Вы находитесь на странице: 1из 2

System for Live Condition

Check of your Metal Oxide


Surge Arresters (MOSA)

LCM II - A complete system for condition monitoring


of your Metal Oxide Surge Arresters.
«No interruption of service operation»

WORLDWIDE POWER DIAGNOSTICS

www.transinor.no
LCM II Features Continuous Monitoring: LCM II can be
used for continuous monitoring of one or
The new LCM II System features the more arresters to investigate details in
following benefits for handling all your leakage current changes versus time.
surge arrester monitoring needs: Can also be used for continuous
registration in substations of big
• Portable importance to the system operation
• Arrester ID reliability. Available solutions include
• Data Management on-line configurations using modem
communication between LCM II instru-
• Cost Effective ment and PC software.
TECHNICAL
• Continuous Monitoring Dimension:
Instrument:
Portable: Instrument for inspection of LCM II – The Technique WxHxD = 21x13x 30 cm
WxHxD = 8x5x12 in
surge arresters for condition assessment Well-proven and acknowledged monito-
on a regular basis. New LCM II is batte- ring technique using third-order harmo- Weight:
ry operated. nic analysis with compensation. Instrument: 4,9 kg / 10.9 lbs
Field and current probe 1,5 kg / 3.3 lbs
Arrester ID: Unique identification of Rated according IEC 60099-5 as the Complete unit: 11 kg / 24.5 lbs
each surge arrester makes Data best field monitoring technique for Metal
Management easy. LCM II can store Oxide Surge Arresters (MOSA). Environmental:
1000 surge arrester ID’s and measure- Instrument enclosure IP 54.
ments performed in the field. LCM II records operating voltage and
Operating temperature:
temperature during field measurements.
Data Management is secured through Operating -10 to +50 °C
new Windows© LCM II Software hand- The LCM II measurements are automati- 14 to 122 °F
ling all your surge arrester readings. cally normalized to standard ambient Storage -20 to +70 °C
Defines individual surge arrester types temperature (+20°C) and 0.7x rated -4 to 158 °F
including operational parameters. arrester voltage based on recorded tem- Mains voltage:
Software includes e.g. possibility to perature and operating voltage during 12 – 15 VDC or 110 – 230 VAC 50/60 Hz
perform evaluation of groups of surge field measurement. Measurements per- Battery: 9.6V 2,4 Ah
arresters e.g. same type of arresters or formed under different conditions can Capacity: 8 hours use
alternatively for a region. thereby easily be compared. Charging: 1.5 h.
Cost effective: Inspection of a surge
arrester takes less than 10 minutes on Performing Field Measurements
location and can be performed with the
arrester in live operation (no disturbance LCM can only be used for arresters on stored data are transferred from LCM II
of power distribution). insulated base and with a separate earth instrument to PC software. You are now
lead. ready to perform analysis and plan your
next inspection.
Arrester ID is downloaded from PC soft-
ware to LCM II instrument prior to perfor-
ming inspection of surge arresters. LCM
II can store 1000 arrester ID’s. APPLICATION
On location choose correct arrester ID The LCM has been used since 1989
and perform measurement. LCM II can to determine short term as well as long-
store 1000 measurements performed in term measurements on arresters from
the field. 66kV to 765kV networks, and is today
delivered to power companies and utiliti-
After completion of field measurements es in about 50 different countries.

General overview of LCM II condition


monitoring system.

WORLDWIDE POWER DIAGNOSTICS


Phone: +47-73 82 53 50 - Telefax:: +47-73 82 53 79 - www.transinor.no - transinor@transinor.no