Paper PS7-1

FAST AND EFFECTIVE RESPONSE TO LNG


VAPOUR RELEASES AND FIRES
Kevin Westwood
Group Fire Advisor
BP
United Kingdom
www.bp.com
Mike Willson
Angus Fire
United Kingdom
www.angusfire.co.uk

ABSTRACT

BP are leading the world in practical test work to define modern approaches to LNG
fire protection and vapour dispersion. Working with partner Texas A&M university and
leading manufacturers, like Angus Fire, in fire suppression and detection technology, they
have developed a world class LNG test facility in Texas. Intended to promote an overall
understanding of LNG safety issues and how to deal with them.

The paper will cover some of the practical LNG testing, training and research work
that has defined optimised high expansion foam application rates for LNG fires and
vapour releases, proven the effectiveness of leading LNG Turbex foam generating
systems and other equipment for detecting and controlling LNG. It has also dispelled
some of the historical misunderstandings surrounding control of LNG releases.

PS7-1.1
Paper PS7-1

Introduction

LNG is playing an increasingly important role in helping meet growing world demand
for energy and cleaner fuels.

Against this background, the Texas Engineering Extension Service (TEEX), a


member of the internationally respected Texas A&M University system, BP, Angus Fire
and other Industry equipment and supply partners have developed the world’s foremost
hands-on LNG fire training and equipment testing facility at Brayton Field, College
Station, Texas..

Open to Industry this facility has received worldwide recognition for providing the
opportunity to develop practical skills and knowledge of how best to handle LNG
incidents in modern LNG liquefaction, storage and vaporisation plants as well as during
loading and unloading operations, shipping and road transportation.

To date, training of personnel who may be faced with an LNG release has taken place
at fire facilities and has mainly been carried out involving pits constructed in wide open
spaces. What makes this new facility unique is that it is purpose built and has full
detection, suppression and infrastructure facilities available. This provides realistic LNG
vapour release and fire scenarios for demonstration and hands on emergency response
training.

The LNG fireground at Texas A&M featuring three containment pits with a
combined area of over 410m2, L shaped two level trench and marine manifold

The facilities are also being utilised for practical LNG research and testing and are
contributing to the accumulation of a body of knowledge that can be shared with all those
involved in the Industry. To date more than 150 first responders from existing and
proposed LNG facilities across the world have completed the intensive three day course
offered by the facility. Such training is leading to a better understanding of facility layout
and operations and additional ways to enhance the safe handling of LNG.

This paper will highlight how the facility has helped the further development and
testing of fast and effective responses to potential LNG vapour releases and fires.

PS7-1.2
Paper PS7-1

The Facility

Test installations are of most value when they reflect actual plant. It is also important
that state-of-the-art equipment requires to be engineered specially to withstand the rigours
of LNG hazards and can be proven in LNG fires, not just under standard test conditions,
but also under more extreme scenarios.

The design and construction of the containment pits and trench which have been
provided at TEEX to collect the run off from LNG spillage, have therefore been based on
those already existing at real LNG terminals. Three different size concrete steel
reinforced pits have been constructed to simulate various design layouts including one
with extended vertical walls above ground. In most facilities, any LNG spill would be
collected via channels that would run from areas around the plant this having been
determined as the most probable location for any accidental release of a spill/release
occurring.

At the TEEX LNG facility, an open L shaped trench is provided, complete with steel
pipes in the lower section, two levels below grade construction, to simulate service
pipework, which some existing facilities carry along their spill channels. The
configuration of the containment pits and trenches allows that multiple variations of small
and large spill vapour release and fires can be produced, which to date have been from
3,000 to 35,000 gallons(US) (or 11 to 132 m3).

The information collected from these initial three years of training and test fires,
shows that containment pit design impacts on the behaviour of the larger LNG vapour
cloud and radiated heat from LNG fires.

All this information is currently being fed into the BP sponsored PhD programme at
the Texas A&M University’s Mary O’Connor Process Safety Center.

Current Standards

The Texas A&M pits have been purpose built to simulate current vertical sided,
reinforced concrete impounding basins in use around the world.

Foam for LNG Facilities

A major activity undertaken at the Facility has been the testing of equipment and
application methods for the best use of foam. The current fire protection standards such
as NFPA 11:2005 provide guidance and state that “discharge rates per unit area shall be
established by test” and “final design rates are generally 3-5 times test rates”. It also
recognises that “special attention should be given to heat effects since time to initiate
actuation is a critical factor in LNG fire control”. NFPA 59A does not currently recognise
the value of foam for vapour control and dispersion or controlling the fire and
suppression of the radiated heat following ignition of the vapours. Rapidly draining
foams will increase LNG vaporisation rates and exaggerate fire intensity, so foam and
equipment should therefore be proven by test on LNG, before selection for use in
operational facilities.

PS7-1.3
Paper PS7-1

Foam can be of major assistance in controlling LNG releases in impounding basins or


spill pits, loading manifold sumps and spill trenches. Foam provides increased safety in
an emergency by reducing the vaporisation rate and dispersing the vapours directly
upwards, away from ignition sources, thereby minimising the risk of vapour cloud
ignition.

If ignition should occur, foam quickly provides high levels of fire control and rapid
heat radiation reduction, thereby protecting personnel and exposed equipment. It is a
valuable protection for a controlled burn-off of the LNG spill and minimises the risk of
escalation.

Throughout the training and testing programme at the TEEX facility, all ratios of
foam production were utilised from low expansion at 7:1 through to high expansion at
500:1 to determine what worked and what did not.. The programme also conducted a
number of trials with CAFS (Compressed Air Foam) that showed practical difficulty and
limited effectiveness on small 10m2 pit fires. These established that a quality high
expansion foam of 500:1 expansion is most effective but that other foams are too wet,
with the result that heat transfer from water to the LNG can cause the product to vaporise
faster, increasing fire intensity without being able to provide adequate control and
radiation reduction.

Vapour Dispersion Technologies

The Facility has been used to analyse the dispersion of vapour arising from LNG.
Several technologies have been looked at: water fan spray; high expansion foam; gas
imaging technology and open path gas detection.

A Hydroshield 180° water fan spray

The Angus Hydroshield 180º water fan spray unit has been tested to show
containment of gas clouds in the facility although care must be taken to avoid run-off
water entering the LNG pit.

PS7-1.4
Paper PS7-1

To reduce vapourisation, a well formed 500:1 high expansion foam cover is


necessary. This can reduce vaporisation by 60% over the course of 2 minutes of foam
application. The foam also warms the reduced vapours so they rise vertically away from
potential ignition sources which are more likely to occur at ground level.

High Expansion foam reducing and dispersal of LNG Vapour

Foam was also observed to lock LNG beneath it, as was found when a hole broken
through the ice found new vapour rising above the 5% LEL limit.

State-of the-art thermal imaging cameras show the effectiveness of the foam blanket
when images are superimposed, to confirm a 60% vapour reduction with this high
expansion foam application.

The latest gas imaging technology has been brought to the Facility for evaluation and
development. Remarkable progress has been made with this cutting edge technology as
the images shown demonstrate. Of particular interest is the ability to ‘see’ the differences
in the flammable methane vapour being held and diverted by water sprays and water
monitors as against the vapours going through the water screens which can be identified
as non-flammable because of lower concentration.

The experiments at the Facility have already resulted in commercially available


remote methane leak detection cameras incorporating lessons learned at TEEX, being
demonstrated in September 2006.

Following many tests of various gas detection techniques, the Facility has the most up
to date infra-red gas and vapour technology, giving coverage around the entire LNG
fireground. Infra-red open path, or line of sight gas detectors are linked back to a central
processor on the edge of the Facility, so that attendees can obtain a first hand
understanding of detector operation, field of view, LEL alarm settings and the optimum
configuration for any given vapour release scenario. Together with hand-held portable
detectors to supplement the fixed systems, this fully operational, state-of-the-art gas
detection system gives the maximum possible flexibility to students, researchers and
design specialists to determine the most efficient application for gas/vapour detection at
both current and future LNG facilities.

PS7-1.5
Paper PS7-1

Open path infra–red fixed gas detection

Fire Control Technologies

The ability to test and understand LNG fires has been enhanced at the Facility by the
installation of closed circuit miniaturised television cameras in flameproof housings,
strobe lights and alarms all linked to a microprocessor in the support building. Such
ground-breaking technology allows an LNG fire to be recognised in seconds and a real
time visual image to appear on a controller’s desk or remote console anywhere in the
world.

Originally developed for the offshore oil industry to counter false alarms from
reflected flare radiation, this detection camera technology has found the ideal application
at the Facility. Over three years of developing the fireground, much refinement of the
digital signal micro-processing and software algorithms has been made, to cater for the
very particular visible range of an LNG flame. Using both stand-alone units and multiple
detectors it is possible to monitor the entire fireground for any ignition, however small or
large, by processing the live image and interpreting flame characteristics, discriminating
between genuine fire conditions and other radiant sources.

PS7-1.6
Paper PS7-1

Miniaturised CCTV flame detection

Testing at the Facility under realistic conditions has confirmed previous work in the
area of fire control. In the specific area of high expansion foam, different application rates
of EXPANDOL foam at 500:1 have enabled recommendations to be developed of what
will work in dynamic situations with less than ideal conditions, such as wind and rain
impacting on the release, which need to be considered in practical facilities.

Schematic showing how High Expansion foam works to control LNG fires

The figure above illustrates how foam can insulate and reduce radiation feedback to
the LNG, allowing a safe and effective controlled burn-off. Pit design can assist or hinder
this process. After an initial foam application, the heat from burning vapours above the
foam can cause it to break down. By pulsing the foam on and off, it is possible to keep
good control with the pit full of foam. These regular top-ups maintain a steady state and
reduce radiation by up to 90%. The skeletal 500:1 frozen foam layer that floats on the
LNG also helps to control the fire intensity.

Extinction of an LNG fire using high performance dry chemical powders such as
MONNEX may be an option on small or medium-size fires, but this is far easier to
achieve above a high performance 500:1 foam blanket.

PS7-1.7
Paper PS7-1

The benefit of this powder is that it can break up as it hits the heat of the fire, enabling
quicker and effective “mop-up” of free radicals. This can help to stop the event early,
before the fire gets out of control. This was observed at TEEX on fires within the
containment pits.

This splitting up of MONNEX in the flames helps to compensate for poor application
technique; all students attending the BP LNG Workshops are given 1 to 1 instruction so
that they are trained in the benefits and limitations of using dry chemical on various sizes
of LNG fire. In practice, physical obstructions, lower quality powders, or the extent of the
fire may inhibit extinction. Hence, technique is still a critical factor in achieving success.

Chemical Dry Powder being used by students under direction


from senior TEEX instructors

It is important to note that attempting extinction may not always be the best answer,
because of the potential for flashbacks or re-ignition. In this case, the best option is
usually a controlled LNG vapour burn-off through a high quality 500:1 high expansion
foam blanket, as it reduces the radiant heat, providing a safer environment and preventing
damage to surrounding plant.

Fixed Foam Generators

The units tested were Angus Fire LNG Turbex high expansion foam generators,
delivering 500:1 expansion ratios and specially rated to be capable of withstanding the
cold and heat of an LNG spill and possible ignition, where high temperatures are likely to
be achieved.

A 316 stainless steel boiler-grade body with 316 stainless steel aerofoil fan blades
avoids distortion and can ensure reliable air flow and foam expansion are achieved.

PS7-1.8
Paper PS7-1

An LNG Turbex Foam generators under test

High temperature bearings and insulation around the water turbine and special
lubricants are essential to prevent seizure and binding of the fan on the casing which
otherwise could halt operation.

Robust discharge hoods are required to direct the foam into the pit and minimise the
impact of wind, without reducing the expansion ratio or stability of the foam being
produced. It is important that enough good quality foam lands in the pit to achieve the
levels of control required.

Angus Fire’s Engineering Division is now using results from the tests, together with
proven Angus Fire products, as the benchmark for any LNG fire protection systems.

Effective Radiation Reduction

Tests run between 2004 to 2006 at the Facility have demonstrated the effectiveness of
foam application rates in reducing radiated heat. This is illustrated in the following graph,
which is based on tests at the 65m2 pit. This shows the Radiometer reduction measured
30m away from the pit in a cross wind direction.

2
65m - 11 October 2005

100

90

80

70

60
% Max Heat flux

50

40

30

20

10

0
0 0.5 1 1.5 2 2.5 3 3.5 4 4.5 5
Time (mins)

Figure showing a 90% radiation reduction in under 60 secs

PS7-1.9
Paper PS7-1

In these specific LNG Turbex tests, application rates of 500:1 high expansion foam at
10litres/m2/min have been shown to provide fast control and reduced radiation emissions
by 90% within 60 seconds with fast pit filling. Quality 500:1 high expansion foams will
produce an effective finished foam blanket with fresh and salt water.

The fire area before and after Expandol High Expansion foam application

This comparison from radiometer readings shows that heat outputs drop fast when the
right foam and equipment combination is applied, e.g. from around 7.5kW/m² to
0.7kW/m² within 60 seconds of foam application when LNG Turbex and EXPANDOL
high expansion (500:1) foam is applied, measured at 30 metres away in the cross-wind
direction on the upwind side. These findings show the benefits of installing the most
efficient and effective detection and protection technology. Ensuring that any spill, leak,
or escape of LNG is immediately detected either as a vapour or if ignited, allows the
operators to utilise fixed foam systems to maximum positive effect in containing vapour
release and/or reducing heat radiation and quickly controlling the fire.

Ongoing Testing and Research

Whilst the LNG Industry can be justifiably proud of its safety record, the TEEX
facility continues both with advanced LNG fire training and practical ongoing research to
improve further the speed and effectiveness of response to potential LNG incidents.
Combination fire hydrants, mobile 5 inch pumper connections, oscillating fire monitors,
and passive fire protection with the latest materials are continually being tested against
radiated heat and flame impingement.

Equally, experience from terminals and liquefaction plants are continually fed back
into the development of the Facility.

The latest tests carried out in October 2006 utilised Pittsburgh Corning Foamglass
inherently fire resisting blocks pre-positioned within the small 10m2 containment pit. The
Foamglass cellular glass block was cut into small cubes of 3.5 x 3.5 cms {1.5 x 1.5
inches); shrink-wrapped and sealed in UV and weather resistant polyethylene bags. The
bags are designed to float to the surface of the LNG should there be a leak or spill. If
ignited, the polyethylene bags are intended to burn off, releasing the cubes of cellular
glass to form a barrier and thereby aid in the suppression of the fire.

LNG was then poured over the “bagged” blocks in a simulated spill scenario. The test
was undertaken to see if the blocks would reduce vapourisation and radiated heat, both of
which would aid suppression by dry chemical extinguishers.

PS7-1.10
Paper PS7-1

The tests indicate a significant reduction in the radiated heat when the vapours were
ignited, the flame being easily extinguished with dry powder. However no visible
minimization or vapour control effects were witnessed and additional testing is required
to determine the effect if any on vapour volume reduction.

Conclusion

The existence of the TEEX Facility is allowing the LNG Industry to further test and
develop methods for the fast and effective response to vapour releases and fires. Tests to
date highlight the effectiveness and benefits of rapid gas detection using open path
systems, visual CCTV flame detection and high expansion foam systems, to provide
effective fast vapour dispersion and fire control capabilities necessary in modern LNG
facilities.

All organisations and companies involved throughout the LNG chain of liquefaction,
shipping, re-gasification and gas transportation can experience this unique facility for the
benefit of the LNG community worldwide. To date the facility, expertise, research and
equipment donated have enhanced the understanding of a wide range of design houses,
constructors, project engineers, regulators and operators who have attended and gained
experience of LNG releases, vapour cloud control, LNG ignition and fire control to the
benefit of them personally, their organisations and the whole LNG industry.

BP and TEEX has provided an enduring facility for the whole LNG industry to use
and many further workshops are planned to maintain this momentum and LNG’s safe
reputation.

PS7-1.11