Академический Документы
Профессиональный Документы
Культура Документы
UPPDRAGSNUMMER
[DESCRIPTION]
[STATUS]
[DOKUMENT NR]
2014-02-19
[NAME] [NAME]
repo002.docx 2013-06-14
Sweco
Ändringsförteckning
WU document1
Summary
Three numbers of pumps are mounted on the turbine halls floors as a part of the Gorzow-
project. The pumps are – together with their steel foundation – mounted directly on the
concrete slab.
The purpose with this report is to analyze the dynamic behavior of the pumps and their
interaction with the concrete slab and the supporting soil. The dynamic behavior is both
analyzed in the ultimate limit state (ULS) and serviceability limit state (SLS).
The lowest natural frequency of the dynamic system is 36 Hz, which is higher than the
permitted 31 Hz (1.25f0). Hence, no further calculations are needed.
repo002.docx 2013-06-14
WU document1
TABLE OF CONTENTS
1 IINTRODUCTION 1
1.1 Purpose 1
1.2 Prerequisites 1
1.3 Geometry 1
3 CALCULATION MODEL 2
3.1 Soil spring 4
3.2 Calculation 1 5
3.3 Calculation 2 5
4 RESULTS, ULS 6
5 RESULTS; SLS 6
5.1 Calculation 1 6
5.2 Calculation 2 7
repo002.docx 2013-06-14
WU document1
1 IINTRODUCTION
Three numbers of pumps are mounted on the turbine halls floors as a part of the Gorzow-
project. The pumps are – together with their steel foundation – mounted directly on the
concrete slab.
1.1 Purpose
The purpose with this report is to analyze the dynamic behavior of the pumps and their
interaction with the concrete slab and the supporting soil. The dynamic behavior is both
analyzed in the ultimate limit state (ULS) and serviceability limit state (SLS).
1.2 Input
The input data for the analysis are listed below:
Pump together with motor and steel frame:
Drawing “Foundation Load”, provided by Xylem, no date.
Dynamic shear modulus of soil and dynamic Poisson ratio:
Document “5941_07_SCPTU_logs”, no date
Exciting frequency of motor:
E-mail, Martin Arvidsson, 2015-03-16
1.3 Geometry
Below, the placement of the pumps is shown.
1 (7)
repo002.docx 2013-06-14
WU document1
2.1 Material
2.1.1 Concrete
With the calculation model used, only the density of concrete is of interest.
Density of concrete: 2500 kg/m3
2.1.2 Soil
Dynamic shear modulus: G0 = 99 MPa
Note that the lowest stiff dynamic shear modulus is chosen. This will result in a lower
natural frequency, thus providing conservative results.
Dynamic Poisson ratio: 0.35
3 CALCULATION MODEL
The calculation model is a simple one-degree-of-freedom model. It is assumed that all the
stiffness is provided by the dynamic shear modulus of the supporting soil only (i.e. no
2 (7)
repo001.docx 2012-03-29
WU document1
bending stiffness of the continuous slab is attributed). As will be shown, all assumptions
resulting in lower natural frequencies are conservative. The soil spring supports the
masses of pumps, motors, steel frames and part of the foundation (the concrete slab).
Two cases are considered, Calculation 1 where the machinery does not interfere with
each other, shown in Figure 2 and Figure 3, and Calculation 2 where the machinery
interfere with each other, shown in Figure 4 and Figure 5
3 (7)
repo002.docx 2013-06-14
WU document1
Figure 4. One-degree-of-freedom model for calculation 2
4 (7)
repo001.docx 2012-03-29
WU document1
Figure 6. Equivalent circular area
3.2 Calculation 1
Calculation 1 compares the exciting frequency of the motor with the natural frequency of
the dynamic system shown in Figure 2. The natural frequency is obviously given by:
1 𝑘𝑠
𝑓= ∙√
2𝜋 𝑊𝑡 + 𝑚𝑓𝑜𝑢𝑛𝑑
where:
ks = soil spring (kN/m)
W t = mass of machinery
mfound = mass of contributing concrete slab
3.3 Calculation 2
Calculation 2 compares the exciting frequency with the natural frequency of the one-
degree-of-freedom model and the first bending mode of the continuous beam supported
by distributed springs as shown in Figure 4.
The natural frequency of the one-degree-of-freedom system is given by:
5 (7)
repo002.docx 2013-06-14
WU document1
4 RESULTS, ULS
The total weight of the pump is 5371 kg or 53 kN, which is less than the load capacity
given by “S-02-DE-CALCULATION REPORT- FLOOR SLAB-200MM THICK_rev02.
Further, loads from the machinery are transformed into linear loads due to the steel
frame. Hence, no further calculations are required. As will be shown in section 5 no
dynamic effects due to the pump are expected.
5 RESULTS; SLS
5.1 Calculation 1
Below, the natural frequency is plotted against the varying contributing area of the
concrete slab.
6 (7)
repo001.docx 2012-03-29
WU document1
It is evident that the area of the contributing slab does not affect the natural frequency of
the dynamic system to a significant extent. Further, the natural frequency is 25 % higher
than the exciting frequency of the motor.
5.2 Calculation 2
As the contributing concrete slab is not varied for this case, only one natural frequency is
given:
The lowest natural frequency permitted without performing a response analysis is:
25𝐻𝑧 ∙ 1.25 = 31.25 𝐻𝑧
7 (7)
repo002.docx 2013-06-14
WU document1