Академический Документы
Профессиональный Документы
Культура Документы
3rd Year
CHAPTER 4
Protection of Power System Elements
1. Feeder Protection
The various protection schemes as applied to feeder protection can be classified to:
a. Time graded protection b. Differential protection.
c. Distance protection. d. Carrier current protection.
i) Radial feeder:
Protection on radial feeder is obtained by employing fuse shunted trip coils as shown in the
figure 1.
This also can be done by inverse definite time relays as shown in fig. 2 are also is set so
that the minimum time of operation decreases from the power station to the remote sub-
station.
Let an earth fault develop on feeder 2 as shown in the figure. It will be seen that this fault is
fed via three routes.
29
Protection Systems & Devices (Relays)
3rd Year
With such an arrangement, it is clear that with a fault at F, all the three relays at the supply
end will start to operate while, at the receiving end, only the relay on feeder 2 (relay no. 4)
will start and operate to isolate the fault from the receiving end.
he method of protection can also be applied to parallel feeders with a tee-off as shown in
figure 4.
The 1.1 second relay on the outgoing side of sub section B will obviously be the first to
complete its operation i.e. trip out the associated circuit breaker and thus clear the fault, the
relays at the power source and the station A immediately resetting.
Considering now the fault flow in the direction “ y ”, the relays at power source and the
outgoing sides of substations C and D have definite minimum time setting of 2.1, 1.6, 1.1
seconds respectively, thus ensuring that the circuit breaker on the outgoing side of the
substation C with its 1.1 seconds setting will clear the fault, leaving the remaining relays to
reset.
The time grading between time settings of the relays should not be closer than 0.33 to 0.5
second and as the longest time that a fault can fed is usually 2.1 seconds, the maximum
number of sections that can be protected in this way is limited to 7 seconds. This is a
disadvantage.
The interlock method has been designed to overcome this disadvantage and it can be
used for any number of sections with a very short time delay. It can be used on radial or
main systems.
30
Protection Systems & Devices (Relays)
3rd Year
If a section is healthy the same current passes at both ends and the overload relays
operate. The operation of this relay
at the beginning of the section
completes the circuit of the trip coil
( closes contact B ) , but the
operation of the relay at the end of
the section closes contact A, and
causes the locking relay to operate
and thus break the trip circuit ( so
nothing happens ).
If a fault occurs within the section, the current entering is high causes the contact B to close
but the current leaving is small and the locking relay does not operate. It is essential that the
locking relay operates before contact B is closed, so the relay B is set to operate in 0.3 to
0.5 second.
When this method is applied on a ring main it is necessary merely to have differential relays
to close the circuit for the locking relays.
b. Differential Protection
Among the more commonly used methods of feeder protection on complex networks is the
differential protection in which the operation can depend on either current balance or an
voltage balance, the difference between these two methods being illustrated in fig. 6.
31
Protection Systems & Devices (Relays)
3rd Year
If a short circuit occurs at P between substation 3 and 4, the fault loop impedances at
power stations and substations 2 and 3 are Z1 + Z2 + Z, Z2 + Z, and Z respectively.
The relays at 1, 2, 3 etc. are set to operate with impedances less than Z 1, Z2 and Z3
respectively, so that under the condition shown only relay 3 will operate. Similarly, if the
fault occurs between substations 2 and 3, only relay 2 operates.
A system with instantaneous impedance relays, set to act on impedances less than or
equal to the impedance of a section would be difficult to adjust, a fault near the junction of
two sections is likely to cause the operation of two relays. Furthermore, if a fault of finite
resistance occurs near the end of a section, it is possible that the total impedance is greater
than the relay setting.
If a fault occurs at X on the system, the relays at substation A will operate with a time lag
of 0.5 second.
Suppose now that the circuit breakers require 0.2 second to open, then the characteristic
representing the time required for the relay to close and circuit breaker to open is given
by the dotted line NP. Thus, for the fault shown, the circuit breaker installed at A will open
in 0.7 second.
It may be noticed that if time impedance relay at A fails to operate, the relay at the power
station will close its contacts at 1.1 seconds, and its circuit breaker will open in 1.3
seconds.
It is important for correct operation that the circuit breaker at A shall open before the
relay at the power station closes its contacts. It’s seen from the figure that there is a time
margin of 0.4 second.
Thus, unlike the scheme using definite impedance relays, impedance time relays provide
backup protection.
32
Protection Systems & Devices (Relays)
3rd Year
In the above discussion we assumed sections of equal impedances. If this were not the
case, such as in the power system shown in fig. 10, then special considerations would have
to be given in selecting the relay settings so that correct discriminating times were obtained
between each relaying point.
For a fault at F, by the time circuit breaker at substation A clears the fault, the relay at the
power station will also have operated. This means that the power station circuit breaker
will also trip out.
It will be necessary to increase the time lag of the power station relay in order that
discrimination times are obtained between the two sections of the line and also to ensure
backup for faults on the section between substation B and C.
Figure 11 shows the time distance curves to afford proper discrimination as desired above.
It can be seen that the modification to the time of operation of the time distance relays at
power station has increased the time during which a fault at the far end of its own section is
cleared.
33
Protection Systems & Devices (Relays)
3rd Year
In order to obtain very rapid disconnection of faults near the point of supply, special high-
speed distance relays operating in about 0.2 second are employed.
With this arrangement very rapid fault clearance can be obtained for faults on the major
portion of transmission line while suitable backup protection is given to neighboring
sections. This is shown in fig. 12.
This high-speed distance relays can be arranged for measuring reactance or impedance,
and normally provided with a built in directional feature.
Figure 13 shows the characteristics for a three-stage impedance relay with directional unit
while figure 14 shows the contact circuit of the principal units.
The directional unit permits tripping only in its positive torque region.
34
Protection Systems & Devices (Relays)
3rd Year
Any value of impedance that is within the Z 1 circle will cause all three impedance units to
operate. The operation of Z 1 and the directional unit will trip a breaker directly in a very short
time, which definite delay which we call T 1. Whenever Z3 and the directional unit operate, the
timing unit is energized. After a definite time delay, the timing unit will first close its T 2
contacts and later its T3 contact, both time delays are independently adjustable. Therefore it
can be seen that a value of impedance within the Z 2 circle, but outside Z 1 circle, will result in
tripping in T2 time. Finally a value of Z outside the Z 1 and Z2 circles, but within Z3 circle will
result in tripping in T3 time.
Reactance relays and mho relays are also commonly used with the same previous method
as shown in figures 15 & 16.
Distance relays are adjusted on the basis of the positive phase sequence impedance
between the relay location and the fault location beyond which operation of a given relay
unit should stop. The impedance or the corresponding distance is called “ reach “ of the
relay. Approximately 0.8 /mile (0.5 /km) is the positive sequence impedance generally
taken.
Usually used in transmission line protection & it is connected similarly to that shown in figure 14 except
that no separate directional unit is required, since it’s inherently directional.
35
Protection Systems & Devices (Relays)
3rd Year
As the relays are energized through C.T’s abd P.T’s, the primary value of impedance must
be converted to secondary values.
36