of the overload current to the inverter's rated output current. For repeated duty, allow time for
the inverter and motor to return to or below the temperatures under 100% load. If the automatic restart after instantaneous power failure function (Pr. 57) or
power failure stop function (Pr. 261) is set and power supply voltage is low while load becomes bigger, the bus voltage decreases to power failure detection
level and load of 100% or more may not be available.
International
∗4
FA Center
The maximum output voltage does not exceed the power supply voltage. The maximum output voltage can be changed within the setting range. However,
Warranty
the pulse voltage value of the inverter output side voltage remains unchanged at about 2 that of the power supply.
∗5 The braking torque indicated is a short-duration average torque (which varies with motor loss) when the motor alone is decelerated from 60Hz in the shortest
time and is not a continuous regenerative torque. When the motor is decelerated from the frequency higher than the base frequency, the average
deceleration torque will reduce. Since the inverter does not contain a brake resistor, use the optional brake resistor when regenerative energy is large. A
brake unit (FR-BU2) may also be used.
∗6 The power supply capacity varies with the value of the power supply side inverter impedance (including those of the input reactor and cables).
∗7 For single-phase 100V power input model, the maximum output voltage is twice the amount of the power supply voltage and cannot be exceeded.
∗8 In a single-phase 100V power input model, the output voltage may fall down when the load is heavy, and larger output current may flow compared to a three-
phase input model. Use the motor with less load so that the output current is within the rated motor current range.
6
Common specifications
Soft-PWM control/high carrier frequency PWM control (V/F control, General-purpose magnetic flux vector control,
Control method
and Optimum excitation control are available)
Output frequency range 0.2 to 400Hz
0.06Hz/60Hz (terminal2, 4: 0 to 10V/10bit)
Control specifications
operation switchover, command source switchover, inverter operation enable signal, and PU operation external
interlock.
Maximum/minimum frequency setting, frequency jump operation, external thermal relay input selection, automatic
restart after instantaneous power failure operation, forward/reverse rotation prevention, remote setting, second
Operational functions function, multi-speed operation, regeneration avoidance, slip compensation, operation mode selection, offline
auto tuning function, PID control, computer link operation (RS-485), Optimum excitation control, power failure
stop, speed smoothing control, Modbus-RTU
Output signal The following signals can be assigned to Pr.190, Pr.192 and Pr.197 (output terminal function selection): inverter
Open collector output (two terminals) operation, up-to-frequency, overload alarm, output frequency detection, regenerative brake prealarm, electronic
Relay output (one terminal) thermal relay function prealarm, inverter operation ready, output current detection, zero current detection, PID
lower limit, PID upper limit, PID forward/reverse rotation output, fan alarm∗1, heatsink overheat pre-alarm,
deceleration at an instantaneous power failure, PID control activated, PID output interruption, safety monitor
Operating status output, safety monitor output 2, during retry, life alarm, current average value monitor, remote output, alarm
output, fault output, fault output 3, and maintenance timer alarm.
The following signals can be assigned to Pr.54 FM terminal function selection: output frequency, output current
(steady), output voltage, frequency setting, converter output voltage, regenerative brake duty, electronic thermal
For meter
relay function load factor, output current peak value, converter output voltage peak value, reference voltage
Pulse train output
output, motor load factor, PID set point, PID measured value, output power, PID deviation, motor thermal load
(MAX 2.4kHz: one terminal) factor, and inverter thermal load factor.
Pulse train output (1440 pulses/s/full scale)
The following operating status can be displayed: output frequency, output current (steady), output voltage,
frequency setting, cumulative energization time, actual operation time, converter output voltage, regenerative
Operating status brake duty, electronic thermal relay function load factor, output current peak value, converter output voltage peak
Indication
Operation panel value, motor load factor, PID set point, PID measured value, PID deviation, inverter I/O terminal monitor, output
power, cumulative power, motor thermal load factor, inverter thermal load factor, and PTC thermistor resistance.
Parameter unit Fault definition is displayed when a fault occurs. Past 8 fault records (output voltage/current/frequency/cumulative
(FR-PU07) Fault record
energization time right before the fault occurs) are stored.
Interactive
Function (help) for operation guide ∗2
guidance
Overcurrent during acceleration, overcurrent during constant speed, overcurrent during deceleration, overvoltage
during acceleration, overvoltage during constant speed, overvoltage during deceleration, inverter protection thermal
Protective operation, motor protection thermal operation, heatsink overheat, input phase loss ∗3 ∗4, output side earth (ground)
function fault overcurrent at start∗3, output phase loss, external thermal relay operation ∗3, PTC thermistor operation∗3,
Protective/warning parameter error, PU disconnection, retry count excess ∗3, CPU fault, brake transistor alarm, inrush resistance
function overheat, analog input error, stall prevention operation, output current detection value exceeded ∗3, safety circuit fault
Fan alarm∗1, overcurrent stall prevention, overvoltage stall prevention, PU stop, parameter write error,
Warning
regenerative brake prealarm ∗3, electronic thermal relay function prealarm, maintenance output ∗3, undervoltage,
function
operation panel lock, password locked, inverter reset, safety stop
Surrounding air temperature -10°C to +50°C maximum (non-freezing) ∗5
Environment
7
Outline Dimension Drawings
zFR-D720-0.1K to 0.75K
zFR-D720S-0.1K to 0.75K
zFR-D710W-0.1K to 0.4K
Features
5
Specifications
Standard
1-φ5 hole
128
118
Dimension
Drawings
Outline
Rating
plate
Terminal Specification
Terminal Connection
Explanation
Diagram
5 4
D1
5
56
D
68
Operation panel
Parameter unit
Inverter Model D D1
FR-D720-0.1K, 0.2K
FR-D720S-0.1K, 0.2K 80.5 10
FR-D710W-0.1K
FR-D710W-0.2K 110.5 10
Parameter
FR-D720-0.4K 112.5 42
List
FR-D720-0.75K 132.5 62
FR-D720S-0.4K
142.5 42
FR-D710W-0.4K
Protective
FR-D720S-0.75K 162.5 62
Functions
(Unit: mm)
zFR-D720-1.5K to 3.7K
zFR-D740-0.4K to 3.7K
Options
zFR-D720S-1.5K
zFR-D710W-0.75K
5
Instructions
FAN *
2-φ5 hole
FR-D700 Series
Difference List
Specification
128
118
Rating
plate International
FA Center
Warranty
5 5
5
W1 D1
W D
∗ FR-D740-0.4K, 0.75K, FR-D710W-0.75K are not provided with the cooling fan.
Inverter Model W W1 D D1
FR-D720-1.5K, 2.2K
135.5 60
FR-D740-1.5K
FR-D740-0.4K, 0.75K 129.5 54
FR-D740-2.2K 108 96
155.5
FR-D720S-1.5K 60
FR-D740-3.7K 165.5
FR-D710W-0.75K 149.5 54
FR-D720-3.7K 170 158 142.5 66.5
(Unit: mm)
8
zFR-D720S-2.2K
6
FAN
2-φ5 hole
138
150
Rating
plate
5 5
6
128 60
140 145
(Unit: mm)
zFR-D720-5.5K, 7.5K
zFR-D740-5.5K, 7.5K
6
FAN
2-φ5 hole
138
150
Rating
plate
5 10
6
208 68
220 155
(Unit: mm)
9
zFR-D720-11K, 15K
zFR-D740-11K, 15K
Features
FAN
Specifications
2-φ6 hole
Standard
244
260
Dimension
Drawings
Outline
Terminal Specification
Terminal Connection
Explanation
Diagram
6 10.5
8
195 84.5
220 190
Operation panel
Parameter unit
Rating plate
Parameter
List
Protective
Functions
211
(Unit: mm)
Options
25.05
(14.2) (11.45)
83
2.5
40 40
*1
Instructions
*1
Air-bleeding
51
50
hole
4-R1
*1 *1
135
FR-D700 Series
Difference List
67
56.8
Specification
57.8
4-φ4 hole
26.5 26.5 (Effective depth of the
installation screw hole 5.0)
International
FA Center
Warranty
M3 screw *2
∗1 When installing the FR-PU07 on the enclosure, etc., remove
screws or fix the screws to the FR-PU07 with M3 nuts.
80.3 ∗2 Select the installation screw whose length will not exceed the
effective depth of the installation screw hole. (Unit: mm)
11
36
45
59
2-M3 screw
24
(15.5)
(Unit: mm)
10
Terminal Connection Diagram
Control circuit
Control input signals (No voltage input allowed) C Relay output
Forward STF
The function of these Terminal functions vary
rotation start B by Pr. 192 A,B,C terminal
terminals can be STR Relay output
changed to the reset Reverse function selection
(Fault output)
signal, etc. with the input rotation start A
RH
terminal assignment High
(Pr. 178 to Pr. 182). speed
Middle RM Open collector output
Multi-speed selection
SOURCE
Note
y To prevent a malfunction caused by noise, separate the signal cables more than 10cm from the power cables. Also
separate the main circuit wire of the input side and the output side.
y After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean. When drilling mounting holes
in an enclosure etc., take care not to allow chips and other foreign matter to enter the inverter.
y The output of the single-phase power input specification is three-phase 200V.
11
Terminal Specification Explanation
Terminal
Type Terminal Name Description
Symbol
R/L1, S/L2, Connect to the commercial power supply. Keep these terminals open when using the high power
AC power input factor converter (FR-HC) or power regeneration common converter (FR-CV).
Features
T/L3 ∗ ∗ When using single-phase power input, terminals are R/L1 and S/L2.
U, V, W Inverter output Connect a three-phase squirrel-cage motor.
Main circuit
Connect a brake resistor (FR-ABR, MRS type, MYS type) across terminals P/+ and PR.
P/+, PR Brake resistor connection
(The brake resistor can not be connected to the 0.1K and 0.2K.)
Connect the brake unit (FR-BU2), power regeneration common converter (FR-CV) or high power
P/+, N/- Brake unit connection
Specifications
factor converter (FR-HC).
Standard
Remove the jumper across terminals P/+-P1 and connect a DC reactor.
P/+, P1 ∗ DC reactor connection Single-phase 100V power input model is not compatible with DC reactor.
∗ Terminal P1 is not available for single-phase 100V power input model.
Earth (Ground) For earthing (grounding) the inverter chassis. Must be earthed (grounded).
Dimension
STF Forward rotation start Turn on the STF signal to start forward rotation and turn it off to stop. When the STF and STR signals
Drawings
Outline
are turned on simultaneously,
STR Reverse rotation start Turn on the STR signal to start reverse rotation and turn it off to stop. the stop command is given.
RH, RM, RL Multi-speed selection Multi-speed can be selected according to the combination of RH, RM and RL signals.
Contact input common
Common terminal for contact input terminal (sink logic) and terminal FM.
Contact input
Terminal Specification
Terminal Connection
When connecting the transistor output (open collector output), such as a programmable controller,
External transistor common
Explanation
SD
Diagram
when source logic is selected, connect the external power supply common for transistor output to this
(source)
terminal to prevent a malfunction caused by undesirable currents.
Common output terminal for 24VDC 0.1A power supply (PC terminal).
24VDC power supply common
Isolated from terminals 5 and SE.
Control circuit/input signal
When connecting the transistor output (open collector output), such as a programmable controller,
External transistor common
Operation panel
Parameter unit
when sink logic is selected, connect the external power supply common for transistor output to this
(sink) (initial setting)
PC terminal to prevent a malfunction caused by undesirable currents.
Contact input common (source) Common terminal for contact input terminal (source logic).
24VDC power supply Can be used as 24VDC 0.1A power supply.
5VDC
Frequency setting power Used as power supply when connecting potentiometer for frequency setting
10 supply (speed setting) from outside of the inverter.
permissible load
current 10mA
Parameter
Inputting 0 to 5VDC (or 0 to 10V) provides the maximum output
List
Input resistance 10kΩ ± 1kΩ
frequency at 5V (10V) and makes input and output proportional.
Frequency setting
Protective
Functions
proportional. This input signal is valid only when the AU signal is Input resistance 10kΩ ± 1kΩ
ON (terminal 2 input is invalid). To use terminal 4 (initial setting is Permissible maximum voltage
4 Frequency setting (current) current input), set "4" in any of Pr.178 to Pr.182 (input terminal 20VDC
function selection) to assign the function, and turn ON AU signal. Current input:
Use Pr. 267 to switch from among input 4 to 20mA (initial setting), 0 Input resistance 249Ω ± 5Ω
to 5VDC and 0 to 10VDC. Set the voltage/current input switch in Maximum permissible current 30mA.
the "V" position to select voltage input (0 to 5V/0 to 10V).
Options
5 Frequency setting common Common terminal for the frequency setting signals (terminals 2 or 4). Do not earth (ground).
Pulse Open collector Relay thermistor
PTC thermistor input When PTC thermistor protection is valid (Pr. 561 ≠ "9999"), terminal
2 2 is not available for frequency setting.
Heat detection resistance :
500Ω to 30kΩ (Set by Pr. 561)
Instructions
1 changeover contact output indicates that the inverter fault occurs.
A, B, C
Control circuit/output signal
Relay output (fault output) Fault: discontinuity across B-C (continuity across A-C), Normal: continuity across B-C (discontinuity
across A-C) Contact capacity 230VAC 0.3A (power factor = 0.4) 30VDC 0.3A
Switched low when the inverter output frequency is equal to or
Permissible load 24VDC
higher than the starting frequency (initial value 0.5Hz). Switched
(Maximum 27VDC) 0.1A
RUN Inverter running high during stop or DC injection brake operation.
FR-D700 Series
Difference List
(a voltage drop is 3.4V maximum
Specification
(Low is when the open collector output transistor is ON (conducts).
when the signal is on)
High is when the transistor is OFF (does not conduct).)
SE Open collector output common Common terminal of terminal RUN and FU.
Select one e.g. output frequency from monitor items. (Not output
Permissible load current 1mA
FM For meter during inverter reset.) The output signal is proportional to the
1440 pulses/s at 60Hz
magnitude of the corresponding monitoring item.
International
FA Center
Warranty
Communication
Note
y Set Pr. 267 and a voltage/current input switch correctly, then input an analog signal in accordance with the setting. Applying
a voltage with voltage/current input switch in "I" position (current input is selected) or a current with switch in "V" position
(voltage input is selected) could cause component damage of the inverter or analog circuit of output devices.
y The inverter will be damaged if power is applied to the inverter output terminals (U, V, W). Never perform such wiring.
y indicates that terminal functions can be selected using Pr. 178 to Pr. 182, Pr. 190, Pr. 192, Pr. 197 (I/O terminal function selection).
y Terminal names and terminal functions are those of the factory set.
12
Explanation of the Operation Panel
Running frequency
Output current
Output voltage
13
Basic operation of the operation panel
Features
Operation mode switchover
Specifications
Standard
Dimension
PU Jog operation mode
Drawings
Outline
Monitor/frequency setting
(Example)
Terminal Specification
Terminal Connection
Explanation
Diagram
PU operation mode
Value change and frequency flicker.
(output frequency monitor)
Frequency setting has been
written and completed!!
Operation panel
Parameter unit
STOP
Output current monitor Output voltage monitor
Parameter
List
Protective
Functions
Parameter setting
Display the
Parameter setting mode present setting
Options
(Example)
Instructions
Value change Parameter and a setting value
flicker alternately.
Parameter write is completed!!
FR-D700 Series
Difference List
Specification
Parameter clear All parameter Faults history clear
clear
International
FA Center
Warranty
Initial value
change list
Faults history
14
Explanations of Parameter unit
z Main functions
Function Description
Monitor 6 types of monitors appear by simply pressing .
For PU operation mode and External/PU combined operation mode (Pr.79 = "3"), frequency setting is available.
Frequency setting Settings is performed by the direct setting, which sets frequency directly by to , and the step setting, which
sets frequency continuously by .
Reading parameter and changing setting values are easily done. To change the setting value of an parameter, specify
Parameter Setting
the parameter number, or select a parameter from the functional parameter list.
FR-PU07 reads parameter settings of an inverter, and stores three different parameter settings.
Batch copy FR-PU07 can also copy the stored parameter setting to another inverter of the same series, or verify its stored
parameter setting against the parameter setting stored in an inverter.
Switching between External operation mode [EXT] and PU operation mode [PU] is easy.
Operation
Start/stop is enabled during PU operation mode and External/PU operation mode (Pr.79 = "3").
∗ Available function differs by the inverter. Please refer to the instruction manual of the inverter and the parameter unit.
15
Parameter List
For simple variable-speed operation of the inverter, the initial setting of the parameters may be used as they are. Set the
necessary parameters to meet the load and operational specifications. Parameter setting, change and check can be made
from the operation panel. For details of parameters, refer to the Instruction Manual.
Features
This catalog explains based on the Japanese specifications.
POINT
Only simple mode parameters are displayed by the initial setting of Pr. 160 Extended function display selection. Set Pr.
Specifications
Standard
160 Extended function display selection as required.
Dimension
Drawings
Outline
9999
Parameters classified as simple mode can be displayed.
(initial value)
Both the parameters classified as simple mode and the parameters
0
classified as extended mode can be displayed.
Terminal Specification
Terminal Connection
Explanation
Diagram
Parameter Initial
Name Unit Range Application
Number Value
Operation panel
Set when you want to increase a
Parameter unit
starting torque under V/F control,
or when the motor with a load will
6%/4%/3/ not rotate, resulting in an alarm
0 Torque boost 0.1% 0 to 30%
2%∗ [OL] and a trip [OC1].
Parameter
∗ Initial values differ according to the
List
inverter capacity. (0.75K or less/
1.5K to 3.7K/5.5K, 7.5K/11K, 15K)
Set when the maximum output
1 Maximum frequency 0.01Hz 120Hz 0 to 120Hz
Protective
Functions
frequency need to be limited.
Set when the minimum output
2 Minimum frequency 0.01Hz 0Hz 0 to 120Hz
frequency need to be limited.
Set when the rated motor
3 Base frequency 0.01Hz 60Hz 0 to 400Hz frequency is 50Hz.
Options
Check the motor rating plate.
Multi-speed setting
4 0.01Hz 60Hz 0 to 400Hz
(high speed)
Set when changing the preset
Multi-speed setting
Instructions
5 0.01Hz 30Hz 0 to 400Hz speed in the parameter with a
(middle speed)
terminal.
Multi-speed setting (low
6 0.01Hz 10Hz 0 to 400Hz
speed)
Acceleration/deceleration time can
FR-D700 Series
Difference List
Specification
7 Acceleration time 0.1s 5s/10s/15s∗ 0 to 3600s
be set.
∗ Initial values differ according to the
8 Deceleration time 0.1s 5s/10s/15s∗ 0 to 3600s inverter capacity. (3.7K or less/
5.5K, 7.5K/11K, 15K)
International
FA Center
Warranty
16
z Extended mode parameter
REMARKS
y indicates simple mode parameters.
y The shaded parameters in the table allow its setting to be changed during operation even if "0" (initial value) is set in Pr. 77
Parameter write selection.
Minimum
Func- Initial Customer
Parameter Name Setting Range Setting
tion Value Setting
Increments
0 Torque boost 0 to 30% 0.1% 6/4/3/2% ∗1
1 Maximum frequency 0 to 120Hz 0.01Hz 120Hz
2 Minimum frequency 0 to 120Hz 0.01Hz 0Hz
3 Base frequency 0 to 400Hz 0.01Hz 60Hz
Basic functions
Acceleration/deceleration reference
20 1 to 400Hz 0.01Hz 60Hz
frequency
prevention
17
Minimum
Func- Initial Customer
Parameter Name Setting Range Setting
tion Value Setting
Increments
Features
44 Second acceleration/deceleration time 0 to 3600s 0.1s 5/10/15s ∗2
Second functions
Specifications
Standard
Second stall prevention operation
48 0 to 200%, 9999 0.1% 9999
current
51 Second electronic thermal O/L relay 0 to 500A, 9999 0.01A 9999
0, 5, 8 to 12, 14, 20,
Dimension
52 DU/PU main display data selection 23 to 25, 52 to 55, 61, 1 0
Drawings
Outline
Monitor functions
Terminal Specification
Terminal Connection
Rated
Explanation
Diagram
56 Current monitoring reference 0 to 500A 0.01A inverter
current
Automatic
Operation panel
Parameter unit
58 Restart cushion time 0 to 60s 0.1s 1s
— 59 Remote function selection 0, 1, 2, 3 1 0
— 60 Energy saving control selection 0, 9 1 0
Parameter
— 65 Retry selection 0 to 5 1 0
List
Stall prevention operation reduction
— 66 0 to 400Hz 0.01Hz 60Hz
starting frequency
67 Number of retries at fault occurrence 0 to 10, 101 to 110 1 0
Retry
Protective
Functions
69 Retry count display erase 0 1 0
— 70 Special regenerative brake duty 0 to 30% 0.1% 0%
0, 1, 3, 13, 23, 40, 43,
— 71 Applied motor 1 0
50, 53
— 72 PWM frequency selection 0 to 15 1 1
Options
— 73 Analog input selection 0, 1, 10, 11 1 1
— 74 Input filter time constant 0 to 8 1 1
Reset selection/disconnected PU
— 75 0 to 3, 14 to 17 1 14
detection/PU stop selection
Instructions
— 77 Parameter write selection 0, 1, 2 1 0
— 78 Reverse rotation prevention selection 0, 1, 2 1 0
— 79 Operation mode selection 0, 1, 2, 3, 4, 6, 7 1 0
80 Motor capacity 0.1 to 15kW, 9999 0.01kW 9999
FR-D700 Series
Motor constants
Difference List
Specification
82 Motor excitation current 0 to 500A, 9999 0.01A 9999
83 Rated motor voltage 0 to 1000V 0.1V 200V/400V
∗4
84 Rated motor frequency 10 to 120Hz 0.01Hz 60Hz
90 Motor constant (R1) 0 to 50Ω , 9999 0.001Ω 9999
International
FA Center
Warranty
18
Minimum
Func- Initial Customer
Parameter Name Setting Range Setting
tion Value Setting
Increments
PID control automatic switchover
127 0 to 400Hz, 9999 0.01Hz 9999
frequency
128 PID action selection 0, 20, 21, 40 to 43 1 0
PID operation
— 168
Parameter for manufacturer setting. Do not set.
— 169
monitor clear
Cumulative
0 to 5, 7, 8, 10, 12,
Input terminal function
178 STF terminal function selection 14, 16, 18, 24, 25, 1 60
60, 62, 65 to 67, 9999
assignment
0 to 5, 7, 8, 10, 12,
179 STR terminal function selection 14, 16, 18, 24, 25, 1 61
61, 62, 65 to 67, 9999
180 RL terminal function selection 0 to 5, 7, 8, 10, 12, 1 0
181 RM terminal function selection 14, 16, 18, 24, 25, 1 1
182 RH terminal function selection 62, 65 to 67, 9999 1 2
19
Minimum
Func- Initial Customer
Parameter Name Setting Range Setting
tion Value Setting
Increments
Features
0, 1, 3, 4, 7, 8, 11 to 16,
25, 26, 46, 47, 64, 70,
80, 81, 90, 91, 93, 95,
96, 98, 99, 100, 101,
Specifications
190 RUN terminal function selection 103, 104, 107, 108, 1 0
Standard
111 to 116, 125, 126,
146, 147, 164, 170, 180,
181, 190, 191, 193, 195,
Output terminal function assignment
Dimension
0, 1, 3, 4, 7, 8, 11 to 16,
Drawings
Outline
25, 26, 46, 47, 64, 70,
80, 81, 90, 91, 95, 96,
98, 99, 100, 101, 103,
192 A,B,C terminal function selection 104, 107, 108, 1 99
Terminal Specification
Terminal Connection
111 to 116, 125, 126,
Explanation
Diagram
146, 147, 164, 170, 180,
181, 190, 191, 195, 196,
198, 199, 9999
0, 1, 3, 4, 7, 8, 11 to 16,
Operation panel
Parameter unit
25, 26, 46, 47, 64, 70,
80, 81, 90, 91, 93, 95,
96, 98, 99, 100, 101,
197 SO terminal function selection 103, 104, 107, 108, 1 80
111 to 116, 125, 126,
146, 147, 164, 170, 180,
Parameter
181, 190, 191, 193, 195,
List
196, 198, 199
232 Multi-speed setting (speed 8) 0 to 400Hz, 9999 0.01Hz 9999
Multi-speed setting
Protective
Functions
234 Multi-speed setting (speed 10) 0 to 400Hz, 9999 0.01Hz 9999
235 Multi-speed setting (speed 11) 0 to 400Hz, 9999 0.01Hz 9999
236 Multi-speed setting (speed 12) 0 to 400Hz, 9999 0.01Hz 9999
237 Multi-speed setting (speed 13) 0 to 400Hz, 9999 0.01Hz 9999
238 Multi-speed setting (speed 14) 0 to 400Hz, 9999 0.01Hz 9999
Options
239 Multi-speed setting (speed 15) 0 to 400Hz, 9999 0.01Hz 9999
— 240 Soft-PWM operation selection 0, 1 1 1
— 241 Analog input display unit switchover 0, 1 1 0
— 244 Cooling fan operation selection 0, 1 1 1
Instructions
245 Rated slip 0 to 50%, 9999 0.01% 9999
compensation
Slip
FR-D700 Series
Difference List
247 0, 9999 1 9999
Specification
compensation selection
— 249 Earth (ground) fault detection at start 0, 1 1 0
0 to 100s,
— 250 Stop selection 1000 to 1100s, 0.1s 9999
8888, 9999
International
FA Center
Warranty
20
Minimum
Func- Initial Customer
Parameter Name Setting Range Setting
tion Value Setting
Increments
Password
1000 to 9998 (0 to 5,
297 Password lock/unlock 1 9999
9999)
— 298 Frequency search gain 0 to 32767, 9999 1 9999
Rotation direction detection selection
— 299 0, 1, 9999 1 0
at restarting
Communication operation command
RS-485 communication
338 0, 1 1 0
source
Communication speed command
339 0, 1, 2 1 0
source
340 Communication startup mode selection 0, 1, 10 1 0
Communication EEPROM write
342 0, 1 1 0
selection
343 Communication error count — 1 0
Second motor
constant
504 Maintenance timer alarm output set time 0 to 9998, 9999 1 9999
21
Minimum
Func- Initial Customer
Parameter Name Setting Range Setting
tion Value Setting
Increments
Features
Regeneration avoidance operation
avoidance function
882 0, 1, 2 1 0
selection
Regeneration
Specifications
Standard
Regeneration avoidance compensation
885 0 to 10Hz, 9999 0.01Hz 6Hz
frequency limit value
886 Regeneration avoidance voltage gain 0 to 200% 0.1% 100%
parameter
Dimension
Drawings
Free
Outline
889 Free parameter 2 0 to 9999 1 9999
Terminal Specification
C0
Terminal Connection
FM terminal calibration — — —
Explanation
Diagram
(900) ∗6
C2 Terminal 2 frequency setting bias
0 to 400Hz 0.01Hz 0Hz
(902) ∗6 frequency
C3
Operation panel
Parameter unit
Terminal 2 frequency setting bias 0 to 300% 0.1% 0%
(902) ∗6
125 Terminal 2 frequency setting gain
0 to 400Hz 0.01Hz 60Hz
(903) ∗6 frequency
C4
Terminal 2 frequency setting gain 0 to 300% 0.1% 100%
Parameter
(903) ∗6
Calibration parameters
List
C5 Terminal 4 frequency setting bias
0 to 400Hz 0.01Hz 0Hz
(904) ∗6 frequency
C6
Terminal 4 frequency setting bias 0 to 300% 0.1% 20%
(904) ∗6
Protective
Functions
126 Terminal 4 frequency setting gain
0 to 400Hz 0.01Hz 60Hz
(905) ∗6 frequency
C7
Terminal 4 frequency setting gain 0 to 300% 0.1% 100%
(905) ∗6
Options
C22 Frequency setting voltage bias
0 to 400Hz 0.01Hz 0
(922) ∗5∗6 frequency (built-in potentiometer)
C23 Frequency setting voltage bias (built-in
0 to 300% 0.1% 0
(922) ∗5∗6 potentiometer)
Instructions
C24 Frequency setting voltage gain
0 to 400Hz 0.01Hz 60Hz
(923) ∗5∗6 frequency (built-in potentiometer)
C25 Frequency setting voltage gain (built-in
0 to 300% 0.1% 100%
(923) ∗5∗6 potentiometer)
FR-D700 Series
Difference List
Specification
990 PU buzzer control 0, 1 1 1
PU
International
FA Center
ALLC All parameter clear 0, 1 1 0
Warranty
22
Protective Functions
When a fault occurs, the inverter trips and the PU display automatically changes to any of the following fault or alarm indications.
Function Name Description Display
Operation panel lock Appears when operation was tried during operation panel lock.
Error message
to
Parameter write error Appears when an error occurred during parameter writing.
Electronic thermal relay function prealarm Appears when the electronic thermal O/L relay has reached 85% of the specified value.
∗3
PU stop Appears when on the operation panel was pressed during external operation.
Maintenance signal output ∗7 Appears when the cumulative energization time has exceeded the maintenance output timer set value.
Undervoltage Appears when the main circuit power became low voltage.
Safety stop Appears when safety stop function is activated (during output shutoff).
Alarms
Appears when the cooling fan remains stopped when operation is required or when the speed has
Fan alarm
∗4
decreased.
Overcurrent trip during acceleration Appears when an overcurrent occurred during acceleration.
Overcurrent trip during constant speed Appears when an overcurrent occurred during constant speed operation.
Overcurrent trip during deceleration
Appears when an overcurrent occurred during deceleration and at a stop.
or stop
Regenerative overvoltage trip during
Appears when an overvoltage occurred during acceleration.
acceleration
Regenerative overvoltage trip during
Appears when an overvoltage occurred during constant speed operation.
constant speed
Regenerative overvoltage trip during
Appears when an overvoltage occurred during deceleration and at a stop.
deceleration or stop
Inverter overload trip
Appears when the electronic thermal relay function for inverter element protection was activated.
(electronic thermal relay function)
Motor overload trip
Appears when the electronic thermal relay function for motor protection was activated.
(electronic thermal relay function) ∗1
Fin overheat Appears when the heatsink overheated.
Appears if one of the three phases on the inverter input side opened. It may function if phase-to-
Input phase loss ∗7 ∗8∗9
phase voltage of the three-phase power input becomes largely unbalanced.
Stall prevention stop Appears when the output frequency drops to 1Hz as a result of deceleration due to the excess motor load.
This function stops the inverter output if an alarm occurs in the brake circuit, e.g. damaged brake
Brake transistor alarm detection
transistors. In this case, the inverter must be powered off immediately.
Output side earth (ground) fault
Fault
Appears when an earth (ground) fault occurred on the inverter's output side. (detects only at a start)
∗5
overcurrent at start ∗7
If one of the three phases (U, V, W) on the inverter's output side (load side) is lost during inverter
Output phase loss operation (except during DC injection brake operation and when output frequency is under 1Hz),
inverter stops the output.
External thermal relay operation∗6 ∗7 Appears when the external thermal relay connected to the OH signal was activated.
Appears when resistance of PTC thermistor connected between terminal 2 and terminal 10 is more
PTC thermistor operation ∗7
than the value set in Pr. 561 PTC thermistor protection level.
Parameter storage device fault Appears when operation of the element where parameters stored became abnormal. (control board)
Appears when a communication error between the PU and inverter occurred, the communication
PU disconnection interval exceeded the permissible time during the RS-485 communication with the PU connector, or
communication errors exceeded the number of retries during the RS-485 communication.
Retry count excess ∗7 Appears when the operation was not restarted within the set number of retries.
CPU fault Appears during the CPU and peripheral circuit errors occurred.
/
∗1 Resetting the inverter initializes the internal cumulative heat value of the electronic thermal relay function.
∗2 The error message shows an operational error. The inverter output is not shut off.
∗3 Warnings are messages given before fault occur. The inverter output is not shut off.
∗4 Alarms warn the operator of failures with output signals. The inverter output is not shut off.
∗5 When faults occur, the protective functions are activated to inverter trip and output the fault signals.
∗6 The external thermal operates only when the OH signal is set in Pr. 178 to Pr. 182 (input terminal function selection).
∗7 This protective function does not function in the initial status.
∗8 Protective function activates when Pr.872 Input phase loss protection selection = "1".
∗9 This protective function is available with the three-phase power input specification model only.
23
Option and Peripheral Devices
Option list
By fitting the following options to the inverter, the inverter is provided with more functions.
Features
Applicable
Name Model Applications, Specifications, etc.
Inverter
FR-PU07 Shared among
Parameter unit (8 languages) Interactive parameter unit with LCD display
FR-PU04 all models
Specifications
This operation panel enables inverter operation and monitoring of frequency,
Enclosure surface operation panel FR-PA07
Standard
etc. from the enclosure surface Shared among
Cable for connection of operation panel or parameter unit all models
Parameter unit connection cable FR-CB20
indicates a cable length. (1m, 3m, 5m)
Compatible with
DIN rail attachment FR-UDA01 to 03 Attachment for installation on DIN rail
the 3.7K or less
Dimension
Drawings
AC reactor FR-HAL According to
Outline
For harmonic current reduction and inverter input power factor improvement
DC reactor FR-HEL capacities
SF
According to
EMC Directive compliant noise filter FR-E5NF EMC Directive (EN61800-3 C3) compliant noise filter
capacities
FR-S5NFSA
Terminal Specification
Terminal Connection
FR-A5AT03
Explanation
EMC compliant EMC filter According to
Diagram
FR-AAT02 For installation of the inverter to the EMC Directive compliant EMC filter (SF).
installation attachment capacities
FR-E5T
Radio noise filter FR-BIF(H) For radio noise reduction (connect to the input side)
Shared among
Stand-alone shared
FR- BSF01
Line noise filter For line noise reduction all models
Operation panel
Parameter unit
FR- BLF
Three-phase
power input
Combination of power factor improving DC reactor, zero phase reactor, and model:
Filterpack FR-BFP2
capacitative filter compatible with
0.4K or bigger
capacity
Parameter
MRS type, 200V: For the
List
Brake resistor For increasing the regenerative braking capability (permissible duty 3%/6%ED)
MYS type 0.4K or more
High-duty brake resistor FR-ABR For increasing the regenerative braking capability (permissible duty 10%/6%ED)
For increasing the braking capability of the inverter (for high-inertia load or For the 0.4K or
Brake unit FR-BU2
negative load)
Protective
Functions
Resistor unit FR-BR more
Brake unit, electrical-discharge resistor and resistor unit are used in
Discharging resistor GZG, GRZG type
combination
Power regeneration common
converter FR-CV Unit which can return motor-generated braking energy back to the power
Stand-alone reactor dedicated for FR-CVL supply in common converter system
According to
the FR-CV
Options
capacities
The high power factor converter switches the converter section on/off to
High power factor converter FR-HC reshape an input current waveform into a sine wave, greatly suppressing
harmonics. (Used in combination with the standard accessory.)
400V: According
FR-ASF
Instructions
to capacities
Surge voltage suppression filter Filter for suppressing surge voltage on motor
400V: For the
FR-BMF
5.5K or more
For independent operation. With frequency meter, frequency potentiometer and
Manual controller FR-AX
start switch.
FR-D700 Series
FR series manual controller/
DC tach. follower FR-AL For synchronous operation (1VA) by external signal (0 to 5V, 0 to 10V DC)∗
Difference List
Specification
For three speed switching, among high, middle and low speed operation
Three speed selector FR-AT
(1.5VA)∗
speed controller
Motorized speed setter FR-FK For remote operation. Allows operation to be controlled from several places (5VA)∗
Ratio setter FR-FH For ratio operation. The ratios of five inverters can be set (3VA)∗
Speed detector FR-FP For tracking operation by a pilot generator (PG) signal (3VA)∗
International
FA Center
Warranty
Master controller FR-FG Master controller (5VA) for parallel operation of multiple (maximum 35) inverters.∗
For soft start and stop. Enables acceleration/deceleration in parallel operation
Soft starter FR-FC Shared among
(3VA)∗
all models
For continuous speed control operation. Used in combination with a deviation
Deviation detector FR-FD
sensor or synchro (5VA)∗
Preamplifier FR-FA Used as an A/V converter or arithmetic amplifier (3VA)∗
Pilot generator QVAH-10 For tracking operation. 70V/35VAC 500Hz (at 2500r/min)
For continuous speed control operation (mechanical deviation detection)
Deviation sensor YVGC-500W-NS
Output 90VAC/90ºC
Frequency setting potentiometer WA2W 1kΩ For frequency setting. Wire-wound 2W 1kΩ type B characteristic
Others
Analog frequency meter Dedicated frequency meter (graduated to 120Hz). Moving-coil type DC
YM206NRI 1mA
(64mm × 60mm) ammeter
Calibration resistor RV24YN 10kΩ For frequency meter calibration. Carbon film type B characteristic
FR Configurator SW3(VFD setup FR-SW3-SETUP- Shared among
Supports an inverter startup to maintenance.
software) WE all models
∗ Rated power consumption. The power supply specifications of the FR series manual controllers and speed controllers are 200VAC 50Hz, 220V/220VAC 60Hz,
and 115VAC 60Hz.
24
Peripheral devices/cable size list
FR-D740-1.5K 1.5 30AF 10A 30AF 10A S-N10 S-N10 2 2 H1.5K H1.5K
FR-D740-2.2K 2.2 30AF 15A 30AF 10A S-N10 S-N10 2 2 H2.2K H2.2K
FR-D740-3.7K 3.7 30AF 20A 30AF 15A S-N10 S-N10 2 2 H3.7K H3.7K
FR-D740-5.5K 5.5 30AF 30A 30AF 20A S-N20, S-N21 S-N11, S-N12 3.5 2 H5.5K H5.5K
FR-D740-7.5K 7.5 30AF 30A 30AF 30A S-N20, S-N21 S-N20, S-N21 3.5 3.5 H7.5K H7.5K
FR-D740-11K 11 50AF 50A 50AF 40A S-N20, S-N21 S-N20, S-N21 5.5 5.5 H11K H11K
FR-D740-15K 15 100AF 60A 50AF 50A S-N25 S-N20, S-N21 8 8 H15K H15K
FR-D720S-0.1K 0.1 30AF 5A 30AF 5A S-N10 S-N10 2 2 0.4K ∗7 0.4K ∗7
Single-Phase 100V Single-phase 200V
FR-D710W-0.2K 0.2 30AF 10A 30AF 10A S-N10 S-N10 2 2 1.5K ∗6, ∗7 — ∗8
FR-D710W-0.4K 0.4 30AF 15A 30AF 15A S-N10 S-N10 2 2 2.2K ∗6, ∗7 — ∗8
FR-D710W-0.75K 0.75 30AF 30A 30AF 20A S-N10 S-N10 3.5 2 3.7K ∗6, ∗7 — ∗8
Note
y When the inverter capacity is larger than the motor capacity, select an MCCB and a magnetic contactor according to
the inverter model and cable and reactor according to the motor output.
y When the breaker on the inverter primary side trips, check for the wiring fault (short circuit), damage to internal parts
of the inverter, etc. Identify the cause of the trip, then remove the cause and power on the breaker.
25
Selecting the rated sensitivity current for the earth leakage current breaker
When using the earth leakage current breaker with the Example
Features
inverter circuit, select its rated sensitivity current as follows,
5.5mm2 × 5m 5.5mm2 × 60m
independently of the PWM carrier frequency.
ELB Noise
y Breaker designed for harmonic and surge suppression filter
3φ
Rated sensitivity current IΔn≥10×(Ig1+Ign+Igi+Ig2+Igm) Inverter IM 400V
Specifications
Standard
y Standard breaker 2.2kW
Rated sensitivity current IΔn≥10×{Ig1+Ign+Igi+3X(Ig2+Igm)} Ig1 Ign Ig2 Igm
Ig1, Ig2: Leakage currents in wire path during commercial power supply
operation Igi
Ign : Leakage current of inverter input side noise filter
(Note) 1 Install the earth leakage breaker (ELB) on the input side of the inverter.
Igm : Leakage current of motor during commercial power supply operation
Dimension
Drawings
Outline
Igi : Leakage current of inverter unit 2 In the connection earthed-neutral system, the sensitivity current is blunt
against an earth (ground) fault in the inverter output side. Earthing (Grounding)
Example of leakage current of Example of leakage current must conform to the requirements of national and local safety regulations and
cable path per 1km during the of three-phase induction motor electrical codes. (NEC section 250, IEC 536 class 1 and other applicable
commercial power supply operation during the commercial standards)
when the CV cable is routed in power supply operation
Terminal Specification
Terminal Connection
metal conduit (200V 60Hz)
Explanation
Diagram
(200V 60Hz) zSelection example
Leakage currents (mA)
Leakage currents (mA)
120 1.0
0.7
0.5
(in the case of the above figure (400V class connection))
100
0.3
80 0.2
Breaker Designed for
Operation panel
Parameter unit
60 0.1 Harmonic and Surge Standard Breaker
0.07
40 0.05 Suppression
0.03
20 0.02 1 5m
Leakage current
0 × 66 × = 0.11
Ig1 (mA) 3
2 3.5 8 142238 80150 0.1 0.2 0.75 2.2 5.5 11 20 1000m
5.5 30 60 100 0.4 1.5 3.7 7.5 15
Leakage current
Parameter
Cable size (mm2) Motor capacity (kW) 0 (without noise filter)
Ign (mA)
List
Example of leakage current per 1km during Example of leakage current of three- Leakage current Igi
1
the commercial power supply operation phase induction motor during the (mA)
when the CV cable is routed in metal conduit commercial power supply operation
(Three-phase three-wire delta (Totally-enclosed fan-cooled 1 60m
Leakage current
connection 400V60Hz) type motor 400V60Hz) × 66 × = 1.32
Ig2 (mA) 3
Protective
Functions
1000m
2. 0 Motor leakage
leakage currents (mA)
120 0.36
current Igm (mA)
100 1. 0
Total leakage
80 0. 7 2.79 6.15
0. 5 current (mA)
60
0. 3
Rated sensitivity
Options
40 current (mA) (≥ Ig × 30 100
0. 2
20 10)
0 0. 1
2 3.5 8 142238 80150 1.5 3.7 7.5 15
5.5 30 60100 2.2 5.5 11 20
Cable size (mm2) Motor capacity (kW)
Instructions
For " " connection, the amount of leakage current is appox.1/3 of the above value.
FR-D700 Series
Difference List
Specification
International
FA Center
Warranty
26
Precautions for Operation/Selection
Wiring
z Application of power to the output terminals (U, V, W) of the
inverter will damage the inverter. Therefore, fully check the
wiring and sequence to ensure that wiring is correct, etc. before
powering on.
z The terminals P/+, PR, P1, N/- are provided for connection of a
dedicated option. Connect only a dedicated option. Do not short
the frequency setting power supply terminal 10 and common
terminal 5 or the terminal PC and terminal SD.
Power supply
z When the inverter is connected
under a large-capacity power
1500
transformer (500kVA or more Power
Range
requiring
supply
transformer) or when a power system 1000
capacity
installation
of the reactor
27
Precautions for selection Power transfer mechanism
(reduction gear, belt, chain, etc.)
Inverter capacity selection
Features
z When an oil-lubricated gear box, speed change/reduction gear
z When operating a special motor or more than one motor in or similar device is used in the power transfer system, note that
parallel with a single inverter, select the inverter capacity so that continuous operation at low speed only may deteriorate oil
1.1 times the total rated motor current is less than the rated lubrication, causing seizure. When performing fast operation at
Specifications
Standard
output current of the inverter. higher than 60Hz, fully note that such operation will cause
strength shortage due to the noise, life or centrifugal force of the
Starting torque of the motor power transfer mechanism.
z The start and acceleration characteristics of the motor driven by
Instructions for overload operation
Dimension
Drawings
the inverter are restricted by the overload current rating of that
Outline
inverter. Generally the torque characteristic is less than when z When performing operation of frequent start/stop of the inverter,
the motor is started by a commercial power supply. If torque rise/fall in the temperature of the transistor element of the
boost adjustment or General-purpose magnetic flux vector inverter will repeat due to a repeated flow of large current,
Terminal Specification
Terminal Connection
control cannot provide enough torque when a large starting shortening the life from thermal fatigue. Since thermal fatigue is
Explanation
Diagram
torque is necessary, select the inverter of one rank higher related to the amount of current, the life can be increased by
capacity or increase the capacities of both the motor and reducing current at locked condition, starting current, etc.
inverter. Decreasing current may increase the life. However, decreasing
Operation panel
Parameter unit
current will result in insufficient torque and the inverter may not
Acceleration/deceleration times start. Therefore, choose the inverter which has enough
z The acceleration/deceleration time of the motor depends on the allowance for current.
motor-generated torque, load torque and moment of inertia of
the load (J).
Parameter
List
z When the stall prevention function is activated during
acceleration/deceleration, increase the acceleration/
deceleration time as the actual time may become longer.
z To decrease the acceleration/deceleration time, increase the
Protective
Functions
torque boost value (setting of a too large value may activate the
stall prevention function at a start, longer the acceleration time),
use the General-purpose magnetic flux vector control or
increase the inverter and motor capacities. To decrease the
Options
deceleration time, it is necessary to add optional brake resistor
MRS type, MYS type, FR-ABR (for the 0.4K or more), the brake
unit (FR-BU2), power regeneration common converter (FR-CV),
or a similar device to absorb braking energy.
Instructions
FR-D700 Series
Difference List
Specification
International
FA Center
Warranty
28
Precautions for Peripheral Device Selection
Handling of the inverter input side Wire thickness and wiring distance
magnetic contactor When the wiring length between the inverter and motor is long,
z For operation via external terminal (terminal STF or STR used), use thick wires so that the voltage drop of the main circuit cable is
provide an input side MC to prevent an accident caused by a 2% or less especially at low frequency output. (A selection
natural restart at power recovery after a power failure, such as example for the wiring distance of 20m is shown on page 25)
an instantaneous power failure, and to ensure safety for Especially at a long wiring distance, the maximum wiring length
maintenance work. Do not use this magnetic contactor to make should be within the length in the table below since the overcurrent
frequent starts and stops. (The switching life of the inverter input protection function may be misactivated by the influence of a
circuit is about 1,000,000 times.) For parameter unit operation, charging current due to the stray capacitances of the wiring.
an automatic restart after power failure is not made and the MC (The overall wiring length for connection of multiple motors should
cannot be used to make a start. Note that the primary side MC be within the value in the table below.)
may be used to make a stop but the regenerative brake specific Pr. 72 Setting 3.7K or
0.1K 0.2K 0.4K 0.75K 1.5K 2.2K
to the inverter does not operate and the motor is coasted to a (carrier frequency) more
stop. 100V
200m 200m 300m 500m 500m 500m 500m
1 or less 200V
z Installation of a magnetic contactor at the input side is
400V — — 200m 200m 300m 500m 500m
recommended. A magnetic contactor avoids overheat or
100V
burnout of a brake resistor when heat capacity of the resistor is 30m 100m 200m 300m 500m 500m 500m
2 to 15 200V
insufficient or a brake regenerative transistor is damaged with 400V — — 30m 100m 200m 300m 500m
short while connecting an optional brake resistor. In this case, When using the automatic restart after instantaneous power failure
shut-off the magnetic contactor when fault occurs and inverter function with wiring length exceeding below, select "without
trips. frequency search" (Pr.162 = "1, 11").
Motor Capacity 0.1K 0.2K 0.4K or more
Handling of the inverter output side Wiring Length 20m 50m 100m
magnetic contactor
Use the recommended connection cable when connecting the
Switch the magnetic contactor between the inverter and motor parameter unit.
only when both the inverter and motor are at a stop. When the For remote operation via analog signal, wire the control cable
magnetic contactor is turned on while the inverter is operating, between the operation box or operation signal and inverter within
overcurrent protection of the inverter and such will activate. When 30m and away from the power circuits (main circuit and relay
an MC is provided for switching to the commercial power supply, sequence circuit) to prevent induction from other devices.
for example, switch it on/off after the inverter and motor have When using the external potentiometer instead of the parameter
stopped. unit to set the frequency, use a shielded or twisted cable, and do
not earth (ground) the shield, but connect it to terminal 5 as shown
Thermal relay installation below.
The inverter has an electronic thermal relay function to protect the Shielded cable
(3) 10 (3)
motor from overheating. However, when running multiple motors (2) (2)
10
2 2
with one inverter or operating a multi-pole motor, provide a thermal (1) (1)
5
relay (OCR) between the inverter and motor. In this case, set the Frequency setting Twisted 5 Frequency setting
potentiometer cable potentiometer
electronic thermal relay function of the inverter to 0A. And for the
setting of the thermal relay, add the line-to line leakage current
(refer to page 30) to the current value on the motor rating plate.
For low-speed operation where the cooling capability of the motor
reduces, it is recommended to use a thermal relay protector
incorporated motor.
29
Earth (Ground) Leakage currents
When the inverter is run in the low acoustic noise mode, more Capacitances exist between the inverter I/O cables, other cables
Features
leakage currents occur than in the non-low acoustic noise mode and earth and in the motor, through which a leakage current flows.
due to high-speed switching operation. Be sure to earth (ground) Since its value depends on the static capacitances, carrier
the inverter and motor before use. In addition, always use the frequency, etc., low acoustic noise operation at the increased
earth (ground) terminal of the inverter to earth (ground) the carrier frequency of the inverter will increase the leakage current.
Specifications
Standard
inverter. (Do not use the case and chassis) Therefore, take the following measures. Select the earth leakage
current breaker according to its rated sensitivity current,
Noise independently of the carrier frequency setting. (Refer to page 26)
When performing low-noise operation at higher carrier frequency, To-earth (ground) leakage currents
Dimension
electromagnetic noise tends to increase. Therefore, refer to the
Drawings
Outline
Type Influence and Measures
following measure example and consider taking the measures.
y Leakage currents may flow not only into the inverter's
Depending on the installation condition, the inverter may be own line but also into the other line through the earth
affected by noise in a non-low noise (initial) status. (ground) cable, etc. These leakage currents may
Terminal Specification
Terminal Connection
z The noise level can be reduced by decreasing the carrier operate earth (ground) leakage circuit breakers and
Explanation
Diagram
frequency (Pr. 72). earth leakage relays unnecessarily.
z As measures against AM radio broadcasting noise, radio noise z Countermeasures
Influence and y If the carrier frequency setting is high, decrease the Pr.
filter FR-BIF produces an effect.
measures 72 PWM frequency selection setting.
Operation panel
Parameter unit
z As measures against sensor malfunction, line noise filter FR-
Note that motor noise increases. Select Pr. 240 Soft-
BSF01, FR-BLF produces an effect. PWM operation selection to make the sound inoffensive.
z As measures against induction noise from the power cable of y By using earth leakage circuit breakers designed for
the inverter, an effect is produced by putting a distance of 30cm harmonic and surge suppression in the inverter's own
(at least 10cm) or more and using a twisted pair shielded cable line and other line, operation can be performed with the
Parameter
carrier frequency kept high (with low noise).
List
as a signal cable. Do not earth (ground) shield but connect it to
signal common cable. Inverter
NV1
Noise reduction examples Power Motor
supply C
Install common mode filter
FR- BLF
Install common mode filter
FR- BLF Undesirable Leakage
Protective
Decrease
Functions
FR- BSF01 FR- BSF01 breaker C
on inverter input side. Enclosure carrier frequency
on inverter output side. current path
NV2 Motor
Inverter
power FR- FR-
supply BSF01 Inverter BSF01 IM Motor C
Leakage
Install capacitor type FR-BIF filter breaker
FR- Use 4-core cable for motor
on inverter input side. power cable and use one
BIF
Options
Use a twisted pair shielded cable
least 10cm) from sensor circuit.
Sensor
Control
power
Power
supply Type Influence and Measures
supply for sensor
Do not earth (ground)
enclosure directly.
Do not earth (ground) shield but • This leakage current flows via a static capacitance
connect it to signal common cable.
Do not earth (ground) control cable. between the inverter output cables.
• The external thermal relay may be operated
Instructions
unnecessarily by the harmonics of the leakage current.
When the wiring length is long (50m or more) for the
400V class model, the external thermal relay is likely to
operate unnecessarily because the ratio of the leakage
FR-D700 Series
Difference List
current to the rated motor current increases.
Specification
Influence and z Countermeasures
measures • Use Pr.9 Electronic thermal O/L relay.
• If the carrier frequency setting is high, decrease the Pr.
72 PWM frequency selection setting.
International
FA Center
Warranty
30
zHarmonic suppression guideline For compliance to "Harmonic suppression guideline of the
transistorized inverter (input current of 20A or less) for consumers
Harmonic currents flow from the inverter to a power receiving point other than specific consumers" published by JEMA.
via a power transformer. The harmonic suppression guideline was
established to protect other consumers from these outgoing Input
Target
harmonic currents. Power Countermeasures
Capacity
The three-phase 200V input specifications 3.7kW or less, single- Supply
phase 200V input specifications 2.2kW or less, single-phase 100V Single- Connect the AC reactor or DC reactor
phase 0.75kW or less recommended in a catalog or an
input specifications 0.75kW or less are previously covered by
100V instruction manual.
"Harmonic suppression guideline for household appliances and
Single- Reference materials
general-purpose products" and other models are covered by
phase 2.2kW or less y "Harmonic suppression guideline of the
"Harmonic suppression guideline for consumers who receive high
200V general-purpose inverter (input current of
voltage or special high voltage". However, the transistorized 20A or less)"
Three-
inverter has been excluded from the target products covered by phase 3.7kW or less JEM-TR226 (revised in Dec. 2003): Japan
"Harmonic suppression guideline for household appliances and 200V Electrical Manufacturer's Association
general-purpose products" in January 2004 and "Harmonic
suppression guideline for household appliances and general- zCalculation of outgoing harmonic current
purpose products" was repealed on September 6, 2004.
Outgoing harmonic current = fundamental wave current (value converted
All capacity and all models of general-purpose inverter used by
from received power voltage) × operation ratio × harmonic content
specific consumers are covered by "Harmonic suppression
yOperation ratio: Operation ratio = actual load factor operation
guideline for consumers who receive high voltage or special high time ratio during 30 minutes
voltage". yHarmonic content: Found in Table.
y "Harmonic suppression guideline for consumers who receive high
voltage or special high voltage" Table 1: Harmonic Contents (Values at the fundamental current of 100%)
This guideline sets forth the maximum values of harmonic currents
Reactor 5th 7th 11th 13th 17th 19th 23rd 25th
outgoing from a high-voltage or especially high-voltage consumer Not used 65 41 8.5 7.7 4.3 3.1 2.6 1.8
who will install, add or renew harmonic generating equipment. If any Three-phase Used
38 14.5 7.4 3.4 3.2 1.9 1.7 1.3
(AC side)
of the maximum values is exceeded, this guideline requires that bridge
Used
consumer to take certain suppression measures. (Capacitor 30 13 8.4 5.0 4.7 3.2 3.0 2.2
(DC side)
smoothing) Used
Users who use models other than the target models are not covered 28 9.1 7.2 4.1 3.2 2.4 1.6 1.4
(AC, DC sides)
by the guideline. However, we ask to connect an AC reactor or a DC Single-phase Not used 50 24 5.1 4.0 1.5 1.4 ⎯ ⎯
reactor as before to the users who are not covered by the guideline. bridge
Used
For compliance to the harmonic suppression guideline for (Capacitor
(AC side)*
6.0 3.9 1.6 1.2 0.6 0.1 ⎯ ⎯
6.6kV (mA)
Current [A]
Single-phase supply harmonics, refer to materials below. (No reactor, 100% operation ratio)
Motor kW
Applied
31
FR-D700 Series Specification Difference List
Features
FR-D720S-0.1K to 2.2K FR-D720S-008 to 100-NA FR-D720S-008 to 100-EC FR-D720S-0.1K to 2.2K-CHT
Type FR-D710W-0.1K to 0.75K FR-D710W-008 to 042-NA Type : Rated current value Type : Rated capacity (kW)
Type : Rated capacity (kW) Type : Rated current value
Main Circuit Terminal
Specifications
Name
Standard
R, S, T L1, L2, L3
AC Power Input
Three-phase Input
Single-phase Input R, S L1, N
Brake Unit
Dimension
Drawings
P, N +, -
Outline
Connection
Control Terminal Logic
Sink logic Sink logic Source logic Sink logic
Initial Setting
Control Terminal
Terminal Specification
Terminal Connection
Explanation
Diagram
Contact Input Common
SD SD PC SD
Terminal
Initial Setting
Monitor Output
Operation panel
Parameter unit
FM (Digital output) AM (Analog output) AM (Analog output) AM (Analog output)
Terminal For Indicator
Parameter
Pr.3, Pr.4, Pr.20,
Pr.55, Pr.66, Pr.84,
Parameter
60Hz 60Hz 50Hz 50Hz
Pr.125, Pr.126, Pr.903,
List
Pr.905, Pr.923
Initial Value
Pr.19 Initial Value 9999 9999 8888 9999
Protective
Functions
Pr.122 Initial Value 0 9999 9999 0
Pr.145 Initial Value 0 1 1 1
Pr.160 Initial Value 9999 0 0 9999
Pr.249 Initial Value 0 0 1 1
Pr.54 FM terminal function Pr.158 AM terminal function Pr.158 AM terminal function Pr.158 AM terminal function
Options
Indicator Output selection, selection, selection, selection,
Terminal Function Pr.900 FM terminal Pr.901 AM terminal Pr.901 AM terminal Pr.901 AM terminal
calibration calibration calibration calibration
Traverse Function
Instructions
Without Without With With
Pr.592 to Pr.597
FR-D700 Series
Difference List
Specification
International
FA Center
Warranty
32
Warranty
[Coverage]
(1) Diagnosis of failure
As a general rule, diagnosis of failure is done on site by the customer.
However, Mitsubishi or Mitsubishi service network can perform this service for an agreed upon fee upon the customer's
request.
There will be no charges if the cause of the breakdown is found to be the fault of Mitsubishi.
(2) Breakdown repairs
There will be a charge for breakdown repairs, exchange replacements and on site visits for the following four conditions
even in gratis warranty period, otherwise there will be no charge.
1)Breakdowns due to improper storage, handling, careless accident, software or hardware design by the customer.
2)Breakdowns due to modifications of the product without the consent of the manufacturer.
3)Breakdowns resulting from using the product outside the specified specifications of the product.
4)Breakdowns that are outside the terms of warranty.
Since the above services are limited to Japan, diagnosis of failures, etc. are not performed abroad.
If you desire the after service abroad, please register with Mitsubishi. For details, consult us in advance.
4. Terms of delivery
In regard to the standard product, Mitsubishi shall deliver the standard product without application settings or adjustments
to the customer and Mitsubishi is not liable for on site adjustment or test run of the product.
33
[ Related
[ Related
Factory
Factory
Automation
Automation
Products
Products
] ]
Introducing
Introducing
the high-speed
the high-speed
QCPU QCPU
(QnUDVCPU)
(QnUDVCPU)
for faster
for processing
faster processing
of largeofdata
largevolumes.
data volumes.
◎Realize◎Realize
high-speed,
high-speed,
high-accuracy
high-accuracy
machine control
machinewith
control
various
withiQvarious
Platform
iQ compatible
Platform compatible
controllerscontrollers
and multiple
andCPUs.
multiple CPUs.
◎Easily◎Easily
connectconnect
to GOTstoand
GOTs
Programming
and Programming
tools using
toolsbuilt-in
using built-in
Ethernet
Ethernet
port. port.
◎25 models
◎25 models
from 10k
from
step
10k
small
stepcapacity
small capacity
to 1000k
to 1000k
step large
stepcapacity,
large capacity,
are available.
are available.
◎Seamless
◎Seamless
communication
communication
and flexible
and flexible
integration
integration
at any network
at any network
level. level.
Product Specifications
Product Specifications
Program capacity
Program capacity 10k steps10k to 1000k
steps to steps
1000k steps
Number of I/O points
Number[X/Y],
of I/Onumber
pointsof[X/Y],
I/O device
numberpoints
of I/O[X/Y]
device points
256[X/Y]
points256to points
4096 points/8192
to 4096 points/8192points points
Basic instruction
Basicprocessing
instructionspeedprocessing
(LD instruction)
speed (LD instruction)
120 ns to120 1.9 nsns to 1.9 ns
External connection
External connection interface interface USB (all models USB (all equipped),
models equipped),
Ethernet, Ethernet,
RS-232, memoryRS-232,card, memory extended
card, extended
SRAM cassette SRAM cassette
Function Function
module module I/O, analog, high-speed
I/O, analog,counter,
high-speed
positioning,
counter,simple
positioning,
motion,simple
temperature
motion, input,
temperature
temperature
input, control,
temperature
network
control,
module
network module
Module extension
Module extension style style Building block
Buildingtypeblock type
Network Network Ethernet, Ethernet,
CC-Link IE CC-Link
controllerIE controller
network, CC-Link
network, IE CC-Link
field network,
IE field CC-Link,
network, CC-Link,
CC-Link/LT, CC-Link/LT,
MELSECNET/H, MELSECNET/H, SSCNETⅢ (/H), AnyWire,
SSCNETⅢ (/H), AnyWire,
RS-232, RS-422
RS-232, RS-422
Programmable
Programmable
Controller
Controller
MELSEC-L
MELSEC-L
Series Series
Light &Light
Flexible
& Flexible
condensing
condensing
variousvarious
functions
functions
easily easily
and flexibly.
and flexibly.
◎CPU ◎CPU
equipped
equipped
as a standard
as a standard
with various
with various
functions
functions
including
including
counter,counter,
positioning
positioning
and CC-Link.
and CC-Link.
◎The base-less
◎The base-less
structure
structure
with high
with
degree
high degree
of freedom
of freedom
saves space
saves in
space
the control
in the control
panel. panel.
◎Easily◎Easily
confirmconfirm
the system
the system
status and
status
change
and change
the settings
the settings
with thewith
display
the display
unit. unit.
◎Ten models
◎Ten models
are available
are available
in program
in program
capacities
capacities
from 20from
k steps
20 ktosteps
260 to
k steps.
260 k steps.
Product specifications
Product specifications
Program capacity
Program capacity 20 k steps/60
20 k steps/60
k steps/260k steps/260
k steps k steps
Number ofNumber input/output
of input/output
points [X/Y] points1024
[X/Y]points/4096
1024 points/4096
points points
Number of input/output
Number of input/output
device pointsdevice
[X/Y]points [X/Y]points
8192 8192 points
Basic instruction
Basicprocessing
instructionspeed
processing
(LD instruction)
speed (LD instruction)
60 ns/ 4060ns/ ns/9.5
40nsns/ 9.5 ns
External connection
External connection
interface interface USB, Ethernet, USB, Ethernet,
RS-232, SD RS-232,
memory SDcard,
memory
CC-Link
card, (L26CPU-BT/PBT)
CC-Link (L26CPU-BT/PBT)
Function Function
modules modules I/O, analog,I/O,
high-speed
analog, high-speed
counter, positioning,
counter, positioning,
simple motion,
simple
temperature
motion, temperature
control, network
control,
module
network module
Unit expansion
Unit expansion
style style Base-lessBase-less
structure structure
Network Network Ethernet, CC-Link
Ethernet,IECC-Link
Field network,
IE FieldCC-Link,
network,CC-Link/LT,
CC-Link, CC-Link/LT,
SSCNETIII(/H),
SSCNETIII(/H),
RS-232, RS-422
RS-232, RS-422
Programmable
Programmable
Controller
Controller
MELSEC-F
MELSEC-F
Series Series
All-in-One
All-in-One
Micro Programmable
Micro Programmable
Controller
Controller
equippedequipped
with all with
necessary
all necessary
functions
functions
in a compact
in a compact
body body
◎Supporting
◎Supporting
small-scale
small-scale
control from
control
10 points
from 10
to points
384 points
to 384
(using
points
CC-Link)
(using CC-Link)
with an outstanding
with an outstanding
cost performance.
cost performance.
◎Wide ◎Wide
range ofrange
options
of options
available
available
for additional
for additional
functions
functions
requiredrequired
by your by
system.
your system.
◎Easy ◎Easy
to use and
to use
highly
andreliable.
highly reliable.
More than
More
12than
million
12 units
million
have
units
shipped
have shipped
worldwide.
worldwide.
(April 2013)
(April 2013)
◎Small-scale
◎Small-scale
control control
is available
is available
in various
in various
networksnetworks
such assuch
CC-Link,
as CC-Link,
Ethernet,
Ethernet,
and MODBUS.
and MODBUS.
Product specifications
Product specifications
Program capacity
Program capacity 16k steps16k 3S ) to 64
(FXsteps (FXk3S)stepsto 64(FX k steps
3U /FX 3UC
(FX) 3U/FX 3UC)
Number ofNumber
input/output
of input/output
points points10 points10 3S ) to 384
(FXpoints (FX 3Spoints
) to 384 (FXpoints
3U /FX 3UC
(FXwith
3U /FXCC-Link)
3UC with CC-Link)
Basic instruction
Basic instruction
processing processing
speed 0.21μs (FX
speed 3S ) to 65
0.21μs (FXns3S ) (FX
to 65 3U /FX
ns 3UC
(FX ) 3U/FX 3UC)
External connection interface interface RS-422, USB
External connection RS-422,
(FX 3S/FXUSB
3G /FX
(FX3GC
3S /FX 3G /FX
3GE only),
3GC /FX
Ethernet
3GE only),
(FXEthernet
3GE only),(FX
CC-Link/LT
3GE only), CC-Link/LT
(FX 3UC-32MT-LT(-2)
(FX 3UC-32MT-LT(-2)
only) only)
Built-in functions
Built-in functions I/O, high-speed
I/O, high-speed
counter input, counter positioning
input, positioning
pulse output, pulseanalog
output, (FX
analog
3GE only)
(FX 3GE only)
Extended Extended
functions functions I/O, analog,
I/O,temperature
analog, temperature control, high-speed
control, high-speed
counter, positioning,
counter, positioning,
network network
Unit expansion
Unit expansion
style style Backplane-less
Backplane-less
design design
Network Network Ethernet, CC-Link,
Ethernet, CC-Link/LT,
CC-Link, CC-Link/LT,
SSCNETⅢ, SSCNETⅢ,
CANopen, J1939,
CANopen,RS-232C,
J1939,RS-422,
RS-232C, RS-485,
RS-422,
MODBUS
RS-485, MODBUS
34
[ Related Factory Automation Products ]
To theTo
topthe
of top
HMIsof with
HMIsfurther
with further
user-friendly,
user-friendly,
satisfactory
satisfactory
standard
standard
features.
features.
◎Comfortable
◎Comfortable
screen screen
operation
operation
even if even
high-load
if high-load
processing
processing
(e.g. logging,
(e.g. logging,
device data
device
transfer)
data transfer)
is running.
is running.
(Monitoring
(Monitoring
performance
performance
is twiceisfaster
twicethan
faster
GT16)
than GT16)
usable space
◎Actual◎Actual usablewithout
space without
using anusing
SD card
an SD
is expanded
card is expanded
to 128MB
to 128MB
for morefor
flexible
more screen
flexible design.
screen design.
◎Multi-touch
◎Multi-touch
features,
features,
two-point
two-point
press, and
press,
scroll
andoperations
scroll operations
for moreforuser-friendliness.
more user-friendliness.
◎Outline
◎Outline
font andfont
PNGandimages
PNG images
for clear,
forbeautiful
clear, beautiful
screen screen
display.display.
Product Specifications
Product Specifications
Screen sizeScreen size 12.1", 10.4",
12.1",
8.4"
10.4",
(15" 8.4"
coming
(15"soon)
coming soon)
ResolutionResolution SVGA, VGASVGA,
(XGAVGA coming
(XGAsoon)
coming soon)
Intensity adjustment
Intensity adjustment 32-step adjustment
32-step adjustment
Touch panelTouch
typepanel type Analog resistive
Analog film
resistive film
Built-in interface
Built-in interface RS-232, RS-422/485,
RS-232, RS-422/485,
Ethernet, Ethernet,
USB, SD USB,
card SD card
ApplicableApplicable
software software GT Works3GT Works3
Input powerInput
supply
powervoltage
supply voltage 100 to 240VAC
100 to (+10%,
240VAC−15%),
(+10%,24VDC
−15%),(+25%,
24VDC−20%)
(+25%, −20%)
AC Servo
AC Servo Mitsubishi
Mitsubishi
General-Purpose
General-Purpose
AC Servo
AC Servo
MELSERVO-J4
MELSERVO-J4
Series Series
Industry-leading
Industry-leading
level of
level
highofperformance
high performance
servo servo
◎Industry-leading
◎Industry-leading
level of basic
level performance:
of basic performance:
Speed frequency
Speed frequency
response response
(2.5kHz), (2.5kHz),
4,000,0004,000,000
(4,194,304p/rev)
(4,194,304p/rev)
encoder encoder
◎Advanced
◎Advanced
one-touchone-touch
tuning function
tuningachieves
function achieves
the one-touch
the one-touch
adjustment
adjustment
of advanced
of advanced
vibration suppression
vibration suppression
control Ⅱ,control
etc. Ⅱ, etc.
◎Equipped
◎Equipped
with large
with
capacity
large capacity
drive recorder
drive recorder
and machine
and machine
diagnosis
diagnosis
functionfunction
for easyfor
maintenance.
easy maintenance.
◎2-axis◎2-axis
and 3-axis
andservo
3-axis
amplifiers
servo amplifiers
are available
are available
for energy-conservative,
for energy-conservative,
space-saving,
space-saving,
and low-cost
and low-cost
machines.
machines.
Product Specifications
Product Specifications
Power supply
Powerspecifications
supply specifications 1-phase/3-phase
1-phase/3-phase
200V AC,200V
1-phaseAC,100V
1-phase
AC,100V
3-phase
AC,400V
3-phaseAC 400V AC
CommandCommand
interface interface SSCNET Ⅲ/H,
SSCNETSSCNET
Ⅲ/H, ⅢSSCNET
(compatible
Ⅲ (compatible
in J3 compatibility
in J3 compatibility
mode), CC-Link
mode),IECC-Link
Field IE Field
Network interface
Network with
interface
Motion,
withpulse
Motion,
train,
pulse
analog
train, analog
Control mode
Control mode Position/Speed/Torque/Fully
Position/Speed/Torque/Fully
closed loop closed loop
Speed frequency
Speed frequency
response response 2.5kHz 2.5kHz
Tuning function
Tuning function Advanced Advanced
one-touch one-touch
tuning, advanced
tuning, advanced
vibration suppression
vibration suppression
control Ⅱ, control
robust filter,
Ⅱ, robust
etc. filter, etc.
Safety function
Safety function STO, SS1STO, SS1
SS2, SOS,SS2,
SLS,SOS,
SBC,SLS,
SSMSBC,
(compatible
SSM (compatible
when combined
when combined
with motionwith
controller)
motion controller)
Compatible
Compatible
servo motor
servo motor Rotary servo
Rotary
motor
servo
(rated
motor
output:
(rated0.05
output:
to 22kW),
0.05 tolinear
22kW),
servo
linear
motor
servo
(continuous
motor (continuous
thrust 50 thrust
to 3000N),
50 to direct
3000N),
drive
direct
motor
drive
(rated
motor
torque:
(rated
2 torque:
to 240N2• m)
to 240N • m)
AC Servo
AC Servo Mitsubishi
Mitsubishi
General-Purpose
General-Purpose
AC Servo
AC Servo
MELSERVO-JE
MELSERVO-JE
Series Series
High performance
High performance
and easy
andtoeasy
use to
servo
use system
servo system
for all for
machines
all machines
◎Easy ◎Easy
To Use:To
The
Use:
advanced
The advanced
one-touch
one-touch
tuning function
tuning function
enablesenables
servo adjustment
servo adjustment
with with
one-touch
one-touch
ease without
ease without
a personal
a personal
computer.
computer.
◎High Performance:
◎High Performance:
Class top-level
Class top-level
basic performance
basic performance
includingincluding
speed frequency
speed frequency
responseresponse
of 2.0kHz.
of 2.0kHz.
◎Global
◎Global
Standard:
Standard:
Command
Command
pulse input
pulseand
input
digital
and input/output
digital input/output
are compatible
are compatible
with both
with
sink
both sink
and source
and source
type connections
type connections
as a standard.
as a standard.
Product specifications
Product specifications
Power supply
Powerspecifications
supply specifications 1-phase/3-phase
1-phase/3-phase
200V AC 200V AC
CommandCommand
interface interface Pulse train,
Pulse
analog
train, analog
Control mode
Control mode Position/speed/torque
Position/speed/torque
Speed frequency
Speed frequency
response response 2.0kHz 2.0kHz
Tuning function
Tuning function AdvancedAdvanced
one-touchone-touch
tuning, advanced
tuning, advanced
vibration control
vibrationII, control
robust II,
filter,
robust
etc.filter, etc.
Compatible
Compatible
servo motor
servo motor Rotary servo
Rotary
motor
servo
(rated
motor
output:
(rated0.1
output:
to 3kW)
0.1 to 3kW)
35
[ Related
[ Related
Factory
Factory
Automation
Automation
Products
Products
] ]
InverterInverter FR-A800
FR-A800
Series Series
High-functionality,
High-functionality,
high-performance
high-performance
inverterinverter
◎Realize◎Realize
even highereven
responsiveness
higher responsiveness
during realduring
sensor-less
real sensor-less
vector control
vector
or vector
controlcontrol,
or vector
andcontrol,
achieveandfaster
achieve
operating
faster frequencies.
operating frequencies.
◎The latest
◎Theautomatic
latest automatic
tuning function
tuning function
supportssupports
various induction
various induction
motors and
motors
alsoand
sensor-less
also sensor-less
PM motors.
PM motors.
◎The standard
◎Themodel
standard
is compatible
model is compatible
with EU Safety
with EU
Standards
Safety Standards
STO (PLd,STO
SIL2).
(PLd,
AddSIL2).
options
Add
to options
support tohigher
support
levelhigher
safetylevel
standards.
safety standards.
◎A variety
◎Aofvariety
usefuloffunctions
useful functions
provide USB
provide
memory
USB memory
support support
and customization
and customization
with a PLC
withfunction.
a PLC function.
Product Specifications
Product Specifications
Inverter capacity
Inverter capacity 200V class:200V0.4kWclass:
to 90kW,
0.4kW 400V
to 90kW, class:
400V
0.4kWclass:
to 500kW
0.4kW to 500kW
Control method
Control method High-carrier
High-carrier
frequency frequency
PWM control PWM (Select
control
from
(Select
V/F, advanced
from V/F, flux
advanced
vector,flux vector,
real sensor-less
real sensor-less
vector or PM vector
sensor-less
or PM sensor-less
vector control),
vectorvector
control),
control
vector
(when
control
using
(when
options)
using options)
Output frequency
Output frequency
range range 0.2 to 590Hz0.2 (when
to 590Hz using
(when
V/F using
control V/F
or advanced
control or flux
advanced
vectorflux
control)
vector control)
Regenerative
Regenerative
braking torque 200V class:
braking torque 200V
0.4Kclass:
to 1.5K0.4K(150%
to 1.5K
at 3%ED)
(150% 2.2K/3.7K
at 3%ED) 2.2K/3.7K
(100% at 3%ED)
(100% 5.5K/7.5K
at 3%ED) 5.5K/7.5K
(100% at 2%ED)
(100% at 2%ED)
(Maximum (Maximum
tolerable usage
tolerable 11K
rate)usage to 55K11K
rate) (20% to continuous)
55K (20% continuous)
75K or more 75K(10%
or more
continuous),
(10% continuous),
400V class:400V
0.4Kclass:
to 7.5K
0.4K
(100%
to 7.5K
at 2%ED)
(100% at 2%ED)
11K to 55K11K(20% to 55K
continuous)
(20% continuous)
75K or more 75K(10%
or more
continuous)
(10% continuous)
Starting torque
Starting torque 200% 0.3Hz 200%
(3.7K0.3Hz
or less),
(3.7K150%
or less),
0.3Hz 150%
(5.5K0.3Hz
or more)
(5.5K(when
or more)
using(when
real sensor-less
using real sensor-less
vector, vector
vector,
control)
vector control)
Three-Phase
Three-Phase
Motor MotorHigh Performance
High Performance
Energy-Saving
Energy-Saving
Motor Motor
Super Super
Line Premium
Line Premium
Series Series
SF-PRSF-PR
High Efficiency
High Efficiency
& Compatible.
& Compatible.
New Launch
New Launch
of Super
of Line
SuperPremium
Line Premium
Series Series
SF-PR SF-PR
Model Model
◎Compared
◎Compared
to general-purpose
to general-purpose
motor SF-JRmotor
model,SF-JR
generated
model,loss
generated
is reduced
lossbyis 37%
reduced
on average,
by 37% onandaverage,
it is compatible
and it is with
compatible
highly efficient
with highly
premium
efficient
IE3.premium IE3.
◎Easy replacement
◎Easy replacement
is achieved
is as
achieved
mounting
as mounting
dimensiondimension
(frame number)
(frameisnumber)
compatible
is compatible
with general-purpose
with general-purpose
motor SF-JR
motor
model.
SF-JR model.
◎One motor◎One
can accommodate
motor can accommodate
different powerdifferent
sourcespower
of Japan
sources
and oftheJapan
U.S. Three
and theratings
U.S. Three
in Japan
ratings
meetintheJapan
Top meet
Runnerthestandards,
Top Runnerwhile
standards,
it corresponds
while ittocorresponds
EISA in thetoU.S.
EISA in the U.S.
◎Can be ◎Can
driven bybeinverters
driven byasinverters
standard.asAdvanced
standard. magnetic-flux
Advanced magnetic-flux
vector control
vector
by our
control
FR-A800
by ourachieves
FR-A800steady
achieves
torque
steady
drivetorque
up to drive
0.5Hz.
up to 0.5Hz.
Product Specifications
Product Specifications
Number ofNumber
poles of 2-poles,
poles 4-poles,
2-poles, 6-poles
4-poles, 6-poles
Voltage・Frequency
Voltage・Frequency
200/200/220/230V
200/200/220/230V
50/60/60/60Hz
50/60/60/60Hz
EISA 230VEISA
60Hz230V
or 400/400/440/460V
60Hz or 400/400/440/460V
50/60/60/60Hz
50/60/60/60Hz
EISA 460VEISA
60Hz460V 60Hz
Exterior Exterior Totally enclosed
Totally enclosed
fan cooledfantype
cooled
(inside,
typeoutside
(inside,installation)
outside installation)
ProtectionProtection
system system
IP44 IP44
Electrically-driven Motor with
Electrically-driven Motor
2-poles
withover
2-poles
11kW over
is dedicated
11kW is dedicated
for a directforconnection.
a direct connection.
power system
power systemMotors with
Motors
4-poles
withand
4-poles
6-poles
andare
6-poles
for both
aredirect
for bothanddirect
crossed
andbelt
crossed
connections.
belt connections.
Rotation direction
Rotation direction
Counter-clock-wise
Counter-clock-wise
(CCW) direction
(CCW) direction
viewed from
viewed
the edge
from the
of axis.
edge of axis.
CompatibleCompatible
standard standard
JEC-2137-2000
JEC-2137-2000
(Efficiency(Efficiency
is compatible
is compatible
with IEC 60034-30.)
with IEC 60034-30.)
High speed,
High high
speed,
precision
high precision
and high
and
reliability
high reliability
industrial
industrial
robot robot
◎Compact
◎Compact
body andbody
slimand
armslim
design,
arm allowing
design, allowing
operatingoperating
area to be
area
expanded
to be expanded
and loadand
capacity
load capacity
increased.
increased.
◎The fastest
◎The fastest
in its class
in itsusing
classhigh
using
performance
high performance
motors motors
and unique
and unique
driver control
driver control
technology.
technology.
◎Improved
◎Improved
flexibility
flexibility
for robotforlayout
robot design
layout considerations.
design considerations.
◎Optimal motor control
◎Optimal motor tuning
controlset
tuning
automatically
set automatically
based onbased
operating
on operating
position,position,
posture, posture,
and loadand
conditions.
load conditions.
Product Specifications
Product Specifications
Degrees of
Degrees
freedom
of freedom Vertical:6 Horizontal:4
Vertical:6 Horizontal:4
Vertical:Floor-mount,
Vertical:Floor-mount,
ceiling mount,
ceiling
wall
mount,
mount
wall
(Range
mountof(Range
motion of
formotion
J1 is limited)
for J1 is limited)
Installation
Installation
Horizontal:Floor-mount
Horizontal:Floor-mount
Maximum Maximum
load capacity
load capacity Vertical:2-20k
Vertical:2-20k
g Horizontal:3-20kg
g Horizontal:3-20kg
Maximum Maximum
reach radius
reach radius Vertical:504-1503mm Horizontal:350-1,000mm
Vertical:504-1503mm Horizontal:350-1,000mm
36
[ Related Factory Automation Products ]
Next-generation
Next-generation
Innovations
Innovations
of our best
of ourselling
best selling
Performance
Performance
Machine.
Machine.
◎Total◎Total
runningrunning
cost reduced
cost reduced
up to 42%,
up towhich
42%, is
which
accounted
is accounted
for 90%forby90%
filter,
byion
filter,
exchange
ion exchange
resin and
resin
power
and consumption.
power consumption.
◎Improved
◎Improved
productivity
productivity
by an innovative
by an innovative
automatic
automatic
wire threading.
wire threading.
◎Faster◎Faster
machining
machining
is realized
is realized
with improved
with improved
power-supply
power-supply
performance.
performance.
(Rz3. (Rz3.
5μm/Ra0.5μm/Ra0.
45μm with
45μm 3cuts)
with(3cuts)
Rz2. (
0μm/Ra0.
Rz2. 0μm/Ra0.
28μm with28μm4cuts)
with 4cuts)
Product Specifications
Product Specifications
Model Model MV1200RMV1200R
MachiningMachining
travel (X×Y×Z)[mm]
travel (X×Y×Z)[mm]
(in) 400(15.7)×300(11.8)×220(8.7)(XY
(in) 400(15.7)×300(11.8)×220(8.7)(XY
axis OPT-drive
axis OPT-drive
specifications)
specifications)
MachiningMachining
travel (U×V)[mm]
travel (U×V)[mm]
(in) ±60(2.4)×±60(2.4)(OPT-drive
(in) ±60(2.4)×±60(2.4)(OPT-drive
specifications)
specifications)
Max. taperMax.
angletaper
[°] angle [° ] 15°(maximum
15°(maximum
200mm)(7.9")
200mm)(7.9")
Max. workpiece
Max. workpiece
dimensions dimensions
[mm] (in) [mm] (in) 810(31.9)×700(27.6)×215(8.5)
810(31.9)×700(27.6)×215(8.5)
Wire diameter
Wire [mm]
diameter [mm] (in) 0.1(.004)
(in) 0.1(.004)
to 0.3(.012)
to 0.3(.012) ※1
※1
DielectricDielectric
fluid fluid Water Water
Footprint Footprint
(W×D)[mm] (W×D)[mm] (in) 2025(79.7)×2760(108.7)
(in) 2025(79.7)×2760(108.7)
※1:Φ0.2(0.08)
※1:Φ0.2(0.08)
DD guidesDD
and
guides
Φ1.5(0.06)
and Φ1.5(0.06)
jet nozzlejet
arenozzle
standard
are equipment.
standard equipment.
Laser Processing
Laser Processing
Machine
Machine
CO 2 2-Dimensional
CO 2 2-Dimensional
Laser Processing
Laser Processing
Machine
Machine
eX-Series
eX-Series
A global
A global
standard
standard
CO 2 2-dimensional
CO 2 2-dimensional
laser processing
laser processing
systems.
systems.
◎Productivity
◎Productivity
has been dramatically
has been dramatically
enhanced owing
enhanced
to improved
owing toacceleration
improved acceleration
and the latest
andcontrol
the latest
technologies
control technologies
exclusive toexclusive
Mitsubishito Electric.
Mitsubishi Electric.
◎2 Action
◎2Cutting
Actionallows
Cuttingforallows
the entire
for the
process,
entire from
process,
job setup
from job
to parts
setupcutting,
to partstocutting,
be completed
to be completed
in two simple
in twoactions.
simple actions.
◎When not ◎When
processing,nottheprocessing,
system switches
the system
to ECO
switches
mode toandECO
themode
resonator
and the
stopsresonator
idling. Minimizes
stops idling.
energy
Minimizes
consumption,
energy consumption,
reducing running
reducing
costs running
by up tocosts
99%*1by during
up to 99%
standby.
*1
during standby.
*1
: Compared
*1
: Compared
to the previous
to the previous
LV-Series
LV-Series
with Mitsubishi's
with Mitsubishi's
designated
designated
benchmark
benchmark
shape. shape.
Product specifications
Product specifications
Model NameModel Name ML3015eX ML3015eX
Drive system
Drive system Flying optic
Flying
(3-axis
opticbeam
(3-axis
movement)
beam movement)
Stroke (X×Y×X)
Stroke (X×Y×X)
[mm] [mm] 3100×1565×150
3100×1565×150
Rapid feedrate
Rapid feedrate
[m/min] [m/min] X,Y axes:X,Y
Max. axes:
100;Max.
Z-axis:
100;Max.
Z-axis:
65 Max. 65
ProcessingProcessing
feedrate feedrate
[m/min] [m/min] Max. 50 Max. 50
Positioning
Positioning
accuracy accuracy
[mm] [mm] 0.05 / 500 0.05(X,Y/ 500
axes)(X,Y axes)
Repeat accuracy
Repeat accuracy
[mm] [mm] ± 0.01 (X,Y
± 0.01axes)(X,Y axes)
Rated output
Rated[W]
output [W] 4500 4500
Laser Processing
Laser Processing
MachineMachine
for Substrate
for Substrate
Drilling Drilling
GTW4 GTW4
Series Series
Ever-evolving
Ever-evolving
global global
standard
standard
machine
machine
◎Newly-developed
◎Newly-developed
super-fast
super-fast
galvano galvano
and 360Wandhigh-power
360W high-power
resonatorresonator
achieve achieve
industry-leading
industry-leading
productivity.
productivity.
◎Laser beam
◎Laser
generated
beam generated
by unparalleled
by unparalleled
resonator enables
resonatorstable
enables
high-quality
stable high-quality
copper-direct
copper-direct
processingprocessing
on variouson
surface
various
treatments.
surface treatments.
◎Single machine
◎Singlecan
machine
support
canvariety
support
of variety
processing
of processing
applicationapplication
with Mitsubishi
with Mitsubishi
unique powerful
uniquelaser
powerful
and optimum
laser andbeam
optimum
control.
beam control.
◎Original
◎Original
resonatorresonator
structure,structure,
which canwhich
be refreshed
can be refreshed
by replacing
by replacing
some parts
some
only,
parts
realizes
only, low
realizes
operating
low operating
cost. cost.
Product specifications
Product specifications
Model nameModel name ML605GTW4(-H)-5350U/ML605GTW4
ML605GTW4(-H)-5350U/ML605GTW4
(-P)-5350U/ML706GTW4-5350U
(-P)-5350U/ML706GTW4-5350U
ProcessingProcessing
workpieceworkpiece
dimensionsdimensions
(mm) (mm)
620×560/815×662
620×560/815×662
XY table maximum
XY table maximum
feedrate (m/min)
feedrate (m/min)
50 50
Laser typeLaser type CO 2 laserCO 2 laser
OscillatorOscillator
power (W)power (W) 360W 360W
OscillatorOscillator
set pulse set
frequency
pulse frequency 10 to 10000Hz
10 to 10000Hz
37
[ Related Factory Automation Products ]
Low Voltage Circuit Breakers Mitsubishi WS-V Series Molded Case Circuit Breakers, Earth Leakage Circuit Breakers
Product specifications
Frame 10 A to 32 A
Applicable standards Certification to various standards including IEC, JIS, CE, UL, TÜV, CCC.
Terminal cover Standard terminal cover improves safety, simplifies ordering, and reduces inventory, etc.
Improved wiring Wiring and operability are improved with streamlining wiring terminal BC specifications.
Operation coil rating Wide range of operation coil ratings reduces number of coil types from 14 (N Series) to 7 types and simplifies selection.
Option units Diverse lineup includes Auxiliary Contact Block, Operation Coil Surge Absorber Unit, Mechanical Interlock Unit.
38
Products for achieving e-F@ctory
The integrated solution, e-F@ctory, is based on our consolidated know-how, which has been developed
through our own experiences as a user of FA products. Our e-F@ctory provides total cost reduction ranging Ethernet
Information network
from development to production and maintenance to achieve optimized production. This solution makes it
possible to save energy and to optimize production by "visualization" that links upstream information systems "Visualization"
and production site information, thus solving various problems on production sites. by information
linkage
Sharing information across production systems Diagnosis unit with MES Interface (MELQIC) HMI with MES Interface Programmable Controllers with MES Interface EcoServer III
M ES In te r f a ce
Information sharing is easy and inexpensive because communication MES linkage function
gateways, such as personal computers, are not necessary to connect factory
equipment to the Manufacturing Execution System (MES). Production site
Controller network
Field network
Safety field network Field network
B/NET
Visualization of energy consumption
e & e co-F @ cto ry Safety remote I/O Energy
measurement unit
MDU Electronic multi-indicating
breaker instrument
Servo-network
It is indispensable for today’ s factory to be energy conscious and efficient.
The e-F@ctory solution enables management of specific energy consump-
tion, which provides the visibility needed to improve productivity. Additionally,
this solution takes the total life cycle into account, including factors such as
“measurement and diagnosis”, “countermeasures”, and “operation and Programmable Geared motor Robots
AC Servo Controllers
management”. Backed by several successes and achievements, our know-
how will support your energy saving efforts. CC-Link-AnyWire
Bitty Bridge
Reduced wiring network Sensor network
iQ Platform-compatible iQ Platform-compatible
Network Remote I/O Foolproof Mapping sensor
equipment engineering environments terminal terminal
CC-Link Family, the open field network of The inter-multi-CPU high-speed base unit Design information is integrated and
the world standard, and SSCNET III/H, the provides slots for arbitrarily connecting shared at stages from system design to
servo network for achieving high-speed programmable controllers, motion programming, tests and startup, and
processing and enhancement of instruction controllers, on-line CNCs, and robot operation and maintenance. In addition,
synchronization, flexibly expanding the controllers. Data communication programming software programs for
connectivity among equipment and speed among devices is enhanced, and programmable controllers, motion
devices in the e-F@ctory environment. their compatibility is extremely improved. controllers, on-line CNCs, robots, and
GOTs, which are separately provided in a
conventional environment, can be
integrated. Inverter
39 40
Global network for comprehensive support of customers' manufacturing.
FA Center Satellite Mechatronics Service Base
Global FA Center Mitsubishi Sales Offices Production Facility Development Center
(China) (China)
Ratingen, Germany Kraków, Poland St.Petersburg, Russia Istanbul, Turkey Seoul, Korea
Mitsubishi Electric Europe B.V. Mitsubishi Electric Europe B.V. Mitsubishi Electric Europe B.V. Mitsubishi Electric Turkey Mitsubishi Electric Automation
German Branch (Germany FA Center) Polish Branch Representative Office in St. Petersburg A.Ş Ümraniye Branch (Turkey FA Center) Korea Co., Ltd. (Korea FA Center)
(Europe FA Center) (Russian FA Center)
Taipei,
Hatfield, UK
Taichung, Taiwan
Pune,
Hanoi,
Gurgaon, India Tlalnepantla De Baz, Mexico
Ho Chi Minh, Vietnam
Bangalore,
Mitsubishi Electric India Pvt. Ltd. L : Mitsubishi Electric Vietnam Co., Ltd. Mitsubishi Electric
Hanoi Branch Automation, Inc. Mexico Branch
R : Mitsubishi Electric Vietnam Co., Ltd. (Mexico FA Center)
Service bases are established around the world to globally provide the same services as in Japan.
China (including Hong Kong District)
Beijing Overseas bases are opened one after another
Mitsubishi Automation (China) Ltd.
Beijing Office (Beijing FA Center) to support business expansion of our customers.
Overseas bases As of September 2013 * Some includes distributors
Changchun
Bases providing
Tianjin Shenyang
Shanghai Area Our overseas offices Countries (Regions)
Beijing FA Center (Satellite) our products
Dalian
Mitsubishi Automation (China) Ltd. Tianjin Mitsubishi Automation (China) Ltd.
Tianjin Office (Tianjin FA Center) (Shanghai FA Center)
Zhengzhou Qingdao EMEA 11 6 (2) 146 54
Chengdu
Xiangfan China 13 4 (10) 171 1
Shanghai
Wuhang 11 10
Chongqing Asia 19 79
Guangzhou Shanghai
Fuzhou
Mitsubishi Electric Automation Guangzhou Taipei Mitsubishi Electric Automation America 14 4 (0) 130 16
(China) Ltd. Guangzhou Solution Center
Office (Guangzhou FA Center) Taichung
Shenzhen Others 1 0 3 2
Safety Warning
To ensure proper use of the products listed
in this catalog, please be sure to read the
instruction manual prior to use.
HEAD OFFICE: TOKYO BLDG., 2-7-3, MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
L(NA)06055ENG-F(1404)MEE