Вы находитесь на странице: 1из 4

CONECTOR DB37 EAC BTS NOKIA

Pin GND Sig


1 19 In #13
2 20 In #14
3 21 In #15
4 22 In #16
5 23 In #17
6 24 In #18

Connector Superior
7 25 In #19
8 26 In #20
9 27 In #21
10 28 In #22
11 29 In #23
12 30 In #24
13 31 NOT USED
14 32 NOT USED
15 33 NOT USED
16 34 NOT USED
17 35 NOT USED
18 36 NOT USED
1 20 Out #1
2 21 Out #2
3 22 Out #3
4 23 Out #4
5 24 Out #5
6 25 Out #6
Connector Inferior

7 26 In #1
8 27 In #2
9 28 In #3
10 29 In #4
11 30 In #5
12 31 In #6
13 32 In #7
14 33 In #8
15 34 In #9
16 35 In #10
17 36 In #11
18 37 In #12
INDOOR SEVERITY

PUERTA ABIERTA MINOR


VANDALISMO CRITICAL
PUERTA ABIERTA DEL NUSS | MCPA VSWR MAJOR
BAJA TEMPERATURA | MCPA FAIL MAJOR
VANDALISMO - AVERÍA DE CERCO ELECTRICO CRITICAL
MCPA DOOR OPEN - VENT -FUSIBLE MAJOR
PUERTA ABIERTA DEL NUSS MINOR
CORTE DE ENERGIA COMERCIAL MAJOR
DC DISTRIBUTION FAIL | CORTE DE ENERGIA AC 3G MAJOR
FALLA DE RECTIFICADOR | FALLA DE MODULO MAJOR
BATERIA BAJA | BAJO VOLTAJE CRITICAL
ALTA TEMPERATURA MAJOR
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
SPARE
SPARE
SPARE
SPARE
SPARE
SPARE
AIRE ACONDICIONADO MINOR
TRANSFER SWITCH MAJOR
FALLA DEL GENERADOR CRITICAL
FUNCIONAMIENTO DEL GENERADOR MAJOR
BAJO NIVEL DE COMBUSTIBLE MAJOR
POWER PLANT MAJOR MAJOR

DETECTOR DE HUMO MAJOR


FUEGO CRITICAL
PORT
OUTDOOR CON NUSS SEVERITY TEXT ID
NUSS
8
PUERTA ABIERTA MINOR 9
VANDALISMO CRITICAL 10
MAJOR 11
BAJA TEMPERATURA MAJOR 12
VANDALISMO - AVERÍA DE CERCO ELECTRICO CRITICAL 13
FALLA DE MODULO MAJOR 14
PUERTA ABIERTA DEL NUSS 1 MINOR 15
CORTE DE ENERGIA COMERCIAL 2 MAJOR 16
DC DISTRIBUTION FAIL | CORTE DE ENERGIA AC 3G 3 MAJOR 17
FALLA DE RECTIFICADOR 4 MAJOR 18
BATERIA BAJA | BAJO VOLTAJE 5 CRITICAL 19
ALTA TEMPERATURA 6 MAJOR 20
NOT USED 21
NOT USED 22
NOT USED 23
NOT USED 24
NOT USED 25
NOT USED 26
SPARE 27
SPARE 28
SPARE 29
SPARE 30
SPARE 31
SPARE 32
AIRE ACONDICIONADO MINOR 33
TRANSFER SWITCH MAJOR 34
FALLA DEL GENERADOR CRITICAL 35
FUNCIONAMIENTO DEL GENERADOR MAJOR 36
BAJO NIVEL DE COMBUSTIBLE MAJOR 37
POWER PLANT MAJOR MAJOR 38
39
DETECTOR DE HUMO MAJOR 40
FUEGO CRITICAL 41
42
43
44
45
46
47
48
49
50
51
52
53
GROUP TEXTOS POSIBLES EN BSC Cable EAC Nokia

ENER. BAJO VOLTAJE DB9 DB37


ENER. FALLA DE MODULO NUSS BTS
ENER. CORTE DE ENERGIA AC 3G 1 <--> 7
ENER. INTERNAL AC POWER FAIL 2 <--> 8
ENER. CORTE DE ENERGIA COMERCIAL 3 <--> 9
ENER. POWER PLANT MAJOR 4 <--> 10
ENER. POWER PLANT MINOR 5 <--> 11
ENER. BATERIA BAJA 6 <--> 12
ENER. BATTERIES ON DISCHARGER 7 <--> 13
ENER. FALLA DE RECTIFICADOR 8 <--> 14
ENER. DC DISTRIBUTION FAIL 9 <--> 19

ENT. DETECTOR DE HUMO


ENT. FUEGO
ENT. BAJA TEMPERATURA
ENT. ALTA TEMPERATURA
ENT. PUERTA ABIERTA
ENT. AIRE ACONDICIONADO Y CALEFACCION
ENT. PUERTA ABIERTA DEL NUSS
MCPA VSWR
MCPA FAIL
MCPA DOOR OPEN - VENT - FUSIBLE
GEN. TRANSFER SWITCH
GEN. FALLA DEL GENERADOR
GEN. FUNCIONAMIENTO DEL GENERADOR
GEN. BAJO NIVEL DE COMBUSTIBLE
GEN.
GEN. PUERTA ABIERTA DEL GENERADOR

TRANSM.
TRANSM.
TRANSM.

TORRE
TORRE
TORRE

VAND. VANDALISMO - INTRUSO EN EL PERIMETRO


VAND. VANDALISMO
VAND. VANDALISMO - AVERÍA DE CERCO ELECTRICO
VAND. VANDALISMO - CERCO ELECTRICO DESACTIVADO

Вам также может понравиться