type - ordering serial-

EN 1. General information input designation code number 4. Electrical Installation maximum supply: 6.5 Description of hysteresis and compare mode
The maximum supply of the plug-on display (VS max) is 36 V.
1.1 Information on the operating manual WARNING! Install the device only when currentless! To invert the respective modes, you have to exchange the
As the connected transmitter is also supplied by the plug-on
values for the switch-on and switch-off points.
This operating manual contains important information on The supply must correspond to the safety class II display, the maximum supply does not only depend on the
proper usage of the device. Read this operating manual (protective insulation)! supply of the PA 430. If the maximum supply of the transmit-
carefully before installing and starting up the pressure ter is lower than 36 V, the maximum supply of the total
Operating Manual The transmitter shall be supplied by Limited Energy appliance may not exceed the transmitter’s value. The
measuring device.
Source (per UL 61010) or NEC Class 2 Power Source! following formulas are valid:
Adhere to the safety notes and operating instructions which Establish the electrical connection of the device according to
are given in the operating manual. Additionally applicable the technical data shown on the manufacturing label and the if VTR max ≥ 36 V: VS max = 36 V
regulations regarding occupational safety, accident preven- pin configuration and the respective wiring diagram below. if VTR max < 36 V: VS max = VTR max
Plug-On Display PA 430 tion as well as national installation standards and engineer- output connector pinout
ing rules must be complied with! 4.1 Pin configuration VTR max = maximum supply of the used 3-wire transmitter
This operating manual is part of the device, must be kept Electrical connections
Fig. 1 manufacturing label 5. Initial start-up
nearest its location, always accessible to all employees. M12x1 Binder Binder
Fig. 4 compare mode Fig. 5 compare mode
This operating manual is copyrighted. The contents of this ! The manufacturing label must not be removed from the ISO 4400 (5-pin),
metal
723
(5-pin)
723
(7-pin) 1
WARNING! Before start-up, the user has to check for
inverted
operating manual reflect the version available at the time of device! proper installation and for any visible defects.
printing. It has been issued to our best knowledge. However, Supply + 1 1 3 3
Supply – 2 2 4 1 WARNING! The device can be started and operated by
errors may have occurred. BD SENSORS is not liable for any 3. Mechanical installation 2 2 1 authorized personnel only, who have read and under-
incorrect statements and their effects. 3-wire: Signal + 3 3 5 -
2 stood the operating manual!
3.1 Mounting and safety instructions Contact 1 3 5 2 -
2 1
– Technical modifications reserved – Contact 2 - 3 1 - WARNING! The device has to be used within the
WARNING! Install the device only when currentless! ground ground technical specifications, only (compare the data in the
1.2 Symbols used Shield 4 2
contact contact data sheet)!
WARNING! This device may only be installed by 1
DANGER! – dangerous situation, which may result in qualified technical personnel who has read and under- intended for usage with DMP 331i, DMP 333i and LMP 331i
death or serious injuries stood the operating manual! with el. connection Binder series 723 (7-pin); pins 4, 5, 6, 7 are 6. Operation
wired through 1:1
WARNING! – potentially dangerous situation, which ! Handle this high-sensitive electronic precision 2
pin configuration according to version 6.1 Operating and display elements
may result in death or serious injuries measuring device with care, both in packed and Fig. 6 hysteresis mode Fig. 7 hysteresis mode
unpacked condition! 4.2 Wiring diagrams LED unit LED inverted
CAUTION! – potentially dangerous situation, which may contact 1 contact 2
result in minor injuries ! There are no modifications/changes to be made on the 2-wire-system (current)
! CAUTION! – potentially dangerous situation, which may device. Supply +
www.bdsensors.com result in physical damage ! Do not throw the package/device! VS min 4-digit seven-

Transmitter
VS min+ 6 V

PA 430
NOTE – tips and information to ensure a failure-free
operation ! Remove packaging only directly before starting up the segment display
Supply –
Headquarters Eastern Europe device to avoid any damage! RL
1.3 Target group
BD SENSORS GmbH BD SENSORS s.r.o. ! Do not use any force when installing the device to pre- Contact 1 RL
BD-Sensors-Str. 1 Hradištská 817 vent damage of the device and the transmitter! Contact 2
WARNING! To avoid operator hazards and damages of ▼-button ▲-button
D - 95199 Thierstein CZ - 687 08 Buchlovice
Germany Czech Republic
the device, the following instructions have to be worked ! The display and the plastic housing are equipped with VS min: minimum supply of the used 2-wire transmitter
out by qualified technical personnel. rotational limiters. Please do only rotate the display or Fig. 3 touchpad for device with two contacts
Tel.: +49 (0) 9235-9811-0 Tel.: +42 (0) 572-4110 11
Fax: +49 (0) 9235-9811-11 Fax: +42 (0) 572-4114 97 the housing within the limit. 3-wire-system (voltage) The device has, according to the order max. 2 LEDs which
1.4 Limitation of liability
3.2 General installation steps Supply +
are allocated to the resp. contacts. The LEDs will light up
By non-observance of the operating manual, inappropriate when the respective set point has been reached and the
Russia China - Carefully remove the pressure measuring device from VTR
use, modification or damage, no liability is assumed and VS contact is active. The display of the measured value as well

Transmitter
BD SENSORS RUS BD SENSORS China Co, Ltd. warranty claims will be excluded. the package and dispose of the package properly. as the configuration of the individual parameters occurs

PA 430
Supply –
39a, Varshavskoe shosse Room B, 2nd Floor, Building 10, - Remove the cable socket or mating plug from the menu-driven via the seven-segment display.
RU - Moscow 117105 No. 1188 Lianhang Rd. 1.5 Intended use RL
transmitter. Signal +
201112 Shanghai, RL 6.2 Configuration
Russia China - The plug-on display PA 430 has been designed to equip Contact 1
3.3 Installation steps for Binder and M12x1
Tel.: +7 (0) 95-380 1683 Tel.: +86 (0) 21-51600 190 transmitters with analogue output 4 … 20 mA / 2-wire or The menu system is a closed system allowing you to scroll
Contact 2
Fax: +7 (0) 95-380 1681 Fax: +86 (0) 21-33600 613 0 … 10 V / 3-wire (pressure, temperature etc.) with a - Plug the display onto the transmitter. both forward and backward through the individual set-up
digital display. Additional up to 2 PNP open collector - Plug the cable socket or mating plug onto the transmit- menus to navigate to the desired setting item. All settings are
contacts for a limiting value control can be offered. The VTR: supply of the used 3-wire transmitter
further agencies in: ter and fasten it properly. permanently stored in an EEPROM and therefore available

EUROPE ASIA
plug-on display has to be installed between male and
female plug and is ready for work immediately. A pre-
! For devices with cable socket, you have to make sure again even after disconnecting from the supply voltage. The
3.4 Installation steps for ISO 4400 that the external diameter of the used cable is within the structure of the menu system is the same for all types of
• Belgium • Romania • India ferred area of use is e.g. on-site process monitoring. devices, regardless of the number of contacts. However,
- Plug the display onto the transmitter. Take care that the allowed clamping range. Moreover you have to ensure
• Denmark • Sweden • Iran - It is the operator's responsibility to check and verify the pre-mounted seal on the bottom fits correctly. that it lies in the cable gland firmly and cleftlessly! they only differ by the number of menus. Following figure and
• Finland • Switzerland • Israel suitability of the device for the intended application. If the menu list shows all possible menus.
• France • Slovakia • Japan any doubts remain, please contact our sales department - Remove the fastening screw from the cable socket. ! Please note that the cable socket or mating plug has to Please follow the manual meticulously and remember
• Great Britain • Spain • Kazakhstan in order to ensure proper usage. BD SENSORS is not be mounted properly to ensure the ingress protection that changes of the adjustable parameters (switch-on
- Replace the pre-assembled profile seal of the cable
• Greece • Turkey • Malaysia liable for any incorrect selections and their effects! mentioned in the data sheet. point, switch-off point, etc.) become only effective after
socket with the delivered seal to ensure an ingress pro-
• Italy • UK • Singapore - The technical data listed in the current data sheet are tection of IP 65. For the electrical connection a shielded and twisted
pushing both buttons simultaneously and leaving the
• Lithuania • Ukraine • Taiwan engaging and must be complied with. If the data sheet is menu item.
- Plug the cable socket onto the plug-on display. multicore cable is recommended.
• Luxemburg • Thailand not available, please order or download it from our
6.3 Password system
• Netherlands AFRICA • Vietnam homepage. (http://www.bdsensors.com/products/down- - Place the delivered stainless steel screw through cable 4.3 Supply of 2-wire-systems
• Norway load/datasheets) socket and plug-on display and tighten it to the transmit- To avoid a configuration by unauthorized persons, the
• Egypt The supply created by the electronics of the plug-on display
• Poland WARNING! – Danger through improper usage! ter with a screwdriver. possibility is given to lock the device by an access protection.
• South Africa AUSTRALIA is approx. 6 VDC. Please take this into consideration when
More information is given in menu 1 of the menu list.
• Portugal planning your power supply. The tolerances for the power
1.6 Package contents 3.5 Positioning of the display module
supply can be calculated as follows: 6.4 Unit
The addresses of our distribution partners are listed on our Please verify that all listed parts are undamaged included in The display module is rotatable so that clear readability is
guaranteed even on unusual installation positions. The minimum supply: VS min = V TR min + 6 V The unit of the values to be measured is determined on
homepage www.bdsensors.com. It is possible to download the delivery and check for consistency specified in your
order: display module can be turned as shown below. maximum supply: VS max = V TR max + 6 V ordering. But it is also possible to change the unit later by
data sheets, operating manuals, ordering codes and certifi-
using one of the enclosed unit labels.
cates, as well. - plug-on display PA 430 VTR min = minimum supply of the used 2-wire transmitter
- only with plug ISO 4400: profile seal, fastening screw VTR max = maximum supply of the used 2-wire transmitter
- sheet of labels
Table of contents 4.4 Supply of 3-wire-systems
- mounting instructions
1. General information minimum supply:
2. Product identification 1.7 UL – Approval (for devices with UL-identification)
The minimum supply of the plug-on display (VS min) is 8 V.
3. Mechanical installation The UL – Approval was done with respect to U.S. standards Fig. 2 display module The connected transmitter is supplied by the PA 430, so the
4. Electrical Installation norms which also correspond with the applicable Canadian minimum supply of the transmitter must be used for the total
5. Initial start-up standards norms for safety. appliance if it is higher than 8 V. The following formulas are
6. Operation valid:
7. Placing out of service Note the following points, so that devices fulfils the demands
8. Maintenance if VTR min ≥ 8 V: VS min = VTR min
of UL approval:
9. Return - The transmitter shall be supplied by Limited Energy if VTR min < 8 V: VS min = 8 V
10. Disposal Source (per UL 61010) or NEC Class 2 Power Source. VTR min = minimum supply of the used 3-wire transmitter
11. Warranty conditions - maximum operating voltage: see technical data
12. Declaration of conformity
2. Product identification
The device can be identified by its manufacturing label. It
provides the most important data. By the ordering code the
product can be clearly identified. The programme version of
the firmware, (e. g. P07) will appear for about 1 second in the
display after starting up the device. Please hold it ready for
inquiry calls.
6.6. Structure of the menu system 6.7 Menu list 7. Placing out of service
- ▲-button: move in the menu system (forward) or increase the displayed value; it will also lead you to the operating mode WARNING! When dismantling the device, it must
Display mode (beginning with menu 1) always be done in the depressurized and currentless
(measured value - ▼-button: move in the menu system (backward) or decrease the displayed value; it will also lead you to the operating mode condition! Check also if the medium has to be drained
is displayed) (beginning with the last menu) off before dismantling!

PA on - - both buttons simultaneously: confirm the menu items and set values WARNING! Depending on the medium, it may cause
Password active danger for the user. Comply therefore with adequate
to increase the counting speed, when setting the values: keeping the respective button pushed for more than 5 seconds
precautions for purification.
Access protection/ Execution of configuration:
Special menu 1:
entry to special - set the desired menu item by pushing the ▲- or ▼-button 8. Maintenance
Full scale set
menus - activate the set menu item by pushing both buttons simultaneously
FS S In principle, this device is maintenance-free. If desired, the
Menu 1: - set the desired value or select one of the offered settings by using the ▲- or ▼-button
Code-No.: 0238 housing of the device can be cleaned when switched of
PAon / PAof
- store the set value / selected setting and exit the menu by pushing both buttons simultaneously
using a damp cloth and non-aggressive cleaning solutions.
menu 1 – access protection
PA of -  PAon  password active  to deactivate: set password 9. Return
Password inactive
Hysteresis- and  PAof  password inactive  to activate: set password
Before every return of your device, whether for recalibration,
Special menu 2: Decimal position default setting for the password is "0005"; modification of the password is described in special menu 4
compare mode decalcification, modifications or repair, it has to be cleaned
Offset set Menu 2: dP Menu 11:  menu 2 – set decimal point position carefully and packed shatter-proofed. You have to enclose a
oF S notice of return with detailed defect description when sending
HY 1 / CP 1
Code-No.: 0247  menus 3 and 4 – set zero point / end point
the device. If your device came in contact with harmful
the device has been configured correctly before delivery, so a later setting of a 2-wire device is only necessary, if a substances, a declaration of decontamination is additionally
Hysteresis- and
 differing displayed value is desired (e. g. 0 ... 100 %) required. Appropriate forms can be downloaded from our
Zero point menu 5 – set damping
Menu 3: ZP
compare mode  homepage www.bdsensors.com. Should you dispatch a
this function allows getting a constant display value although the measuring values may vary considerably; the time device without a declaration of decontamination and if there
Menu 12:
Special menu 3: constant for a simulated low-pass filter can be set (0.3 up to 30 sec permissible) are any doubts in our service department regarding the used
HY 2 / CP 2 menu 6 – exceeding message
Defaults  medium, repair will not be started until an acceptable
LoAd set "on" or "off" declaration is sent.
menus 7 – set switch-on point
Code-No.:0729 End point Switch-on delay S1  If the device came in contact with hazardous
set the values, for the activation of contact 1 (S1on)
Menu 4: EP Menu 13: d1on substances, certain precautions have to be
menus 8 – set switch-off point
 complied with for purification!
set the values, for the deactivation of contact 1 (S1oF)
menus 9 – select hysteresis or compare mode
  10. Disposal
Special menu 4: select hysteresis mode (HY 1) or compare mode (CP 1) for contact 1
Password Damping Switch-off delay S1   compare "7.4 Description of hysteresis and compare mode" The device must be disposed according to the
SEtP Menu 5: FILt Menu 14: d1off menus 10 – set switch-on delay European Directives 2002/96/EG and
 2003/108/EG (on waste electrical and electronic
Code-No.: 0835 set the value of the switch-on delay after reaching contact 1 (d1on)
(0 up to 100 sec permissible) equipment). Waste of electrical and electronic
menus 11 – set switch-off delay equipment may not be disposed by domestic
 refuse!
Exceeding set the value of the delay after reaching switch-of point 1 (d1of)
Switch-on delay S2 (0 up to 100 sec permissible)
message
Menu 15: d2on
WARNING! Depending on the measuring medium,
menus 12 and 13 – maximum / minimum value display
Menu 6: HILo  deposit on the device may cause danger for the user
view high pressure (HIPr) or low pressure (LoPr) during the measurement process and the environment. Comply with adequate precau-
 (the value will not remain stored if the power supply is interrupted) tions for purification and dispose of it properly.
to erase: push both buttons again within one second
Switch-on point S1 Switch-off delay S2  menu 14 – measured value update (display) 11. Warranty conditions
Menu 7: S1on set the length of the update cycles for the display (0.0 up to 10 sec permissible)
Menu 16: d2off The warranty conditions are subject to the legal warranty
special menus
(to access a special menu, select the menu item "PAof" with the ▲- or ▼-button and confirm it; "1" appears in the display) period of 24 months from the date of delivery. In case of
improper use, modifications of or damages to the device, we
  special menu 1 – full scale compensation
do not accept warranty claims. Damaged diaphragms will
for full scale compensation, which is necessary if the indicated value for full scale differs from the real full scale
Switch-off point S1 value in the application: a compensation is only possible with a respective reference source, if the deviation of the also not be accepted. Furthermore, defects due to normal
Maximum value wear are not subject to warranty services.
Menu 8: S1of measured value is within defined limits; set "0238"; confirm with both buttons; "FS S" will appear in the display; now
Menu 17: HIPr
it is necessary to place the device under pressure (the pressure must correspond to the end point of the pressure
measuring range); push both buttons, to store the signal being emitted from the pressure switch as full scale; in the 12. Declaration of conformity / CE
display the set end point will appear although the full scale sensor signal is displaced. The delivered device fulfils all legal requirements.
the analogue output signal (for devices with analogue output) is not affected by this change The applied directives, harmonised standards and docu-
Switch-on point S2 Minimum value
  special menu 2 – offset compensation / position correction ments are listed in the EC declaration of conformity, which is
Menu 9: S2on Menu 18: LoPr set "0247";confirm menu item; if offset ≠ ambient pressure it is necessary to place the device under pressure available online at http://www.bdsensors.com.
(pressure reference has to corresponding to the zero point of the pressure measuring range); push both buttons to Additionally, the operational safety is confirmed by the CE
store the signal being emitted from the pressure switch as offset; in the display the set zero point will appear sign on the manufacturing label.
although the sensor signal in the offset is displaced
Measured value a position correction is necessary, if the installation position differs from the calibration position (otherwise this
Switch-off point S2 can cause a little deviation of the signal, which gives a wrong value indication)
update (display)
Menu 10: S2of the analogue output signal (for devices with analogue output) is not affected by this change;
Menu 19: dLdS
when displacing the offset, the full scale will also be displaced
 special menu 3 – load defaults
set "0729; to load the defaults, push both buttons simultaneously
any changes carried out will be reset (password will be set on "0005")
 special menu 4 – set password
set "0835"; confirm with both buttons; "SEtP" appears in the display; set the password using the ▲- or ▼-button
(0 ... 9999 are permissible, the code numbers 0238, 0247, 0729, 0835 are exempt); confirm the password by
pushing both buttons simultaneously

BA_PA430_E_011015