Академический Документы
Профессиональный Документы
Культура Документы
00 (FM-200 - UL/FM)
EX5104 / Component of FM Approved System
Consolidated Report
Customer Information
Company Name:
Address:
Phone:
Contact:
Title:
Project Data
Project Name: Control Room
Designer:
Number:
Account:
Location:
Description: Novec Main System
Enclosure Report
Page: 1 of 8
Consolidated Report
Minimum: 7.17 % Total Volume: 170.51 m ³
Min. Agent Required: 96.21 kg
Adjusted Agent Required: 97.00 kg
Page: 2 of 8
Consolidated Report
Parts Report
Pipe &
Fittings Type Diameter Length Elbows (90) Elbows (45) Tees Unions
40T 32 mm 3.20 m 2 0 0 0
40T 50 mm 6.44 m 2 0 1 0
Other
Objects Name Quantity Part Number
50 mm Swivel Union Adaptor 1 309.002.012
Enclosure Number: 1
Enclosure Name: Control Room
Minimum Design Concentration: 7.17%
Page: 3 of 8
Consolidated Report
Adjusted Design Concentration: 7.23%
Predicted Concentration: 7.23%
Maximum Expected Agent Concentration: 7.83% (At 45.0 C)
Page: 4 of 8
Consolidated Report