COVER SHEET
UPS of 10KVA shall be supplied for
the area as per approved load list
PROJECT:
SCCL COAL BASED THERMAL POWER
PLANT (2X600 MW)
OWNER:
THE SINGARENI COLLIERIES COMPANY
LTD.
PREPARED EMERS OWNER’S
BY: CONSULTANT:
ON NTPC LIMITED
CHECKED RSM (A GOVERNMENT OF INDIA ENTERPRISE)
CONSULTANT WING
BY:
Digitally signed
MBE JOB NO.: Signature Not PVerified
byBP05R SEN
. THIS DOCUMENT IS
PROPERTY OF MBE AND MUST Date: 2015.08.28
NOT BE USED EXCEPT IN 17:35:57 IST
CONNECTION WITH WORK OF GA , BOM, SLD, SIZING CALCULATION
Reason:&CAT
DATA
I NO. OF REV.
MBE. REPRODUCTION, USE OR DOCUMENT TITLE: SHEETS NO.
DISCLOSURE OF THE SHEET OF UPS SYSTEM Location:
– 10KVA
CONTENTS OF THIS NTPCEOC
DOCUMENT TO THIRD
PARTY/IES WITHOUT EXPRESS
/ WRITTEN PERMISSION OF NTPC DOC. NO.: 9661-777-PVI-U-001B 01
MBE IS STRICTLY PROHIBITTED 72
REV. NO.: 01
DATE: 27.07.15
PROJECT- SINGARENI THERMAL POWER PROJECT (2X600MW)
SHEET A
DOCUMENT :
REFERENCE :
PO NO / LOI NO :
DISTRIBUTION :
NTPC : 2SETS OF HARD COPY
NTPC HD ---- 01 SET ( HARD COPY)
APPD
APPD NTPC
Engineering
CHKD
Manager
Model Hipulse D
INPUT
Power Factor > 0.92 (at Input full load & Input nominal voltage)
OUTPUT
Regulation +/-1 %
Air fail Alarm Alarm shall be provided to all important protections. Pls. refer display details enclosed.
Panel Colour RAL 9002 & side covers RAL5012 –Lista blue
Painting
Frame & base Frame RAL 7021
Protection Level Electronic Protection provided for overload & shortcircuit at inverter output.
at no load - -
Guaranteed dimensions of UPS (UPS 1 & 2 + SCVS) W 2100 x D 900 x H 1850 mm
System excluding Battery
Heat for the total system Refer Heat Load enclosed
Engineering Units : Flow : Liquid - M3 / Hr, Steam Kg / Hr, Pressure : Kg / cm2 , Temperatue : Deg C, Level : mm
Overloading capacity and duration 125% for 10min & 150% for 60sec.
No of switches Two
Transfer Time
Type of Charger Constant voltage constant current with automatic float cum boost charging.
Output votlage under float/rapid charging Maximum DC voltage : 141 V
condition Minimum DC voltage : 103.4 V
Output voltage accuracy under specified ±1%
BATTERY CHARGER
input
Charger Output voltage regulation ±1% for mains variation
SUCH 2SETS
SR NO ITEM DESCRIPTION QTY
1 UPS, Hipulse D, 3 X 1, 10 kVA ,Input 415V ,Output 230 V AC, 50 Hz with 02 Nos
2 Parallel kit 01 No
01 No
3 Servo control voltage stabilizer - 10kVA 1PH 230V output
6 MODBUS Protocol 01 No
SUCH 1SETS
SR NO ITEM DESCRIPTION QTY
QTY
SR NO PART NO DESCRIPTION SPECIFICATION (UPS1&2)
1 L3 INPUT REACTOR 3PH INPUT CHOKE 2
PRI:0-280V
4 TM2 OUTPUT X'MER 2
SEC:0-240V/11KVA
5 L2 AC CHOKE 2.5mH/36A DUAL 2
THYRISTOR DIODE MODULE
6 VTD1 TO VTD3 55A/1600V-1800V 6
FOR RECTIFIER BRIDGE
7 VQM5 IGBT FOR BUCK-BOOST 200A / 1200V 2
23 E1-2 FAN FOR RECTIFIER & INV & STSW 4 INCH FAN 230V 4
FOR UPS:-
4 IGBT MITSUBISHI/SEMIKRON
GE/BUSSMAN/
5 POWER FUSE
MERSON (FERRAZ)
ABB/ MERLIN
6 BREAKER(MCCB)
GERIN(SCHNEIDER)/C&S
7 BREAKER (MCB) LEXIC(LEGRAND)/SCHNEIDER
9 AC CAPACITOR EPCOS
10 FAN SUNON/NADI/NISIKI/HICOOL
11 DIGITAL METERS MECO / AE/RISHABH/SOCOMEC
12 ANALOG METERS MECO / AE/RISHABH
13 TRANSDUCERS KANA / ELSTER/SETO/ RISHABH
FINOLEX / POLYCAB / RR/
14 POWER CABLES /IND.GLASS/TONY
CAB./MIRACLE/ROLLIFLEX
15 CHASSIS NP/MONGA/JP
1 SCVS RISHAB
QTY
SR NO PART NO DESCRIPTION MAKE
SHIFT KEY When pressed, you can changeover from group parameters to group
alarms. Also if acknowledge key is pressed followed by shift key, you
get into setting mode. In this mode you can view & alter Date & Time
parameters. To change press shift key, parameters will be selected
then to change setting use UP or DOWN key. To skip press shift key.
DOWN KEY
a) To decrease any value during setting.
b) To see the set of parameters or group which is DOWN in order to
that which is displayed presently.
RTC SETTING With Date & Time parameters on LCD display, Press first acknowledge
key, then shift key to enter in RTC setting mode. Use UP/ DOWN key
change the setting of day, date & time. SHIFT key is used to select
day, date & time.
STORED FAULTS In alarm group, using DOWN key, we can see the stored faults in that
group.To see previous fault press DOWN key & see recent fault stored
press UP key.
7. LOAD ON BATTERY : Flashes incase of Battery low pre-alarm, Battery low trip,
Battery Over-voltage & Battery switch open.
GENERAL GROUP:-
System rating
Date & Time
Time on battery (hrs)
Time on bypass (hrs)
System SR.NO.
d) Bypass
Load on manual byp
a) Input
Input MCCB
Input Single phasing
Input Under/Over voltage
Rectifier Over voltage
Input Fuse Fail
Rectifier Over Temperature
b)Battery
Battery MCCB
Battery Low
Battery over voltage
Battery Charging current limit
c)Output
Output under Voltage
Output over Voltage
Output overload
Output Short Circuit
Inverter Over temperature
D) CONNECTIVITY :-
a. MODBUS
E) OTHERS :-
Inverter Output kW
Inverter Efficiency = Inverter Input kW
Considering Inverter
Efficiency = 92 %
8 KW
Input (DC kW) = 92
= 8.70 KW
Total Rectifier output kW = 8.70 KW+ Charger Input kW
= 4.07 kw
Hence total Rectifier output
kW = 8.70 kw + 4.0701 kw
= 12.77 kW
Considering Rectifier
Efficiency = 94.6 %
Rectifier output kW
Input Power = Rectifier Efficiency
12.77 kw
= 0.946
= 13.49 kw
Considering Input power
1 Factor as 0.92, total input
kVA = 14.66 kva
1. HALL DEVICE BM
2. TEMPERATURE SENSOR BT
3. CAPACITOR C
4. DC-DC CONVERTER CN
5. FAN E
6. FUSE F
7. HEAT SINK HS
8. RELAY KA
9. CONTACTOR KM
10. CHOKE L
11. LINE FILTER LF
12. ISOLATING LINKS LK
13. AMMETER PA
14. PRINTED CIRCUIT BOARD PB
15. VOLTMETER PV
16. BREAKER (MCBs, MCCBs) Q
17. RESISTOR R
18. R. C. NETWORK RC
19. SPACE HEATER RH
20. METAL OXIDE VARISTOR RV
21. SWITCH, ISOLATOR S
22. STATIC SWITCH MODULE STSW
23. CURRENT TRANSFORMER TA
24. POTENTIAL TRANSFORMER TM, TV
25. DIODE VD
26. DIODE-DIODE MODULE VDD
27. IGBT MODULE VQM
28. THYRISTOR-DIODE MODULE VTD
29. THYRISTOR-THYRISTOR MODULE VTT
30. CONNECTOR X
31. TERMINAL BLOCK XM, XD
32. TERMINAL STRIP XS
The UPS shall provide high quality conditioned AC power to the equipment loads. The UPS
shall automatically provide continuity of electrical power, in case of failure of mains (AC utility
source) within the defined limits. The system consists of a solid state Converter with Battery
Charger, PWM Inverter, Automatic static bypass transfer circuit, and integral maintenance
bypass circuit.
APPLICATION AREAS:
Two UPS are connected in parallel redundant configuration. The outputs of two systems are
paralleled paralleling unit to form common ac bus.
In case of failure of one UPS, the entire load is transferred to the other one. Thus both the UPS
should be able to provide 100% load individually.
In case of failure of both the systems (mains-fail & battery-low) the load is automatically
transferred to bypass source via static switch without any interruption.
On rectification of the fault or mains resumption, the load is retransferred. Both UPS are backed
by common battery.
The DC output voltage of Rectifier is fed to buck boost converter and inverter. The Buck Boost
converter operates with two modes,
1) Buck Charger
2) Boost converter
During normal operation i.e. when input power supply is present and it is within the specified
limits, the buck chargers which operate with switching frequency about 5 KHz. provides ripple
free regulated voltage to battery bank using IGBT (VQM5), inductor (L5) and DC capacitor Bank
(C7). The state of the battery is monitored and accordingly float, boost voltage selection is done
automatically along with current limit protection by buck boost converter card. The extended
boost mode facility is provided for initial commissioning of the batteries.
In case of input supply failure or any abnormal condition at input the booster converter is turned
on instantaneously by the buck boost converter card to provide controlled DC voltage to inverter
to get uninterrupted inverter output to the load. The booster converter boosts the battery voltage
using inductor (L5), IGBT (VQM5) and DC capacitors bank (C8). The booster converter
operates with switching frequency
Battery bank is connected at buck boost converter output via Semiconductor Fuse (F4,F4A),
Booster Choke (L5) & Battery Breaker (Q2).
1) Rectifier Operation
The buck boost control card (PB1) takes care of battery operation in addition to rectifier control
operation, card receive control supply 20-0-20V DC from Power Supply Card (PB74). The Three
Phase Synchronization Signal given to Mains feedback Card
When Input Breaker (Q1) is switched on, the time delay circuit starts counting a preset time
interval approx. 10 secs. This is provided for various circuits to stabilize before pulses are
applied to the thyristors.
When timer blocking is released, the rectifier voltage starts rising depending on the error voltage
generated by proportionate integrator comparing DC voltage feedback and set reference
voltage. The reference voltage setting for rectifier is adjusted such that if DC voltage exceeds
600V then only controlled rectifier comes into picture to protect DC capacitor and other circuitry.
1. Mains Fail
2. Over temperature
3. Input UV/OV
4. Charger OV
5. Input single phasing
6. Input Fuse fail
7. Rectifier OV
8. Heat sink over temperature
If transient fluctuation in input grid voltage exceeds + 10% for maximum period of one minute
then rectifier will gets block and inverter will be fed by Battery.
1. Mains Fail
2. Over Temperature
3. Input UV/OV
4. Charger OV
5. Input Single phasing
In case of any abnormal condition at input like UV/OV, etc. DC Voltage on DC bus is monitored
& if it falls below 410V DC immediately booster converter is turned ON. Buck charger output
feedback voltage is also sensed with high precision resistor divided to prevent any high voltage
being applied to battery bank in case of charger converter device failure. Adequate precaution is
taken to ensure highest reliabilities of this device.
Depending upon the state of the battery which is sensed by Battery current feedback from CT
(TA1) the buck charger selects float / boost mode of charging for batteries (Float to boost mode
selected at @ 70% of battery current limit.
The Mains feedback card (PB82) senses mains voltage, regulated DC voltage of Rectifier,
Battery Voltage, Booster Current using Current transformer (TA2). Under input abnormal
condition i.e. mains fail, input uv/ov, input spp, etc. or if DC bus voltage falls below 410V the
booster converter is turned on. The Current mode PWM based 3842 IC provides PWM signals
to driver card (PB2) which in turn provides amplified gate-emitter signals to booster IGBT
(VQM5). The booster voltage is controlled by sensing DC voltage on DC Bus. The booster
current limit protection is provided by sensing booster current through Current Transformer
(TA2). The booster converter is blocked under following conditions.
•Rectifier OV / Booster OV
•Battery Low
•Heat Sink Over temperature
When mains fails or DC voltage goes below 410V, Booster starts & DC voltage is maintained at
430V. When mains resumes again at 470V DC, Booster is blocked & charger comes up When
charger trips by DC OV, even if mains fails Booster comes up without affecting load at the
output.
DC bus voltage i.e. output of Boost converter feedback and monitoring signal are sensed with
high precision resistor divider separately & redundancy is ensured for safety of DC Capacitors.
RECT.OV setting is done at 700V DC and booster OV is set at 750V DC. If rectifier & Booster
voltage exceeds beyond this limit Booster converter gets blocked due to over voltage .Possibility
of booster OV is a remote condition. This OV is provided for safety of DC capacitor & devices
used in Inv. Bridge.
Battery low setting is done . Below this voltage Boost converter is blocked to avoid battery
discharging.
Nominal heat sink temp. of buck-boost is set at <65 degree Cel. while OT setting is done at 90
degree C. If temperature exceeds beyond this limit, Booster converter gets block due to over
temperature .Possibility of over temperature is a remote condition
In modulator section the error signal (sine wave) generated by control amplifier section is
compared with carrier wave (Triangular waveform) and its inter sections results into PWM
pulses which are given to Driver Card. 28V DC Control supply is given to Driver Converter Card
(PB8) which gives isolated supply to driver card. Driver card (PB18-PB18A) receives PWM
signals from Inverter Control Card which are amplified and given to IGBT of Inverters.
Transfer and re-transfer operation is controlled by sensing output voltage and its
synchronization with bypass source. This card generates block/de-block signal for Static Switch
provides in Inverter path (VTT1) and in bypass path (VTT2). Gate / Cathode firing signals are
given to STSW’s by Static Switch Control Card (PB24,24A).
Electronic Static Switch
Static switches are provided in Inverter (VTT1) and in bypass path (VTT2). The static switch in
bypass line provides an alternative power during overload or UPS fault condition.
Transfer: If the internal control system detects a fault in the UPS module while it is supporting
the load, the load will transferred to bypass static switch. If the transfer takes place in sync.
Condition transfer time will be less than 5 ms whereas in no sync. Mode it is less than 20 ms.
Retransfer: Retransfer of load (Bypass to Inverter) is automatic operation if the UPS is healthy
and synchronized with the bypass.
Manual transfer/retransfer: Test transfer switch (S4) enables the load change over from
Inverter to Bypass & Retransfer load (Bypass to Inverter) only when the UPS is healthy and
synchronized with the bypass.
Maintenance bypass MCCB enables the load change over from Inverter / static bypass to
maintenance bypass. To achieve no break change over defined sequence of operation has to
be followed.
Operation of manual bypass input MCCB and inverter output MCCB provides total UPS system
free for maintenance. To achieve no break change over following sequence shall be followed.
1) Load transfer from Inverter to static bypass with test transfer switch (S4)
2) Switch ‘ON’ maintenance bypass MCCB
3) Switch ‘OFF’ inverter output MCCB
Data monitoring system is operated through data logger card (PB9). Data logger card comprises
of following sections.
1) Analog Measurement section
2) Control section to provide blocking signal to inverter control card
3) Fault detection and display
4) Computer Interfacing
For analog measurement section feedbacks are derived from inverter control card (PB7).
Such as
a) DC Voltage Feedback
b) Battery Voltage Feedback
c) Inverter Output Voltage Feedback
d) Inverter Output Current Feedback
e) Battery Current Feedback
f) Heat Sink Temperature Feedback
g) Bypass Voltage Feedback
Such as
a) Fuse Fail Card (PB35 )
b) Buck Boost Converter Card (PB1)
Some faults are generated internally through Data Logger card by sensing various feedbacks
received.
Such as
a) Output Under voltage
b) Output Over voltage
c) Output Overload
d) Over temperature
RS 232,RS485 serial interface is provided for computer interface, through PC interface card
(PB10,PB151)
Control supply for all PCBs and other circuitry is generated from regulated DC power supply
using DC-DC Converters (CN1). DC voltage is applied to DC-DC Converters via fuses. The
mains is fed to CN1 through Isolation Transformer (TV4) so that +28V control supply is available
to UPS control circuitry as soon as mains is available.
= 10 X 0.8 X 1000
90 X 1.1 X 0.92
= 87.83 Amp.
2
c c
3 -
·~~
!=l<...l
D
D
...lP..;$
~~~
.... ~~ r- -
~~B 4 PVC TERMINAL COVER 42 REFER DRG No. T15G255-I-O FOR GENERAL ARRANGEMENT DRG.
ll~~
~~6 3 50 Sq FLEXIBLE COPPER CONNECTOR (350 mm L) 02 2015 Date Initial
The broadest Ownership (TCO), only AMCO Saft Ni-Cd batteries provide a truly
reliable solution.
capability in For installations requiring totally reliable power back-up, failsafe
the world engine starting or bulk energy storage, the uniquely long life and
low maintenance characteristics of AMCO Saft Ni-Cd batteries
cannot be surpassed.
2
KPL, KPM, KPH
Wide range – main benefits
Performance in temperature extremes
Nickel-cadmium plates are completely reliable, with no risk of thermal runaway
or sudden death. Generally operating between temperatures of – 20°C to
+ 50°C, they can tolerate extremes of – 50°C to + 70°C for short periods.
Assured reliability
Ni-Cd is reliable in controlled city environments or harsh, unpredictable
conditions in the world’s most remote and unattended areas.
The Ni-Cd battery’s construction makes it highly resistant to electrical abuse and
transport over rough terrain, precluding risk of subsequent failure.
3
AMCO Saft KPL, KPM, KPH offer different performance characteristics and cover a
Ni-Cd batteries wide capacity range, enabling selection of an AMCO Saft Ni-Cd battery
for any application.
all kinds of KPL has the thickest plates and is designed for applications where the battery is
required to provide:
industry l
l
a reliable source of energy over long discharge periods
a current that is relatively low in comparison with the total stored energy
l discharges are generally infrequent
KPL is typically used in power back-up and bulk energy storage applications.
KPM
KPM is designed for applications where the batteries are usually required to
sustain:
l electrical loads between 30 minutes and 3 hours
l “mixed” loads which involve high and low discharge rates
l frequent or infrequent discharges
KPM type is typically used in power back-up applications.
KPH
KPH uses very thin plates and is designed for applications demanding:
l a relatively high current over short periods
l usually less than 1 hour duration
l frequent or infrequent discharges
KPH type is typically used in starting and power back-up applications.
Power back-up
KPL
Bulk energy storage • • • • • •
KPM Power back-up • • • • • • • •
Starting
KPH
Power back-up • • • • • • •
100 50
hours hours 10
hours
3
hours
KPL
1.00 V 1
hour
KPM
1.05 V 30
min
1.10 V
KPH 10
min
1
1.14 V sec
4
Calculating your battery size KPL/KPM/KPH
It is important to define the optimum battery size for your particular
installation. Nickel-cadmium ranges offer many capacity steps to create
batteries
the optimum battery for your application. AMCO Saft’s battery sizing
software has been developed to make your battery selection easy. Our
sales engineers have been specifically trained to fine-tune sizing of the
batteries according to your specific conditions.
End lug
150
Cable between
steps/rows,
100
Amperes
inside-inside
50 Cable between
steps/rows,
outside-outside
0
0 27 54 81 108 135
Minutes
2. Separator
AMCO Saft engineered grid ensures separation between electrodes of opposite
polarity.
6
3. Electrolyte
The electrolyte used in KPL, KPM and KPH cells is aqueous solution of
potassium hydroxide and lithium hydroxide and acts only as an ion transfer
4
medium, delivering optimum performance without causing base material
degradation. It is not necessary to change the electrolyte during the life of
the cell. For extremely low temperatures a special high density electrolyte is
available.
4. Terminals 1 3
5
Easy to bolt nickel-plated terminals made of steel are provided for both polarities.
5. Cell containers 2
AMCO Saft cells are available in polypropylene or stainless steel containers.
The polypropylene container can withstand high mechanical stresses, shocks,
vibrations and extreme temperatures. It has excellent electrical insulation, is
corrosion resistant and permits visible check of electrolyte level for ease of
maintenance.
6. Venting system
The battery is fitted with a specially designed flame arresting flip top vent and
does not produce corrosive vapours. This vent allows easy topping up operation
when needed.
5
KPL/KPM/KPH Nominal voltage: 1.2 V/cell rated (nominal) capacity
batteries Rated Capacity C5 (as per IEC 60623) is defined as available ampere-hours (Ah)
at 5 hours discharge rate to an end voltage of 1.0 V/cell at ambient temperature
Technical
+ 20°C.
Charging characteristics
Batteries can be charged in:
l constant voltage mode with load connected
or
l constant current or declining current mode when load is isolated.
6
Performance Data KPL/KPM/KPH
Rated discharge performance of cells are at + 20°C ± 2°C temperature for
different durations and end cell voltages as given in performance data sheets.
batteries
The rated capacity “C5” is a baseline performance measure. Use the discharge
performance tables to select a proper battery for your specific application. Performance
State of charge diagrams Data
Time required to attain state of charge using constant voltage charging with
Current limited to C5 rate for a fully discharged cell.
KPL
1.75
1.70
90% Charged
1.55
85% Charged
1.50
80% Charged
1.45
75% Charged
1.40
1 10 100 1000
Hours
KPM
1.75
1.70
1.65
Volts per cell
Fully Charged
1.60
1.50
75 90% Charged
1.45 % 80%
Ch Cha
ar rged 85% Charged
ge
d
1.40
1 10 100 1000
Hours
KPH
1.75
1.70
1.65
Volts per cell
1.55
75 80 85 90% Charged
1.45 % % %
Ch
Ch Ch arg
arg arg ed
ed ed
1.40
1 10 100 1000
Hours
7
AMCO Saft L Range
Ni-Cd batteries
Physical and Cell Type C5 Ah
Cell Dimension
L W H
Approx Cell Wt Electrolyte
Volume
Terminals
performance
(KG)
(mm) (mm) (mm) (Litres)
KPL11P 11 1.6 0.7
KPL18P 18 46 87 272 1.8 0.6 M10
data KPL25P
KPL32P
25
32
2
2.8
0.5
1.1
KPL39P 39 3.1 1
KPL45P 45 86 87 272 3.4 0.9 M10
KPL52P 52 3.6 0.8
KPL58P 58 3.7 0.8
KPL69P 69 5 1.9
KPL75P 75 5.2 1.8
KPL80P 80 5.3 1.7
58 139 401 M20
KPL88P 88 5.4 1.6
KPL94P 94 5.5 1.6
KPL100P 100 5.7 1.5
KPL115P 115 6.2 1.9
KPL125P 125 6.4 1.8
75 139 401 M20
KPL135P 135 6.5 1.7
KPL145P 145 6.6 1.6
KPL155P 155 9.4 3.7
KPL165P 165 9.6 3.6
KPL177P 177 9.8 3.5
KPL191P 191 103 165 401 10 3.3 M20
KPL205P 205 10.1 3.2
KPL216P 216 10.2 3.1
KPL230P 230 10.4 3
KPL240P 240 14.1 4.2
KPL256P 256 14.3 4.1
KPL265P 265 14.5 4
128 165 401 2XM20
KPL282P 282 14.7 3.9
KPL290P 290 15 3.8
KPL310P 310 15.3 3.6
KPL335P 335 16.8 4.8
KPL365P 365 156 165 401 17 4.6 2XM20
KPL390P 390 17.2 4.4
KPL400P 400 21.6 6
KPL425P 425 21.8 6
KPL445P 445 22 5.8
KPL457P 457 176 195 405 22.4 5.8 2XM10
KPL485P 485 22.6 5.7
KPL500P 500 22.8 5.6
KPL515P 515 23 5.6
KPL540P 540 31.2 9.3
KPL575P 575 31.5 9.3
KPL595P 595 32.4 9
KPL635P 635 32.7 9
261 195 405 3XM10
KPL670P 670 33 8.7
KPL685P 685 33.6 8.7
KPL730P 730 33.9 8.4
KPL775P 775 34.5 8.4
KPL800P 800 43.2 12
KPL850P 850 43.6 12
KPL895P 895 44 11.6
345 195 405 4XM10
KPL915P 915 44.8 11.6
KPL970P 970 45.2 11.2
KPL1030P 1030 46 11.2
KPL1060P 1060 54.5 15
KPL1120P 1120 55 14.5
KPL1145P 1145 430 195 405 56 14.5 5XM10
KPL1220P 1220 56.5 14
KPL1285P 1285 57.5 14
KPL1350P 1350 66 17.4
KPL1370P 1370 67.2 17.4
515 195 405 6XM10
KPL1460P 1460 67.8 16.8
KPL1550P 1550 69 16.8
8
L Range
Performance for fully charged cells
Available Amperes at + 20°C Final voltage: 1.00 V/cell
9
L Range
Performance for fully charged cells
Available Amperes at + 20°C Final voltage: 1.05 V/cell
10
L Range
Performance for fully charged cells
Available Amperes at + 20°C Final voltage: 1.10 V/cell
11
L Range
Performance for fully charged cells
Available Amperes at + 20°C Final voltage: 1.14 V/cell
12
M Range AMCO Saft
Ni-Cd batteries
Cell Type C5 Ah
Cell Dimension
L W H
Approx Cell Wt Electrolyte
Volume
Terminals Physical and
performance
(KG)
(mm) (mm) (mm) (Litres)
KPM10P 10 1.5 0.7
data
KPM16P 16 46 87 272 1.7 0.6 M10
KPM20P 20 1.8 0.5
KPM25P 25 2.8 1.2
KPM32P 32 3 1.1
86 87 272 M10
KPM39P 39 3.1 1.1
KPM45P 45 3.3 1
KPM55P 55 4.6 1.7
KPM62P 62 4.9 1.6
58 139 401 M20
KPM74P 74 5.3 1.5
KPM80P 80 5.5 1.4
KPM90P 90 6.6 1.9
KPM95P 95 6.8 1.8
75 139 401 M20
KPM105P 105 7 1.7
KPM112P 112 7.2 1.6
KPM128P 128 9.6 3.7
KPM137P 137 9.8 3.6
KPM150P 150 10 3.5
KPM158P 158 10.2 3.4
103 165 401 M20
KPM167P 167 10.4 3.3
KPM180P 180 10.6 3.2
KPM188P 188 10.8 3.1
KPM200P 200 11 3
KPM220P 220 14.1 4.2
KPM240P 240 128 165 401 14.5 4 2XM20
KPM260P 260 14.9 3.8
KPM280P 280 17 5
KPM300P 300 156 165 401 17.4 4.8 2XM20
KPM323P 323 17.8 4.6
KPM350P 350 21.3 6.2
KPM376P 376 21.8 6.1
KPM400P 400 176 195 405 22.3 6 2XM10
KPM425P 425 22.8 5.9
KPM455P 455 23.3 5.8
KPM490P 490 31.4 9.6
KPM520P 520 32 9.4
KPM565P 565 32.8 9.2
261 195 405 3XM10
KPM600P 600 33.5 9
KPM635P 635 34.2 8.9
KPM680P 680 35 8.7
KPM700P 700 42.6 12.5
KPM750P 750 43.7 12.3
KPM800P 800 345 195 405 44.6 12 4XM10
KPM850P 850 45.6 11.8
KPM900P 900 46.6 11.6
KPM945P 945 54.6 15.3
KPM1000P 1000 55.8 15
430 195 405 5XM10
KPM1060P 1060 57 14.8
KPM1130P 1130 58.3 14.5
KPM1200P 1200 67 18
KPM1285P 1285 515 195 405 68.4 17.8 6XM10
KPM1365P 1365 70 17.4
13
M Range
Performance for fully charged cells
Available Amperes at + 20°C Final voltage: 1.00 V/cell
14
M Range
Performance for fully charged cells
Available Amperes at + 20°C Final voltage: 1.05 V/cell
15
M Range
Performance for fully charged cells
Available Amperes at + 20°C Final voltage: 1.10 V/cell
16
M Range
Performance for fully charged cells
Available Amperes at + 20°C Final voltage: 1.14 V/cell
17
AMCO Saft H Range
Ni-Cd batteries
Physical and Cell Type C5 Ah
Cell Dimension
L W H
Approx Cell Wt Electrolyte
Volume
Terminals
performance
(KG)
(mm) (mm) (mm) (Litres)
KPH 8 P 8 1.4 0.7
KPH 11 P 11 1.6 0.6
data KPH 15 P
KPH 19 P
15
19
47 87 272 1.8
2
0.6
0.5
M10
18
H Range
Performance for fully charged cells. Available Amperes at + 20°C
Final voltage: 0.65 V/cell Final voltage: 0.85 V/cell
Seconds Seconds
Cell Type C5 Ah Cell Type C5 Ah
90 60 30 10 5 1 90 60 30 10 5 1
KPH 8 P 8 74.4 82.3 87.4 105 116 125 KPH 8 P 8 56.7 62.0 69.3 78.6 85.4 92.9
KPH 11 P 11 102 113 120 145 159 172 KPH 11 P 11 77.9 85.2 95.3 108 117 128
KPH 15 P 15 140 154 164 198 217 234 KPH 15 P 15 106 116 130 147 160 174
KPH 19 P 19 177 195 208 250 275 297 KPH 19 P 19 135 147 165 187 203 221
KPH 22 P 22 205 226 240 290 318 344 KPH 22 P 22 156 170 191 216 235 255
KPH 26 P 26 242 267 284 343 376 406 KPH 26 P 26 184 201 225 255 278 302
KPH 30 P 30 279 309 328 395 434 469 KPH 30 P 30 212 232 260 295 320 348
KPH 35 P 35 326 360 382 461 506 547 KPH 35 P 35 248 271 303 344 374 406
KPH 38 P 38 354 391 415 501 549 594 KPH 38 P 38 269 294 329 373 406 441
KPH 42 P 42 391 432 459 554 607 656 KPH 42 P 42 297 325 364 413 448 488
KPH 46 P 46 428 473 503 606 665 719 KPH 46 P 46 326 356 399 452 491 534
KPH 50 P 50 465 514 546 659 723 781 KPH 50 P 50 354 387 433 491 534 581
KPH 58 P 58 540 597 634 764 838 906 KPH 58 P 58 411 449 503 570 619 673
KPH 65 P 65 605 669 710 857 939 1016 KPH 65 P 65 460 504 563 639 694 755
KPH 75 P 75 698 771 820 988 1084 1172 KPH 75 P 75 531 581 650 737 801 871
KPH 85 P 85 791 874 929 1120 1228 1328 KPH 85 P 85 602 659 736 835 907 987
KPH 94 P 94 875 967 1027 1239 1358 1469 KPH 94 P 94 666 728 814 924 1004 1091
KPH 100 P 100 930 1028 1093 1318 1445 1563 KPH 100 P 100 708 775 866 983 1068 1161
KPH 111 P 111 1033 1142 1213 1463 1604 1734 KPH 111 P 111 786 860 962 1091 1185 1289
KPH 120 P 120 1116 1234 1311 1582 1734 1875 KPH 120 P 120 850 930 1040 1179 1281 1393
KPH 130 P 130 1209 1337 1421 1713 1879 2031 KPH 130 P 130 921 1007 1126 1277 1388 1509
KPH 140 P 140 1303 1440 1530 1845 2023 2188 KPH 140 P 140 991 1085 1213 1376 1495 1626
KPH 148 P 148 1377 1522 1617 1951 2139 2313 KPH 148 P 148 1048 1147 1282 1454 1580 1718
KPH 160 P 160 1489 1646 1749 2109 2312 2500 KPH 160 P 160 1133 1240 1386 1572 1708 1858
KPH 170 P 170 1582 1748 1858 2240 2457 2656 KPH 170 P 170 1204 1317 1473 1670 1815 1974
KPH 180 P 180 1675 1851 1967 2372 2601 2813 KPH 180 P 180 1275 1395 1560 1769 1922 2090
KPH 190 P 190 1768 1954 2076 2504 2746 2969 KPH 190 P 190 1346 1472 1646 1867 2028 2206
KPH 200 P 200 1861 2057 2186 2636 2890 3125 KPH 200 P 200 1416 1550 1733 1965 2135 2322
KPH 213 P 213 1982 2191 2328 2807 3078 3328 KPH 213 P 213 1508 1650 1846 2093 2274 2473
KPH 225 P 225 2093 2314 2459 2965 3251 3516 KPH 225 P 225 1593 1743 1950 2211 2402 2613
KPH 235 P 235 2186 2417 2568 3097 3396 3672 KPH 235 P 235 1664 1821 2036 2309 2509 2729
KPH 245 P 245 2279 2520 2677 3229 3540 3828 KPH 245 P 245 1735 1898 2123 2407 2616 2845
KPH 265 P 265 2465 2725 2896 3492 3829 4141 KPH 265 P 265 1877 2053 2296 2604 2829 3077
KPH 275 P 275 2558 2828 3005 3624 3974 4297 KPH 275 P 275 1948 2131 2383 2702 2936 3193
KPH 290 P 290 2698 2983 3169 3822 4191 4531 KPH 290 P 290 2054 2247 2513 2850 3096 3367
KPH 300 P 300 2791 3085 3279 3954 4335 4688 KPH 300 P 300 2125 2325 2599 2948 3203 3483
KPH 315 P 315 2931 3240 3442 4151 4552 4922 KPH 315 P 315 2231 2441 2729 3095 3363 3658
KPH 330 P 330 3070 3394 3606 4349 4769 5156 KPH 330 P 330 2337 2557 2859 3243 3523 3832
KPH 353 P 353 3284 3630 3858 4652 5101 5516 KPH 353 P 353 2500 2735 3059 3469 3769 4099
KPH 375 P 375 3489 3857 4098 4942 5419 5859 KPH 375 P 375 2656 2906 3249 3685 4004 4354
KPH 390 P 390 3628 4011 4262 5140 5636 6094 KPH 390 P 390 2762 3022 3379 3832 4164 4528
KPH 410 P 410 3814 4217 4481 5403 5925 6406 KPH 410 P 410 2904 3177 3552 4029 4377 4761
KPH 430 P 430 4001 4422 4699 5667 6214 6719 KPH 430 P 430 3045 3332 3726 4225 4591 4993
KPH 450 P 450 4187 4628 4918 5931 6503 7031 KPH 450 P 450 3187 3487 3899 4422 4804 5225
KPH 471 P 471 4382 4844 5147 6207 6806 7359 KPH 471 P 471 3336 3650 4081 4628 5028 5469
KPH 491 P 491 4568 5050 5366 6471 7095 7672 KPH 491 P 491 3477 3805 4254 4825 5242 5701
KPH 520 P 520 4838 5348 5683 6853 7514 8125 KPH 520 P 520 3683 4029 4506 5110 5552 6038
KPH 530 P 530 4931 5451 5792 6985 7659 8281 KPH 530 P 530 3753 4107 4592 5208 5658 6154
KPH 540 P 540 5024 5554 5901 7117 7803 8438 KPH 540 P 540 3824 4184 4679 5306 5765 6270
KPH 575 P 575 5350 5914 6284 7578 8309 8984 KPH 575 P 575 4072 4456 4982 5650 6139 6677
KPH 590 P 590 5489 6068 6448 7776 8526 9219 KPH 590 P 590 4178 4572 5112 5797 6299 6851
KPH 600 P 600 5582 6171 6557 7908 8671 9375 KPH 600 P 600 4249 4649 5199 5896 6406 6967
KPH 615 P 615 5722 6325 6721 8105 8887 9609 KPH 615 P 615 4355 4766 5329 6043 6566 7141
KPH 630 P 630 5861 6479 6885 8303 9104 9844 KPH 630 P 630 4462 4882 5459 6190 6726 7315
KPH 640 P 640 5954 6582 6994 8435 9249 10000 KPH 640 P 640 4532 4959 5545 6289 6833 7431
KPH 656 P 656 6103 6747 7169 8646 9480 10250 KPH 656 P 656 4646 5083 5684 6446 7004 7617
KPH 670 P 670 6233 6891 7322 8830 9682 10469 KPH 670 P 670 4745 5192 5805 6583 7153 7780
KPH 680 P 680 6326 6994 7431 8962 9827 10625 KPH 680 P 680 4816 5269 5892 6682 7260 7896
KPH 691 P 691 6429 7107 7551 9107 9986 10797 KPH 691 P 691 4894 5354 5987 6790 7377 8023
KPH 715 P 715 6652 7354 7814 9423 10332 11172 KPH 715 P 715 5064 5540 6195 7026 7634 8302
KPH 725 P 725 6745 7456 7923 9555 10477 11328 KPH 725 P 725 5134 5618 6282 7124 7740 8418
KPH 755 P 755 7024 7765 8251 9950 10910 11797 KPH 755 P 755 5347 5850 6542 7419 8060 8767
KPH 800 P 800 7443 8228 8743 10543 11561 12500 KPH 800 P 800 5665 6199 6932 7861 8541 9289
KPH 825 P 825 7675 8485 9016 10873 11922 12891 KPH 825 P 825 5843 6393 7148 8107 8808 9579
KPH 840 P 840 7815 8639 9180 11071 12139 13125 KPH 840 P 840 5949 6509 7278 8254 8968 9754
KPH 865 P 865 8048 8896 9453 11400 12500 13516 KPH 865 P 865 6126 6703 7495 8500 9235 10044
KPH 885 P 885 8234 9102 9672 11664 12789 13828 KPH 885 P 885 6267 6858 7668 8696 9448 10276
KPH 910 P 910 8466 9359 9945 11993 13150 14219 KPH 910 P 910 6444 7051 7885 8942 9715 10566
KPH 927 P 927 8624 9534 10131 12217 13396 14484 KPH 927 P 927 6565 7183 8032 9109 9897 10764
KPH 950 P 950 8838 9770 10382 12520 13728 14844 KPH 950 P 950 6728 7361 8231 9335 10142 11031
KPH 990 P 990 9211 10182 10819 13047 14306 15469 KPH 990 P 990 7011 7671 8578 9728 10569 11495
KPH 1012 P 1012 9415 10408 11059 13337 14624 15813 KPH 1012 P 1012 7167 7842 8768 9944 10804 11751
19
H Range
Performance for fully charged cells
Available Amperes at + 20°C Final voltage: 1.00 V/cell
20
H Range
Performance for fully charged cells
Available Amperes at + 20°C Final voltage: 1.05 V/cell
21
H Range
Performance for fully charged cells
Available Amperes at + 20°C Final voltage: 1.10 V/cell
22
H Range
Performance for fully charged cells
Available Amperes at + 20°C Final voltage: 1.14 V/cell
23
Head Office
AMCO Saft India Ltd.
Plot No 10/1A,1B & 1 C, Abbanakuppe,
Bidadi Industrial Area,
Bangalore, Karnataka, India 562 109
Tel : +91 80 2730 7165 / 7166
Fax : +91 80 2728 7716
E-mail: contact@amcosaft.com
Regional Offices
Delhi Branch
AMCO Saft India Ltd.
1202,12th Floor,
6, Devika Towers,
Nehru Place,
New Delhi - 110019
Tel : +91 11 4063 8644
Fax : +91 11 4063 8644
E-mail: contact@amcosaft.com
Mumbai Branch
AMCO Saft India Ltd.
No 124-125, 1st Floor, Plot No 75,
Vardhaman Market,
Sector 17, Vashi,
Navi Mumbai - 400703
Tel : +91 22 2780 2568
E-mail: mumbai@amcosaft.com
Kolkata
Tel : +91 98 3153 0967
E-mail: kolkata@amcosaft.com
Web site: http://www.amcosaft.com
21832-2-1114
TO McNally Bharat Engineering Co. Ltd. FROM Emerson Network Power (Pune) Private Limited
PROJ. NAME SINGARENI THERMAL POWER PROJECT SUBJECT COMPLIANCE 1
Refer. COMMENTS DTD 27.07.15 Date 03.08.15