MANAR AL OMRAN

SCAFFOLDING AND FORMWORK

DATE :

SUBJECT : CALCULATION SHEET FOR STEEL WALER SHUTTERING

STRUCTURAL ELEMENT : WALL TWO- SIDE

PROJECT : C1 WATER DRILLING CHEMICAL INDUSTRY

CONSULTANT: CAPITAL ENGINEERING CONSULTANCY

CONTRACTOR : AMAKEN

Prepared by: Eng'r Muhammed zohair

Checked by: Eng'r Muhammed Shahid

(Technical Dept Head)


Subjet : CALCULATION SHEET FOR STEEL WALER SHUTTERING (Two Side Wall)

Project : C1 WATER DRILLING CHEMICAL INDUSTRY MANAR AL OMRAN

Table of contents:

1) Codes References and Design Parameters

2) Relevant Standards and Material Data

3) Checking For Formwork Components

A. Check For Plywood

B. Check for Aluminum

C. Check for Waler

D. Check for Tie Rod

|Page
Subjet : CALCULATION SHEET FOR STEEL WALER SHUTTERING (Two Side Wall)

Project : C1 WATER DRILLING CHEMICAL INDUSTRY MANAR AL OMRAN

1) CODES REFERENCES:

BS 5975 CODE OF PRACTICE FOR FALSEWORK

CIRIA Report 108 FOR CONCRETE PRESSURE

BS 5268 STRUCTURAL USE OF TIMBER

2) MATERIAL TECHNICAL DATA:


Plywood (18mm):
Plywood to be provided by the client and it should have the below specifications:

Allowable Bending stress Fb = 17.58 N/mm2


Allowable shear stress Fv = 4.83 N/ mm2
Modulus of Elasticity E = 4600 N/ mm2

Aluminum Beam:
Allowable Bending Moment = 8.75 KN-m
Allowable Shear Force = 45.11 KN

Waler:
Allowable Bending Moment = 11.4 KN-m
Allowable Shear Force = 100 KN

Push Pull:
Allowable Maximum Load = 70KN

Tie Rod:
Allowable Maximum Load = 70KN

|Page
Subjet : CALCULATION SHEET FOR STEEL WALER SHUTTERING (Two Side Wall)

Project : C1 WATER DRILLING CHEMICAL INDUSTRY MANAR AL OMRAN

3) CALCULATION OF PRESSURE ON FORMWORK (TWO SIDES):


The following is an extract from CIRIA Report 108 for Calculating Concrete Pressure on
Formwork:

Considering height of 3.65m and pouring rate of 0.5 m/h

Therefore the design pressure:

Pmax = D [C1 √ R + C2 K √ H - C1 √ R ] KN/m2

= 25 [1 √ 0.5 + 0.45 x 1 √ 3.7- 1 √ 0.5 ] KN/m2


= 37.14 KN/m2 , D h = 25 x 3.7= 92.5 KN/m2
Taking lesser value i.e. 37.14 KN/m2
Pmax
At = from top.
D
And the pressure envelope is as follows

1.486 m
5m
3.7m

Pmax = 37.14 KN/m2

Based on the above pressure we check for the safety of Plywood, distance between Primary
walers, spacing of Aluminum beams and Load on Tie Rod.

|Page
Subjet : CALCULATION SHEET FOR STEEL WALER SHUTTERING (Two Side Wall)

Project : C1 WATER DRILLING CHEMICAL INDUSTRY MANAR AL OMRAN

A) CHECK FOR PLYWOOD:


Technical data of plywood
Modulus of Elasticity E = 4600 N/mm2
(Cross grain)
Allowable Shear = 4.83 N/mm2

Considering Plywood Strip 10cm


Width of plywood strip = 0.10m
Span of plywood
(B/w Secondary beam) =260 mm

Loading Intensity 0.10 KN/M run:

37.14 KN/M2 x 0.10m= 3.71 KN/M

Check through Bending Stress, Shear & Allowable Deflection

Max. Bending Moment BM = WL2 = 3.7*0.262 = 0.0251 KN-M


10 10

Max. Shear Force V = 0.60WL = 0.60*3.7*0.26 = 0.579 KN

Allowable Deflection δ = L/270 = 260/270 = 0.963 mm

For 0.10m strip * 18mm thick of Plywood

Section modulus Z =bd2/6 =100(18)2/6 = 5400mm3


Moment of Inertia Ixx =bd3/12 =100(18) 3/12 = 48600mm4
Moment Area about N/A axis Q =100*9*9/2 = 4050mm3
Width of plywood strip B = 100mm

Bending Stress Fbr = M = 0.0251*1000*1000 = 4.64 N/mm2


Z 5400
2 2
4.64 N/mm < 17.58 N/mm ------------------------------- (SAFE)

Shear stress Fvr = VQ = 0.579*1000*4050 = 0.48 N/mm2


IxxB 48600*100
0.48 N/mm2 < 4.83 N/mm2 --------------------------- (SAFE)

|Page
Subjet : CALCULATION SHEET FOR STEEL WALER SHUTTERING (Two Side Wall)

Project : C1 WATER DRILLING CHEMICAL INDUSTRY MANAR AL OMRAN

Max. Deflection δmax WL4 = 3.71 * (260)4 = 0.52 mm


145EI 145*4600*48,600

0.52 mm < 0.96 mm -------------------------------- (SAFE)

B) CHECK FOR ALUMINIUM:

Technical data of Aluminum


Max Span (Length of Secondary) = 1.3M (i.e. max distance between two primary horizontal Walers)

Allowable Shear Force = 45.11 KN

Allowable Bending Moment on Aluminum = 8.75 KNM

Allowable Deflection = L/360= 1300/360= 3.611 mm.

Modulus of Elasticity (E) =70,000 N/mm2

Moment of Inertia (I) =458.160423 cm4

Maximum UDL on Secondary beam = 0.26x 37.14


= 9.65KN/M
Check for Shear Force, Bending Moment & Deflection

Max. Bending Moment BM = WL2 = 9.65*1.3*1.3 = 1.63KNM


10 10

Max B.M= 1.63 KNM < 8.75 KNM (SAFE)

Max. Shear Force V = 0.60WL = 0.60*9.65*1.3 = 7.53 KN

Max S.F= 7.53 KN < 45.11 KN (SAFE)

Max. Deflection δmax WL4 = 9.65* (1300)4 = 0.593mm


145EI 145*70000*4581604

Max Deflection= 0.59 mm < 3.611mm (SAFE)

|Page
Subjet : CALCULATION SHEET FOR STEEL WALER SHUTTERING (Two Side Wall)

Project : C1 WATER DRILLING CHEMICAL INDUSTRY MANAR AL OMRAN

C) CHECK FOR STEEL WALER:


Maximum Span of Waler =0.85m

Allowable Deflection = L/360= 850/360= 2.36 mm.

Load on Waler =2 x Reaction from Secondary

= 2 x 7.53=15.06 KN @0.26m c/c

Therefore from the above result for primary beam:

Max S.F= 27.64 KN < 100 KN (SAFE)

Max B.M= 5.21 KNM < 11.4 KNM (SAFE)

Max Deflection= 0.02 mm< 2.36 mm (SAFE)


D) CHECK FOR TIE ROD:

Max Tensile force on Tie rod = 37.14x 1.3 x 0.85 =41.03 KN < 70KN (Safe)

|Page