Catalogo de Productos 
 
Por favor use los marcadores y el menù ampliable del 
PDF para una conveniente selecciòn y visualizaciòn de 
la lìnea de productos de Hochiki America. 
 
7050 Village Drive, Suite 100 
Buena Park, CA 90621  
(714) 522‐2246 
sales@hochiki.com 
www.hochiki.com 
FireNET™4127 - ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL
STANDARD FEATURES
• UL 864 9th edition Listed
• Analog design using Hochiki’s advanced DCP
protocol for fast and robust communication
• Up to 127 sensors & modules, plus 127 analog sounder
bases, for a total of 254 points possible per loop
• Uses standard wire, no shielded or twisted pair required
on SLC loops
• Supports Class B (style 4) and Class A (style 6 or 7)
SLC loops
• 4 on board Class B (style Y) NAC circuits rated at 2.5
Amp each
• Programmable sensitivity levels per device & automatic
day/night sensitivity modes
• Automatic daily calibration & drift compensation routine
• Large 8-line x 40-character LCD display (320 char.)
• 2 or 4 loop versions (800 addresses/sub-addr. max.)
• Dual RS-485 bus for panel network
DESCRIPTION
• 2 built-in RS-232 interfaces for programming via a PC
The FireNET™ 4127 control panel is an analog and serial printer interface
addressable fire alarm panel containing 2 or 4 SLC • 5 on board programmable Form C relays rated at 1 amp
at 30VDC (Fire1, Fire2, trouble, supervisory, aux.)
loops with each loop supporting 127 devices of any
combination (sensors or modules), and 127 analog • 500mA of auxiliary power available rated at 24 VDC
sounder bases, for a possible total of 254 points. • Loop Explorer Windows® configuration utility
Communication between devices is transferred • *500 network wide software zones
through standard cable (shielded or twisted pair is • Network Capability of up to 64 panels
not required). Each panel includes a 5.25 amp • RS485 slave bus for expansion - up to 31 FN-4127-IO
power supply and has 4 on board NAC circuits. An boards or up to 15 FN-LCD-S serial annunciators and up
RS-485 bus provides communication to the panel to16 FN-4127-IO boards
network, while the RS-232 interface allows the • Auto-learn feature
convenience of programming via a PC. The system • Built in help and alarm information screens
will support a variety of Hochiki devices: photo, ion • Fire Drill test function
and heat sensors, which contain a unique, patented • Walk Test function
sensor design incorporating automatic drift compen- • Alarm Verification feature
sation and day/night sensitivity mode. Additional • FireNET is UL listed for Central Station Service when
devices include contact monitors, relay controllers, used with the Bosch D9068 contact dialer
supervised auxiliary output and short circuit isolator • Operates on 120VAC or 240VAC input voltage
modules. In addition, interfaces to conventional • Powerful & versatile Cause & Effect programming (up to
detection systems can be established by using a 500 maximum, network wide) including:
conventional zone-monitoring module. The Loop *Cause & Effect action
Explorer Windows® Software interface provides the *Disable function configuration
installer with fingertip access to installation program- *Test mode configuration Continued on back.
ming and diagnostic tools. An Auto-learn feature PRODUCT LISTINGS
offers the convenience for quick start applications. UL 864, Local Signaling Unit.
Add to this a reputation for high quality and dedi- Types: Automatic, manual,
California
cated service makes this an exceptional product waterflow, sprinkler supervisory,
Auxiliary Service(local energy), State Fire
both in performance and value. S8255 and Central Station Service Marshal
(DACT) Non-coded signaling.
Specifications subject to change without notice. NFPA 70, 72 &13 Compliant 7170-0410:170

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0068 01/2008
SPECIFICATIONS
Primary AC 120VAC @ 2.1 Amps 60hz or 220VAC @ 1.1Amps 60hz
Output DC 24VDC @ 5.25 Amps (4 Amps availble for system power)
Power Supply 5.25 Amp integrated
Charger Current 1.5 Amps max.
Dimensions 14.5" W x 24" H x 5" D
Weight 31 lbs. (without batteries)
Color Red (optional charcoal)
Material ABS/steel enclosure
Display 8 line x 40 character LCD (320 characters total)
Network Dual RS485 ports (64 panels max.)
Zones 500 network wide software zones per system
SLC loops 2 or 4 (class A, "style 6 or 7" or class B, "style 4")
Devices per loop 127 sensors & modules, plus 127 analog sounder bases, 254 total
Addresses per panel (800 addresses+sub-addresses max. per panel)
NAC Outputs (4) 2.5 Amp @ 24VDC (class B)
Relay Outputs (5) Form C 1 Amp @ 30VDC
Voltage Outputs (3) 500mA @ 24VDC FireNET ORDERING MODELS
Aux. Power 500mA @ 24VDC MODEL DESCRIPTION
Aux. Inputs (8) digital pull downs
FN-2127 FACP (2 Loop/5.25 Amp)
PC Port RS232
FN-2127N FACP (2 Loop/5.25 Amp) (w/Network)
Printer Port RS232
FN-4127 FACP (4 Loop/5.25 Amp)
FN-4127N FACP (4 Loop/5.25 Amp) (w/Network)

SLC COMPATIBLE DEVICES & SYSTEM ACCESSORIES


MODEL DESCRIPTION
CONTROL PANEL EXPANDERS
FN-4127-SLC Dual SLC Loop Expansion Card
FN-4127-NIC Network Interface Card
FN-4127-IO 16 Channel Input/Output Board
FN-CTM City-Tie Module (Local Energy Type)
ANNUNCIATORS
FN-LCD-N Network LCD Annunciator
FN-LCD-S Serial LCD Annunciator
SLC LOOP DEVICES
ALG-V Analog Addressable Photoelectric Sensor
AIE-EA Analog Addressable Ionization Sensor
ATG-EA Analog Addressable Heat Sensor
NSA-6 Six inch Sensor Base
NSA-4 Four inch Sensor Base
ASB Analog Sounder Base
DH-98A Anaolg Addressable Duct Detector Unit
DH-98AR Analog Addressable Duct Detector Unit (with relays)
MS-RA, MS-RA/R,
MS-KA/R Remote Test Station for DH98A & DH98AR
FRCME-S Contact Monitoring Module (mini w/terminal blocks)
FRCME-P Contact Monitoring Module (mini w/pigtail leads)
FRCME-4 Contact Monitoring Module (with faceplate/indicating LED)
DIMM Dual Input Monitor Module (with faceplate/indicating LED)
CZM Conventional Zone Module
R2M Dual Relay Module
SOM Supervised Output Module
SCI Short Circuit Isolator Module
AMS Series Addressable Manual Pull Station
ACCESSORIES
TCH-B100 Hand Held Programmer (portable device addresser)
FN-ACC Battery/Accessory Enclosure (houses up to 33AH size batteries)
FN-ETR Enclosure Trim Ring for Panel Flush Mount
Hochiki America Corporation FireNET ANALOG ADDRESSABLE FIRE ALARM CONTROL PANEL Specifications subject to change without notice.
FN-LCD-N - LCD NETWORK ANNUNCIATOR

STANDARD FEATURES
• UL 864 9th edition Listed
• 320 character liquid crystal display (8 line x 40
character)
• LED indicators for Fire, Supervisory Alarm, Pre-
Alarm, Fire Output Active, Power On, On Test, Panel
Sounder Silenced, Delay Active, More Events, Point
Bypassed, General Trouble, Power Trouble, System
Trouble & NAC Trouble
• Dual RS485 ports for primary fire network
• RS485 slave bus for expansion - up to 31 FN-4127-IO
DESCRIPTION boards or up to 15 FN-LCD-S serial annunciators and
up to16 FN-4127-IO boards
The FN-LCD-N type LCD network annunciator is • 2 built-in RS-232 interfaces for programming via a PC
designed to be used with the FireNET analog and serial printer interface
addressable system. It allows for remote access,
• 4 on board programmable Form C relays rated at 1
monitoring & control of the FireNET system throughout Amp at 30VDC (Fire, Supervisory, Trouble &
the building. Auxiliary)
The FN-LCD-N is a true network annunciator that can • Same controls as the FireNET fire panel (Reset,
access, monitor & control any or all FireNET panels in Panel Sounder Silence, Lamp Test, Alarm Silence,
the network. Each FN-LCD-N is completely Re-sound Alarm, Fire Drill, Programmable Function,
independent. The highly intuitive user interface and More Events, More Fire Events, Enter & Exit)
320 character LCD display of the FN-LCD-N is exactly • Local piezo sounder for event notification
the same as the FireNET panel. In addition to routing • Supports user codes & firefighter key to enable
any panel in the network to the FN-LCD-N, every event access & controls
category within each panel can also be individually • Powered by FireNET Aux 24VDC or UL fire listed
routed, as well as routing of all remote control functions Aux. 24VDC supply
(reset, alarm silence, re-sound alarm) from individual • Available in red or charcoal, and can be surface or
panels. The FN-LCD-N supports the same RS485 flush mounted (using trim ring)
expansion port as the FireNET panel, allowing for • True network annunciator, any or all panels can be
FireNET expansion boards and accessories to be routed to the FN-LCD-N. In addition, each event
connected to the network annunciator. category can be individually routed to the FN-LCD-N
The FN-LCD-N also has (4) output relays for fire, • Up to (64) FireNET panels & FN-LCD-N's can be
supervisory, trouble & auxiliary. The relays are networked together in any combination
programmable (except supervisory). • 500mA of auxiliary power available rated at 24VDC
Security is established by the use of a password or • Auto-learn feature
firefighters enable key. Designed to be aesthetically • Built-in help & alarm information screens
pleasing, the FN-LCD-N is available in charcoal grey
• Fire drill function
or red and can be surface or flush mounted using a
standard trim ring kit.
• Each FN-LCD-N is completely independent
• Supports up to (31) FN-4127-IO boards on RS485
PRODUCT LISTINGS expansion port
UL 864, NFPA 70 & 72: California • The FN-LCD-N can be configured to remote reset,
Signaling Device State Fire silence, resound, any or all panels on the network in
Marshal any combination
S8255 Vol. 2
7120-0410:165
Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0071 09/2007
SPECIFICATIONS
Input DC 24VDC @ 270mA Max. ( + Aux. Power Load)
Aux. Output DC 24VDC @ 500mA
Dimensions 14.5" W x 10" H x 3.3" D
Weight 9.4 lbs
Color Red (optional charcoal)
Material ABS/steel enclosure
Display 8 line x 40 character LCD (320 characters total)
Network Dual RS485 ports (64 nodes max.)
Relay Outputs (4) Form C 1amp@30VDC
PC Port RS232
Printer Port RS232
Expansion Port RS485 (for optional expansion boards)

ENGINEERING SPECIFICATION

The contractor shall furnish and install where indicated on the plans, the network annunciator model FN-LCD-N.
The FN-LCD-N shall connect to the FireNET fire alarm control panel (FACP) network. The network annunciator
shall be capable of annunciating on its 320 character display and local buzzer, the condition of any FireNET FACP
or network annunciator on the network. Up to 64 FN-LCD-N network annunciators or FireNET FACP's may be
connected together on the network. The FN-LCD-N shall be UL listed, and have surface or flush mount capability.

WIRING DIAGRAM

Hochiki America Corporation FN-LCD-N Specifications subject to change without notice.


FN-LCD-S - SERIAL LCD ANNUNCIATOR
STANDARD FEATURES

• UL 864 9th edition Listed


• Large 320 character liquid crystal display (8 line
x 40 character) allows viewing of system status
• LED indicators for Fire, Supervisory Alarm, Pre-
Alarm, Fire Output Active, AC Power On, On
Test, Panel Sounder Silenced, Delay Active,
More Events, Point Bypassed, General Trouble,
Power Trouble, System Trouble & NAC Trouble
• Same controls as the FireNET fire panel (Reset,
Panel Sounder Silence, Lamp Test, Alarm
Silence, Re-sound Alarm, Fire Drill, Program-
mable Function, More Events, More Fire Events,
Enter & Exit)
• Up to 15 FN-LCD-S serial annunicators may be
connected to a FireNET control panel or network
DESCRIPTION annunciator
• Resides on the FireNET slave RS-485 line
The FN-LCD-S serial annunciator provides a • Local piezo sounder for event notification
convenient and cost effective remote annunciator • Supports user codes & firefighter key to enable
solution. Up to 15 FN-LCD-S annunciators can be access & controls
connected to the slave RS-485 port of the FireNET • Powered by FireNET Aux 24VDC or UL fire listed
control panel or network annunciator. The FN-LCD-S’s Aux. 24VDC supply
large 320 character display and navigation buttons are • Available in red or charcoal, and can be surface
a complete mimic of the FireNET control panel or flush mounted
display. The use of a common interface allows the
• Built-in help & alarm information screens
user to easily operate the FN-LCD-S as if he were
operating the FireNET control panel directly. • Fire drill function

Security is established by the use of a password or SPECIFICATIONS


firefighters enable key. Designed to be aesthetically
pleasing, the FN-LCD-S is available in charcoal grey Current Draw
or red enclosures. The FN-LCD-S can be surface or Standby: 20mA @ 24VDC
flush mounted without the need for a trim ring. Alarm: 110mA @ 24VDC
Dimensions
FN-LCD-S 10.88" W x 8.00" H x 1.38" D
Back Box 10.38" W x 7.38" H x 1.25" D
PRODUCT LISTINGS Weight 3.5 lbs
Color Red (optional charcoal)
UL 864, NFPA 70 & 72: California
Signaling Device State Fire Material ABS/steel enclosure
S8255 Vol. 2 Marshal Display 8 line x 40 character LCD
7120-0410:165 (320 characters total)
Network RS485 port

Specifications subject to change without notice.


Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0070 09/2007
ENGINEERING SPECIFICATION

The contractor shall furnish and install where indicated on the plans, the serial remote annunciator model
FN-LCD-S. The FN-LCD-S shall connect to the FireNET fire alarm control panel (FACP) or network
annunciator (FN-LCD-N) RS485 slave bus. The serial remote annunciator shall annunciate on its 320
character display and local buzzer, the condition of its master FireNET FACP. Up to 15 FN-LCD-S serial
annunciators may be connected together on a single RS-485 FireNET slave bus. The FN-LCD-S shall be
UL listed and compatible with the Hochiki FireNET control panel, and have surface or flush mount
capability.

WIRING DIAGRAM

1522RO @

FIT JUMPER
ADDRESS COMM1 0V +24V COMM2 FOR END OF LINE
RESET W / DOG RESET COMM1 COMM2
+

+
l

ON K S

1 2 3 4 COMMS
ACTIVE

Reset
Not Used
Switch
Not Used

DIP Switch used to set


the FN-LCD-S address RS485 End-of-line jumper . Put
between 1 -15 jumper in place when FN-LCD-S
is the last device on the RS485
buss “I/O Comm”.

7. PR2

8. PR3
l +

COMMS
ADDITIONAL
I/O BOARDS To next
( +)
AUX serial
24 VDC
l +

24X (- ) FN-LCD-
S or
other
NETWORK (+)
RS485
l +

IN RS-485
(- ) Buss
Device
NETWORK
l +

OUT

To AUX 24VDC of control


FireNET Control Panel panel (as shown) or to UL
(section) 864/1481 listed AUX
24VDC Power Supply

Hochiki America Corporation FN-LCD-S Specifications subject to change without notice.


FN-DAC - DIGITAL ALARM COMMUNICATOR

STANDARD FEATURES

• Contact ID and SIA reporting formats


• UL 864 9th Edition listed
• Programmable from FireNET control panel or by
using Loop Explorer
•Zone or Address (Point) reporting
• Remote upload / download and diagnostic tools
• Backup and Duplicate reporting
• Programmable daily test report interval
• Quick installation in FireNET enclosure
DESCRIPTION

The FN-DAC Digital Alarm Communicator reports


Alarm, Trouble, Supervisory and other system events
SPECIFICATIONS
using PSTN telephone lines. Events are reported to
a compatible central station monitoring receiver. The Power Requirements 24VDC @ 20mA
communicator may be configured to report by zone or Operating Temperature 0-49 C @ 93% RH
by address (point). The FN-DAC is installed in the Dimensions 5.48" x 7.48"
FireNET enclosure, or may alternately be installed in FireNET Firmware Required 3.8 or higher
the FN-LCD-N network annunciator. The FN-DAC Loop Explorer Version Required 6.0 or higher
receives data and power from the FireNET panel, or
power may be provided by a UL listed 24 VDC
regulated power supply. Events from one or more
networked panels may be reported using just one
FN-DAC communicator.

The FN-DAC contains a built-in modem which


allows a remote user to connect to the panel(s)
to view current status, panel event history and
sensor analog values. Panel programming data
may also be copied or sent to one or more network PRODUCT LISTINGS
panels. UL 864, NFPA 72: California
Central Station, Remote State Fire
Station & Proprietary S8255 7170-0410:170

Continued on back.
Specifications subject to change without notice.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0073 01/2008
ENGINEERING SPECIFICATION
The contractor shall furnish and install where indicated on the plans, the FN-DAC Digital Alarm Communicator. The
FN-DAC shall connect to the FireNET 4127 fire alarm control panel RS-232 port. The communicator shall be
programmable by using the front panel controls or by using Loop Explorer software. The FN-DAC shall allow the
use of a computer and modem to remotely access the FireNET network to perform remote diagnostics and system
configuration. The FN-DAC shall be programmable to report events by zone or by address, and shall be capable of
reporting using Contact ID or SIA format.

WIRING DIAGRAM

Telephone line
connections

24 VDC
Input Power

To J5 connector
on FireNET panel

Hochiki America Corporation FN-DAC Specifications subject to change without notice.


DCP-AMS SERIES ADDRESSABLE MANUAL PULL STATIONS
SPECIFICATIONS
Operating Voltage (SLC) 17~41 VDC
Average Current Consumption 600uA (Typical)
Alarm Current 8mA
Ambient Temperature 32°F (0 °C) ~ 120°F (49°C)
Maximum Humidity 90% RH, non-condensing
Dimensions 3.4"W x 4.8"H x 2.0"D
Mounting Single gang or 4" square
electrical box

MODEL DESCRIPTION
DCP-AMS Single Action Hex Key Lock
DCP-AMS DCP-AMS-KL DCP-AMS-LP Dual Action Hex Key Lock
DCP-AMS-KL Single Action Key Lock
DCP-AMS-KL-LP Dual Action Key Lock

DESCRIPTION
The DCP-AMS are the Hochiki America series of
addressable manual pull stations that provide a fast and
practical means of manually initiating a fire alarm signal.
Both single action and dual action manual pull stations
are available. Resetting of the pull station requires either
a Cat 211 key or a 1/8" hex key (depending upon the
model used).

An alarm condition is actuated by pulling down on the


handle of the DCP-AMS and DCP-AMS-KL single action
models. On the dual action models DCP-AMS-LP and
DCP-AMS-LP DCP-AMS-KL-LP DCP-AMS-KL-LP the Lift and Pull cover must be lifted
before pulling down on the pull station handle. Once
the pull station is activated, the handle cannot be put
STANDARD FEATURES back into a normal standby condition without using the
key operated reset feature.
• Addressable integrated design
• All metal construction The DCP-AMS series is electronically addressable and
• Single and dual action models available includes a bi-colored status LED. The LED blinks green
• Extremely easy to operate indicating normal communication with the DCP
• Bi-colored status LED indicates Standby and compatible SLC loop. When an alarm condition is
Alarm conditions actuated by pulling the handle, the LED will latch Red
• Address is programmable in EEPROM to indicate the alarm condition.
• Address can be programmed when installed
• Key lock or hex key lock models available
PRODUCT LISTINGS
• Terminals accept up to 14AWG wire California State
• Surface mount back box available Fire Marshal
S6512 7150-0410:169
Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0066 01/2007
ENGINEERING SPECIFICATIONS
Manual pull stations shall be Hochiki addressable AMS-series single or dual action models, DCP-AMS, DCP-AMS-
KL, DCP-AMS-LP, or DCP-AMS-KL-LP. Models shall be made of 14 AWG CRS and painted with Red enamel. The
words Fire Alarm shall be in a contrasting color and be embossed text 1/2" tall. The electronics shall be fully
integrated into the manual pull station requiring only connection to the SLC loop of the control panel. Programming of
the manual pull station address must be possible with the manual pull station fully installed.

Manual pull stations shall be Underwriters Laboratories Inc. Listed, CSFM Approved, and be installed within the limits
defined in the American Disabilities Act.

WIRING DIAGRAMS
Hochiki America Corporation
OUT TO
NEXT DCP-AMS
MODULE Addressable Manual Pull Station
Ser. No.
SC- S+

S+ SC-
For Proper Installation, see HA-06-135 Rev 12/05
S6512

NON-CODED ALARM BOX


36CC

UL
Listed + S
Hochiki
DCP - SC
Compatible
Panel

TYPICAL WIRING DIAGRAM EXAMPLE, CONNECTED


TO A COMPATIBLE LISTED CONTROL PANEL

Class B (Style 4)
Hochiki America Corporation Hochiki America Corporation Hochiki America Corporation
DCP-AMS DCP-AMS DCP-AMS
Addressable Manual Pull Station Addressable Manual Pull Station Addressable Manual Pull Station
Ser. No. Ser. No. Ser. No.

S+ SC- S+ SC- S+ SC-


For Proper Installation, see HA-06-135 Rev 12/05 For Proper Installation, see HA-06-135 Rev 12/05 For Proper Installation, see HA-06-135 Rev 12/05

S6512 S6512 S6512


+ S NON-CODED ALARM BOX NON-CODED ALARM BOX NON-CODED ALARM BOX
UL 36CC 36CC 36CC

Listed
Hochiki
- SC
DCP
+ S
Compatible
Panel - SC
Class A Return (Style 6)

Class A (Style 7)
Hochiki America Corporation Hochiki America Corporation
DCP-AMS DCP-AMS
Addressable Manual Pull Station Addressable Manual Pull Station
Ser. No. Ser. No.

+ S
For Proper Installation, see HA-06-063 Rev 2/02

For Proper Installation, see HA-06-063 Rev 2/02

For Proper Installation, see HA-06-063 Rev 2/02

For Proper Installation, see HA-06-063 Rev 2/02


Hochiki America Corporation

Hochiki America Corporation

Hochiki America Corporation

Hochiki America Corporation

(IN) S (IN) S (IN) S (IN) S


SIGNALING DEVICE

SER. NO. XXXXXXXXX

SER. NO. XXXXXXXXX

SER. NO. XXXXXXXXX

SER. NO. XXXXXXXXX


ISSUE NO. AH-9774

SIGNALING DEVICE

SIGNALING DEVICE

SIGNALING DEVICE

-
ISSUE NO. AH-9774

ISSUE NO. AH-9774

ISSUE NO. AH-9774

SC
DCP-SCI

DCP-SCI

DCP-SCI

DCP-SCI

(IN) SC (IN) SC (IN) SC (IN) SC


LISTED

LISTED
LISTED

LISTED

S+ SC- S+ SC-
UL (OUT) S
For Proper Installation, see HA-06-135 Rev 12/05
S6512 (OUT) S (OUT) S
For Proper Installation, see HA-06-135 Rev 12/05
S6512 (OUT) S

Listed NON-CODED ALARM BOX


S5694

NON-CODED ALARM BOX


S5694

S5694
S5694

(OUT) SC 36CC (OUT) SC (OUT) SC 36CC (OUT) SC

Hochiki
DCP
Compatible
Panel - SC

+ S

Hochiki America Corporation DCP-AMS, DCP-AMS-LP, DCP-AMS-KL AND DCP-AMS-KL-LP Specifications subject to change without notice.
FN-4127-SLC DUAL SLC LOOP EXPANDER

SPECIFICATIONS
Operating Voltage 24 - 40VDC
Board Current 100mA (+ loop current)
Loop Current 400mA max. each
System Capacity One expander per FireNET
control panel
Loops per 2 SLC (Class A or B)
expander
Devices per loop 127 sensors/modules +
127 analog sounder bases, 254 total
STANDARD FEATURES Loop Load 50 ohms, 1uF, 1mH max.
impedance
• Adds two SLC loops to a two loop FireNET Size 6.3" L x 4.5" W
control panel
• Each SLC loop is capable of 127 sensors/
modules, plus 127 analog sounder bases, DESCRIPTION
for a potential total of 254 addresses per
loop (127+127 per loop)
The model FN-4127-SLC Dual SLC Loop Expander is
• FN-4127-SLC can be added at the factory or
a two loop expander board that increases the
installed in the field
standard FireNET loop capacity from 2 to 4 loops.
• Supports Class A and B wiring methods per The FN-4127-SLC can be added at the factory or
NFPA72 Styles 4, 6, and 7 (with isolators) installed in the field, and mounts within the main
• Fully supervised & power limited SLC loops control board location as a piggy-back board. By
• Supports Hochiki’s DCP (Digital adding the FN-4127-SLC, the FireNET capacity is
Communication Protocol) loop protocol increased from 254+254 to 508+508 analog
• Same functionality as built-in SLC loops of addressable points within the overall 800 address/
FireNET control panel sub-address limit. The FN-4127-SLC has the same
• One SLC expander (maximum) may be functionality as the built-in SLC loops. The FN-4127-
added per FireNET control panel SLC utilizes Hochiki’s robust DCP loop protocol for
• Each SLC loop is completely independent highly reliable and fast alarm reporting without the
and autonomous need for shielded or twisted pair wiring for the SLC
loops.
• Uses standard wire, no shielded or twisted
pair required on SLC loops

PRODUCT LISTINGS
UL 864 Category UOJZ CNN: California
Signal System Control Unit State Fire
S8255 Sub-Assembly Marshal
Vol. 1 NFPA72 compliant
7170-0410:170
Specifications subject to change without notice.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0062 01/2008
Hochiki America Corporation Specifications subject to change without notice.
FN-4127-IO 16 CHANNEL INPUT/OUTPUT BOARD
(RS-485 BUS DEVICE)
SPECIFICATIONS
Supply Voltage 24 VDC Nominal
Channels (16) total per I/O board (each
configurable as input or output)
I/O Comms Bus Up to (32) expansion boards
Quiescent Current 20mA
Current per input 3mA max.
Current per output 100mA max. (*within overall limits)
*Current per bank of 500mA max. (for banks 1-8 & 9-16)
8 outputs
*Current per I/O board 1A max.
STANDARD FEATURES Communications RS485 two wire
• 16 channels of input/output points Max Distance from 4,000 ft. (depends on method &
• 32 I/O boards per FireNET panel (512 channels of panel wire size used for input power).
input/output points) Cable Capacity 12 AWG max.
• Each channel configurable as input or output point Indicators (2) LED's for communication status
• Inputs are opto-isolated non-supervised pulldown Size 7.5" L x 2.4" W
type triggered by “dry” contact from input source
• Outputs are open collector transistor pulldown DESCRIPTION
type (100mA max each) that provide “wet” voltage
output The FireNET FN-4127-IO is a 16 channel Input/Output
• Simple 4 wire connection to control panel (2 for board that provides powerful input/output expansion &
power, 2 for data) addition to the FireNET system allowing up to thirty two I/O
• All inputs/outputs can be assigned to global boards to be connected to each FireNET panel within the
functions, any event category, and used in network FireNET network. Every I/O board connected to any panel
wide Cause & Effect logic is available to the entire network, which allows for network
wide input/output mapping. Typical uses include graphical
• Can be mounted locally within control panel
LED map displays/annunciators, tabular LED zone display/
enclosure or remotely via FN-ACC accessory
annunciators, input/output logic to & from the fire system
enclosure up to 4000ft from the panel
for secondary use (I/O board points cannot be used for
• Each I/O board has a unique address 1-32 (set via primary fire initiation inputs or notification outputs) such as
DIP switch) on the I/O Comms Bus access control, burglar, CCTV, intercom, voice, or other 3rd
• Input/Outputs are for secondary use, not for party systems. Each channel can be configured to produce
primary fire initiation inputs or notification outputs a variety of input actions or respond to a variety of output
• Two LED’s are provided for communication status categories or logic. All channels can trigger, or react from,
network wide cause and effect logic depending on their
configuration. The flexibility of these boards is further
PRODUCT LISTINGS enhanced by the fact that each of the channels is
UL 864 Category UOJZ CNN: configurable as either an input or an output. Connection
California
Signal System Control Unit can be achieved through a simple two wire RS485
State Fire
S8255 Sub-Assembly Marshal communications protocol and two wire power input. I/O
Vol. 1 NFPA72 compliant boards can be mounted locally in the control panel or
Sec. 2 7170-0410:170 distributed on a bus up to 4,000ft from the panel when
Specifications subject to change without notice. using the FN-ACC accessory enclosure.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0061 01/2008
Hochiki America Corporation Specifications subject to change without notice.
FN-CTM CITY TIE MODULE

SPECIFICATIONS
Operating Voltage 12 ~ 30 VDC
Average Current Consumption 0mA (Standby)
Alarm Current 1A for 0.5 seconds
Ambient Temperature 32°F (0 C) ~ 120°F (49C)
Maximum Humidity 90% RH, non-condensing
Dimensions 4.2"W X 4.7"H X 1.1"D
Weight Approximately 3.0 ounces
Mounting 4" square electrical box

DESCRIPTION

STANDARD FEATURES The FN-CTM City Tie Module is used to connect a


Fire Alarm Control Panel to a Local Energy type City
Tie Monitoring circuit. The FN-CTM City Tie Module
• Interfaces Fire Alarm Control Panels to a Local circuit provides the power necessary to trip the
Energy type City Tie monitoring circuit Master Box Trip Coil when the Fire Alarm Control
• Integrates Fire Alarm Control Panel EOL device Panel goes into alarm.
into module for supervision of interface wiring
• Wide operating voltage The City Tie Circuit is capable of providing 1A for 0.5
• Power limited operation seconds to operate the Master Box Trip Coil. The
• Transient protection wiring is supervised to the Master Box by placing the
Fire Alarm Control Panel EOL device on the terminals
• Terminals accept up to 14 AWG wire
of the FN-CTM City Tie Module.
• Mounts to a standard 4" electrical back box

PRODUCT LISTINGS
UL 864, NFPA 70 & 72: California
Signaling Device State Fire
S8255 Vol. 2 Marshal
7170-0410:170

Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0064 01/2008
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, the Hochiki America FN-CTM City Tie Module.
The module terminal blocks shall be capable of accepting up to 14 AWG wire. The FN-CTM shall be configured
such that the Fire Alarm Control Panel’s EOL (end of line) device connects directly with the FN-CTM to ensure
supervision of the interface wiring. The module shall fit into a standard 4" electrical back box. The FN-CTM shall
be Underwriter’s Laboratories Listed for the intended purpose.

Rear view of FN-CTM City Tie Module

WIRING DIAGRAM

Note: When City Tie wiring leaves


the building, install 26 AWG wire
between the City Tie module and
the Trip Coil. A short length of 24
AWG wire must be used to
interface between the 26 AWG
and the City Tie Module terminal
block. Maximum coil resistance
and wire resistance must not
exceed 30 Ohms.
Ground Wire

Hochiki America Corporation


FN-CTM
City Tie Module
Local Energy SERIAL NO.XXXXX
City Tie
Trip Coil
+
-
City Tie
Hochiki FireNET
+ or

-
NAC Input Compatible UL Listed
E.O.L. DEVICE Fire Alarm Control Panel
EOL
NAC Circuit NAC Circuit
For Proper Installation
S8255 see HA-06-137 Rev 5/06

Signaling Devices Wiring Polarity Shown in


ISSUE NO. BF-8887 Alarm Condition.
U.L. LISTED
E.O.L. DEVICE
FOR FireNET
PART NUMBER
0400-01046
10K OHM 1/4W

All Wiring is Power Limited, Connect only to Power Limited Circuits.


For Use Only With Supervised Circuits.
Hochiki America Corporation FN-CTM City Tie Module Specifications subject to change without notice.
ALK-V PHOTOELECTRIC SMOKE SENSOR
APPLICATION
The HOCHIKI America ALK-V Photoelectric Smoke
Sensor is particularly suited to detecting optically dense
smoke typical of fires involving materials such as soft
furnishings, plastic, foam or other similar materials which
tend to smoulder and produce large visible smoke particles.
Hochiki's unique design allows fast response to flaming
fires as well as smoldering fires while eliminating false
alarms.

OPERATION
The detection chamber consists of a light emitting diode
(LED) and photodiode arrangement. The chamber is
designed such that light emitted by the LED cannot
Shown without base normally reach the photo diode. In the event of fire,
STANDARD FEATURES particles of smoke enter the chamber and scatter the
• Low Profile - Only 2.0" high, including base light. As the smoke level increases, the scattering effect
• Simple and reliable device addressing method increases, causing more light to hit the photodiode. The
chamber contains a unique baffle design which allows
• Automatic compensation for sensor contamination smoke to enter the chamber while preventing external
• Built-in fire test feature light from affecting the photodiode. The photodiode input
• Uses the noise immune Digital Communication level is sampled to sense smoke density.
Protocol (DCP), which utilizes interrupts for fast
response to fires When the smoke density exceeds a preset threshold
• Two built-in power/sensitivity supervision/alarm LED's the sensor transmits an interrupt to the fire control panel
• Non-directional smoke chamber indicating a fire condition. The fire alarm control panel
• Vandal resistant security locking feature can adjust the sensor threshold to compensate for
contamination.
• Removable smoke labyrinth for cleaning or
replacement Up to 127 devices are permitted on each loop. A sensor
• Compatible with the AIE-EA ionization detector & the address can be set by a hand held programming unit.
ATG-EA heat detector The sensor mounts to an electronics free base and
incorporates a locking mechanism for secure installation.
SPECIFICATIONS The base provides mounting slots, terminals for field wiring
Operating Voltage 17-41 VDC and a third contact for a remote indicator/LED. The sensor
Current Consumption incorporates dual LED's for easy viewing of sensor status.
Standby Normal: 390µA (typical)
Average when Polled 2mA ENGINEERING SPECIFICATIONS
Alarm 8mA
Transmission Method DCP - Digital The contractor shall furnish and install where indi-
Communication Protocol cated on the plans, photoelectric sensors HOCHIKI
Maximum Humidity 95% RH Non-Condensing America Model ALK-V. The combination sensor
UL Ambient Installation 32°F to 100° F head and twist lock base shall be UL listed compat-
Temperature Range (0° C to 37.8° C) ible with a UL listed fire alarm control panel.
Operating Temperature 14°F to 122° F
Range (-10° C to 50° C) PRODUCT LISTINGS
Sensitivity Range 0.5 - 3.8%/FT@300FPM
0.5 - 2.74%/FT@2000FPM California
0.5 - 2.68%/FT@4000FPM State Fire
Air Velocity Range 0-4000 fpm Marshal
Color & Case Material Bone PC / ABS Blend S1383 7272-0410:173
Weight 3.4oz (5.1 oz. with 4" base)
Bases 4" YBN-NSA-4
Continued on back.
6" HSB-NSA-6

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0076 04/2008
ENGINEERING SPECIFICATIONS, continued

The base shall permit direct interchange with the HOCHIKI America AIE-EA ionization type smoke sensor, and the
ATG-EA heat sensor.

The sensitivity of the sensor shall be capable of being measured by the control panel.

The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be optional and can be implemented when required.

BASES
The HOCHIKI America YBN-NSA-4 and the HSB-NSA-6 mounting bases are electronics free and are a simple
rugged design with screw terminals for wiring connections. A common mounting base allows sensor interchange
and maintains loop continuity when sensors are removed. A simple anti-tamper head locking system is provided
which is enabled by removing a small plastic tab on the back of the sensor. Once locked, the head can be removed
using a small diameter screw driver.

YBN-NSA-4 Base HSB-NSA-6 Base

TYPICAL WIRING DIAGRAMS

NOTE: Fire alarm control panel compatibility is required for DCP products.
State-of-the-art communications protocol, DCP, allows system components (DCP sensors AIE-EA,
ALK-V and ATG-EA, bases and modules), to be used concurrently in a system's signal conditioning loop.
Hochiki America Corporation ALK-V Specifications subject to change without notice.
ALG-V PHOTOELECTRIC SMOKE SENSOR
APPLICATION
The HOCHIKI America ALG-V Photoelectric Smoke
Sensor is particularly suited to detecting optically dense
smoke typical of fires involving materials such as soft
furnishings, plastic, foam or other similar materials which
tend to smoulder and produce large visible smoke particles.
Hochiki's unique design allows fast response to flaming
fires as well as smoldering fires while eliminating false
alarms.

OPERATION
The detection chamber consists of a light emitting diode
(LED) and photodiode arrangement. The chamber is
designed such that light emitted by the LED cannot
normally reach the photo diode. In the event of fire,
Shown without base particles of smoke enter the chamber and scatter the
light. As the smoke level increases, the scattering effect
STANDARD FEATURES increases, causing more light to hit the photo- diode.
The chamber contains a unique baffle design which allows
• Low Profile - Only 1.97" high, including base smoke to enter the chamber while preventing external
• Simple and reliable device addressing method light from affecting the photodiode. The photodiode input
• Automatic compensation for sensor contamination level is sampled to sense smoke density.
• Built-in optical fire test feature
• Uses the noise immune Digital Communication When the smoke density exceeds a preset threshold
Protocol (DCP), which utilizes interrupts for fast the sensor transmits an interrupt to the fire control panel
indicating a fire condition. The fire alarm control panel
response to fires can adjust the sensor threshold to compensate for
contamination.

SPECIFICATIONS Up to 127 devices are permitted on each loop. A sensor


Operating Voltage 17-41 VDC address can be set by a hand held programming unit.
The sensor mounts to an electronics free base and
Current Consumption incorporates a locking mechanism for secure installation.
Standby Normal: 390µA (typical) The base provides mounting slots, terminals for field wiring
Average when Polled 2mA and a third contact for a remote indicator/LED. The sensor
Alarm 8mA incorporates dual LED's for easy viewing of sensor status.
Transmission Method DCP - Digital
Communication Protocol ENGINEERING SPECIFICATIONS
Maximum Humidity 95% RH Non-Condensing The contractor shall furnish and install where indi-
UL Ambient Installation 32°F to 100° F cated on the plans, photoelectric sensors HOCHIKI
Temperature Range (0° C to 37.8° C) America Model ALG-V. The combination sensor
Operating Temperature 14°F to 122° F head and twist lock base shall be UL listed compat-
ible with a UL listed fire alarm control panel.
Range (-10° C to 50° C)
Air Velocity Range 0-4000 fpm PRODUCT LISTINGS
MEA
Color & Case Material Bone PC / ABS Blend
Weight 3.4oz California
284-91-E Vol. IV
(5.1 oz. with 4" base) State Fire
Bases 4" YBN-NSA-4 Marshal
S1383 7272-0410:149
6" HSB-NSA-6
3022559
Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0021 01/2008
ENGINEERING SPECIFICATIONS, continued

The base shall permit direct interchange with the HOCHIKI America AIE-EA ionization type smoke sensor, and the
ATG-EA heat sensor.

The sensitivity of the sensor shall be capable of being measured by the control panel.

The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The
locking feature shall be optional and can be implemented when required.

BASES
The HOCHIKI America YBN-NSA-4 and the HSB-NSA-6 mounting bases are electronics free and are a simple
rugged design with screw terminals for wiring connections. A common mounting base allows sensor interchange
and maintains loop continuity when sensors are removed. A simple anti-tamper head locking system is provided
which is enabled by removing a small plastic tab on the back of the sensor. Once locked, the head can be removed
using a small diameter screw driver.

YBN-NSA-4 Base HSB-NSA-6 Base

TYPICAL WIRING DIAGRAMS

NOTE: Fire alarm control panel compatibility is required for DCP products.
State-of-the-art communications protocol, DCP, allows system components (DCP sensors AIE-EA,
ALG-V and ATG-EA, bases and modules), to be used concurrently in a system's signal conditioning loop.
Hochiki America Corporation ALG-V Specifications subject to change without notice.
AIE-EA IONIZATION SMOKE SENSOR
APPLICATION
The HOCHIKI America AIE-EA Ionization smoke sensor
has a responsive and highly stable operation that gives
it an extremely wide range of uses. The AIE-EA can be
used in areas where early warning of trouble from super-
heated or flaming combustibles is expected. The AIE-
EA is also constructed to be effectively used where out-
side RFI (Radio Frequency Interference) and other elec-
trical interference is expected to be encountered.

OPERATION
Shown without base
A single radioactive source ionizes two chambers which
causes a small DC current to flow between the elec-
STANDARD FEATURES. trodes in each chamber. Smoke can freely enter the
outer chamber while the inner chamber is virtually sealed
• Low Profile - Only 2.22" high, including base to smoke. Smoke entering the outer chamber causes a
• Simple and reliable device addressing method reduction in the DC current, the imbalance between the
• Automatic compensation for sensor two chambers is proportional to the smoke density. The
contamination two chamber design is utilized to compensate for changes
in atmospheric and environmental conditions. When the
• Built in fire test feature sensed input value exceeds a predetermined threshold,
• Uses the noise immune Digital Communication an interrupt is issued to the control panel indicating a
Protocol (DCP), which utilizes interrupts for fast fire alarm.
response to fires
The fire alarm control panel can adjust the sensor thresh-
old to compensate for contamination. Up to 127 de-
vices are permitted on each loop. A sensor address can
be set by a hand held programming unit. The sensor
SPECIFICATIONS mounts to an electronics free base and incorporates a
Operating Voltage 17-41 VDC locking mechanism for secure installation. The base
Current Consumption provides mounting slots, terminals for field wiring and a
third contact for a remote indicator/LED. The sensor in-
Standby Normal: 350µA (typical) corporates dual LED's for easy viewing of sensor status.
Average when polled 2mA
Alarm 8mA
Transmission Method DCP - Digital ENGINEERING SPECIFICATIONS
Communication Protocol
Maximum Humidity 95% RH Non Condensing The contractor shall furnish and install where indicated
UL Ambient Installation 32°F to 100°F on the plans, dual-chamber, ionization smoke sensor
Temperature Range (0°C to 37.8°C) HOCHIKI America AIE-EA. The combination sensor head
and twist-lock base shall be UL listed compatible with a
Operating Temperature 14°F to 122°F UL listed fire alarm control panel.
Range (-10°C to 50°C)
Radiation Source Americium 241 (0.98µCi) PRODUCT LISTINGS
MEA
Color & Case Material Bone PC / ABS Blend
Weight 4.2oz (5.9 oz. w/ 4" base) California
284-91-E Vol. IV
Base 4" YBN-NSA-4 State Fire
6" HSB-NSA-6 Marshal
S1383 7271-0410:148
3022559
Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0022 01/2008
ENGINEERING SPECIFICATIONS, continued
The base shall permit direct interchange with the HOCHIKI America ALG-V photoelectric sensor and the
ATG-EA heat sensor.

The sensitivity of the sensor shall be capable of being measured by the control panel.

The vandal-resistant, security locking feature shall be used in those areas indicated on the drawing. The
locking feature shall be optional and can be implemented when required.

BASES
The HOCHIKI America HSB-NSA-6 and the YBN-NSA-4 mounting bases are electronics free and are a
simple rugged design with screw terminals for wiring connections. A common mounting base allows
sensor interchange and maintains loop continuity when sensors are removed. A simple anti-tamper head
locking system is provided which is enabled by removing a small plastic tab on the back of the sensor.
Once locked, the head can be removed using a small diameter screw driver.

HSB-NSA-6 Base YBN-NSA-4 Base


TYPICAL WIRING DIAGRAMS

NOTE: Fire alarm control panel compatibility is required for DCP products.
State-of-the-art communications protocol, DCP, allows system components (DCP sensors AIE-EA,
ALG-V and ATG-EA, bases and modules), to be used concurrently in a system's signal conditioning loop.
Hochiki America Corporation • AIE-EA Specifications subject to change without notice.
ATG-EA HEAT SENSOR
APPLICATION
The HOCHIKI America ATG-EA Sensor provides accurate
temperature measurement data to the fire alarm control
panel. This sensor is particularly suited to environments
where smoke detectors are unsuitable because of the
precense of system or cooking fumes such as in a
kitchen.

OPERATION
The ATG-EA Heat sensor incorporates a highly linear
thermistor circuit, with the thermistor mounted externally.
The specially designed cover protects the thermistor
while allowing maximum air flow. The thermistor circuit
produces a voltage proportional to temperature which is
STANDARD FEATURES scaled, and transmitted as a digitally encoded value to
• Low Profile - Only 2.0" high, including base the control panel. When the ambient temperature
• Simple and reliable device addressing method exceeds a pre-programmed threshold (fixed
• Uses the noise immune Digital Communication temperature), the sensor transmits an interrupt to the
Protocol (DCP), which utilizes interrupts for fast control panel indicating a fire alarm. The fire alarm control
response to fires panel can adjust the sensor threshold for different
• Adjustable threshold temperature 135°F - 150°F Standard's requirements.
(determined by panel)
Up to 127 devices are permitted on each loop. A sensor
address can be set by a hand-held programming unit.
The sensor mounts to an electronics free base and in-
SPECIFICATIONS corporates a locking mechanism secure installation. The
Operating Voltage 17-41 VDC base provides mounting slots, terminals for field wiring,
Current Consumption and a third contact for a remote indicator/LED. The sen-
Standby Normal: 350µA (typical) sor incorporates dual LED's for easy viewing of sensor
status.
Average when Polled 2mA
Alarm 8mA
Transmission Method DCP - Digital ENGINEERING SPECIFICATIONS
Communication Protocol
Heat sensors are installed in accordance with NFPA
Maximum Humidity 95% RH Non-Condensing
(National Fire Pretection Association) 72, the UL Listed
UL Ambient Installation 32°F to 115° F
Spacing Requirements and the rules and regulations set
Temperature Range (0° C to 47° C) forth by the local authorities having
Operating Temperature 135°F to 150° F
Range (57.2° C to 65.6° C)
Color & Case Material Bone PC / ABS blend PRODUCT LISTINGS
Weight 3.2oz
California MEA
(4.9 oz. with 4" base) 284-91-E Vol. IV
State Fire
Bases 4" YBN-NSA-4 Marshal
6" HSB-NSA-6 S2966 7270-0410:147
3022559

Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0023 06/2008
ENGINEERING SPECIFICATIONS, continued
jurisdiction. Automatic heat sensors shall be Underwriters Laboratories listed.
The base shall permit direct interchange with the HOCHIKI America AIE-EA ionization type smoke sensor, and the
ALG-V photoelectric smoke sensor.
The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be optional and can be implemented when required.
It shall be possible to perform a functional test of the sensor without generating heat. The test method shall simulate

BASES
The HOCHIKI America HSB-NSA-6 and the YBN-NSA-4 mounting bases are electronic free and are a simple rugged
design with screw terminals for wiring connections. A common mounting base allows sensor interchange and main-
tains loop continuity when sensors are removed. A simple anti-tamper head locking system is provided which is
enabled by removing a small plastic tab on the back of the sensor. Once locked, the head can be removed using a
small diameter screw driver.

(DIAGRAM OF 2 BASES HERE)

HSB-NSA-6 Base YBN-NSA-4 Base

TYPICAL WIRING DIAGRAMS

NOTE: Fire alarm control panel compatibility is required for DCP products.
State-of-the-art communications protocol, DCP, allows system components (DCP sensors AIE-EA,
ALG-V and ATG-EA, bases and modules), to be used concurrently in a system's signal conditioning loop.
Hochiki America Corporation ATG-EA Specifications subject to change without notice.
ANALOG SENSOR BASES
APPLICATION

The HOCHIKI America YBN-NSA-4 and the HSB-NSA-


6 mounting bases are electronics free and contain a
simple rugged design with screw terminals for wiring
connections. A common mounting base allows sensor
interchange and maintains loop continuity when sen-
sors are removed. A simple anti-tamper head locking
system is provided which is enabled by removing a small
plastic tab on the back of the sensor. Once locked, the
head can only be removed using a small diameter screw
driver.
YBN-NSA-4
OPERATION

The YBN-NSA-4 and HSB-NSA-6 are designed specifi-


cally for use with the Hochiki NS Analog models AIE-EA
Ionization Smoke Sensor, ALG-V Photoelectric Smoke
Sensor and ATG-EA Heat Sensor.

The YBN-NSA-4 and HSB-NSA-6 common mounting


bases allows for complete compatibility for all of the
Hochiki NS Series Analog sensors. The bases are
lightweight and very thin, providing a low profile once
installed. The solder-less screw terminals enable quick
and easy wiring connections.

HSB-NSA-6
STANDARD FEATURES
• UL & ULC Listed
• Designed for use with all NS analog sensors.
• Available in 4 and 6 inch models.
• Contains a security locking tab for tamper
protection.
PRODUCT LISTINGS
Underwriters Laboratories: S1383
Underwriters Laboratories of Canada: CS463
SPECIFICATIONS CSFM #: 7300-0410:132
FM#: 3022559
YBN-NSA-4 4 inches
MEA Report #: 284-91-E Vol. IV
HSB-NSA-6 6 inches
Security Feature Plastic Tamper-Lock
Color Bone PC / ABS Blend
Continued on back.
Specifications subject to change without notice.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0013 04/2005
ENGINEERING SPECIFICATIONS

The base shall permit direct interchange with the HOCHIKI America AIE-EA ionization type smoke sensor, ALG-V
photoelectric smoke sensor, and the ATG-EA heat sensor.

The sensitivity of the sensor shall be capable of being measured by the control panel.

The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be optional and can be implemented when required.

It shall be possible to perform a functional test of the sensor without the need of generating smoke. The test method
shall simulate the effects of products of combustion in the chamber to ensure testing of internal circuitry.

TYPICAL WIRING DIAGRAMS

YBN-NSA-4
(+)
U.L.
LISTED
COMPATIBLE
DCP
LOOP (-) 8mA MAX.
OUTPUT
U.L.
LISTED (+)
POWER
LIMITED
SUPPLY 8mA MAX.
OUTPUT

HSB-NSA-6
(+)
U.L.
LISTED
COMPATIBLE
CONTROL (-)
PANEL

U.L.
LISTED
POWER
LIMITED (+)
SUPPLY

8mA MAX. 8mA MAX.


OUTPUT OUTPUT

- OPTIONAL WIRING CONFIGURATIONS FOR REMOTE OUTPUT

NOTE: Fire alarm control panel compatibility is required for DCP products.
State-of-the-art communications protocol, DCP, allows system components (DCP sensors AIE-EA,
ALG-V and ATG-EA, bases and modules), to be used concurrently in a system's signaling line circuit.

Hochiki America Corporation Analog Sensor Bases Specifications subject to change without notice.
ASB - ANALOG SOUNDER BASE

SPECIFICATIONS

Operating Voltage 17 - 41 VDC


SLC Loop Idle Current 110 µA
SLC Loop Max. Alarm Current 110 µA
Aux. Power Supply Voltage 16 - 31 VDC
Device Aux. Power Min. Voltage 15.0 VDC
Aux. Idle Current 550µA
Aux. Max. Alarm Current 18mA
Shown without sensor Shown with sensor Max. Humidity 93%RH (non-condensing)
Sound Pressure Level at 10 ft 85dB
UL Ambient Installation
Temperature Range 32°F (0°C) ~ 100°F (38°C)
STANDARD FEATURES Operating Temperature Range
32°F (0°C) ~ 122°F (50°C)
• Programmable evacuation codes - Continuous, Base Diamater 5.9"
March, ANSI Temporal patterns Base Height (without sensor) 1.3"
• Base learns the sensor address and assumes an Weight 0.455 lb
upper range address (128-254) Compatible Sensors ALG-V, AIE-EA & ATG-EA
• Up to 127 sensors and 127 ASBs can be used on
one SLC loop
• Can be alarmed or reset by zone or by individual
address DESCRIPTION
• ASB SLC loop wire resistance = 50 ohms Max.
(total SLC wire run length)
• High sound pressure level (85dB SPL at 10 feet) The ASB Analog Sounder Base is designed for use
with Hochiki analog style sensors models ALG-V,
AIE-EA, and ATG-EA. Each addressable base is to
be connected to a Hochiki America Corporation DCP
Signaling Line Circuit (SLC). The ASB provides an
audible alarm in the immediate vicinity. Typical
applications are use in hotels, apartments, and
hospitals.

The ASB has a highly configurable programming


algorithm that allows the user to setup groups of
PRODUCT LISTINGS bases for synchronization of modulation tones. Each
Underwriters Laboratories: S1383 device has 16 states that are programmed with the
CSFM #: 7300-0410:161 desired output pattern to be used (e.g., “Temporal” or
“March”) for each state.

Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0056 11/2005
WIRING DIAGRAM

FireNET
CONTROL NEXT DEVICE
8mA Max.
PANEL

LOOP OUT

NEXT DEVICE
(+) FIGURE A

TOP VIEW
8mA MAX.
OUTPUT

NOTE: Class A style 7 wire configuration requires the installation of short circuit isolators (SCI).

DO NOT CONNECT FOR CLASS B (STYLE 4)

LOOP IN
CONNECT FOR CLASS A (STYLE 6 OR 7)
HO HA

HO HA-
CH -0 8-

CH 08
IKI 06 AS

IKI -067 AS
M M
AM 7 R B

AM R B
ER EV.

ER EV
IC A B

IC . B
A
CO

CO
RP

RP
.

.
SC

SC
G

G
TP3

TP
3
F

F
DET

DE
TP

T P1
TS
SC

AUX POWER
TP2

TP
S

S
2
S5

S56
6

S
BLK

BLK
BLK

BLK
RED

RED
C-0103

C-0103
RED

RED
2

2
2

2
RED RED RED

BLACK BLACK BLACK

FIGURE B

BOTTOM VIEW

NUMBER OF BASES PERMITTED


# of Bases Aux. Wire Resistance SLC Wire Resistance
In Alarm (Total SLC Run Lenght) (Total SLC Run Lenght)

127 1.4 ohm 50 ohm


75 2.4 ohm 50 ohm
60 3.0 ohm 50 ohm
50 3.6 ohm 50 ohm
30 6.1 ohm 50 ohm
20 9.1 ohm 50 ohm
15 12.2 ohm 50 ohm
10 18.3 ohm 50 ohm

Hochiki America Corporation ASB Specifications subject to change without notice.


DH-98 ANALOG DUCT DETECTOR
STANDARD FEATURES
• Detects and limits the spread of smoke
throughout building HVAC ducts
• Compatible with building automation and fire
alarm systems
• Installs quickly and easily
• No screens or filters to clean
• Rugged gray steel back box with clear cover
• Accessories - Remote LED alarm
indication capability
• Meets UL 268A Requirements

APPLICATION
The HOCHIKI AMERICA DH-98 Analog duct smoke
Duct housing with an ALG-DH analog detector provides early detection of smoke and
photoelectric sensor. products of combustion present in air moving
through HVAC ducts in Commercial, Industrial and
SPECIFICATIONS Residential applications. The DH-98 is designed to
prevent the recirculation of smoke in areas by the
D uct Detector Model # DH-98-A DH-98-AR
air handling systems, fans and blowers. Complete
Detector Head model ALG-DH systems may be shut down in the event of smoke
Detector Head Type Analog Photoelectric detection. The HOCHIKI AMERICA DH-98-A and
the DH-98-AR operate on a DCP powered loop
Communication DCP Powered Loop (24 VDC source required for DH-98-AR)
DCP Powered Loop DCP Powered Loop/
Input Voltage 24V DC PRODUCT DESCRIPTION
Standby Current 2mAAVG 10mA The DH-98 is designed and built to meet all local
Alarm Current 8mA 55mA requirements, as well as the NFPA regulations re-
2 form C rated at
garding duct smoke detectors. Output terminals
Alarm Contacts N/A are provided for remote accessories such as a
10A@250V AC
Sensitivity Test Method Control Panel horn, strobe, remote status indicators and reset
key switches or push buttons. Air sampling is
Power,Alarm,
Remote Indication Compatibility
Alarm
accomplished by two tubes which protrude into
(Refer to DH-98 Accessories) Horn/Piezo
Test the duct. An exhaust tube of one standard length
Air Velocity 300 to 4000 ft/min.
(7.5") is supplied in the installation kit with the
smoke duct unit. Once the duct width has been
Ambient Temperature 32°F to 120°F (0°C to 49°C)
determined the air intake sampling tubes must be
Humidity 10% to 85% Relative Humidity ordered. Sampling tubes are supplied in three
(non-condensing) standard lengths 2.5 ft., 5 ft. and 10 ft. and cut to
Housing Material 18 G.A. steel backbox, clear plastic cover size to fit the duct.
Finish Grey Paint PRODUCT LISTINGS
Dimensions 91/8"L x 71/4"W x 21/4"H
California MEA
Maximum Net Weight 3lbs. 284-91E Vol. V
State Fire
Sampling Tubes 2.5ft., 5ft. or 10ft. Marshal
S1383 3240-0410:155
Specifications subject to change without notice. 3022559
Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0036 01/2008
PRODUCT DESCRIPTION, continued
Mounting the duct smoke unit is accomplished by the used of a template and 4 sheet metal screws, which are
provided. Mounting can be achieved without the removal of the clear cover which is secured by 4 capture
screws.

The compact DH-98-AR contains 2 sets of form "C" contacts rated at 10 amps.

The pilot and alarm visual indicators, provided on the front of the DH-98-AR duct unit, signal the operating
status of the device. A manual test/ reset switch is located along side the visual indicators.

ENGINEERING SPECIFICATIONS
Air duct smoke detectors shall be HOCHIKI AMERICA DH-98 Series. The detectors shall be listed by Underwriters
Laboratories per UL 268A. The detectors shall operate at air velocities from 300 feet per minute to 4000 feet per
minute.

The duct detector housings shall be of metal construction and complete mechanical installation may be
performed without removal of detector cover. The duct detector shall not require additional filters or screens
which must be maintained. The housing shall contain a base which will accept an analog photoelectric sensor
head. Terminal connections shall be of the screw type and be a minimum of #6 screw. For installations
requiring relay function, terminals shall be provided for remote pilot, remote alarm indication, strobe/ horn and
remote key switch. For installation not requiring relay function, visual indication of alarm and power must be
provided on detector front. A manual reset switch shall be located on front of the device. All wiring must
comply with local codes and regulations.

WIRING DIAGRAMS
ALG-DH ANALOG
DH-98-A SENSOR
1 2 3 4
Note ○ ○ ○ ○ ○ ○ ○ ○ ○ ○

The DH-98-A and DH-98-AR


UL LISTED (-) (+) REMOTE ALARM LED WIRING MUST are not self-contained
CONTROL PANEL HAVE POLARITY AS SHOWN sensors. This product is
LOOP INTERFACE

24 VDC (8mA MAX.)


S (+) compatible only with fire
alarm control panels that
TO NEXT utilize Hochiki's Digital
SENSOR Communications Protocol,
SC (-) DCP. For example the
FireNET Control Panel.

FAN SHUT DOWN EXAMPLE

DH-98-AR OBSERVE POLARITY


FAN
SUPPLY VOLTAGE
INPUT VOLTAGE
24 V.D.C.
10 mA Standby
55mA Alarm

+ -
REMOTE
ADDRESSABLE ALARM
LOOP LED
+
1 2 3 4 5 6 7 8 9 10 11 12
- +
C C
REMOTE
NC NO NC NO
PILOT LED ALARM CONTACTS ALARM CONTACTS
10.0A @ 250VAC 10.0A @ 250VAC

UL LISTED REMOTE TEST


CONTROL PANEL SWITCH
(Test function only. does not reset.)
LOOP INTERFACE

S (+)
TO NEXT SENSOR
ANALOG ADDRESSABLE
OR RETURN
SC (-) FIELD LOOP WIRING
TO CONTROL PANEL
Terminate Remote Accessories as indicated above (if required).
This is not a self-contained stand alone detector.
A U.L. Listed Analog Addressable Fire System is required.

Hochiki America Corporation DH-98 ANALOG DUCT DETECTOR Specifications subject to change without notice.
DH-98 DUCT DETECTOR REMOTE ACCESSORIES
APPLICATION SPECIFICATIONS
The DH-98 Duct Detector Remote Accessories are Power Requirements
designed to be used with the DH-98 Conventional Alarm LED 15 mA
and DH-98 Analog Duct Detectors to provide audible Pilot LED 15 mA
and visual indication as well as remote test/reset Horn 20 mA @ 24 VDC
functions. Sound Pressure
Horn 78 db @ 10 feet
These devices are contructed of brushed stainless Dimensions
steel and mount on a standard single or double gang Single Gang 2.75" (69.85mm) W
backbox. 4.5" (114.3mm) H
Double Gang 4.5" (114.3mm) W
4.5" (114.3mm) H

MS-RA MS-KA/P/R
Functions: Functions:
Remote Alarm LED (red) ALARM
Remote Alarm LED (red)
For Use with: Pilot LED (green)
ALARM
DH-98-I, DH-98-P PILOT
Key-Operated Test/Reset
DH-98-HVI, DH-98-HVP Switch
DH-98-A, DH-98-AR For Use with:
TEST/RESET
DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP

MS-KA/R MS-RA/R
Functions: Functions:
ALARM Remote Alarm LED (red) Remote Alarm LED (red)
Key-Operated Test/Reset ALARM
Push-button Test/Reset
Switch Switch
For Use with: For Use with:
DH-98-I, DH-98-P TEST/RESET DH-98-I, DH-98-P
TEST/RESET
DH-98-HVI, DH-98-HVP DH-98-HVI, DH-98-HVP
DH-98-AR DH-98-AR

MS-RA/P MS-RA/P/R
Functions: Functions:
Remote Alarm LED (red) Remote Alarm LED (red)
ALARM
ALARM Pilot LED (green) Pilot LED (green)
For Use with: Push-button Test/Reset
PILOT
DH-98-I, DH-98-P Switch
PILOT DH-98-HVI, DH-98-HVP For Use with:
TEST/RESET DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 01/2004
MS-RH/KA/P/R
Functions:
Remote Alarm Horn
ALARM
Remote Alarm LED (red)
Pilot LED (green)
PILOT Key-Operated Test/Reset
Switch
TEST/RESET
For Use with:
DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP

WIRING DIAGRAM
RED
RED

RED GREEN
ALARM
24VDC PILOT
24VDC ALARM HORN
LED LED

BLACK
BLACK
ALARM
PILOT

BLACK

KEY OR
PUSH BUTTON
24VDC
"TEST/RESET"
SWITCH

BLACK

TEST/RESET

PRODUCT SPECIFICATIONS
PUSH KEY
PILOT ALARM BUTTON OPERATED
LED LED TEST/ TEST/ SINGLE DOUBLE
(GREEN) (RED) RESET RESET HORN GANG GANG
MODEL #
MS-RA
MS-RA/P
MS-RA/R
MS-RA/P/R
MS-KA/R
MS-KA/P/R
MS-RH/KA/P/R

Hochiki America Corporation DH-98 Duct Detector Remote Accessories Specifications subject to change without notice.
SOM - SUPERVISED OUTPUT MODULE

SPECIFICATIONS
Supply Voltage (S-SC) 17-41 VDC
Auxiliary Supply Voltage 18-30 VDC
Average Current Consumption Normal 220 µA
(on S-SC Line) Maximum 300 µA
Current Consumption on
Auxiliary Power Lines Typical 150 µA
Dimensions 4.2"W x 4.7"H x 1.4"D
Ambient Temperature 32°F (0°C) ~ 120°F (49°C)
Mounting 4" square electrical box
Maximum Output Current 2A@30VDC power limited
Relative Humidity 90% RH Non-condensing

STANDARD FEATURES
• Flexible application DESCRIPTION
• Quick response to emergency conditions
The Supervised Output Module (SOM), has been
• Operation parameters are maintained by the designed to provide application flexibility and quick
module, and individual communication with the response to emergency conditions. Flexibility is
control system during emergency conditions provided by a wide range of operating modes, including
is not required
supporting multi-zone operations, and/or functions, up
• Contacts are rated 2.0 Amps @ 30VDC to 16 different modulation patterns and multi-state
• Programming is highly flexible providing 16 programming. The operating parameters for the SOM
priority states plus zoning capability are maintained by the module and do not require
Program status: individual communication with the control system
• LED will flash red or green during emergency conditions to operate. The control
• Programmed device output is turned off, silenced, panel simply broadcasts system conditions on the
or programmed to modulate pattern Signaling Line Circuit (SLC) and the SOMs do the rest
based upon the custom configuration. Each SOM
provides a Class B Individual Circuit rated for 2.0 Amp
PRODUCT LISTINGS @ 30 VDC. Each SOM also requires a 24 Volt power
source in addition to the SLC. Provide software
controlled LED indication: blinks green or red when
polled, or can be latched on.
CS943 3022559
S5694
California
MEA State Fire
Marshal
284-91-E Vol. IV
7300-0410:150

Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0057 02/2008
ENGINEERING SPECIFICATIONS

The contractor shall furnish and install where indicated on the plans, addressable Supervised Output Module (SOM).
The modules shall be UL listed and compatible with Hochiki FireNET fire alarm control panel. The device address
shall be electrically programmable and stored in EEPROM. A bi-colored LED shall indicate device status.
The SOM shall be supplied with a plastic cover and shall be suitable for mounting to a 4" square or double gang
electrical back box. The SOM shall provide a monitor LED that is visible from outside the cover plate.

Back side of a SOM

WIRING DIAGRAM
U.L. LISTED
0400-01046
DEVICE
NOTIFICATION APPLIANCE CIRCUIT (NAC) E.O.L. DEVICE
E.O.L.

NAC INSTALLATION WIRING SHALL NOT EXCEED PART NUMBER


50 OHMS (14-18 AWG.) 0400-01046

OUTPUT TO
COMPATIBLE
U.L. LISTED
DEVICES FOR
FIRE
PROTECTION
SIGNALING
SERVICE

DCP-SOM
OUT TO NEXT MODULE SER. NO. XXXXXXXXX TB2
U.L. LISTED REGULATED,
TB1 OUT TO POWER LIMITED SUPPLY FOR
2

24+
FIRE PROTECTION
NEXT SIGNALING SERVICE FOR
U.L. LISTED
SC MODULE AUDIBLE DEVICES. REFER
COMPATIBLE GND
TO CONTROL PANEL
FIRE CONTROL S MANUFACTURER'S
INSTALLATION
PANEL OUT+ INSTRUCTIONS.
1

ALL WIRING SHOWN ON TB1 OUT -


S5694
IS SUPERVISED AND
INHERENTLY POWER LIMITED SIGNALING DEVICE ALL WIRING SHOWN ON TB2
ISSUE NO. AH-9758 IS SUPERVISED AND
INHERENTLY POWER LIMITED

WARNING!!!
USE ONLY FPL, FPLR, OR
FPLP WIRING IN ACCORDANCE
WITH ARTICLE 760 OF THE
NATIONAL ELECTRICAL CODE.

Hochiki America Corporation SOM Specifications subject to change without notice.


DCP-FRCME - FAST RESPONSE CONTACT MODULE
SPECIFICATIONS
Operating Voltage DCP Powered Loop 17~41 VDC
Average Current Consumption 550 µA (Typical)
Alarm Current 8mA
Dimensions
FRCME-4 4.2"W x 4.7"H x 1.4"D
FRCME-P 3.0"W x 1.9"H x 0.5"D
FRCME- S 2.8"W x 1.8"H x 0.7"D
Ambient Temperature 32°F (0°C) ~ 120°F (49°C)
Max. Humidity 90% RH, non-condensing
Mounting
FRCME-4
Mounts to double gang/4" square back box
FRCME-S/FRCME-P
FRCME-4 Mounts inside a single gang back box

STANDARD FEATURES DESCRIPTION


The Hochiki FRCME Fast Response Contact Monitoring
• Single input contact monitor Modules are designed to be used with pull stations, water
• Fast, reliable contact monitoring utilizing the flow switches, and other applications requiring the moni-
Hochiki DCP (Digital Communications Protocol) toring of dry contact alarm initiating devices. The interrupt
driven Digital Communications Protocol (DCP) combines
• Two different mounting configurations
maximum communication reliability and fast response to
• 127 devices can be used per DCP loop emergency conditions. Two different mounting configura-
• Bi-colored indicating LED provides module status tions are provided to meet a wide range of applications.
(FRCME-4 only) The FRCME contact monitoring module does not require a
separate 24 VDC power source.
• Can be programmed to monitor Normally Open
(NO) or Normally Closed (NC) contacts Each addressable contact monitoring module is
programmed with its own unique Signaling Line Circuit
• Operates on Class A or Class B SLC loop
(SLC) loop address. The device address is electrically
• Accepts up to 14 AWG wire programmable and stored in onboard EEPROM. Up to
• UL listed UL 864 127 devices can be placed on the Hochiki DCP SLC loop.
The module supervises the wiring to the contact with an
End Of Line (EOL) resistor. It can be programmed to monitor
Normally Open (NO) or Normally Closed (NC) contacts. If
PRODUCT LISTINGS a fault condition occurs in the wiring, the module sends a
FRCME-4/ trouble status signal to the fire alarm control panel. When
a change of status (contact changes state) is sensed by
FRCME-S only
the FRCME, it sends an interrupt to the FireNET control
3022559 panel indicating that an alarm has occurred.
S5694
The FRCME-P and FRCME-S are small package designs
California and are suitable for mounting in a small junction box behind
CS943
State Fire a pull station or other monitored device.
MEA Marshal
7300-0410:150 The FRCME-4 is mounted to a cover plate for a 4" square or
284-91-E Vol. IV double gang junction box. It contains a visible bi-colored
indicating LED to provide module status.
Specifications subject to change without notice.
Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0002 02/2008
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, addressable contact monitoring modules Hochiki
DCP-FRCME-4, DCP-FRCME-S and FRCME-P. The modules shall be UL listed and compatible with the Hochiki
FireNET fire alarm control panel. The device address shall be electrically programmable and stored in EEPROM.

The FRCME-S and FRCME-P shall fit inside a single gang electrical back box. The FRCME-4 shall be supplied with a
plastic face plate and shall be suitable for mounting to a 4" square or double gang electrical back box. The FRCME-4
shall provide a monitor LED that is visible through the face plate.

FRCME-4 FRCME-S FRCME-P


OUT TO
NEXT
MODULE
TYPICAL WIRING FOR N/O CONTACTS ONLY

WIRING DIAGRAM U.L. LISTED


SER. NO. XXXXXXXXX

E.O.L. DEVICE
DCP-FRCME-4
SIGNALING DEVICE
ISSUE NO. AH-9755

S+ PART NUMBER
COMPATIBLE
0400-01046
SC- CONTROL
IN-A PANEL
S5694

FRCME-4/FRCME-S IN-B

ANY NUMBER OF UL LISTED N/O CONTACT CLOSURE


DEVICES MAY BE USED . DO NOT MIX FIRE ALARM U.L. LISTED
INITIATING OR SUPERVISORY ON THE SAME MODULE E.O.L. DEVICE
PART NUMBER
0400-01046
ALL WIRING SHOWN IS SUPERVISED
AND INHERENTLY POWER LIMITED.

OUT TO
NEXT
MODULE

U.L. LISTED
SER. NO. XXXXXXXXX
DCP-FRCME-4
SIGNALING DEVICE
ISSUE NO. AH-9755

S+ COMPATIBLE
SC- CONTROL
PANEL
IN-A
S5694

IN-B

TYPICAL WIRING FOR N/C CONTACTS ONLY

E.O.L. DEVICE U.L. LISTED


ALL WIRING SHOWN IS SUPERVISED PART NUMBER E.O.L. DEVICE
0400-01046
AND INHERENTLY POWER LIMITED. PART NUMBER
0400-01046

CAUTION!
DO NOT CONNECT MORE THAN ONE N/C CONTACT TO AN INPUT.
FRCME-P OUT TO
NEXT
MODULE TYPICAL WIRING FOR N/O CONTACTS ONLY
S SC

S U.L. LISTED E.O.L. DEVICE


S (OUT)
COMPATIBLE PART NUMBER
SIGNALING DEVICE

DCP-FRCME-P

0400-01046
ISSUE NO. AH-9765

SER. NO. XXXXXXXXX

RED

SC CONTROL
S (IN)

PANEL
SC (OUT)
BLK
SC (IN)
S5694

IN-A
WHT
IN-B

ANY NUMBER OF UL LISTED N/O CONTACT CLOSURE


DEVICES MAY BE USED . DO NOT MIX FIRE ALARM U.L. LISTED
ALL WIRING SHOWN IS SUPERVISED INITIATING OR SUPERVISORY ON THE SAME MODULE E.O.L. DEVICE
AND INHERENTLY POWER LIMITED. PART NUMBER
OUT TO 0400-01046
NEXT
MODULE
S SC

S U.L. LISTED
S (OUT)
COMPATIBLE
SIGNALING DEVICE

DCP-FRCME-P
ISSUE NO. AH-9765

SER. NO. XXXXXXXXX

RED

SC CONTROL
S (IN)

PANEL
SC (OUT)
BLK
SC (IN)
IN-A
S5694

WHT
IN-B

ALL WIRING SHOWN IS SUPERVISED


AND INHERENTLY POWER LIMITED. TYPICAL WIRING FOR N/C CONTACTS ONLY

E.O.L. DEVICE U.L. LISTED


PART NUMBER
0400-01046
E.O.L. DEVICE
PART NUMBER
0400-01046

CAUTION!
DO NOT CONNECT MORE THAN ONE N/C CONTACT TO AN INPUT.

Hochiki America Corporation DCP-FRCME Specifications subject to change without notice.


SCI - SHORT CIRCUIT ISOLATOR
OPERATION

* Class A Configuration Wiring:


The DCP-SCI short circuit isolator should be located
between any devices on the SLC loop. In the event of
a short on the SLC loop, the two adjacent isolators
(closest isolators to the left and right of the shorted
section) will activate and their respective LED indica-
tors will be turned on. All devices between the active
short circuit isolators will be dead. This will prevent
entire loop failure. Upon removal of the short condi-
tion, the DCP-SCIs will automatically restore, the
entire loop to the normal operating state.

* Class B Configuration Wiring:


The DCP-SCI short circuit isolator should be located
between any devices on the SLC loop. In the event of
STANDARD FEATURES a short on SLC loop, an isolator closest to the shorted
section will activate and the LED will be turned on. All
• Can be placed at any location on SLC loop the devices beyond the shorted section will be
• Checks the line for short circuit at power up. If the disabled. Upon removal of the short condition, the
line is normal, the relay will be returned on. If a DCP-SCI will automatically restore the entire loop to
line short is detected, the relay remains open the normal operating state.
• Indication of short circuit by a yellow LED
For the best performance of DCP-SCI short circuit,
use class A configuration.
SPECIFICATIONS
WIRING:
Absolute Max. Applied Voltage S, SC: 41 VDC Note: All wiring must conform to local codes, ordi-
Supply Voltage Norminal S, SC: 33 VDC nances and regulations.
Normal Current Consumption 270 µA (Typical) 1. Install module wiring in accordance with job draw-
ings and appropriate wiring diagram.
Active Current Consumption 10 mA (Typical)
2. Secure the module to an approved electrical box
(Short Circuit Condition) (supplied by installer).
Dimensions 4.2"W x 4.7"H x 1.4"D
Weight 1.4 oz MOUNTING REQUIREMENTS: 4" SQ Electrical box.
Visual Indicator (Yellow Status LED)
- No indication in normal condition. PRODUCT LISTINGS
- On steady in active (short) condition.
California
Maximum Quantity Per Loop 127 State Fire
Operation Temperature Range Marshal
0ºC (32ºF)~ 49ºC (120ºF) Non-condensing S5694 CS943 7300-0410:150
Allowable Ambient Humidity MEA
90% Non-condensing 284-91-E Vol. IV

Specifications subject to change without notice.


Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0008 02/2008
ENGINEERING SPECIFICATIONS

The contractor shall furnish and install where indicated on the plans, the Hochiki DCP-SCI short circuit isolator. The
modules shall be UL listed compatible with Hochiki Digital Communications Protocol (DCP) supporting control panel
loops. The isolator module must be suitable for mounting in a standard 4" square electrical box. The isolator
module must provide a yellow LED for indication of status.

Back side of a DCP-SCI

WIRING DIAGRAM

TB1
SER. NO. XXXXXXXXX

UL LISTED
SIGNALING DEVICE
ISSUE NO. AH-9774

(IN) S
DCP-SCI

(IN) SC

(OUT) SC
(OUT) S
COMPATIBLE
S5694

CONTROL
PANEL

SHORT CIRCUIT ISOLATOR


--
SER. NO. XXXXXXXXX

TB1
SIGNALING DEVICE
ISSUE NO. AH-9774
LISTED

(IN) S
DCP-SCI

(IN) SC
(OUT) S
GROUP OF VARIOUS DCP MODULES
(OUT) SC

-
S5694

OPTIONAL RETURN LINE


GROUP OF VARIOUS DCP SENSORS (NOT REQUIRED)
++ +

SHORT CIRCUIT ISOLATOR


TB1

(OUT) SC
(OUT) S
(IN) SC
(IN) S

SER. NO. XXXXXXXXX


DCP-SCI
ISSUE NO. AH-9774
SIGNALING DEVICE
LISTED
S5694

SHORT CIRCUIT ISOLATOR

TYPICAL WIRING DIAGRAM EXAMPLE, CONNECTED ALL WIRING SHOWN IS SUPERVISED


AND INHERENTLY POWER LIMITED.
TO A COMPATIBLE LISTED CONTROL PANEL ANY COMBINATION OF MODULES
AND/OR SENSORS MAY BE PLACED
BETWEEN ISOLATORS

Hochiki America Corporation DCP-SCI Specifications subject to change without notice.


DCP-R2M - DUAL RELAY MODULE

SPECIFICATIONS
Contacts 2 Independenly Controlled Form C
Contact Rating 1A @ 30 VDC / 0.5A @ 125 VAC
Standby Current 150 µA Max.
Alarm Current 150 µA Max.
Dimensions 4.2"W x 4.7"H x 1.4"D
Ambient Temperature 32°F (0°C) ~ 120°F (49°C)
Humidity 90% RH, Non-Condensing
Mounting 4" square electrical box

DESCRIPTION
STANDARD FEATURES
The Dual Relay Module (R2M), has been designed to
• Provides two independently configurable Form C provide flexibile and quick response to emergency
contacts per address conditions. The R2M allows independent control of
• Contacts are rated 1.0 Amps @ 30 VDC or two form C contacts for a variety of normally open and
0.5 Amp @ 125 VAC normally closed contact applications such as fan
• Up to127 devices can be used on each SLC loop operation, elevator recall, door closure, and auxiliary
notification.
• Visible Bi-colored LED is software controlled and
can be programmed to blink red or green when
Each R2M module provides independent control of two
polled. The LED can be latched on when activated
Form C contacts while utilizing one SLC (Signaling
• Programming is highly flexible providing 16 priority Line Circuit) address. The R2M module has a highly
states plus zoning capability configurable programming algorithm that allows the
user to setup groups of devices (zoning) for simulta-
neous operation of multiple R2M modules. Each
module has 16 priority states that are programmed.
PRODUCT LISTINGS The operating parameters are maintained by the
module and do not require individual communication
with the control panel during the emergency condition
to operate. The control panel broadcasts the control
3022559 command on the SLC loop and the R2M modules do
S5694 CS943
the rest based on their custom configuration. Since
mechanically latching relays are used within the R2M
MEA California
State Fire
module, a separate 24VDC power source is not
284-91-E Vol. IV required.
Marshal
7300-0410:150

Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0058 02/2008
ENGINEERING SPECIFICATIONS

The contractor shall furnish and install where indicated on the plans, the Hochiki DCP-R2M addressable relay
module. The modules shall be UL listed compatible with Hochiki Digital Communications Protocol (DCP) supporting
control panel loops. The relay module must provide two Form C dry contacts rated at 1A @ 30 VDC or 0.5A @ 125
VAC. The relay module must be suitable for mounting in a standard 4" square electrical box. The relay module
must provide a bi-colored LED for indication of status.

Back side of a R2M

WIRING DIAGRAM

DCP-R2M NO1
OUT TO NEXT MODULE S, SC WIRING SERIAL NO. XXXXXXXXX
POWER LIMITED
COM1 SET 1
2

TB1
POWER
LIMITED

U.L. LISTED SC - NON NC1 (FORM "C" CONTACTS)


POWER
COMPATIBLE LIMITED (NON-SUPERVISED)
FIRE CONTROL S + NO2
PANEL CROSS OUT
1

TYPE NOT
USED
COM2 SET 2

S5694
NC2
SIGNALING DEVICE
ISSUE NO. AH-9769 B

Hochiki America Corporation DCP-R2M Specifications subject to change without notice.


DIMM - DUAL INPUT MONITOR MODULE

SPECIFICATIONS
Operating Voltage 17~41 VDC
Average Current Consumption 600µA(Typical)
Alarm Current 30mA
Dimensons 4.2"W x 4.7"H x 1.4"D
Ambient Temperature 32°F (0°C) ~ 120°F (49°C)
Max. Humidity 90% RH, non-condensing
Mounting 4" square electrical box

DESCRIPTION
STANDARD FEATURES
The Hochiki Dual Monitor Module (DIMM) is designed
• Fast, reliable contact monitoring utilizing the for use on the FireNET analog addressable system.
Hochiki DCP (Digital Communications Protocol) It provides two independent contact monitoring cir-
• 127 devices can be used per DCP loop cuits while only utilizing one address on the SLC loop.
Up to 127 devices can be placed on a single SLC
• Bi-colored indicating LED provides module status loop. The device address is uniquely stored on an
• Dual input contact monitor onboard EEPROM. The module can be programmed
to monitor Normally Open (NO) or Normally Closed
• Can be programmed to monitor Normally Open (NC) contact fire alarm and supervisory devices. The
(NO) or Normally Closed (NC) contacts interrupt driven Digital Communication Protocol (DCP)
• Operates on Class A or Class B SLC loop combines maximum communication reliability and
fast response to emergency conditions. The module
• Accepts up to 14 AWG wire
has a single bi-colored LED to indicate device sta-
• Mounts to 4" square gang box tus. It fits into a standard 4" square or double gang
electrical back box.

PRODUCT LISTINGS
California
State Fire
Marshal
S5694 7300-0410:150

Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0003 02/2008
ENGINEERING SPECIFICATIONS

The contractor shall furnish and install where indicated on the plans, addressable contact monitoring modules
Hochiki DIMM. The modules shall be UL listed and compatible with the Hochiki FireNET fire alarm control panel.
The device address shall be electrically programmable and stored in EEPROM. A bi-colored LED shall indicate
device status.

Back Side of a DIMM

WIRING DIAGRAM

U.L. LISTED
E.O.L. DEVICE 22K DCP-DIMM OUT TO NEXT MODULE
PART NUMBER Dual Input Monitor Module
0400-01000 TB2
TYPICAL WIRING FOR N/O CONTACTS ONLY
SER. NO. XXXXXXXXX -
+ +
TB1
Input A
E.O.L. DEVICE 22K
PART NUMBER
0400-01000 - S + + U.L. LISTED
COMPATIBLE
+ SC - - FIRE CONTROL
ANY NUMBER OF UL LISTED N/O CONTACT CLOSURE
DEVICES MAY BE USED . Input B PANEL
-
TYPICAL WIRING FOR N/C CONTACTS ONLY
S5694

SIGNALING DEVICE AND INHERENTLY POWER LIMITED.


U.L. LISTED ISSUE NO. AU-6031
E.O.L. DEVICE 22K
E.O.L. DEVICE 22K PART NUMBER
0400-01000
PART NUMBER
0400-01000

CAUTION!
DO NOT CONNECT MORE
THAN ONE N/C CONTACT
TO AN INPUT!

Hochiki America Corporation DIMM Specifications subject to change without notice.


CZM - CONVENTIONAL ZONE MODULE
SPECIFICATIONS
Operating Voltage 17~41 VDC
Auxiliary Supply Voltage Nominal 18.8~27.2 V
Average Current Consumption (From S-SC)
Typical Quiescent 400µA
2-Wire Detector Loop Current
Standby Detector Load 1mA Max
From Auxiliary Supply
Alarm (Short across detector line) 60mA Max
Data Transmission Current 22mA ± 20%
EOL Device 4.7K Ohms
Alarm Threshold Level <1.5K Ohms
Wiring OK Threshold Level
>2.5K Ohms & <6K Ohms
STANDARD FEATURES Open Circuit Threshold Level >10K Ohms
Max. 2-Wire Conventional Detector
• Provides an address point for a zone of up to 25 Loop Resistance 50 Ohms (total SLC run length)
conventional smoke detectors Operating Temperature
• Blinks green when polled. Latched on red (con
Range 32°F (0°C) ~ 120°F (49°C)
trolled by panel) when activated
• Device address can also be programmed with a
handheld programmer. Device address- ranges DESCRIPTION
from 1 to 127
The Hochiki Conventional Zone Module (CZM) is
• Compatible with Class B (Style B) and Class A (Style designed for use on the FireNET analog addressable
D) wiring
system. Up to 127 devices can be placed on a single
• Auxiliary power source provides power for the zone SLC loop. The device address is uniquely stored on an
of detectors onboard EEPROM. The module allows the panel to
• Compatible with conventional detectors, SLR, SIJ, interface and monitor dry contacts such as two-wire
SLK and SIH series conventional detectors or pull stations. Each CZM is
addressed through the panel and transmits the status
of one zone of devices (25 maximum per zone) back
to the panel. It supervises the power supply as well
PRODUCT LISTINGS as the entire zone of devices. Status conditions are
reported as normal, open or alarm. All 2-wire smoke
California detectors must be UL listed as compatible to be
State Fire interfaced with the CZM. The interrupt driven Digital
Marshal Communication Protocol (DCP) combines maximum
S5694 7300-0410:150 communication reliability and fast response to emer-
gency conditions. The module has a single bi-colored
LED to indicate device status. It fits into a standard 4"
square or double gang electrical back box.
Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0004 02/2008
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Conventional Zone Module (CZM). The
modules shall be UL listed and compatible with the Hochiki America Analog Control Panel Protocol. The device
address shall be electrically programmable and stored in EEPROM. A bi-colored LED shall indicate device status.
The CZM shall be supplied with a plastic cover and shall be suitable for mounting to a 4" square or double gang
electrical back box. The CZM shall provide a monitor LED that is visible from outside the cover plate.

LIST OF COMPATIBLE DEVICES


Detector Model Detector Type Base Model

SLK-24F Photoelectric HSB-224

SIH-24F Ionization HSB-224


SLR-24H Photoelectric w/heat NS4-224, NS6-224
SLR-24V Photoelectric NS4-224, NS6-224
SLR-835/-835W Photoelectric (8-35V) NS4-224, NS6-224
NS4-224W, NS6-224W
Photoelectric (8-35V) NS4-224, NS6-224
SLR-835H/-835HW
w/thermal NS4-224W, NS6-224W
SLR-835B-2 Photoelectric (8-35V) (baseless) N/A

Photoelectric (8-35V) N/A


SLR-835BH-2 w/thermal (baseless)
SIJ-24 Ionization NS4-224, NS6-224

DCD-135/-190 Heat Fixed Temp/Rate of Rise NS4-224, NS6-224

DFE-135/-190 Heat Fixed Temp HSC-224L


Back side of a CZM
EXPLODED VIEW
NFPA STYLE D WIRING DIAGRAM

3-4: CLASS A

OPTIONAL BRANCH
CIRCUIT TO NEXT
INTERFACE MODULE.
JP2
MODULE SUPERVISES
SUPPLY VOLTAGE AND CZM CLASS A
DETECTOR LOOP. Conventional Zone Module
S SC SER. NO. XXXXXXXXX NOTE: ENSURE JUMPER IS IN CORRECT POSITION
TB1 TB2
U.L. LISTED FOR WIRING CONFIGURATION. (POSITION 3-4)
COMPATIBLE SC SC IN+
FIRE CONTROL S
PANEL S IN-
24V- OUT+
UL LISTED 24VDC -
24V+ OUT-
POWER LIMITED +
AND REGULATED MAX. 25 CONVENTIONAL
POWER SUPPLY, DETECTORS
LISTED FOR FIRE 24- 24V+
PROTECTION S5694
NEXT DEVICE ALL WIRING IS SUPERVISED AND POWER LIMTED.
WITH BATTERY
BACKUP. SIGNALING DEVICE
ISSUE NO. AU-6110 EB
DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR
SECURITY DEVICES ON THE SAME MODULE.

NFPA STYLE B WIRING DIAGRAM EXPLODED VIEW

1-2: CLASS B

OPTIONAL BRANCH
CIRCUIT TO NEXT
INTERFACE MODULE.
MODULE SUPERVISES
SUPPLY VOLTAGE AND CZM JP2
CLASS B
DETECTOR LOOP. Conventional Zone Module
S SC
TB1 SER. NO. XXXXXXXXX TB2
NOTE: ENSURE JUMPER IS IN CORRECT POSITION
U.L. LISTED FOR WIRING CONFIGURATION. (POSITION 1-2)
COMPATIBLE SC SC IN+
FIRE CONTROL S
PANEL S IN-
24V- OUT+ U.L. LISTED
UL LISTED 24VDC - E.O.L. DEVICE 4.7K
PART NUMBER
0400-01820
E.O.L. DEVICE 4.7K
24V+ OUT- PART NUMBER
POWER LIMITED +
MAX. 25 CONVENTIONAL 0400-01820
AND REGULATED
POWER SUPPLY, DETECTORS
LISTED FOR FIRE 24- 24V+
PROTECTION S5694
NEXT DEVICE
WITH BATTERY
BACKUP. SIGNALING DEVICE
EB
ISSUE NO. AU-6110 ALL WIRING IS SUPERVISED AND POWER LIMTED.

DO NOT MIX FIRE ALARM INITIATING, SUPERVISORY, OR


SECURITY DEVICES ON THE SAME MODULE.

Hochiki America Corporation CZM Specifications subject to change without notice.


Features:
True Multiplex 6 Channel Distributed Audio
Integrated Fire Phone, Area of Rescue VoiceNET
and Fan & Damper Control capability
Modular System - components added as needed
High Rise Voice
Integrated 2 Channel Digital Message Repeater
Live Microphone Page to any zone
Evacuation System
Fast RS-485 Communication Protocol SYSTEM

Fully Supervised RESET

Easy Installation and Operation


PAGE
ALL-CALL

Natural Sound Voice Recordings FAULT


SILENCE PAGING
CONTROL
Built in Alarm and Alert Signals
Up to 4 Minute Message Capacity
Works with 12VDC or 24VDC Fire Alarm Panel
Works with Analog/Addressable and
Microprocessor based Fire Alarm Panels.
3 Minute Message Restart on Microphone Key
Made in the USA.

277-96-E
6911-1446:103
LISTED
Description: #S5661
The Hochiki VoiceNET High Rise Evacuation
System operates in conjunction with the Fire Alarm
Control Panel (FACP) in a building to provide
automatic response to life safety emergencies.

The Hochiki VoiceNET includes all necessary


features to provide an effective voice evacuation
system. The Hochiki VoiceNET can be custom
configured to satisfy the needs of any high rise
application.
System Configuration:
Fire department authorities can easily take Basic System Includes:
command of evacuation or relocation procedures Master Panel (FNV-MP)
and emergencies. Building management and fire Master Mic Control
brigades can monitor and control emergency 16 switch control points
response even before the professionals arrive Dual Channel DMR
High speed communication loop
The VoiceNET system includes capacity for 6 Distributed Panel (FNV-DP)
channels of simultaneous audio. This provides for 4 Output Zones (may be configured for 8)
evacuation, stay-in-place, or other public address Dual Channel Audio Interface
announcements and automatic messages. Dual Channel Amplification
Optional
Fire Fighter Phones or Warden Stations may be Integrated Fire Phone
included as required. Area-of-Rescue stations can Area-of-Rescue
Number of distributed panels to be
reassure handicapped occupants that help is on Determined by building specifications
the way.
Maximum System Configuration
Up to 256 Distributed Panels (FNV-DP)
And up to 2028 monitor and control points

7051 Village Drive, Suite 100 Buena Park, CA 90621-2268 714.522.2246 www.hochiki.com
FNV-DP Voice Evacuation
Speaker Circuits
Distributed Panel
#18 AWG
F
I
R
E

F
I
R
E

F
I
R

Hochiki VoiceNET
E

F
I

True-Multiplex
R
E

TB1 TB1
TB2 TB2

#22 AWG Twisted Pair

System
TB3 TB3

Fire Phone

Fire Fire

Capabilities FNV-25/50/100 FNV-25/50/100


Phone Phone

NetComm Loop:
-Twisted Pair, Category 5
-4,000 Feet between panels
-50,000 Feet Total System Loop
-Data and 6 Audio Channels Simultaneously
-High Speed RS-485 Communications
-Style “4” or Style “7” Field Selectable

FNV-DP
Distributed Panel Voice Evacuation
Speaker Circuits

Head End Control F


I
R
E

F
FNV-MP I
R
E

Master Panel
F
I
R
E

PAGING F
CONTROL
I
R
E

TB1 TB1
TB2 TB2

TB3 TB3

Fire Phone

Fire Fire

FNV-25/50/100 FNV-25/50/100
Phone Phone

FIRE PHONE CONTROL


Hochiki VoiceNET
High Rise Multiplex
11 Floor Typical Riser Diagram

11th Floor S S
P
AR

S S
10th Floor
P
AR

S S
9th Floor CM FNV-DP
P
AR

S S
8th Floor
P
AR

S S
7th Floor
P
AR

S S
6th Floor
P
AR

S S
5th Floor CM FNV-DP
P
AR

S S
4th Floor
P
AR

S S
3rd Floor P
AR

RS 485
DATA LOOP S S
2nd Floor
P
AR

S S
1st Floor FNV-MP FNV-DP
P

S S
Basement
P

S Speaker, Speaker/Strobe AR Area of Rescue Station


P Fire Fighter Phone Jack

7051 Village Drive, Suite 100


Buena Park, CA 90621-2268
Engineering Specifications
Hochiki VoiceNET High Rise

The voice evacuation system shall be Hochiki Series VoiceNET FNV High Rise or approved
equal.

The VoiceNET FNV system shall include one Master Panel and one or more Distributed
Panels. The system shall be microprocessor based, and shall be compatible for use with
contact closures from the Fire Alarm Control Panel, (FACP). The system shall have a high-
speed communication bus and have the capacity for 6 channels of audio and data on a single
pair of wires. The field wiring for the communication bus may be configured for either Style "4"
or Style "7" supervision. The system shall have the capacity for Fire Fighters Phone, Area-of-
Rescue communication and also have the capacity for Fan & Damper control with monitored
feedback. The system shall have a minimum capacity of 2028 monitor and control points.

The Master Panel shall contain an integral microphone, dual channel digital message repeater,
(DMR) and digital tone generator, 120 VAC power supply, and battery charger. The system
shall be modular in design, and shall be expandable such that additional system control points
may be configured. The system shall include integral self-diagnostic routines that shall
continually monitor system status, and shall indicate the precise type of trouble conditions
should they occur in the system. A trouble condition within the system shall cause a trouble
indication to be transmitted to the FACP.

Distributed panels shall provide a minimum of 4 Class "B" speaker circuits, expandable to
sixteen total. Alternately, panel may be configured for 4 Class "A" speaker circuits, up to 8 total.
Panel may be configured for 1 to 8 amplifiers. Panel must provide up to 6 simultaneous audio
channels, up to 8 Fire Phone circuits, up to 4 Area of Refuge circuits and up to two
Control/Monitor loops. Amplifiers will contain their own power supplies, battery chargers and
provide auxiliary power for other components. Speaker circuits shall be supervised for short
and open circuit conditions, and shall be able to withstand transient or continuous short-circuit
conditions without damage to the system.

System may be configured for General Alarm All Call operation, Alarm by Zone or
Floor Above / Floor Below as required. Contact closures shall allow immediate broadcast of an
alarm signal and evacuation message to the appropriate area. Non-Alarm areas may receive
alert tones and messages as required or activated by the FACP.

The alarm signal/evacuation message shall be broadcast until the FACP is reset, or until
emergency personnel interrupt the broadcast with a manual page.

To prevent unauthorized tampering, the voice evacuation system shall disable the microphone
if the microphone is keyed continuously for 3 minutes or more. Systems that do not have this
feature shall not be acceptable.

Specifications are subject to change without notice. Specifications


are provided for information only and no responsibility is assumed
by Hochiki America, Inc. for their use.
Features:
True Multiplex 6 Channel Distributed Audio FNV-MP
Integrated Fire Phone, Area of Rescue High Rise Voice Evacuation System
and Fan & Damper Control capability
Modular System - components added as needed
Master Panel
Integrated 2 Channel Digital Message Repeater
Live Microphone Page to any zone SYSTEM
RESET

Fast RS-485 Communication Protocol PAGE


ALL-CALL

Fully Supervised FAULT


SILENCE PAGING
Easy Installation and Operation CONTROL

Natural Sound Voice Recordings


Built in Alarm and Alert Signals
Up to 4 Minute Message Capacity
Works with 12VDC or 24VDC Fire Alarm Panel
Works with Analog/Addressable and
Microprocessor based Fire Alarm Panels.
3 Minute Message Restart on Microphone Key
Made in the USA.

Description:

The Hochiki FNV High Rise Evacuation System


operates in conjunction with the Fire Alarm Control
Panel (FACP) in a building to provide automatic
response to life safety emergencies.

The Hochiki FNV includes all necessary features


to provide an effective voice evacuation system.
The Hochiki FNV can be custom configured to
satisfy the needs of any high rise application.

Fire department authorities can easily take


command of evacuation or relocation procedures System Configuration:
and emergencies. Building management and fire Basic System Includes:
brigades can monitor and control emergency
response even before the professionals arrive Master Panel (FNV-MP)
Master Mic Control
The FNV system includes capacity for 6 channels 16 Switch Control points
of simultaneous audio. This provides for Dual Channel DMR
evacuation, stay-in-place, or other public address High Speed communication loop
announcements and automatic messages.
Optional
Fire Fighter Phones or Warden Stations may be Integrated Master Fire Phone
included as required. Area-of-Rescue stations can
reassure handicapped occupants that help is on Area-of-Rescue
the way. Smoke control, stair pressurization, and Fan and Damper system control
HVAC shutdown can be completely automatic,
unless controlled manually by management or fire Maximum System Configuration
authorities.
Up to 1000 monitor and control points

LISTED

7051 Village Drive, Suite 100 Buena Park, CA 90621-2268 714.522.2246 www.hochiki.com
FNV MP64/P
Master Panel
Ribbon Cable Connection Detail

MMC

20 Pin Ribbon

1
2 J1
3
TB1
TB1 TB2

MFP P3 P5

SLC SLC P2 P2

2 1
DCC ASC
34 Pin Ribbon P4 P5
P1

P2

SLC SLC 10 Pin Ribbon P1


LED1 LED2 LED3
TB3 TB4 TB5 P3

4 3

34 Pin Ribbon
34 Pin Ribbon
SSC

1 2 3
1
TB2 2

TB3
M
F PWR-2A TB1 TB2
I I/O
Card
TB1
1 2 3 IOI

Components mounted to
back plate inside of cabinet.

Components mounted on hinged front panel.


Connectors shown are on the back of the
components.

In the Master Panel system components are mounted to a removable back plate. The door and front panel are
removable. This enables field wiring to be installed cleanly.

Connections to the User Interface components ( Switch/LED banks, Mic/System control and Master Fire Phone)
is accomplished with ribbon cables. The front panel mounts separately on a continuous hinge so once installed
the access for system programming is easily accommodated.
NetComm Loop Wiring (Style 4)
IN FROM LAST PANEL RETURN TO MASTER

OUT TO FIRST DISTRIBUTED PANEL IN FROM PREVIOUS PANEL

NetCom Bus
(Supervised)

*A - Optional wiring for


Style 7 supervision
1

P3
1
2 J1 P4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 2
3
J1
3
TB1 TB2 TB1 TB1 TB2 TB3 TB4 TB1 TB2

1 2 3 4
LED1

P5 P3
P3
TB5

P2

1 2 3 4
P1 P2 P2

TB6
MFP DCC ASC DCC

1 2 3 4
P5 P4
P4
P1
TB7

P2

MBR
LED1 LED2 LED3
LED1 LED2 LED3 P1 TB3 TB4 TB5
P1 TB3 TB4 TB5 P3 TB9

MASTER PANEL DISTRIBUTED PANEL

NetComm Loop Wiring (Style 7)

Redundant Communication Bus

Primary Communication Bus

P3
1
2 J1 P4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 2
3
J1
3
TB1 TB2 TB1 TB1 TB2 TB3 TB4 TB1 TB2
1 2 3 4

LED1

P5 P3
P3
TB5

P2
1 2 3 4

P1 P2 P2

TB6
MFP DCC ASC DCC
1 2 3 4

P5 P4
P4
P1
TB7

P2

MBR
LED1 LED2 LED3
LED1 LED2 LED3 P1 TB3 TB4 TB5
P1 TB3 TB4 TB5 P3 TB9

MASTER PANEL DISTRIBUTED PANEL

The redundant loop must be run in separate conduit


with minimum spacing from the primary. Check local
code requirements.
Master Panel Configurations:

FNV-MP16 Master Panel, 16 Switch Control


FNV-MP32 Master Panel, 32 Switch Control
FNV-MP48 Master Panel, 48 Switch Control
FNV-MP64 Master Panel, 64 Switch Control
FNV-MP80 Master Panel, 80 Switch Control
FNV-MP96 Master Panel, 96 Switch Control

FNV-MP16/P Master Panel, 16 Switch Control, Master Fire Phone


FNV-MP32/P Master Panel, 32 Switch Control, Master Fire Phone
FNV-MP48/P Master Panel, 48 Switch Control, Master Fire Phone
FNV-MP64/P Master Panel, 64 Switch Control, Master Fire Phone
FNV-MP80/P Master Panel, 80 Switch Control, Master Fire Phone
FNV-MP96/P Master Panel, 96 Switch Control, Master Fire Phone

Panel Options: Cards may be added as job requirements demand

FNV-MFP Master Fire Phone Enables system to incorporate 2 way communication.


Included with /P panels.

FNV-SSC Switch Scan Card Included in basic panels, up to 7 additional cards may be
added.
FNV-SLC Switch LED Card 16 Switch LED Bank, up to 8 per FNV-SSC.

FNV-IOI Input Interface Card One included with basic panel, additional cards give 16 control

Technical Characteristics:

Primary Power: 120 VAC


24 VDC Battery Power
Communications Bus: RS-485 Standard,
Electrical Ratings:All Circuits @ 24VDC.
1M Baud data rate, Category 5 cable.

Master Panel Voltage: 5V peak-to-peak max.


Current: 50mA max.
Standby Alarm Impedance: 120 Ohms
DCC 80 mA 80 mA (max. imp. between panels)
ASC 30 mA 30 mA Frequency: 1.024MHz
MFP 10 mA 10 mA
SSC 25 mA 25 mA Backbox Dim: 14.5 x 27 x 4“ w•h•d
SLC 6 mA 6 mA Color: Charcoal Grey•standard
MMC 45 mA 45 mA Red•optional
IOI 20 mA 20 mA

Specifications are subject to change without notice. Specifications


are provided for information only and no responsibility is assumed
by Hochiki America, Inc. for their use.
Features:
True Multiplex 6 Channel Distributed Audio FNV-DP
Integrated Fire Phone, Area of Rescue High Rise Voice Evacuation System
and Fan & Damper Control capability Distributed Panel
Modular System - components added as needed
Integrated 2 Channel Digital Message Repeater
Live Microphone Page to any zone
Fast RS-485 Communication Protocol
Fully Supervised
Easy Installation and Operation 1 2 3 4
TB1
1 2 3 4
TB2
1 2 3 4
TB3
1 2 3 4
TB4
1
2
3
J1
TB1 TB2

Natural Sound Voice Recordings

1 2 3 4
TB5 P3

Built in Alarm and Alert Signals

1 2 3 4
P2

TB6
DCC
Up to 4 Minute Message Capacity DCC

1 2 3 4
P4

TB7

Works with 12VDC or 24VDC Fire Alarm Panel 1

MBK
8 “B”

AMI
Works with Analog/Addressable and TB8
MBR
P1

Microprocessor based Fire Alarm Panels. 4 “A”

3 Minute Message Restart on Microphone Key TB1 TB1

Made in the USA.


1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

TB2 11 TB2 11
J1 10 J1 10
9 9
8 8
1 TB3 7 1 TB3 7
2 6 2 6
3 J2 5 3 J2 5
4 4 4 4
5 YEL FAULT 1 2 3 3 5 YEL FAULT 1 2 3 3
6 2 6 2
7 GRN NORMAL 1 7 GRN NORMAL 1
8 8
RED ALARM RED ALARM

P2 P2
MESSAGE MIC MESSAGE MIC
GAIN GAIN GAIN GAIN

Description: FNV-25E FNV-25E

SN1 SN1

The Hochiki FNV High Rise Evacuation System


S1 S1

operates in conjunction with the Fire Alarm Control


Panel (FACP) in a building to provide automatic
response to life safety emergencies.

The Hochiki FNV includes all necessary features


to provide an effective voice evacuation system.
The Hochiki FNV can be custom configured to
satisfy the needs of any high rise application.
System Configuration:
Fire department authorities can easily take
Basic System Includes:
command of evacuation or relocation procedures
and emergencies. Building management and fire Distributed Panel (FNV-DP)
brigades can monitor and control emergency 4 Output Zones (may be configured for 8)
response even before the professionals arrive Dual Channel Audio Interface
Dual/Single Channel Amplification
The FNV system includes capacity for 6 channels
of simultaneous audio. This provides for Amplifier Options:
evacuation, stay-in-place, or other public address 25 / 50 / 100W Dual Channel
announcements and automatic messages. 25 / 50 / 100 / 200W Single Channel

Fire Fighter Phones or Warden Stations may be Optional


included as required. Area-of-Rescue stations can Integrated Fire Phone
reassure handicapped occupants that help is on 4 Circuits expandable to 8 or 12
the way. Smoke control, stair pressurization, and
HVAC shutdown can be completely automatic, Area-of-Rescue
unless controlled manually by management or fire Fan and Damper system control
authorities.
Maximum System Configuration
LISTED Up to 256 Distributed Panels (FNV-DP)

7051 Village Drive, Suite 100 Buena Park, CA 90621-2268 714.522.2246 www.hochiki.com
FNV
Distributed Panel
Connection Detail

10K
EOLR
Speaker Circuits

SEE FIG. 2 FOR FPI TO MBR CONNECTION DETAIL


1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 SEE FIG. 3 FOR AMI TO AMPLIFIER CONNECTION DETAIL
P10
MBK
Fire Phone Circuits

1 2 3 4

AMI
FPI
1 2 3 4

P14

10K
EOLR
1 2 3 4

P15

P3 P2 P1
DCC

MBR
TB3
TB8
P1 1234

TB9 TB11

Set EOLR

TB1 TB1
1 2 3 4 5 6 7 8 1 2 3 4 5 6 7 8

TB2 11 TB2 11
J1 10 J1 10
9 9
8 8
1 TB3 7 1 TB3 7
2 6 2 6
3 J2 5 3 J2 5
4 4 4 4
5 YEL FAULT 1 2 3 3 5 YEL FAULT 1 2 3 3
6 2 6 2
7 GRN NORMAL 1 7 GRN NORMAL 1
8 8
RED ALARM RED ALARM

P2 P2
MESSAGE MIC MESSAGE MIC
GAIN GAIN GAIN GAIN

FNV-25E FNV-25E

10 PIN RIBBON 10 PIN RIBBON

SN1 SN1
S1 S1
FPI to MBR Connection AMI to Amplifier Connection
To left side
Amplifier
To right side
10 PIN RIBBON Amplifier

TO MBR J7 10 PIN RIBBONS

MBR J7

This side plugs


into MBR, 2nd
slot on right

FPI Each AMI card provides audio


This side plugs
into MBR, 1st channels and control to two
slot on right
amplifier modules or amplifier
AMI banks. Maximum configuration
Each FNV-DP panel may is 5 AMI cards in each FNV-DP.
(Additional modules would mount in
have up to 4 FPI cards for separate cabinets)
a max. of 16 phone circuits.
(Additional FPI cards require
an FNV-FPO for circuit termination)

Eight Class “B” Speaker Lines


E
O
L 1
F F
EOLR
I I
R R
E E

E
O
L 2 Eight Class "B" may
F
I
F
I
EOLR also be configured
R
E
R
E as 4 A / B circuits

E
O
L 8
1 2 3 4 5 6 7 8 F F
EOLR
I I
R R
E E

Standard Life Safety Speakers,


Strobes connected and powered separately
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
TB1 TB2 TB3 TB4
Four Class “A” Speaker Lines
1 2 3 4

F F
I I
TB5 R
E
R
E
1 2 3 4

TB6
1 2 3 4

F F
I I
R R
E E
TB7
1 EOL
2 3 4 EOL
MBK#2
MBK#1

AMI

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
MBR TB1 TB2 TB3 TB4
1 2 3 4

TB8 TB5

Second FNV-MBK card provides


additional speaker circuits
May be configured as several options
Distributed Panel Configurations:

FNV-DPS25 Distributed Panel, Single Channel, 25W


FNV-DPS50 Distributed Panel, Single Channel, 50W
FNV-DPS100 Distributed Panel, Single Channel, 100W

FNV-DPS25/P Distributed Panel, Single Channel, 25W, Fire Phone


FNV-DPS50/P Distributed Panel, Single Channel, 50W, Fire Phone
FNV-DPS100/P Distributed Panel, Single Channel, 100W, Fire Phone

FNV-DP25 Distributed Panel, Dual Channel, 25W


FNV-DP50 Distributed Panel, Dual Channel, 50W
FNV-DP100 Distributed Panel, Dual Channel, 100W

FNV-DP25/P Distributed Panel, Dual Channel, 25W, Fire Phone


FNV-DP50/P Distributed Panel, Dual Channel, 50W, Fire Phone
FNV-DP100/P Distributed Panel, Dual Channel, 100W, Fire Phone

Panel Options: Cards may be added as job requirements demand

FNV-MBK Motherboard Relay Card Expands MBR output 8 Class B or 4 Class A speaker circuits

FNV-FPI Fire Phone Interface Card Included in /P panels, up to 3 additional cards may be added
FNV-FPO Fire Phone Output Card Used with additional FNV-FPIs for termination

FNV-AMI Audio Module Interface Card Included with basic panel, additional cards give the ability to control
multiple modules or accommodate full 3 channel operation

Technical Characteristics:

Primary Power: 120 VAC


24 VDC Battery Power
Electrical Ratings: All Circuits @ 24VDC. Communications Bus: RS-485 Standard,
1M Baud data rate, Category 5 cable.
Distributed Panel Voltage: 5V peak-to-peak max.
Standby Alarm Current: 50mA max.
DCC 55 mA 55 mA Impedance: 120 Ohms
MBR 10 mA 55 mA (max. imp. between panels)
AMI 10 mA 10 mA Frequency: 1.024MHz
FPI 13 mA 13 mA

Battery Charging: Maximum charging current from Backbox Dim: 14.5 x 27 x 4“ w•h•d
FNV-25/50 is 800mA. Maximum battery size is 17AHr. Color: Charcoal Grey•std Red•optional
FNV-100 Maximum battery size is 24AHr.

Specifications are subject to change without notice. Specifications


are provided for information only and no responsibility is assumed
by Hochiki America, Inc. for their use.
Description:
Fire Phone accessories give the FNV system two
VoiceNet
way communication capability. Fire Phone Equipment
Fire Phone jacks are mounted on a single gang plate.

Fixed telephone and warden stations are available in


Surface/Semi-Flush mount cabinet with a Thumb
Turn latch

FNV-FJ

Ordering Information:
Model Number Description

FNV-FJ Telephone Jack FNV-FH


Brushed Stainless Steel Single Gang
Plate

FNV-FH Portable Handset


Color - Red
(6 mount in FNV-TC cabinet)

FNV-TC Telephone Cabinet


Holds 6 FNV-FH Portable Handset
Cabinet: Charcoal Gray - std. -R Red
(Surface/Semi-Flush Mount / Key Lock
27 x 14-1/2 x 4” h-w-d)

FNV-FS Fire Phone Station


Coil cord / Thumb Turn Latch FNV-FS
Cabinet: Red FNV-TC
(Surface/Semi-Flush Mount
(Shown with 6 FNV-FH) FNV-WS
12-3/4 x 7-1/4 x 3-3/4” h-w-d)

FNV-WS Warden Station


Armored cable / Thumb Turn Latch
Cabinet: Red
(Surface/Semi-Flush Mount
12-3/4 x 7-1/4 x 3-3/4” h-w-d)

LISTED

7051 Village Drive, Suite 100 Buena Park, CA 90621-2268 714.522.2246 www.hochiki.com
10K 1/2W
EOLR

Fire Phone Fire Phone


Handset Handset
Jack Jack

10K 1/2W
EOLR

Fire Phone Fire Phone


Handset Handset
Jack Jack

10K 1/2W
EOLR

Fire Phone Fire Phone


Handset Handset
Jack Jack

All Fire Phone


Circuits use
Twisted Pair 10K 1/2W
/

EOLR
#22 AWG min.
Fire Phone Fire Phone
Handset Handset
Jack Jack

10K 1/2W
EOLR

To Additional Fire Phone Fire Phone


Handset Handset

Fire Phone Circuits Jack Jack

(not shown)

1 2 3 4 1 2 3 4 1 2 3 4 1 2
TB1 TB2 TB3 TB
1 2 3 4

TB5
1 2 3 4

TB6
FPO Fire
1 2 3 4

Phone TB7
Loops
(Supervised)

MBR
/
10 Pin Ribbon Cable FPI
Cards plug into slots
available on MBR
First FPI allows 4 Fire Phone
Circuits off of MBR. Adding 2nd
FPI and an FPO allows 4
additional Fire Phone Circuits
(16 circuits max. in any FNV-DP)

7051 Village Drive, Suite 100


Buena Park, CA 90621-2268
Features:
True Multiplex 6 Channel Distributed Audio
Integrated Fire Phone, Area of Rescue VoiceNET
and Fan & Damper Control capability
Modular System - components added as needed
High Rise Voice
Integrated 2 Channel Digital Message Repeater
Live Microphone Page to any zone
Evacuation System
Fast RS-485 Communication Protocol SYSTEM

Fully Supervised RESET

Easy Installation and Operation


PAGE
ALL-CALL

Natural Sound Voice Recordings FAULT


SILENCE PAGING
CONTROL
Built in Alarm and Alert Signals
Up to 4 Minute Message Capacity
Works with 12VDC or 24VDC Fire Alarm Panel
Works with Analog/Addressable and
Microprocessor based Fire Alarm Panels.
3 Minute Message Restart on Microphone Key
Made in the USA.

277-96-E
6911-1446:103
LISTED
Description: #S5661
The Hochiki VoiceNET High Rise Evacuation
System operates in conjunction with the Fire Alarm
Control Panel (FACP) in a building to provide
automatic response to life safety emergencies.

The Hochiki VoiceNET includes all necessary


features to provide an effective voice evacuation
system. The Hochiki VoiceNET can be custom
configured to satisfy the needs of any high rise
application.
System Configuration:
Fire department authorities can easily take Basic System Includes:
command of evacuation or relocation procedures Master Panel (FNV-MP)
and emergencies. Building management and fire Master Mic Control
brigades can monitor and control emergency 16 switch control points
response even before the professionals arrive Dual Channel DMR
High speed communication loop
The VoiceNET system includes capacity for 6 Distributed Panel (FNV-DP)
channels of simultaneous audio. This provides for 4 Output Zones (may be configured for 8)
evacuation, stay-in-place, or other public address Dual Channel Audio Interface
announcements and automatic messages. Dual Channel Amplification
Optional
Fire Fighter Phones or Warden Stations may be Integrated Fire Phone
included as required. Area-of-Rescue stations can Area-of-Rescue
Number of distributed panels to be
reassure handicapped occupants that help is on Determined by building specifications
the way.
Maximum System Configuration
Up to 256 Distributed Panels (FNV-DP)
And up to 2028 monitor and control points

7051 Village Drive, Suite 100 Buena Park, CA 90621-2268 714.522.2246 www.hochiki.com
FNV-DP Voice Evacuation
Speaker Circuits
Distributed Panel
#18 AWG
F
I
R
E

F
I
R
E

F
I
R

Hochiki VoiceNET
E

F
I

True-Multiplex
R
E

TB1 TB1
TB2 TB2

#22 AWG Twisted Pair

System
TB3 TB3

Fire Phone

Fire Fire

Capabilities FNV-25/50/100 FNV-25/50/100


Phone Phone

NetComm Loop:
-Twisted Pair, Category 5
-4,000 Feet between panels
-50,000 Feet Total System Loop
-Data and 6 Audio Channels Simultaneously
-High Speed RS-485 Communications
-Style “4” or Style “7” Field Selectable

FNV-DP
Distributed Panel Voice Evacuation
Speaker Circuits

Head End Control F


I
R
E

F
FNV-MP I
R
E

Master Panel
F
I
R
E

PAGING F
CONTROL
I
R
E

TB1 TB1
TB2 TB2

TB3 TB3

Fire Phone

Fire Fire

FNV-25/50/100 FNV-25/50/100
Phone Phone

FIRE PHONE CONTROL


Hochiki VoiceNET
High Rise Multiplex
11 Floor Typical Riser Diagram

11th Floor S S
P
AR

S S
10th Floor
P
AR

S S
9th Floor CM FNV-DP
P
AR

S S
8th Floor
P
AR

S S
7th Floor
P
AR

S S
6th Floor
P
AR

S S
5th Floor CM FNV-DP
P
AR

S S
4th Floor
P
AR

S S
3rd Floor P
AR

RS 485
DATA LOOP S S
2nd Floor
P
AR

S S
1st Floor FNV-MP FNV-DP
P

S S
Basement
P

S Speaker, Speaker/Strobe AR Area of Rescue Station


P Fire Fighter Phone Jack

7051 Village Drive, Suite 100


Buena Park, CA 90621-2268
Engineering Specifications
Hochiki VoiceNET High Rise

The voice evacuation system shall be Hochiki Series VoiceNET FNV High Rise or approved
equal.

The VoiceNET FNV system shall include one Master Panel and one or more Distributed
Panels. The system shall be microprocessor based, and shall be compatible for use with
contact closures from the Fire Alarm Control Panel, (FACP). The system shall have a high-
speed communication bus and have the capacity for 6 channels of audio and data on a single
pair of wires. The field wiring for the communication bus may be configured for either Style "4"
or Style "7" supervision. The system shall have the capacity for Fire Fighters Phone, Area-of-
Rescue communication and also have the capacity for Fan & Damper control with monitored
feedback. The system shall have a minimum capacity of 2028 monitor and control points.

The Master Panel shall contain an integral microphone, dual channel digital message repeater,
(DMR) and digital tone generator, 120 VAC power supply, and battery charger. The system
shall be modular in design, and shall be expandable such that additional system control points
may be configured. The system shall include integral self-diagnostic routines that shall
continually monitor system status, and shall indicate the precise type of trouble conditions
should they occur in the system. A trouble condition within the system shall cause a trouble
indication to be transmitted to the FACP.

Distributed panels shall provide a minimum of 4 Class "B" speaker circuits, expandable to
sixteen total. Alternately, panel may be configured for 4 Class "A" speaker circuits, up to 8 total.
Panel may be configured for 1 to 8 amplifiers. Panel must provide up to 6 simultaneous audio
channels, up to 8 Fire Phone circuits, up to 4 Area of Refuge circuits and up to two
Control/Monitor loops. Amplifiers will contain their own power supplies, battery chargers and
provide auxiliary power for other components. Speaker circuits shall be supervised for short
and open circuit conditions, and shall be able to withstand transient or continuous short-circuit
conditions without damage to the system.

System may be configured for General Alarm All Call operation, Alarm by Zone or
Floor Above / Floor Below as required. Contact closures shall allow immediate broadcast of an
alarm signal and evacuation message to the appropriate area. Non-Alarm areas may receive
alert tones and messages as required or activated by the FACP.

The alarm signal/evacuation message shall be broadcast until the FACP is reset, or until
emergency personnel interrupt the broadcast with a manual page.

To prevent unauthorized tampering, the voice evacuation system shall disable the microphone
if the microphone is keyed continuously for 3 minutes or more. Systems that do not have this
feature shall not be acceptable.

Specifications are subject to change without notice. Specifications


are provided for information only and no responsibility is assumed
by Hochiki America, Inc. for their use.
TCH-B100 HAND-HELD PROGRAMMER

APPLICATION

TCH-B100 is designed for use with all analog sensors


and modules.

ADDRESS SETTING:

1. Install sensor onto programmer, ensuring that


sensor protrusions align with programmer grooves.
2. Press the left gray button to switch programmer on.
A battery check message will appear followed by
the device's address (Unprogrammed sensors will
read address 127).
STANDARD FEATURES 3. Set the required address by incrementing the left
and right gray buttons (the display will show three
• Compact unit red flashing dots if the address being programmed
• Easy to use is different from the device's current address).
• Provides address setting and reading 4. When the desired address is present, press the red
• Can be used on both sensors and modules button to store that address. The three red dots on
the display will no longer be present.
• Has the diagnostic ability to display the
analog value
• Over 8000 address settings from one battery.

SPECIFICATIONS
Rated Voltage: 9 VDC
Battery: 9 VDC
Weight: 0.34 lbs
PRODUCT PARTS
Length: 6 1/4"
• 9 Volt Battery
Color: White
• Remote Programming Cables

Continued on back

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 • Buena Park, CA 90621-2268
Phone: 714/522-2246 • Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 9/2003
Remote Programming
Jack

Programming Buttons
Display

PROGRAMMING BUTTONS:

LEFT GRAY BUTTON Power on. Automatically reads the addresss of a sensor.
Subsequent operations will advance the device address by ten.
RIGHT GRAY BUTTON Power off. Advances the device address by one.
RED BUTTON Stores the displayed address to the device and is used to read sensor analog
levels.

NOTE: Prior to programming, ensure battery is connected.

Remote Programming Cable


(All Modules except DCP-FRCME-S)

To Remote
Programming Jack

Remote Programming Cable


(DCP-FRCME-S)
TESTING A SENSOR
Note: Ionization sensors require a 30 second stabilization period before analog value reading should be taken.

1. Install the sensor and power up programmer as previously described on page 1


2. Press the “Red” button. An “A” will appear on the display followed by the analog value. The
value will be continuously updated for three minutes
3. The “ALG’ photoelectric sensor should have a value displayed of between 56-63. The “AIE”
ionization sensor should have a value displayed of between 52-73.

Values out of these ranges indicate that the sensor chamber has become contaminated. Refer to technical
bulletin “HA-96” for proper servicing instructions or return sensor to factory for servicing.

DISPLAY MESSAGES:
bAt- On upon power up (battery check). Also on when battery is low. Low battery good for up to 3,000
address setting operation.
E0 - Attempting to set an address beyond 127.
E1 - Attempting to program an address with no device connected.
E2 - Can not find device after power up.
E3 - Invalid sensor response.
E4 - Can not find the device program.
E5 - Device read error.
E6 - Fail during Analog value reading
Hochiki America Corporation • TCH-B100 Hand-Held Programmer Specifications subject to change without notice.
TSE-A100 SELF-CONTAINED SMOKE GENERATOR
APPLICATION
The Hochiki America TSE-A100 is one of the most
advanced units of its kind and is the result of extensive
research and development aimed at making the job of
testing detectors a simple and efficient operation .

The TSE-A100 can be used to test all types of smoke


detectors by applying smoke from an internal smoke
source.

Although this is not a calibrated amount of smoke, the


TSE-A100 is an excellent choice for periodic functional
testing of smoke detectors.

OPERATION
Preparation
1. Remove the TSE-A100 from its carrying case.
2. Unscrew the combustion chamber from the
bottom of the TSE-A100.
3. Unscrew the punk stick holder retainer from
the combustion chamber.
4. Insert a punk stick into the punk stick holder in
the combustion chamber.
5. Light the punk stick with a flame.
STANDARD FEATURES 6. Reassemble the combustion chamber.
• Tests all types of smoke detectors. 7. Screw the combustion chamber back into the
• Completely self contained and portable. bottom of the TSE-A100
• Extends from 5.25 feet to 14.1 feet. 8. Extend the telescopic pole of the TSE-A100 to
• Internal Smoke Source. a length which enables you to reach the
• Non-Toxic Smoke Source. detector you wish to test.
• Unit includes shoulder sling carrying case.
• Optional adapter for high velocity conditions. Testing a Detector
Once you have prepared the TSE-A100, follow the steps
• Exhaust function to clear detector.
in this section to test smoke detectors.
• Built-in filter to prevent tar residue from adhering to
the surface of the detector. NOTE: Allow 30 to 60 seconds after igniting punk stick
for sufficient smoke generation.
SPECIFICATIONS
Continued on back
Rated Voltage 3 VDC
Battery 2 - "D" Batteries
PRODUCT PARTS
Combustion Material Punk Stick
(7 mm diameter, 150 mm long) • TSE-A100 Self-Contained Smoke Generator
Weight 5 Lbs. • Punk Stick (Part No. TSE-P100)
Length 5.25 to 14.1 feet
Color Brown
Specifications subject to change without notice.

Hochiki America Corporation


7051 Village Drive, Suite 100 • Buena Park, CA 90621-2268
Phone: 714/522-2246 • Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 01/2002
OPERATION, continued

Testing a Detector, continued Storing the TSE-A100

1. Rotate the combustion chamber so the #2


1. Rotate the combustion chamber to the #1
arrow line sup with the power indicator screw.
position to turn the power off.
The fan powers on and a steady flow of smoke
is released from the tip of the TSE-A100. 2. Compress the telescopic pole to its shortest
length.
2. Raise the extended tip of the TSE-A100 to
within 6-8' of the detector. The detector should 3. Replace the TSE-A100 in its carry case.
alarm. 4. Store in a cool, dry place.
If no smoke comes out, check to make sure the 5. For extended storage, remove the batteries.
punk stick is ignited, and the power indicator on
the combustion chamber is set to #2.

NOTE

1. Use only the filter and combustion material


specified.
2. Check battery capacity before use to assure
efficient operation.
3. Remove batteries before long-period storage.
Telescopic Pole

Power Indicator Screw

Punk Stick Holder Retainer

Combustion Chamber
Punk Stick

Instruction Label

Hochiki America Corporation • TSE-A100 Specifications subject to change without notice.


NSRT / NSTT
SMOKE DETECTOR REMOVAL TOOL / TESTER

STANDARD FEATURES

NSRT

• Combination removal tool/outer cover removal tool


for AIE, ALG, SIJ, and SLR-24/-835 series sensors/
detectors.
• Choose either a Hand held or 15’ stainless steel
extension pole with easy grip black handle.

NSTT

NSRT HEAD • Tests Hochiki America SIJ-24 and SLR-24/-835


series smoke detector with a reed switch.
• Choose either a Hand held or 15’ stainless steel
extension pole with easy grip black handle.
• No combustion material needed.
• No meter, batteries, or screwdriver required.
• Meets outlined requirements in the NFPA72,
NSRT-A100 WITH 15' POLE Inspection, Testing and Maintenance, Chapter 10.
(COMPLETE)

SPECIFICATIONS
Detector Tester/Removal Tool
Dimensions
NSRT HEAD: 4.0" D x 2.0" H
NSTT HEAD: 4.0" D x 1.5" H
Material Highly durable PVC
molded plastic
Color Black - provides visible contrast
Alignment
NSRT HEAD: One side for arrow labels for
easy visibility, one side for
removal from base.
NSTT HEAD: One side for sensitivity testing.
NSTT HEAD
Extension Pole
Dimensions Pole extends to 15'
Material Stainless steel with easy grip
black handle
NSTT-A100 WITH 15' POLE
(COMPLETE) Specifications subject to change without notice.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F044 02/2005
APPLICATION
NSRT-A100
The Hochiki America NSRT-A100 will enable the user to easily remove and replace the ALG, AIE, SLR, and SIJ series
sensors/ detectors from their mounting bases. Also, the NSRT-A100 is designed to remove the outer covers of the
ALG, AIE and SLR series sensors/detectors

NSTT-A100
The SIJ-24 and SLR-24/-835 series detectors, manufactured with magnetically activated dual reed switches for sensitivity
testing, can be sensitivity tested with the NSTT-A100. This meets the requirements of a UL listed calibrated test
without the use of combustion materials.
The NSTT-A100 is in compliance with the test requirements outlined in the NFPA 72 Inspection, Testing and Maintenance,
Chapter 10.

Hochiki America Corporation NSRT & NSTT Specifications subject to change without notice.
HCP-202 FIRE ALARM CONTROL PANEL

DESCRIPTION
Hochiki’s HCP-202 Fire Alarm Control Panel is a
microprocessor based unit designed for small to medium
commercial, institutional and industrial occupancies.
Fully configurable using DIP switches, it enables the user
to configure the system to meet their specific
requirements.

The HCP-202 comes standard with 2 Class B (Style B)


initiating circuits which may be configured as 1 Class A
(Style D) circuits. In addition it comes equipped with 2
Class A/B (Style Z/Y) indicating circuits which are each
STANDARD FEATURES rated at 1.25 amps. The panel also includes a 2.75 amp
power supply which powers the system and supplies a
• 2 Class B (Style B) initiating circuits which may 4-wire resettable regulated smoke power supply of 24
be configured as 1 Class A (Style D) circuits VDC 100mA maximum.
• 2 Class A/B (Style Z/Y) indicating circuits with
individual trouble indicators (1.25 Amps max. per The HCP-202 utilizes a simple DIP switch configuration
circuit) for programming initiating and indicating circuits as well
• Each indicating circuit can be configured as as the enabling and disabling of system functions such
silenceable or non-silenceable. Audibles may be as signal silence, fire drill and auxiliary disconnect. In
configured as Steady, Temporal Code, California addition the HCP-202 allows for alarm verification on the
Code or March Time initiating circuits. The indicating circuits may be
• Selectable alarm verification on initiating circuits configured as silenceable or non-silenceable with the
• Output for 4-wire resettable regulated smoke power audibles configured for Steady, March-Time, Temporal
supply of 24 VDC 100mA maximum Code, or California Code.
• Output for RTI or Remote Annunciators of 24VDC,
300 mA max, unfiltered The cabinet is available in a beige color for the Canadian
• Built-in walk test operation market and a red exterior for the U.S. and International
• Auxiliary relay contacts for common alarm, markets. A Fire Retardant Lexan Window in the hinged
common trouble and common supervisory. If no door allows for viewing of the status LEDs. It comes
supervisory circuits are enabled, the supervisory with a durable CAT-30 lock and key. Space is provided
relay becomes a second alarm relay for up to 10 AH batteries.
• 2.75 Amp power supply
• Easy configuration via DIP switches

SPECIFICATIONS PRODUCT LISTINGS


Primary Input Power 120 volts, 60 Hz, 1 Amps California
(Optional 220VAC) State Fire
Indicating Current 24VDC unfiltered, 2.5Amps Marshal
Standby Power 24VDC standby batteries S6468 7165-0410:152
Charging Capability 4 – 6.5 AH batteries
Dimensions 12 3/4"H x 13 3/4"W x 3 1/8"D
Continued on back.
Specifications subject to change without notice.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0032 01/2007
ORDERING INFORMATION

Model Description
Fire Alarm Control Panel
HCP-202 Two Zone Microprocessor Based Fire Alarm Control Panel comes with 2 Class B (Style B)
or 1 Class A (Style D) initiating circuits, 2 Class A/B (Style Z/Y) indicating circuits and a
2.75 amp power supply. Allows for one HDACT-100 Digital Communicator or one HPR-100
Polarity Reversal Module or one HRM-204 or HRM-208 Auxiliary Relay Module. Red
enclosure comes with keylock door.
HRTI-1 Remote Trouble Indicator
Adder Modules
HDACT-100 Digital Alarm Communication Transmitter/Dialer Module
HPR-100 Polarity Reversal/City Tie Module
HRM-204 Auxiliary Relay Module comes with 4 configurable relays
HRM-208 Auxiliary Relay Module comes with 8 configurable relays
(Note: Only one of the above modules can be used with the HCP-202)

Hochiki America Corporation HCP-202 Specifications subject to change without notice.


HCP-204 FIRE ALARM CONTROL PANEL
DESCRIPTION

Hochiki’s HCP-204 Fire Alarm Control Panel is a


microprocessor based unit designed for small to medium
commercial, institutional and industrial occupancies.
Fully configurable using DIP switches, it enables the user
to configure the system to meet their specific
requirements.

The HCP-204 comes standard with 4 Class B (Style B)


initiating circuits which may be configured as 2 Class A
(Style D) circuits. In addition, it comes equipped with 2
Class A/B (Style Z/Y) indicating circuits which are each
rated at 1.25 Amps. The panel also includes a 2.75 amp
STANDARD FEATURES power supply which powers the system and supplies a
4-wire resettable regulated smoke power supply of 24
• 4 Class B (Style B) initiating circuits which may VDC 100mA maximum.
be configured as 2 Class A (Style D) circuits
• 2 Class A/B (Style Z/Y) indicating circuits with The HCP-204 utilizes a simple DIP switch configuration
individual trouble indicators (1.25 Amps max. per for programming initiating and indicating circuits as well
circuit) as the enabling and disabling of system functions such
• Each indicating circuit can be configured as as signal silence, fire drill and auxiliary disconnect. Some
silenceable or non-silenceable. Audibles may be predefined initiating circuits can optionally be configured
configured as Steady, Temporal Code, California as waterflow or latching/non-latching supervisory. In
Code or March Time
addition the HCP-204 allows for alarm verification on the
• Selectable alarm verification on initiating circuits initiating circuits. The indicating circuits may be
• Output for 4-wire resettable regulated smoke configured as silenceable or non-silenceable with the
power supply of 24 VDC 100mA maximum audibles configured for Steady, March-Time, Temporal
• Output for RTI or Remote Annunciators of 24VDC, Code, or California Code. The HCP-204 is equipped with
300 mA max. unfiltered auxiliary relay contacts for common alarm, trouble and
• Built-in walk test operation supervisory. If no supervisory circuits are enabled, the
• Auxiliary relay contacts for common alarm, supervisory relay becomes a second alarm relay.
common trouble and common supervisory. If no
supervisory circuits are enabled, the supervisory The cabinet is available in a beige color for the Canadian
relay becomes a second alarm relay market and a red exterior for the U.S. and International
• 2.75 Amp power supply markets. A Fire Retardant Lexan Window in the hinged
• Easy configuration via DIP switches door allows for viewing of the status LEDs. It comes
with a durable CAT-30 lock and key. Space is provided
SPECIFICATIONS for up to 10 AH batteries.

Primary Input Power 120 volts, 60 Hz, 1 Amps


(Optional 220VAC) PRODUCT LISTINGS
Indicating Current 24VDC unfiltered, 2.5Amps California
Standby Power 24VDC standby batteries State Fire
Charging Capability 4 – 6.5 AH batteries Marshal
S6468 7165-0410:152
Dimensions 12 3/4"H x 13 3/4"W x 3 1/8"D

Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0031 01/2007
ORDERING INFORMATION

Model Description
Fire Alarm Control Panel
HCP-204 Four Zone Microprocessor Based Fire Alarm Control Panel comes with 4 Class B (Style B)
or 2 Class A (Style D) initiating circuits, 2 Class A/B (Style Z/Y) indicating circuits and a
2.75 amp power supply. Allows for one HDACT-100 Digital Communicator or one HPR-100
Polarity Reversal Module or one HRM-204 or HRM-208 Auxiliary Relay Module. Red
enclosure comes with keylock door.
HRTI-1 Remote Trouble Indicator
Adder Modules
HDACT-100 Digital Alarm Communication Transmitter/Dialer Module
HPR-100 Polarity Reversal/City Tie Module
HRM-204 Auxiliary Relay Module comes with 4 configurable relays
HRM-208 Auxiliary Relay Module comes with 8 configurable relays
(Note: Only one of the above modules can be used with the HCP-204)
Remote Annunciator
HRAM-208 Remote Multiplex Annunciator comes with common control features, indicators and 8
bi-colored LEDs
Controls: Signal Silence, Buzzer Silence, Lamp Test & System Reset
Indicators: A.C. On, Common Trouble & Signal Silence

Hochiki America Corporation HCP-204 Specifications subject to change without notice.


HCP-204E FIRE ALARM CONTROL PANEL
DESCRIPTION
Hochiki’s HCP-204E Fire Alarm Control Panel is a
microprocessor based unit designed for small to medium
commercial, institutional and industrial occupancies. Fully
configurable using DIP switches, it enables the user to
configure the system to meet their specific requirements.
The HCP-204E comes standard with 4 Class B (Style B)
initiating circuits which may be configured as 2 Class A
(Style D) circuits. In addition it comes equipped with 2
Class A/B (Style Z/Y) indicating circuits which are each
rated at 1.7 amps. The HCP-204E can be expanded up
to 8 Class B (Style B) or 4 Class A (Style D) initiating
circuits and 4 Class A/B (Style Z/Y) indicating circuits
with the addition of an HDM-204 Adder Zone Module. The
STANDARD FEATURES panel also includes a 6 amp power supply which powers
• 4 Class B (Style B) initiating circuits which may the system and supplies a 4-wire resettable regulated
be configured as 2 Class A (Style D) circuits. smoke power supply of 24 VDC 100mA maximum.
Expandable up to 8 Class B (Style B) or 4 Class A
(Style D) initiating circuits The HCP-204E utilizes a simple DIP switch configuration
for programming initiating and indicating circuits as well
• 2 Class A/B (Style Z/Y) indicating circuits with
as the enabling and disabling of system functions such
individual trouble indicators (1.7 amps max. per
circuit.) Expandable up to 4 Class A/B (Style Z/Y) as signal silence, fire drill and auxiliary disconnect. Some
indicating circuits predefined initiating circuits can optionally be configured
as waterflow or latching/non-latching supervisory. In
• Each indicating circuit can be configured as
silenceable or non-silenceable. Audibles may be addition the HCP-204E allows for alarm verification on
configured as Steady, Temporal Code, California the initiating circuits. The indicating circuits may be
Code or March Time configured as silenceable or non-silenceable with audibles
configured for Steady, March-Time,Temporal Code, or
• Output for RTI or Remote Annunciators of 24VDC,
California Code.
300 mA max, unfiltered
• Built-in walk test operation The HCP-204E is equipped with auxiliary relay contacts
• Auxiliary relay contacts for common alarm, for common alarm, trouble and supervisory. If no
common trouble and common supervisory. If no supervisory circuits are enabled, the supervisory relay
supervisory circuits are enabled, the supervisory becomes a second alarm relay. The cabinet is available
relay becomes a second alarm relay in a beige color for the Canadian market and a red exterior
• 6 Amp power supply for the U.S. and International markets. A Fire Retardant
Lexan Window in hinged door allows for viewing of the
• Easy configuration via DIP switches
status LED’s. It comes with a durable CAT-30 lock and
key. Space is provided for up to 10 AH batteries.
SPECIFICATIONS
Primary Input Power 120 volts, 60 Hz, 1 Amps
PRODUCT LISTINGS
(Optional 220VAC)
Indicating Current 24VDC unfiltered, 5Amps California
Standby Power 24VDC standby batteries State Fire
Charging Capability 10 – 24 AH batteries Marshal
S6468 7165-0410:152
Dimensions 14 7/8"H x 14 1/2"W x 5"D
Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0030 01/2007
ORDERING INFORMATION

Model Description
Fire Alarm Control Panel
HCP-204E Four expandable to Eight Zone Microprocessor Based Fire Alarm Control Panel comes with
4 Class B (Style B) or 2 Class A (Style D) initiating circuits, 2 Class A/B (Style Z/Y) indicat-
ing circuits and a 6 amp power supply. Expandable up to 8 Class B (Style B) initiating
circuits or 4 Class A (Style D) and 4 Class A/B (Style Z/Y) indicating circuits. Allows for one
HDACT-100 Digital Communicator or one HPR-100 Polarity Reversal Module. Also allows
for one HRM-204 or HRM-208 Auxiliary Relay Module. Red enclosure comes with keylock
door.
HRTI-1 Remote Trouble Indicator
Adder Modules
HDM-204 Four Class B (Style B) or Two Class A (Style D) Initiating Circuit and 2 Class A/B (Style Z/Y)
Indicating Circuit Module
HDACT-100 Digital Alarm Communication Transmitter/Dialer Module
HPR-100 Polarity Reversal/City Tie Module
HRM-204 Auxiliary Relay Module comes with 4 configurable relays
HRM-208 Auxiliary Relay Module comes with 8 configurable relays
Remote Annunciator
HRAM-208 Remote Multiplex Annunciator comes with common control features, indicators and 8
bi-colored LEDs
Controls: Signal Silence, Buzzer Silence, Lamp Test & System Reset
Indicators: A.C. On, Common Trouble & Signal Silence

Hochiki America Corporation HCP-204E Specifications subject to change without notice.


HCP-1008E FIRE ALARM CONTROL PANEL
DESCRIPTION
Hochiki’s HCP-1008E Fire Alarm Control Panel is a
microprocessor based unit designed for maximum flexibility
and easy installation. Fully configurable from the front
panel using the push buttons and DIP switches, it enables
the user to configure the system to meet their specific
requirements.
The HCP-1008E consists of one HMCC-1024-6 main
Chassis in an HBB-1024 Enclosure. The HMCC1024-6
main Chassis comes complete with 8 Class B (Style B)
initiating circuits which may be configured as 4 Class A
(Style D) circuits. It can be expanded up to 24 Class B or
12 Class A circuits with the addition of two HDM-1008
Initiating Circuit Modules. In addition it comes equipped
with 4 Class A/B (Style Z/Y) indicating circuits which are
each rated at 1.7 Amps. The main Chassis also includes
a 6 amp power supply which powers the system and
supplies two 4-wire resettable regulated smoke power
supply of 24 VDC 200mA maximum each. The HMCC-
STANDARD FEATURES 1024-6 also allows for the addition of two HSGM-1004
• 8 Class B (Style B) initiating circuits which may Signal Modules or two HRM-1008 Relay Modules in place
be configured as 4 Class A (Style D) circuits of the HDM-1008 Initiating Circuit Adder Modules.
Expandable up to 24 Class B or 12 Class A (Maximum of 2 adder modules and 1 communication
initiating circuits module).
• 4 Class A/B (Style Z/Y) indicating circuits with The cabinet is available in a beige color for the Canadian
individual trouble indicators (1.7 Amps max. per market and a red exterior for the U.S. and international
circuit) markets. A Fire Retardant Lexan Window in the hinged
• Each indicating circuit can be configured as door allows for viewing of the status LEDs. It comes with
silenceable or non-silenceable. Audibles may be a durable CAT-30 lock and key. Space is provided for up
configured as Steady, Temporal Code, California to 17 AH Gel Cell batteries.
Code or March Time
Hochiki's HCP-1008E is designed as an economical
• Each initiating circuit can be configured as alarm, Microprocessor Based Fire Alarm Control Panel which is
supervisory, waterflow or trouble expandable up to 24 display points. Its modular design
• Two outputs for 4 wire resettable smoke power suits various applications. Ideal for applications such as
supply (200 mA Max. each) small institutional and commercial buildings, shopping
• Alarm verification on initiating circuits malls, offices and public establishments, the HCP-1008E
is configurable to meet virtually all requirements. The panel
• Easy configuration via push buttons and DIP
is designed to be easy in its installation, operation and
switches on the front panel
maintenance. This makes the system cost effective and
SPECIFICATIONS very reliable for its intended applications.
Primary Input Power 120 volts, 60 Hz, 1 Amps
(Optional 220 - 240VAC) PRODUCT LISTINGS
Indicating Current 24VDC unfiltered, 5Amps California
Standby Power 24VDC standby batteries State Fire
Charging Capability 10 – 24 AH batteries Marshal
S6468 7165-0410:154
Dimensions 26"H x 14 1/2"W x 4 1/2" D

Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 • Buena Park, CA 90621-2268
Phone: 714/522-2246 • Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0067 08/2007
ORDERING INFORMATION

Model Description
Fire Alarm Control Panel
HCP-1008E Microprocessor Based Fire Alarm Control Panel expandable up to 24 display points.
Includes HMCC-1024-6 main Chassis complete with 8 Class B (Style B) initiating circuits
or 4 Class A (Style D) initiating circuits, 4 Class A/B (Style Z/Y) indicating circuits, 6 amp
power supply and one HBB-1024 Red Enclosure. (DIP switches)
HCP-1008ES Microprocessor Based Fire Alarm Control Panel expandable up to 24 display points.
Includes HMCC-1024-6S main Chassis complete with 8 Class B (Style B) initiating
circuits or 4 Class A (Style D) initiating circuits, 4 Class A/B (Style Z/Y) indicating circuits,
6 amp power supply and one HBB-1024 Red Enclosure. (Slide switch version)
HFA-1024TR Semi-Flush Trim Ring
HRTI-1 Remote Trouble Indicator
Adder Modules
HDM-1008 Eight Class B (Style B) or 4 Class A (Style D) Initiating Circuit Module
HSGM-1004 Four Class A/B (Style Z/Y) Indicating Circuit Module (Rated at 1.7 Amps per circuit).
HRM-1008 Eight Relay Circuit Module comes with eight Form C relays (Rated for 28 VDC @ 1 Amp.
max. per relay)
Auxiliary Modules
HDACT-100U Universal Digital Alarm CommunicationTransmitter/Dialer Module
HDACT-100 Digital Alarm Communication Transmitter/Dialer Module
HPR-100 Polarity Reversal and City Tie Module
Remote Annunciator
HRAM-1032 Main Annunciator Chassis comes with common control features, indicators and 32
bi-colored LEDs
HBB-1001 Annunciator backbox with keylock door

Hochiki America Corporation • HCP-1008E Fire Alarm Control Panel Specifications subject to change without notice.
HCP-200 AUXILIARY MODULES
GENERAL

The HCP-200 Microprocessor Based Fire Alarm System The following modules have been designed to adapt the
can be configured to meet virtually any requirements. system to suit the particular requirements of a building.

HDM-204
FOUR INITIATING CIRCUIT & TWO INDICATING
CIRCUIT MODULE

The HDM-204 Module provides the HCP-204E Fire Alarm


Control Panel with up to 4 Class B (Style B) or 2 Class
A (Style D) Initiating Circuits. In addition it provides up
to 2 Class A/B (Style Z/Y) Indicating Circuits which are
rated for 1.7 Amps each. Each of the indicating circuits
can be configured for silenceable or non silenceable. In
addition each circuit comes with an individual trouble
indicator. All circuits are power limited for use with limited
energy cable. The HDM-204 consists of a PC board
which mounts at the bottom of the chassis. The PC
board is connected via cables to the board on the main
chassis.

HRM-204
AUXILIARY QUAD RELAY MODULE

The HRM-204 Auxiliary Relay Module provides the HCP-


200 Series with four configurable auxiliary relays. The
relays can be configured for either relay per zone,
Common Alarm relay(s) or Common Supervisory relay(s).
Each relay is rated for 28 VDC @ 1 Amp max. The
module is mounted on the top of any detection module,
with hardware provided for the module. Requires one
HCH-429 Accessory Mounting Plate when HRM-204 is
mounted in the HCP-202 or HCP-204.

Continued on back.

PRODUCT LISTINGS

Underwriters Laboratories: S6468


CSFM #: 7165-0410:152
Specifications subject to change without notice.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0054 12/2004
HRM-208
EIGHT RELAY MODULE

The HRM-208 Auxiliary Relay Module provides the HCP-


200 Series with eight configurable auxiliary relays. The
relays can be configured for either relay per zone,
Common Alarm relay(s) or Common Supervisory relay(s).
Each relay is rated for 28 VDC @ 1 Amp max. The
module is mounted on the top of any detection module,
with hardware provided for the module. Requires one
HCH-429 Accessory Mounting Plate when an HRM-208
is mounted in the HCP-202 or HCP-204.

HPR-100
POLARITY REVERSAL & CITY TIE MODULE

The HPR-100 Polarity Reversal & City Tie Module allows


connection to two different types of monitoring systems.
The City Tie provides an output of 24 VDC at 210 mA
max. The module supervises the City Tie connection
and will provide a system trouble if not connected. A
terminating resistor is supplied with the module. The
Polarity Reversal provides a 24 VDC output for normal
condition and a polarity reverse 24 VDC output for alarm.
The module is also capable of transmitting a system
trouble “Zero Volts.” This option is jumper selectable.
The output current is limited to 8 mA.

HDACT-100
DIGITAL ALARM COMMUNICATOR TRANSMITTER/
DIALER MODULE

The HDACT-100 Digital Alarm Communicator Transmitter/


Dialer Module allows the HCP-200 Fire Alarm Control
Panels to use one or two phone lines to call a Central
Station and report a local Alarm, Trouble or Supervisory
condition. Requiring two supervised telephone lines, the
HDACT-100 can be programmed to use the Security
Industry Association (SIA) Digital Communication
Standard (DCS) and Ademco Contact ID protocols. The
HDACT-100 is powered by the HCP-200 Fire Alarm
Control Panels and communicates with them via an RS-
485 Interface. The HCFG-100 Configuration and
Diagnostics Tool is required to program the HDACT-100.

Hochiki America Corporation HCP-200 Auxiliary Module Specifications subject to change without notice.
HRAM-208 REMOTE ANNUNCIATOR

DESCRIPTION

The HRAM-208 Remote Annunciator is a multiplexed


annunciator that provides control, indication of com-
mon annunciator functions and 8 zones of LED
annunciation. The HRAM-208 Remote Annunciator
comes standard with 8 Bi-Colored LEDs which are
automatically configured for either Alarm (Red) or
Supervisory (Amber) to match the HCP-200 Series
Fire Alarm Control Panels. The unit mounts in a 4-
gang electrical box.

The HRAM-208 also comes equipped with common


control switches for Signal Silence, Buzzer Silence,
Lamp Test and System Reset. In addition it has LEDs
for Power On, Common Trouble and Signal Silence. The
HRAM- 208 is equipped with a keyswitch which allows for
the enabling and disabling of Common Control functions.

All points are identified by the corresponding label the


slides in beside the LED. Up to three HRAM-208 remote
annunciators can be used with the HCP-204 and HCP-
STANDARD FEATURES 204E Fire Alarm Control Panels.

• 8 Bi-Colored LEDs which are automatically


configured for either Alarm (Red) or Supervisory
(Amber) to match the Series 200 Fire Alarm Control
Panels
• Signal Silence, Buzzer Silence, Lamp Test and
System Reset switches
• LEDs for Power On, Common Trouble and Signal
Silence
• Equipped with a keyswitch which allows for enabling
and disabling of the Common Control functions
• Each point can be identified by the corresponding
label beside the LED
• Mounts in a standard 4-gang electrical box
• Up to three HRAM-208 Remote Annunciators can
be used with the HCP-204 and HCP-204E Fire
Continued on back.
Alarm Control Panels
PRODUCT LISTINGS
Underwriters Laboratories: S5694

CSFM #: 7120-0410:153

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 12/2003
INSTALLATION DIAGRAM

Standard Electrical
Box

Secure
with
#6-32
Screws

Paper Label

Wall

Clear Lexan Std Std


Elec. Elec.
Wall Box
Box

Surface Mount Flush Mount

TYPICAL WIRING DIAGRAM

24 VDC - 24 VDC POWER FROM


OUTPUT FIRE ALARM CONTROL PANEL
+

24 VDC - 24 VDC POWER TO


INPUT NEXT ANNUNCIATOR
+

- RS-485 FROM FIRE ALARM


(TWISTED SHIELDED PAIR)
RS-485
OUTPUT S

- RS-485 TO NEXT ANNUNCIATOR


RS-485 (TWISTED SHIELDED PAIR)
INPUT S

NOTE: ALL CIRCUITS ARE POWER LIMITED AND


MUST USE TYPE FPL, FPLR, OR FPLP POWER
LIMITED CABLE.

Hochiki America Corporation HRAM-208 Specifications subject to change without notice.


HRA-1000 REMOTE ANNUNCIATORS
HRAM-1032- Main Annunciator Chassis

The HRAM-1032 Main Annunciator Chassis is an


expandable module used in the HRA-1000 Series
Remote Annunciators to provide control, indication of
common annunciator functions and up to 32 points of
annunciation. The HRAM-1032 comes standard with Bi-
colored LEDs which are automatically configured for
either alarm (Red) or Supervisory (Amber) to match the
HCP-1000 Fire Alarm Control Panel configuration. Each
display point can be identified by the slide-in label that
HRAM-1032 slides in beside the LED. Equipped with sealed
membrane-like buttons and LED indicators, the HRAM-
1032 has a Local Buzzer as well as indicators for A.C.
On, Common Trouble, Remote Failure, Aux. Disconnect,
Acknowledge, General Alarm, Signal Silence and Test/
Configuration mode. In addition it has controls for System
Reset, Lamp Test, Fire Drill, Auxiliary Disconnect, Buzzer
Silence, Signal Silence, General Alarm and Acknowledge.
It occupies one slot in the HBB-1000 enclosures.

HRAX-1048 HRAX-1048 - Adder Annunciator Chassis


STANDARD FEATURES The HRAX-1048 Adder Annunciator Chassis is used in
the HRA-1000 Series Remote Annunciators to provide
• Large capacity of annunciation 48 additional points of annunciation. The HRAX-1048 is
• Bi-Colored LEDs an expandable annunciator module which can be
• Slide-in labels for each display point connected to an HRAM-1032. A maximum of four HRAX-
• Sealed membrane-like buttons and LED indicators 1048 can be connected to the HRAM-1032 Main
• Each annunciation point is automatically selected Annunciator Chassis. As with the HRAM-1032 Main
for either Alarm (Red) or Supervisory (Amber) to Annunciator Chassis, the HRAX-1048 has Bi-colored
match the HCP-1000 Fire Alarm Panel configuration LEDs which are automatically configured for either Alarm
• LEDs for A.C. On, Common Trouble, Remote Failure, (Red) or Supervisory (Amber) to match the HCP-1000
Aux. Disconnect, Ackowledge, General Alarm, Signal Fire Alarm Control Panel configuration. Each display
Silence and Test/Config Mode point can be identified by the slide-in label that slides in
• Controls for System Reset, Lamp Test, Fire Drill, besides the LED. It occupies one slot in the HBB-1000
Aux. Disconnect, Buzzer Silence, Signal Silence, enclosures.
General Alarm and Ackowledge
• Three sizes of enclosures Continued on back.

SPECIFICATIONS PRODUCT LISTINGS


HBB-1001 Enclosure 9¼”H x 13¼”W x 1¼”D Underwriters Laboratories: S5694
HBB-1002 Enclosure 16¼”H x 13¼”W x 1¼”D
HBB-1003 Enclosure 23¼”H x 13¼”W x 1¼”D CSFM #: 7120-0410:157
Specifications subject to change without notice.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 • Buena Park, CA 90621-2268
Phone: 714/522-2246 • Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 06/2003
TYPICAL WIRING DIAGRAM

BACKBOX HEIGHT MOUNTING BACKBOX WALL

H (IN.) A(IN.) B(IN.)

HBB-1001 9.0" 9.95" 7.5"

HBB-1002 16.0" 9.95" 14.5"


DOOR
HBB-1003 23.0" 9.95" 21.5"

BACKBOX CAN BE MOUNTED


WITH STANDARD 4" X 4"
ELECTRICAL BOXES
12.75"

1.2"

#6-32
HEXNUTS
BB-1001 BACKBOX IS SHOWN

ANNUNCIATOR CHASSIS

ORDERING INFORMATION

Model Description

Modules
HRAM-1032 Main Annunciator Chassis comes with Common Control Features, Indicators and 32 Bi-Colored
LEDs
HRAX-1048 Adder Annunciator Chassis comes with 48 Bi-Colored LEDs

Backboxes
HBB-1001 Annunciator backbox with keylock door (Houses 1 module)
HBB-1002 Annunciator backbox with keylock door (Houses 2 modules)
HBB-1003 Annunciator backbox with keylock door (Houses 3 modules)

Hochiki America Corporation • HRA-1000 Remote Annunciators Specifications subject to change without notice.
SLV-24 PHOTOELECTRIC SMOKE DETECTOR
APPLICATION
The SLV-24 can be used in all areas where Photoelec-
tric Smoke Detectors are required. The patented smoke
chamber makes the SLV-24 well suited for fires ranging
from smoldering to flaming fires.
NS-4 Series, NS-6 Series, HSC-4R or HSC-xxx R Style
bases may be used with the SLV-24. Current
interchangeable/compatible devices are the SIJ-24
ionization detector, the SLR-24H photoelectric detector
with heat sensor, and the DCD-135/190 heat detectors.
All NS conventional devices are mechanically
compatible with Hochiki America HSB, HSC and YBA
Shown without base type bases which may have been used in previous
STANDARD FEATURES installations. Please check individual panel listings for
• Low profile, 2.0" high (with base) compatible bases.
• 2 or 4 wire base compatibility, relay bases available
• Highly stable operation, RF/Transient protection OPERATION
• Low standby current, 45µA at 24VDC The SLV-24 photoelectric smoke detector utilizes two
• Two built-in power/sensitivity supervision/alarm LEDs bicolored LEDs for indication of status. In a normal
• Non-directional smoke chamber standby condition the LEDs flash Green every 3 sec-
• Vandal resistant security locking feature onds. When the detector senses that its sensitivity has
• Built-in magnetic go/no go detector test feature drifted outside the UL listed sensitivity window the LEDs
• Removable smoke labyrinth for cleaning or will flash Red every 3 seconds. When the detector
replacement
senses smoke and goes into alarm the status LEDs will
• Automatic Sensitivity window verification function latch on Red.
meets outlined requirements in NFPA 72, Chapter
10 Inspection, Testing and Maintenance The detector utilizes an infrared LED light source and
• Compatible with SIJ-24 ionization detectors silicon photo diode receiving element in the smoke cham-
• Backwards compatible with Hochiki SLK/SLR-24 ber. In a normal standby condition, the receiving ele-
and SIH detectors ment receives no light from the pulsing LED light source.
• Highly resistant to false alarms caused by steam In the event of a fire, smoke enters the detector smoke
SPECIFICATIONS chamber and light is reflected from the smoke particles
to the receiving element. The light received is converted
Light Source GaAlAs Infrared
into an electronic signal.
Emitting Diode
Rated Voltage 17.7 - 30.0 VDC Signals are processed and compared to a reference level,
Working Voltage 15.0 - 33.0 VDC and when two consecutive signals exceeding the refer-
ence level are received within a specified period of time,
Maximum Voltage 42 VDC
the time delay circuit triggers the SCR switch to activate
Supervisory Current 45µA @ 24 VDC the alarm signal. The status LEDs light continuously
Surge Current 160µA max. @ 24VDC during the alarm period.
Alarm Current 150mA max. @ 24 VDC
Air Velocity Range 0-300 fpm PRODUCT LISTINGS
Ambient Temperature 32°F to 120°F (0°C to 49°C)
California
Color & Case Material Bone PC/ABS Blend
Sensitivity Test Feature Automatic Sensitivity State Fire
window verification test Marshal
Sensitivity Range 0.5 - 3.8%/ft S1383 7272-0410:174
Mounting Refer to NS Conventional Continued on back.
Detector Base Data Sheet

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0075 04/2008
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Hochiki America Model SLV-24 photoelectric smoke detectors.
The combination detector head and twist-lock base shall be UL listed compatible with a UL listed fire alarm panel.
The base shall permit direct interchange with Hochiki America SLR-24H combination photoelectric/heat detector, SIJ-24 ionization
type smoke detector and/or DCD-135/190 fixed temperature/rate-of-rise heat detectors. The base shall be appropriate twist-lock base
NS-4 Series, NS-6 Series, HSC-4R, or HSC-xxx R. In the event of partial or complete retrofit, the SLV-24 maybe used in conjunction
with, or as a replacement for, Hochiki America detectors (SLK-24, SLK-24FH, SLR-24V and the SIH-24) on most HSB and HSC base
applications.
The smoke detector shall have two flashing status LEDs for visual supervision. When the detector is in standby condition the LEDs
will flash Green. When the detector is outside the UL listed sensitivity window the LEDs will flash Red. When the detector is
actuated, the flashing LEDs will latch on Red. The detector may be reset by actuating the control panel reset switch.
The sensitivity of the detector shall be capable of being measured. It shall be possible to perform a functional test of the detector
without the need of generating smoke. The sensitivity of the detector shall be monitored automatically and continuously to verify that
it is operating within the listed sensitivity range.
To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be employed to
minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated.

SLV-24 SENSITIVITY TEST FEATURE


The SLV-24 Photoelectric Smoke Detector has a built-in automatic sensitivity test feature.
1. In normal condition, both LED's flash green.
2. When the sensitivity drifts outside of its sensitivity limits, both LED's flash red.
3. In the alarm state both LED's are red continuously.
4. When the sensitivity drifts outside of its sensitivity limits and both LED's flash red, the device needs to be cleaned or returned
to the factory for cleaning. Refer to HA Technical Bulletin HA-97 for cleaning information.

2-WIRE OPERATION
UL LISTED
CONTROL LISTED
PANEL END OF LINE
DEVICE

PANEL Resistor shown is for


example only. Not all
POWER annunciators have in
SUPPLY line resistance.
NOTE: - WIRING TERMINALS FOR THE NS4
NEGATIVE AND NS6 ARE IDENTICAL
NS4 SERIES NS6 SERIES - BASES WITH THE "W" SUFFIX
Annunciation device must be current limited to 20 mA @ ARE WHITE IN COLOR
24VDC Maximum. Not limiting current could result in
damage to the detector or cause a no alarm condition.

2-WIRE RELAY OPERATION


UL LISTED LISTED
CONTROL END OF LINE
PANEL
DEVICE
TERMINAL BLOCK USED ON
HSC-224RA/RST VERSION ONLY
HSC-(XXX)R (2-WIRE)
COM 6
GRY
N/C 5 BLU
GRN
N/O 4 YEL

HSC-RELAY SERIES
ORN
N/O 3 PUR

N/C 2 2 AND 4 WIRE BASE


RELAYS SHOWN WITH
1 POWER OFF.
4-WIRE OPERATION
COM

INITIATING LISTED
CIRCUIT END OF LINE
DEVICE
HSC-4R
CONTACTS
H1
H2
YEL
ORN
PUR

UL LISTED LISTED
POWER END OF LINE
SUPPLY RELAY
12VDC OR 24VDC HA-EOLR-12 OR HA-EOLR-24

HSC-4R HSC-4R
Hochiki America Corporation SLV-24 Specifications subject to change without notice.
SLV-24V PHOTOELECTRIC SMOKE DETECTOR
APPLICATION
The SLV-24V can be used in all areas where Photoelec-
tric Smoke Detectors are required. The patented smoke
chamber makes the SLV-24V well suited for fires rang-
ing from smoldering to flaming fires.
NS-4 Series, NS-6 Series, HSC-4R or HSC-xxx R Style
bases may be used with the SLV-24V. Current
interchangeable/compatible devices are the SIJ-24
ionization detector, the SLR-24H photoelectric detector
with heat sensor, and the DCD-135/190 heat detectors.
All NS conventional devices are mechanically
compatible with Hochiki America HSB, HSC and YBA
Shown without base type bases which may have been used in previous
STANDARD FEATURES installations. Please check individual panel listings for
• Low profile, 2.0" high (with base) compatible bases.
• 2 or 4 wire base compatibility, relay bases available
• Highly stable operation, RF/Transient protection OPERATION
• Low standby current, 45µA at 24VDC The SLV-24V photoelectric smoke detector utilizes two
• Two built-in power/sensitivity supervision/alarm LEDs bicolored LEDs for indication of status. In a normal
• Non-directional smoke chamber standby condition the LEDs flash Green every 3 sec-
• Vandal resistant security locking feature onds. When the detector senses that its sensitivity has
• Built-in magnetic go/no go detector test feature drifted outside the UL listed sensitivity window the LEDs
• Removable smoke labyrinth for cleaning or will flash Red every 3 seconds. When the detector
replacement senses smoke and goes into alarm the status LEDs will
• Automatic Sensitivity window verification function latch on Red.
meets outlined requirements in NFPA 72, Chapter 10
Inspection, Testing and Maintenance The detector utilizes an infrared LED light source and
• Compatible with SIJ-24 ionization detectors silicon photo diode receiving element in the smoke cham-
• Backwards compatible with Hochiki SLK/SLR-24V ber. In a normal standby condition, the receiving ele-
and SIH detectors ment receives no light from the pulsing LED light source.
• Highly resistant to false alarms caused by steam In the event of a fire, smoke enters the detector smoke
SPECIFICATIONS chamber and light is reflected from the smoke particles
to the receiving element. The light received is converted
Light Source GaAlAs Infrared
into an electronic signal.
Emitting Diode
Rated Voltage 17.7 - 30.0 VDC Signals are processed and compared to a reference level,
Working Voltage 15.0 - 33.0 VDC and when two consecutive signals exceeding the refer-
ence level are received within a specified period of time,
Maximum Voltage 42 VDC
the time delay circuit triggers the SCR switch to activate
Supervisory Current 45µA @ 24 VDC the alarm signal. The status LEDs light continuously
Surge Current 160µA max. @ 24VDC during the alarm period.
Alarm Current 150mA max. @ 24 VDC
Air Velocity Range 0-4000 fpm PRODUCT LISTINGS
Ambient Temperature 32°F to 120°F (0°C to 49°C)
California
Color & Case Material Bone PC/ABS Blend
State Fire
Sensitivity Test Feature Automatic Sensitivity
Marshal
window verification test
S1383 7272-0410:174
Sensitivity Range 0.5 - 2.68%/ft
Mounting Refer to NS Conventional Continued on back.
Detector Base Data Sheet

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0076 04/2008
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Hochiki America Model SLV-24V photoelectric smoke detectors.
The combination detector head and twist-lock base shall be UL listed compatible with a UL listed fire alarm panel.
The base shall permit direct interchange with Hochiki America SLR-24H combination photoelectric/heat detector, SIJ-24 ionization
type smoke detector and/or DCD-135/190 fixed temperature/rate-of-rise heat detectors. The base shall be appropriate twist-lock base
NS-4 Series, NS-6 Series, HSC-4R, or HSC-xxx R. In the event of partial or complete retrofit, the SLV-24V maybe used in conjunction
with, or as a replacement for, Hochiki America detectors (SLK-24, SLK-24FH, SLR-24V and the SIH-24) on most HSB and HSC base
applications.
The smoke detector shall have two flashing status LEDs for visual supervision. When the detector is in standby condition the LEDs
will flash Green. When the detector is outside the UL listed sensitivity window the LEDs will flash Red. When the detector is
actuated, the flashing LEDs will latch on Red. The detector may be reset by actuating the control panel reset switch.
The sensitivity of the detector shall be capable of being measured. It shall be possible to perform a functional test of the detector
without the need of generating smoke. The sensitivity of the detector shall be monitored automatically and continuously to verify that
it is operating within the listed sensitivity range.
To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be employed to
minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated.

SLV-24V SENSITIVITY TEST FEATURE


The SLV-24V Photoelectric Smoke Detector has a built-in automatic sensitivity test feature.
1. In normal condition, both LEDs flash green.
2. When the sensitivity drifts outside of its sensitivity limits, both LEDs flash red.
3. In the alarm state both LEDs are red continuously.
4. When the sensitivity drifts outside of its sensitivity limits and both LEDs flash red, the device needs to be cleaned or returned
to the factory for cleaning. Refer to HA Technical Bulletin HA-97 for cleaning information.

2-WIRE OPERATION
UL LISTED
CONTROL LISTED
PANEL END OF LINE
DEVICE

PANEL Resistor shown is for


example only. Not all
POWER annunciators have in
SUPPLY line resistance.
NOTE: - WIRING TERMINALS FOR THE NS4
NEGATIVE AND NS6 ARE IDENTICAL
NS4 SERIES NS6 SERIES - BASES WITH THE "W" SUFFIX
Annunciation device must be current limited to 20 mA @ ARE WHITE IN COLOR
24VDC Maximum. Not limiting current could result in
damage to the detector or cause a no alarm condition.

2-WIRE RELAY OPERATION


UL LISTED LISTED
CONTROL END OF LINE
PANEL
DEVICE
TERMINAL BLOCK USED ON
HSC-224RA/RST VERSION ONLY
HSC-(XXX)R (2-WIRE)
COM 6
GRY
N/C 5 BLU
GRN
N/O 4 YEL

HSC-RELAY SERIES
ORN
N/O 3 PUR

N/C 2 2 AND 4 WIRE BASE


RELAYS SHOWN WITH
1 POWER OFF.
4-WIRE OPERATION
COM

INITIATING LISTED
CIRCUIT END OF LINE
DEVICE
HSC-4R
CONTACTS
H1
H2
YEL
ORN
PUR

UL LISTED LISTED
POWER END OF LINE
SUPPLY RELAY
12VDC OR 24VDC HA-EOLR-12 OR HA-EOLR-24

HSC-4R HSC-4R
Hochiki America Corporation SLV-24V Specifications subject to change without notice.
SLR-24V PHOTOELECTRIC SMOKE DETECTOR
APPLICATION
The SLR-24V can be used in all areas where Photoelec-
tric Smoke Detectors are required. The wide range
smoke chamber makes the SLR-24V well suited for fires
ranging from smoldering to flaming fires.
NS-4 Series, NS-6 Series, HSC-4R or HSC-xxx R Style
bases may be used with the SLR-24V. Current
interchangeable/compatible devices are the SIJ-24
ionization detector, the SLR-24H photoelectric detector
with heat sensor, and the DCD-135/190 heat detectors.
All NS conventional devices are mechanically
compatible with Hochiki America HSB, HSC and YBA
Shown without base. type bases which may have been used in previous
STANDARD FEATURES installations. Please check individual panel listings for
compatible bases.
• Low profile, 1.8" high (with base)
• 2 or 4 wire base compatibility, relay bases available OPERATION
• Highly stable operation, RF/Transient protection
• Low standby current, 45μA at 24VDC The SLR-24V photoelectric smoke detector utilizes two
• Two built-in power/sensitivity supervision/alarm LEDs bicolored LEDs for indication of status. In a normal
• Non-directional smoke chamber standby condition the LEDs flash Green every 3 sec-
• Vandal resistant security locking feature onds. When the detector senses that its sensitivity has
• Built-in magnetic go/no go detector test feature drifted outside the UL listed sensitivity window the LEDs
• Removable smoke labyrinth for cleaning or will flash Red every 3 seconds. When the detector
replacement senses smoke and goes into alarm the status LEDs will
• Automatic Sensitivity window verification function latch on Red.
meets outlined requirements in NFPA 72, Chapter 2 The detector utilizes an infrared LED light source and
& 7, Inspection, Testing and Maintenance silicon photo diode receiving element in the smoke cham-
• Compatible with SIJ-24 ionization detectors ber. In a normal standby condition, the receiving ele-
• Backwards compatible with Hochiki SLK and SIH ment receives no light from the pulsing LED light source.
detectors In the event of a fire, smoke enters the detector smoke
SPECIFICATIONS chamber and light is reflected from the smoke particles
Light Source GaAlAs Infrared to the receiving element. The light received is converted
Emitting Diode into an electronic signal.
Rated Voltage 17.7 - 30.0 VDC Signals are processed and compared to a reference level,
Working Voltage 15.0 - 33.0 VDC and when two consecutive signals exceeding the refer-
Maximum Voltage 42 VDC ence level are received within a specified period of time,
the time delay circuit triggers the SCR switch to activate
Supervisory Current 45μA @ 24 VDC
the alarm signal. The status LEDs light continuously
Surge Current 160μA max. @ 24VDC during the alarm period.
Alarm Current 150mA max. @ 24 VDC
Air Velocity Range 0-4000 fpm PRODUCT LISTINGS
Ambient Temperature 32°F to 120°F (0°C to 49°C)
Color & Case Material Bone PC/ABS Blend California
Sensitivity Test Feature Automatic Sensitivity State Fire
window verification test Marshal
1D5A1.AY
Mounting Refer to NS Conventional S1383 7272-0410:107
Detector Base Data Sheet Continued on back.
Specifications subject to change without notice.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0017 04/2007
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Hochiki America Model SLR-24V photoelectric smoke detectors.
The combination detector head and twist-lock base shall be UL listed compatible with a UL listed fire alarm panel.
The base shall permit direct interchange with Hochiki America SLR-24H combination photoelectric/heat detector, SIJ-24 ionization
type smoke detector and/or DCD-135/190 fixed temperature/rate-of-rise heat detectors. The base shall be appropriate twist-lock base
NS-4 Series, NS-6 Series, HSC-4R, or HSC-xxx R. In the event of partial or complete retrofit, the SLR-24V maybe used in conjunction
with, or as a replacement for, Hochiki America detectors (SLK-24, SLK-24FH and the SIH-24) on most HSB and HSC base applica-
tions.
The smoke detector shall have two flashing status LEDs for visual supervision. When the detector is in standby condition the LEDs
will flash Green. When the detector is outside the UL listed sensitivity window the LEDs will flash Red. When the detector is
actuated, the flashing LEDs will latch on Red. The detector may be reset by actuating the control panel reset switch.
The sensitivity of the detector shall be capable of being measured. It shall be possible to perform a functional test of the detector
without the need of generating smoke. The sensitivity of the detector shall be monitored automatically and continuously to verify that
it is operating within the listed sensitivity range.
To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be employed to
minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated.

SLR-24V SENSITIVITY TEST FEATURE


The SLR-24V Photoelectric Smoke Detector has a built-in automatic sensitivity test feature.
1. In normal condition, both LED's flash green.
2. When the sensitivity drifts outside of its sensitivity limits, both LED's flash red.
3. In the alarm state both LED's are red continuously.
4. When the sensitivity drifts outside of its sensitivity limits and both LED's flash red, the device needs to be cleaned or returned
to the factory for cleaning. Refer to HA Technical Bulletin HA-97 for cleaning information.

2-WIRE OPERATION
UL LISTED
CONTROL LISTED
PANEL END OF LINE
DEVICE

PANEL Resistor shown is for


example only. Not all
POWER annunciators have in
SUPPLY line resistance.
NOTE: - WIRING TERMINALS FOR THE NS4
NEGATIVE AND NS6 ARE IDENTICAL
NS4 SERIES NS6 SERIES - BASES WITH THE "W" SUFFIX
Annunciation device must be current limited to 20 mA @ ARE WHITE IN COLOR
24VDC Maximum. Not limiting current could result in
damage to the detector or cause a no alarm condition.

2-WIRE RELAY OPERATION


UL LISTED LISTED
CONTROL END OF LINE
PANEL
DEVICE
TERMINAL BLOCK USED ON
HSC-224RA/RST VERSION ONLY
HSC-(XXX)R (2-WIRE)
COM 6
GRY
N/C 5 BLU
GRN
N/O 4 YEL

HSC-RELAY SERIES
ORN
N/O 3 PUR

N/C 2 2 AND 4 WIRE BASE


RELAYS SHOWN WITH
1 POWER OFF.
4-WIRE OPERATION
COM

INITIATING LISTED
CIRCUIT END OF LINE
DEVICE
HSC-4R
CONTACTS
H1
H2
YEL
ORN
PUR

UL LISTED LISTED
POWER END OF LINE
SUPPLY RELAY
12VDC OR 24VDC HA-EOLR-12 OR HA-EOLR-24

HSC-4R HSC-4R
Hochiki America Corporation SLR-24V Specifications subject to change without notice.
SLR-24H PHOTOELECTRIC/ HEAT SMOKE DETECTOR
APPLICATION
The SLR-24H can be used in all areas where Photoelectric
Smoke Detectors are required. The wide range smoke
chamber makes the SLR-24H well suited for fires ranging
from smoldering to flaming fires.

NS-4 Series, NS-6 Series, HSC-4R or HSC-xxx R Style


bases may be used with the SLR-24H. Current
interchangeable/compatible devices are the SIJ-24
ionization detector, SLR-24V photoelectric detector and
the DCD-135/190 heat detectors.

All NS conventional devices are mechanically compatible


with Hochiki America HSB, HSC and YBA type bases
which may have been used in previous installations.
Shown without base. Please check individual panel listings for compatible
bases.
STANDARD FEATURES
• Low profile, 2.2" high (with base)
OPERATION
• 2 or 4 wire base compatibility, relay bases available
• 135°F latching heat sensor The SLR-24H photoelectric smoke detector utilizes two
• Heat sensor protected by a built-in guard bicolored LED's for indication of status. In a normal
standby condition the LED's flash Green every 3
• Highly stable operation, RF/Transient protection
seconds. When the detector senses that its sensitivity
• Low standby current, 45μA at 24VDC has drifted outside the UL listed sensitivity window the
• Two built-in power/sensitivity supervision/alarm LED's LED's will flash Red every 3 seconds. When the detector
• Non-directional smoke chamber senses smoke and goes into alarm the status LED's will
• Vandal resistant security locking feature latch on Red.
• Removable smoke labyrinth for cleaning or replacement
• Automatic Sensitivity window verification function The detector utilizes an infrared LED light source and
meets outlined requirements in NFPA 72, Chapter 2 & 7, silicon photo diode receiving element in the smoke
Inspection, Testing and Maintenance chamber. In a normal standby condition, the receiving
element receives no light from the pulsing LED light
SPECIFICATIONS source. In the event of a fire, smoke enters the detector
smoke chamber and light is reflected from the smoke
Light Source GaAlAs Infrared particles to the receiving element. The light received is
Emitting Diode converted into an electronic signal.
Heat Sensor 135°F
Rated Voltage 17.7 - 30.0 VDC Signals are processed and compared to a reference level,
Working Voltage 15.0 - 33.0 VDC and when two consecutive signals exceeding the
Maximum Voltage 42 VDC reference level are received within a specified period of
Supervisory Current 45μA @ 24 VDC time, the time delay circuit triggers the SCR switch to
Surge Current 160μA max. @ 24 VDC activate the alarm signal. The status LED's light
continuously during the alarm period.
Alarm Current 150mA max. @ 24 VDC
Ambient Temperature 32°F to 120°F
(0°C to 49°C) PRODUCT LISTINGS
Color & Case Material Bone PC/ABS Blend Underwriters Laboratories: S1383
Sensitivity Test Feature Automatic Sensitivity CSFM #: 7272-0410:107
window verification test Factory Mutual: 3006185
Mounting Refer to NS Conventional
Detector Base Data Sheet
Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0015 10/2005
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Hochiki America Model SLR-24H photoelectric
smoke detectors. The combination detector head and twist-lock base shall be UL listed compatible with a UL listed fire
alarm panel.

The base shall permit direct interchange with Hochiki America SLR-24V photoelectric detector, SIJ-24 ionization type
smoke detector and/or DCD-135/190 fixed temperature/rate-of-rise heat detectors. The base shall be appropriate twist-
lock base NS-4 Series, NS-6 Series, HSC-4R, or HSC-xxx R. In the event of partial or complete retrofit, the SLR-24
maybe used in conjunction with, or as a replacement for, Hochiki America detectors (SLK-24, SLK-24FH and the SIH-
24) on most HSB and HSC base applications.

The smoke detector shall have two flashing status LED's for visual supervision. When the detector is in standby
condition the LED's will flash Green. When the detector is outside the UL listed sensitivity window the LED's will flash
Red. When the detector is actuated, the flashing LED's will latch on Red. The detector may be reset by actuating the
control panel reset switch.

The sensitivity of the detector shall be capable of being measured. It shall be possible to perform a functional test of the
detector without the need of generating smoke. The sensitivity of the detector shall be monitored automatically and
continuously to verify that it is operating within the listed sensitivity range.

To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be
employed to minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated.

The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be field removable when not required.

SLR-24H SENSITIVITY TEST FEATURE


The SLR-24H Photoelectric Smoke Detector has a built-in automatic sensitivity test feature.
1. In normal condition, both LED's flash green.
2. When the sensitivity drifts outside of its sensitivity limits, both LED's flash red.
3. In the alarm state both LED's are red continuously.
4. When the sensitivity drifts outside of its sensitivity limits and both LED's flash red, the device needs to be
cleaned or returned to the factory for cleaning. Refer to HA Technical Bulletin HA-97 for cleaning information.

(+) 4-WIRE OPERATION


INITIATING LISTED
CIRCUIT END OF LINE
DEVICE
HSC-4R
CONTACTS
(-) H1
H2
YEL
ORN
PUR

UL LISTED (+) LISTED


POWER END OF LINE
SUPPLY RELAY
12VDC OR 24VDC
(-)

HSC-4R HSC-4R

2-WIRE OPERATION
UL LISTED (+)
CONTROL LISTED
PANEL END OF LINE
DEVICE
(-)
PANEL Resistor shown is for example
POWER only. Not all annunciators have
in line resistance.
SUPPLY
(-) NOTE: - WIRING TERMINALS FOR THE NS4
NEGATIVE AND NS6 ARE IDENTICAL
NS4 SERIES NS6 SERIES - BASES WITH THE "W" SUFFIX
Annunciation device must be current limited to 20 mA @ ARE WHITE IN COLOR
24VDC Maximum. Not limiting current could result in
damage to the detector or cause a no alarm condition.

2-wire relay wiring diagram is also available


Hochiki America Corporation SLR-24H Specifications subject to change without notice.
SLR-835/SLR-835H PHOTOELECTRIC SMOKE DETECTOR

SLR-835 Shown without a base SLR-835H Shown without a base


STANDARD FEATURES
APPLICATION
• Low Profile - Only 1.8" high (2.2" 835H)
• 2 or 4 wire base compatibility, relay bases available The HOCHIKI America SLR-835/-835H can be used in all
areas where photoelectric smoke detectors are required. It is
• 135°F latching heat sensor (835H only)
suited for fires ranging from smoldering to flaming fires.
• Heat sensor protected by a built-in guard (835H only) NS4 Series, NS6 Series, HSC-4R or HSC-(X)R Style bases
• Highly stable operation, RF/Transient protection may be used with the SLR-835/-835H.
• Low standby current
• Two built-in power/sensitivity supervision/alarm LEDs
• Non-directional smoke chamber OPERATION
• Vandal resistant security locking feature The SLR-835/-835H Photoelectric Smoke Detector utilizes
• Removable smoke labyrinth for cleaning or replacement two bicolored LEDs for indication of status. In a normal
• Backwards compatible with Hochiki SLK and SIH detectors standby condition the LEDs flash green every 3 seconds.
• Automatic Sensitivity window verification function meets When the detector senses that its sensitivity has drifted
outline requirements in the NFPA 72 Inspection Testing outside the UL listed sensitivity window the LEDs will flash
and Maintenance, Chapter 7 Red every 3 seconds. When the detector senses smoke
and goes into alarm the status LEDs will latch on Red.
SPECIFICATIONS
Light Source GaAl AS infrared L.E.D. The detector utilizes an infrared LED light source and silicon
Operating Voltage Nominal 12 VDC or 24 VDC photo diode receiving element in the smoke chamber. In a
normal standby condition, the receiving element receives
Working Voaltage 8.0-35.0 VDC no light from the pulsing LED light source. In the event of a
Wave Form Filtered DC 15% Ripple Max fire, smoke enters the detector smoke chamber and light is
Heat Sensor 135° F (835H only) reflected from the smoke particles to the receiving element.
Supervisory Current 38μA AVG @12 VDC The light received is converted into an electronic signal.
55μA AVG @24 VDC Signals are processed and compared to a reference level,
70μA AVG @35 VDC and when two consecutive signals exceeding the reference
Surge Current 200μA Max @24 VDC level are received within a specified period of time, the time
Alarm Current 150mA Max delay circuit triggers the SCR switch to activate the alarm
Ambient Temperature 32° F - 120° F (0°C - 49°C) signal. The status LEDs light continuously during the alarm
Compatibility Identifier HD-3 period.
Color & Case Material Bone/White PC/ABS Blend
Sensitivity Test Feature Automatic Sensitivity PRODUCT LISTINGS
window verification Test
Ordering Codes California
White SLR-835W/SLR-835HW State Fire
Bone SLR-835/SLR-835H Marshal
Dimensions 1.8" (2.2" 835H) H x 3.94" W 3007144
S1383 7272-0410:107
Mounting Refer to NS Conventional
Detector Base Data Sheet Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0024 04/2007
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Hochiki America Model SLR-835 Photoelectric smoke
detectors. The combination detector head and twist-lock base shall be UL listed compatible with a UL listed fire alarm panel.
When the supply power is 24VDC, the base shall permit direct interchange with Hochiki America SLR-24H combination
photoelectric/heat detector, SLR-24 photoelectric smoke detector, SIJ-24 ionization type smoke detector and DCD-135/190heat
detector.
The base shall be the appropriate twist-lock base NS4 Series, NS6 Series, HSC-4R, or HSC-(X)R Series. In the event of partial
or complete retrofit, the SLR-835, SLR-835H may be used in conjunction with, or as a replacement for, Hochiki America
detectors ( SLK-835H, SLK-24F, SLK-24FH and the SIH-24F) on most HSB and HSC base application.
The smoke detector shall have two flashing status LEDs for visual supervision. When the detector is in standby condition the
LEDs will flash Green. When the detector is outside the UL listed sensitivity window the LEDs will flash Red. When the detector
is actuated, the flashing LEDs will latch on Red. The detector may be reset by actuating the control panel reset switch.
The sensitivity of the detector shall be capable of being measured. It shall be possible to perform a functional test of the detector
without the need of generating smoke. The sensitivity of the detector shall be monitored automatically and continuously to verify
that it is operating within the listed sensitivity range.
To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be
employed to minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated on the drawing. The
locking feature shall be field removable when not required.

SLR-835/-835H SENSITIVITY TEST FEATURE


The SLR-835/-835H Photoelectric Smoke Detector has a built-in automatic sensitivity test feature.
1. In normal condition, both LEDs flash Green.
2. When the sensitivity drifts outside of its sensitivity limits, both LEDs flash Red.
3. In the alarm state both LEDs are Red continuously.
4. When the sensitivity drifts outside of its sensitivity limits and both LED's flash Red, the device needs to be cleaned or
returned to the factory for cleaning. Refer to HA Technical Bulletin HA-97 for cleaning information.

4-WIRE OPERATION
INITIATING LISTED
CIRCUIT END OF LINE
DEVICE
HSC-4R
CONTACTS
H1
H2

YEL
ORN
PUR
UL LISTED
POWER
SUPPLY LISTED
24VDC END OF LINE
RELAY
HA-EOLR-24

HSC-4R HSC-4R
2-WIRE OPERATION
UL LISTED
CONTROL LISTED
PANEL END OF LINE
DEVICE

PANEL Resistor shown is for example


POWER only. Not all annunciators have
in line resistance.
SUPPLY

NEGATIVE NS4 SERIES


NS6 SERIES
Annunciation device must be current limited to 20 mA @ NOTE: - WIRING TERMINALS FOR THE NS4
24VDC Maximum. Not limiting current could result in AND NS6 ARE IDENTICAL
damage to the detector or cause a no alarm condition. BASES WITH THE "W" SUFFIX
ARE WHITE IN COLOR

2-WIRE RELAY OPERATION


UL LISTED LISTED
CONTROL END OF LINE
PANEL DEVICE
TERMINAL BLOCK USED ON

HSC-(XXX)R (2-WIRE)
COM 6
N/C 5 GRY
BLU
GRN
N/O 4 YEL
ORN
HSC-RELAY SERIES N/O 3 PUR

N/C 2 2 AND 4 WIRE BASE


RELAYS SHOWN WITH
COM 1 POWER OFF.

Hochiki America Corporation SLR-835 Specifications subject to change without notice.


SLR-835B DIRECT-WIRE PHOTOELECTRIC
SMOKE DETECTOR
STANDARD FEATURES
• Low Profile - Only 2.0" High
• 2 or 4 Wire Models
• Highly Stable Operation, RF/Transient Protection
• Two built-in power/sensitivity supervision/alarm LED's
• Non-Directional Smoke Chamber
• Vandal Resistant Security Locking Feature
• Removable smoke labyrinth for cleaning or
replacement
• Automatic Sensitivity window verification function
meets outlined requirements in NFPA 72,
Inspection,Testing and Maintenance
Shown with Trim Ring

APPLICATION
SPECIFICATIONS The HOCHIKI America SLR-835B Series can be used in
all areas where Photoelectric Smoke Detectors are re-
Light Source GaAlAs Infrared LED quired. It is suited for smoldering or flaming fires.
Operating Voltage Nominal: 12 VDC or 24 VDC
Working Voltage 8.0 - 35.0 VDC
OPERATION
(35.0 VDC Max)
Wave Form Filtered DC 15% Ripple Max. The SLR-835B Series photoelectric smoke detector
Alarm Current 150mA Maximum utilizes two bicolored LED's for indication of status. In
a normal standby condition the LED's flash Green every
Surge Current 200µA Maximum (2 wire)
3 seconds. When the detector senses that its sensitivity
Average Stand-By 38µA AVG @12 VDC
has drifted outside the UL listed sensitivity window the
Current 55µA AVG @24 VDC
LED's will flash Red every 3 seconds. When the detector
70µA AVG @35 VDC senses smoke and goes into alarm the status LED's
Ambient Temperature 32° F - 120° F (0° C - 49° C) will latch on Red.
Sensitivity Test Feature Automatic Sensitivity
Window Verification Test The unit is comprised of an LED light source and silicon
Compatibility Identifier HD-6 photo diode receiving element. In a normal standby
Order Codes condition, the receiving element receives no light from
2-Wire Detector & Trim Ring pulsing light source. In the event of fire, smoke enters
Bone SLR-835B-2 the detector and light is reflected from the smoke
White SLR-835B-2W particles to the receiving element. The light received is
converted to an electronic signal. Signals are processed
4-Wire Detector & Trim Ring
Bone SLR-835B-4 Continued on back.

White SLR-835B-4W
PRODUCT LISTINGS
Underwriters Laboratories: S1383
Factory Mutual: 3007144
Specifications subject to change without notice. CSFM #: 7272-0410:107

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0026 11/2005
OPERATION, continued
in the comparator, and when two consecutive signals exceeding the basic level are received within a specific period of
time, the time delay circuit triggers the SCR switch to activate the alarm signal. The status LED lights continuously
during alarm period.

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans HOCHIKI America SLR-835B direct-wire photoelectric
smoke detectors. The detector shall be UL listed compatible (2-wire model) with a UL listed fire alarm panel.

The smoke detector shall have green flashing status LED's for visual supervision. When the detector is actuated, the
flashing LED's will turn red and latch on steady. The detector may be reset by actuating the control panel reset switch.

The detector shall have a sensitivity window verification feature. If the sensitivity of the detector drifts outside its
approved window the LED's will flash red to indicate an out of sensitivity condition.

The vandal resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be field selectable.

It shall be possible to perform a functional test of the detector without the need of generating smoke. The method shall
simulate effects of products of combustion in the chamber to ensure testing of detector circuits.

Voltage and RF transient suppression techniques shall be employed to minimize false alarm potential.

WIRING DIAGRAMS
2-Wire Wiring Diagram

U.L. Listed Listed


Compatible End-of-Line
Control Device
Panel

4-Wire Wiring Diagram

U.L. Listed Listed


Control End-of-Line
Device
Panel

U.L. Listed
Power
Supply
*24VDC Listed
End-of-Line
Relay
12 or 24VDC
U.L. Listed
Power
Supply
*12VDC
* Use either 12 OR 24VDC . They cannot be used simultaneously.

Hochiki America Corporation SLR-835B Specifications subject to change without notice.


SLR-835BH DIRECT-WIRE PHOTOELECTRIC
HEAT SMOKE DETECTOR
STANDARD FEATURES
• Low Profile - Only 2.375" High.
• 2 or 4 Wire Models
• 135° F Latching Heat Sensor
• Highly Stable Operation, RF/Transient Protection
• Two built-in power/sensitivity supervision/alarm LED's
• Non-Directional Smoke Chamber
• Vandal Resistant Security Locking Feature
• Removable smoke labyrinth for cleaning or
replacement
• Automatic Sensitivity window verification function
meets outlined requirements in NFPA 72,
Inspection,Testing and Maintenance.
Shown With Trim Ring
DESCRIPTION
SPECIFICATIONS The SLR-835BH Series photoelectric smoke detector
Light Source GaAl AS Infrared LED utilizes two bicolored LEDs for indication of status. In a
normal standby condition the LEDs flash Green every 3
Voltage
seconds. When the detector senses that its sensitivity
Nominal 12 VDC or 24 VDC
has drifted outside the UL listed sensitivity window the
Working 8.0 - 35.0 VDC (35.0 VDC Max)
LEDs will flash Red every 3 seconds. When the detector
Wave Form Filtered DC senses smoke and goes into alarm the status LEDs
15% Ripple Max. will latch on Red.
Alarm Current 150mA Maximum
The unit is comprised of an LED light source and silicon
Surge Current 200μA Maximum (2 wire)
photo diode receiving element. In a normal standby
Average Stand-By 38μA AVG @12 VDC
condition, the receiving element receives no light from
Current 55μA AVG @24 VDC pulsing light source. In the event of fire, smoke enters
70μA AVG @35 VDC the detector and light is reflected from the smoke
Ambient Temperature 32° F - 120° F (0° C - 49° C) particles to the receiving element. The light received is
Sensitivity Test Feature converted to an electronic signal. Signals are processed
Automatic Sensitivity Window Verification Test in the comparator, and when two consecutive signals
Compatibility Identifier HD-6 exceeding the basic level are received within a specific
Heat Sensor 135° F period of time, the time delay circuit triggers the SCR
Order Codes switch to activate the alarm signal. The Status LED
lights continuously during alarm period.
2-Wire Detector & Trim Ring
White SLR-835BH-2W
PRODUCT LISTINGS
Bone SLR-835BH-2
4-Wire Detector & Trim Ring California
White SLR-835BH-4W State Fire
Marshal
Bone SLR-835BH-4 3012444
S1383 7272-0410:107
Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0019 04/2007
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans HOCHIKI America SLR-835BH baseless photoelectric
smoke detectors. The combination detector head shall be UL listed compatible with an UL listed fire alarm panel.

The smoke detector shall have flashing status LED for visual supervision. When the detector is actuated, the flashing
LED will latch on steady at full brilliance. The detector may be reset by actuating the control panel reset switch.

The detector shall have a sensitivity window verification feature.

The vandal resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be field selectable.

It shall be possible to perform a functional test of the detector without the need of generating smoke. The method shall
simulate effects of products of combustion in the chamber to ensure testing of detector circuits.

Voltage and RF transient suppression techniques shall be employed to minimize false alarm potential.

WIRING DIAGRAMS

2-Wire Wiring Diagram

U.L. Listed Listed


Compatible End-of-Line
Control Device
Panel

4-Wire Wiring Diagram

U.L. Listed Listed


Control End-of-Line
Device
Panel

U.L. Listed
Power 24VDC 12VDC C NO 24VDC 12VDC C NO

Supply
*24VDC Listed
End-of-Line
Relay
12 or 24VDC
U.L. Listed
Power
Supply
*12VDC
* Use either 12 OR 24VDC . They cannot be used simultaneously.

Hochiki America Corporation SLR-835BH Specifications subject to change without notice.


SIJ-24 IONIZATION SMOKE DETECTOR
APPLICATION
The SIJ-24 can be used in all areas where Ionization
Smoke Detectors are required. The responsive yet highly
stabile operation allows the SIJ-24 to fit in a wide range
of uses. The SIJ-24 can be used in areas where early
warning of superheated or flaming combustibles is
expected.

NS-4 Series, NS-6 Series, HSC-4R or HSC-(X)R Style


bases may be used with the SIJ-24. Current compatible
devices are the SLR-24V Photoelectric detector, the SLR-
24H photoelectric detector with heat sensor and the DCD-
135/190 heat detectors.

All NS conventional devices are mechanically compatible


with Hochiki America HSB, HSC and YBA type bases
Shown without base. which may have been used in previous installations.
Please check individual panel listings for compatible
STANDARD FEATURES bases.
• Low profile, 1.8" high (with base)
• 2 or 4 wire base compatibility, relay bases available OPERATION
• Highly stable operation, RF/Transient protection
The SIJ-24 ionization smoke detector utilizes two bi-
• Low standby current, 40µA at 24 VDC
colored LEDs for status indication purposes. In a normal
• Two built-in power/alarm LEDs for 360° viewing
• Non-directional smoke chamber standby condition the LEDs flash green approximately
• Vandal resistant security locking feature once each second. When the detector senses smoke
• Built-in magnetic detector sensitivity test feature and goes into alarm the status LEDs will latch on red.
Meets NFPA 72, Chapter 2 & 7, Inspection, Testing
and Maintenance requirements A single radioactive source of Americium-241 ionizes two
• Compatible with SLR-24V photoelectric detectors chambers within the detector, a reference chamber, and
• Backwards compatible with Hochiki SLK and SIH the smoke sensing chamber. The air is ionized by this
smoke detectors source and a small DC current flows between the
electrodes of each chamber. Smoke can freely enter
SPECIFICATIONS the sensing chamber while the inner chamber is virtually
Radioactive Source AM-241 0.5µCi sealed to smoke. Smoke entering the sensing chamber
Rated Voltage 17.7 - 30.0 VDC causes a reduction in the DC current flow, the voltage
Working Voltage 15.0 - 33.0 VDC imbalance between the two chambers is proportional to
Maximum Voltage 42 VDC the smoke density. When the voltage differences become
Supervisory Current 40µA @ 24 VDC great enough it causes the detector to go into alarm.
Surge Current 200µA max. @ 24 VDC The two chamber design is utilized to compensate for
Alarm Current 150mA max. @ 24 VDC changes in atmospheric and environmental conditions.
Ambient Temperature 32°F to 120°F (0°C to 49°C)
%/FT Obsc. 0.53 - 1.40 PRODUCT LISTINGS
Color & Case Material Bone PC/ABS Blend
Sensitivity Test Feature Magnetically activated California
dual reed switch test State Fire
Mounting Refer to the NS Conventional Marshal
1D5A1.AY
S1383 7271-0410:135
Detector Base Data Sheet
Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0027 01/2008
ENGINEERING SPECIFICATIONS
The contractor shall furnish and install where indicated on the plans, Hochiki America Model SIJ-24 ionization smoke
detectors. The combination detector head and twist-lock base shall be UL listed compatible with a UL listed fire alarm
panel.

The base shall permit direct interchange with Hochiki America, SLR-24V photoelectric type smoke detector, SLR-24H
combination photoelectric/heat detector, and/or DCD-135/190 fixed temperature/rate-of-rise heat detectors. The base
shall be appropriate twistlock base NS-4 Series, NS-6 Series, HSC-4R or HSC-(X)R. In the event of partial or complete
retrofit, the SIJ-24 maybe used in conjunction with, or as a replacement for, Hochiki America detectors (SLK-24, SLK-
24FH and the SIH-24F) on most HSB and HSC base applications.

The smoke detector shall have two flashing status LEDs for visual supervision. When the detector is in standby
condition the LEDs will flash Green. When the detector is actuated, the flashing LEDs will latch on Red. The detector
may be reset by actuating the control panel reset switch.

The sensitivity of the detector shall be capable of being measured. It shall be possible to perform a functional test of the
detector without the need of generating smoke. The test method shall simulate effects of products of combustion in the
chamber to ensure testing of the detector electronics.

To facilitate installation, the detector shall be non-polarized. Voltage and RF transient suppression techniques shall be
employed to minimize false alarm potential. Auxiliary SPDT relays shall be installed where indicated.

The vandal-resistant, security locking feature shall be used in those areas as indicated on the drawing. The locking
feature shall be field removable when not required.

SIJ-24 SENSITIVITY TEST FEATURE


TEST PROCEDURE
1. With detector wired to appropriate initiating circuit or current limited power source and with normal applied
power, place a magnet as shown in Figure 1.
2. Wait at least six seconds. Detector SHOULD NOT alarm and LED should not light.
3. Place magnet on detector as shown in Figure 2 (opposite side).
4. Wait at least six seconds. Detector SHOULD alarm.
5. If detector does alarm when magnet is positioned as in Figure 1 or does not produce an alarm when magnet
is positioned as in Figure 2, detector is not within specified sensitivity limits and may require service. See
Technical Bulletin HA-97 for more information and for additional sensitivity test devices.

WARNING: Conduct testing only under Normal Standby conditions. Abnormal or Low Power conditions may
affect sensitivity. Always reset power prior to testing of next unit.

LED's
Figure 1 Figure 2

Hochiki America Corporation SIJ-24 Specifications subject to change without notice.


DCD 135/190 FIXED TEMPERATURE/RATE OF RISE HEAT DETECTOR
APPLICATION
The DCD-135/-190 fixed temperature/rate-of-rise heat
detector are suited for installation where high heat output
fires are expected or in areas where ambient conditions
would not allow use of other detection methods. Heat
detectors are intended for protection of property. Do
not rely on heat detectors for life safety protection.
Where life safety is a concern, smoke detectors must
also be used. A UL listed fire alarm panel must
electronically supervise the DCD-135/-190 heat
detectors.

All NS conventional devices are mechanically compatible


with Hochiki America HSB, HSC and YBA type bases.
Please check individual panel listings for appropriate
Shown without base
listed bases.
STANDARD FEATURES
• Choice of fixed temperature/rate-of-rise OPERATION
135°F or 190°F heat detector
The DCD-135/-190 fixed temperature/rate-of-rise heat
• UL Listed spacing up to 60' by 60'
detectors are suited to detect in the presence of slow or
• 2 or 4 wire base compatibility, relay bases available
fast rising temperatures due to burning combustibles.
• Highly stable operation, RF/Transient protection
The construction of these models incorporate a
• Low standby current, 35µA nominal
thermistor heat element protected from damage by the
• Two built-in power/alarm LED's for 360° viewing
built-in, durable plastic guard. These electronic heat
• Fully electronic operation
detectors incorporate two power/alarm LED's for 360°
• Power/alarm LED's confirm detector status
indication of status. In standby condition the power LED's
• Compatible with Hochiki SLR-24V and SIJ-24
flash Green. In an alarm condition the LED's latch on
detectors and their bases
Red. The DCD-135/-190 electronic heat detection
circuitry performs the same function as a Mechanical
SPECIFICATIONS Device but with Electronic Precision. If the heat rise is
Response Temperature 135° ± 7.5°F less than 12°/minute the DCD will not alarm until it
Temperature 190° ± 7.5°F reaches its alarm temperature (135° or 190° ± 7.5°F). If
Rated Voltage 17.7 - 30.0 VDC the heat rise is greater than 12°/minute the DCD will
Working Voltage 15.0 - 33.0 VDC alarm immediately giving an early warning signal and
Maximum Voltage 42 VDC latching the Red alarm LED's on.
Supervisory Current 40µA @ 24 VDC
Surge Current 160µA max. @ 24 VDC PRODUCT LISTINGS
Alarm Current 150mA max. @ 24 VDC
Ambient Temperature 32°F to 120°F
(0°C to 49°C) MEA
284-91E Vol. IV
Contact Rating N/O Contacts
150mA max. @ 24 V 1D5A1.AY
S2966 California
Color & Case Material Bone PC/ABS blend State Fire
Mounting Refer to the NS Conventional Marshal
Detector Base Data Sheet 7270-0410:151

Specifications subject to change without notice. Continued on back.

Find latest revision at www.hochiki.com


Hochiki America Corporation
7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0016 01/2008
ENGINEERING SPECIFICATIONS

Automatic heat detectors where ambient temperatures do not exceed 120°F shall be the DCD-135 fixed temperature/
rate-of-rise heat detector rated at 135°F. For areas where ambient temperatures exceed 120°F, but not 160°F, the
DCD-190 fixed temperature/rate-of-rise heat detector rated at 190°F shall be used. Electrical contacts shall be
normally open, rated at 150mA @ 24VDC.

Heat detectors shall be installed in accordance with National Fire Protection Association Standard 72, the spacing
assigned by Underwriters Laboratories and in accordance with the rules and regulations set forth by the local authorities
having jurisdiction. Automatic heat detectors shall be Underwriters Laboratories listed.

4-WIRE OPERATION
(+)
INITIATING LISTED
CIRCUIT END OF LINE
DEVICE
HSC-4R
CONTACTS
(-) H1
H2
YEL
ORN
PUR

UL LISTED (+) LISTED


POWER END OF LINE
SUPPLY RELAY
24VDC (-) HA-EOLR-24

HSC-4R HSC-4R

2-WIRE OPERATION

UL LISTED (+)
CONTROL LISTED
PANEL END OF LINE
DEVICE
(-)
PANEL Resistor shown is for example
POWER only. Not all annunciators have
in line resistance.
SUPPLY
(-)
NEGATIVE
NS4 SERIES NS6 SERIES
Annunciation device must be current limited to 20 mA @
24VDC Maximum. Not limiting current could result in
damage to the detector or cause a no alarm condition.

2-WIRE RELAY OPERATION

(+)

UL LISTED LISTED
CONTROL END OF LINE
PANEL DEVICE
TERMINAL BLOCK USED ON
HSC-224RA/RST VERSION ONLY
(-) HSC-(XXX)R (2-WIRE)
COM 6
GRY
N/C 5 BLU
GRN
N/O 4 YEL
ORN
HSC-RELAY SERIES N/O 3 PUR

N/C 2 2 AND 4 WIRE BASE


RELAYS SHOWN WITH
COM 1 POWER OFF.

Hochiki America Corporation DCD-135/-190 Specifications subject to change without notice.


DFE 135/190 FIXED TEMPERATURE HEAT DETECTOR
APPLICATION
The DFE 135/190 fixed temperature heat detector is
suited for installation where high heat output fires are
expected or in areas where ambient conditions would
not allow use of other detection methods.

Heat detectors are used for property protection. Do not


rely on heat detectors for life safety protection. Where
life safety is involved, smoke detectors must also be
used.

Heat detectors should be electronically supervised from


a UL listed alarm panel.

OPERATION
The DFE 135/190 fixed temperature heat detector is
STANDARD FEATURES suited to alarm in the presence of slowly rising
temperatures. The construction of this model
• Choice of fixed temperature - 135°F or 190°F
incorporates an oversized heat collector protected from
• UL Listed ceiling spacing of 50' by 50' damage by the built-in, durable plastic guard. The DFE
135/190 fixed temperature heat detector used the proven
(2,500 square feet) snap-disc principle of operation. This bi-metal disc
• Self-Restoring deflects when temperature reaches a predetermined
value. The disc deflection then causes a push-rod to
• Heat element protected by a built-in guard close the internal contact resulting in an alarm condition.
• Contact Rating of 100 mA The bi-metal disc returns to its normal shape when the
heat subsides causing internal contacts to return to their
• Highly Dependable normally open position. A standby condition is restored.
• Latching LED base available

ENGINEERING SPECIFICATIONS
SPECIFICATIONS
Automatic heat detectors shall be fixed temperature rated
Response Temperature 135° ± 7.5°F at 135°F for areas where ambient temperatures do not
Temperature 190° ± 7.5°F exceed 120°F and 190°F where ambient temperatures
Contact Rating N/O Contacts exceed 120°F but not 160°F. The fixed temperature el-
100mA @ 60 V ement shall consist of a bi-metallic disc and actuator
Color & Case Material Ivory ACS shaft. Electrical contacts shall be normally open, rated
Mounting Refer to back of this sheet at 100mA @ 60VDC.

Heat detectors shall be installed in accordance with


PRODUCT LISTINGS National Fire Protection Association Standard 72, the
spacing assigned by Underwriters Laboratories, and in
Underwriters Laboratories: S2966 accordance with the rules and regulations set forth by
CSFM #: 7270-0410:119 the local authorities having jurisdiction. Automatic heat
MEA Report #: 284-91-E Vol. II detectors shall be Underwriters Laboratories listed.

Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 10/2003
COMPATIBLE BASES

HSC-(XXX)L HEAT DETECTOR BASE

The HSC-xxx L Series is a 6" base featuring a current limiting resistor, latching annunciator output
and a latching circuit so the alarm LED will remain lit until the control panel has been reset. Heat
detectors are not recognized as proper detection for life safety protection, therefore they should
be utilized only for the protection of property.

COMPATIBLE (+)
UL LISTED LISTED
CONTROL END OF LINE
PANEL DEVICE
3.9K 1/2W
(-)
Pig Tail Lead
PANEL
POWER (-)
SUPPLY
HSC-(XXX)L SERIES
NEGATIVE
Nominal alarm current shown at 24V. Polarized with annunciator output.
HSC-21L 24mA HSC-221L 41mA
HSC-224L 38mA HSC-220L 73mA

NS6-100 DETECTOR BASE

The NS6-100 is a 6" diameter base that has no current limiting nor annunciator output features.
A direct short occurs across the loop when the detector is actuated. Heat detectors are not
recognized as proper detection for life safety protection, therefore they should be utilized only
for the protection of property.

(+)
COMPATIBLE
UL LISTED LISTED
CONTROL
PANEL DEVICE
(-)
6 6

NS6-100
Non polarized, not current limited. No annunciator output.

We try to keep our product information up-to-date and accurate. However, we cannot cover
all specifications or anticipate all requirements. For additional information contact
your local distributor or call or write Hochiki America Corporation.

Hochiki America Corporation DFE-135/190 Specifications subject to change without notice.


SPC-24 PROJECTED BEAM SMOKE DETECTOR
APPLICATION
The Hochiki America SPC-24 Projected Beam Smoke
Detector consists of an emitter and receiver. The
projected beam smoke detector should be placed so
that smoke generated by a fire will likely rise into the
path of the beam. The receiver is constantly monitoring
and measuring the intensity of the beam transmitted
by the emitter. Should the smoke from a fire cause a
decrease in the signal strength of a magnitude that
exceeds the programmed obscuration setting, an alarm
signal is generated.
The SPC-24 Projected Beam Smoke Detector can
provide vital fire detection in applications where other
types of detectors may not be able to respond quickly,
STANDARD FEATURES or at all, to a fire condition. Examples of some applica-
• Microprocessor based for reliability tions where projected beam smoke detectors have
• Simple setup & alignment with signal strength LED's been successfully used include:
atriums gymnasiums theatres
• Provides 60 feet on center linear protection at a museums factories tunnels
range of 32.8 feet to 328 feet churches stables warehouses
• Automatic compensation for signal drift or dirty lens anecoic chambers high air velocity areas
• Three field adjustable sensitivity settings The Hochiki America SPC-24 Projected Beam Smoke
• Form A alarm and Form B trouble contacts Detector may also be used in conjunction with more
• Calibrated filters available to verify sensitivity traditional spot type smoke detection devices to provide
• Color-coded emitter and receiver labels for easy an even more comprehensive detection system.
recognition
OPERATION
SPECIFICATIONS The near infrared pulsed beam generated by the
Rated Voltage 24VDC emitter is sensed by the photodiode of the receiver,
Working Voltage 19VDC - 33VDC where it is converted into an electrical signal. This
Supervisory Current Emitter 50µA @ 24VDC signal is then amplified and applied, via an analog to
Receiver 200µA @24VDC digital converter, to a microprocessor. The normal
Alarm Current 20mA @ 24DC state signal (the initial beam data) once stored in the
Trouble Current 20mA @ 24VDC microprocessor is used as reference for comparison
Operating Temperature with subsequent beam signals.
Range 14° F - 122° F
UL Installation
When there is a difference between actual beam
Temperature Range 32° F - 100° F strength and stored reference data that exceeds the
Sensitivity Test Feature Hochiki test filters programmed alarm obscuration reference level, a fire
Allowable missalignment Emitter +/- 0.5° signal is produced. A trouble signal is generated if the
angle (MAX) Reciever +/-1.0° beam is more that 90% obstructed (as opposed to
Dimensions 5.5" Tall partially obscured by smoke).
3.2" Wide
4.0" Deep PRODUCT LISTINGS
Mounting Wall mount or
Single Gang Box California
Maximum Humidity 95% R.H. non-condensing State Fire
S1383 7260-0410:172
Specifications subject to change without notice.
Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0072 03/2008
OPERATION, continued
The microprocessor also provides compensation for a change in received signal value, with time, caused by contamination
of the optics. Since such a change with time appears as a slow change in the beam signal, the microprocessor
compensates in such a manner that the signal moves closer to the reference data at a rate approximately +1% per
hour. When this compensating capability reaches a limit, the SPC-24 automatically generates a trouble signal.
A calibrated test filter is available upon request to test and verify the sensitivity setting of the SPC-24 projected beam
smoke detectors.

ENGINEERING SPECIFICATIONS
The contractor shall furnish and install, where indicated on the plans, Hochiki America SPC-24 Projected Beam Smoke
Detector. The projected beam smoke detector shall have a range of 32.8 feet to 328 feet. The projected beam smoke
detector shall be field adjustable to one of the three obscuration settings of 25%, 50% or 70% per span. These settings
shall be capable of being verified with calibrated filters. Side to side spacing shall be a maximum of 60 feet on center.
The projected beam smoke detector shall possess circuitry that automatically compensates for normal ambient changes
in the intensity of the emitted beam strength. The microprocessor shall provide compensation for a change in received
signal value, with time, caused by contamination of the optics. Since such a change with time appears as a slow change
in the beam signal, the microprocessor shall compensate in such a manner that the signal moves closer to the reference
data at a rate of approximately +1% per hour. When this compensating capability reaches a limit, the microprocessor
shall automatically generate a trouble signal.
The projected beam smoke detector(s) shall also signal a trouble condition if the beam has a blockage of 90% or more for
more than 20 seconds and automatically resets to normal when blockage is removed.
The projected beam smoke detector(s) shall be UL listed for these applications. Voltage and RF transient protection shall
be integral to the internal circuitry of the projected beam smoke detector so as to minimize false alarm potential.
To facilitate easy installation and setup, the projected beam smoke detectors shall employ signal strength indicating
LED's. Alignment shall be facilitated by turning an alignment adjustment wheel and monitoring the relative signal strength
based upon which LED's are illuminated.
The detectors shall also illuminate a red LED, which is visible externally, when an alarm condition is indicated.
The projected beam smoke detector shall provide a Form "A" dry contact for alarm and Form "B" dry contact for trouble.

INSTALLATION
The HOCHIKI America SPC-24 Projected Beam Smoke Detector shall be installed in accordance with the Installation
Instruction Guide provided with every unit. Refer to the applicable NFPA Standards for additional guidance on spacing,
irregular ceiling surfaces and other design considerations.

FOUR WIRE CONNECTION TO THE CONTROL PANEL

24V + E1 E1 E1 E1
24V - E2 E2 E2 E2
Emitter Emitter

EOL-24

Receiver Receiver
End of Line
24V + 24V 24V 24V 24V Resistor
24V - 0V 0V 0V 0V
F1 F1 F1 F1
Zone +
Zone - F2 F2 F2 F2
T1 T2 T1 T2
Control
Panel

NOTE: EOLR-24 required


NOTE: End of line relay and trouble contacts are closed for power supervision on
when power is applied. Receiver.

Hochiki America Corporation SPC-24 Specifications subject to change without notice.


SRA-24 REFLECTIVE BEAM DETECTOR
APPLICATION
Hochiki's Reflective Beam Detector is designed for
smoke detection in large spaces such as halls, ware-
house, museums, theatres etc., where conventional
point detection is impractical or more costly. The unit
is not suitable for applications where strong or reflected
sunlight is present, in these instances the SPB-24N
should be considered. The unit detects smoke linearly
over the protected range enabling early detection be-
fore the fire spreads. Compact design, good looks and
flush mounting installation makes this unit ideal for fit-
ting in areas where architectural considerations are
important.

GENERAL DESCRIPTION
The Photoelectric reflective beam detector consists of
STANDARD FEATURES the SRA-24 unit and a reflector, which face each other
• Detector spacing from 25ft-100ft. at a distance of between 25ft and 100ft.
• Pulsed beam to reduce overall consumption and In the event of fire the smoke generated will decrease
improve the noise rejection characteristics. the amount of near infrared light energy on the
• Small flat reflector. SRA-24, this decrease is electronically interpreted to
• Automatic drift compensation.
identify the occurrence of fire. An important feature of
• Fire detection sensitivity can be set to 20% or
the detector is that it monitors the protected space
30% obscuration.
linearly. This enables the detector to identify a fire
before it spreads, even when the smoke is scattered
over a large area.
SPECIFICATIONS
The fire detection sensitivity is factory set at 20%
Operating Voltage 15-33Vdc
beam obscuration and it can be changed to 30% with
Stand-by Current 350µA at 24Vdc
a sensitivity switch.
Max Current In Alarm 50mA at 24Vdc
Operating Range 25ft - 100ft The status of the unit is indicated by three LEDs
Sensitivity 20% or 30% which are viewed through a unique lens that allows
Compensation 1% per Hr. ±50% good visibility from any viewing angle, particularly from
Reflector mounting ±10% beneath the unit. The LEDs indicate, Normal, Setup,
angle Fault and Fire Condition, so the user can verify which
unit is in alarm.
Operating Temp. Range 32°F to +100°F
Storage Temp. Range -22°F to +158°F The unit indicates a fault on the zone under the
Maximum Humidity 95%RH - Non condensing following conditions:
(at 104°F)
Color & Case Material Ivory ABS
• Compensation limit exceeded
Size: SRA-24 6" x 4.8" x 3.1"
• Total obscuration of beam
Reflector 7.5" x 7.5" x.1"
• Beam detector unit removed from zone
Weight: SRA-24 1.9 lbs (Including termination module)
Reflector 1.6 oz. PRODUCT LISTINGS
Underwriters Laboratories: S1383
Factory Mutual:
CSFM #: 7260-0410:158

Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 12/2003
ENGINEERING SPECIFICATIONS

The contractor shall furnish and install, where indicated on the plans, HOCHIKI America SRA-24 Reflective
Beam Detector. The detector shall have a range of 25 feet to 100 feet. The beam smoke detector shall be
field adjustable to one of the two obscuration settings of 20%, or 30% per span. These settings shall be
capable of being verified with calibrated filters. Side to side spacing shall be a maximum of 60 feet on
center.

The reflective beam detector shall posses circuitry that automatically compensates for normal ambient
changes in the intensity of the emitted beam strength. The microprocessor shall provide compensation for
a change in received signal value, with time, caused by contamination of the optics. Since such a change
with time appears as a slow change in the beam signal, the microcomputer compensates in such a manner
that the signal moves closer to the reference data at a rate of approximately +1% per hour. When this
compensating capability reaches a limit, the microcomputer automatically generates a trouble signal.

The reflective beam detector(s) shall also signal a trouble condition if the beam has a blockage of 90% for
more than 20 seconds and automatically resets to normal when blockage is removed.

The reflective beam detector(s) shall be UL listed for these applications. Voltage and RF transient protec-
tion shall be integral to the internal circuitry of the reflective beam detector so as to minimize false alarm
potential.

To facilitate easy installation and setup, the reflective beam detectors shall employ signal strength indicat-
ing LED's. Alignment shall be facilitated by turning an alignment adjustment screws and monitoring the
relative signal strength based upon which LEDs are illuminated.

The detectors shall also illuminate a red LED, which is visible externally, when an alarm condition is indi-
cated.

The reflective beam detector shall provide a Form "A" dry contact for alarm and Form "B" dry contact for
trouble.

INSTALLATION
The HOCHIKI America SRA-24 Reflective Beam Detector shall be installed in accordance with the Instal-
lation Instruction Guide provided with every unit. Refer to the applicable NFPA Standards for additional
guidance on spacing, irregular ceiling surfaces and other design considerations.

TYPICAL WIRING

Reflector Reflector

End of Line Relay

End of Line
24V + 24V 24V 24V 24V Resistor
24V - 0V 0V 0V 0V
F1 F1 F1 F1
Zone +
Zone - F2 F2 F2 F2
T1 T2 T1 T2
Control
Panel

NOTE: End of line relay and trouble contacts are closed when power is applied.

Hochiki America Corporation SRA-24 Specifications subject to change without notice.


HF-24 ULTRAVIOLET FLAME DETECTOR
APPLICATION
The HF-24 is suited for use wherever there is a need for
automatic detection of fires which can develop quickly
or where contents have great value.

Suggested applications include:


• Petroleum Storage
• Photographic or Film Storage
• Computer Rooms
• Print Shops
• Museums

The HF-24 is not a substitute for smoke or heat detectors,


but is an added level of protection against fast flaming
fires only.
STANDARD FEATURES
There is no set area for which the HF-24 Ultraviolet
• Detects fast flaming fires Detector is able to cover. The reason is that the size of
• Highly reliable, long life UV receptor tube the fire and the distance from this fire to the detector all
• Low power consumption effect how the detector will respond. There is one non-
• HF-24 can be intermixed with other types of variable, however, and that is very small fires must have
detection on the panel's detection circuitry a duration of at least 7-15 seconds if within 12 feet, 20-
• Interchangeable with Hochiki America's standard 30 seconds at 25 feet.
smoke and heat detector bases.
• Size and color similar to other Hochiki America
smoke and heat detectors.
OPERATION
• Easily Maintained - cleaning can be accomplished The HF-24 uses an ultraviolet detector tube which absorbs
without disassembling the detector. very weak ultraviolet light such as that emitted from a
• Not UL Listed flame. This is detected as a train of discharge pulses
creating a current. The electronic circuitry in the detector
SPECIFICATIONS body translates this action as an alarm signal. There is
Rated Voltage: 17.6 - 27.7 VDC a counter circuit which prevents the alarm from occurring
Working Voltage: 15 - 30 VDC from one-shot ultraviolet light such as lightning or cosmic
Normal Current: 200µA @ 24 VDC flares. Additionally there are circuit refinements which
Alarm Current: 250mA Maximum limit the detection of only wave lengths from 1850 to 3000
Response to Ultraviolet: 1850 - 3000 Angstrom angstroms thus ignoring visible and infrared light.
Ambient Temperature:
14° to 122° Fahrenheit (-10° C to +50° C)
See Reverse Side for
Mounting: HSC-4R, HSB series, Detection Range Graph
NS4 series, NS6 series & and Wiring Diagram.
HSC-xxx L series bases
Color: Ivory ACS
Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 10/2003
DETECTION RANGE

Ceiling
#1
120°
2m
#2
3m
Ceiling Height

4m
5m
6m
7m
8m

Floor

# 1: Flame from a candle or lighter


# 2: Flame from a wad or newspaper, burning flame

WIRING DIAGRAMS

NS Series and HSC Series Base

(+) HSC SERIES NS6 SERIES NS4 SERIES


COMPATIBLE
UL LISTED
CONTROL
PANEL
LISTED
END OF LINE
DEVICE

PANEL
POWER (-)
SUPPLY

HSB-2 Wire

UL LISTED
CONTROL
(+)
PANEL
LISTED
END OF LINE
DEVICE
(-) 3.9K 1/2W
PANEL
POWER 16mA MAX.
SUPPLY OUTPUT
(-) 16mA MAX.
OUTPUT
NEGATIVE CURRENT LIMTED AT 24VDC

Hochiki America Corporation HF-24 Specifications subject to change without notice.


DH-98 CONVENTIONAL DUCT DETECTOR
STANDARD FEATURES
• Detects and limits the spread of smoke throughout
building HVAC ducts
• Ability to interconnect (all relays operate wth a single
alarm) up to 30 units using the same independent
power supply
• Compatible with building automation and fire
alarm systems
• Installs quickly and easily
• Interchangeable “Plug-In” photoelectric or
ionization heads
• No screens or filters to clean
• Cover provides magnet window and
placement guide for operational testing without
Duct housing is available with either a conventional
photoelectric or ionization detector. disassembly
• Rugged gray steel back box with clear cover
• Accessories - Remote power, remote alarm
SPECIFICATIONS indication capability and remote, horn/piezo
Duct Detector Model # DH-98-I DH-98-P DH-98-HVI DH-98-HVP
capability
Operating Voltage 115V AC,
24V AC/DC
115V AC,
24V AC/DC
230V AC,
24V AC/DC
230V AC,
24V AC/DC
• Meets UL 268A Requirements
Detector Head Model SIJ-24DH
Conventional
SLR-24DH
Conventional
SIJ-24DH
Conventional
SLR-24DH
Conventional
DESCRIPTION
Detector Head Type Ionization Photoelectric Ionization Photoelectric
Power Requirements 230 VAC 8mA 8mA The HOCHIKI AMERICA DH-98 Duct Smoke Detector
Standby
115 VAC 14mA 14mA provides early detection of smoke and products of
24 VAC 20mA 20mA 20mA 20mA combustion present in air moving through HVAC ducts in
Power Requirements
24 VDC 13mA 13mA 13mA 13mA
Commercial, Industrial and Residential applications. The
230 VAC 15mA 15mA
Alarm
115 VAC 28mA 28mA
DH-98 is designed to prevent the recirculation of smoke in
24 VAC 95mA 95mA 95mA 95mA
areas by the air handling systems, fans and blowers.
24 VDC 60mA 60mA 60mA 60mA Complete systems may be shut down in the event of smoke
Alarm Contacts 1 form "C" and 1 form "C" and 1 form "C" and 1 form "C" and detection. The HOCHIKI AMERICA DH-98-I and the DH-
1 form "A" rated
at 10 amps @
1 form "A" rated
at 10 amps @
1 form "A" rated
at 10 amps @
1 form "A" rated
at 10 amps @
98-P operate on 115 VAC, 24 VAC and 24 VDC and the
115 V.A.C. 115 V.A.C. 115 V.A.C. 115 V.A.C. DH-98-HVI and the DH-98-HVP operate on 230 VAC, 24
Detection Loop 1 Form A (1A) 1 Form A (1A) 1 Form A (1A) 1 Form A (1A) VAC and 24 VDC.
Trouble Contacts 1 Form "C" 1 Form "C" 1 Form "C" 1 Form "C"

Sensitivity Test Method Dual Reed Self Diagnostic Dual Reed Self Diagnostic
Switch Test Test Switch Test Test The DH-98 is designed and built to meet all local
Remote Indication Capability Power, Alarm, Power, Alarm, Power, Alarm, Power, Alarm, requirements, as well as the NFPA regulations regarding
(Refer to DH-98 Accessories Horn/Piezo, Horn/Piezo, Horn/Piezo, Horn/Piezo,
Data Sheet for Specifications) Test Test Test Test duct smoke detectors. Output terminals are provided for
Air Velocity 300 to 4000 ft./min remote accessories such as a horn, strobe, remote status
Ambient Temperature 32°F to 120°F (0°C to 49°C) indicators and reset key switches or push buttons.
Humidity 10% to 85% Relative Humidity (non-condensing)

Housing Material 18 G.A. steel backbox, clear plastic cover PRODUCT LISTINGS
Finish Grey Paint
Underwriters Laboratories: S1383
Dimensions 9 1/8"L X 7 1/4"W X 2 1/4"H

Maximum Net Weight 3 lbs.


CSFM #: 3240-0410:155
Sampling Tubes
FM #: 3005751
2.5 ft., 5 ft. or 10 ft.

Radioactive Element DH-98-I and DH-98-HVI Only: Americum 241 0.5 Mirco-Curie
Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0038 10/2005
PRODUCT DESCRIPTION, continued
Air sampling is accomplished by two tubes which protrude into the duct. An exhaust tube of one standard length (7.5")
is supplied in the installation kit with the smoke duct unit. Once the duct width has been determined the air intake
sampling tubes must be ordered. Sampling tubes are supplied in three standard lengths 2.5 ft., 5 ft. and 10 ft. and cut
to size to fit the duct. Mounting the duct smoke unit is accomplished by the use of a template and 4 sheet metal
screws, which are provided. Mounting can be achieved without the removal of the clear cover which is secured by 4
capture screws.

The compact DH-98 contains 3 sets of alarm contacts, 1 set of form “C” contacts rated at 10 amps, 1 set of form “A”
contacts rated at 10 amps, 1 set of form “A” contacts rated at 1 amp. There is also 1 set of form “C” 10 amp trouble
contacts for monitoring detector head removal, and the failure of the input supply voltage.

The pilot and alarm visual indicators provided on the front of the DH-98 duct unit, signal the operating status of the
device. A manual test/reset switch is located along side the visual indicators. This switch can be defeated by cutting
a jumper on the PCB.

ENGINEERING SPECIFICATIONS
Air duct smoke detectors shall be HOCHIKI AMERICA DH-98 Series. The detectors shall be listed by Underwriters
Laboratories per UL 268A. The detectors shall operate at air velocities from 300 feet per minute to 4000 feet per minute.
The detectors shall have the ability to interconnect up to 30 units using the same independent power supply.

The duct detector housings shall be of metal construction and complete mechanical installation may be performed
without removal of detector cover. Visual indication of alarm and power must be provided on detector front. A manual
reset switch shall be located on front of the device. Detector heads shall not require additional filters or screens which
must be maintained. The housing shall contain a detector base which will accept photoelectric or ionization detector
heads. Terminal connections shall be of the screw type and be a minimum of # 6 screw. Terminals shall be provided for
remote pilot, remote alarm indication, strobe/horn and remote key switch. All wiring must comply with local codes and
regulations. See
Power
ALARM
CONTACTS
ALARM
CONTACTS
*TROUBLE
CONTACTS
REMOTE
ACCESSORIES
Connections 10.0A @ 115VAC 1A @ 24VDC 10.0A @ 115VAC

WIRING DIAGRAMS
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

*Trouble contacts are shown in non-energized


condition. Trouble contacts monitor power
DH-98 DUCT SMOKE DETECTOR connected and head removed.

24 VDC 60 Hz INPUT
24 VAC 60 Hz INPUT @ 0.1 AMP MAX.(Detector only).
@ 0.1 AMP MAX.(Detector only). UP TO 1.9 AMPS FOR AUXILIARY
UP TO 1.9 AMPS FOR AUXILIARY OUTPUTS (HORNS/STROBES).
OUTPUTS (HORNS/STROBES).

- +

1 2 3 4 5 6 1 2 3 4 5 6

DH-98-I DH-98-I
DH-98-P DH-98-P
24 V.A.C. OPERATION 24 V.D.C. OPERATION

115 VAC 60 Hz INPUT 230 VAC 60 Hz INPUT


@ 0.1 AMP MAX. @ 0.1 AMP MAX.

G N H G N H

1 2 3 4 5 6 1 2 3 4 5 6

DH-98-I DH-98-HVI
DH-98-P DH-98-HVP
115 V.A.C. OPERATION 230 V.A.C. OPERATION

INTERCONNECT WIRING DIAGRAMS


DUCT UNIT #1 DUCT UNIT #2 DUCT UNIT #3

INPUT P
POWER
P

Input Power Source


Will Be Either 16 16 16
24V, 115V or 230V
18 18 18

Hochiki America Corporation DH-98 Conventional Specifications subject to change without notice.
DH-98 DUCT DETECTOR REMOTE ACCESSORIES
APPLICATION SPECIFICATIONS
The DH-98 Duct Detector Remote Accessories are Power Requirements
designed to be used with the DH-98 Conventional Alarm LED 15 mA
and DH-98 Analog Duct Detectors to provide audible Pilot LED 15 mA
and visual indication as well as remote test/reset Horn 20 mA @ 24 VDC
functions. Sound Pressure
Horn 78 db @ 10 feet
These devices are contructed of brushed stainless Dimensions
steel and mount on a standard single or double gang Single Gang 2.75" (69.85mm) W
backbox. 4.5" (114.3mm) H
Double Gang 4.5" (114.3mm) W
4.5" (114.3mm) H

MS-RA MS-KA/P/R
Functions: Functions:
Remote Alarm LED (red) ALARM
Remote Alarm LED (red)
For Use with: Pilot LED (green)
ALARM
DH-98-I, DH-98-P PILOT
Key-Operated Test/Reset
DH-98-HVI, DH-98-HVP Switch
DH-98-A, DH-98-AR For Use with:
TEST/RESET
DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP

MS-KA/R MS-RA/R
Functions: Functions:
ALARM Remote Alarm LED (red) Remote Alarm LED (red)
Key-Operated Test/Reset ALARM
Push-button Test/Reset
Switch Switch
For Use with: For Use with:
DH-98-I, DH-98-P TEST/RESET DH-98-I, DH-98-P
TEST/RESET
DH-98-HVI, DH-98-HVP DH-98-HVI, DH-98-HVP
DH-98-AR DH-98-AR

MS-RA/P MS-RA/P/R
Functions: Functions:
Remote Alarm LED (red) Remote Alarm LED (red)
ALARM
ALARM Pilot LED (green) Pilot LED (green)
For Use with: Push-button Test/Reset
PILOT
DH-98-I, DH-98-P Switch
PILOT DH-98-HVI, DH-98-HVP For Use with:
TEST/RESET DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 01/2004
MS-RH/KA/P/R
Functions:
Remote Alarm Horn
ALARM
Remote Alarm LED (red)
Pilot LED (green)
PILOT Key-Operated Test/Reset
Switch
TEST/RESET
For Use with:
DH-98-I, DH-98-P
DH-98-HVI, DH-98-HVP

WIRING DIAGRAM
RED
RED

RED GREEN
ALARM
24VDC PILOT
24VDC ALARM HORN
LED LED

BLACK
BLACK
ALARM
PILOT

BLACK

KEY OR
PUSH BUTTON
24VDC
"TEST/RESET"
SWITCH

BLACK

TEST/RESET

PRODUCT SPECIFICATIONS
PUSH KEY
PILOT ALARM BUTTON OPERATED
LED LED TEST/ TEST/ SINGLE DOUBLE
(GREEN) (RED) RESET RESET HORN GANG GANG
MODEL #
MS-RA
MS-RA/P
MS-RA/R
MS-RA/P/R
MS-KA/R
MS-KA/P/R
MS-RH/KA/P/R

Hochiki America Corporation DH-98 Duct Detector Remote Accessories Specifications subject to change without notice.
Conventional Detector Bases
NS6 AND NS4 SERIES BASE

The NS6 and NS4 Series is designed specifically for use with
HOCHIKI Conventional Models SIJ-24 Ionization Smoke Detector,
SLR-24V Photoelectric Smoke Detector, SLR-24H Photoelectric with
Heat Smoke Detector, SLR-835 Photoelectric Smoke Detector, SLR-
835H Photelectric Smoke Detector w/heat, or DCD-135/190 Fixed
Temperature/Rate-of-Rise Heat Detector. The Base is an electronics
free 6" base featuring a plastic tamper-lock lug. Each base is
N S Series B ases Alarm C urrent ID
equipped with a resistor. Refer to the chart (left) for additional
specifications. The NS4 base is a 4" version of the NS6 base.
NS6-224 OR NS4-224 43mA (70mA @ 33.0V MAX) HB-5

NS6-220 OR NS4-220 93mA (136mA @ 33.0V MAX) HB-3

NS6-221 OR NS4-221 46mA (77mA @ 33.0V MAX) HB-4

NS6-100* OR NS4-100* 150mA @ 15.0 - 33.0V MAX HB-55

* Requi res external current li mi ti ng to 150mA maxi mum. Models HSC-224R, HSC-220R and the HSC-221R are designed
specifically for use with the HOCHIKI Conventional Models SIJ-24,
HSC- (X)R RELAY BASE & SLR-24V, SLR-24H, SLR-835, SLR-835H or DCD-135/190. The
HSC- 4R 4 WIRE BASE HSC-(X)R series is a 6" base with two sets of Form "C" relay
contacts.
Models HSC-224R, HSC-220R and the HSC-221R are also
approved for use with HOCHIKI previous Conventional Models
SIH-24F, SLK-24F, SLK-24FH and the DFE 135/190.

The HSC-4R is designed specifically for 24 volt 4 wire applications


using HOCHIKI Conventional Models SIJ-24, SLR-24V, SLR-24H,
SLR-835, SLR-835H or DCD-135/190. The 6" diameter base is current
limited. Relay contact place a direct short occurs across the loop
2 Wire Auxilliary
R elay B ases
Alarm C urrent ID when the detector is actuated.
Model HSC-4R is also approved for use with previous HOCHIKI
HSC -224R 43mA (58mA @ 30.0V MAX) HB-73
Conventional Models SIH-24F, SLK-24F, SLK-24FH and the DFE 135/
HSC -220R 88mA (98mA @ 26.5V MAX) HB-72
190.
HSC -221R 49mA (62mA @ 30.0V MAX) HB-71

4 Wire B ase Alarm C urrent ID The HSC-4R12 is designed specifically for 12 volt 4 wire applications
HSC -4R 43mA (58mA @ 30.0V MAX) N/A using HOCHIKI Conventional Models SLR-835, SLR-835H. The 6"
HSC -4R12 47mA (75mA @ 18.0V MAX) N/A diameter base is current limited. Relay contact place a direct short
occurs across the loop when the detector is actuated.
HSC- (X) L LATCHING LED BASE Model HSC-4R12 is also approved for use with previous HOCHIKI
Conventional Models SLK-835, SLR-835, and SLR-835H.

The HSC-L Base Series is designed specifically for use with the
HOCHIKI Fixed Temperature Heat Detectors Models
DFE-135/ 190.
The HSC-L Series is a 6" base featuring a current limiting
2 Wire Latching Alarm C urrent ID
resistor, latching annunciator output and a latching circuit so the
HSC -224L 35-42mA @ 24V (54mA MAX) HB-62
alarm LED will remain lit until the control panel has been reset.
67-80mA @ 24V
HSC -220L HB-64
(88.5mA @ 26.5VD C MAX)

HSC -221L 37-45mA @ 24V (57mA MAX) HB-63

We try to keep our product information up-to-date and accurate. However, we cannot cover all specifications or
anticipate all requirements. For additional information contact your local distributor or Hochiki America Corporation.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0014 04/2004
Conventional Detector Bases
NS4 AND NS6 SERIES BASE
2-WIRE OPERATION

UL LISTED
CONTROL LISTED
PANEL END OF LINE
DEVICE

PANEL Resistor shown is for example


POWER only. Not all annunciators
have in line resistance.
SUPPLY
NOTE: - WIRING TERMINALS FOR THE NS4
NEGATIVE NS4 SERIES AND NS6 ARE IDENTICAL
NS6 SERIES - BASES WITH THE "W" SUFFIX
Annunciation device must be current limited to 20 mA @ ARE WHITE IN COLOR
24VDC Maximum. Not limiting current could result in
damage to the detector or cause a no alarm condition.

HSC-(X)R RELAY BASE


2-WIRE OPERATION

UL LISTED LISTED
CONTROL END OF LINE
PANEL
DEVICE

GRY
BLU PIGTAIL AUXILLIARY
GRN CONTACTS
HSC- (X) R SERIES YEL
ORN TWO FORM "C"
PUR

RELAYS SHOWN WITH


POWER OFF.
HSC-4R FOUR WIRE BASE
4-WIRE OPERATION
LISTED
INITIATING END OF LINE
DEVICE
CIRCUIT

LISTED
END OF LINE
RELAY
HA-EOLR-12 OR HA-EOLR-24
UL LISTED
POWER
SUPPLY
12VDC OR 24VDC

H1
H2 H1,H2 - TERMINAL
YEL PIGTAIL AUXILLIARY CONTACTS
ORN
PUR ONE FORM "C"

HSC-4R OR HSC-4R12

HSC- (X) L LATCHING LED BASE

2-WIRE OPERATION

COMPATIBLE
UL LISTED
CONTROL LISTED
PANEL 6 END OF LINE
DEVICE

PANEL
POWER Pig Tail Lead
SUPPLY HSC-(X) L SERIES NS6 SERIES
NEGATIVE

We try to keep our product information up-to-date and accurate. However, we cannot cover all specifications or anticipate all
requirements. For additional information contact your local distributor or Hochiki America Corporation.
Hochiki America Corporation • Conventional Detector Bases Specifications subject to change without notice.
SBC - CONVENTIONAL SOUNDER BASE

DESCRIPTION

The Models SBC Conventional Sounder Base Series


are designed specifically for use with HOCHIKI NS
conventional style smoke detectors Models SIJ-24
Ionization Smoke Detector, SLR-24V Photoelectric
Smoke Detector and SLR-835 Wide Operating Voltage
Photoelectric Smoke Detectors. The SBC Series will
provide an audible evacuation signal (continuous or
temporal Code) upon detector alarm. Easily configured
Shown without detector Shown with detector
to 12 or 24-volt applications through use of a dipswitch,
STANDARD FEATURES the bases can also be configured to activate in indi-
• Wide operating voltage vidual, group, or global modes. The relay base model
SBC-2R contains two sets of Form “C” Relay Contacts
• Selectable Evacuation Codes: continuous or temporal rated at 1 Amps @ 28VDC or 0.5 Amps @ 120VAC.
• Three different configurations: individual, group, and All models come in 6” diameter size and are available
global modes in both bone and white colored plastic.
• High sound pressure level (85 dB at 10 ft)
• Can be configured to satisfy a wide variety of
applications
• Available with or without relay, 2 and 4 wire
configurations, and bone or white color
SPECIFICATIONS
Model SBC-2, 2W SBC-2R, 2RW SBC-4/12, 4/12W SBC-4/24, 4/24W
GROUP/ GROUP/
Operating Voltage Range 8.7-30VDC GLOBAL MODE 19-30VDC GLOBAL MODE 10-18VDC 18-30VDC

26mA@8.7VDC 12mA@8.7VDC 53mA@19VDC 30mA@19VDC 75mA@12VDC 65mA@24VDC


18mA@12VDC 65mA@24VDC 40mA@24VDC
Max. Alarm Current 35mA@12VDC
65mA@24VDC 45mA@24VDC
12345678901234
12345678901234 12345678901
1234567890112345678901234
12345678901234 12345678901
12345678901
Rated Voltage 12345678901234
12345678901234123456789011234567890123412345678901
1234567890112345678901234 12345678901 12VDC 24VDC
12345678901234
12345678901234 12345678901
12345678901 1A@28VDC 12345678901
12345678901
Contact Rating of Relay 12345678901234
12345678901234 12345678901 OR 12345678901 2A@30VDC OR 0.5A@120VAC
12345678901234123456789011234567890123412345678901
1234567890112345678901234
0.5A@120VAC
12345678901
Alarm Contact Rating 12345678901234
1234567890123412345678901
1234567890112345678901234
1234567890123412345678901
12345678901 2A@30VDC OR 0.5A@120VAC
12345678901 12345678901
Max. Humidity 93%RH(non-condensing) 1234567890193%RH(non-condensing)12345678901
12345678901
12345678901 12345678901
12345678901
93%RH(non-condensing)

Sound Pressure Level at 10ft 12345678901 12345678901


12345678901 12345678901
85 dB 85 dB 85 dB
32°°F (0°°C) to 12345678901
12345678901 32°°F (0°°C) to 12345678901
12345678901
Operating Temperature Range 32°°F( 0°°C ) to 100°°F (38°°C)
100°°F (38°°C) 12345678901 100°°F (38°°C) 12345678901
Dimensions 5.94” x 1.34”
12345678901
12345678901 5.94” x 1.34”
12345678901
12345678901 5.94” x 1.34”
12345678901
12345678901 12345678901
12345678901
Weight 0.365 lb
12345678901 0.455 lb
12345678901 0.455 lb
SLR-24V, SIJ-24, SLR- 12345678901 SLR-24V, SIJ-24, SLR- 12345678901
Compatible Detectors 835/-835W/-835H/-
12345678901
12345678901 835/-835W/-835H/- 12345678901
12345678901 SLR-835/-835W SLR-24V, SLR-
835HW 12345678901 835HW 12345678901 835H/-835HW

PRODUCT LISTINGS Note: “W” at the end of model designation indicates


Underwriters Laboratories: S1383 white colored plastic.
CSFM #: 7300-0410:160

Specifications subject to change without notice. Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0012 11/2005
GROUP SOUNDER WIRING DIAGRAM (2 WIRE) SBC-2 AND 2R
NEXT DEVICE

EOL
INITIATING
LOOP RESISTOR

UL
LISTED
CONTROL
PANEL

NEXT DEVICE
TOP VIEW
OR
CONVENTIONAL SOUNDER BASE 12V/24V WITHOUT RELAY (2 WIRE) SBC-2

EOL
P57
20
1
P57
20
1
RELAY
+12 +12

-12 -12
12V/24V NEXT NEXT
AUX J2
J4
J2
J4

S1 S1
8 8
7 7
6 6
J3
5
J3
S 8 S 8
5
05 4 05 4
S 3 S 3
D D
G 2 G 2
CO 1 1 CO 1 1
AL AL
GRY

GRY
ON ON
VLT

VLT
BRN

BRN
GRN

GRN
ORG
YEL

ORG
YEL
RED

RED
BLK

BLK
WHT

WHT
BOTTOM VIEW

CONVENTIONAL SOUNDER BASE 24V WITH RELAY (2 WIRE) SBC-2R


P 57
P57

20
20

1
1

NC NC
NO NO EOL
COM COM RELAY
24V ONLY + 12 + 12
J2
J2

AUX - 12 - 12
NEXT NEXT
J4
J4

S1
J3
S1
J3

8
8

7
8S
8S

05

6
05

DS

5
WHT
S

BLK

G
5

RED
ORG

4
GD
WHT

CO
BLK

YEL
GRN
RED

4
ORG

BRN

3
VLT

AL
YEL

GRY
CO
GRN
BRN

2
AL
VLT
GRY

1 1
1

ON
1
ON

NOTES: FOR ADDITIONAL SOUNDER WIRING DIAGRAM SBC-2, AND SBC-2R INFORMATION, PLEASE REFER TO
INSTALLATION INSTRUCTION HA-06-085.

INDIVIDUAL SOUNDER WIRING DIAGRAM (4 WIRE) SBC-4


NEXT DEVICE

UL LISTED
12V/24V EOL
POWER RELAY
SUPPLY

12V: SBC-4/12
24V: SBC-4/24

NEXT DEVICE
TOP VIEW
M

M
P572

P5
7203
03

INITIATING
G

LOOP NC NC
F

NO NO
J2

J2

COM COM
+ 12 + 12
UL - 12 - 12
NEXT NEXT
J4

J4

LISTED
CONTROL
J3

J3

PANEL
WH
BLK
RE

S1

S1
ORG
T

YEL
GRN
D

BLK
RE
BLK

WHT
RE D

BLK
5

5
RED
D

ORG
4

4
YEL
GRN
3

3
BLK
RED
BLK
2

2
RED
1

1
1

1
ON

ON

RED RED RED


EOL
BLACK BLACK BLACK RESISTOR

BOTTOM VIEW

NOTES: FOR ADDITIONAL SOUNDER WIRING DIAGRAM SBC-4 INFORMATION, PLEASE REFER TO INSTALLATION
INSTRUCTION HA-06-086.

Hochiki America Corporation Conventional Sounder Base Specifications subject to change without notice.
SZA-NA(FM) HIGH SENSITIVITY SMOKE
DETECTION SYSTEM
DESCRIPTION
The Hochiki America SZA-NA(FM) high sensitivity
smoke detection system is capable of detecting
minute particles of smoke. The SZA-NA(FM) is ideal
for applications where response time is critical. It
provides the earliest response to fires available. The
SZA-NA(FM) provides a detection solution for rooms
with high air flow, and rooms with large open spaces.

SPECIFICATIONS
Power Supply 24 VDC ± 10% 0.5A or less
STANDARD FEATURES Current Output
4-20mA DC output (Receiving resistance: 100 ohm or less)
• Detects very low density smoke Contact Output
• 200 m2 detection area (2150 ft2) Alarm 1 output, Alarm 2 output , Alarm 3 output,
• No filter necessary & System Fault output
• N/O or N/C alarm contacts form A, form B Contact Capacity
• Automatic and manual laser tests 24 VDC, 0.5A or less (each contact output)
• Four selectable sensitivity ranges:
Contact Output Logic
*Sensitivity 1: 0.005 to 0.1%/m (0.002 to 0.03%/ft)
NO (form A) or NC (form B) selectable
*Sensitivity 2: 0.01 to 0.2%/m (0.003 to 0.06%/ft)
by a jumper pin
*Sensitivity 3: 0.025 to 0.5%/m (0.008 to 0.15%/ft)
AC Power Supply Monitoring Input
*Sensitivity 4: 0.25 to 5.0%/m (0.08 to 1.55%/ft)
NO (form A) or NC (form B) selectable
• 3 alarm levels: by system setting
*Alarm 1 (low)
Internal Wiring Heat-resistance shielded wires
*Alarm 2 (medium)
*Alarm 3 (high) Materials
Body & panel: Steel plate of 0.8 mm thick, baked painting
Display operating panel: Steel plate of 1.0 mm thick
Colors
Body & panel: Munsell 2.5Y9/1 or equivalent
Display operating panel: Munsell 5Y6/0.5 or equivalent
Weight Approximately 8.2 lbs. (3.7kg.)
Dimensions 12.48" W x 8.86" H x 4.00" D
317mm x 225mm x 102mm
Exploded View of Front Panel Operating Temperature 14°F to 122°F
(-10 ºC to +50 ºC)
PRODUCT LISTINGS
Installation Indoor (Non-condensing)
Accessory Dedicated flexible pipe
3026973
Continued on back.
Specifications subject to change without notice.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0069 11/2006
OPERATION

An aspirating smoke detection system continuously draws air from the monitored area into the sampling pipes. The
air is drawn from the sampling pipes into the main sampling unit. In the main sampling unit, the air is analyzed by
very sensitive laser detection components. The laser detection components constantly monitor for the presence of
smoke particles.

If smoke particles are detected, the unit will activate the alarm output relays in accordance with the sensitivity
selected and the alarm level reached. The SZA-NA(FM) High Sensitivity Smoke Detector is between 20 and 1000
times more sensitive than spot-type smoke detectors. The SZA-NA(FM) has three alarm stages. Alarm 1 is the
lowest obscuration alarm (high sensitivity), activating when very small amounts of smoke are detected. The Orange
Alarm 1 LED will light, and the Alarm 1 relay will activate. As the smoke density reaches alarm level 2, the Red
Alarm 2 LED will light and Alarm 2 relay will activate. As the smoke density reaches alarm level 3, the Red Alarm 3
LED will flash and the Alarm 3 relay will activate.

The SZA-NA(FM) is ideal for use in areas such as computer server rooms, clean rooms, telecommunication
equipment rooms, medical equipment/operating rooms, power generation plants, and many other applications. By
continuously sampling the area, the SZA-NA(FM) can provide the earliest warning of the presence of smoke, even
before the smoke is visible to the human eye.

4
3

1 – Relay Connections 2 – Jumpers (N/O or N/C) 3 – Programming Display


4 – Fan Unit 5 – Laser Unit and Air Flow Sensor 6 – 24 VDC Fuse

TERMINAL BLOCK MOUNTING

Hochiki America Corporation SZA-NA(FM) Specifications subject to change without notice.


Series HPS-SAH, HPS-SAK, HPS-DAH, HPS-DAH/S, HPS-DAK, HPS-DAK/S
Manual Non-Coded Pull Station

STANDARD FEATURES

• Metal Construction
• Enclosed switch with glass rod (included)
• 10 Amps @ 120 VAC
• Available in: Single Action, Dual Action and
Dual Action in Spanish (HPS-DAH/S)
• UL, FM, CSFM Listed
• Made in USA

HPS-SAH HPS-SAK
DESCRIPTION

Hochiki America’s Models HPS series pull stations


are available in six models:

• HPS-SAH single action


• HPS-SAK single action with key lock
• HPS-DAH dual action
• HPS-DAH/S dual action (Spanish)
• HPS-DAK dual action with key lock
• HPS-DAK/S dual action with key lock (Spanish)

HPS-DAH HPS-DAH/S Each model is constructed of a solid die cast housing


and comes in glossy red. The back switch plate is
plated steel. The electrical switch is rated for 10 Amps
@ 120 VDC normally open contact rating. All models
are connected via terminal block connections.

PRODUCT LISTING
Underwriters Laboratories: S2984
CSFM #: 7150-0410:162

HPS-DAK HPS-DAK/S
Continued on back.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0033 10/2005
Rear View Front View

PULL DOWN

SPECIFICATION

ELECTRICAL WIRING

Hochiki America Corporation Series HPS-SAH, HPS-SAK, HPS-DAH, HPS-DAH/S, HPS-DAK, HPS-DAK/S Specifications subject to change without notice.
HPS-SAH-WP Weather Proof Manual Pull Stations
DESCRIPTION
The Hochiki HPS-SAH-WP Weatherproof Manual Pull
Station is a UL Listed fire alarm initiating device
suitable for applications requiring outdoor mounting of
the manual fire alarm pull station. The HPS-SAH-WP
is appropriate for applications where the manual pull
station may be subject to wet conditions.

The HPS-SAH-WP consists of a die-cast aluminum


back box, Neoprene sealing gasket and a special
manual fire alarm box. The unit is a high quality pull
station constructed entirely of nontoxic materials with
a low profile and rounded edges to fit most design
requirements. All components are pre-painted, or have
plated surfaces to inhibit corrosion.

The latching pull-down lever on the HPS-SAH-WP


requires a hex key to reset it. This allows only
authorized personnel to reset the manual pull station
so that the origin of the alarm can be determined
STANDARD FEATURES easily.
• Weatherproof Manual Pull Station
The HPS-SAH-WP has one set of Normally Open
• 10 A, 120 VAC contacts
contacts rated for 10A @ 120 VAC, making the device
• Rugged die-cast aluminum housing
suitable for installations involving large current loads.
• Neoprene sealing gasket
• Corrosion-resistant construction
The HPS-SAH-WP conforms with the Americans with
• Hex reset
Disabilities Act (ADA).
• Latching pull-down lever
• Screw terminal connections
Manual Station

SPECIFICATIONS
Contact Current Rating 10A @ 120 VAC To Fire Alarm 1
Control/Communicator N/O
zone or point 2

Switch

PRODUCT LISTING
Underwriter Laboratories: S2984
CSFM #: 7150-0410:162 Wire Connections

Specifications subject to change without notice

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0035 8/2004
Hochiki America Corporation Specifications subject to change without notice.
HPS-CP CALL POINT BREAK GLASS STATIONS

SPECIFICATIONS
Contacts Normally Open
Contact Current Rating 3A @ 120 VAC
Dimensions (WxHxD) 3.5" x 5 1/4" x 3/4"

DESCRIPTION

Hochiki America Models HPS-CP series pull stations


are available in two models:
• HPS-CP call point/break glass
• HPS-CP/S call point/break glass (Spanish)

HPS-CP The Hochiki HPS-CP series is very dependable break


glass station intended for simple yet failsafe operation.
The actuating switch is a heavy duty plunger type, with
a Glass plate covering (2.5" x 2.5") which is a
Factrolite single strength (obscured) type. Design of
this station is such that it seems to inhibit the "false
alarm" factor that is so prevalent in public schools and
places of public assembly. The steel rod attached to
the station is not necessary to break the glass. A
slight blow of the hand, coin, key, pencil, etc. is
sufficient to break the glass and initiate the alarm.
The HPS-CP is intended for mounting in a standard
electrical outlet box.

WIRING DIAGRAM
TOP REAR VIEW

HPS-CP/S
STANDARD FEATURES
L1
• Actuating switch, a heavy duty plunger type L2
IN
CIRCUIT
• Glass plate (2.5" x 2.5"), a Factrolite single L2 OUT
strength (obscured) type. L1
• Steel rod attached
• Mounts in a standard electrical outlet box
• Available in English & Spanish
• UL listed
• Made in USA PRODUCT LISTING
Underwriter Laboratories: S6512
Specifications subject to change without notice CSFM #: 7150-0410:164

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0059 6/2005
Hochiki America Corporation HPS-CP Specifications subject to change without notice.
HPS-SA-EX/WP Explosion Proof Manual Pull Stations

DESCRIPTION

The Hochiki HPS-SA-EX/WP Explosion Proof Manual


Pull Station is a single action, UL listed fire alarm
initiating device. With a UL rating of class I groups B
(hydrogen), C and D; class II groups E, F and G; class
III and an outdoor rating of type 4X, this station offers
unmatched placement flexibility. The 2 sets of Form
"C" (NO/C/NC) contacts are rated for 10 Amps at 120/
240 VAC. The HPS-SA-EX/WP has an easily identifi-
able pull down lever and contains an integral break
glass rod carrier.

The unit is a high quality manual fire alarm box con-


structed entirely of a high strength metal die-cast alloy
with a low profile and rounded edges to fit most design
applications. All components are prepainted or have
plated surfaces to inhibit corrosion. Non-corroding
STANDARD FEATURES screw terminals are provided for wire connections to
the HPS-SA-EX/WP.

• Compatible with all Hochiki Control Panels The HPS-SA-EX/WP is manufactured in conformance
• Rugged die-cast housing with the standards set forth in the Americans with
• Rated class I group B (hydrogen) C&D, class II Disabilities Act (ADA).
groups E,F,G, class III, 4X outdoor
The HPS-SA-EX/WP has a white pull down lever in its
• Weather Proof center. Pulling down the lever latches it into place.
• Corrosion-resistant construction The HPS-SA-EX/WP's normally open contact switch is
• Latching alarm levers shorted causing an alarm on the fire initiating loop.
The pull down lever can not be reset unless the correct
• Screw Terminals 12-22 AWG
key is inserted into the manual fire alarm box lock and
• Key-locked reset the unit is opened. The latching lever can then be
• Optional glass break rod restored to its normal position.
• DPDT Contacts
When the HPS-SA-EX/WP is being reset and has a
glass break rod installed, all debris must be removed
SPECIFICATIONS prior to installing another rod to ensure the unit will
close and lock securely.
Contacts DPDT Form "C" (NO/C/NC)
Contact Current Rating 10 Amps @ 120/240 VAC
Dimensions (HxWxD) 4.75 in. x 3.125 in. x
3.375 in. (12.1 cm x 7.9 PRODUCT LISTING
cm x 8.6 cm) Underwriter Laboratories: E154860
CSFM #: 7151-0410:163
Specifications subject to change without notice

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F0034 07/2005
Hochiki America Corporation Specifications subject to change without notice.
TSE-A100 SELF-CONTAINED SMOKE GENERATOR
APPLICATION
The Hochiki America TSE-A100 is one of the most
advanced units of its kind and is the result of extensive
research and development aimed at making the job of
testing detectors a simple and efficient operation .

The TSE-A100 can be used to test all types of smoke


detectors by applying smoke from an internal smoke
source.

Although this is not a calibrated amount of smoke, the


TSE-A100 is an excellent choice for periodic functional
testing of smoke detectors.

OPERATION
Preparation
1. Remove the TSE-A100 from its carrying case.
2. Unscrew the combustion chamber from the
bottom of the TSE-A100.
3. Unscrew the punk stick holder retainer from
the combustion chamber.
4. Insert a punk stick into the punk stick holder in
the combustion chamber.
5. Light the punk stick with a flame.
STANDARD FEATURES 6. Reassemble the combustion chamber.
• Tests all types of smoke detectors. 7. Screw the combustion chamber back into the
• Completely self contained and portable. bottom of the TSE-A100
• Extends from 5.25 feet to 14.1 feet. 8. Extend the telescopic pole of the TSE-A100 to
• Internal Smoke Source. a length which enables you to reach the
• Non-Toxic Smoke Source. detector you wish to test.
• Unit includes shoulder sling carrying case.
• Optional adapter for high velocity conditions. Testing a Detector
Once you have prepared the TSE-A100, follow the steps
• Exhaust function to clear detector.
in this section to test smoke detectors.
• Built-in filter to prevent tar residue from adhering to
the surface of the detector. NOTE: Allow 30 to 60 seconds after igniting punk stick
for sufficient smoke generation.
SPECIFICATIONS
Continued on back
Rated Voltage 3 VDC
Battery 2 - "D" Batteries
PRODUCT PARTS
Combustion Material Punk Stick
(7 mm diameter, 150 mm long) • TSE-A100 Self-Contained Smoke Generator
Weight 5 Lbs. • Punk Stick (Part No. TSE-P100)
Length 5.25 to 14.1 feet
Color Brown
Specifications subject to change without notice.

Hochiki America Corporation


7051 Village Drive, Suite 100 • Buena Park, CA 90621-2268
Phone: 714/522-2246 • Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 01/2002
OPERATION, continued

Testing a Detector, continued Storing the TSE-A100

1. Rotate the combustion chamber so the #2


1. Rotate the combustion chamber to the #1
arrow line sup with the power indicator screw.
position to turn the power off.
The fan powers on and a steady flow of smoke
is released from the tip of the TSE-A100. 2. Compress the telescopic pole to its shortest
length.
2. Raise the extended tip of the TSE-A100 to
within 6-8' of the detector. The detector should 3. Replace the TSE-A100 in its carry case.
alarm. 4. Store in a cool, dry place.
If no smoke comes out, check to make sure the 5. For extended storage, remove the batteries.
punk stick is ignited, and the power indicator on
the combustion chamber is set to #2.

NOTE

1. Use only the filter and combustion material


specified.
2. Check battery capacity before use to assure
efficient operation.
3. Remove batteries before long-period storage.
Telescopic Pole

Power Indicator Screw

Punk Stick Holder Retainer

Combustion Chamber
Punk Stick

Instruction Label

Hochiki America Corporation • TSE-A100 Specifications subject to change without notice.


NSRT / NSTT
SMOKE DETECTOR REMOVAL TOOL / TESTER

STANDARD FEATURES

NSRT

• Combination removal tool/outer cover removal tool


for AIE, ALG, SIJ, and SLR-24/-835 series sensors/
detectors.
• Choose either a Hand held or 15’ stainless steel
extension pole with easy grip black handle.

NSTT

NSRT HEAD • Tests Hochiki America SIJ-24 and SLR-24/-835


series smoke detector with a reed switch.
• Choose either a Hand held or 15’ stainless steel
extension pole with easy grip black handle.
• No combustion material needed.
• No meter, batteries, or screwdriver required.
• Meets outlined requirements in the NFPA72,
NSRT-A100 WITH 15' POLE Inspection, Testing and Maintenance, Chapter 10.
(COMPLETE)

SPECIFICATIONS
Detector Tester/Removal Tool
Dimensions
NSRT HEAD: 4.0" D x 2.0" H
NSTT HEAD: 4.0" D x 1.5" H
Material Highly durable PVC
molded plastic
Color Black - provides visible contrast
Alignment
NSRT HEAD: One side for arrow labels for
easy visibility, one side for
removal from base.
NSTT HEAD: One side for sensitivity testing.
NSTT HEAD
Extension Pole
Dimensions Pole extends to 15'
Material Stainless steel with easy grip
black handle
NSTT-A100 WITH 15' POLE
(COMPLETE) Specifications subject to change without notice.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com F044 02/2005
APPLICATION
NSRT-A100
The Hochiki America NSRT-A100 will enable the user to easily remove and replace the ALG, AIE, SLR, and SIJ series
sensors/ detectors from their mounting bases. Also, the NSRT-A100 is designed to remove the outer covers of the
ALG, AIE and SLR series sensors/detectors

NSTT-A100
The SIJ-24 and SLR-24/-835 series detectors, manufactured with magnetically activated dual reed switches for sensitivity
testing, can be sensitivity tested with the NSTT-A100. This meets the requirements of a UL listed calibrated test
without the use of combustion materials.
The NSTT-A100 is in compliance with the test requirements outlined in the NFPA 72 Inspection, Testing and Maintenance,
Chapter 10.

Hochiki America Corporation NSRT & NSTT Specifications subject to change without notice.
TRT-A100 SMOKE DETECTOR TESTER/REMOVAL TOOL
APPLICATION
The HOCHIKI America TRT-A100 Smoke Detector Tester/
Removal Tool enables the user to access, test, remove
and reinstall the SIH and SLK series smoke detectors.
The detectors, manufactured with a magnetically
activated dual reed switch for sensitivity testing, can be
sensitivity tested. This meets the requirements of a UL
listed calibrated test without the use of combustion
materials.

The TRT-A100 is in compliance with the test requirements


outlined in the NFPA 72 Inspection, Testing and
Maintenance, Chapter 7.

OPERATION
Test Procedure

This method of sensitivity testing is designed only for


HOCHIKI America smoke detector models SIH and SLK
Series that contain a label which identities this specific
feature. See below. DO NOT attempt to use this method
STANDARD FEATURES of sensitivity testing on detectors without this label.
• Combination tester/removal.
• Tests Hochiki America smoke detectors with a
dual reed switch.
• Choose either a Hand held or 15' stainless steel
extension pole with easy grip black handle.
• No combustion material needed.
• No meter, batteries, or screwdriver required.
• UL listed.
• Meets outlined requirements in the NFPA 72
Inspection, Testing and Maintenance, Chapter 7. Conduct the testing with detector wired to appropriate
initiating circuit or current limited power source and with
SPECIFICATIONS normal applied power. Abnormal or low power conditions
Detector Tester/Removal Tool may effect sensitivity. Always reset the power before
you test the next unit.
Dimensions 3.4" D x 2.4" H
Material Highly durable PVC 1. Place the TRT-A100 onto the detector aligning the
molded plastic orange arrow shown on the removal/test tool with
Color Gray-provides visible contrast the tamper resistant set screw on the detector.
Alignment One side for test, one side 2. Wait six to eight seconds. Detector SHOULD NOT
for removal. Color-coded alarm.
labels for easy visibility Continued on back.
Tester/Removal Tool Handle
Options Hand Held or Extension Pole PRODUCT LISTINGS
Dimensions Pole extends to 15'
Material Stainless steel with Underwriters Laboratories: S1316
easy grip black handle MEA Report #: 284-91-E Vol. II
Specifications subject to change without notice.

Hochiki America Corporation Find latest revision at www.hochiki.com


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 12/2003
OPERATION, continued

3. If the detector does alarm when the removal/test tool is placed in this position, the detector is not within specified
sensitivity limits and may require service.
4. Rotate the TRT-A100 one-half circle (180°). Align white arrow shown on tester tool with tamper resistant set
screw.
5. Wait six to eight seconds. Detector SHOULD alarm and the indicator LED should remain lit.
6. If detector does not alarm when the TRT-A100 is positioned correctly, may not within specified sensitivity limits
and may require service. See Technical Bulletin HA-88 (November '96) for more information.

Removal Procedure

This section explains how to use the HOCHIKI America TRT-A100 Tester/Removal Tool to remove smoke detectors
from their bases.

1. Flip the TRT-A100 so the five small arrows located beneath the white orange arrows are point upward.
2. Fit the TRT-A100 to the detector and lock into place.
3. To remove a detector, rotate the TRT-A100 to the left (counterclockwise).
4. To install a detector, rotate the TRT-A100 to the right (clockwise).

Hochiki America Corporation TRT-A100 Specifications subject to change without notice.


H E AT D E T E C T O R T E S T E R S

fast
efficient
convenient
innovative
safe
patented
30ft reach

CAT™
Heat Detector Testing: Why and How ?
National standards require that heat detectors are tested regularly by application of a heat source.
The SOLO™ range includes two professional, alternative Or, for those seeking a lower cost solution,
solutions to meet that requirement:
2. The SOLO 409 provides a powerful heat source
1. The cordless SOLO 461, incorporating the innovative contained within the transparent cup, which enables a view
CAT™ (Cross Air Technology), activates 95% of all spot of the illuminated LED upon successful activation.
type heat detectors (fixed temperature, rate of rise and
combination) within seconds and many times faster While the SOLO 409 does need a power cord, it is nonetheless a
than previous designs. professional heat detector testing tool, designed for safe use in
the appropriate environment without causing damage to the
The rechargeable Battery Batons™, mounted inside the heat detector.
access pole, enable safe and efficient testing without any
trailing cords or the need for a safety transformer.

SOLO RANGE INTEGRATION


Both products integrate with the universal SOLO™ range, which represents today's most advanced system for
testing, removing and replacing both smoke and heat detectors at heights up to 30ft.

SOLO 409
HEAT TESTER
The SOLO 409 is a professional and robust tool for testing heat
detectors fitted at heights up to 30ft. Unlike the SOLO 461, it
does require a power cord lead but, conversely, does not require any
special energy saving features.

● Designed for use on fixed temperature, rate of rise and


combination detectors.
● Suitable for any model of spot type heat detector fitted at heights of
up to 30ft.
● Large clear cup fits over detector enabling a clear view of the
detector LED.
● Tests detectors up to 194˚F operating temperature.
● Thermal cut-out for added protection.
What is CAT™ ? Under the control of a microprocessor,
The revolutionary and patented CAT™ (Cross Air Technology) system applies blown air is heated by the element
just before exiting the duct. The narrow
the stimulus directly to the sensor in the most efficient way possible - horizontally.
opening focuses the heat into a 'beam'.

In the case of heat detector testing, CAT™:


● Reduces test times dramatically.
● Sets detectors into alarm more rapidly than any other safe technique.
● Uses the minimum power necessary, thereby extending battery life.
● Suits rate of rise, fixed temperature and combination detectors up to 194˚F.
● Minimises the possibility of heat damage to the plastic of the detector.
For tests on combination rate of rise / non-restorable detectors, a silicon baffle is supplied
to ensure correct airflow. energy efficient
The SOLO 461 incorporates a 'reference platform', which ensures that the 'beam' of heated
air is lined up correctly with the sensor, whatever size and shape of detector.
Under the control of a microprocessor, blown air is heated by the element
just before exiting the duct. The narrow opening focuses the heat into a 'beam'.
Because the hot 'beam' of air is targeted directly at the sensor, substantial amounts of energy
and time are saved. This design allows many more tests per Battery Baton™ than ever before.

SOLO 461 CORDLESS (CAT™) HEAT TESTER


The SOLO 461 provides a solution for testing heat detectors that is second to none.
Its patented design is convenience itself, while offering the fastest functional test possible
in the safest and most controlled way.

● Heat is directed straight at the detector sensor.


● Sets 95% of all heat detector types into alarm within seconds.
● Tests detectors up to 30ft with SOLO universal access poles.
● No cords - power from Battery Baton™ is delivered to unit via the frame.
● Uses same Battery Batons™ and charger as previous model - no need to buy new ones.
● Infra-red beam is broken by detector to activate heat generation.
● Microprocessor control maintains constant heat and airflow with variations in battery voltage.
● Goes into standby after 120 secs of use for protection.
● Switches off completely after 5 minutes in standby for further protection.
● Supplied with 2 Battery Batons™ and fast charger
(operates from 110 / 120V, AC supply
or 12V DC car battery).
Specifications

SOLO 461 (CATTM Cordless)

Suitable detector types : Spot type, Rate of Rise, Fixed Temperature and Combination up to 194ºF
Maximum detector size : Any - so long as the sensing element can be targeted by the heat source
Number of test: Typically 50 tests of 30 secs duration per Battery BatonTM
Limitless, if using one Battery Baton™ while charging another
Maximum height: Up to 10ft using SOLO 461 alone. Up to 30ft using SOLO extension poles
Approvals: CE Mark
UL listed (charger)
Safety Features: Battery over-current cut-out
Element safety cut out after 120 seconds
Auto power off after 5 mins
Operating features: Color coded LED user feedback
Automatic infrared sensing of detector
Multi position head
1 hour recharge time for Battery Baton™ (car - 12V DC or 110 / 120V AC)
Other interchangeable equipment available in Environment: Operating temperature 40ºF to 115ºF
the range includes: Storage Temperature 15ºF to 120ºF
Humidity: 0-85% RH non-condensing
● Functional smoke detector tester.
Relevant Weights and Dimensions
● A single universal detector removal / Weight Dimensions
extraction tool. Solo 460: 21oz Inside diameter 4in approx
Solo 720: 18oz Diameter 1.15in, Length 19.3in
● Telescopic access pole to 20ft.
Solo 724: 2lb 10oz 3in (w) X 5.3in (l) X 2.6in(h)
● Further extension poles to 30ft.

SOLO 409 (Corded)

Suitable detector types: Spot type, Rate of Rise, Fixed Temperature and Combination up to 90ºC / 194ºF
Maximum height: Up to 30ft using SOLO extension poles
Operating voltages: 110 / 120V AC
Power: 600W approx
Frequency: 50 / 60 Hz
Cable length: 20in nominal
Type of connector: CEE 17 Industrial
Weight: 1lb 14oz
Dimensions: Inside diameter 4.5in approx, working depth 3in approx
Smoke detector sensitivity Safety: Thermal cut out, electrically fused, double insulated
testing instrument

Please note the following important information regarding these products:


Not for use in hazardous areas (those containing explosive vapours or dust).
Care must be taken when handling these products immediately after use, as parts may be hot to the touch.
Tests with these products may prove that the detector is operational and capable of responding to heat;
they do not indicate the calibration level of the fixed temperature element or the grade status.
Care needs to be taken when testing combination non-restorable / rate of rise devices.

Ordering Information

Part No Description
Solo 409: 110 / 120V AC Corded Heat Detector Tester
Solo 460: Cordless “Head Unit” - note: requires Solo 720 and Solo724
Solo 461: Cordless Heat Detector Test kit including:
1x Solo 460 CAT™ Cordless Heat Detector Tester
2x Solo 720 Battery Baton™
1x Solo 724 Universal Battery Charger
Solo 720: Battery Baton™ for Solo 460
Solo 724: Universal Fast Charger for Battery Batons™
Engineering Specifications:
The Audible alarm indicating appliance shall be AMSECO model H24W or equivalent device. The horn shall be listed under UL 464
standard for Audible Signaling Appliance and shall be approved for fire protective service. The sound output shall be field selectable.
The Horn shall provide two different field selectable tones a High and Low field selectable sound output setting. The signaling Select-A-
Horn Horn shall operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The Horn shall be
H24W Horn capable of WALL mounting to a universal backbox. The H24W shall be installed as per plans and specifications.
TM
Select -A- Horn Series Select-A-Horn dB Output & Current Draw Table:
Description: P P P
PC3 PC2 PC1 Average Current ( mA ) Sound Output
AMSECO’s Select-A-Horn Series is designed to comply C C C ( dBA @ DC )
with NFPA/ANSI audible emergency evacuations signal Pattern Tone Volume 3 2 1 DC FWR
and UL 464 audible signaling appliances. The Horn 16V 24V 33V 16V 24V 33V 16V 24V 33V
provides two different field selectable tones, and a High /
Electro High 1 1 1 27 35 52 36 45 64 85 87 88
Low output setting that can be accomplished with the use of
mini jumpers located on back of the unit. The horn is clearly Mechanical Low 1 1 0 15 22 39 23 30 39 75 78 81
NON-TEMP
labeled with FIRE lettering and is polarized for connecting to High 1 0 1 27 35 52 36 45 64 85 88 88
3000 Hz
supervised fire alarm circuits. Horn with Universal Mounting Plate Low 1 0 0 15 22 39 23 30 39 75 78 81
The Select-A-Horn series is available in red or white Horn High 0 1 1 27 35 52 36 45 64 81 83 84
Electro
housing 24VDC models. The horn signals are listed for LI
STI N

Mechanical
UL 15 22 39 23 30 39 71 75 77

G
ULC TE
OF CA L IFO
R

Low 0 1 0
MEA

NI
ST

A
TEMPORAL
indoor use, ceiling and wall mount, under UL 1971

ST

LL
27 35 52 36 45 64 80 83 84
TE

A
FIR
E MAR
SH

High 0 0 1

E
E

S
RV I C

Standard. 3000 Hz
Low 0 0 0 15 22 39 23 30 39 71 75 77
Features:
* Designed to meet or exceed NFPA/ANSI Standards and UL **Sound output varies with tone and options selected.
464 Audible Signal Appliance.
Application: * UL listed for Wall mount.
The H24W Horn series is recommended for use in areas * Screw terminals capacity up to 12 AWG. Wired Without Audible Silence Feature: Wired for Audible Silence Feature:
such as: meeting rooms, schools, corridors, apartments, * Universal mounting plate included with each unit.
* 24 volts DC with two field selectable settings Sync Module Sync Module
office buildings, restaurants, hotels, and any other
* Polarized with wide listed voltage ranges using filtered F.A.C.P. SMS1-3A F.A.C.P. F.A.C.P. SMS1-3A
application where effective audible warning is required by Signal To Next Device or Strobe Signal
Circuit
Horn Signal To Next Device or
Federal, State, or local authority having jurisdiction. DC or unfiltered FWR input voltage. Circuit_ _ IN_ _
OUT End-Of Line-Resistor
_
Circuit
_ IN OUT End-Of Line-Resistor
+ H+H + + + _ H+H
_ _
* Horn field selectable tones: + + +
3000 Hz interrupted or Electro-mechanical + _ +
_
Temporal or Non-temporal
High or Low dBA output
* All models mount to 4” square, single gang, double gang, *The Sync module is rated for 3.0 amperes at 24 VDC.
or octagon back box.
Horn Selectable Sound Output: * Available in red or white housing. Dimensions:
* Synchronization requires an AMSECO SMS1-3A Sync Inches (mm)
3-3/8 (85.7)
Module.
5 (127) 1-17/32 (39) 1-13/16 (46)
Select- A -Horn Wiring:

3-9/32 (83.5)
Jumper

3-3/8 (85.7)

3-9/32 (83.5)
PC3 PC2 PC1 Control To Next Device or

5 (127)
Panel End-Of Line-Resistor
+ _

Temporal - Non-Temporal + _
Electro Mech - 3000 Hz
High - Low

WARNING:
Conductor Size (AWG), Length and capacity should be taken into consideration Mounting Options:
prior to design and installation of these products, particularly in retrofit
installations.
Mounting to a single gang box. Mounting to a 4” square back box. Mounting to a double gang box. Surface mount.

Ordering Information:
Model Input Sync w/ Universal Wall Ceiling Color Color
Number Voltage SMS1-3A Mounting Mount Mount Red White
( VDC ) Module
4” x 4” x 1-1/2”
H24WR 24 2” backbox 4” x 4” x 1-1/2”
backbox
backbox 4BX-1
H24WW 24 Surface Mount
Universal Mounting Plate Universal Mounting Plate Universal Mounting Plate back box
4SP-M
Horn Horn Horn Horn Mounting Plate
Specifications subject to change without notice.

Hochiki America Corporation


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Hochiki America Corporatrion:H24W-HORN
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 06/2003 Specifications subject to change without notice.
Engineering Specifications:
The Audible alarm indicating appliance shall be AMSECO model H24W or equivalent device. The horn shall be listed under UL 464
standard for Audible Signaling Appliance and shall be approved for fire protective service. The sound output shall be field selectable.
The Horn shall provide two different field selectable tones a High and Low field selectable sound output setting. The signaling Select-A-
Horn Horn shall operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The Horn shall be
H24W Horn capable of WALL mounting to a universal backbox. The H24W shall be installed as per plans and specifications.
TM
Select -A- Horn Series Select-A-Horn dB Output & Current Draw Table:
Description: P P P
PC3 PC2 PC1 Average Current ( mA ) Sound Output
AMSECO’s Select-A-Horn Series is designed to comply C C C ( dBA @ DC )
with NFPA/ANSI audible emergency evacuations signal Pattern Tone Volume 3 2 1 DC FWR
and UL 464 audible signaling appliances. The Horn 16V 24V 33V 16V 24V 33V 16V 24V 33V
provides two different field selectable tones, and a High /
Electro High 1 1 1 27 35 52 36 45 64 85 87 88
Low output setting that can be accomplished with the use of
mini jumpers located on back of the unit. The horn is clearly Mechanical Low 1 1 0 15 22 39 23 30 39 75 78 81
NON-TEMP
labeled with FIRE lettering and is polarized for connecting to High 1 0 1 27 35 52 36 45 64 85 88 88
3000 Hz
supervised fire alarm circuits. Horn with Universal Mounting Plate Low 1 0 0 15 22 39 23 30 39 75 78 81
The Select-A-Horn series is available in red or white Horn High 0 1 1 27 35 52 36 45 64 81 83 84
Electro
housing 24VDC models. The horn signals are listed for LI
STI N

Mechanical
UL 15 22 39 23 30 39 71 75 77

G
ULC TE
OF CA L IFO
R

Low 0 1 0
MEA

NI
ST

A
TEMPORAL
indoor use, ceiling and wall mount, under UL 1971

ST

LL
27 35 52 36 45 64 80 83 84
TE

A
FIR
E MAR
SH

High 0 0 1

E
E

S
RV I C

Standard. 3000 Hz
Low 0 0 0 15 22 39 23 30 39 71 75 77
Features:
* Designed to meet or exceed NFPA/ANSI Standards and UL **Sound output varies with tone and options selected.
464 Audible Signal Appliance.
Application: * UL listed for Wall mount.
The H24W Horn series is recommended for use in areas * Screw terminals capacity up to 12 AWG. Wired Without Audible Silence Feature: Wired for Audible Silence Feature:
such as: meeting rooms, schools, corridors, apartments, * Universal mounting plate included with each unit.
* 24 volts DC with two field selectable settings Sync Module Sync Module
office buildings, restaurants, hotels, and any other
* Polarized with wide listed voltage ranges using filtered F.A.C.P. SMS1-3A F.A.C.P. F.A.C.P. SMS1-3A
application where effective audible warning is required by Signal To Next Device or Strobe Signal
Circuit
Horn Signal To Next Device or
Federal, State, or local authority having jurisdiction. DC or unfiltered FWR input voltage. Circuit_ _ IN_ _
OUT End-Of Line-Resistor
_
Circuit
_ IN OUT End-Of Line-Resistor
+ H+H + + + _ H+H
_ _
* Horn field selectable tones: + + +
3000 Hz interrupted or Electro-mechanical + _ +
_
Temporal or Non-temporal
High or Low dBA output
* All models mount to 4” square, single gang, double gang, *The Sync module is rated for 3.0 amperes at 24 VDC.
or octagon back box.
Horn Selectable Sound Output: * Available in red or white housing. Dimensions:
* Synchronization requires an AMSECO SMS1-3A Sync Inches (mm)
3-3/8 (85.7)
Module.
5 (127) 1-17/32 (39) 1-13/16 (46)
Select- A -Horn Wiring:

3-9/32 (83.5)
Jumper

3-3/8 (85.7)

3-9/32 (83.5)
PC3 PC2 PC1 Control To Next Device or

5 (127)
Panel End-Of Line-Resistor
+ _

Temporal - Non-Temporal + _
Electro Mech - 3000 Hz
High - Low

WARNING:
Conductor Size (AWG), Length and capacity should be taken into consideration Mounting Options:
prior to design and installation of these products, particularly in retrofit
installations.
Mounting to a single gang box. Mounting to a 4” square back box. Mounting to a double gang box. Surface mount.

Ordering Information:
Model Input Sync w/ Universal Wall Ceiling Color Color
Number Voltage SMS1-3A Mounting Mount Mount Red White
( VDC ) Module
4” x 4” x 1-1/2”
H24WR 24 2” backbox 4” x 4” x 1-1/2”
backbox
backbox 4BX-1
H24WW 24 Surface Mount
Universal Mounting Plate Universal Mounting Plate Universal Mounting Plate back box
4SP-M
Horn Horn Horn Horn Mounting Plate
Specifications subject to change without notice.

Hochiki America Corporation


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Hochiki America Corporatrion:H24W-HORN
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 06/2003 Specifications subject to change without notice.
HP-24 / HP-24T
Piezo Alert Mini Horn
Description:
AMSECO’s Series mini horns are designed for alarm signaling
in individual rooms, apartments, hotels, offices, etc. where
dependable high performance alarm signaling is required.The
mini horns produce a high sound output with a minimum
current draw of just 15mA at 24VDC.
The mini horn is clearly labeled with FIRE lettering and is
polarized for connecting to supervised fire alarm circuits.
The mini horn is available with terminals or 4-wires, in red or
white housing 24VDC models.
TI
IS N

Application:

G
L
UL ULC
OF C A L IFO
TE R

A
MEA

NI
ST
FM

A
ST

LL
The HP-24 mini horn series is recommended for use in areas
T

A
E SH
FIR

A DA
E MA R

E
E

S
RVI C
APPROVED
such as; meeting rooms, schools, corridors, apartments, office
Features:
buildings, restaurants, hotels, and any other application where
* Designed to meet or exceed NFPA/ANSI Standards
effective audible warning is required by Federal, State, or local
and UL 464 Audible Signal Appliance.
authority having jurisdiction.
* Screw terminals capacity up to 12 AWG.
* 4-wires for easy field wiring.
Engineering Specifications: * Polarized with wide listed voltage ranges using filtered
The Audible alarm indicating appliance shall be AMSECO DC or unfiltered FWR input voltage.
model HP-24 or equivalent device. The horn shall be listed * Mounts to a single gang box.
under UL 464 standard for Audible Signaling Appliance and * Available in red or white housing.
shall be approved for fire protective service. The sound output
shall be 82 dB at 10 ft. The signaling mini Horn shall operate on Mini Horn Wiring:
24VDC from a non-coded regulated DC supply or full-wave
rectified, unfiltered supply. The Horn shall be capable of WALL
mounting to a single gang box. The HP-24 shall be installed as
per plans and specifications.
Control To Next Device or
Panel End-of Line-Resistor
Dimensions: Inches (mm) _ + _ +

“FIRE” 0.26 (6.5) 0.26 (6.5)


6.7
(170) WARNING: Conductor Size (AWG), Length and capacity should be
taken into consideration prior to design and installation of these
products, particularly in retrofit installations.
3.29 (83.5)

Mounting:

FIR
E

0.16 (4)

2.73 1.42 1.42


(69.2) (36) (36) Single gang box.

Specifications:
Model Rated Wiring Operating UL Indoor Average Plate Temperature
Number Voltage Type Range dB @ 10ft. dB @ 10ft Current Color Operating
( VDC ) (VDC) ( dBA ) ( dBA) ( Amps) Range

HP-24R 24 4-wire 19.2 ~ 26.4 82 97 0.015 Red


HP-24W 24 4-wire 19.2 ~ 26.4 82 97 0.015 White -4°F ~ 140 °F
(-20°C ~ 60°C)
HP-24TR 24 Terminal 19.2 ~ 26.4 82 97 0.015 Red
HP-24TW 24 Terminal 19.2 ~ 26.4 82 97 0.015 White

Specifications subject to change without notice.

Hochiki America Corporation


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 06/2003
Mounting: using SPC-1 retrofit plate
Single gang
Double gang Octagon Engineering Specifications:
back box back box The audible and visual alarm indicating appliance shall be AMSECO model SH24C-177 or equivalent device. The Strobe shall be listed Horn/Strobe Current Draw Table:
back box
under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The candela
4” square
back box output shall be 177 intensity output. All settings shall be UL1971 listed for both ceiling and wall mount applications. The Horn shall =1 =0 Average Current ( mA ) Sound Output
provide two different field selectable tones, and a High and Low field selectable sound output setting. The signaling Horn/Strobe shall
SH24C-177 SPC-1 SPC-1 SPC-1
operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be PC3 PC2 PC1 P P P
C C C
DC FWR ( dBA@DC)
Horn /Strobe designed to produce a signal flash of one flash per second with continuously applied minimum voltage. When strobe synchronization is Pattern Tone Volume 3 2 1 16V 24V 33V 16V 24V 33V 16V 24V 33V
required, the horn/strobe shall be compatible with the AMSECO SMS1-3A or SMD10-3A (daisy chain) or other source of AMSECO sync HIGH 419 294 235 511 379 312 86 88 88
1 1 1
Ceiling and Wall Mount Combination protocol. The Horn/Strobe shall be capable of CEILING and WALL mounting to a 4” x 4”x 1-1/2” back box. Signaling devices shall be ELECTRO
MECHANICAL
installed in all sleeping and non-sleeping areas as per plans and specifications. LOW 1 1 0 402 275 220 497 366 301 76 80 83
Horn NON-TEMP.
HIGH 1 0 1 419 294 235 511 379 312 87 88 88
Description: & 3000 Hz
LOW 1 0 0 402 275 220 497 366 301 77 81 83
AMSECO’s Ceiling and Wall mount Horn/Strobe is designed to Strobe
comply with the Americans with Disability Act (ADA) and meet UL Light Output Dispersion: @ ELECTRO HIGH 0 1 1 419 294 235 511 379 312 80 84 84

90 °
MECHANICAL *1
Standard 1971 requirements for emergency signaling devices WA 177cd. LOW 0 1 0 402 275 220 497 366 301 73 76 79
Surface Mount: using RBX-1 back box skirt and SPC-1 retrofit plate 90° LL TEMPORAL

G
for the hearing impaired. The SH24C-177 Horn/Strobe features

IN
HIGH 0 0 1 419 294 235 511 379 312 82 84 84

IL
a 177 candela intensity output. The Horn provides two different Single gang Double gang Octagon 3000 Hz

E
*2
Compound Compound LOW 0 0 0 402 275 220 497 366 301 74 77 79

C
field selectable tones, and a High / Low output setting that can be back box back box back box

°
°
Horn/Strobe 177cd.

90
90
90°

45°
achieved with the use of mini jumpers located on back of the unit. Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and

45°
FI
The round housing design offers a low profile appearance and is LI
STI N
4” square Private Modes only).

R
UL

G
A
OF C L IFOR

ULC FI FI

E
TE

MEA

NI
E

ST
E

A
back box R R

R
clearly labeled with “FIRE” lettering to be view from all angles.

ST

LL

FI

FI
E

E
T

A
E SH
FIR
E MAR

E
E

S
RV I C

SPC-1 Horn Only Current Draw Table:

FI R E
These appliances are polarized for connecting to supervised fire SPC-1 SPC-1
alarm circuits. The strobe is designed with a xenon flashtube and Features:
* 177 candela output.
FI R E FI R E
=1 =0 Average Current ( mA ) Sound Output
provides a candela intensity field selector switch for maximum 45° 45°

FI
performance. * ADA/NFPA/ANSI compliant. R
P P P DC ( dBA@DC)
E
PC3 PC2 PC1 FWR



The Ceiling mount Horn/Strobe series is available in red and * UL listed for Ceiling and Wall mounting under UL1971. 90° C C C

°
90
Pattern Tone Volume

90
* Designed for use in sleeping and non-sleeping areas. 0° 3 2 1 16V 24V 33V 16V 24V 33V 16V 24V 33V
white housing 24V DC models. The SH24C-177 can be RBX-1
synchronized by using the SMD10-3A (daisy chain) Sync * Screw terminal capacity up to 12 AWG. RBX-1 RBX-1 RBX-1 ELECTRO HIGH 1 1 1 34 44 49 33 40 45 86 88 88
Module to comply with NFPA recommendations concerning * Polarized strobes with wide listed voltage ranges using 90° MECHANICAL LOW 1 1 0 17 25 34 19 27 34 76 80 83

90 °
filtered DC or unfiltered FWR input voltage. NON-TEMP.

45°
photosensitive epilepsy when installing 2 or more visual 0°

45°
* Horn field selectable tones: HIGH 1 0 1 34 44 49 33 40 45 87 88 88
appliances within the field of view. The strobe signals are 3000 Hz
3000 Hz interrupted or Electro-mechanical Horn LOW 1 0 0 17 25 34 19 27 34 77 81 83
designed for sleeping and non-sleeping areas and are listed for Compound Compound only
indoor use, ceiling and wall mount, under UL 1971 Standard. Temporal or Non-temporal ELECTRO HIGH 0 1 1 34 44 49 33 40 45 80 84 84
High or Low dBA output MECHANICAL LOW 0 1 0 17 25 34 19 27 34 *1
73 76 79
* Meets ADA guidelines for minimum one flash per/sec (1Hz). TEMPORAL
* All models mount to 4” x 4” x 1-1/2” back box. Horn/Strobe Combination Wiring: Wired Without Audible Silence Feature: HIGH 0 0 1 34 44 49 33 40 45 82 84 84
Application: 3000 Hz *2
* 24 volt strobe models 177 candela intensity. Sync Module LOW 0 0 0 17 25 34 19 27 34 74 77 79
The SH24C-177 Ceiling Horn/Strobe Series is recommended
* Synchronization requires an AMSECO SMD10-3A Room Spacing for Ceiling-Mounted Visible Appliances Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
for use in areas such as: meeting rooms, schools, corridors, Using the Sync Modules: F.A.C.P. FI
To Next Device F.A.C.P. SMD10-3A FI
To Next Device or
(daisy chain) Sync Module. R
E
Signal R
E
Private Modes only).

R
apartments, office buildings, restaurants, hotels, and any other Minimum Light Output by Room Size. Signal or End-Of Line- IN OUT End-Of Line-

FI

E
FI

E
* RBX-1 back box skirt for surface mount (optional). The Sync module is designed to provide a synchronized temporal Circuit Circuit
_ _ _ _
application where effective audible and visual warning are
* The SPC-1 retrofit plate allows mounting to a variety of back pattern (code 3) tone, and synchronize the strobe flashes when used + _ Resistor
+ H+H + + Resistor

required by Federal, State, or local authority having jurisdiction. Maximum Maximum Room Size (ft.)
+ _
FI R E

boxes (optional). with AMSECO’s 177cd Strobe, and Horn/Strobe as well as the ability Ceiling
FI R E

Strobe Only Current Draw Table:


* Available in red or white housing. to silence the horn while maintaining the strobe flashes. The SMD10- Height (ft.) 20 X 20 30 X 30 40 X 40 50 X 50 + _
3A has the capability of connecting two style Y (class B) circuits or
Wiring Terminals: Horn Selectable Sound Output: one style Z (class A) circuit, and is rated for 3 amperes per circuit. 30 75cd. 75cd. 177cd. 177cd.
DC FWR
The SMD10-3A can be interconnected so that more than two alarm 20 30cd. 75cd. 110cd. 177cd. *The Sync module is rated for 3.0 amperes at 24 VDC. Current ( mA )
zones can be synchronized when connected using the SYNC 10 30cd. 30cd. 75cd. 110cd. 16V 24V 33V 16V 24V 33V
terminals. (Daisy chain connection). The Max number of Average 390 255 191 483 344 272
interconnected SMD10-3A modules is twenty (20). All input are Signals Wired for Independent Operation: Wired for Audible Silence Feature: Strobe only
Peak 596 438 386 859 816 708
polarized for compatibility with standard reverse polarity supervision of @ 177cd.
circuit wiring, when used with a Fire Alarm Control Panel (F.A.C.P.). Room Spacing for Wall-Mounted Visible Appliances In-Rush 460 476 508 788 828 716
FI
Minimum Light Output by room Size (Non-Sleeping) R
E
F.A.C.P. FI

R
E
To Next Device

FI
SMD10-3A

E
R

R
Strobe Signal Horn Signal

FI

E
Circuit Circuit or End-Of Line-
PC3 PC2 PC1 For a synchronization system, the maximum number of strobe lights Maximum One Strobe To Next Device or +
_ _ H+H
_ _ OUTPUT
INPUT _ Resistor
Two Strobes Four Strobes + + +
that can be connected to a listed Fire Alarm Control Panel 3Amp
FI R E

Room End-Of Line-Resistor


+ _ Dimensions: Inches (mm)
FI R E

per Room per Room per Room Strobe Horn _


Loop circuit is as follows: Size F.A.C.P. _ _ +
+ +
14 (30cd, 16~33VDC) or 10 (30cd, 16~33V FWR)
13 (75cd, 16~33VDC) or 8 (75cd, 16~33V FWR) 20¢X 20¢ 15 cd. NA NA
Temporal - Non-Temporal 30¢X 30¢ 30 cd. 15 cd. NA
Strobe
Signal
+
_
Electro Mech - 3000 Hz 11 (110cd, 16~33VDC) or 7 (110cd, 16~33V FWR) Circuit
High - Low The maximum wire impedance between any adjacent strobe light is 40¢X 40¢ 60 cd. 30 cd. 15 cd.
Ordering Information: To Next Device or
5.6 ohms. 50¢X 50¢ 95 cd. 60 cd. 30 cd. End-Of Line-Resistor + - + -
_
+

3-3/8 (85.7)
Model Input Strobe Sync Mounting Horn Flash Housing 60¢X 60¢ 135 cd. 95 cd. 30 cd.
Voltage Output Module Type Sound Rate Color Ordering Information: Horn
Number 70¢X 70¢ 185 cd. 95 cd. 60 cd. Signal +
(VDC) (Candela) Output (Times/min.) Circuit _
Model Input Maximum Average Mounting Color 80¢X 80¢ 240 cd. 135 cd. 60 cd.
SH24C-177R 24 177 SMD10-3A Ceiling/Wall Selectable 60 Red Number Voltage Load Current Back Box 90¢X 90¢ 305 cd. 185 cd. 95 cd.
SH24C-177W 24 177 SMD10-3A Ceiling/Wall Selectable 60 White (VDC) (Amps) (mA) 100¢X 100¢ 375 cd. 240 cd. 95 cd. WARNING:
The Horn/Strobe is listed for indoor use with a temperature operating range of 32°F ~ 120°F (0°C ~ 49°C ) * The Horn/Strobe must be used only on circuits with continuously operating voltage. DO NOT use strobe on coded or interrupted circuits in which
SMS1-3A 24 3 9 4"x4"x1-1/2" Red 110¢X 110¢ 455 cd. 240 cd. 135 cd. the applied voltage is interrupted ON and OFF as the strobe may fail to flash.
120¢X 120¢ 540 cd. 305 cd. 135 cd. * The applied voltage must be within its rated input voltage range. 1-13/32 (35)
SMD10-3A 24 3 9 4"x4"x1-1/2" Red
Specifications subject to change without notice.
130¢X 130¢ 635 cd. 375 cd. 185 cd. * Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits. 6-7/8 (174) 2-25/32 (70) 3-3/8 (85.7)
The total current draw from all devices connected to the sync module should not exceed
NA: Not allowable
Hochiki America Corporation 3.0A, and should only be connected to circuits that provide continuously applied voltage.
7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Hochiki America Corporatrion : SH24C-177
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 06/2003 Hochiki America Corporatrion : SH24C-177 Specifications subject to change without notice. Hochiki America Corporatrion : SH24C-177 Specifications subject to change without notice. Specifications subject to change without notice.
Mounting: using SPC-1 retrofit plate
Single gang
Double gang Octagon Engineering Specifications:
back box back box The audible and visual alarm indicating appliance shall be AMSECO model SH24C-177 or equivalent device. The Strobe shall be listed Horn/Strobe Current Draw Table:
back box
under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The candela
4” square
back box output shall be 177 intensity output. All settings shall be UL1971 listed for both ceiling and wall mount applications. The Horn shall =1 =0 Average Current ( mA ) Sound Output
provide two different field selectable tones, and a High and Low field selectable sound output setting. The signaling Horn/Strobe shall
SH24C-177 SPC-1 SPC-1 SPC-1
operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be PC3 PC2 PC1 P P P
C C C
DC FWR ( dBA@DC)
Horn /Strobe designed to produce a signal flash of one flash per second with continuously applied minimum voltage. When strobe synchronization is Pattern Tone Volume 3 2 1 16V 24V 33V 16V 24V 33V 16V 24V 33V
required, the horn/strobe shall be compatible with the AMSECO SMS1-3A or SMD10-3A (daisy chain) or other source of AMSECO sync HIGH 419 294 235 511 379 312 86 88 88
1 1 1
Ceiling and Wall Mount Combination protocol. The Horn/Strobe shall be capable of CEILING and WALL mounting to a 4” x 4”x 1-1/2” back box. Signaling devices shall be ELECTRO
MECHANICAL
installed in all sleeping and non-sleeping areas as per plans and specifications. LOW 1 1 0 402 275 220 497 366 301 76 80 83
Horn NON-TEMP.
HIGH 1 0 1 419 294 235 511 379 312 87 88 88
Description: & 3000 Hz
LOW 1 0 0 402 275 220 497 366 301 77 81 83
AMSECO’s Ceiling and Wall mount Horn/Strobe is designed to Strobe
comply with the Americans with Disability Act (ADA) and meet UL Light Output Dispersion: @ ELECTRO HIGH 0 1 1 419 294 235 511 379 312 80 84 84

90 °
MECHANICAL *1
Standard 1971 requirements for emergency signaling devices WA 177cd. LOW 0 1 0 402 275 220 497 366 301 73 76 79
Surface Mount: using RBX-1 back box skirt and SPC-1 retrofit plate 90° LL TEMPORAL

G
for the hearing impaired. The SH24C-177 Horn/Strobe features

IN
HIGH 0 0 1 419 294 235 511 379 312 82 84 84

IL
a 177 candela intensity output. The Horn provides two different Single gang Double gang Octagon 3000 Hz

E
*2
Compound Compound LOW 0 0 0 402 275 220 497 366 301 74 77 79

C
field selectable tones, and a High / Low output setting that can be back box back box back box

°
°
Horn/Strobe 177cd.

90
90
90°

45°
achieved with the use of mini jumpers located on back of the unit. Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and

45°
FI
The round housing design offers a low profile appearance and is LI
STI N
4” square Private Modes only).

R
UL

G
A
OF C L IFOR

ULC FI FI

E
TE

MEA

NI
E

ST
E

A
back box R R

R
clearly labeled with “FIRE” lettering to be view from all angles.

ST

LL

FI

FI
E

E
T

A
E SH
FIR
E MAR

E
E

S
RV I C

SPC-1 Horn Only Current Draw Table:

FI R E
These appliances are polarized for connecting to supervised fire SPC-1 SPC-1
alarm circuits. The strobe is designed with a xenon flashtube and Features:
* 177 candela output.
FI R E FI R E
=1 =0 Average Current ( mA ) Sound Output
provides a candela intensity field selector switch for maximum 45° 45°

FI
performance. * ADA/NFPA/ANSI compliant. R
P P P DC ( dBA@DC)
E
PC3 PC2 PC1 FWR



The Ceiling mount Horn/Strobe series is available in red and * UL listed for Ceiling and Wall mounting under UL1971. 90° C C C

°
90
Pattern Tone Volume

90
* Designed for use in sleeping and non-sleeping areas. 0° 3 2 1 16V 24V 33V 16V 24V 33V 16V 24V 33V
white housing 24V DC models. The SH24C-177 can be RBX-1
synchronized by using the SMD10-3A (daisy chain) Sync * Screw terminal capacity up to 12 AWG. RBX-1 RBX-1 RBX-1 ELECTRO HIGH 1 1 1 34 44 49 33 40 45 86 88 88
Module to comply with NFPA recommendations concerning * Polarized strobes with wide listed voltage ranges using 90° MECHANICAL LOW 1 1 0 17 25 34 19 27 34 76 80 83

90 °
filtered DC or unfiltered FWR input voltage. NON-TEMP.

45°
photosensitive epilepsy when installing 2 or more visual 0°

45°
* Horn field selectable tones: HIGH 1 0 1 34 44 49 33 40 45 87 88 88
appliances within the field of view. The strobe signals are 3000 Hz
3000 Hz interrupted or Electro-mechanical Horn LOW 1 0 0 17 25 34 19 27 34 77 81 83
designed for sleeping and non-sleeping areas and are listed for Compound Compound only
indoor use, ceiling and wall mount, under UL 1971 Standard. Temporal or Non-temporal ELECTRO HIGH 0 1 1 34 44 49 33 40 45 80 84 84
High or Low dBA output MECHANICAL LOW 0 1 0 17 25 34 19 27 34 *1
73 76 79
* Meets ADA guidelines for minimum one flash per/sec (1Hz). TEMPORAL
* All models mount to 4” x 4” x 1-1/2” back box. Horn/Strobe Combination Wiring: Wired Without Audible Silence Feature: HIGH 0 0 1 34 44 49 33 40 45 82 84 84
Application: 3000 Hz *2
* 24 volt strobe models 177 candela intensity. Sync Module LOW 0 0 0 17 25 34 19 27 34 74 77 79
The SH24C-177 Ceiling Horn/Strobe Series is recommended
* Synchronization requires an AMSECO SMD10-3A Room Spacing for Ceiling-Mounted Visible Appliances Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
for use in areas such as: meeting rooms, schools, corridors, Using the Sync Modules: F.A.C.P. FI
To Next Device F.A.C.P. SMD10-3A FI
To Next Device or
(daisy chain) Sync Module. R
E
Signal R
E
Private Modes only).

R
apartments, office buildings, restaurants, hotels, and any other Minimum Light Output by Room Size. Signal or End-Of Line- IN OUT End-Of Line-

FI

E
FI

E
* RBX-1 back box skirt for surface mount (optional). The Sync module is designed to provide a synchronized temporal Circuit Circuit
_ _ _ _
application where effective audible and visual warning are
* The SPC-1 retrofit plate allows mounting to a variety of back pattern (code 3) tone, and synchronize the strobe flashes when used + _ Resistor
+ H+H + + Resistor

required by Federal, State, or local authority having jurisdiction. Maximum Maximum Room Size (ft.)
+ _
FI R E

boxes (optional). with AMSECO’s 177cd Strobe, and Horn/Strobe as well as the ability Ceiling
FI R E

Strobe Only Current Draw Table:


* Available in red or white housing. to silence the horn while maintaining the strobe flashes. The SMD10- Height (ft.) 20 X 20 30 X 30 40 X 40 50 X 50 + _
3A has the capability of connecting two style Y (class B) circuits or
Wiring Terminals: Horn Selectable Sound Output: one style Z (class A) circuit, and is rated for 3 amperes per circuit. 30 75cd. 75cd. 177cd. 177cd.
DC FWR
The SMD10-3A can be interconnected so that more than two alarm 20 30cd. 75cd. 110cd. 177cd. *The Sync module is rated for 3.0 amperes at 24 VDC. Current ( mA )
zones can be synchronized when connected using the SYNC 10 30cd. 30cd. 75cd. 110cd. 16V 24V 33V 16V 24V 33V
terminals. (Daisy chain connection). The Max number of Average 390 255 191 483 344 272
interconnected SMD10-3A modules is twenty (20). All input are Signals Wired for Independent Operation: Wired for Audible Silence Feature: Strobe only
Peak 596 438 386 859 816 708
polarized for compatibility with standard reverse polarity supervision of @ 177cd.
circuit wiring, when used with a Fire Alarm Control Panel (F.A.C.P.). Room Spacing for Wall-Mounted Visible Appliances In-Rush 460 476 508 788 828 716
FI
Minimum Light Output by room Size (Non-Sleeping) R
E
F.A.C.P. FI

R
E
To Next Device

FI
SMD10-3A

E
R

R
Strobe Signal Horn Signal

FI

E
Circuit Circuit or End-Of Line-
PC3 PC2 PC1 For a synchronization system, the maximum number of strobe lights Maximum One Strobe To Next Device or +
_ _ H+H
_ _ OUTPUT
INPUT _ Resistor
Two Strobes Four Strobes + + +
that can be connected to a listed Fire Alarm Control Panel 3Amp
FI R E

Room End-Of Line-Resistor


+ _ Dimensions: Inches (mm)
FI R E

per Room per Room per Room Strobe Horn _


Loop circuit is as follows: Size F.A.C.P. _ _ +
+ +
14 (30cd, 16~33VDC) or 10 (30cd, 16~33V FWR)
13 (75cd, 16~33VDC) or 8 (75cd, 16~33V FWR) 20¢X 20¢ 15 cd. NA NA
Temporal - Non-Temporal 30¢X 30¢ 30 cd. 15 cd. NA
Strobe
Signal
+
_
Electro Mech - 3000 Hz 11 (110cd, 16~33VDC) or 7 (110cd, 16~33V FWR) Circuit
High - Low The maximum wire impedance between any adjacent strobe light is 40¢X 40¢ 60 cd. 30 cd. 15 cd.
Ordering Information: To Next Device or
5.6 ohms. 50¢X 50¢ 95 cd. 60 cd. 30 cd. End-Of Line-Resistor + - + -
_
+

3-3/8 (85.7)
Model Input Strobe Sync Mounting Horn Flash Housing 60¢X 60¢ 135 cd. 95 cd. 30 cd.
Voltage Output Module Type Sound Rate Color Ordering Information: Horn
Number 70¢X 70¢ 185 cd. 95 cd. 60 cd. Signal +
(VDC) (Candela) Output (Times/min.) Circuit _
Model Input Maximum Average Mounting Color 80¢X 80¢ 240 cd. 135 cd. 60 cd.
SH24C-177R 24 177 SMD10-3A Ceiling/Wall Selectable 60 Red Number Voltage Load Current Back Box 90¢X 90¢ 305 cd. 185 cd. 95 cd.
SH24C-177W 24 177 SMD10-3A Ceiling/Wall Selectable 60 White (VDC) (Amps) (mA) 100¢X 100¢ 375 cd. 240 cd. 95 cd. WARNING:
The Horn/Strobe is listed for indoor use with a temperature operating range of 32°F ~ 120°F (0°C ~ 49°C ) * The Horn/Strobe must be used only on circuits with continuously operating voltage. DO NOT use strobe on coded or interrupted circuits in which
SMS1-3A 24 3 9 4"x4"x1-1/2" Red 110¢X 110¢ 455 cd. 240 cd. 135 cd. the applied voltage is interrupted ON and OFF as the strobe may fail to flash.
120¢X 120¢ 540 cd. 305 cd. 135 cd. * The applied voltage must be within its rated input voltage range. 1-13/32 (35)
SMD10-3A 24 3 9 4"x4"x1-1/2" Red
Specifications subject to change without notice.
130¢X 130¢ 635 cd. 375 cd. 185 cd. * Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits. 6-7/8 (174) 2-25/32 (70) 3-3/8 (85.7)
The total current draw from all devices connected to the sync module should not exceed
NA: Not allowable
Hochiki America Corporation 3.0A, and should only be connected to circuits that provide continuously applied voltage.
7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Hochiki America Corporatrion : SH24C-177
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 06/2003 Hochiki America Corporatrion : SH24C-177 Specifications subject to change without notice. Hochiki America Corporatrion : SH24C-177 Specifications subject to change without notice. Specifications subject to change without notice.
Mounting: using SPC-1 retrofit plate
Single gang
Double gang Octagon Engineering Specifications:
back box back box The audible and visual alarm indicating appliance shall be AMSECO model SH24C-177 or equivalent device. The Strobe shall be listed Horn/Strobe Current Draw Table:
back box
under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The candela
4” square
back box output shall be 177 intensity output. All settings shall be UL1971 listed for both ceiling and wall mount applications. The Horn shall =1 =0 Average Current ( mA ) Sound Output
provide two different field selectable tones, and a High and Low field selectable sound output setting. The signaling Horn/Strobe shall
SH24C-177 SPC-1 SPC-1 SPC-1
operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be PC3 PC2 PC1 P P P
C C C
DC FWR ( dBA@DC)
Horn /Strobe designed to produce a signal flash of one flash per second with continuously applied minimum voltage. When strobe synchronization is Pattern Tone Volume 3 2 1 16V 24V 33V 16V 24V 33V 16V 24V 33V
required, the horn/strobe shall be compatible with the AMSECO SMS1-3A or SMD10-3A (daisy chain) or other source of AMSECO sync HIGH 419 294 235 511 379 312 86 88 88
1 1 1
Ceiling and Wall Mount Combination protocol. The Horn/Strobe shall be capable of CEILING and WALL mounting to a 4” x 4”x 1-1/2” back box. Signaling devices shall be ELECTRO
MECHANICAL
installed in all sleeping and non-sleeping areas as per plans and specifications. LOW 1 1 0 402 275 220 497 366 301 76 80 83
Horn NON-TEMP.
HIGH 1 0 1 419 294 235 511 379 312 87 88 88
Description: & 3000 Hz
LOW 1 0 0 402 275 220 497 366 301 77 81 83
AMSECO’s Ceiling and Wall mount Horn/Strobe is designed to Strobe
comply with the Americans with Disability Act (ADA) and meet UL Light Output Dispersion: @ ELECTRO HIGH 0 1 1 419 294 235 511 379 312 80 84 84

90 °
MECHANICAL *1
Standard 1971 requirements for emergency signaling devices WA 177cd. LOW 0 1 0 402 275 220 497 366 301 73 76 79
Surface Mount: using RBX-1 back box skirt and SPC-1 retrofit plate 90° LL TEMPORAL

G
for the hearing impaired. The SH24C-177 Horn/Strobe features

IN
HIGH 0 0 1 419 294 235 511 379 312 82 84 84

IL
a 177 candela intensity output. The Horn provides two different Single gang Double gang Octagon 3000 Hz

E
*2
Compound Compound LOW 0 0 0 402 275 220 497 366 301 74 77 79

C
field selectable tones, and a High / Low output setting that can be back box back box back box

°
°
Horn/Strobe 177cd.

90
90
90°

45°
achieved with the use of mini jumpers located on back of the unit. Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and

45°
FI
The round housing design offers a low profile appearance and is LI
STI N
4” square Private Modes only).

R
UL

G
A
OF C L IFOR

ULC FI FI

E
TE

MEA

NI
E

ST
E

A
back box R R

R
clearly labeled with “FIRE” lettering to be view from all angles.

ST

LL

FI

FI
E

E
T

A
E SH
FIR
E MAR

E
E

S
RV I C

SPC-1 Horn Only Current Draw Table:

FI R E
These appliances are polarized for connecting to supervised fire SPC-1 SPC-1
alarm circuits. The strobe is designed with a xenon flashtube and Features:
* 177 candela output.
FI R E FI R E
=1 =0 Average Current ( mA ) Sound Output
provides a candela intensity field selector switch for maximum 45° 45°

FI
performance. * ADA/NFPA/ANSI compliant. R
P P P DC ( dBA@DC)
E
PC3 PC2 PC1 FWR



The Ceiling mount Horn/Strobe series is available in red and * UL listed for Ceiling and Wall mounting under UL1971. 90° C C C

°
90
Pattern Tone Volume

90
* Designed for use in sleeping and non-sleeping areas. 0° 3 2 1 16V 24V 33V 16V 24V 33V 16V 24V 33V
white housing 24V DC models. The SH24C-177 can be RBX-1
synchronized by using the SMD10-3A (daisy chain) Sync * Screw terminal capacity up to 12 AWG. RBX-1 RBX-1 RBX-1 ELECTRO HIGH 1 1 1 34 44 49 33 40 45 86 88 88
Module to comply with NFPA recommendations concerning * Polarized strobes with wide listed voltage ranges using 90° MECHANICAL LOW 1 1 0 17 25 34 19 27 34 76 80 83

90 °
filtered DC or unfiltered FWR input voltage. NON-TEMP.

45°
photosensitive epilepsy when installing 2 or more visual 0°

45°
* Horn field selectable tones: HIGH 1 0 1 34 44 49 33 40 45 87 88 88
appliances within the field of view. The strobe signals are 3000 Hz
3000 Hz interrupted or Electro-mechanical Horn LOW 1 0 0 17 25 34 19 27 34 77 81 83
designed for sleeping and non-sleeping areas and are listed for Compound Compound only
indoor use, ceiling and wall mount, under UL 1971 Standard. Temporal or Non-temporal ELECTRO HIGH 0 1 1 34 44 49 33 40 45 80 84 84
High or Low dBA output MECHANICAL LOW 0 1 0 17 25 34 19 27 34 *1
73 76 79
* Meets ADA guidelines for minimum one flash per/sec (1Hz). TEMPORAL
* All models mount to 4” x 4” x 1-1/2” back box. Horn/Strobe Combination Wiring: Wired Without Audible Silence Feature: HIGH 0 0 1 34 44 49 33 40 45 82 84 84
Application: 3000 Hz *2
* 24 volt strobe models 177 candela intensity. Sync Module LOW 0 0 0 17 25 34 19 27 34 74 77 79
The SH24C-177 Ceiling Horn/Strobe Series is recommended
* Synchronization requires an AMSECO SMD10-3A Room Spacing for Ceiling-Mounted Visible Appliances Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
for use in areas such as: meeting rooms, schools, corridors, Using the Sync Modules: F.A.C.P. FI
To Next Device F.A.C.P. SMD10-3A FI
To Next Device or
(daisy chain) Sync Module. R
E
Signal R
E
Private Modes only).

R
apartments, office buildings, restaurants, hotels, and any other Minimum Light Output by Room Size. Signal or End-Of Line- IN OUT End-Of Line-

FI

E
FI

E
* RBX-1 back box skirt for surface mount (optional). The Sync module is designed to provide a synchronized temporal Circuit Circuit
_ _ _ _
application where effective audible and visual warning are
* The SPC-1 retrofit plate allows mounting to a variety of back pattern (code 3) tone, and synchronize the strobe flashes when used + _ Resistor
+ H+H + + Resistor

required by Federal, State, or local authority having jurisdiction. Maximum Maximum Room Size (ft.)
+ _
FI R E

boxes (optional). with AMSECO’s 177cd Strobe, and Horn/Strobe as well as the ability Ceiling
FI R E

Strobe Only Current Draw Table:


* Available in red or white housing. to silence the horn while maintaining the strobe flashes. The SMD10- Height (ft.) 20 X 20 30 X 30 40 X 40 50 X 50 + _
3A has the capability of connecting two style Y (class B) circuits or
Wiring Terminals: Horn Selectable Sound Output: one style Z (class A) circuit, and is rated for 3 amperes per circuit. 30 75cd. 75cd. 177cd. 177cd.
DC FWR
The SMD10-3A can be interconnected so that more than two alarm 20 30cd. 75cd. 110cd. 177cd. *The Sync module is rated for 3.0 amperes at 24 VDC. Current ( mA )
zones can be synchronized when connected using the SYNC 10 30cd. 30cd. 75cd. 110cd. 16V 24V 33V 16V 24V 33V
terminals. (Daisy chain connection). The Max number of Average 390 255 191 483 344 272
interconnected SMD10-3A modules is twenty (20). All input are Signals Wired for Independent Operation: Wired for Audible Silence Feature: Strobe only
Peak 596 438 386 859 816 708
polarized for compatibility with standard reverse polarity supervision of @ 177cd.
circuit wiring, when used with a Fire Alarm Control Panel (F.A.C.P.). Room Spacing for Wall-Mounted Visible Appliances In-Rush 460 476 508 788 828 716
FI
Minimum Light Output by room Size (Non-Sleeping) R
E
F.A.C.P. FI

R
E
To Next Device

FI
SMD10-3A

E
R

R
Strobe Signal Horn Signal

FI

E
Circuit Circuit or End-Of Line-
PC3 PC2 PC1 For a synchronization system, the maximum number of strobe lights Maximum One Strobe To Next Device or +
_ _ H+H
_ _ OUTPUT
INPUT _ Resistor
Two Strobes Four Strobes + + +
that can be connected to a listed Fire Alarm Control Panel 3Amp
FI R E

Room End-Of Line-Resistor


+ _ Dimensions: Inches (mm)
FI R E

per Room per Room per Room Strobe Horn _


Loop circuit is as follows: Size F.A.C.P. _ _ +
+ +
14 (30cd, 16~33VDC) or 10 (30cd, 16~33V FWR)
13 (75cd, 16~33VDC) or 8 (75cd, 16~33V FWR) 20¢X 20¢ 15 cd. NA NA
Temporal - Non-Temporal 30¢X 30¢ 30 cd. 15 cd. NA
Strobe
Signal
+
_
Electro Mech - 3000 Hz 11 (110cd, 16~33VDC) or 7 (110cd, 16~33V FWR) Circuit
High - Low The maximum wire impedance between any adjacent strobe light is 40¢X 40¢ 60 cd. 30 cd. 15 cd.
Ordering Information: To Next Device or
5.6 ohms. 50¢X 50¢ 95 cd. 60 cd. 30 cd. End-Of Line-Resistor + - + -
_
+

3-3/8 (85.7)
Model Input Strobe Sync Mounting Horn Flash Housing 60¢X 60¢ 135 cd. 95 cd. 30 cd.
Voltage Output Module Type Sound Rate Color Ordering Information: Horn
Number 70¢X 70¢ 185 cd. 95 cd. 60 cd. Signal +
(VDC) (Candela) Output (Times/min.) Circuit _
Model Input Maximum Average Mounting Color 80¢X 80¢ 240 cd. 135 cd. 60 cd.
SH24C-177R 24 177 SMD10-3A Ceiling/Wall Selectable 60 Red Number Voltage Load Current Back Box 90¢X 90¢ 305 cd. 185 cd. 95 cd.
SH24C-177W 24 177 SMD10-3A Ceiling/Wall Selectable 60 White (VDC) (Amps) (mA) 100¢X 100¢ 375 cd. 240 cd. 95 cd. WARNING:
The Horn/Strobe is listed for indoor use with a temperature operating range of 32°F ~ 120°F (0°C ~ 49°C ) * The Horn/Strobe must be used only on circuits with continuously operating voltage. DO NOT use strobe on coded or interrupted circuits in which
SMS1-3A 24 3 9 4"x4"x1-1/2" Red 110¢X 110¢ 455 cd. 240 cd. 135 cd. the applied voltage is interrupted ON and OFF as the strobe may fail to flash.
120¢X 120¢ 540 cd. 305 cd. 135 cd. * The applied voltage must be within its rated input voltage range. 1-13/32 (35)
SMD10-3A 24 3 9 4"x4"x1-1/2" Red
Specifications subject to change without notice.
130¢X 130¢ 635 cd. 375 cd. 185 cd. * Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits. 6-7/8 (174) 2-25/32 (70) 3-3/8 (85.7)
The total current draw from all devices connected to the sync module should not exceed
NA: Not allowable
Hochiki America Corporation 3.0A, and should only be connected to circuits that provide continuously applied voltage.
7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Hochiki America Corporatrion : SH24C-177
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 06/2003 Hochiki America Corporatrion : SH24C-177 Specifications subject to change without notice. Hochiki America Corporatrion : SH24C-177 Specifications subject to change without notice. Specifications subject to change without notice.
Mounting: using SPC-1 retrofit plate
Single gang
Double gang Octagon Engineering Specifications:
back box back box The audible and visual alarm indicating appliance shall be AMSECO model SH24C-177 or equivalent device. The Strobe shall be listed Horn/Strobe Current Draw Table:
back box
under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The candela
4” square
back box output shall be 177 intensity output. All settings shall be UL1971 listed for both ceiling and wall mount applications. The Horn shall =1 =0 Average Current ( mA ) Sound Output
provide two different field selectable tones, and a High and Low field selectable sound output setting. The signaling Horn/Strobe shall
SH24C-177 SPC-1 SPC-1 SPC-1
operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be PC3 PC2 PC1 P P P
C C C
DC FWR ( dBA@DC)
Horn /Strobe designed to produce a signal flash of one flash per second with continuously applied minimum voltage. When strobe synchronization is Pattern Tone Volume 3 2 1 16V 24V 33V 16V 24V 33V 16V 24V 33V
required, the horn/strobe shall be compatible with the AMSECO SMS1-3A or SMD10-3A (daisy chain) or other source of AMSECO sync HIGH 419 294 235 511 379 312 86 88 88
1 1 1
Ceiling and Wall Mount Combination protocol. The Horn/Strobe shall be capable of CEILING and WALL mounting to a 4” x 4”x 1-1/2” back box. Signaling devices shall be ELECTRO
MECHANICAL
installed in all sleeping and non-sleeping areas as per plans and specifications. LOW 1 1 0 402 275 220 497 366 301 76 80 83
Horn NON-TEMP.
HIGH 1 0 1 419 294 235 511 379 312 87 88 88
Description: & 3000 Hz
LOW 1 0 0 402 275 220 497 366 301 77 81 83
AMSECO’s Ceiling and Wall mount Horn/Strobe is designed to Strobe
comply with the Americans with Disability Act (ADA) and meet UL Light Output Dispersion: @ ELECTRO HIGH 0 1 1 419 294 235 511 379 312 80 84 84

90 °
MECHANICAL *1
Standard 1971 requirements for emergency signaling devices WA 177cd. LOW 0 1 0 402 275 220 497 366 301 73 76 79
Surface Mount: using RBX-1 back box skirt and SPC-1 retrofit plate 90° LL TEMPORAL

G
for the hearing impaired. The SH24C-177 Horn/Strobe features

IN
HIGH 0 0 1 419 294 235 511 379 312 82 84 84

IL
a 177 candela intensity output. The Horn provides two different Single gang Double gang Octagon 3000 Hz

E
*2
Compound Compound LOW 0 0 0 402 275 220 497 366 301 74 77 79

C
field selectable tones, and a High / Low output setting that can be back box back box back box

°
°
Horn/Strobe 177cd.

90
90
90°

45°
achieved with the use of mini jumpers located on back of the unit. Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and

45°
FI
The round housing design offers a low profile appearance and is LI
STI N
4” square Private Modes only).

R
UL

G
A
OF C L IFOR

ULC FI FI

E
TE

MEA

NI
E

ST
E

A
back box R R

R
clearly labeled with “FIRE” lettering to be view from all angles.

ST

LL

FI

FI
E

E
T

A
E SH
FIR
E MAR

E
E

S
RV I C

SPC-1 Horn Only Current Draw Table:

FI R E
These appliances are polarized for connecting to supervised fire SPC-1 SPC-1
alarm circuits. The strobe is designed with a xenon flashtube and Features:
* 177 candela output.
FI R E FI R E
=1 =0 Average Current ( mA ) Sound Output
provides a candela intensity field selector switch for maximum 45° 45°

FI
performance. * ADA/NFPA/ANSI compliant. R
P P P DC ( dBA@DC)
E
PC3 PC2 PC1 FWR



The Ceiling mount Horn/Strobe series is available in red and * UL listed for Ceiling and Wall mounting under UL1971. 90° C C C

°
90
Pattern Tone Volume

90
* Designed for use in sleeping and non-sleeping areas. 0° 3 2 1 16V 24V 33V 16V 24V 33V 16V 24V 33V
white housing 24V DC models. The SH24C-177 can be RBX-1
synchronized by using the SMD10-3A (daisy chain) Sync * Screw terminal capacity up to 12 AWG. RBX-1 RBX-1 RBX-1 ELECTRO HIGH 1 1 1 34 44 49 33 40 45 86 88 88
Module to comply with NFPA recommendations concerning * Polarized strobes with wide listed voltage ranges using 90° MECHANICAL LOW 1 1 0 17 25 34 19 27 34 76 80 83

90 °
filtered DC or unfiltered FWR input voltage. NON-TEMP.

45°
photosensitive epilepsy when installing 2 or more visual 0°

45°
* Horn field selectable tones: HIGH 1 0 1 34 44 49 33 40 45 87 88 88
appliances within the field of view. The strobe signals are 3000 Hz
3000 Hz interrupted or Electro-mechanical Horn LOW 1 0 0 17 25 34 19 27 34 77 81 83
designed for sleeping and non-sleeping areas and are listed for Compound Compound only
indoor use, ceiling and wall mount, under UL 1971 Standard. Temporal or Non-temporal ELECTRO HIGH 0 1 1 34 44 49 33 40 45 80 84 84
High or Low dBA output MECHANICAL LOW 0 1 0 17 25 34 19 27 34 *1
73 76 79
* Meets ADA guidelines for minimum one flash per/sec (1Hz). TEMPORAL
* All models mount to 4” x 4” x 1-1/2” back box. Horn/Strobe Combination Wiring: Wired Without Audible Silence Feature: HIGH 0 0 1 34 44 49 33 40 45 82 84 84
Application: 3000 Hz *2
* 24 volt strobe models 177 candela intensity. Sync Module LOW 0 0 0 17 25 34 19 27 34 74 77 79
The SH24C-177 Ceiling Horn/Strobe Series is recommended
* Synchronization requires an AMSECO SMD10-3A Room Spacing for Ceiling-Mounted Visible Appliances Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
for use in areas such as: meeting rooms, schools, corridors, Using the Sync Modules: F.A.C.P. FI
To Next Device F.A.C.P. SMD10-3A FI
To Next Device or
(daisy chain) Sync Module. R
E
Signal R
E
Private Modes only).

R
apartments, office buildings, restaurants, hotels, and any other Minimum Light Output by Room Size. Signal or End-Of Line- IN OUT End-Of Line-

FI

E
FI

E
* RBX-1 back box skirt for surface mount (optional). The Sync module is designed to provide a synchronized temporal Circuit Circuit
_ _ _ _
application where effective audible and visual warning are
* The SPC-1 retrofit plate allows mounting to a variety of back pattern (code 3) tone, and synchronize the strobe flashes when used + _ Resistor
+ H+H + + Resistor

required by Federal, State, or local authority having jurisdiction. Maximum Maximum Room Size (ft.)
+ _
FI R E

boxes (optional). with AMSECO’s 177cd Strobe, and Horn/Strobe as well as the ability Ceiling
FI R E

Strobe Only Current Draw Table:


* Available in red or white housing. to silence the horn while maintaining the strobe flashes. The SMD10- Height (ft.) 20 X 20 30 X 30 40 X 40 50 X 50 + _
3A has the capability of connecting two style Y (class B) circuits or
Wiring Terminals: Horn Selectable Sound Output: one style Z (class A) circuit, and is rated for 3 amperes per circuit. 30 75cd. 75cd. 177cd. 177cd.
DC FWR
The SMD10-3A can be interconnected so that more than two alarm 20 30cd. 75cd. 110cd. 177cd. *The Sync module is rated for 3.0 amperes at 24 VDC. Current ( mA )
zones can be synchronized when connected using the SYNC 10 30cd. 30cd. 75cd. 110cd. 16V 24V 33V 16V 24V 33V
terminals. (Daisy chain connection). The Max number of Average 390 255 191 483 344 272
interconnected SMD10-3A modules is twenty (20). All input are Signals Wired for Independent Operation: Wired for Audible Silence Feature: Strobe only
Peak 596 438 386 859 816 708
polarized for compatibility with standard reverse polarity supervision of @ 177cd.
circuit wiring, when used with a Fire Alarm Control Panel (F.A.C.P.). Room Spacing for Wall-Mounted Visible Appliances In-Rush 460 476 508 788 828 716
FI
Minimum Light Output by room Size (Non-Sleeping) R
E
F.A.C.P. FI

R
E
To Next Device

FI
SMD10-3A

E
R

R
Strobe Signal Horn Signal

FI

E
Circuit Circuit or End-Of Line-
PC3 PC2 PC1 For a synchronization system, the maximum number of strobe lights Maximum One Strobe To Next Device or +
_ _ H+H
_ _ OUTPUT
INPUT _ Resistor
Two Strobes Four Strobes + + +
that can be connected to a listed Fire Alarm Control Panel 3Amp
FI R E

Room End-Of Line-Resistor


+ _ Dimensions: Inches (mm)
FI R E

per Room per Room per Room Strobe Horn _


Loop circuit is as follows: Size F.A.C.P. _ _ +
+ +
14 (30cd, 16~33VDC) or 10 (30cd, 16~33V FWR)
13 (75cd, 16~33VDC) or 8 (75cd, 16~33V FWR) 20¢X 20¢ 15 cd. NA NA
Temporal - Non-Temporal 30¢X 30¢ 30 cd. 15 cd. NA
Strobe
Signal
+
_
Electro Mech - 3000 Hz 11 (110cd, 16~33VDC) or 7 (110cd, 16~33V FWR) Circuit
High - Low The maximum wire impedance between any adjacent strobe light is 40¢X 40¢ 60 cd. 30 cd. 15 cd.
Ordering Information: To Next Device or
5.6 ohms. 50¢X 50¢ 95 cd. 60 cd. 30 cd. End-Of Line-Resistor + - + -
_
+

3-3/8 (85.7)
Model Input Strobe Sync Mounting Horn Flash Housing 60¢X 60¢ 135 cd. 95 cd. 30 cd.
Voltage Output Module Type Sound Rate Color Ordering Information: Horn
Number 70¢X 70¢ 185 cd. 95 cd. 60 cd. Signal +
(VDC) (Candela) Output (Times/min.) Circuit _
Model Input Maximum Average Mounting Color 80¢X 80¢ 240 cd. 135 cd. 60 cd.
SH24C-177R 24 177 SMD10-3A Ceiling/Wall Selectable 60 Red Number Voltage Load Current Back Box 90¢X 90¢ 305 cd. 185 cd. 95 cd.
SH24C-177W 24 177 SMD10-3A Ceiling/Wall Selectable 60 White (VDC) (Amps) (mA) 100¢X 100¢ 375 cd. 240 cd. 95 cd. WARNING:
The Horn/Strobe is listed for indoor use with a temperature operating range of 32°F ~ 120°F (0°C ~ 49°C ) * The Horn/Strobe must be used only on circuits with continuously operating voltage. DO NOT use strobe on coded or interrupted circuits in which
SMS1-3A 24 3 9 4"x4"x1-1/2" Red 110¢X 110¢ 455 cd. 240 cd. 135 cd. the applied voltage is interrupted ON and OFF as the strobe may fail to flash.
120¢X 120¢ 540 cd. 305 cd. 135 cd. * The applied voltage must be within its rated input voltage range. 1-13/32 (35)
SMD10-3A 24 3 9 4"x4"x1-1/2" Red
Specifications subject to change without notice.
130¢X 130¢ 635 cd. 375 cd. 185 cd. * Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits. 6-7/8 (174) 2-25/32 (70) 3-3/8 (85.7)
The total current draw from all devices connected to the sync module should not exceed
NA: Not allowable
Hochiki America Corporation 3.0A, and should only be connected to circuits that provide continuously applied voltage.
7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Hochiki America Corporatrion : SH24C-177
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 06/2003 Hochiki America Corporatrion : SH24C-177 Specifications subject to change without notice. Hochiki America Corporatrion : SH24C-177 Specifications subject to change without notice. Specifications subject to change without notice.
SH24C-3075110
Ceiling and Wall Mount
Select --A--HornStrobe Combination
Description:
AMSECO’s Ceiling and Wall mount is Select -A- - -HornStrobe
designed to comply with the Americans with Disability Act (ADA)
and meet UL Standard 1971 requirements for emergency
signaling devices for the hearing impaired. The SH24C-3075110
Select --A--HornStrobe features a unique candela intensity field
selector switch for alternating the candela to 30cd, 75cd or 110cd
intensity output. The Horn provides two different field selectable Horn/Strobe with Selectable 30cd, 75cd or 110cd.
tones, and a High / Low output setting that can be achieved with
the use of mini jumpers located on back of the unit. The round UL ULC
MEA
housing design offers a low profile appearance and is clearly
labeled with “FIRE” lettering to be view from all angles. These Features:
appliances are polarized for connecting to supervised fire alarm * Selectable Candela 30cd, 75cd or 110 candela output.
circuits. The strobe is designed with a xenon flashtube and * ADA/NFPA/ANSI compliant.
provides a candela intensity field selector switch for maximum * UL listed for Ceiling and Wall mounting under UL1971.
performance. The Ceiling/Wall mount Select -A-HornStrobe * Designed for use in non-sleeping areas.
series is available in red and white housing 24V DC models. The * Screw terminal capacity up to 12 AWG.
SH24C-3075110 can be synchronized by using the SMD10-3A * Polarized strobes with wide listed voltage ranges using filtered
(daisy ch ain) Sync Module to comply with NFPA DC or unfiltered FWR input voltage.
recommendations concerning photosensitive epilepsy when * Horn field selectable tones:
installing 2 or more visual appliances within the field of view. The 3000Hz interrupted or Electro-mechanical
strobe signals are designed for non-sleeping areas and are listed Temporal or Non-temporal
for indoor use, ceiling and wall mount, under UL 1971 Standard. High or Low dBA output
* Meets ADA guidelines for minimum one flash per/sec (1 Hz).
* All models mount to 4” x 4” x 1-1/2” back box.
* Synchronization requires an AMSECO SMD10-3A
Application:
(daisy chain) Sync Module.
The SH24C-3075110 Ceiling Horn/Strobe Series is
* RBX-1 back box skirt for surface mount (optional).
recommended for use in areas such as: meeting rooms, schools,
* The SPC-1 retrofit plate allows mounting to a variety of back
corridors, apartments, office buildings, restaurants, hotels, and
boxes (optional).
any other application where effective audible and visual warning
* Available in red or white housing.
are required by Federal, State, or local authority having
jurisdiction. Horn Selectable Sound Output:

Wiring Terminals:

PC3 PC2 PC1

Temporal - Non-Temporal
Electro Mech - 3000 Hz
High - Low
Ordering Information:

Model Input Strobe Sync Mounting Horn Flash Housing


Number Voltage Candela Module Type Sound Rate Color
(VDC) (Selectable) Output (Times/min.)
SH24C-3075110R 24 30, 75, 110 SMD10-3A Ceiling/Wall Selectable 60 Red
SH24C-3075110W 24 30, 75, 110 SMD10-3A Ceiling/Wall Selectable 60 White
The Horn/Strobe is listed for indoor use with a temperature operating range of 32F ~ 120F (0C °~ 49C ° )
Specifications subject to change without notice.

Hochiki America Corporation


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 06/2003
Mounting: using SPC-1 retrofit plate Single gang
Double gang Octagon
back box back box
back box
4” square
back box
SPC-1 SPC-1 SPC-1

Surface Mount: using RBX-1 back box skirt and SPC-1 retrofit plate
Single gang Double gang Octagon
back box back box back box

4” square
back box
SPC-1 SPC-1 SPC-1

RBX-1
RBX-1 RBX-1 RBX-1

Room Spacing for Wall-Mounted Visible Appliances Minimum Light Output by room Size (Non-Sleeping)
Maximum One Strobe Two Strobes Four Strobes Maximum One Strobe Two Strobes Four Strobes
Room per Room per Room per Room Room per Room per Room per Room
Size Size
20¢X 20¢ 15 cd. NA NA 80¢X 80¢ 240 cd. 135 cd. 60 cd.
30¢X 30¢ 30 cd. 15 cd. NA 90¢X 90¢ 305 cd. 185 cd. 95 cd.
40¢X 40¢ 60 cd. 30 cd. 15 cd. 100¢X 100¢ 375 cd. 240 cd. 95 cd.
50¢X 50¢ 95 cd. 60 cd. 30 cd. 110¢X 110¢ 455 cd. 240 cd. 135 cd.
60¢X 60¢ 135 cd. 95 cd. 30 cd. 120¢X 120¢ 540 cd. 305 cd. 135 cd.
70¢X 70¢ 185 cd. 95 cd. 60 cd. 130¢X 130¢ 635 cd. 375 cd. 185 cd.
NA: Not allowable
Room Spacing for Ceiling-Mounted Vis ible Appliances
Minimum Light Output by Room Size.
Maximum Maximum Room Size (ft.)
Ceiling
Height (ft.) 20 X 20 30 X 30 40 X 40 50 X 50
30 75cd. 75cd. 177cd. 177cd.
20 30cd. 75cd. 110cd. 177cd.
10 30cd. 30cd. 75cd. 110cd.

Dimensions: inches (mm)


3-3/8 (85.7)

1-13/32 (35)
6-7/8 (174) 2-25/32 (70) 3-3/8 (85.7)

Hochiki America Corporatrion : SH24C-3075110 Specifications subject to change without notice.


Engineering Specifications:
The audible and visual alarm indicating appliance shall be AMSECO model SH24C-3075110 or equivalent device. The Strobe shall be
listed under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The
candela output shall be field selectable, having three (3) settings 30cd, 75cd and 110cd output. All settings shall be UL1971 listed for both
ceiling and wall mount applications. The Horn shall provide two different field selectable tones, and a High and Low field selectable sound
output setting. The signaling Horn/Strobe shall operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered
supply. The signaling strobe shall be designed to produce a signal flash of one flash per second with continuously applied minimum
voltage. When strobe synchronization is required, the horn/strobe shall be compatible with the AMSECO SMS1-3A or SMD10-3A (daisy
chain) or other source of AMSECO sync protocol. The Horn/Strobe shall be capable of CEILING and WALL mount to a variety of back
boxes using the AMSECO SPC-1 retrofit back plate.
Signaling devices shall be installed in all non-sleeping areas as per plans and specifications.

Light Output Dispersion:

90°
G
IN

90°
IL
E
C

°
°

90
90

Compound Compound
FI 90°
45 °

E FI

45 °
R
R

R
FI

E
FI
E
R
R
FI

FI R E
FI R E

FI R E

45 ° 45 °
°

FI
°
90

90

R
E

90°


90°

90°
45 °
45 °

Compound Compound

Horn/Strobe Combination Wiring: Wired Without Audible Silence Feature:


Sync Module

F.A.C.P. FI F.A.C.P. SMD10-3A FI


E To Next Device E To Next Device or
R Signal R
R

Signal or End-Of Line- IN OUT End-Of Line-


FI

E
FI

Circuit
_ Resistor
Circuit
_ _ _ _ Resistor
+ + H+H + +
+ _
FI R E

FI R E

+ _

*The Sync module is rated for 3.0 amperes at 24 VDC.

Signals Wired for Independent Operation: Wired for Audible Silence Feature:

Sync Module
FI
E FI
R F.A.C.P.
R

E
To Next Device
FI

SMD10-3A
E

R
R

Strobe Signal Horn Signal


FI

Circuit Circuit or End-Of Line-


To Next Device or +
_ _ H+H
_ _ OUTPUT
INPUT _ Resistor
FI R E + + +
End-Of Line-Resistor
+ _
FI R E

Strobe Horn _
F.A.C.P. _ _ +
+ +
Strobe
Signal
+
_
Circuit

To Next Device or
End-Of Line-Resistor + - + -
_
+
Horn
Signal +
_
Circuit

WARNING:
* The Horn/Strobe must be used only on circuits with continuously operating voltage. DO NOT use strobe on coded or interrupted circuits in which
the applied voltage is interrupted ON and OFF as the strobe may fail to flash.
* The applied voltage must be within its rated input voltage range.
* Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits.

Hochiki America Corporatrion : SH24C-3075110 Specifications subject to change without notice.


Horn/Strobe Current Draw Table:
=1 =0
Average Current (mA) Sound Output
PC3 P P P ( dBA @ DC )
PC2 PC1 DC FWR
Pattern C C C
Tone Volume 16V 24V 33V 16V 24V 33V 16V 24V 33V
3 2 1
Electro High 1 1 1 160 129 116 203 171 153 86 88 88
Horn NON-TEMP
Mechanical Low 1 1 0 138 110 101 189 158 142 76 80 83
& High 1 0 1 160 129 116 203 171 153 87 88 88
3000 Hz
Strobe Low 1 0 0 138 110 101 189 158 142 77 81 83
@ Electro High 0 1 1 160 129 116 203 171 153 80 84 84
30cd Mechanical Low 0 1 0 138 110 101 189 158 142 *1
73 76 79
TEMPORAL
High 0 0 1 160 129 116 203 171 153 82 84 84
3000 Hz *2
Low 0 0 0 138 110 101 189 158 142 74 77 79
Electro High 1 1 1 218 170 148 276 221 195 86 88 88
Mechanical Low 1 1 0 201 151 133 262 208 184 76 80 83
Horn NON-TEMP
High 1 1 218 170 148 221 195 88 88
0 276 87
& 3000 Hz
Low 201 151 208
1 0 0 133 262 184 77 81 83
Strobe High 170 221
Electro 0 1 1 218 148 276 195 80 84 84
@ Mechanical Low *1
0 1 0 201 151 133 262 208 184 73 76 79
75cd TEMPORAL
High 0 0 1 218 170 148 276 221 195 82 84 84
3000 Hz *2
Low 0 0 0 201 151 133 262 208 184 74 77 79
Electro High 1 1 1 273 207 173 348 270 232 86 88 88
Mechanical Low 1 1 0 256 188 158 334 257 221 76 80 83
Horn NON-TEMP High 1 0 1 273 207 173 348 270 232 87 88 88
& 3000 Hz
Low 1 0 0 256 188 158 334 257 221 77 81 83
Strobe High 0 1 1 273 207 173 348 270 232 80 84 84
Electro
@ Mechanical Low 0 1 0 188 158 257 221 *1
76 79
256 334 73
110cd TEMPORAL High 0 1 207 173 270 232 84 84
0 273 348 82
3000 Hz *2
Low 0 0 0 256 188 158 334 257 221 74 77 79
Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
Private Modes only).

Horn Only Current Draw and Sound Output Table:


=1 =0
Average Current (mA) Sound Output
PC3 P P P ( dBA @ DC )
PC2 PC1 DC FWR
Pattern C C C
Tone Volume 16V 24V 33V 16V 24V 33V 16V 24V 33V
3 2 1
Electro High 1 1 1 34 44 49 33 40 45 86 88 88
Mechanical Low 1 1 0 17 25 34 19 27 34 76 80 83
NON-TEMP High 1 0 1 34 44 49 33 40 45 87 88 88
Horn 3000 Hz
Low 1 0 0 17 25 34 19 27 34 77 81 83
Only High 0 1 1 34 44 49 33 40 45 80 84 84
Electro
Mechanical *1
Low 0 1 0 17 25 34 19 27 34 73 76 79
TEMPORAL High 0 0 1 44 49 40 45 84 84
34 33 82
3000 Hz *2
Low 0 0 0 17 25 34 19 27 34 74 77 79
Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
Private Modes only).

Strobe Only Current Draw Table:


DC FWR
Current (mA)
16V 24V 33V 16V 24V 33V
Average 126 90 72 175 136 113
@ 30cd Peak 225 218 167 421 355 341
Strobe In-Rush 254 298 338 402 418 458
Only Average 189 131 104 248 186 155
@ 75cd Peak 304 222 212 562 464 454
In-Rush 306 342 374 540 478 498
Average 244 168 129 320 235 192
@ 110cd Peak 418 288 208 680 572 532
In-Rush 386 398 430 644 580 548

Hochiki America Corporatrion : SH24C-3075110 Specifications subject to change without notice.


SH24W-153075 Patented

Select -A- Horn /Strobe Combination


Description:
AMSECO’s Select-A-Horn/Strobe Series is designed to
comply with the Americans with Disability Act (ADA) and meet
UL Standard 1971 requirements for emergency signaling
devices for the hearing impaired. The SH24W series Select-
A-Horn/Strobe features a unique candela intensity field
selector switch for alternating the candela output 15cd to 30cd
(75cd on axis). The Horn provides two different field
selectable tones, and a High / Low output setting that can be Horn/Strobe with Universal Mounting Plate Included
achieved with the use of mini jumpers located on back of the
unit. The strobe housing is clearly labeled with vertical “FIRE” TI
IS N

UL

G
L
O F C A L I FO

ULC TE R

MEA

A
FM

NI
ST

A
lettering and is polarized for connecting to supervised fire

ST

LL
TE

A
FIR SH
E MA R

E
S
E

alarm circuits. The strobe is designed with a xenon flashtube APPROVED RVI C

and provides a candela intensity field selector switch for Features:


maximum performance.
* Designed to meet or exceed NFPA/ANSI Standards and ADA
The Select-A-Horn/Strobe series is available in red and white
Accessibility Guidelines.
housing 24V DC models. The SH24W-153075 can be
* UL listed for wall mounting.
synchronized by using the SMD10-3A Sync Module to comply
* Screw terminal capacity up to 12 AWG.
with NFPA recommendations concerning photosensitive
* Universal mounting plate included with each unit.
epilepsy when installing 2 or more visual appliances within the
* 24V DC strobe with two field selectable settings 15cd or 30cd.
field of view. The strobe signals are listed for indoor use, wall
* Polarized strobes with wide listed voltage ranges using filtered
mount, under UL 1971 Standard.
DC or unfiltered FWR input voltage.
* Horn field selectable tones:
3000 Hz interrupted or Electro-mechanical
Application: Temporal or Non-temporal
The SH24W-153075 Horn/Strobe Series is recommended High or Low dBA output
for use in areas such as: meeting rooms, schools, corridors, * Meets ADA guidelines for minimum one flash per/sec (1Hz).
apartments, office buildings, restaurants, hotels, and any * All models mount to 4” square, single gang, double gang, or
other application where effective audible and visual warning octagonal back box.
are required by Federal, State, or local authority having * 24 volt strobe models 15 or 30 candela intensity.
jurisdiction. * Tamper-proof candela selector switch.
* Synchronization requires an AMSECO SMD10-3A Sync Module.
* Available in red or white housing.
Strobe Selectable Candela Output:

15 Horn Selectable Sound Output:


cd
30
cd
F
I
R 15
E PC3 PC2 PC1

30

Tamper Proof Temporal - Non-Temporal


Electro Mech - 3000 Hz
High - Low

Ordering Information:

Model Input Selectable Sync Mounting Horn Wiring Housing


Number Voltage Strobe Output Module Type Sound Type Color
(VDC) (Candela) Output
SH24W-153075R 24 15 or 30 SMD10-3A Wall Only Selectable Terminals Red
SH24W-153075W 24 15 or 30 SMD10-3A Wall Only Selectable Terminals White
The Horn/Strobe is listed for indoor use with a temperature operating range of 32°F ~ 120°F (0°C ~ 49°C )
Specifications subject to change without notice.

Hochiki America Corporation


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 06/2003
Mounting Options:
Strobe with Universal mounting Strobe with Universal mounting Strobe with Universal mounting Strobe with Universal mounting
plate and single gang box. plate and 4” square back box. plate and double gang box. plate and surface mount back box.

4” x 4” x 1-1/2” 4” x 4” x 1-1/2”
2” back box
back box back box
F
4BX-1
F F
I I I
F 4SP-M Surface Mount
I
R Universal Mounting Plate R Universal Mounting Plate R Universal Mounting Plate R Mounting back box
E E E E
Plate
Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe

Dimensions: Inches (mm)


5 (127) 2 1/4(56.9) 3 3/8(85.7)
1 13/16(46)

3 9/32(83.5)
3 3/8(85.7)

3 9/32(83.5)
5 (127)

Using the Sync Module:


The Sync module is designed to provide a synchronized temporal pattern Dimensions: Inch (mm)
(code3) tone, and synchronize the strobe flashes when used with AMSECO’s 4.33 (110)
line of Select-A-Strobe and Select-A-Horn/Strobe series as well as the ability
3.374 (85.7)
to silence the horn while maintaining the strobe flashes. 0.2 (5)
The SMD10-3A has the capability of connecting two style Y (class B) circuits or
one style Z (class A) circuit and is rated for 3 amperes per circuit.
The SMD10-3A can be interconnected so that more than two alarm zones can
be synchronized when connected using the SYNC terminals (daisy chain
3.374 (85.7)

connection).The maximum number of interconnected SMD10-3A modules is


4.33 (110)

twenty (20). All inputs are polarized for compatibility with standard reverse
polarity supervision of circuit wiring, when used with Fire Alarm Control Panel
(F.A.C.P).

Ordering Information:
Model Input Maximum Average Mounting Color
Number Voltage Load Current Back Box
(VDC) (Amps) (mA)
SMD10-3A 24 3 9 4"x4"x1-1/2" Red
The total current draw from all devices connected to the SMD10-3A should not exceed 3.0A. Mounting:
The SMD10-3A should only be connected to circuits that provide continuously applied voltage.

SMD10-3A Current Draw Table: Electrical Back box


4”x4”x1-1/2”

Voltage Average Peak In-Rush

DC FWR DC FWR DC FWR

16V 7mA 7mA 30mA 55mA 40mA 57mA


24V 9mA 9mA 32mA 62mA 52mA 75mA
33V 11mA 11mA 34mA 68mA 74mA 99mA
The SMD10-3A module is listed for indoor use with a temperature operating SMD10-3A
range of 32° F ~ 120° F ( 0° C ~ 49° C ).

Hochiki America Corporatrion : SH24W-153075 Specifications subject to change without notice.


Engineering Specifications:
The audible and visual alarm indicating appliance shall be AMSECO model SH24W-153075 or equivalent device. The Strobe shall be
listed under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The
candela output shall be field selectable, having a dual setting of 15cd or 30cd output. The Horn shall provide two different field
selectable tones and a High and Low field selectable sound output setting. The signaling Horn/Strobe shall operate on 24VDC from a
non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be designed to produce a signal
flash of one flash per second with continuously applied minimum voltage. The Horn/Strobe shall be capable of WALL mounting to a
universal backbox. Visual signaling devices shall be mounted 80” above the highest floor point or 6” below ceiling; (whichever is lowest)
and are to be installed as per plans and specifications.

Light Output Distribution / Horizontal and Vertical Dispersion:


UL Required Minimum Light Output (cd) 45
Wall Mount Horizontal Wall Mount Vertical WALL WALL
Degrees @15cd @30cd @15cd @30cd 90 90
0 75.00 75.00 75.00 75.00
5 ~ 25 13.50 27.00 13.50 27.00
30 11.25 22.50 13.50 27.00
35 11.25 22.50 9.75 19.50
45
40 11.25 22.50 6.90 13.80
Compound 45
45 11.25 22.50 5.10 10.20 90
50 8.25 16.50 4.05 8.10 90
55 6.75 13.50 3.30 6.60
60 6.00 12.00 2.70 5.40 0
65 5.25 10.50 2.40 4.50 45 0
70 5.25 10.50 2.25 4.50
75 4.50 9.00 1.95 3.90 Compound 45 90
80 4.50 9.00 1.80 3.60
85 ~ 90 3.75 7.50 1.80 3.60
Compound 45 3.60 7.20

Sound Output Dispersion (dB)


Degrees Wall Mount Horizontal Wall Mount Vertical Wired Without Audible Silence Feature:
+90 -6 dB -3 dB
+60 -2 dB -2 dB
+30 -1 dB -1 dB F.A.C.P. SMD10-3A
0 0 dB 0 dB Signal To Next Device or
IN
-30 -1 dB -3 dB Circuit_ _ _ _
OUT F
I
End-Of Line-Resistor
-60 -2 dB -5 dB + H+ H + + R
E

+ _
-90 -6 dB -6 dB

Horn/Strobe Combination Wiring:

Control To Next Device or


Panel F
End-Of Line-Resistor
+ _ I
R
E

+ _

*The Sync module is rated for 3.0 amperes at 24 VDC.

Wired for Audible Silence Feature:


Signals Wired for Independent Operation:

F.A.C.P. F.A.C.P.
Strobe Signal Horn Signal
SMD10-3A F
To Next Device or
I
Circuit Circuit R
F
I
+
_ _ H+H
_ IN_ OUT
_ E End-Of Line-Resistor
R + + +
F.A.C.P. E To Next Device or
Strobe Signal End-Of Line-Resistor _
Circuit
_ Strobe Horn _ +
+ _ _ +
+ +

F.A.C.P. To Next Device or


Horn Signal End-Of Line-Resistor
Circuit
_ _
+ +

WARNING:
* Strobes must be used only on circuits with continuously operating voltage. DO NOT use strobe on coded or interrupted
Circuits in which the applied voltage is interrupted ON and OFF as the strobe may fail to flash.
* The applied voltage must be within its rated input voltage range.
* Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits.

Hochiki America Corporatrion : SH24W-153075 Specifications subject to change without notice.


Horn/Strobe Current Draw Table:
=1 =0
Average Current (mA) Sound Output
PC3 P P P ( dBA @ DC )
PC2 PC1 DC FWR
Pattern C C C
Tone Volume 16V 24V 33V 16V 24V 33V 16V 24V 33V
3 2 1
Electro High 1 1 1 112 98 96 145 115 142 85 87 88
Horn NON-TEMP
Mechanical Low 1 1 0 109 91 83 142 110 95 75 78 81
& High 1 0 1 118 111 108 153 128 119 85 88 88
3000 Hz
Strobe Low 1 0 0 106 85 83 139 105 89 75 78 81
@ Electro High 0 1 1 112 98 96 145 115 142 81 83 84
15cd Mechanical Low 0 1 0 109 91 83 142 110 95 *1
71 75 77
TEMPORAL
High 0 0 1 118 111 108 153 128 119 80 83 84
3000 Hz *2
Low 0 0 0 106 85 83 139 105 89 71 75 77
Electro High 1 1 1 158 130 133 207 157 168 85 87 88
Mechanical Low 1 1 0 155 123 108 204 152 121 75 78 81
Horn NON-TEMP High 1 164 143 146 170 145 88 88
1 0 215 85
& 3000 Hz
Low 152 117 147
1 0 0 108 201 115 75 78 81
Strobe High
Electro 0 1 1 158 130 133 207 157 168 81 83 84
@ Mechanical Low *1
0 1 0 155 123 108 204 152 121 71 75 77
30cd TEMPORAL
High 0 0 1 164 143 146 215 170 145 80 83 84
3000 Hz *2
Low 0 0 0 152 117 108 201 147 115 71 75 77
Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
Private Modes only).

Horn Only Current Draw and Sound Output Table:


=1 =0
Average Current (mA) Sound Output
PC3 P P P ( dBA @ DC )
PC2 PC1 DC FWR
Pattern C C C
Tone Volume 16V 24V 33V 16V 24V 33V 16V 24V 33V
3 2 1
Electro High 1 1 1 28 41 57 30 41 91 85 87 88
Mechanical Low 1 1 0 25 34 42 27 36 44 75 78 81
NON-TEMP High 1 0 1 34 54 70 38 54 68 85 88 88
Horn 3000 Hz
Low 1 0 0 22 28 36 24 31 38 75 78 81
Only High 0 1 1 28 41 57 30 41 91 81 83 84
Electro
*1
Mechanical Low 0 1 0 25 34 42 27 36 44 71 75 77
TEMPORAL High 0 0 1 54 70 54 68 83 84
34 38 80
3000 Hz *2
Low 0 0 0 22 28 36 24 31 38 71 75 77
Note: The low volume Temporal setting of *1 & *2 at 16V FWR/DC are not suitable to use for Fire Alarm Public Mode (Suitable for General and
Private Modes only).

Strobe Only Current Draw Table:


DC FWR
Current (mA)
16V 24V 33V 16V 24V 33V
Average 89 64 50 125 94 81
Strobe @ 30cd Peak 127 103 87 269 229 210
Only In-Rush 127 103 119 269 229 210
Average 135 96 75 187 136 107
@ 75cd Peak 170 134 119 377 306 269
In-Rush 170 135 223 377 306 269

Room Spacing for Wall-Mounted Visible Appliances Minimum Light Output by room Size (Non-Sleeping)
Maximum One Strobe Four Strobes Maximum One Strobe Two Strobes Four Strobes
Two Strobes
Room per Room per Room Room per Room per Room
per Room per Room
Size Size
20¢X 20¢ 15 cd. NA NA 80¢X 80¢ 240 cd. 135 cd. 60 cd.
30¢X 30¢ 30 cd. 15 cd. NA 90¢X 90¢ 305 cd. 185 cd. 95 cd.
40¢X 40¢ 60 cd. 30 cd. 15 cd. 100¢X 100¢ 375 cd. 240 cd. 95 cd.
50¢X 50¢ 95 cd. 60 cd. 30 cd. 110¢X 110¢ 455 cd. 240 cd. 135 cd.
60¢X 60¢ 135 cd. 95 cd. 30 cd. 120¢X 120¢ 540 cd. 305 cd. 135 cd.
70¢X 70¢ 185 cd. 95 cd. 60 cd. 130¢X 130¢ 635 cd. 375 cd. 185 cd.
NA: Not allowable

Hochiki America Corporatrion : SH24W-153075 Specifications subject to change without notice.


SH24W-75110 Patented
TM
Select -A- Horn /Strobe Combination
Description:
AMSECO’s Select-A-Horn/Strobe Series is designed to
comply with the Americans with Disability Act (ADA) and
meet UL Standard 1971 requirements for emergency
signaling devices for the hearing impaired. The SH24W
series Select-A-Horn/Strobe features a unique candela
intensity field selector switch for alternating the candela
output 75cd to 110cd. The Horn provides two different field
selectable tones, and a High / Low output setting that can Horn/Strobe with Universal Mounting Plate Included
be achieved with the use of mini jumpers located on back of
the unit. The strobe housing is clearly labeled with vertical STI N
LI F CA LI

UL

G
ULC
O FO
TE R

MEA

A
FM

NI
ST

A
“FIRE” lettering and is polarized for connecting to

ST

LL
T

A
A DA
E SH
F IR
E MAR

E
E

S
RV I C
supervised fire alarm circuits. The strobe is designed with a APPROVED

xenon flashtube and provides a candela intensity field


selector switch for maximum performance. Features:
The Select-A-Horn/Strobe series is available in red and * Designed to meet or exceed NFPA/ANSI Standards and ADA
white housing 24V DC models. The SH24W-75110 can be Accessibility Guidelines.
synchronized by using the SMS1-3A Sync Module to * UL listed for wall mounting.
comply with NFPA recommendations concerning * Screw terminal capacity up to 12 AWG.
photosensitive epilepsy when installing 2 or more visual * Universal mounting plate included with each unit.
appliances within the field of view. The strobe signals are * 24V DC strobe with field selectable settings 75cd or 110cd.
listed for indoor use, wall mount, under UL 1971 Standard. * Polarized strobes with wide listed voltage ranges using filtered
DC or unfiltered FWR input voltage.
* Horn field selectable tones:
Application: 3000 Hz interrupted or Electro-mechanical
The SH24W-75110 Horn/Strobe Series is recommended for Temporal or Non-temporal
use in areas such as: meeting rooms, schools, corridors, High or Low dBA output
apartments, office buildings, restaurants, hotels, and any * Meets ADA guidelines for minimum one flash per/sec (1Hz).
other application where effective audible and visual warning * All models mount to 4” square, single gang, double gang, or.
are required by Federal, State, or local authority having octagonal back box.
jurisdiction. * 24 volt strobe models 75 or 110 candela intensity.
* Tamper-proof candela selector switch.
* Synchronization requires an AMSECO SMS1-3A Sync Module.
Strobe Selectable Candela Output: * Available in red or white housing.

75 Horn Selectable Sound Output:


cd
11
0cd
F
I
R 75
E PC3 PC2 PC1

11
0

Tamper Proof Temporal - Non-Temporal


Electro Mech - 3000 Hz
High - Low

Ordering Information:

Model Input Selectable Sync Mounting Horn Wiring Housing


Number Voltage Strobe Output Module Type Sound Type Color
(VDC) (Candela) Output
SH24W-75110R 24 75 or 110 SMS1-3A Wall Only Selectable Terminals Red
SH24W-75110W 24 75 or 110 SMS1-3A Wall Only Selectable Terminals White

Specifications subject to change without notice.

Hochiki America Corporation


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 06/2003
Engineering Specifications:
The audible and visual alarm indicating appliance shall be AMSECO model SH24W-75110 or equivalent device. The Strobe shall
be listed under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service.
The candela output shall be field selectable, having a dual setting of 75cd or 110cd output. The Horn shall provide two different
field selectable tones, and a High and Low field selectable sound output setting. The signaling Horn/Strobe shall operate on
24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be designed to
produce a signal flash of one flash per second with continuously applied minimum voltage. The Horn/Strobe shall be capable of
WALL mounting to a universal backbox. Visual signaling devices shall be mounted 80” above the highest floor point or 6” below
ceiling; (whichever is lowest) and are to be installed as per plans and specifications.

Light Output Distribution / Horizontal and Vertical Dispersion:


UL Required Minimum Light Output (cd)
45
Wall Mount Horizontal Wall Mount Vertical WALL
Degrees @75cd @110cd @75cd @110cd
0 75.00 110.00 75.00 110.00 90
5 ~ 25 67.50 99.00 67.50 99.00
30 56.25 82.50 67.50 99.00
35 56.25 82.50 48.75 71.50 45
40 56.25 82.50 34.50 50.60
45 56.25 82.50 25.50 37.40 Compound 45
50 41.25 60.50 20.25 29.70 90
55 33.75 49.50 16.50 24.20
60 30.00 44.00 13.50 19.80 0
65 26.25 38.50 12.00 17.60 45
70 26.25 38.50 11.25 16.50
75 22.50 33.00 9.75 14.30
80 22.50 33.00 9.00 13.20 Compound 45
85 ~ 90 18.75 27.50 9.00 13.20 WALL
Compound 45 18.00 26.40 90

Sound Output Dispersion (dB)


Degrees Wall Mount Horizontal Wall Mount Vertical
+90 -6 dB -3 dB 90
+60 -2 dB -2 dB
+30 -1 dB -1 dB
0 0 dB 0 dB 0
-30 -1 dB -3 dB
-60 -2 dB -5 dB 90
-90 -6 dB -6 dB

Horn/Strobe Combination Wiring: Wired Without Audible Silence Feature:

Control To Next Device or F.A.C.P. SMS1-3A


Signal To Next Device or
Panel End-Of Line-Resistor Circuit_ _ IN_ F End-Of Line-Resistor
_
F
+ _
OUT I

+
I
R
E
H+H + + R
E

+ _
+ _

*The Sync module is rated for 3.0 amperes at 24 VDC.

Signals Wired for Independent Operation: Wired for Audible Silence Feature:

F
I
R F.A.C.P. F.A.C.P.
F.A.C.P. E To Next Device or Strobe Signal Horn Signal
SMS1-3A F
To Next Device or
I
Strobe Signal End-Of Line-Resistor
Circuit Circuit R
Circuit
_ Strobe Horn _ +
_ _ H+H
_ IN _ OUT
_ E End-Of Line-Resistor
+ _ _ + + + +
+ +
+ _

F.A.C.P. To Next Device or


Horn Signal End-Of Line-Resistor
Circuit
_ _
+ +

WARNING:
* Horn/Strobe must be used only on circuits with continuously operating voltage. DO NOT use strobe on coded or interrupted
circuits in which the applied voltage is interrupted ON and OFF as the strobe may fail to flash.
* The applied voltage must be within its rated input voltage range.
* Fuse ratings on signaling circuits must handle peak currents from all devices connected to those circuits.

Hochiki America Corporatrion : SH24W-75110 Specifications subject to change without notice.


Horn/Strobe Current Draw Table:

P P P Average Current (mA) Sound Output


PC3 PC2 PC1 ( dBA @ DC )
C C C DC FWR
Pattern Tone Volume 3 2 1
16V 24V 33V 16V 24V 33V 16V 24V 33V
Electro High 1 1 1 160 125 115 212 159 145 85 87 88
Mechanical Low 1 1 0 148 112 102 199 144 120 75 78 81
NON-TEMP
High 1 0 1 160 125 115 212 159 145 85 88 88
3000 Hz
@ Low 1 0 0 148 112 102 199 144 120 75 78 81
75cd Electro High 0 1 1 160 125 115 212 159 145 81 83 84
Mechanical Low 0 1 0 148 112 102 199 144 120 71 75 77
TEMPORAL
High 0 0 1 160 125 115 212 159 145 80 83 84
3000 Hz
Low 0 0 0 148 112 102 199 144 120 71 75 77
Electro High 1 1 1 212 157 141 277 205 173 85 87 88
Mechanical Low 1 1 0 200 144 128 264 190 148 75 78 81
NON-TEMP
High 1 0 1 212 157 141 277 205 173 85 88 88
@ 3000 Hz
Low 1 0 0 200 144 128 264 190 148 75 78 81
110cd Electro High 0 1 1 212 157 141 277 205 173 81 83 84
Mechanical Low 0 1 0 200 144 128 264 190 148 71 75 77
TEMPORAL High 0 0 1 212 157 141 277 205 173 80 83 84
3000 Hz
Low 0 0 0 200 144 128 264 190 148 71 75 77
Electro High 1 1 1 27 35 52 36 45 64 85 87 88
Mechanical Low 1 1 0 15 22 39 23 30 39 75 78 81
NON-TEMP High 1 35 45
1 0 27 52 36 64 85 88 88
Horn 3000 Hz
Low 1 0 0 15 22 39 23 30 39 75 78 81
Only Electro High 0 1 1 27 35 52 36 45 64 81 83 84
Mechanical Low 0 1 0 15 22 39 23 30 39 71 75 77
TEMPORAL High 0 0 1 35 52 45 64 83 84
27 36 80
3000 Hz
Low 0 0 0 15 22 39 23 30 39 71 75 77

Strobe Only Current Draw Table:

Average Current (mA) Peak Current (mA) In-Rush Current (mA)


24 volt models 24 volt models 24 volt models
16V 24V 33V 16V 24V 33V 16V 24V 33V
Candela DC FWR DC FWR DC FWR Candela DC FWR DC FWR DC FWR Candela DC FWR DC FWR DC FWR
75 138 186 97 134 75 111 75 163 362 137 286 112 248 75 163 362 137 286 121 248
110 190 251 129 180 98 139 110 203 442 163 366 131 307 110 203 442 163 366 131 307

The SH24W-75110 series horn/strobe is listed for indoor use with a temperature operating range of 32 ° F ~ 120° F ( 0° C ~ 49° C ).

Dimensions: Inches (mm) 3 3/8(85.7)


5(127) 2 1/4(56.9)
1 13/16(46)
3 9/32(83.5)
3 9/32(83.5)
3 3/8(85.7)
5(127)

Mounting Options:
Horn/Strobe with Universal mounting Horn/Strobe with Universal mounting Horn/Strobe with Universal mounting Horn/Strobe with Universal mounting
plate and single gang box. plate and 4” square back box. plate and double gang box. plate and surface mount back box.

4” x 4” x 1-1/2” 4” x 4” x 1-1/2”
2” backbox
backbox backbox
F F
4BX-1
F F
I I I I Surface Mount
R Universal Mounting Plate R Universal Mounting Plate R Universal Mounting Plate R back box
E E E E 4SP-M
Mounting
Horn/Strobe Horn/Strobe Horn/Strobe Horn/Strobe Plate

Hochiki America Corporatrion : SH24W-75110 Specifications subject to change without notice.


SMS1-3A
Sync Module
When used with the SH24W Horn/Strobe Series the SMS1-3A
provides synchronized temporal pattern and a synchronized
strobe flash while using a single pair of wires on a single class
"A" circuit.
SMS1-3A Sync Module

I STI N
L F CALI

UL

G
ULC
O FO
TE R

MEA

A
FM

N
ST

IA
ST

LL
TE

A
FIR SH
E MA R

E
S
E
APPROVED RVI C

Model Number Input Maximum Average Mounting Color


Voltage Load Current Back Box
(VDC) (Amps) (mA)
SMS1-3A 24 3 9 4"x4"x1-1/2" Red

* The total current draw from all devices connected to the SMS1-3A should not exceed 3.0A.
**The SMS1-3A should only be connected to circuits that provide continuously applied voltage.

SMS1-3A Current Draw Table:

Voltage Average Peak In-Rush

DC FWR DC FWR DC FWR

20V 8mA 8mA 31mA 57mA 44mA 62mA


24V 9mA 9mA 32mA 62mA 52mA 75mA
30V 10mA 10mA 33mA 66mA 70mA 94mA

The SMS1-3A module is listed for indoor use with a temperature


operating range of 32 F ~ 120 F ( 0 C ~ 49 C ).

Mounting: Dimensions: Inch (mm)


4.33
Electrical Back box
(110)

3.374 0.2
(85.7)
(5)
(85.7)
(110)
4.33

3.374

4”x4”X1-1/2”

SMS1-3A

Hochiki America Corporatrion : SH24W-75110 Specifications subject to change without notice.


SL24C-177
Ceiling and Wall Mount Strobe
Description:
AMSECO’s Ceiling and Wall mount strobe is designed to comply
with the Americans with Disability Act (ADA) and meet UL
Standard 1971 requirements for emergency signaling devices
for the hearing impaired. The SL24C-177 strobe round housing
design offers a low profile appearance and is clearly labeled with
“FIRE” lettering to be view from all angles. These appliances are
polarized for connecting to supervised fire alarm circuits. The
strobe is designed with a xenon flashtube and provides a 177 Strobe 177cd.
candela intensity output for maximum performance. STI N
LI

The Ceiling mount strobe series is available in red and white UL

G
OF CA L IFOR

ULC TE

MEA

NI
ST

A
ST

LL
housing 24V DC models. T

A
E SH
FI R
E MAR

E
E

S
RV I C

The SL24C-177 can be synchronized by using the SMD10-3A


Sync Module to comply with NFPA recommendations
concerning photosensitive epilepsy when installing 2 or more Features:
visual appliances within the field of view. The strobe signals are * ADA/NFPA/ANSI Compliant.
listed for indoor use, ceiling and wall mount, for sleeping and * UL listed for Ceiling and Wall mounting under UL1971.
non/sleeping areas under UL 1971 Standard. * Screw terminal capacity up to 12 AWG.
* 24V DC strobe with 177cd output.
* Polarized strobes with wide listed voltage ranges using
Application: Filtered DC or unfiltered FWR input voltage.
The SL24C-177 Ceiling Strobe Series is recommended for use * Meets ADA guidelines for minimum one flash per/sec (1Hz).
in areas such as: warehouses, meeting rooms, schools, * Munts to 4” square, back box.
corridors, apartments, office buildings, restaurants, hotels, and * 24 volt strobe models.
any other application where effective visual warning is required * Designed for sleeping and non/sleeping areas.
by Federal, State, or local authority having jurisdiction. * Synchronization requires an AMSECO SMS1-3A or
SMD10-3A (daisy chain) Sync Module.
* RBX-1 back box skirt for surface mount (optional)
Strobe Wiring: * The SPC-1 retrofit plate allows mounting to a variety of back
boxes (optional).
FI
* Available in red or white housing.
Control E To Next Device
R
R

Panel or End-Of Line-


FI

Resistor
+ _
FI R E
Wiring Terminals:
+ _

Current Draw Table:


DC FWR
Current (mA)
16V 24V 33V 16V 24V 33V
Average 378 245 185 468 332 264
@ 177cd Peak 584 428 380 844 804 700
In-Rush 460 476 508 788 828 716

Ordering Information:
Model Input Strobe Sync Mounting Flash Operating Housing
Number Voltage Output Module Type Rate Voltage Range Color
(VDC) (Candela) (Times/min.) (VDC)
SL24C-177R 24 177 SMD10-3A Ceiling / Wall 60 16 ~ 33 Red
SL24C-177W 24 177 SMD10-3A Ceiling / Wall 60 16 ~ 33 White
The strobe is listed for indoor use with a temperature operating range of 32°F ~ 120°F (0°C ~ 49°C )

Specifications subject to change without notice.

Hochiki America Corporation


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 06/2003
Engineering Specifications:
The visual alarm indicating appliance shall be AMSECO model SL24C-177 or equivalent device. The Strobe shall be listed under UL 1971 Standard for
signaling devices for the hearing impaired and shall be approved for fire protective service. The candela output shall be 177cd. The strobe shall be
UL1971 listed for both ceiling and wall mount applications. The signaling Strobe shall operate on 24VDC from a non-coded regulated DC supply or full-
wave rectified, unfiltered supply. The signaling strobe shall be designed to produce a signal flash of one flash per second with continuously applied
minimum voltage. When strobe synchronization is required, the strobe shall be compatible with the AMSECO SMS1-3A or SMD10-3A or other source of
AMSECO sync protocol. The Strobe shall be capable of CEILING and WALL mount ing to a 4’’ x 4’’ x 1-1/2’’ back box. Signaling devices shall be installed
in all sleeping and non/sleeping areas as per plans and specifications.

Light Output Dispersion:

90 °
G

WA
IN

90° LL
IL
E
C

°
°

90
90

Compound Compound
FI 90°
45°
E FI

45°
R
R

R
FI

E
FI
E
R

R
FI

FI R E
FI R E

FI R E

45° 45°
°

FI
°
90

90

R
E


90°


90 °

45° 90°
45°

Compound Compound
Using the Sync Module:
Sync Module Room Spacing for Ceiling-Mounted Visible Appliances
F.A.C.P. Minimum Light Output by Room Size.
SMD10-3A FI
To Next Device or
Signal R
E
R

Circuit IN OUT End-Of Line- Maximum


FI

_ _ _ _ Resistor Maximum Room Size (ft.)


+ H+H + + Ceiling
20 X 20 30 X 30 40 X 40 50 X 50
+ _
Height (ft.)
FI R E

30 75cd. 75cd. 177cd. 177cd.


20 30cd. 75cd. 110cd. 177cd.
*The Sync module is rated for 3.0 amperes at 24 VDC. 10 30cd. 30cd. 75cd. 110cd.

Mounting:
*The SPC-1 Universal Retrofit Plate is designed for mounting to a variety of back boxes.
*Surface mount installations, use the RBX-1 Back Box Skirt.
Single gang Double gang Octagon
back box back box back box

4” square
back box
SPC-1 SPC-1 SPC-1

4” square
back box RBX-1
RBX-1 RBX-1 RBX-1

Dimensions: Inches (mm)


3-3/8 (85.7)

6-7/8 (174) 1-13/32 (35) 3-3/8 (85.7)


2-25/32 (70)

Hochiki America Corporatrion : SL24C-177 Specifications subject to change without notice.


SL24C-3075110
Ceiling and Wall Mount
Select -A- Strobe

Description:
AMSECO’s Ceiling and Wall mount Select-A-Strobe is designed
to comply with the Americans with Disability Act (ADA) and meet
UL Standard 1971 requirements for emergency signaling
devices for the hearing impaired. The SL24C-3075110 Select-
A-Strobe features a unique candela intensity field selector
switch for alternating the candela 30cd, 75cd or 110cd intensity
Strobe with Selectable Candela 30cd, 75cd, 110cd
output. The round housing design offers a low profile
appearance and is clearly labeled with “FIRE” lettering to be LI
STI N

UL

G
OF CA L IFOR

ULC TE

MEA

NI
ST
view from all angles. These appliances are polarized for

A
ST

LL
T

A
E SH
FI R
E MAR

connecting to supervised fire alarm circuits. The strobe is

E
E

S
RV I C

designed with a xenon flashtube and provides a candela Features:


intensity field selector switch for maximum performance. The * Selectable Candela 30cd, 75cd or 110 candela output.
Ceiling/Wall mount Select-A-Strobe series is available in red * ADA/NFPA/ANSI compliant.
and white housing 24V DC models. The SL24C-3075110 can be * UL listed for Ceiling and Wall mounting under UL1971.
synchronized by using the SMD10-3A (daisy chain) Sync * Designed for use in non-sleeping areas.
Module to comply with NFPA recommendations concerning * Screw terminal capacity up to 12 AWG.
photosensitive epilepsy when installing 2 or more visual * Polarized strobes with wide listed voltage ranges using filtered
appliances within the field of view. The strobe signals are DC or unfiltered FWR input voltage.
designed for non-sleeping areas and are listed for indoor use, * Meets ADA guidelines for minimum one flash per/sec (1Hz).
ceiling and wall mount, under UL 1971 Standard. * All models mount to 4” x 4” x 1-1/2” back box.
* Synchronization requires an AMSECO SMD10-3A
(daisy chain) Sync Module.
Application: * RBX-1 back box skirt for surface mount (optional)
The SL24C-3075110 Ceiling Strobe Series is recommended for * The SPC-1 retrofit plate allows mounting to a variety of back
use in areas such as: warehouses, meeting rooms, schools, boxes (optional).
corridors, apartments, office buildings, restaurants, hotels, and * Available in red or white housing.
any other application where effective visual warning is required Strobe Wiring:
by Federal, State, or local authority having jurisdiction.
FI To Next Device
Control E
R
R

Panel or End-Of Line-


FI

Resistor
Strobe Selectable Candela:
+ _
FI R E

+ _
H
C
IT

Room Spacing for Ceiling-Mounted Visible Appliances


W
S

Minimum Light Output by Room Size.


0
11
d Maximum
0c Maximum Room Size (ft.)
75 11
Ceiling
cd
30
75 Height (ft.) 20 X 20 30 X 30 40 X 40 50 X 50
cd Tamper
30 proof cap 30 75cd. 75cd. 177cd. 177cd.
20 30cd. 75cd. 110cd. 177cd.
10 30cd. 30cd. 75cd. 110cd.
Ordering Information:
Model Input Strobe Sync Mounting Flash Operating Housing
Number Voltage Selectable Module Type Rate Voltage Range Color
(VDC) (Candela) (Times/min.) (VDC)
SL24C-3075110R 24 30, 75, 110 SMD10-3A Ceiling / Wall 60 16 ~ 33 Red
SL24C-3075110W 24 30, 75, 110 SMD10-3A Ceiling / Wall 60 16 ~ 33 White
The strobe is listed for indoor use with a temperature operating range of 32°F ~ 120°F (0°C ~ 49°C )
Specifications subject to change without notice.

Hochiki America Corporation


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 06/2003
Engineering Specifications:
The visual alarm indicating appliance shall be AMSECO model SL24C-3075110 or equivalent device. The Strobe shall be listed
under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The candela
output shall be field selectable, having three (3) settings 30cd, 75cd and 110cd output. All settings shall be UL1971 listed for both
ceiling and wall mount applications. The signaling Strobe shall operate on 24VDC from a non-coded regulated DC supply or full-
wave rectified, unfiltered supply. The signaling strobe shall be designed to produce a signal flash of one flash per second with
continuously applied minimum voltage. When strobe synchronization is required, the strobe shall be compatible with the AMSECO
SMS1-3A or SMD10-3A (daisy chain) or other source of AMSECO sync protocol. The Strobe shall be capable of CEILING and WALL
mount to a variety of back boxes using the AMSECO SPC-1 retrofit back plate.
Signaling devices shall be installed in all non-sleeping areas as per plans and specifications.

Light Output Dispersion:

90 °
WA
LL
G

90°
IN
IL
E
C

°
°

Compound Compound
90
90

90°
45°
FI

45°
FI

R
E

E
R
R

FI
E
FI

R
FI

FI R E
FI R E

FI R E

45° 45°

FI
R
E
°



°
90

90

90°

90 °

0° 90°
45°
45°

Compound Compound
Strobe Current Draw Table:
DC FWR
Current (mA)
16V 24V 33V 16V 24V 33V
Average 121 87 70 168 131 110
@ 30cd Peak 221 215 165 414 350 338
In-Rush 254 298 338 402 418 458
Strobe Average 183 127 101 240 180 151
@ 75cd Peak 298 218 209 554 458 450
In-Rush 306 342 374 540 478 498
Average 236 162 125 310 227 186
@ 110cd Peak 410 282 204 670 564 526
In-Rush 386 398 430 644 580 548

Mounting:
*The SPC-1 Universal Retrofit Plate is designed for mounting to a variety of back boxes.
*Surface mount installations, use the RBX-1 Back Box Skirt.
Single gang Double gang Octagon
back box back box back box

4” square
back box
SPC-1 SPC-1 SPC-1

4” square
back box RBX-1
RBX-1 RBX-1 RBX-1

Using the Sync Module: Dimensions: Inches (mm)


Sync Module
F.A.C.P. SMD10-3A FI
Signal R
E To Next Device or
R

IN OUT
3-3/8 (85.7)

Circuit End-Of Line-


FI

_ _ _ _ Resistor
+ H+H + +
+ _
FI R E

1-13/32 (35)
*The Sync module is rated for 3.0 amperes at 24 VDC. 6-7/8 (174) 2-25/32 (70) 3-3/8 (85.7)

Hochiki America Corporatrion : SL24C-3075110 Specifications subject to change without notice.


SL24W-153075 Patented

Selectable 15cd or 30cd.


Select -A- Strobe TM Series

Description:
AMSECO’s Select-A-Strobe Series is designed to comply
with the Americans with Disability Act (ADA) and meet UL
Standard 1971 requirements for emergency signaling
devices for the hearing impaired. The SL24W series Select-
A-Strobe features a unique candela intensity field selector
Strobe with Universal Mounting Plate Included
switch for alternating the candela output 15cd to 30cd (75cd
on axis). The strobe housing is clearly labeled with vertical I STI N

UL

G
F CA L IFO

ULC
O
TE R

MEA

A
FM

NI
ST
“FIRE” lettering and is polarized for connecting to

A
ST

LL
T

A
A DA
E SH
F IR
E MAR

supervised fire alarm circuits. The strobe is designed with a


ER

E
S
APPROVED VI C

xenon flashtube and provides a candela intensity field


selector switch for maximum performance. Features:
The Select-A-Strobe Series is available in red and white * Designed to meet or exceed NFPA/ANSI Standards and ADA
housing 24VDC models. The SL24W-153075 can be Accessibility Guidelines.
synchronized by using the SMS1-3A sync module to comply * UL listed for wall mounting.
with NFPA recommendations concerning photosensitive * Screw terminal capacity up to 12 AWG.
epilepsy when installing 2 or more visual appliances within * Universal mounting plate included with each unit.
the field of view. The strobe signals are listed for indoor * 24V DC strobe with two field selectable settings 15cd or 30cd.
use, wall mount, under UL 1971 Standard. * Polarized strobes with wide listed voltage ranges using filtered
DC or unfiltered FWR input voltage.
* Meets ADA guidelines for minimum one flash per/sec (1Hz).
* All models mount to 4” square, single gang, double gang, …
Application: or octagonal back box.
The SL24W-153075 Strobe series is recommended for use * 24 volt strobe models 15 or 30 candela Intensity.
in areas such as: meeting rooms, schools, corridors, * Tamper-proof candela selector switch.
apartments, office buildings, restaurants, hotels, and any * Synchronization requires an AMSECO SMS1-3A Sync Module.
other application where effective visual warning is required * Available in red or white housing.
by Federal, State, or local authority having jurisdiction.

Selectable Candela Output:


Strobe Wiring:
15
cd Control To Next Device or
30 Panel F
End-Of Line-Resistor
cd _
I
R
+ E

+ _
F
I
R 15
E

30
Conductor size (AWG), length and capacity should be taken into
Tamper Proof consideration prior to design and installation.

Ordering Information:

Model Input Selectable Sync Mounting Universal Flash Housing


Number Voltage Output Module Type Mounting Per/Min. Color
(VDC) (Candela) Compatible Plate
SL24W-153075R 24 15 or 30 SMS1-3A Wall Included 60 Red
SL24W-153075W 24 15 or 30 SMS1-3A Wall Included 60 White

Specifications subject to change without notice.

Hochiki America Corporation


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 06/2003
Engineering Specifications:
The visual alarm indicating appliance shall be AMSECO model SL24W-153075 or equivalent device. The Strobe shall be listed
under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The
candela output shall be field selectable, having a dual setting of 15cd or 30cd output. The signaling Strobe shall operate on 24V
DC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be designed to
produce one signal flash per second with continuously applied minimum voltage. The strobe shall be capable of WALL mounting
to a universal backbox. Visual signaling devices shall be mounted 80” above the highest floor point or 6” below ceiling; whichever
is lowest and are to be installed as per plans and specifications.

Light Output Distribution / Horizontal and Vertical Dispersion:


UL Required Minimum Light Output (cd)
Wall Mount Horizontal Wall Mount Vertical
45
WALL WALL Degrees @15cd @30cd @15cd @30cd
0 75.00 75.00 75.00 75.00
90 90 5 ~ 25 13.50 27.00 13.50 27.00
30 11.25 22.50 13.50 27.00
35 11.25 22.50 9.75 19.50
45 40 11.25 22.50 6.90 13.80
Compound 45 45 11.25 22.50 5.10 10.20
90 50 8.25 16.50 4.05 8.10
90
55 6.75 13.50 3.30 6.60
0 60 6.00 12.00 2.70 5.40
45 0 65 5.25 10.50 2.40 4.50
90 70 5.25 10.50 2.25 4.50
Compound 45
75 4.50 9.00 1.95 3.90
80 4.50 9.00 1.80 3.60
85 ~ 90 3.75 7.50 1.80 3.60
Compound 45 3.60 7.20

Strobe Current Draw Table:

DC FWR
Current (mA)
16V 24V 33V 16V 24V 33V
Average 84 60 47 118 89 76
@ 15cd Peak 122 99 84 264 224 205
In-Rush 122 100 119 264 224 205
Average 129 91 71 178 128 102
@ 30cd Peak 164 129 115 368 298 264
In-Rush 164 135 223 368 298 264

Dimensions: inches (mm) Using the SMS1-3A Sync Module:

5 (127) 2-1/4 (56.9) 3-3/8 (85.7)


1-13/16 (46)
F.A.C.P. SMS1-3A
Signal To Next Device or
Circuit_ _ IN_ _
OUT F
I
End-Of Line-Resistor
+ + +
3-9/32 (83.5)

3-9/32 (83.5)
3-3/8 (85.7)

H+H R
5 (127)

+ _

*The Sync module is rated for 3.0 amperes at 24 VDC.

Mounting Options:
Strobe with Universal mounting Strobe with Universal mounting Strobe with Universal mounting Strobe with Universal mounting
plate and single gang box. plate and 4” square back box. plate and double gang box. plate and surface mount back box.

4” x 4” x 1-1/2” 4” x 4” x 1-1/2”
2” backbox
backbox backbox
F
4BX-1
F F F
I I I I
Surface Mount
R Universal Mounting Plate R Universal Mounting Plate R Universal Mounting Plate R back box
E E E E
4SP-M
Strobe Strobe Strobe Strobe Mounting Plate

Hochiki America Corporatrion : SL24W-153075 Specifications subject to change without notice.


SL24W-75110 Patented

Selectable 75cd or 110cd.


Select -A- Strobe Series

Description:
AMSECO’s Select-A-Strobe Series is designed to comply
with the Americans with Disability Act (ADA) and meet UL
Standard 1971 requirements for emergency signaling
devices for the hearing impaired. The SL24C series Select-
A-Strobe features a unique candela intensity field selector
Strobe with Universal Mounting Plate Included
switch for alternating the candela output 30cd, 75cd or
110cd. The strobe is polarized for connecting to supervised I STI N

UL

G
F CA L IFO

ULC
O
TE R

MEA

A
FM

NI
ST
fire alarm circuits. The strobe is designed with a xenon

A
ST

LL
T

A
A DA
E SH
F IR
E MAR

flashtube and provides a candela intensity field selector

E
E

S
R V IC
APPROVED

switch for maximum performance.


The Select-A-Strobe Series is available in red and white Features:
housing 24VDC models. The SL24W-75110 can be * Designed to meet or exceed NFPA/ANSI Standards and ADA
synchronized by using the SMS1-3A sync module to comply Accessibility Guidelines.
with NFPA recommendations concerning photosensitive * UL listed for wall mounting.
epilepsy when installing 2 or more visual appliances within * Screw terminal capacity up to 12 AWG.
the field of view. The strobe signals are listed for indoor * Universal mounting plate included with each unit.
use, wall mount, under UL 1971 Standard. * 24V DC strobe with field selectable settings 75cd or 110cd.
* Polarized strobes with wide listed voltage ranges using filtered
DC or unfiltered FWR input voltage.
* Meets ADA guidelines for minimum one flash per/sec (1Hz).
* All models mount to 4” square, single gang, double gang, or
Application: octagonal back box.
The SL24W-75110 Strobe series is recommended for use in * 24 volt strobe models 75 or 110 candela Intensity.
areas such as: meeting rooms, schools, corridors, * Tamper-proof candela selector switch.
apartments, office buildings, restaurants, hotels, and any * Synchronization requires an AMSECO SMS1-3A Sync Module.
other application where effective visual warning is required * Available in red or white housing.
by Federal, State, or local authority having jurisdiction.

Selectable Candela Output:


Strobe Wiring:
75
cd Control To Next Device or
11 Panel F
End-Of Line-Resistor
0cd _
I
R
+ E

+ _
F
I
R 75
E

11
0
Conductor size (AWG), length and capacity should be taken into consideration
Tamper Proof prior to design and installation.

Ordering Information:

Model Input Selectable Sync Mounting Universal Flash Housing


Number Voltage Output Module Type Mounting Per/Min. Color
(VDC) (Candela) Compatible Plate
SL24W-75110R 24 75 or 110 SMS1-3A Wall Included 60 Red
SL24W-75110W 24 75 or 110 SMS1-3A Wall Included 60 White

Specifications subject to change without notice.

Hochiki America Corporation


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 06/2003
Engineering Specifications:
The visual alarm indicating appliance shall be AMSECO model SL24W-75110 or equivalent device. The Strobe shall be listed
under UL 1971 Standard for signaling devices for the hearing impaired and shall be approved for fire protective service. The
candela output shall be field selectable, having a dual setting of 75cd or 110cd output. The signaling Strobe shall operate on
24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The signaling strobe shall be designed to
produce a one signal flash per second with continuously applied minimum voltage. The Strobe shall be capable of WALL mounting
to a universal backbox. Visual signaling devices shall be mounted 80” above the highest floor point or 6” below ceiling; whichever
is lowest and are to be installed as per plans and specifications.

Light Output Distribution / Horizontal and Vertical Dispersion:


UL Required Minimum Light Output (cd)
Wall Mount Horizontal Wall Mount Vertical
45
WALL WALL Degrees @75cd @110cd @75cd @110cd
0 75.00 110.00 75.00 110.00
90 90 5 ~ 25 67.50 99.00 67.50 99.00
30 56.25 82.50 67.50 99.00
35 56.25 82.50 48.75 71.50
45 40 56.25 82.50 34.50 50.60
Compound 45 45 56.25 82.50 25.50 37.40
90 50 41.25 60.50 20.25 29.70
90
55 33.75 49.50 16.50 24.20
0 60 30.00 44.00 13.50 19.80
45 0 65 26.25 38.50 12.00 17.60
90 70 26.25 38.50 11.25 16.50
Compound 45
75 22.50 33.00 9.75 14.30
80 22.50 33.00 9.00 13.20
85 ~ 90 18.75 27.50 9.00 13.20
Compound 45 18.00 26.40

Strobe Current Draw Table:

DC FWR
Current (mA)
16V 24V 33V 16V 24V 33V
Average 132 92 71 178 128 105
@ 75cd Peak 157 132 108 354 280 242
In-Rush 157 132 121 354 280 242
Average 181 122 94 241 170 134
@ 110cd Peak 194 156 127 432 356 302
In-Rush 194 156 127 432 356 302

Dimensions: inches (mm) Using the SMS1-3A Sync Module:

5 (127) 2-1/4 (56.9) 3-3/8 (85.7)


1-13/16 (46)
F.A.C.P. SMS1-3A
Signal To Next Device or
Circuit_ _ IN_ _
OUT F
I
End-Of Line-Resistor
+ + +
3-9/32 (83.5)
3-9/32 (83.5)
3-3/8 (85.7)

H+H R
5 (127)

+ _

*The Sync module is rated for 3.0 amperes at 24 VDC.

Mounting Options:
Strobe with Universal mounting Strobe with Universal mounting Strobe with Universal mounting Strobe with Universal mounting
plate and single gang box. plate and 4” square back box. plate and double gang box. plate and surface mount back box.

4” x 4” x 1-1/2” 4” x 4” x 1-1/2”
2” back box
back box back box
F
4BX-1
F F F
I I I I
Surface Mount
R Universal Mounting Plate R Universal Mounting Plate R Universal Mounting Plate R back box
E E E E
4SP-M
Strobe Strobe Strobe Strobe Mounting Plate

Hochiki America Corporatrion : SL24W-75110 Specifications subject to change without notice.


SSC25-177
SSC70-177
Ceiling and Wall Mount
Speaker/Strobe Combination

Description:
AMSECO’s ceiling and wall mount fire alarm Speaker/Strobe series
is designed to generate attention grabbing tones and voice
commands for emergency signaling evacuation applications.
These highly efficient low profile speakers are available with field Speaker/Strobe Combination 177cd.
selectable taps ¼, ½, 1, 2 watts. The low profile speakers are
STI N

available in two input voltage models 25 and 70.7 Vrms and can be UL
LI

G
OF CA L IFOR

ULC TE

MEA

NI
ST

A
installed on a standard 4” square back box. The strobe features a

ST

LL
T

A
E SH
FI R
E MAR

E
E

S
RV I C

177 candela intensity output. The housing is clearly labeled with Pending
“FIRE” lettering and is polarized for connecting to supervised fire Features:
alarm circuits. The strobe is designed with a xenon flash tube and * ADA / NFPA / ANSI Compliant
provides a high intensity output for maximum performance. The * UL Listed for Ceiling and Wall mounting under UL 1971
SSC-177 Speaker/Strobe Series is available in red or white housing * 177 candela output
models. * Speaker field selectable taps 1/4w, 1/2w, 1w, 2 watts
The Strobe can be synchronized by using the SMD10-3A sync * Available 25Vrms and 70.7Vrms models
module to comply with NFPA recommendations concerning * Screw terminals capacity up to 12 AWG.
photosensitive epilepsy when installing 2 or more visual appliances * Frequency range 400 Hz ~ 4,000 Hz.
within the field of view. The strobe signals are listed for indoor use, * Integral blocking capacitor for line supervision
ceiling and wall mount, under UL 1971 Standard. * Polarized strobes with wide listed voltage ranges
using filtered DC or unfiltered FWR input voltage
* Meets ADA guidelines for minimum one flash per/sec (1Hz)
* Strobe is polarized and rated at 24VDC
How to Order: * Synchronization requires an AMSECO SMD10-3A (daisy-
Chain) Sync Module
SSC25-177R * RBX-1back box skirt for surface mount (Optional)
* Available in red or white housing
25 = 25Vrms
70 = 70.7Vrms
177 = 177cd Using the Sync Module:
R = Red
FI
E
W = White R
R

F.A.C.P &
FI

VOICE / EVAC
TO NEXT DEVICE
Strobe
_ SSpeaker
_ FI R E
or END-OF-LINE
+ +S Speaker Strobe -RESISITOR
Application: S+ S _ L+ L _
The SSC-177 Series is recommended for use in areas such as:
warehouses, meeting rooms, schools, corridors, apartments,
office buildings, restaurants, hotels, and any other application Sync Module
where effective visual warning is required by Federal, State, or TO NEXT DEVICE
SMD10-3A or END-OF-LINE
local authority having jurisdiction. _ IN_ OUT
_ -RESISITOR
H+ H + +

Ordering Information: *The Sync module is rated for 3.0 amperes at 24 VDC.

Model Speaker Strobe Sync Speaker Strobe Mounting Housing


Number Voltage Output Module Selectable Taps Flash Rate Type Color
(Vrms) (Candela) (Watts) (times/min)
SSC25-177R 25 177 SMD10-3A ¼, ½, 1, 2 60 Ceiling & Wall Red
SSC25-177W 25 177 SMD10-3A ¼, ½, 1, 2 60 Ceiling & Wall White
SSC70-177R 70.7 177 SMD10-3A ¼, ½, 1, 2 60 Ceiling & Wall Red
SSC70-177W 70.7 177 SMD10-3A ¼, ½, 1, 2 60 Ceiling & Wall White
The speaker/strobe is listed for indoor use with a temperature operating range of 32 °F ~ 120°F (0°C ~ 49°C )

Specifications subject to change without notice.

Hochiki America Corporation


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 06/2003
Engineering Specifications:
The Fire alarm speaker shall be capable of reproducing alarm tones or voice commands on 25Vrms or 70.7Vrms. Speakers shall
provide incremental tap settings of ¼, ½, 1, and 2 watts and shall be selected by means of a jumper wire. The speaker shall have a
frequency range of 400 to 4,000 Hz. The speaker shall produce a UL sound pressure level at 10 feet up to 84dB. The speaker shall be
approved for fire alarm signaling use. The Strobe shall be listed under UL 1971 Standard for signaling devices for the hearing impaired
and shall be approved for fire protective service. The candela output shall be 177. The signaling strobe shall operate on 24VDC from a
non-coded regulated DC supply or full-wave rectified, unfiltered supply. The strobe shall be designed to produce one signal flash per
second with continuously applied minimum voltage. When strobe synchronization is required, the strobe shall be compatible with the
AMSECO SMS1-3A, SMD10-3A or other source of AMSECO sync protocol. The Speaker/Strobe shall be capable of WALL or CEILING
mounting. The Visual signaling devices are to be installed in all sleeping and non-sleeping areas as per plans and specifications.

Light Output Dispersion:

90 °
G

WA
IN

90° LL
IL
E
C

°
°

Compound
90
90

Compound
45°
90°

45°
FI
E FI
R
R

FI

R
FI

E
R

R
FI

FI R E
FI R E

FI R E

45° 45°

FI
°


°


90

R
90

90°

90 °


45°
90°
45°

Compound Compound
Speaker specifications:

Rated Input Voltage 25V 70.7V


( V r.m.s./ 1kHz )
Input Power (Watts) ¼ ½ 1 2 ¼ ½ 1 2
Impedance (k ohms) 2.5 1.25 0.62 0.31 20 10 5 2.5
Sound Pressure Level (dB/10ft) 75 78 81 84 75 78 81 84
Frequency Response (Hz) 400 ~ 4,000
Low Frequency Cut Off (Hz) 200
Operating Temperature Range 32°F ~ 120°F ( 0°C ~ 49°C )

Room Spacing for Ceiling-Mounted Visible Appliances


Strobe Only Current Draw Table: Minimum Light Output by Room Size.

DC FWR Maximum Maximum Room Size (ft.)


Current (mA)
16V 24V 33V 16V 24V 33V Ceiling
Height (ft.) 20 X 20 30 X 30 40 X 40 50 X 50
Average 378 245 185 468 332 264
@177cd Peak 584 428 380 844 804 700 30 75cd. 75cd. 177cd. 177cd.
20 30cd. 75cd. 110cd. 177cd.
In-Rush 460 476 508 788 828 716
10 30cd. 30cd. 75cd. 110cd.

Surface Mount
Mounting:
4” square
x 2-1/8” deep
back box.

Dimensions: Inches (mm) Wall or Ceiling Mount

4” square
x 2-1/8” deep RBX-1
back box. back box
skirt
(Optional)
3-3/8 (85.7)

FI
E
R
R
FI

FI R E

6-7/8 (174) 1-49/64 (45) 1 (25.5) 3-3/8 (85.7)


2-25/32 (70)

Hochiki America Corporatrion : SSC-177 Specifications subject to change without notice.


SSC25-3075110
SSC70-3075110
Ceiling and Wall Mount
Select -A- Speaker/Strobe Combination
Description:
AMSECO’s ceiling and wall mount fire alarm Select-A-
Speaker/Strobe are designed to generate attention grabbing
tones and voice commands for emergency signaling evacuation
applications. These highly efficient low profile speakers are
available with field selectable taps ¼, ½, 1, 2 watts. The low profile Selectable 30cd, 75cd, 110cd.
speakers are available in two input voltage models 25 and 70.7 LI
STI N

UL ULC

G
OF C A L IFOR

Vrms and can be installed on a standard 4” square back box. The TE

MEA

NI
ST

A
ST

LL
series is designed with the exclusive Select-A-Strobe. The strobe
T

A
E SH
FIR
E MA R

E
E

S
RV I C

features a unique candela intensity field selector switch for Features:


alternating the candela output 30cd, 75cd and 110cd. The strobe * ADA / NFPA / ANSI Compliant
housing is clearly labeled with “FIRE” lettering and is polarized for * UL Listed for Ceiling and Wall mounting under UL 1971
connecting to supervised fire alarm circuits. The strobe is * Three field selectable settings 30cd, 75cd and 110cd
designed with a xenon flash tube and provides a candela intensity * Speaker field selectable taps 1/4w, 1/2w, 1w and 2 watts
field selector switch for maximum performance. * Available 25Vrms and 70.7Vrms models
The Select-A-Speaker/Strobe Series is available in red or white * Screw terminals capacity up to 12 AWG
housing models. The Strobe can be synchronized by using the * Frequency range 400 Hz ~ 4,000 Hz
SMD10-3A sync module to comply with NFPA recommendations * Integral blocking capacitor for line supervision
concerning photosensitive epilepsy when installing 2 or more * Polarized strobes with wide listed voltage ranges
visual appliances within the field of view. The strobe signals are using filtered DC or unfiltered FWR input voltage
listed for indoor use, ceiling and wall mount, under UL 1971 * Meets ADA guidelines for minimum one flash per/sec (1Hz).
Standard. * All models mount to 4” square back box
* Strobes are polarized and rated at 24VDC.
* Synchronization requires an AMSECO SMD10-3A (daisy
How to Order: chain) Sync Module
SSC25-3075110R * RBX-1 back box skirt for surface mount (optional)
* Available in red or white housing
25 = 25Vrms
70 = 70.7Vrms
3075110 = 30cd, 75cd or 110cd Strobe Selectable Candela:
R = Red
W = White

Application:
H
C
IT
W
S

The SSC-3075110 Series is recommended for use in areas such


as: warehouses, meeting rooms, schools, corridors, 11
0
d
apartments, office buildings, restaurants, hotels, and any other 0c
75 11
application where effective visual warning is required by cd
30
75
Federal, State, or local authority having jurisdiction.
d Tamper
30c
proof cap

Ordering Information:

Model Speaker Strobe Sync Speaker Strobe Mounting Housing


Number Voltage Selectable Module Selectable Taps Flash Rate Type Color
(Vrms) (Candela) (Watts) (times/min)
SSC25-3075110R 25 30, 75, 110 SMD10-3A ¼, ½, 1, 2 60 Ceiling & Wall Red
SSC25-3075110W 25 30, 75, 110 SMD10-3A ¼, ½, 1, 2 60 Ceiling & Wall White
SSC70-3075110R 70.7 30, 75, 110 SMD10-3A ¼, ½, 1, 2 60 Ceiling & Wall Red
SSC70-3075110W 70.7 30, 75, 110 SMD10-3A ¼, ½, 1, 2 60 Ceiling & Wall White
The speaker/strobe is listed for indoor use with a temperature operating range of 32 °F ~ 120°F (0°C ~ 49°C )

Specifications subject to change without notice.

Hochiki America Corporation


7051 Village Drive, Suite 100 Buena Park, CA 90621-2268
Phone: 714/522-2246 Fax: 714/522-2268
Technical Support: 800/845-6692 or technicalsupport@hochiki.com 06/2003
Engineering Specifications:
The Fire alarm speaker shall be capable of reproducing alarm tones or voice commands on 25Vrms or 70.7Vrms. Speakers shall
provide incremental tap settings of ¼, ½, 1, and 2 watts and shall be selected by means of a jumper wire. The speaker shall have a
frequency range of 400 to 4,000 Hz. The speaker shall produce a UL sound pressure level at 10 feet up to 84dB. The speaker shall be
approved for fire alarm signaling use. The Strobe shall be listed under UL 1971 Standard for signaling devices for the hearing impaired
and shall be approved for fire protective service. The candela output shall be field selectable, having three setting 30cd, 75cd and 110cd
output. The signaling strobe shall operate on 24VDC from a non-coded regulated DC supply or full-wave rectified, unfiltered supply. The
strobe shall be designed to produce one signal flash per second with continuously applied minimum voltage. When strobe
synchronization is required, the strobe shall be compatible with the AMSECO SMS1-3A or SMD10-3A or other source of AMSECO sync
protocol. The Speaker/Strobe shall be capable of WALL or CEILING mounting. The Visual signaling devices are to be installed in all
non-sleeping areas as per plans and specifications.

Light Output Dispersion: Using the Sync Module:

90 °
G
IN
IL

FI
E

E
R

R
F.A.C.P &
C

FI

E
°
°

Compound
90
90

Compound VOICE / EVAC


TO NEXT DEVICE
45°

Strobe
_ SSpeaker
_

45°
FI
FI R E
or END-OF-LINE
R
E
+ +S Speaker Strobe -RESISITOR
R

FI
S+ S _ L+ L _
FI

E
R
R
FI

FI R E

FI R E

45° 45°
Sync Module
°


°


90

TO NEXT DEVICE
90

SMD10-3A or END-OF-LINE
_ IN_ OUT
_ -RESISITOR
H+ H + +
90 °


45°
45°

Compound Compound
*The Sync module is rated for 3.0 amperes at 24 VDC.
Speaker specifications:

Rated Input Voltage 25V 70.7V


( V r.m.s./ 1kHz )
Input Power (Watts) ¼ ½ 1 2 ¼ ½ 1 2
Impedance (k ohms) 2.5 1.25 0.62 0.31 20 10 5 2.5
Sound Pressure Level (dB/10ft) 75 78 81 84 75 78 81 84
Frequency Response (Hz) 400 ~ 4,000
Low Frequency Cut Off (Hz) 200
Operating Temperature Range 32°F ~ 120°F ( 0°C ~ 49 °C )

Room Spacing for Ceiling-Mounted Visible Appliances


Strobe Only Current Draw Table: Minimum Light Output by Room Size.
DC FWR Maximum Maximum Room Size (ft.)
Current (mA)
16V 24V 33V 16V 24V 33V Ceiling
Average 121 87 70 168 131 110 Height (ft.) 20 X 20 30 X 30 40 X 40 50 X 50
@30cd Peak 221 215 165 414 350 338 30 75cd. 75cd. 177cd. 177cd.
254 298 338 402 418 458 20 30cd. 75cd. 110cd. 177cd.
In-Rush
183 101 240 180 151 10 30cd. 30cd. 75cd. 110cd.
Average 127
@75cd Peak 298 218 209 554 458 450
Surface Mount
In-Rush 306 342 374 540 478 498
Mounting:
Average 236 162 125 310 227 186
4” square
@110cd Peak 410 282 204 670 564 526 x 2-1/8” deep
back box.
In-Rush 386 398 430 644 580 548
Wall or Ceiling Mount
Dimensions: Inches (mm)
4” square
x 2-1/8” deep RBX-1
back box. back box
skirt
(Optional)
3-3/8 (85.7)

FI
E
R
R
FI

FI R E

6-7/8 (174) 1-49/64 (45) 1 (25.5) 3-3/8 (85.7)


2-25/32 (70)

Hochiki America Corporatrion : SSC-3075110 Specifications subject to change without notice.


FN-300ULX Data Sheet
Rev. FN-300ULX- J20E

Overview
• This power supply/charger converts a 115VAC / 60Hz input, to a 12VDC
or 24VDC regulating output.

FN-300ULX
• 12VDC or 24VDC @ 2.5 amp.

Specifications Enclosure Dimensions


• Input 115VAC / 60Hz, 1.45 amp. 13”H x 13.5”W x 3.25”D
• 12VDC or 24VDC selectable output. 1.40” 4.85” 4.85” 1.40”

• Class 2 Rated power limited output.


• Input fuse rated @ 3.5 amp/250V. 3.25”

• Filtered and electronically regulated output. 1.20”

• Short circuit and thermal overload protection. 0.75”


12.50”

11.00” 1.20”

• AC fail supervision (form "C" contacts). 1.40”


0.5275”

1.40”

• Low battery supervision (form "C" contacts).


• Battery presence supervision (form “C” contacts).
• Built-in charger for sealed lead acid
5.10” 5.10”

or gel type batteries. 11.125”

• Automatic switch over to stand-by battery when 13.00”

AC fails.
• Maximum charge current .7 amp. 5.10”

6.50”

• Zero voltage drop when switched over to


battery backup. 1.40” 1.3475”

• AC input and DC output LED indicators. 3.25” 11.00” 3.25”

• Accommodates up to two (2) 12VDC/7AH batteries. 1.25” 10.00” 1.25”

1.25”

• Power supply, enclosure, cam lock and battery leads. 3.25”

Agency Approvals
UL 294 UL Listed for Access Control MEA - NYC Department of
System Units. Buildings Approved.
UL 603 UL Listed Standard for Power
Supplies for Use with Burglar-
Alarm Systems. CSFM - California State Fire
Marshal Approved.
UL 1069 UL Listed Hospital Signaling and
Nurse Call Equipment.
UL 1481 UL Listed Standard for Safety for
Fire Protective Signaling Systems.

02/2005
FN-400ULX Data Sheet
Rev. DSFN-400ULX - J24E

Overview
• This power supply/charger converts a 115VAC / 60Hz input, to a
12VDC or 24VDC regulating output.

FN-400ULX
• 12VDC @ 4 amp or 24VDC @ 3 amp supply current.

Specifications Enclosure Dimensions


• Input 115VAC / 60Hz, 1.45 amp. 13”H x 13.5”W x 3.25”D
• 12VDC or 24VDC selectable output. 1.40” 4.85” 4.85” 1.40”

• Single Class 2 Rated power limited output.


• Input fuse rated @ 3.5 amp/250V.
3.25”

1.20”

• Filtered and electronically regulated output. 0.75”


12.50”

• Short circuit and thermal overload protection.


11.00” 1.20”

0.5275”

1.40” 1.40”

• AC fail supervision (form "C" contacts).


• Low battery supervision (form "C" contacts).
• Battery presence supervision (form “C” contacts). 5.10” 5.10”

• Built-in charger for sealed lead acid 11.125”

or gel type batteries. 13.00”

• Automatic switch over to stand-by battery when 5.10”

AC fails. 6.50”

• Maximum charge current .7 amp.


• Zero voltage drop when switched over to 1.40” 1.3475”

battery backup.
3.25” 11.00” 3.25”

1.25” 10.00” 1.25”

• AC input and DC output LED indicators. 1.25”

• Accommodates up to two (2) 12VDC/7AH batteries.


3.25”

• Power supply, enclosure, cam lock and battery leads.

Agency Approvals
UL 294 UL Listed for Access Control MEA - NYC Department of
System Units. Buildings Approved.
UL 603 UL Listed Standard for Power
Supplies for Use with Burglar-
Alarm Systems. CSFM - California State Fire
Marshal Approved.
UL 1069 UL Listed Hospital Signaling and
Nurse Call Equipment.
UL 1481 UL Listed Standard for Safety for FM - Factory Mutual Approved.
Fire Protective Signaling Systems.

02/2005
FN-600ULX Data Sheet
Rev. DSFN-600ULX - J24E

Overview
• This power supply/charger converts a 115VAC / 60Hz input, to a
12VDC or 24VDC regulating output.

FN-600ULX
• 12VDC or 24VDC @ 6 amp supply current.

Specifications Enclosure Dimensions


• Input 115VAC / 60Hz, 1.9 amp. 13”H x 13.5”W x 3.25”D
• 12VDC or 24VDC selectable output. 1.40” 4.85” 4.85” 1.40”

• Single Class 2 Rated power limited output.


• Input fuse rated @ 3.5 amp/250V. 3.25”

• Filtered and electronically regulated output. 1.20”

• Short circuit and thermal overload protection.


12.50”

0.75”
11.00” 1.20”

• AC fail supervision (form "C" contacts).


0.5275”

1.40” 1.40”

• Low battery supervision (form "C" contacts).


• Battery presence supervision (form “C” contacts).
• Built-in charger for sealed lead acid
5.10” 5.10”

or gel type batteries. 11.125”

• Automatic switch over to stand-by 13.00”

battery when AC fails.


• Maximum charge current .7 amp.
5.10”

6.50”

• Zero voltage drop when switched


over to battery backup. 1.40” 1.3475”

• AC input and DC output LED indicators. 3.25” 11.00” 3.25”

• Accommodates up to two (2) 12VDC/7AH batteries.


1.25” 10.00” 1.25”

1.25”

• Power supply, enclosure, cam lock and battery leads. 3.25”

Agency Approvals
UL 294 UL Listed for Access Control CSFM - California State Fire
System Units. Marshal Approved.
UL 1481 UL Listed Standard for Safety for
Fire Protective Signaling Systems
FM - Factory Mutual Approved.
MEA - NYC Department of
Buildings Approved.

02/2005
FN-1024ULX Data Sheet
Rev. DSFN-1024ULX - J24E

Overview
• These power supply/chargers convert a 115VAC / 60Hz input, to a
24VDC regulating output.

FN-1024ULX
• Access Control applications:
24VDC @ 10 amp.
Fire Alarm applications:
24VDC @ 8 amp supply current w/10 amp during alarm.

Specifications Enclosure Dimensions


• Input 115VAC / 60Hz, 4.4 amp. 15.5”H x 12”W x 4.5”D
• 24VDC output. 2.25" 3.68"
12"
4.56"

• Single non-power limited output. 1.22"

• Input fuse rated @ 3.5 amp/250V.


• Filtered and electronically regulated output.
• Short circuit and thermal overload protection. 1.22"
4.5"
.875" 9.97" 1.3" 1.22"

• AC fail supervision (form "C" contacts). 2"


1" 1"

2"

• Low battery supervision (form "C" contacts).


• Battery presence supervision (form “C” contacts).
• Built-in charger for sealed lead acid or 8"

gel type batteries.


• Automatic switch over to stand-by battery when
13.25"
13.53"

AC fails.
• Maximum charge current 3.6 amp.
• Zero voltage drop when switched over to
3.25"

battery backup. 2.2"

• AC input and DC output LED indicators.


1.25"
1"

15.5"

• Accommodates up to two (2) 12VDC/12AH batteries.


• Power supply, enclosure, cam lock and battery leads.
1.22"

2.25" 3.68" 4.56"

Agency Approvals
UL 294 UL Listed for Access Control MEA - NYC Department of
System Units. Buildings Approved.
UL 1481 UL Listed Standard for Safety for
Fire Protective Signaling Systems.
CSFM - California State Fire
Marshal Approved.

02/2005
FN-642-ULADA, FN-842-ULADA, FN-1042-ULADA
Data Sheet Rev. FN-642/842/1042-ULADA- J24E

Overview

• The FN-642-ULADA, FN-842-ULADA and FN-1042-ULADA are extremely


cost effective voltage regulated remote NAC Power Extenders. They may be
connected to any 12 or 24 volt Fire Alarm Control Panel (FACP). Primary
applications include Notification Appliance Circuit (NAC) expansion
(supports ADA requirements) and will provide auxiliary power to support
system accessories.
FN-642-ULADA FN-842-ULADA FN-1042-ULADA
• 24VDC or 12VDC • 24VDC or 12VDC • 24VDC rated
rated @ 6.5 amp max. rated @ 8 amp max. @ 10 amp max.
• Four (4) Class A or • Four (4) Class A or • Four (4) Class A or
four (4) Class B outputs. four (4) Class B outputs. four (4) Class B outputs.
Specifications
• Two (2) Class A or two (2) Class B FACP inputs. • Horn/Strobe sync protocols include: Gentex®,
• Two (2) NC dry contact trigger inputs. System Sensor®, Faraday, Amseco.
• Four (4) Class A or four (4) Class B indicating • Temporal Code 3 Mode.
circuits. • Steady Mode.
• Two (2) Class B outputs may be paralleled for more • Input to Output Follower Mode (maintains
power on an indicating circuit. synchronization of notification appliance circuits).
• One (1) Aux. Power Output @ 1 amp supply current • March Time.
(w/battery back up). • Compatible with 24VDC or 12VDC fire panels.
• One (1) Aux. Power Output @ 1 amp supply current • Ground fault detection.
(w/o battery back up). • Input 115VAC.
• Signal Circuit Trouble Memory - facilitates quickly • AC fail, battery presence & low battery monitoring.
locating intermittent system trouble and eliminates • Accommodates up to two (2) 12VDC/12AH batteries.
costly and unnecessary service calls. LEDs indicate a • Power supply, logic board, red enclosure, cam lock,
prior fault (short, open, ground) has occurred on one transformer & battery leads.
or more signaling circuit outputs.
• 2 wire Horn/Strobe Sync mode allows audible
notification appliances (Horns) to be silenced while
visual notification appliances (Strobes) continue
to operate.

Continued on back.

02/2005
Agency Approvals Enclosure Dimensions
18"H x 14.5"W x 4.625"D
UL 864 UL Listed Control Units and 14.5"

Accessories for Fire Alarm Systems. 4.5"

UL 1481 UL Listed Standard for Safety for


Fire Protective Signaling Systems.
1.25"

4.5"
1.5" 6.5" 4.0" 1.5"
1.25" 1.25"

1.0"
1.5"

1.5"

NYC Department of Buildings Approved.


4.0"

18"
18" 18"

10"

California State Fire Marshal Approved. 10.0"

1.0" 1.0"

Factory Mutual Approved.


1.0" 1.5" 4.5"
4.5"

4.5"

1.25"

2.75" 7.25" 2.75"


14.5"
Introduction Ionization Smoke Sensor
Hochiki America Corporation provides its customers with
reliable, high quality fire detection equipment utilizing Features
the latest technology available. The AIE-EA ionization smoke sensor has a
computer-designed smoke chamber that can detect
Analog Sensors smoldering or fast-flaming fires.
Our new sensors are dramatically small in size like their The combination of a high signal-to-noise ratio and
predecessors the Hochiki America low profile conventional sensitivity stability make this sensor effective in a wide
smoke detectors. Yet they maintain the dependability range of environmental conditions.
Hochiki customers have come to rely on. This bulletin User programmable alarm thresholds.
documents all the NS Analog Sensors (ALG-EA, ALG-V A reliable and fully digital transmission method, which
AIE-EA, and ATG-EA).
is highly immune to noise.
Photoelectric Smoke Sensor The control panel is able to verify the status of any
device. Whether the device is dirty or approaching an
Features alarm condition. It can make this determination
The ALG-EA/-V photoelectric smoke chamber that can routinely.
detect smoldering or fast-flaming fires. It is possible to assign a priority to any device that is
The combination of a high signal-to-noise ratio and deemed necessary by the nature of the systems design.
sensitivity stability make this sensor effective in a wide There is an interrupt sequence, which can assign
range of environmental conditions. priority to fire and other similar signals.
User programmable alarm thresholds.
A reliable and fully digital transmission method, which is
highly immune to noise.
The control panel is able to verify the status of any device.
Whether the device is dirty or approaching an alarm
condition, it can make this determination routinely.
It is possible to assign a priority to any device that is AIE-EA
deemed necessary by the nature of the systems design.
There is an interrupt sequence, which can assign priority
to fire and other similar signals. AIE-EA Specifications
Radioactive Source Americium 241 (0.98 µCi)
Voltage Operating Range 24.0 ~ 40.7 VDC
Average Current Consumption 41.0 VDC MAXIMUM
Normal Mode (S-SC) 350 µ A Typical
460 µA Maximum
Low Power Mode (S-SC) 140 µA @ 0.75s
ALG-EA/-V 100 µA @ 1.50s
When Called (S-SC) 2mA (momentary)
ALG-EA/-V Specifications Alarm mode (S-SC) 8mA
Light Source GaAlAs Infrared Emitting Diode Remote LED (during alarm) 8mA
Voltage Operating Range 24.0 ~ 40.7 VDC Device Type Code A8 Hex
Average Current Consumption 41.0 VDC MAXIMUM Operating Temperature -10°~ 50°C
Normal Mode (S-SC) 390 µ A Typical Storage Temperature -20°~ 60°C
540 µA Maximum S-SC Protocol
Low Power Mode (S-SC) 120 µA @ 0.75s Half duplex, asynchronous communication
110 µA @ 1.50s Speed: 1200 bps
When Called (S-SC) 2mA (momentary) 1 stop bit, 1 parity bit
Alarm mode (S-SC) 8mA Error check: Check-sum, even parity check
Remote LED (during alarm) 8mA TX protocol control: polling, selecting, interrupt
Device Type Code 88 Hex TX code: 8 bit binary data
Operating Temperature -10°~ 50°C S-SC line resistance 50 Ohm MAX. (14~18 AWG. wiring)
Storage Temperature -20°~ 60°C Dimensions 3-15/16"D X 1-1/2"H
S-SC Protocol Weight 4.2 oz. (with YBN-NSA-4 base 5.9 oz.)
Half duplex, asynchronous communication Test Feature See control panel operating manual
Speed: 1200 bps Environment Indoor Use Only
1 stop bit, 1 parity bit Address setting method EEPROM (refer to control panel
Error check: Check-sum, even parity check (1 - 127 addresses) operating manual for address
TX protocol control: polling, selecting, interrupt setting procedure or utilize
TX code: 8 bit binary data Hochiki TCH-B100 - See Page 9)
S-SC line resistance 50 Ohm MAX. (14~18 AWG. wiring) Base Requirement HSB-NSA-6 or YBN-NSA-4
Dimensions 3-15/16"D X 1-1/2"H
Weight 3.4 oz. (with YBN-NSA-4 base 5.1 oz.)
Test Feature See control panel operating manual
Environment Indoor Use Only
Address setting method EEPROM (refer to control panel
(1 - 127 addresses) operating manual for address
setting procedure or utilize
Hochiki TCH-B100 - See Page 9)
Base Requirement HSB-NSA-6 or YBN-NSA-4
TECHNICAL BULLETIN HA-96
DECEMBER 2003 1
Heat Sensor Space involved.
Height of ceilings.
Features Surface condition of ceilings.
The ATG-EA heat sensor is a computer-designed heat Total area.
sensing device that can accurately detect fast-flaming fires. Air movement--stratification.
The combination of a high signal-to-noise ratio and Vent locations--velocities and dilution.
sensitivity stability make this sensor effective in a wide Deflections and obstructions.
range of environmental conditions.
User programmable alarm thresholds. Location Sensors
A reliable and fully digital transmission method, which is One smoke sensor covers 450 to 900 square feet.
highly immune to noise.
One heat sensor covers up to 2500 square feet.
The control panel is able to verify the status of any device.
Such as whether or not the device is approaching an Consider local conditions and codes along with engineering evaluations
alarm condition. The control panel can make this to determine the proper spacing and specifications.
determination routinely. Warning: HEAT SENSORS ARE NOT LIFE SAFETY DEVICES. WHERE LIFE
It is possible to assign a priority to any device that is SAFETY IS A FACTOR SMOKE SENSORS ARE RECOMMENDED.
deemed necessary by the nature of the systems design. Examples
There is an interrupt sequence, which can assign priority You may use 30-foot spacing on smooth ceilings for smoke sensors.
to fire and other similar signals. You may use 50-foot spacing on smooth ceilings for heat sensors.
Beams other obstructions extending more that 18" below the ceiling
reduce the effective range of the sensors. Such obstructions should
designate a new separation point, and be considered a border for a new
section.
ATG-EA Beams or other obstructions extending more that 8" but less than 18"
require reduced spacing at the perpendicular of the obstructions.
ATG-EA Specifications NOTE: FOR INFORMATION ON DIFFERING STYLES OF CONSTRUCTION
Heat Sensing Element Thermistor
CONSULT THE NFPA HANDBOOK, SECTION 72.
Voltage Operating Range 24.0 ~ 40.7 VDC
Average Current Consumption 41.0 VDC MAXIMUM Warning: DO NOT INSTALL HOCHIKI SMOKE SENSORS IN THE
FOLLOWING AREAS:
Normal Mode (S-SC) 350 µ A Typical
500 µ A Maximum Where temperatures are likely to exceed 100°F or fall below 32°F.
Low Power Mode (S-SC) 110 µA @ 0.75s Closer than 4 inches to any side wall.
100 µA @ 1.50s Where forced ventilation can dilute the smoke from a fire
When Called (S-SC) 2mA (momentary) In known areas of combustion such as kitchens or furnace rooms.
Alarm mode (S-SC) 8mA
Remote LED (during alarm) 8mA Testing
Device Type Code 98 Hex
Operating Temperature -10°~ 50°C Smoke Sensors
Storage Temperature -20°~ 60°C Remember, for a smoke sensor to operate efficiently, combustion
S-SC Protocol
Half duplex, asynchronous communication products must enter the outer chamber. Air flow, stratification, velocity,
Speed: 1200 bps stagnation, and migration all affect the efficiency and accuracy of the
1 stop bit, 1 parity bit sensor.
Error check: Check-sum, even parity check You may use an air flow meter to determine the movement of air within
TX protocol control: polling, selecting, interrupt
TX code: 8 bit binary data a structure.
S-SC line resistance 50 Ohm MAX. (14~18 AWG. wiring) Field testing equipment is available from Hochiki for testing the function
Dimensions 3-15/16"D X 1-9/16"H of the sensors. See the Hochiki Tester section in this bulletin and the
Weight 3.2 oz. (with YBN-NSA-4 base 4.9 oz.) control panel operation manual for more information.
Test Feature See control panel operating manual
Environment Indoor Use Only
Address setting method EEPROM (refer to control panel Maintenance
(1 - 127 addresses) operating manual for address Consult local codes and ordinances.
setting procedure or utilize
Hochiki TCH-B100 - See Page 9) Hochiki recommends biannual confirmation of functional operation and
Base Requirement HSB-NSA-6 or YBN-NSA-4 external appearance.
You can obtain field testing equipment from Hochiki. See the Hochiki
Proper placement of sensors Tester section in this bulletin for more information.
This section explains how to determine the number of sensors you
need, and where to place them. Heat Sensors
By following the guidelines listed in NFPA 72, base the number
and location of sensors on an engineering survey of the area to be There are two basic test methods that can be used to determine proper
protected. operation of the ATG-EA.
Factors to consider 1. Testing can be accomplished by use of the built in test feature.
Contents to be protected. For proper operation refer to the control panel operation manual.
Type of construction and use of structure. 2. Functional testing can be accomplished by using the TTA-1H
Human occupancy. heat sensor tester. See testers section.
Burning characteristics of contents
TECHNICAL BULLETIN HA-96
2 DECEMBER 2003
Manual cleaning procedures
BOTTOM VIEW OF ALG-EA
Cleaning the photoelectric sensor
OUTER COVER
This section explains how to clean the ALG-EA/-V sensors.
RECESS AND KEY Use the diagram to identify the sensor's parts.

OUTER COVER Tools


You will need:
Hochiki America's NSRT-A100 Cover Removal Tool
A small soft bristled artist's paint brush
Denatured alcohol
Clean dry compressed air

NOTE: Use only lint-free materials when cleaning the chambers of


the photoelectric smoke detector. Use of fibrous materials may result
in false alarms.

Remove and disassemble the sensor


Follow the steps in this section to prepare the sensor for cleaning:
1. Remove the sensor from its base.
2. Disassemble sensor by following the NSRT-A100 instructions found
on page 5 of this document.

OUTER COVER OUTER COVER


RECESS AND KEY
Clean the sensor
Follow the steps in this section to clean the sensor.
CAUTION: Do not attempt to remove the insect screen.
1. Remove the Outer Cover of the sensor as specified on page 5
and set aside.
2. Place the sensor in the palm of your left hand and grasp the
Chamber Cover with your right hand. Twist the Chamber Cover counter
clockwise until the Cover Tabs clear the Tab Catches. Lift and
separate the Chamber Cover from the Optical Unit.
3. Swab the Optical Unit with denatured alcohol using a small soft
bristled brush.
4. Use dry clean compressed air to dry the optical unit and to remove
any remaining particles.
ALIGNMENT 5. Clean the Chamber Cover and Outer Cover in the same manner.
ARROW 1
CHAMBER
COVER COVER Reassemble the sensor.
TABS Follow the steps in this section to reassemble the sensor.
(3 total
1 hidden) 1. Locate the Alignment Arrows on both the Chamber Cover and the
Optical Unit.
2. Set the Chamber Cover onto the Optical Unit while making sure that
SENSING TAB
CHAMBER
OPE
N SE CATCH Alignment Arrow 1 and Alignment Arrow 2 are aligned with one another.
CLO (3 TOTAL 3. Holding the sensor in your left hand and grasping the Chamber Cover
1 hidden)
with your right hand, rotate the Chamber Cover clockwise until the
Cover Tabs snap into the Tab Catches.
PHOTO-
DIODE 4. Place the Outer Cover of the sensor nose down on a flat surface.
5. Align the Outer Cover Keys with the Recess in the Outer Cover (two
OUTER orientations are possible, only one will fit properly).
COVER
KEY 6. With the Outer Cover Keys aligned with the Cover Recessed, press
OUTER down firmly on the back of the sensor. The sensor will snap into
COVER the Outer Cover. The sensor is now ready to be returned to the
KEY
IR LED base from which it was removed.
ALIGNMENT 7. The sensor should be re-tested by following the test procedure
ARROW 2 found in the control panel literature.
OPTICAL UNIT
(BLACK AREA)
EXPLODED VIEW OF ALG-EA NOTE: If after testing, the sensor is not working within the prescribed
range then return it to the manufacturer for servicing.

TECHNICAL BULLETIN HA-96


DECEMBER 2003 3
AIE Cleaning Instructions
This section explains how to clean the AIE-EA sensor. Use the
diagram to identify the sensor's part.

Tool
You will need:
Hochiki America's NSRT-A100 Cover Removal Tool
Soap solution (1 teaspoon of Lemon Joy to 1 gallon clean water)
Soap bristled brush
Clean dry compressed air
Distilled water
Vacuum

Remove and disassemble the sensor


Follow the steps in this section to prepare the sensor for cleaning:
1. Remove the sensor from its base.
2. Disassemble sensor by following the NSRT-A100 instructions
found on page 5 of this document. OUTER COVER
CAUTION: Only the Outer Cover may be cleaned with a soap RECESS AND KEY
solution. Never attempt to clean any other part of the sensor with a
soap solution. This may render the sensor inoperable.
DO NOT ATTEMPT TO REMOVE THE INSECT SCREEN !!!. BOTTOM VIEW OF AIE-EA

Clean the sensor OUTER COVER


Follow the steps in this section to clean the sensor.
1. Remove the Outer Cover of the sensor as specified on page 5 and
set aside.
2. Vacuum the Outer Chamber and Insect Screen to remove any
foreign matter from the sensor.
3. Submerse the Outer Cover in the soap solution and scrub with the
brush to remove any foreign matter from the Outer Cover.
4. Rinse the Outer Cover in distilled water and blow it dry with clean
compressed air.

Reassemble the sensor


Follow the steps in this section to reassemble the sensor:
1. Place the Outer Cover of the sensor nose down on a flat surface.
2. Align the Outer Cover Keys with the Recessed in the Outer Cover STATUS LEDS OUTER CHAMBER
(Two orientations are possible, only one will fit properly).
3. With the Outer Cover Keys aligned with the Outer Cover INSECT SCREEN
Recessed, press down firmly on the back of the sensor. The sensor
will snap into the Outer Cover. The sensor is now ready to be
returned to the base from which it was removed.
4. The sensor should be re-tested by following the test procedure
found in the control panel literature.
NOTE: If after testing, the sensor is not working within the
prescribed range, then return it to the manufacturer for
servicing.

OUTER COVER KEYS

EXPLODED VIEW OF AIE-EA

TECHNICAL BULLETIN HA-96


4
DECEMBER 2003
Sensor Cover Removal Instructions
LOCATOR
This section explains how to remove the outer cover from the
AIE-EA or the ALG-EA/ ALG-V by using the NSRT-A100.

Tool
You will need:
Hochiki America's NSRT-A100 tool

Remove and disassemble the sensor


Follow the steps in this section for removal of the sensor cover:
1. Place the sensor to be disassembled on the NSRT-A100 tool
making sure that the Locator on the sensor is aligned as shown
on the diagram.
2. Using your thumb and index finger rotate the sensor back and
forth until it drops into place on the NSRT-A100.
3. Grasp the sensor firmly and rotate the sensor clockwise
(approximately 30 deg.) until the Locator on the sensor lines up
with the Mounting Ears of the NSRT-A100. The contact blades
on the sensor will engage on the NSRT-A100 and will prevent ALIGN
further rotation. LOCATOR
4. The sensor cover is now disengaged from the sensor body and can HERE
be removed by pulling the sensor cover away from the NSRT- MOUNTING
A100. EARS
5. After the cover has been removed, refer to the sensor cleaning
instructions to clean and reassemble the sensor.
ROTATE
TO
REMOVE
COVER
ALIGN
LOCATOR
HERE

NSRT-A100

TECHNICAL BULLETIN HA-96


DECEMBER 2003 5
Testers
The TSE-A100 smoke detector tester
The Hochiki TSE-A100 is one of the most advanced units of its kind and
is the result of extensive research and development aimed at making the
job of testing sensors a simple and efficient operation.

The TSE-A100 can be used to test all types of smoke sensors by


applying smoke from an internal smoke source.
Telescopic Pole
Features
The TSE-A100 employs telescoping construction for easy adjustment
to ceiling height.
Simple operating controls are located on the base of the unit.
The TSE-A100 houses its own source of smoke (punk sticks) within a
special chamber that isolates the combustion material from the
outside. This unique design enables the tester safely to generate a
stable volume of smoke.
The unit comes with a shoulder-sling carrying case for easy
portability from one site to another.
The TSE-A100 extends from 5.25 feet to 14.1 feet.

Power Indicator Screw

Punk Stick Holder Retainer


Preparing the TSE-A100
This section explains how to prepare the TSE-A100 to test smoke
Combustion Chamber sensor.
Punk Stick 1. Remove the TSE-A100 from its carrying case.
2. Unscrew the combustion chamber from the bottom of the TSE-A100
3. Unscrew the punk stick holder retainer from the combustion chamber.
4. Insert a punk stick into the punk stick holder in the combustion
chamber.
5. Light the punk stick with a flame.
6. Reassemble the combustion chamber.
7. Screw the combustion chamber back into the bottom of the TSE-A100
8. Extend the telescopic pole of the TSE-A100 to a length which
Instruction Label enables you to reach the detector you wish to test.

Testing a detector
Once you have prepared the TSE-A100, follow the steps in this section
to test smoke detectors.
NOTE: Allow 30 to 60 seconds after igniting punk stick for sufficient
smoke generation. For proper airflow, observe battery polarity.
1. Rotate the combustion chamber so the #2 arrow lines up with the
power indicator screw. The fan powers on and a steady flow of smoke
is released from the tip of the TSE-A100.
2. Raise the extended tip of the TSE-A100 to within 6-8" of the sensor.
TSE-A100 specifications The sensor should alarm.
Rated Voltage 3 VDC
Battery D size (2) Storing the TSE-A100
Combustion material Punk stick (7mm diameter, 150mm long) This section explains how to store the TSE-A100 after use.
Weight 5 pounds 1. Rotate the combustion chamber to the #1 position to turn the power
Maximum length 14.1 feet off.
2. Compress the telescopic pole to its shortest length.
3. Replace the TSE-A100 in its carrying case.
4. Store in a cool, dry place.
5. For extended storage, remove the batteries.
TECHNICAL BULLETIN HA-96
6 DECEMBER 2003
The TTA-1H Heat Sensor Tester ATG-EA
View of TTA-1H
The TTA-1H is a state of the art heat sensor tester. It is the most in relationship
advanced heat testing device of its kind. It is the result of intense to sensor
research and developement aimed at making the job of testing self
restoring heat devices a simple and efficient operation.
Lightweight Head
Features with built in
Quick response ceramic heater element. circulation fan
Built in circulation fan for even distribution of heat.
Swivel mounted head for easy access to heat sensor.
Rubber contact points to protect the heat sensor, yet allowing
good contact for rapid testing.
Inline switch between test pole and battery pack adding to the
simple and easy operation.
Power indicating LED on bottom of test head.
Three section pole with friction power locks.
Use of portable battery pack with belt mount. Adjustable
Optional use shoulder strap for battery pack. aluminum pole
Battery pack protected by a 10A circuit breaker.
Special calibration plate provided so as to perform a quick
periodic calibration check.

Top View Of TTA-1H Head


Special Quick Response
Rubber Bumbers
Ceramic Heater and Pad
Testing a heat sensor
This section explains how to use the TTA-1H to test
smoke sensors.

WARNING:
DO NOT USE THIS DEVICE ON NON-RESTORABLE
HEAT SENSORS OR DETECTORS!!!!

1. Connect 12Volt plug from the TTA-1H into the


battery pack.

2. Raise the extended head of the TTA-1H up to the


Mounting Knobs the sensor, and slip the head over the sensor.

3. Rotate the HDT-380 until it is snug over the device.


Specifications Tester and Pole
4. Slide the power switch located at the bottom of the
Operating Voltage 12 VDC pole to the on position. The sensor should alarm
Current Consumption between 5 and 15 seconds.
Normal Operation 4 amps
Maximum Surge 14 amps (2sec. typical) 5. Once the sensor has alarmed remove the TTA-1H
Heater Temperature 380°F (maximum) and slide the power switch to the off position.
Pole extension 3 sections 3.6ft.(min.) 8.8ft.(max.)
Weight Head 15.87oz. 6. Testing is now complete for that sensor.
Pole 2.15 lbs.
Dimensions Head 4.33in.D X 6.10in.H 7. For added details refer to operation manual.
Pole 1.38in.D

Battery Pack
Battery type NICAD 12V. 2.8Ah
Life 500 charges (minimum)
Number of sensors tested 200 max. (5sec. ON - 60sec. OFF)
per charge 150 max. (10sec. ON - 60sec. OFF)
Weight 2.2 lbs.
Dimensions 8.03in.L X 2.99in.W X 2.17D
Charger 12VDC 350mA
TECHNICAL BULLETIN HA-96
DECEMBER 2003 7
Reactions to particle size
The following table shows how photoelectric and ionization sensors react to materials of varying particle size. The
solid lines indicate absolute size. The dashed lines identify areas to consider when engineering a job using Hochiki
sensors.
Particle Size in Microns
1000 100 10 1 0.1 0.01 0.001
Rain Fine Rain Mist Wood Smoke

Sulfuric Acid Mist Cigarette Smoke

Pine Resin Smoke

Carbon Powder

Pigments

Ammonia Vapor

Smoke of Zinc Oxide

Gas Molecules

Flare Smoke (magnesium-oxide)

Chimney Smoke

Factory Dust

Dust in Clean Air

Pollen Yellow Ochre

Bacteria Viruses
Particles Visible
To naked eye Through microscope Through high power microscope
Hochiki Sensors
Photoelectric Smoke Sensors
Ionization Smoke Sensors

Particle Size and the Hochiki Sensors

TECHNICAL BULLETIN HA-96


July 2000 8
TCH-B100-NS Programmer operating instruction
TCH-B100-NS is a hand held programmer. It is designed for use with
the following products: ALG-V/ ALG-EA, AIE-EA, ATG-EA,
FRCME-S, FRCME-P, FRCME-4, SOM, R2M, RM.

Features Remote
The TCH-B100-NS is a compact unit and easy to use. Programming Jack
The TCH-B100-NS provides address setting and reading.
Has the diagnostic ability to display the analog value.
Use 9V battery
Automatically increments the address ready to set the address of
the next sensor.
Automatically switches the power off after use
Programming
Programming Buttons Buttons Display
Left Gray Button: Power on. Automatically reads the address of a
sensor. Subsequent operations will advance the
device address by ten.
Right Gray Button: Power off. Advances the device address by
one.
Red Button: Stores the displayed address to the device and is
used to read sensor analog levels.

Address Setting
Remote Programming Cable
1. Install sensor onto programmer, ensuring that sensor protrusion (All Modules except DCP-FRCME-S
aligns with programmer grooves. and FRCME-P)
2. Press the left gray button to switch programmed on. A battery
check message will appear followed by the devices address
( un-programmed sensors will read address 127). To Remote
3. Set the required address by incrementing the left and right gray Programming
buttons (the display will show three red flashing dots if the address Jack
being programmed is different from the device's current address).
4. When the desired address is present press the red button to store
that address. The three red dots on the display will no longer be Remote Programming Cable
(DCP-FRCME-P)
present.

Reading Analog Value:


NOTE: For Ion Sensor, do not read analog value for 30 seconds
Remote
( stabilization period).
Programming Cable
1. Install the sensor and power up programmer as previously described. (DCP-FRCME-S)
2. Press the red button. An "A" will appear on the display followed
by the analog value. This value will be continuously updated for
three minutes or until the unit is turned off.

Display Message:
bAt - On upon power up ( battery check). Also on when battery is
low. Low battery good for up to 3,000 address setting
operation.
E0 - Attempting to set an address beyond 127.
E1 - Attempting to program an address with no device connected.
E2 - Can not find device after power up.
E3 - Invalid sensor response
E4 - Can not find the device program.
E5 - Device read error.
E6 - Fail during Analog value reading.

TECHNICAL BULLETIN HA-96


DECEMBER 2003 8
Introduction
Hochiki America Corporation provides its customers with reliable, high
quality fire detection equipment utilizing the latest technology available.
NS Detectors SLR-835/-835H/-835B-2/-
Our new conventional NS detectors are dramatically small in size like their 835BH-2/-835B-4/-835BH-4
predecessor the original low profile conventional smoke detectors. Yet Front View Of All Versions Back View Of Baseless Version
they maintain the dependability Hochiki customers have come to rely on.
This bulletin documents all the NS Conventional Smoke Detectors SLR-835 Specifications
(SLR-24/-24V/-24VN/-24H, SLR-835/-835H/-835HW*/-835B-2/ Light Source GaAlAs Infrared Emitting Diode
-835B-2W*/-835BH-2/-835BH-2W*/-835B-4/-835B-4W*/ Voltage Operating Range
-835BH-4/-835BH-4W*/, SIJ-24 and DCD-135/190). Nominal Rated Voltage 12.0 VDC or 24.0 VDC
* W= Indicates white Working Voltage 8.0 ~ 35.0 VDC
Maximum Allowable Voltage 42.0 VDC MAXIMUM
Maximum Ripple 15%
Photoelectric Smoke Detector Average Current Consumption
Features Supervisory Current 38 A (at 12VDC)
The SLR series photoelectric smoke detector has a computer- 55 A (at 24VDC)
designed smoke chamber that can detect smoldering or 70 A (at 35VDC)
fast-flaming fires. Surge Current 200 A (at 24VDC)
Maximum Allowable Current 150mA Maximum
The SLR series has a wider range than other photoelectric Minimum, Alarm Trip Current 6mA
detectors. It's coverage extends into the range of the Ionization Alarm Current For SLR-835B-4 48mA (at 12VDC, 25°C)
detector. This makes the SLR series a uniquely versatile smoke 34mA (at 24VDC, 25°C)
detector. 52mA (at 35VDC, 25°C)
The combination of a high signal-to noise ratio and sensitivity Heat Element Rating
stability make this sensor effective in a wide range of ( SLR-835H only) 135°F
environmental conditions. Operating Temperature -10° ~ +50°C
Two indicator LEDS set at 180 degrees from each other offer Storage Temperature -20° ~ +60°C
360 degree viewing of detector status. Dimensions of the SLR-835
and SLR-835H 3-15/16"D X 2.0"H W/TRIM RING
Automatic built-in test feature. Indicates when chamber is dirty
Dimensions of the
or if sensitivity has shifted outside its intended range. It will SLR-835B-2, and -4 3-15/16"D X 2.4"H
automatically indicate its status with no testing. SLR-835BH-2, and 835BH-4 3-15/16"D X 2.4"H
A hidden self locking feature (requires activation). Weight of the SLR-835
Inter-changeability with SLK series and SIH series detectors. and SLR-835H 3.1 oz. (with NS4-100 base 4.6 oz.)
Weight of the
SLR-835B-2, and -4 3.96 oz. (with Trim Ring 5.76 oz.)
SLR-835BH-2, and 835BH-4 3.96 oz. (with Trim Ring 5.76 oz.)
Test Feature Automatic built-in test feature
(see HA-06-074 page 4)
Environment Indoor Use Only
Base Requirement NS6 Series, NS4 Series, and HSC
SLR-24H SLR-24/ -24V
For SLR-835 Only Relay Series
SLR-24/-24V/-24VN/-24H Specifications Mounting Requirement For
SLR-835B-2,/-835BH-2/-
Light Source GaAlAs Infrared Emitting Diode 835B-4/-835BH-4
Voltage Operating Range Baseless Detector Trim Ring SLR-835 Baseless
Nominal Rated Voltage 24.0 VDC
Working Voltage 15.0 ~ 33.0 VDC Ionization Smoke Detector
Maximum Allowable Voltage 42.0 VDC MAXIMUM Features
Allowable Wave Form Filtered DC, 5V Ripple Max. The SIJ-24 ionization smoke detector uses a dual-chamber design
Average Current Consumption that detects smoldering or fast-flaming fires.
Supervisory Current 45 A (at 24VDC) The combination of a high signal-to-noise ratio and sensitivity
Surge Current 160 A (at 24VDC) stability make this sensor effective in a wide range of
Maximum Allowable Current 150mA Maximum environmental conditions.
Minimum, Alarm Trip Current 6mA A single radioactive source ionizes the air in both the detection
Operating Temperature -10° ~ +50°C and reference chambers. Though the reference chamber is not
Storage Temperature -20° ~ +60°C sealed, it provides a clean air comparison for the detection
Heat Element Rating chamber.
( SLR-24H only) 135°F This dual-chamber design makes the SIJ-24 remarkably stable in
Dimensions 3-15/16"D X 1-1/2"H a wide range of environmental conditions.
Weight 3.1 oz. (with NS4-100 base 4.6 oz.)
Test Feature Automatic built-in test feature
(see HA-06-060 page 4)
Environment Indoor Use Only
Base Requirement NS6 Series, NS4 Series, and HSC
Relay Series SIJ-24
TECHNICAL BULLETIN HA-97
OCTOBER 2002 Page 1 of 7
SIJ-24 Specifications Proper placement of detectors
Radioactive Source Americium 241 (0.50 Ci) This section explains how to determine the number of detectors
Voltage Operating Range you need, and where to place them.
Nominal Rated Voltage 24.0 VDC By following the guidelines listed in NFPA 72, base the number and
Working Voltage 15.0 ~ 33.0 VDC location of detectors on an engineering survey of the area to be
Maximum Allowable Voltage 42.0 VDC MAXIMUM protected.
Allowable Wave Form Filtered DC, 5V Ripple Max.
Average Current Consumption
Factors to consider
Contents to be protected
Supervisory Current 45 A (at 24VDC) Type of construction and use of structure
Surge Current 200 A (at 24VDC) Human occupancy
Maximum Allowable Current 150mA Maximum Burning characteristics of contents
Minimum, Alarm Trip Current 6mA Space involved
Operating Temperature -10° ~ +50°C Height of ceilings
Storage Temperature -20° ~ +60°C Surface condition of ceilings
Dimensions 3-15/16"D X 1-1/2"H Total area
Weight 3.0 oz. (with NS4-100 base 4.5 oz.) Air movement--stratification
Built-in test feature with magnet Vent locations--velocities and dilution
Test Feature
Deflections and obstructions
activation (see HA-06-060 page 4)
Environment Indoor Use Only Locating Detectors
Base Requirement NS6 Series, NS4 Series, and HSC One smoke detector covers 450 to 900 square feet.
Relay Series One heat detector covers up to 2500 square feet.
Consider local conditions and codes along with engineering
Heat Detectors evaluation to determine the proper spacing and specifications.
WARNING: HEAT DETECTORS ARE NOT LIFE SAFETY DEVICES. WHERE
Features LIFE SAFETY IS A FACTOR SMOKE DETECTORS ARE RECOMMENDED.
The DCD-135/190 heat detectors are computer-designed heat
detectors that can accurately detect fast-flaming fires. Examples
The combination of a high signal-to-noise ratio and sensitivity You may use 30-foot spacing on smooth ceilings for smoke detectors.
stability make this detector effective in a wide range of You may use 50-foot spacing on smooth ceilings for heat detectors.
environmental conditions. Beams or other obstructions extending more than 18" below the ceiling
360 degree viewing of detector status using two LEDs. reduce the effective range of the sensors. Such obstructions should
Bi-color LEDs. Blinks Green for normal standby and then turns designate a new separation point, and be considered a border for a new
steady Red when detectors goes into alarm. section.
Inter-changeability with SIJ-24 and SLR-24. Beams or other obstructions extending more than 8" but less than 18"
A hidden self locking feature (requires activation). require reduced spacing at the perpendicular of the obstructions.
NOTE: FOR INFORMATION ON DIFFERING STYLES OF
CONSTRUCTION CONSULT THE NFPA HAND BOOK, SECTION 72
WARNING: DO NOT INSTALL HOCHIKI SMOKE DETECTORS IN THE
FOLLOWING AREAS:
Where temperatures are likely to exceed 100°F or fall below 32°F
Closer than 4 inches to any side wall
DCD-135/ 190 Where forced ventilation can dilute the smoke from a fire
In known areas of combustion such as kitchens or furnace rooms
DCD-135/190 Specifications
Heat Sensing Element Thermistor Testing
Voltage Operating Range Smoke Detectors
Nominal Rated Voltage 24.0 VDC Remember, for a smoke detector to operate efficiently, combustion
Working Voltage 15.0 ~ 33.0 VDC products must enter the outer chamber. Air flow, stratification,
Maximum Allowable Voltage 42.0 VDC MAXIMUM velocity, stagnation, and migration all affect the efficiency and
Allowable Wave Form Filtered DC, 5V Ripple Max. accuracy of the detector.
Average Current Consumption You may use an air flow meter to determine the movement of air
Supervisory Current 35 A (at 24VDC) within a structure.
Surge Current 160 A (at 24VDC) Field testing equipment is available from Hochiki for testing the
Maximum Allowable Current 150mA Maximum function of the detectors. See the Hochiki Testers section in this
Minimum, Alarm Trip Current 6mA bulletin and the installation instructions for more information.
Operating Temperature -10° ~ +50°C Maintenance
Storage Temperature -20° ~ +60°C Consult local codes and ordinances.
Dimensions 3-15/16"D X 1-1/2"H Hochiki recommends bi-annual confirmation of functional operation
Weight 3.1 oz. (with NS4-100 base 4.6 oz.) and external appearance.
Test Feature See page 7 of this bulletin You can obtain field testing equipment from Hochiki. See the Hochiki
Fixed Temperature Rating Testers section in this bulletin for more information.
Model DCD-135 135°F
Model DCD-190 190°F Heat Detectors
Rate of Rise Rating (Both) 15°F/min. There is one basic test method that can be used to determine proper
Environment Indoor Use Only operation of the DCD-135/190
Base Requirement NS6 Series, NS4 Series, and HSC 1 Functional testing can be accomplished by using the TTA-1H
Relay Series heat detector/sensor tester. See testers section.
TECHNICAL BULLETIN HA-97
OCTOBER 2002 Page 2 of 7
Manual cleaning procedures
BOTTOM VIEW OF SLR-24/-24V/-24VN/-835/-835H
ALIGNMENT ARROW Cleaning the photoelectric detector
This section explains how to clean the SLR-24/-24V/-24VN/-24H/-835
and SLR-835H detectors.
Use the diagram to identify the detector's parts.

Tools
You will need:
Hochiki America's NSRT-A100 Cover Removal Tool
A small soft-bristled artist's paint brush
Denatured alcohol
Clean dry compressed air

NOTE: Use only lint-free materials when cleaning the chambers of


the photoelectric smoke detector. Use of fibrous materials may result
in false alarms.

Remove and disassemble the detector


ENCLOSURE Follow the steps in this section to prepare the detector for cleaning:
1. Remove the detector from its base.
OUTER COVER
OUTER COVER NUB 2. Disassmble detector by following the NSRT-A100 instructions found
on page 5 of this document.
Clean the detector
Follow the steps in this section to clean the detector.
CAUTION: Do not attempt to remove the insect screen.
1. Remove the Outer Cover of the detector as specified on page 5
and set aside.
2. Place the detector in the palm of your left hand and grasp the
Chamber Cover with your right hand. Twist the Chamber Cover counter
clockwise until the Cover Tabs clear the Tab Catches. Lift and
separate the Chamber Cover from the Optical Unit.
3. Swab the Optical Unit with denatured alcohol using a small soft
ALIGNMENT bristled brush.
ARROW 1 4. Use dry clean compressed air to dry the optical unit and to remove
CHAMBER any remaining particles.
COVER COVER
TABS 5. Clean the Chamber Cover and Outer Cover in the same manner.
(3 total
1 hidden)
Reassemble the detector
Follow the steps in this section to reassemble the detector.
SENSING OPE TAB 1. Locate the Alignment Arrows on both the Chamber Cover and the
CHAMBER N SE CATCH
CLO (3 total Optical Unit.
1 hidden) 2. Set the Chamber Cover onto the Optical Unit while making sure that
Alignment Arrow 1 and Alignment Arrow 2 are aligned with one another.
PHOTO- 3. Holding the detector in your left hand and grasping the Chamber Cover
DIODE with your right hand, rotate the Chamber Cover clockwise until the
Cover Tabs snap into the Tab Catches.
4. Place the Outer Cover of the detector nose down on a flat surface.
5. Align the Outer Cover Nub with the Alignment Arrow on the Enclosure
(two orientations are possible, only one will fit properly).
6. With the Outer Cover Nub aligned with the Alignment Arrow, press
IR LED down firmly on the back of the detector. The detector will snap into
ALIGNMENT
ARROW 2 the Outer Cover. The detector is now ready to be returned to the
base from which it was removed.
EXPLODED VIEW OF SLR-24/ -24V/-24VN/-835/-835H 7. The detector should be re-tested by following the test procedure
found in the control panel literature.
NOTE:
1. ON SLR-24H, SLR-835BH AND SLR-835H TAKE CARE NOT
TO DISTURB OR DAMAGE THE THERMISTOR HEAT
ELEMENT DURING THE CLEANING PROCEDURE
2. If after testing, the detector is not working within the Prescribed
range then return it to the manufacturer for servicing.

TECHNICAL BULLETIN HA-97 Page 3 of 7


OCTOBER 2002
Disassembly, Cleaning, And Test Procedure For
SLR-835B Series Detectors

Disassembly Procedure
SCREWDRIVER HEAD
1. Remove the detector from the trim ring.

2. Disassemble detector by placing one screwdriver under the


TAB as shown in Diagram 1. TAB

3. Place the second screwdriver under the next adjacent TAB DIRECTION TO
pushing it the direction shown in Diagram 1. MOVE TAB

DIAGRAM 1
4. Push the screwdriver outward from the center of the
detector and lift the Enclosure upward.

5. Do the same with the second screwdriver, but do not


remove it. Keep it in place.

6. Take the first screwdriver and place it under the second


TAB. Push the TAB outward and lift the Enclosure upward.

7. With three Tabs freed, the Enclosure should finally remove


TAB LOCATIONS
easily with the application of the screwdriver.

Cleaning Procedure

1. The cleaning instructions are the same as for the SLR-24


Series Detectors (refer to page 3).

Testing Procedure BACK OF THE SLR-835 BASELESS

1. The SLR-835B series photoelectric smoke detector has a


built-in test feature that will automatically indicate a change in
sensitivity.

2. When the detector's LEDs blink green. This is an


indication that it is within it's listed sensitivity window.

3. When the detector's LEDs begin to blink red, then this


indicates the detector's sensitivity is out of its listed range.

4. For go-no-go testing refer to diagram 2 magnet placement.


Detector should alarm within 10 seconds.

DIAGRAM 2

TECHNICAL BULLETIN HA-97


OCTOBER 2002 Page 3A of 7
SIJ Cleaning Instructions
This section explains how to clean the SIJ-24 detectors. Use the
diagram to identify the detector's parts. CONTACT BLADES

Tools
You will need:
Small blade type screw driver.
Soap solution (1 teaspoon of Lemon Joy to 1 gallon clean water)
Soft bristled brush
Clean dry compressed air
Distilled water
Vacuum

Remove and disassemble the detector


Follow the steps in this section to prepare the detector for cleaning:
1. Remove the detector from its base, and place it with the bottom up.
2. Take the small screw driver and gently pry each of the Outer Cover OUTER COVER
Clips outward from the center of the detector, and at the same time CLIP - LARGE
lifting the enclosure upward by the Contact Blades. This will free
the Outer Chamber/ Enclosure form the Outer Cover OUTER COVER
CLIPS (3 SMALL)
CAUTION: Only the Outer Cover may be cleaned with a soap solution. BOTTOM VIEW OF SIJ-24
Never attempt to clean any other part of the detector with
a soap solution. This may render the detector inoperable.
DO NOT ATTEMPT TO REMOVE THE INSECT SCREEN. OUTER COVER

Clean the sensor


Follow the steps in this section to clean the detector.
1. Remove the Outer Cover of the detector as specified above, and
set aside.
2. Vacuum the Outer Chamber to remove any foreign matter from the
detector.
3. Submerse the Outer Cover in the soap solution and scrub with the
brush to remove any foreign matter from the Outer Cover.
4. Rinse the Outer Cover in distilled water and blow it dry with
clean compressed air.

Reassemble the detector


Follow the steps in this section to reassemble the detector.
1. Place the Outer Cover of the detector nose down on a flat surface.
2. Align the Outer Cover Clips with the Enclosure Keys (There is STATUS LEDS
one large clip and three small clips, observe orientation).
3. With the Outer Cover Clips aligned with the Enclosure Keys, OUTER CHAMBER
press down firmly on the back of the detector. The detector will
snap into the Outer Cover. The detector is now ready to be (ONE HIDDEN)
returned to the base from which it was removed.
4. The detector should be re-tested by following the test procedure
found in the detectors installation instructions (HA-06-060).

NOTE: If, after testing, the detector is not working within the prescribed
range, then return it to the manufacturer for servicing.

ENCLOSURE KEYS
(4 TOTAL TWO ARE HIDDEN)
CONTACT BLADE

EXPLODED VIEW OF SIJ-24

TECHNICAL BULLETIN HA-97


OCTOBER 2002
Page 4 of 7
SLR-24/-24V/-24VN/-835 Cover Removal Instructions
This section explains how to remove the outer cover from the
SLR-24/-24V/-24VN/-835 by using the NSRT-A100.

Tools
You will need:
Hochiki America's NSRT-A100 tool

Remove and disassemble the SLR-24/- 24V/-24VN/-835


Follow the steps in this section for removal of the SLR-24/-24V/-24VN/-835
cover:

1.Place the SLR-24/-24V/-835 to be disassembled on the


NSRT-A100 tool, making sure that the Locator on the SLR-24/-24V/
-24VN/-835 is aligned as shown on the diagram.

2.Using your thumb and index finger rotate the SLR-24/-24V/-24VN/-835


back and forth until it drops into place on the NSRT-A100.

3.Grasp the SLR-24/-24V/-24VN/-835 firmly and rotate it clockwise


approximately 30 deg.) until the Locator on the SLR-24/24V/-24VN/-835
lines up with the Mounting Ears of the NSRT-A100. The contact
blades on the SLR-24/-24V/-24VN/-835 will engage on the NSRT-A100
and will prevent further rotation.

4.The SLR-24/-24V/-24VN/-835 cover is now disengaged from the body


and can be removed by pulling the SLR-24/-24V/-24VN/-835 cover away LOCATOR
from the NSRT-A100.
5.After the cover has been removed, refer to the SLR-24/-24V/-24VN/-835/
cleaning instructions to clean and reassemble the SLR-24/-24V/-24VN/-835.

ALIGN
LOCATOR
HERE
MOUNTING
EARS

ROTATE
TO
REMOVE
COVER
ALIGN
LOCATOR
HERE

NSRT-A100

TECHNICAL BULLETIN HA-97


OCTOBER 2002
Page 5 of 7
Testers
The TSE-A100 smoke detector tester
The Hochiki TSE-A100 is one of the most advanced units of its kind and
is the result of extensive research and development aimed at making the
job of testing detectors a simple and efficient operation.

The TSE-A100 can be used to test all types of smoke detectors by


applying smoke from an internal smoke source.
Telescopic Pole
Features
The TSE-A100 employs telescoping construction for easy adjustment
to ceiling height.
Simple operating controls are located on the base of the unit.
The TSE-A100 houses its own source of smoke (punk sticks) within a
special chamber that isolates the combustion material from the
outside. This unique design enables the tester safely to generate a
stable volume of smoke.
The unit comes with a shoulder-sling carrying case for easy
portability from one site to another.
The TSE-A100 extends from 5.25 feet to 14.1 feet.

Power Indicator Screw

Punk Stick Holder Retainer


Preparing the TSE-A100
This section explains how to prepare the TSE-A100 to test smoke
Combustion Chamber detectors.
Punk Stick 1. Remove the TSE-A100 from its carrying case.
2. Unscrew the combustion chamber from the bottom of the TSE-A100
3. Unscrew the punk stick holder retainer from the combustion chamber.
4. Insert a punk stick into the punk stick holder in the combustion
chamber.
5. Light the punk stick with a flame.
6. Reassemble the combustion chamber.
7. Screw the combustion chamber back into the bottom of the TSE-A100
8. Extend the telescopic pole of the TSE-A100 to a length which
enables you to reach the detector you wish to test.
Instruction Label
Testing a detector
Once you have prepared the TSE-A100, follow the steps in this section
to test smoke detectors.
NOTE: Allow 30 to 60 seconds after igniting punk stick for sufficient
smoke generation. For proper airflow, observe battery polarity.
1. Rotate the combustion chamber so the #2 arrow lines up with the
power indicator screw. The fan powers on and a steady flow of smoke
is released from the tip of the TSE-A100.
2. Raise the extended tip of the TSE-A100 to within 6-8" of the detector.
TSE-A100 specifications The detector should alarm.
Rated Voltage 3 VDC
Battery D size (2) Storing the TSE-A100
Combustion material Punk stick (7mm diameter, 150mm long) This section explains how to store the TSE-A100 after use.
Weight 5 pounds 1. Rotate the combustion chamber to the #1 position to turn the power
Maximum length 14.1 feet off.
2. Compress the telescopic pole to its shortest length.
3. Replace the TSE-A100 in its carrying case.
4. Store in a cool, dry place.
5. For extended storage, remove the batteries.
TECHNICAL BULLETIN HA-97
OCTOBER 2002
Page 6 of 7
The TTA-1H Heat Detector Tester DCD-135/190
View of TTA-1H
The TTA-1H is a state of the art heat detector tester. It is the most in relationship
advanced heat testing device of its kind. It is the result of intense to detector
research and development aimed at making the job of testing self
restoring heat devices a simple and efficient operation.
Lightweight Head
Features with built in
Quick response ceramic heater element. circulation fan
Built in circulation fan for even distribution of heat.
Swivel mounted head for easy access to heat detector.
Rubber contact points to protect the heat detector, yet allowing
good contact for rapid testing.
Inline switch between test pole and battery pack adding to the
simple and easy operation.
Power indicating LED on bottom of test head.
Three section pole with friction power locks.
Use of portable battery pack with belt mount. Adjustable
Optional use shoulder strap for battery pack. aluminum pole
Battery pack protected by a 10A circuit breaker.
Special calibration plate provided so as to perform a quick
periodic calibration check.

Top View Of TTA-1H Head


Special Quick Response
Rubber Bumpers
Ceramic Heater and Pad
Testing a heat detector
This section explains how to use the TTA-1H to test
smoke detectors.

WARNING:
DO NOT USE THIS DEVICE ON NON-RESTORABLE
HEAT SENSORS OR DETECTORS.

1. Connect 12Volt plug from the TTA-1H into the


battery pack.

2. Raise the extended head of the TTA-1H up to the


Mounting Knobs the detector, and slip the head over the detector.

3. Rotate the TTA-1H until it is snug over the device.


Specifications Tester and Pole
4. Slide the power switch located at the bottom of the
Operating Voltage 12 VDC pole to the on position. The detector should alarm
Current Consumption between 5 and 15 seconds.
Normal Operation 4 amps
Maximum Surge 14 amps (2sec. typical) 5. Once the detector has alarmed remove the TTA-1H
Heater Temperature 380°F (maximum) and slide the power switch to the off position.
Pole extension 3 sections 3.6ft.(min.) 8.8ft.(max.)
Weight Head 15.87oz. 6. Testing is now complete for that detector.
Pole 2.15 lbs.
Dimensions Head 4.33in.D X 6.10in.H 7. For added details refer to operation manual.
Pole 1.38in.D

Battery Pack
Battery type NICAD 12V. 2.8Ah
Life 500 charges (minimum)
Number of detectors tested 200 max. (5sec. ON - 60sec. OFF)
per charge 150 max. (10sec. ON - 60sec. OFF)
Weight 2.2 lbs.
Dimensions 8.03in.L X 2.99in.W X 2.17D
Charger 12VDC 350mA
TECHNICAL BULLETIN HA-97
OCTOBER 2002
Page 7 of 7
Reactions to particle size
The following table shows how photoelectric and ionization detectors react to materials of varying particle size. The
solid lines indicate absolute size. The dashed lines identify areas to consider when engineering a job using Hochiki
detectors.
Particle Size in Microns

Rain Fine Rain Mist Wood Smoke

Sulfuric Acid Mist Cigarette Smoke

Pine Resin Smoke

Carbon Powder

Pigments

Ammonia Vapor

Smoke of Zinc Oxide

Gas Molecules

Flare Smoke (magnesium-oxide)

Chimney Smoke

Factory Dust

Dust in Clean Air

Pollen Yellow Ochre

Bacteria Viruses
Particles Visible
To naked eye Through microscope Through high power microscope
Hochiki Detectors
Photoelectric Smoke Detectors
Ionization Smoke Detectors

Particle Size and the Hochiki Detectors

TECHNICAL BULLETIN HA-97


July 2000 8
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989
ADEMCO
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR DETECTOR BASE MODEL BASE ID
ID STYLE DET MODEL ID
VISTA 100 N/A A B 10 2K OHMS SLR-835B-2 HD-6 N/A N/A
VISTA 100 N/A A B 10 2K OHMS SLR-835B-2W HD-6 N/A N/A
VISTA 100 N/A A B 10 2K OHMS SLR-835BH-2 HD-6 N/A N/A
VISTA 100 N/A A B 10 2K OHMS SLR-835BH-2W HD-6 N/A N/A
VISTA 100-24 N/A A B 10 2K OHMS SLR-835B-2 HD-6 N/A N/A
VISTA 100-24 N/A A B 10 2K OHMS SLR-835B-2W HD-6 N/A N/A
VISTA 100-24 N/A A B 10 2K OHMS SLR-835BH-2 HD-6 N/A N/A
VISTA 100-24 N/A A B 10 2K OHMS SLR-835BH-2W HD-6 N/A N/A
VISTA 20HWSE N/A A B 10 2K OHMS SLR-835B-2 HD-6 N/A N/A
VISTA 20HWSE N/A A B 10 2K OHMS SLR-835B-2W HD-6 N/A N/A
VISTA 20HWSE N/A A B 10 2K OHMS SLR-835BH-2 HD-6 N/A N/A
VISTA 20HWSE N/A A B 10 2K OHMS SLR-835BH-2W HD-6 N/A N/A
VISTA 40 N/A A B 10 2K OHMS SLR-835B-2 HD-6 N/A N/A
VISTA 40 N/A A B 10 2K OHMS SLR-835B-2W HD-6 N/A N/A
VISTA 40 N/A A B 10 2K OHMS SLR-835BH-2 HD-6 N/A N/A
VISTA 40 N/A A B 10 2K OHMS SLR-835BH-2W HD-6 N/A N/A
VISTA 50PUL N/A A B 10 2K OHMS SLR-835B-2 HD-6 N/A N/A
VISTA 50PUL N/A A B 10 2K OHMS SLR-835B-2W HD-6 N/A N/A
VISTA 50PUL N/A A B 10 2K OHMS SLR-835BH-2 HD-6 N/A N/A
VISTA 50PUL N/A A B 10 2K OHMS SLR-835BH-2W HD-6 N/A N/A
VISTA 20SE N/A A B 10 2K OHMS SLR-835B-2 HD-6 N/A N/A
VISTA 20SE N/A A B 10 2K OHMS SLR-835B-2W HD-6 N/A N/A
VISTA 20SE N/A A B 10 2K OHMS SLR-835BH-2 HD-6 N/A N/A
VISTA 20SE N/A A B 10 2K OHMS SLR-835BH-2W HD-6 N/A N/A
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

ADT
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR DETECTOR BASE MODEL BASE ID
ID STYLE DET MODEL ID
ADT-XP XPM-8 A B;D 60 2.2K SIH-24F HD-3 HS-2-RB HB-10
ADT-XP XPM-8 A B;D 60 2.2K SIH-24F HD-3 HS-22D HB-3
ADT-XP XPM-8 A B;D 60 2.2K SIH-24F HD-3 HSB-220 HB-56
ADT-XP XPM-8 A B;D 60 2.2K SIH-24F HD-3 HSB-224 HB-53
ADT-XP XPM-8 A B;D 60 2.2K SIH-24F HD-3 YBA-M22 HB-3
ADT-XP XPM-8 A B;D 60 2.2K SLK-24F HD-3 HS-2-RB HB-10
ADT-XP XPM-8 A B;D 60 2.2K SLK-24F HD-3 HS-22D HB-3
ADT-XP XPM-8 A B;D 60 2.2K SLK-24F HD-3 HSB-220 HB-56
ADT-XP XPM-8 A B;D 60 2.2K SLK-24F HD-3 HSB-224 HB-53
ADT-XP XPM-8 A B;D 60 2.2K SLK-24F HD-3 YBA-M22 HB-3
ADT-XP XPM-8 A B;D 60 2.2K SLK-24FH HD-3 HS-2-RB HB-10
ADT-XP XPM-8 A B;D 60 2.2K SLK-24FH HD-3 HS-22D HB-3
ADT-XP XPM-8 A B;D 60 2.2K SLK-24FH HD-3 HSB-220 HB-56
ADT-XP XPM-8 A B;D 60 2.2K SLK-24FH HD-3 HSB-224 HB-53
ADT-XP XPM-8 A B;D 60 2.2K SLK-24FH HD-3 YBA-M22 HB-3
UNIMODE 4-16 IZ4;8W/WO IZE-A A B;D 35 4.7K SIH-24F HD-3 HS-2-RB HB-10
UNIMODE 4-16 IZ4;8W/WO IZE-A A B;D 35 4.7K SIH-24F HD-3 HS-22D HB-3
UNIMODE 4-16 IZ4;8W/WO IZE-A A B;D 35 4.7K SIH-24F HD-3 HSB-220 HB-56
UNIMODE 4-16 IZ4;8W/WO IZE-A A B;D 35 4.7K SIH-24F HD-3 HSB-224 HB-53
UNIMODE 4-16 IZ4;8W/WO IZE-A A B;D 35 4.7K SIH-24F HD-3 YBA-M22 HB-3
UNIMODE 4-16 IZ4;8W/WO IZE-A A B;D 35 4.7K SLK-24F HD-3 HS-2-RB HB-10
UNIMODE 4-16 IZ4;8W/WO IZE-A A B;D 35 4.7K SLK-24F HD-3 HS-22D HB-3
UNIMODE 4-16 IZ4;8W/WO IZE-A A B;D 35 4.7K SLK-24F HD-3 HSB-220 HB-56
UNIMODE 4-16 IZ4;8W/WO IZE-A A B;D 35 4.7K SLK-24F HD-3 HSB-224 HB-53
UNIMODE 4-16 IZ4;8W/WO IZE-A A B;D 35 4.7K SLK-24F HD-3 YBA-M22 HB-3
UNIMODE 4-16 IZ4;8W/WO IZE-A A B;D 35 4.7K SLK-24FH HD-3 HS-2-RB HB-10
UNIMODE 4-16 IZ4;8W/WO IZE-A A B;D 35 4.7K SLK-24FH HD-3 HS-22D HB-3
UNIMODE 4-16 IZ4;8W/WO IZE-A A B;D 35 4.7K SLK-24FH HD-3 HSB-220 HB-56
UNIMODE 4-16 IZ4;8W/WO IZE-A A B;D 35 4.7K SLK-24FH HD-3 HSB-224 HB-53
UNIMODE 4-16 IZ4;8W/WO IZE-A A B;D 35 4.7K SLK-24FH HD-3 YBA-M22 HB-3
UNIMODE 4-16 IZ4;9W/WO IZE-A A B;D 35 4.7K SLK-24F HD-3 YBA-M22 HB--3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

ADVANTOR
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR DETECTOR BASE MODEL BASE ID
ID STYLE DET MODEL ID
ULF 3000-24 N/A ULF1 A 10 6.8K SIH-24F HD-3 HS-200D HB-20
ULF 3000-24 N/A ULF1 A 10 6.8K SIH-24F HD-3 HS-220D HB-3
ULF 3000-24 N/A ULF1 A 10 6.8K SIH-24F HD-3 HS-221D HB-4
ULF 3000-24 N/A ULF1 A 10 6.8K SIH-24F HD-3 HS-224D HB-5
ULF 3000-24 N/A ULF1 A 10 6.8K SIH-24F HD-3 HSB-200 HB-55
ULF 3000-24 N/A ULF1 A 10 6.8K SIH-24F HD-3 HSB-220 HB-56
ULF 3000-24 N/A ULF1 A 10 6.8K SIH-24F HD-3 HSB-221 HB-54
ULF 3000-24 N/A ULF1 A 10 6.8K SIH-24F HD-3 HSB-224 HB-53
ULF 3000-24 N/A ULF1 A 10 6.8K SLK-24F HD-3 HS-200D HB-20
ULF 3000-24 N/A ULF1 A 10 6.8K SLK-24F HD-3 HS-220D HB-3
ULF 3000-24 N/A ULF1 A 10 6.8K SLK-24F HD-3 HS-221D HB-4
ULF 3000-24 N/A ULF1 A 10 6.8K SLK-24F HD-3 HS-224D HB-5
ULF 3000-24 N/A ULF1 A 10 6.8K SLK-24F HD-3 HSB-200 HB-55
ULF 3000-24 N/A ULF1 A 10 6.8K SLK-24F HD-3 HSB-220 HB-56
ULF 3000-24 N/A ULF1 A 10 6.8K SLK-24F HD-3 HSB-221 HB-54
ULF 3000-24 N/A ULF1 A 10 6.8K SLK-24F HD-3 HSB-224 HB-53
ULF 3000-24 N/A ULF1 A 10 6.8K SLK-24FH HD-3 HS-200D HB-20
ULF 3000-24 N/A ULF1 A 10 6.8K SLK-24FH HD-3 HS-220D HB-3
ULF 3000-24 N/A ULF1 A 10 6.8K SLK-24FH HD-3 HS-221D HB-4
ULF 3000-24 N/A ULF1 A 10 6.8K SLK-24FH HD-3 HS-224D HB-5
ULF 3000-24 N/A ULF1 A 10 6.8K SLK-24FH HD-3 HSB-200 HB-55
ULF 3000-24 N/A ULF1 A 10 6.8K SLK-24FH HD-3 HSB-220 HB-56
ULF 3000-24 N/A ULF1 A 10 6.8K SLK-24FH HD-3 HSB-221 HB-54
ULF 3000-24 N/A ULF1 A 10 6.8K SLK-24FH HD-3 HSB-224 HB-53
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

ANSUL
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR DETECTOR BASE MODEL BASE ID
ID STYLE DET MODEL ID
AUTOPULSE FOUR 415413 REV.4 B 45 417213 DCA-135 N/A HSC-21L HB-60
AUTOPULSE FOUR 415413 REV.4 B 45 417213 DCA-190 N/A HSC-21L HB-60
AUTOPULSE FOUR 415413 REV.4 B 45 417213 SIH-24F HD-3 HS-21D HB-2
AUTOPULSE FOUR 415413 REV.4 B 45 417213 SIH-24F HD-3 HSB-21 HB-51
AUTOPULSE FOUR 415413 REV.4 B 45 417213 SIH-24F HD-3 HSC-224R HB-73
AUTOPULSE FOUR 415413 REV.4 B 45 417213 SLK-24F HD-3 YBA-M21 HB-2
AUTOPULSE FOUR 415413 REV.4 B 45 417213 SLK-24F HD-3 HS-21D HB-2
AUTOPULSE FOUR 415413 REV.4 B 45 417213 SLK-24F HD-3 HSB-21 HB-51
AUTOPULSE FOUR 415413 REV.4 B 45 417213 SLK-24F HD-3 HSB-21 HB-51
AUTOPULSE FOUR 415413 REV.4 B 45 417213 SLK-24F HD-3 HSC-224R HB-73
AUTOPULSE FOUR 415413 REV.4 B 45 417213 SLK-24FH HD-3 YBA-M21 HB-2
AUTOPULSE FOUR 415413 REV.4 B 45 417213 SLK-24FH HD-3 HS-21D HB-2
AUTOPULSE FOUR 415413 REV.4 B 45 417213 SLK-24FH HD-3 HSB-21 HB-51
AUTOPULSE FOUR 415413 REV.4 B 45 417213 SLK-24FH HD-3 HSC-224R HB-73
AUTOPULSE FOUR 415413 REV.4 B 45 417213 DCA-135 N/A YBA-M21 HB-2
AUTOPULSE FOUR 416610 REV. 1 D 45 417213 DCA-190 N/A HSC-21L HB-60
AUTOPULSE FOUR 416610 REV. 1 D 45 417213 SIH-24F HD-3 HSC-21L HB-60
AUTOPULSE FOUR 416610 REV. 1 D 45 417213 SIH-24F HD-3 HS-21D HB-2
AUTOPULSE FOUR 416610 REV. 1 D 45 417213 SIH-24F HD-3 HSB-21 HB-51
AUTOPULSE FOUR 416610 REV. 1 D 45 417213 SIH-24F HD-3 HSC-224R HB-73
AUTOPULSE FOUR 416610 REV. 1 D 45 417213 SLK-24F HD-3 YBA-M21 HB-2
AUTOPULSE FOUR 416610 REV. 1 D 45 417213 SLK-24F HD-3 HS-21D HB-2
AUTOPULSE FOUR 416610 REV. 1 D 45 417213 SLK-24F HD-3 HSB-21 HB-51
AUTOPULSE FOUR 416610 REV. 1 D 45 417213 SLK-24F HD-3 HSC-224R HB-73
AUTOPULSE FOUR 416610 REV. 1 D 45 417213 SLK-24F HD-3 YBA-M21 HB-2
AUTOPULSE FOUR 416610 REV. 1 D 45 417213 SLK-24FH HD-3 HS-21D HB-2
AUTOPULSE FOUR 416610 REV. 1 D 45 417213 SLK-24FH HD-3 HSB-21 HB-51
AUTOPULSE FOUR 416610 REV. 1 D 45 417213 SLK-24FH HD-3 HSC-224R HB-73
AUTOPULSE FOUR 416610 REV. 1 D 45 417213 SLK-24FH HD-3 YBA-M21 HB-2
AUTOPULSE IQ301 MMX-2, M3-TW A B 24 3.9K 1400 A N/A N/A
AUTOPULSE IQ301 MMX-2, M3-TW A B 20 3.9K 1451 A B401 A
AUTOPULSE IQ301 MMX-2, M3-TW A B 20 3.9K 1451 A B401B A
AUTOPULSE IQ301 MMX-2, M3-TW A B 1 3.9K 1451 A B406B A
AUTOPULSE IQ301 MMX-2, M3-TW A B 20 3.9K 1451DH A DH400 A
AUTOPULSE IQ301 MMX-2, M3-TW A B 20 3.9K 1851DH A DH1851DC A
AUTOPULSE IQ301 MMX-2, M3-TW A B 20 3.9K 2400 A N/A N/A
AUTOPULSE IQ301 MMX-2, M3-TW A B 1 3.9K 2400AIT A N/A N/A
AUTOPULSE IQ301 MMX-2, M3-TW A B 1 3.9K 2400AT A N/A N/A
AUTOPULSE IQ301 MMX-2, M3-TW A B 20 3.9K 2400TH A N/A N/A
AUTOPULSE IQ301 MMX-2, M3-TW A B 20 3.9K 2451 A B401 A
AUTOPULSE IQ301 MMX-2, M3-TW A B 20 3.9K 2451 A B401B A
AUTOPULSE IQ301 MMX-2, M3-TW A B 20 3.9K 2451 A DH400 A
AUTOPULSE IQ301 MMX-2, M3-TW A B 20 3.9K 2451TH A B401 A
AUTOPULSE IQ301 MMX-2, M3-TW A B 20 3.9K 2451TH A B401B A
AUTOPULSE IQ301 MMX-2, M3-TW A B 1 3.9K 2451TH A B406B A
AUTOPULSE IQ301 MMX-2, M3-TW A B 20 3.9K 2851DH A DH2851DC A
AUTOPULSE IQ301 MMX-2, M3-TW A B 1 3.9K SIH-24F HD-3 HS-2-RB HB-10
AUTOPULSE IQ301 MMX-2, M3-TW A B 25 3.9K SIH-24F HD-3 HS-22D HB-3
AUTOPULSE IQ301 MMX-2, M3-TW A B 25 3.9K SIH-24F HD-3 YBA-M22 HB-3
AUTOPULSE IQ301 MMX-2, M3-TW A B 1 3.9K SLD-24F HD-3 HS-2-RB HB-10
AUTOPULSE IQ301 MMX-2, M3-TW A B 25 3.9K SLK-24F HD-3 HS-22D HB-3
AUTOPULSE IQ301 MMX-2, M3-TW A B 1 3.9K SLK-24FH HD-3 HS-2-RB HB-10
AUTOPULSE IQ301 MMX-2, M3-TW A B 25 3.9K SLK-24FH HD-3 YBA-M22 HB-3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

C & K SYSTEMS
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR DETECTOR BASE MODEL BASE ID
ID STYLE DET MODEL ID
238,2316 ZONE 8 NONE A 10 2.2K SLK-12 HD-4 HSB-12-1 HB-80
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 5-Mar-2003
LISTED AFTER MARCH 1, 1989

CADDX
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR DETECTOR BASE MODEL BASE ID
ID STYLE DET MODEL ID
NX6, NX8 3800-0001 MDL NO A 20 680 OHMS SLR-835,-835W HD-3 NS4-220,NS6-220 HB-3
NX6,NX8 3800-0001 MDL NO A 20 680 OHMS SLR-835B-2 HD-6 N/A N/A
NX8-E 3800-0020 MDL NO A 20 680 OHMS SLR-835,-835W HD-3 NS4-220,NS6-220 HB-3
NX8-E 3800-0020 MDL NO A 20 680 OHMS SLR-835B-2 HD-6 N/A N/A
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

CHEMETRON
2-Wire Compatibility Listings
PANEL MODEL ZONE MODELZONE LOOP MAX EOL DETECTOR DETECTOR BASE MODEL BASE ID
ID STYLE DET MODEL ID
MICRO 1-EV A A D 60 N/A SIH-24F HD-3 HS-220D HB-3
MICRO 1-EV A A D 60 N/A SIH-24F HD-3 HS-224D HB-5
MICRO 1-EV A A D 60 N/A SIH-24F HD-3 HS-224RB HB-12
MICRO 1-EV A A D 50 N/A SLK-24F HD-3 HS-220D HB-3
MICRO 1-EV A A D 50 N/A SLK-24F HD-3 HS-220RB HB-12
MICRO 1-EV A A D 50 N/A SLK-24F HD-3 HS-224D HB-5
MICRO 1-EV A A D 50 N/A SLK-24F HD-3 HS-224RB HB-14
MICRO 1-EV A A D 50 N/A SLK-24FH HD-3 HS-220D HB-3
MICRO 1-EV A A D 50 N/A SLK-24FH HD-3 HS-220RB HB-12
MICRO 1-EV A A D 50 N/A SLK-24FH HD-3 HS-224D HB-5
MICRO 1-EV A A D 50 N/A SLK-24FH HD-3 HS-224RB HB-14
MICRO1-EV N/A 4 B,D 14 2.7K OHM DCD-135, DCD-190 HD-3 HSC-224L HB-62
MICRO1-EV N/A 4 B,D 14 2.7K OHM DCD-135, DCD-190 HD-3 HSC-224L HB-62
MICRO1-EV N/A 4 B,D 14 2.7K OHM DFE-190 HD-3 HSC-220L HB-64
MICRO1-EV N/A 4 B,D 14 2.7K OHM DFE-190 HD-3 HSC-220L HB-64
MICRO1-EV N/A 4 B,D 14 2.7K OHM SIJ-24 HD-3 NS4-224,NS6-224 HB-5
MICRO1-EV N/A 4 B,D 14 2.7K OHM SIJ-24 HD-3 NS4-224,NS6-224 HB-5
MICRO1-EV N/A 4 B,D 14 2.7K OHM SLR-24 HD-3 NS4-224,NS6-224 HB-5
MICRO1-EV N/A 4 B,D 14 2.7K OHM SLR-24,-24H HD-3 HSC-220R HB-72
MICRO1-EV N/A 4 B,D 14 2.7K OHM SLR-24,-24H HD-3 NS4-220,NS6-220 HB-3
MICRO1-EV N/A 4 B,D 14 2.7K OHM SLR-24, SLR-24H HD-3 HSC-224R HB-73
MICRO1-EV N/A 4 B,D 14 2.7K OHM SLR-24, SLR-24H HD-3 HSC-224R HB-73
MICRO1-EV N/A 4 B,D 14 2.7K OHM SLR-24H HD-3 NS4-224,NS6-224 HB-5
MICRO1-EV N/A 4 B,D 14 2.7K OHM SLR-835B-2 HD-6 N/A N/A
MICRO1-EV CLASS N/A 4 B,D 10 2.7K OHM DCD-135 HD-3 HSC-220R HB-72
MICRO1-EV CLASS N/A 4 B,D 10 2.7K OHM DCD-135 HD-3 NS4-220,NS6-220 HB-3
MICRO1-EV CLASS N/A 4 B,D 10 2.7K OHM DCD-190 HD-3 HSC-220R HB-72
MICRO1-EV CLASS N/A 4 B,D 10 2.7K OHM DCD-190 HD-3 NS4-220,NS6-220 HB-3
MICRO1-EV CLASS N/A 4 B,D 10 2.7K OHM SIJ-24 HD-3 HSC-220R HB-72
MICRO1-EV CLASS N/A 4 B,D 10 2.7K OHM SIJ-24 HD-3 NS4-220,NS6-220 HB-3
MICRO1-EV CLASS N/A 4 B,D 10 2.7K OHM SLR-24 HD-3 HSC-220R HB-72
MICRO1-EV CLASS N/A 4 B,D 10 2.7K OHM SLR-24 HD-3 NS4-220,NS6-220 HB-3
SG N/A 1 B 33 4.7K OHM SIF-24F HD-3 HS-220D HB-3
SG N/A 1 B 33 4.7K OHM SIH-24F HD-3 HS-220D HB-3
SG N/A 1 B 33 4.7K OHM SLK-24F HD-3 HS-220D HB-3
SG N/A 1 B 33 4.7K OHM SLK-24FH HD-3 HS-220D HB-3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

DETECTION SYS.
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR DETECTOR BASE MODEL BASE ID
ID STYLE DET MODEL ID
DS9400I, DS9400M N/A A B 20 2.2K OHM DCD-135,-190 HD-3 HSC-220L HB-64
DS9400I, DS9400M N/A A B 20 2.2K OHM DCD-135,-190 HD-3 HSC-220R HB-72
DS9400I, DS9400M N/A A B 20 2.2K OHM DCD-135,-190 HD-3 NS4-220,NS6-220 HB-3
DS9400I, DS9400M N/A A B 20 2.2K OHM DCD-135,-190 HD-3 HSC-220L HB-64
DS9400I, DS9400M N/A A B 20 2.2K OHM SIJ-24 HD-3 HSC-220R HB-72
DS9400I, DS9400M N/A A B 20 2.2K OHM SIJ-24 HD-3 NS4-220,NS6-220 HB-3
DS9400I, DS9400M N/A A B 20 2.2K OHM SLR-24H,-24V HD-3 HSC-220R HB-72
DS9400I, DS9400M N/A A B 20 2.2K OHM SLR-24H,-24V HD-3 NS4-100,NS6-100 HB-55
DS9400I, DS9400M N/A A B 20 2.2K OHM SLR-24H,-24V HD-3 NS4-220,NS6-220 HB-3
DS9400I, DS9400M N/A A B 20 2.2K OHM SLR-835 HD-3 NS4-100,NS6-100 HB-55
DS9400I, DS9400M N/A A B 20 2.2K OHM SLR-835 HD-3 NS4-220,NS6-220 HB-3
DS9400I, DS9400M N/A A B 20 2.2K OHM SLR-835B-2 HD-6 N/A N/A
DS9400I, DS9400M N/A A B 20 2.2K OHM SLR-835H HD-5 HSC-220R HB-72
DS9400I, DS9400M N/A A B 20 2.2K OHM SLR-835H HD-5 NS4-220,NS6-220 HB-3
DS9400I, DS9400M N/A A B 1 2.2K OHM SLR-835,-835W HD-5 SBC-2R,SBC-2RW HB-85
DS9400I, DS9400M N/A A B 1 2.2K OHM SIJ-24 HD-3 SBC-2 HB-85
DS9400I, DS9400M N/A A B 1 2.2K OHM SLR-24V HD-3 SBC-2 HB-85
DS9400I, DS9400M N/A A B 1 2.2K OHM SLR-24V HD-3 SBC-2R HB-86

UPDATED 9/11/03
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

DIGITAL MONITOR
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR DETECTOR BASE MODEL BASE ID
ID STYLE DET MODEL ID
XR5FC 2--5 A A 22 3.3k SLK12 HD-4 HSB-12-1,-12-1N HB-80
XR5FC 2--5 A A 7 3.3k SLK-835,-835H HD-5 HSB-200,-200N HB-55
XR5SL 2--5 A A 22 3.3k SLK-12 HD-4 HSB-12-1,-12-1N HB-80
XR5SL 2--5 A A 7 3.3k SLK-835,-835H HD-5 HSB-200,-200N HB-55
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

DMP
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR DETECTOR BASE MODEL BASE ID
ID STYLE DET MODEL ID
XR10 10 ON XR10 A A 22 3.3K SLK-12 HD-4 HSB-12-1,-12-1N HB-80
XR10 10 ON XR10 A A 7 3.3K SLK-835,-835H HD-5 HSB-200,-200N HB-55
XR10 10 ON XR10 A A 7 3.3K SLR-835 HD-3 NS6-100 HB-55
XR20 10 ON XR20 A A 22 3.3K SLK-12 HD-4 HSB-12-1,-12-1N HB-80
XR20 10 ON XR20 A A 7 3.3K SLK-835,-835H HD-5 HSB-200,-200N HB-55
XR20 10 ON XR20 A A 7 3.3K SLR-835 HD-3 NS6-100 HB-55
XR20 10 ON XR20 A A 7 3.3K SLR-835B HD-6 NA NA
XR20 715 A A 7 3.3K SLR-835 HD-3 NS6-100 HB-55
XR20 715,-16 A A 7 3.3K SLR-835B HD-6 NA NA
XR20 715,-16,-8 A A 7 3.3K SLK-835,-835H HD-5 HSB-200,-200N HB-55
XR20 715,-16-,-8 A A 22 3.3K SLK-12 HD-4 HSB-12-1,-12-1N HB-80
XR20 715-16 A A 7 3.3K SLR-835 HD-3 NS6-100 HB-55
XR20 715-8 A A 7 3.3K SLR-835 HD-3 NS6-100 HB-55
XR20 715-8 A A 7 3.3K SLR-835B HD-6 NA NA
XR200 10 ON XR200 A A 7 3.3K SLK-835,-835H HD-5 HSB-200,-200N HB-55
XR200 715 A A 22 3.3K SLK-12 HD-4 HSB-12-1,-12-1N HB-80
XR200 715 A A 7 3.3K SLK-835,-835H HD-5 HSB-200,-200N HB-55
XR200 715 OR Z 9 &10 A A 22 3.3K SLK-12 HD-4 HSB-12-1,-12-1N HB-80
XR200 715, 715-16 A A 7 3.3K SLK-835,-835H HD-5 HSB-200,-200N HB-55
XR200 715,-16 A A 7 3.3K SLR-835 HD-3 NS6-100 HB-55
XR200 715,-16 A A 7 3.3K SLR-835B HD-6 NA NA
XR200 715,-16,-8 A A 22 3.3K SLK-12 HD-4 HSB-12-1,-12-1N HD-4
XR200 715-8 A A 7 3.3K SLK-835,-835H HD-5 HSB-200,-200N HB-55
XR200 715-8 A A 7 3.3K SLR-835 HD-3 NS6-100 HB-55
XR200 9 & 10 ON XR200 A A 22 3.3K SLK-12 HD-4 HSB-12-1,-12-1N HB-80
XR200 9 ON XR200 A A 7 3.3K SLK-835,-835H HD-5 HSB-200,-200N HB-55
XR200 9,10 ON XR200 A A 7 3.3K SLR-835 HD-3 NS6-100 HB-55
XR200 9,10 ON XR200 A A 7 3.3K SLR-835B HD-6 NA NA
XR200 XR200 A A 22 3.3K SLK-12 HD-4 HSB-12-1,-12-1N HB-80
XR200 XR200 A A 7 3.3K SLK-835,-835H HD-5 HSB-200,-200N HB-55
XR5FC 2-5 ON XR5FC A A 22 3.3K SLK-12 HD-4 HSB-12-1,-12-1N HB-80
XR5FC 2-5 ON XR5FC A A 7 3.3K SLK-835,-835H HD-5 HSB-200,-200N HB-55
XR5FC 2-5 ON XR5FC A A 7 3.3K SLR-835 HD-6 NA NA
XR5FC 2-5 ON XR5FC A A 7 3.3K SLR-835 HD-3 NS6-100 HB-55
XR5SL 2-5 ON XR5SL A A 22 3.3K SLK-12 HD-4 HSB-12-1,-12-1N HB-80
XR5SL 2-5 ON XR5SL A A 7 3.3K SLK-835,-835H HD-5 HSB-200,-200N HB-55
XR5SL 2-5 ON XR5SL A A 7 3.3K SLR-835 HD-3 NS6-100 HB-55
XR5SL 2-5 ON XR5SL A A 7 3.3K SLR-835B HD-6 NA NA
XR6 6 ON XR6 A A 7 3.3K SLR-835 HD-3 NS6-100 HB-55
XR6 6 ON XR6 A A 7 3.3K SLR-835B HD-6 NA NA
XR6 715 A A 7 3.3K SLR-835B HD-6 NA NA
XR6 715 ON XR6 A A 7 3.3K SLR-835 HD-3 NS6-100 HB-55
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

DSC
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR DETECTOR BASE MODEL BASE ID
ID STYLE DET MODEL ID
PC1555 UA000 PC15-1 B 30 2.2K OHM SLR-835, 835W HD-3 NS4-220,NS6-220 HB-3
PC1555 UA000 PC15-1 B 30 2.2K OHM SLR-835B-2 HD-6 N/A N/A
PC1555 UA000 PC15-1 B 30 2.2K OHM SLR-835BH-2 HD-6 N/A N/A
PC4020CF PC4701 PM-2 B 30 2.2K OHM SLR-835, 835W HD-3 NS4-220,NS6-220 HB-3
PC4020CF PC4701 PM-2 B 30 2.2K OHM SLR-835B-2 HD-6 N/A N/A
PC4020CF PC4701 PM-2 B 30 2.2K OHM SLR-835BH-2 HD-6 N/A N/A
PC5010 PC5010 PC5-1 B 30 2.2K OHM SLR-835, 835W HD-3 NS4-220,NS6-220 HB-3
PC5010 PC5010 PC5-1 B 30 2.2K OHM SLR-835B-2 HD-6 N/A N/A
PC5010 PC5010 PC5-1 B 30 2.2K OHM SLR-835BH-2 HD-6 N/A N/A
PC5020 PC5020 PC5-2 B 30 2.2K OHM SLR-835, 835W HD-3 NS4-220,NS6-220 HB-3
PC5020 PC5020 PC5-2 B 30 2.2K OHM SLR-835B-2 HD-6 N/A N/A
PC5020 PC5020 PC5-2 B 30 2.2K OHM SLR-835BH-2 HD-6 N/A N/A
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

EDWARDS
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR DETECTOR BASE MODEL BASE ID
ID STYLE DET MODEL ID
5783B N/A 001 B 33 4.7K OHM SIF-24F HD-2 HS-220D HB-3
5783B N/A 001 B 33 4.7K OHM SIH-24F HD-3 HS-220D HB-3
5783B N/A 001 B 33 4.7K OHM SLK-24F HD-3 HS-220D HB-3
5783B N/A 001 B 33 4.7K OHM SLK-24FH HD-3 HS-220D HB-3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

F.A.S.T. INC.
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
RZB12-6MFC 240204 5389 B 15 PN260001 SIF-24F HD-2 HS-22D HB-3
RZB12-6MFC 240204 5389 B 15 PN260001 SIF-24F HD-3 YBA-M22 HB-3
RZB12-6MFC 240204 5389 B 15 PN260001 SLK-24F HD-3 HS-22D HB-3
RZB12-6MFC 240204 5389 B 15 PN260001 SLK-24F HD-3 YBA-M22 HB-3
RZB12-6MFC 240204 5389 B 15 PN260001 SLK-24FH HD-3 HS-22D HB-3
RZB12-6MFC 240204 5389 B 15 PN260001 SLK-24FH HD-3 YBA-M22 HB-3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

FARADAY
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
852 N/A FOS1 B 30 3.9K OHM DCA-135 N/A HS-224L HB-18
852 N/A FOS1 B 30 3.9K OHM DCA-190 N/A HS-224L HB-18
852 N/A FOS1 B 30 3.9K OHM DCA-190 N/A HS-224L HB-18
852 N/A FOS1 B 30 3.9K OHM DFE-135 N/A HS-224L HB-18
852 N/A FOS1 B 30 3.9K OHM DFE-190 N/A HS-224L HB-18
854 N/A FOS1 B 30 3.9K OHM DCA-135 N/A HS-224L HB-18
854 N/A FOS1 B 30 3.9K OHM DCA-190 N/A HS-224L HB-18
854 N/A FOS1 B 30 3.9K OHM DFE-135 N/A HS-224L HB-18
854 N/A FOS1 B 30 3.9K OHM DFE-190 N/A HS-224L HB-18
15108AL N/A FOS2 B 30 5.6K OHM DCA-135 N/A HS-224L HB-18
15108AL N/A FOS2 D 30 N/A DCA-135 N/A HS-224L HB-18
15108AL N/A FOS2 B 30 5.6K OHM DCA-190 N/A HS-224L HB-18
15108AL N/A FOS2 D 30 N/A DCA-190 N/A HS-224L HB-18
15108AL N/A FOS2 B 30 5.6K OHM DFE-135 N/A HS-224L HB-18
15108AL N/A FOS2 B 30 5.6K OHM DFE-135 N/A HS-224L HB-18
15108AL N/A FOS2 D 30 N/A DFE-135 N/A HS-224L HB-18
15108AL N/A FOS2 D 30 N/A DFE-135 N/A HS-224L HB-18
15108AL N/A FOS2 B 30 5.6K OHM DFE-190 N/A HS-224L HB-18
15108AL N/A FOS2 B 30 5.6K OHM DFE-190 N/A HS-224L HB-18
15108AL N/A FOS2 D 30 N/A DFE-190 N/A HS-224L HB-18
15108AL N/A FOS2 D 30 N/A DFE-190 N/A HS-224L HB-18
15112AL N/A FOS2 B 30 5.6K OHM DCA-135 N/A HS-224L HB-18
15112AL N/A FOS2 B 30 5.6K OHM DCA-135 N/A HS-224L HB-18
15112AL N/A FOS2 D 30 N/A DCA-135 N/A HS-224L HB-18
15112AL N/A FOS2 D 30 N/A DCA-135 N/A HS-224L HB-18
15112AL N/A FOS2 B 30 5.6K OHM DCA-190 N/A HS-224L HB-18
15112AL N/A FOS2 B 30 5.6K OHM DCA-190 N/A HS-224L HB-18
15112AL N/A FOS2 D 30 N/A DCA-190 N/A HS-224L HB-18
15112AL N/A FOS2 D 30 N/A DCA-190 N/A HS-224L HB-18
15112AL N/A FOS2 B 30 5.6K OHM DFE-135 N/A HS-224L HB-18
15112AL N/A FOS2 B 30 5.6K OHM DFE-135 N/A HS-224L HB-18
15112AL N/A FOS2 D 30 N/A DFE-135 N/A HS-224L HB-18
15112AL N/A FOS2 D 30 N/A DFE-135 N/A HS-224L HB-18
15112AL N/A FOS2 B 30 5.6K OHM DFE-190 N/A HS-224L HB-18
15112AL N/A FOS2 B 30 5.6K OHM DFE-190 N/A HS-224L HB-18
15112AL N/A FOS2 D 30 N/A DFE-190 N/A HS-224L HB-18
15112AL N/A FOS2 D 30 N/A DFE-190 N/A HS-224L HB-18
15116AL N/A FOS2 B 30 5.6K OHM DCA-135 N/A HS-224L HB-18
15116AL N/A FOS2 B 30 5.6K OHM DCA-135 N/A HS-224L HB-18
15116AL N/A FOS2 D 30 N/A DCA-135 N/A HS-224L HB-18
15116AL N/A FOS2 D 30 N/A DCA-135 N/A HS-224L HB-18
15116AL N/A FOS2 B 30 5.6K OHM DCA-190 N/A HS-224L HB-18
15116AL N/A FOS2 B 30 5.6K OHM DCA-190 N/A HS-224L HB-18
15116AL N/A FOS2 D 30 N/A DCA-190 N/A HS-224L HB-18
15116AL N/A FOS2 D 30 N/A DCA-190 N/A HS-224L HB-18
15116AL N/A FOS2 B 30 5.6K OHM DFE-135 N/A HS-224L HB-18
15116AL N/A FOS2 B 30 5.6K OHM DFE-135 N/A HS-224L HB-18
15116AL N/A FOS2 D 30 N/A DFE-135 N/A HS-224L HB-18
15116AL N/A FOS2 D 30 N/A DFE-135 N/A HS-224L HB-18
15116AL N/A FOS2 B 30 5.6K OHM DFE-190 N/A HS-224L HB-18
15116AL N/A FOS2 B 30 5.6K OHM DFE-190 N/A HS-224L HB-18
15116AL N/A FOS2 D 30 N/A DFE-190 N/A HS-224L HB-18
15116AL N/A FOS2 D 30 N/A DFE-190 N/A HS-224L HB-18
19000A N/A B B 30 5.6K OHM DCA-135 N/A HS-224L HB-18
19000A N/A B B 30 5.6K OHM DCA-135 N/A HS-224L HB-18
19000A N/A B D 30 N/A DCA-135 N/A HS-224L HB-18
19000A N/A B D 30 N/A DCA-135 N/A HS-224L HB-18
19000A N/A B B 30 5.6K OHM DCA-190 N/A HS-224L HB-18
19000A N/A B B 30 5.6K OHM DCA-190 N/A HS-224L HB-18
19000A N/A B D 30 N/A DCA-190 N/A HS-224L HB-18
19000A N/A B D 30 N/A DCA-190 N/A HS-224L HB-18
19000A N/A B B 30 5.6K OHM DFE-135 N/A HS-224L HB-18
19000A N/A B B 30 5.6K OHM DFE-135 N/A HS-224L HB-18
19000A N/A B D 30 N/A DFE-135 N/A HS-224L HB-18
19000A N/A B D 30 N/A DFE-135 N/A HS-224L HB-18
19000A N/A B B 30 5.6K OHM DFE-190 N/A HS-224L HB-18
19000A N/A B B 30 5.6K OHM DFE-190 N/A HS-224L HB-18
19000A N/A B D 30 N/A DFE-190 N/A HS-224L HB-18

Page 1 of 2
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

2-Wire Compatibility Listings


PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
19000A N/A B D 30 N/A DFE-190 N/A HS-224L HB-18
19000A EVAC N/A B B 30 5.6K OHM DCA-135 N/A HS-224L HB-18
19000A EVAC N/A B B 30 5.6K OHM DCA-135 N/A HS-224L HB-18
19000A EVAC N/A B D 30 N/A DCA-135 N/A HS-224L HB-18
19000A EVAC N/A B D 30 N/A DCA-135 N/A HS-224L HB-18
19000A EVAC N/A B B 30 5.6K OHM DCA-190 N/A HS-224L HB-18
19000A EVAC N/A B B 30 5.6K OHM DCA-190 N/A HS-224L HB-18
19000A EVAC N/A B D 30 N/A DCA-190 N/A HS-224L HB-18
19000A EVAC N/A B D 30 N/A DCA-190 N/A HS-224L HB-18
19000A EVAC N/A B B 30 5.6K OHM DFE-135 N/A HS-224L HB-18
19000A EVAC N/A B B 30 5.6K OHM DFE-135 N/A HS-224L HB-18
19000A EVAC N/A B D 30 N/A DFE-135 N/A HS-224L HB-18
19000A EVAC N/A B D 30 N/A DFE-135 N/A HS-224L HB-18
19000A EVAC N/A B B 30 5.6K OHM DFE-190 N/A HS-224L HB-18
19000A EVAC N/A B B 30 5.6K OHM DFE-190 N/A HS-224L HB-18
19000A EVAC N/A B D 30 N/A DFE-190 N/A HS-224L HB-18
19000A EVAC N/A B D 30 N/A DFE-190 N/A HS-224L HB-18
2022-FSP NA C B 30 3.9K AL-DCA-135 NA HS-224L HB-18
2022-FSP NA C B 30 3.9K AL-DCA-190 NA HS-224L HB-18
2022-FSP NA C B 30 3.9K AL-DFE-135 NA HS-224L HB-18
2022-FSP NA C B 30 3.9K AL-DFE-190 NA HS-224L HB-18
2022-FSP NA C B 30 3.9K SIF-24F HD-2 AL-HS-224D HB-5
2022-FSP NA C B 30 3.9K SIH-24F HD-3 AL-HS-224D HB-5
2022-FSP NA C B 30 3.9K SLK-24F HD-3 AL-HS-224D HB-5
2022-FSP NA C B 30 3.9K SLK-24FH HD-3 AL-HS-224D HB-5
2042-FSP NA C B 30 3.9K AL-DCA-135 NA HS-224L HB-18
2042-FSP NA C B 30 3.9K AL-DCA-190 NA HS-224L HB-18
2042-FSP NA C B 30 3.9K AL-DFE-135 NA HS-224L HB-18
2042-FSP NA C B 30 3.9K AL-DFE-190 NA HS-224L HB-18
2042-FSP NA C B 30 3.9K SIF-24F HD-2 AL-HS-224D HB-5
2042-FSP NA C B 30 3.9K SIH-24F HD-3 AL-HS-224D HB-5
2042-FSP NA C B 30 3.9K SLK-24F HD-3 AL-HS-224D HB-5
2042-FSP NA C B 30 3.9K SLK-24FH HD-3 AL-HS-224D HB-5
6110-FSP 401310, 311, 312 D B 30 3.9K AL-DCA-135 NA HS-224L HB-18
6110-FSP 401310, 311, 312 D B 30 3.9K AL-DCA-190 NA HS-224L HB-18
6110-FSP 401310, 311, 312 D B 30 3.9K AL-DFE-135 NA HS-224L HB-18
6110-FSP 401310, 311, 312 D B 30 3.9K AL-DFE-190 NA HS-224L HB-18
6110-FSP 401310, 311, 312 D B 30 3.9K SIF-24F HD-2 AL-HS-224D HB-5
6110-FSP 401310, 311, 312 C B 30 3.9K SIH-24F HD-3 AL-HS-224D HB-5
6110-FSP 401310, 311, 312 C B 30 3.9K SLK-24F HD-3 AL-HS-224D HB-5
6110-FSP 401310, 311, 312 C B 30 3.9K SLK-24FH HD-3 AL-HS-224D HB-5
MPC-2000 401310 D B 30 10808 SIF-24F HD-2 HS-224D HB-5
MPC-2000 401310 D D 30 N/A SIF-24F HD-2 HS-224D HB-5
MPC-2000 401310 D D 30 N/A SIH-24F HD-3 HS-224D HB-5
MPC-2000 401310 D B 30 10808 SIH-24F HD-3 HS-224D HB-5
MPC-2000 401310 D D 30 N/A SLK-24F HD-3 HS-224D HB-5
MPC-2000 401310 D B 30 10808 SLK-24F HD-3 HS-224D HB-5
MPC-2000 401310 D D 30 N/A SLK-24FH HD-3 HS-224D HB-5
MPC-2000 401310 D B 30 10808 SLK-24FH HD-3 HS-224D HB-5
MPC-2000 401311 D D 30 N/A SIF-24F HD-2 HS-224D HB-5
MPC-2000 401311 D B 30 10808 SIF-24F HD-2 HS-224D HB-5
MPC-2000 401311 D B 30 10808 SIH-24F HD-3 HS-224D HB-5
MPC-2000 401311 D D 30 N/A SIH-24F HD-3 HS-224D HB-5
MPC-2000 401311 D B 30 10808 SLK-24F HD-3 HS-224D HB-5
MPC-2000 401311 D D 30 N/A SLK-24F HD-3 HS-224D HB-5
MPC-2000 401311 D B 30 10808 SLK-24FH HD-3 HS-224D HB-5
MPC-2000 401311 D D 30 N/A SLK-24FH HD-3 HS-224D HB-5

Page 2 of 2
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

FIKE
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
RHINO 10-2141, 10-2144 DET220 B, D 50 3.3K OHM DFE-135, -190 N/A HSC-220L HB-64
RHINO 10-2141, 10-2144 DET220 B, D 50 3.3K OHM SLR-24H HD-3 HSC-220R HB-72
RHINO 10-2141, 10-2144 DET220 B, D 50 3.3K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
RHINO 10-050 10-2141, -2144 DET220 B, D 50 3.3K OHM SLR-835B-2 HD-6 N/A N/A
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM DCD-135 HD-3 HSC-220R HB-72
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM DCD-135 HD-3 HSC-221R HB-71
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM DCD-135 HD-3 HSC-224R HB-73
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM DCD-135 HD-3 NS4-220, NS6-220 HB-3
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM DCD-135 HD-3 NS4-221, NS6-221 HB-4
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM DCD-135 HD-3 NS4-224, NS6-224 HB-5
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM DCD-190 HD-3 HSC-220R HB-72
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM DCD-190 HD-3 HSC-221R HB-71
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM DCD-190 HD-3 HSC-224R HB-73
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM DCD-190 HD-3 NS4-220, NS6-220 HB-3
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM DCD-190 HD-3 NS4-221, NS6-221 HB-4
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM DCD-190 HD-3 NS4-224, NS6-224 HB-5
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM SIJ-24 HD-3 HSC-220R HB-72
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM SIJ-24 HD-3 HSC-221R HB-71
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM SIJ-24 HD-3 HSC-224R HB-73
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM SIJ-24 HD-3 NS4-221, NS6-221 HB-4
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM SIJ-24 HD-3 NS4-224, NS6-224 HB-5
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM SLR-24 HD-3 HSC-220R HB-72
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM SLR-24 HD-3 HSC-221R HB-71
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM SLR-24 HD-3 HSC-224R HB-73
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM SLR-24 HD-3 NS4-220, NS6-220 HB-3
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM SLR-24 HD-3 NS4-221, NS6-221 HB-4
RHINO 10-050 10-2141, 10-2144 DET470 B 30 3.3K OHM SLR-24 HD-3 NS4-224, NS6-224 HB-5
SHP 10-051 10-2171 102171 B 25 4.3K OHM DCD-135 HD-3 HSC-220R HB-72
SHP 10-051 10-2171 102171 B 25 4.3K OHM DCD-135 HD-3 HSC-221R HB-71
SHP 10-051 10-2171 102171 B 25 4.3K OHM DCD-135 HD-3 HSC-224R HB-73
SHP 10-051 10-2171 102171 B 25 4.3K OHM DCD-135 HD-3 NS4-220, NS6-220 HB-3
SHP 10-051 10-2171 102171 B 25 4.3K OHM DCD-135 HD-3 NS4-221, NS6-221 HB-4
SHP 10-051 10-2171 102171 B 25 4.3K OHM DCD-135 HD-3 NS4-224, NS6-224 HB-5
SHP 10-051 10-2171 MDL. NO B, D 25 4.3K OHM DCD-135, DCD-190 HD-3 NS4-221, NS6-221 HB-4
SHP 10-051 10-2171 102171 B 25 4.3K OHM DCD-190 HD-3 HSC-220R HB-72
SHP 10-051 10-2171 102171 B 25 4.3K OHM DCD-190 HD-3 HSC-221R HB-71
SHP 10-051 10-2171 102171 B 25 4.3K OHM DCD-190 HD-3 HSC-224R HB-73
SHP 10-051 10-2171 102171 B 25 4.3K OHM DCD-190 HD-3 NS4-220, NS6-220 HB-3
SHP 10-051 10-2171 102171 B 25 4.3K OHM DCD-190 HD-3 NS4-221, NS6-221 HB-4
SHP 10-051 10-2171 102171 B 25 4.3K OHM DCD-190 HD-3 NS4-224, NS6-224 HB-5
SHP 10-051 10-2171 102171 B 25 4.3K OHM SIJ-24 HD-3 HSC-220R HB-72
SHP 10-051 10-2171 102171 B 25 4.3K OHM SIJ-24 HD-3 HSC-221R HB-71
SHP 10-051 10-2171 102171 B 25 4.3K OHM SIJ-24 HD-3 HSC-224R HB-73
SHP 10-051 10-2171 102171 B 25 4.3K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
SHP 10-051 10-2171 MDL. NO B, D 25 4.3K OHM SIJ-24 HD-3 NS4-221, NS6-221 HB-4
SHP 10-051 10-2171 102171 B 25 4.3K OHM SIJ-24 HD-3 NS4-221, NS6-221 HB-4
SHP 10-051 10-2171 102171 B 25 4.3K OHM SIJ-24 HD-3 NS4-224, NS6-224 HB-5
SHP 10-051 10-2171 102171 B 25 4.3K OHM SLR-24 HD-3 HSC-220R HB-72
SHP 10-051 10-2171 102171 B 25 4.3K OHM SLR-24 HD-3 HSC-221R HB-71
SHP 10-051 10-2171 102171 B 25 4.3K OHM SLR-24 HD-3 HSC-224R HB-73
SHP 10-051 10-2171 102171 B 25 4.3K OHM SLR-24 HD-3 NS4-220, NS6-220 HB-3
SHP 10-051 10-2171 102171 B 25 4.3K OHM SLR-24 HD-3 NS4-221, NS6-221 HB-4
SHP 10-051 10-2171 MDL NO B, D 25 4.3K OHM SLR-24 HD-3 NS4-221, NS6-221 HB-4
SHP 10-051 10-2171 102171 B 25 4.3K OHM SLR-24 HD-3 NS4-224, NS6-224 HB-5
SHP 10-051 10-2171 MDL. NO B, D 25 4.3K OHM SLR-835B-2 HD-6 N/A N/A
10-038 N/A 038000 B 87 1.5K OHM SIH-24F HD-3 HS-220D HB-3
10-038 N/A 038000 D 87 N/A SIH-24F HD-3 HS-220D HB-3
10-038 N/A 038000 B 87 1.5K OHM SIH-24F HD-3 YBA-M220 HB-3
10-038 N/A 038000 D 87 N/A SIH-24F HD-3 YBA-M220 HB-3
10-038 N/A 038000 B 87 1.5K OHM SLK-24F HD-3 HS-220D HB-3
10-038 N/A 038000 D 87 N/A SLK-24F HD-3 HS-220D HB-3
10-038 N/A 038000 D 87 N/A SLK-24F HD-3 HS-220RB HB-12
10-038 N/A 038000 B 87 1.5K OHM SLK-24F HD-3 HS-220RB HB-12
10-038 N/A 038000 B 87 1.5K OHM SLK-24F HD-3 YBA-M220 HB-3
10-038 N/A 038000 D 87 N/A SLK-24F HD-3 YBA-M220 HB-3
10-039 N/A 038000 D 87 N/A SIH-24F HD-3 HS-220D HB-3
10-039 N/A 038000 B 87 1.5K OHM SIH-24F HD-3 HS-220D HB-3

Page 1 of 2
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

2-Wire Compatibility Listings


PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
10-039 N/A 038000 B 87 1.5K OHM SIH-24F HD-3 YBA-M220 HB-3
10-039 N/A 038000 D 87 N/A SIH-24F HD-3 YBA-M220 HB-3
10-039 N/A 038000 D 87 N/A SLK-24F HD-3 HS-220D HB-3
10-039 N/A 038000 B 87 1.5K OHM SLK-24F HD-3 HS-220D HB-3
10-039 N/A 038000 D 87 N/A SLK-24F HD-3 HS-220RB HB-12
10-039 N/A 038000 B 87 1.5K OHM SLK-24F HD-3 HS-220RB HB-12
10-039 N/A 038000 D 87 N/A SLK-24F HD-3 YBA-M220 HB-3
10-039 N/A 038000 B 87 1.5K OHM SLK-24F HD-3 YBA-M220 HB-3
RHINO 10-050 N/A 1 SIH-24F HD-3 HSB-224 HB-53
RHINO 10-050 DCM-10-2141 DET220 B, D 50 3.3K SIH-24F HD-3 HSB-220 HB-56
RHINO 10-050 DCM-10-2141 DET B, D 50 3.3K SIH-24F HD-3 HSB-24 HB-53
RHINO 10-050 DCM-10-2141 DET220 B, D 50 3.3K SIH-24F HD-3 YBA-M220 HB-3
RHINO 10-050 DCM-10-2141 DET B, D 50 3.3K SIH-24F HD-3 YBA-M224 HB-5
RHINO 10-050 DCM-10-2141 DET220 B, D 50 3.3K SLK-24F HD-3 HSB-220 HB-56
RHINO 10-050 DCM-10-2141 DET B, D 50 3.3K SLK-24F HD-3 HSB-224 HB-53
RHINO 10-050 DCM-10-2141 DET220 B, D 50 3.3K SLK-24F HD-3 YBA-M220 HB-3
RHINO 10-050 DCM-10-2141 DET220 B, D 50 3.3K SIH-24F HD-3 HSB-220 HB-56
RHINO 10-050 DCM-10-2141 DET220 B, D 50 3.3 SIH-24F HD-3 HSB-220 HB-56
RHINO 10-050 DCM-10-2141 DET B, D 50 3.3K SIH-24F HD-3 HSB-224 HB-53
RHINO 10-050 DCM-10-2141 DET220 B, D 50 3.3K SIH-24F HD-3 YBA-M220 HB-3
RHINO 10-050 DCM-10-2141 DET B, D 50 3.3K SIH-24F HD-3 YBA-M224 HB-5
RHINO 10-050 DCM-10-2141 DET220 B, D 50 3.3K SLK-24F HD-3 HSB-220 HB-56
RHINO 10-050 DCM-10-2141 DET B, D 50 3.3K SLK-24F HD-3 HSB-224 HB-53
RHINO 10-050 DCM-10-2141 DET220 B, D 50 3.3K SLK-24F HD-3 YBA-M220 HB-3
RHINO 10-050 DCM-10-2141 DET B, D 50 3.3 SLK-24F HD-3 YBA-M224 HB-5
RHINO 10-050 DCM-10-2141 DET B, D 50 3.3K SLK-24F HB-5 YBA-M224 HB-5
SHP 10-051 10-2171 MDL NO B, D 25 4.3K SIH-24F HD-3 HS-221D HB-4
SHP 10-051 10-2171 MDL NO B, D 25 4.3K SIH-24F HD-3 HSB-220 HB-56
SHP 10-051 10-2171 MDL NO B, D 25 4.3K SIH-24F HD-3 HSB-224 HB-53
SHP 10-051 10-2171 MDL NO B, D 25 4.3K SIH-24F HD-3 YBA-M220 HB-3
SHP 10-051 10-2171 MDL NO B, D 25 4.3K SIH-24F HD-3 YBA-M224 HB-5
SHP 10-051 10-2171 MDL NO B, D 25 4.3K SLK-24F HD-3 HS-221D HB-4
SHP 10-051 10-2171 MDL NO B, D 25 4.3K SLK-24F HD-3 HSB-224 HB-53
SHP 10-051 10-2171 MDL NO B, D 25 4.3K SLK-24F HD-3 YBA-M220 HB-3
SHP 10-051 10-2171 MDL NO B, D 25 4.3K SLK-24F HD-3 YBA-M224 HB-5

Page 2 of 2
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

FIRELITE
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
MP-12 N/A A B, D 11 2.2K LPSD-12 HD-4 BLP-12-R HB-83
MP-12 N/A A B, D 11 2.2K LPSD-12 HD-4 BLP-12-RN HB-83
MP-12 N/A A B, D 15 2.2K OHM SLR-835 HD-3 NS4-220, NS6-220 HB-3
MP-12 N/A A B, D 15 2.2K OHM SLR-835B-2 HD-6 N/A N/A
MP-24 N/A A B 15 2.2K OHM DCD-135, -190 HD-3 HSC-220L HB-64
MP-24 N/A A B 15 2.2K OHM DCD-135, -190 HD-3 HSC-220R HB-72
MP-24 N/A A B 15 2.2K OHM DCD-135, -190 HD-3 NS4-220, NS6-220 HB-3
MP-24 N/A A B 15 2.2K OHM DFE-135, -190 HD-3 HSC-220L HB-64
MP-24 N/A A B 15 2.2K OHM SIJ-24 HD-3 HSC-220R HB-72
MP-24 N/A A B 15 2.2K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
MP-24 N/A A B 15 2.2K OHM SLR-24H, -24V HD-3 HSC-220R HB-72
MP-24 N/A A B 15 2.2K OHM SLR-24H, -24V HD-3 NS4-220, NS6-220 HB-3
MP-24 N/A A B 15 2.2K OHM SLR-835 HD-3 NS4-220, NS6-220 HB-3
MP-24 N/A A B 15 2.2K OHM SLR-835B-2 HD-6 N/A N/A
MS-4012 N/A A B 11 2.2K LPSD-12 HD-4 BLP-12-R HB-83
MS-4012 N/A A B 11 2.2K LPSD-12 HD-4 BLP-12-RN HB-83
MS-4412B N/A A B 15 2.2K OHM DCD-135, -190 HD-3 HSC-220L HB-64
MS-4412B N/A A B 15 2.2K OHM DCD-135, -190 HD-3 HSC-220R HB-72
MS-4412B N/A A B 15 2.2K OHM DCD-135, -190 HD-3 NS4-220, NS6-220 HB-3
MS-4412B N/A A B 15 2.2K OHM DFE-135, -190 HD-3 HSC-220L HB-64
MS-4412B N/A A B 15 2.2K LPSD-12 HD-4 BLP-12-R HB-83
MS-4412B N/A A B 15 2.2K LPSD-12 HD-4 BLP-12-RN HB-83
MS-4412B N/A A B 15 2.2K OHM SIJ-24 HD-3 HSC-220R HB-72
MS-4412B N/A A B 15 2.2K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
MS-4412B N/A A B 15 2.2K OHM SLR-24H, -24V HD-3 HSC-220R HB-72
MS-4412B N/A A B 15 2.2K OHM SLR-24H, -24V HD-3 NS4-220, NS6-220 HB-3
MS-4412B N/A A B 15 2.2K OHM SLR-835 HD-3 NS4-220, NS6-220 HB-3
MS-4412B N/A A B 15 2.2K OHM SLR-835B-2 HD-6 N/A N/A
MS4412B N/A A B 10 2.2K OHM SLR-835BH-2 HD-6 N/A N/A
MS4412B N/A A B 10 2.2K OHM SLR-835H HD-5 NS4-220,NS6-220 HB-3
MS-5012 N/A A B 15 2.2K OHM DCD-135, -190 HD-3 HSC-220L HB-64
MS-5012 N/A A B 15 2.2K OHM DCD-135, -190 HD-3 HSC-220R HB-72
MS-5012 N/A A B 15 2.2K OHM DCD-135, -190 HD-3 NS4-220, NS6-220 HB-3
MS-5012 N/A A B 15 2.2K OHM DFE-135, -190 HD-3 HSC-220L HB-64
MS-5012 N/A A B 15 2.2K OHM SIJ-24 HD-3 HSC-220R HB-72
MS-5012 N/A A B 15 2.2K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
MS-5012 N/A A B 15 2.2K OHM SLR-24H, -24V HD-3 HSC-220R HB-72
MS-5012 N/A A B 15 2.2K OHM SLR-24H, -24V HD-3 NS4-220, NS6-220 HB-3
MS-5012 N/A A B 10 2.2K OHM SLR-835H HD-5 NS4-220,NS6-220 HB-3
MS-5012 N/A A B 15 2.2K OHM SLR-835 HD-3 NS4-220, NS6-220 HB-3
MS-5012 N/A A B 15 2.2K OHM SLR-835B-2 HD-6 N/A N/A
MS-5012 ZONE 2, 3 A B 11 2.2K LPSD-12 HD-4 BLP-12-R HB-83
MS-5012 ZONE 2, 3 A B 11 2.2K LPSD-12 HD-4 BLP-12-RN HB-83
MS-5024, -5024UD N/A A B, D 15 4.7K OHM DCD-135, -190 HD-3 HSC-220L HB-64
MS-5024, -5024UD N/A A B, D 15 4.7K OHM DCD-135, -190 HD-3 HSC-220R HB-72
MS-5024, -5024UD N/A A B, D 15 4.7K OHM DCD-135, -190 HD-3 NS4-220, NS6-220 HB-3
MS-5024, -5024UD N/A A B, D 15 4.7K OHM DFE-135, -190 HD-3 HSC-220L HB-64
MS-5024, -5024UD N/A A B, D 15 4.7K OHM SIJ-24 HD-3 HSC-220R HB-72
MS-5024, -5024UD N/A A B, D 15 4.7K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
MS-5024, -5024UD N/A A B, D 15 4.7K OHM SLR-24H, -24V HD-3 HSC-220R HB-72
MS-5024, -5024UD N/A A B, D 15 4.7K OHM SLR-24H, -24V HD-3 NS4-220, NS6-220 HB-3
MS-5024, -5024UD N/A A B, D 15 4.7K OHM SLR-835 HD-3 NS4-220, NS6-220 HB-3
MS-5024, -5024UD N/A A B, D 15 4.7K OHM SLR-835B-2 HD-6 N/A N/A
MS-5024,-5024UD N/A A B 10 4.7K OHM SLR-835H HD-5 HSC-220R HB-72
MS-5024,-5024UD N/A A B 10 4.7K OHM SLR-835H HD-5 NS4-220,NS6-220 HB-3
MS-5024,-5024UD N/A A B,D 1 4.7K OHM SLR-835,-835W HD-5 SBC-2,SBC-2W HB-85
MS-5024,-5024UD N/A A B,D 1 4.7K OHM SLR-835,-835W HD-5 SBC-2R,SBC-2RW HB-85
MS-5024,-5024UD N/A A B,D 1 4.7K OHM SLR-835H,-835HW HD-5 SBC-2R,SBC-2RW HB-85
MS-5024,-5024UD N/A A B,D 1 4.7K OHM SLR-835H,-835HW HD-5 SBC-2,SBC-2W HB-85
MS-5024,-5024UD N/A A B,D 1 4.7K OHM SIJ-24 HD-3 SBC-2 HB-85
MS-5024,-5024UD N/A A B,D 1 4.7K OHM SLR-24V HD-3 SBC-2 HB-85
MS-5024,-5024UD N/A A B,D 1 4.7K OHM SLR-24V HD-3 SBC-2R HB-85
MS-5210UD CAC-10E A B,D 10 4.7K OHM SLR-835BH-2 HD-6 N/A N/A
MS-5210UD CAC-10E A B,D 10 4.7K OHM SLR-835H HD-5 HSC-220R HB-72
MS-5210UD CAC-10E A B,D 10 4.7K OHM SLR-835H HD-5 NS4-220,NS6-220 HB-3
MS-5210UD N/A A B, D 15 4.7K OHM DCD-135, -190 HD-3 HSC-220L HB-64
MS-5210UD N/A A B, D 15 4.7K OHM DCD-135, -190 HD-3 HSC-220R HB-72
MS-5210UD N/A A B, D 15 4.7K OHM DCD-135, -190 HD-3 NS4-220, NS6-220 HB-3
MS-5210UD N/A A B, D 15 4.7K OHM DFE-135, -190 HD-3 HSC-220L HB-64
MS-5210UD N/A A B, D 15 4.7K OHM SIJ-24 HD-3 HSC-220R HB-72
MS-5210UD N/A A B, D 15 4.7K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
Page 1 of 2
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

2-Wire Compatibility Listings


PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
MS-5210UD N/A A B, D 15 4.7K OHM SLR-24H, -24V HD-3 HSC-220R HB-72
MS-5210UD N/A A B, D 15 4.7K OHM SLR-24H, -24V HD-3 NS4-220, NS6-220 HB-3
MS-5210UD N/A A B, D 15 4.7K OHM SLR-835 HD-3 NS4-220, NS6-220 HB-3
MS-5210UD N/A A B, D 15 4.7K OHM SLR-835B-2 HD-6 N/A N/A
MS-5210UD N/A,CAC-10F A B, D 1 4.7K OHM SLR-835,-835W HD-5 SBC-2R,SBC-2RW HB-85
MS-5210UD N/A,CAC-10F A B, D 1 4.7K OHM SLR-835H,-835HW HD-5 SBC-2,SBC-2W HB-85
MS-5210UD N/A,CAC-10F A B, D 1 4.7K OHM SLR-835H,-835HW HD-5 SBC-2R,SBC-2RW HB-85
MS-5210UD N/A,CAC-10F A B, D 1 4.7K OHM SIJ-24 HD-3 SBC-2 HB-85
MS-5210UD N/A,CAC-10F A B, D 1 4.7K OHM SLR-24V HD-3 SBC-2 HB-85
MS-5210UD N/A,CAC-10F A B, D 1 4.7K OHM SLR-24V HD-3 SBC-2R HB-85
MS4424 N/A A B,D 1 4.7K OHM SLR-835,-835W HD-5 SBC-2,SBC-2W HB-85
MS4424 N/A A B,D 1 4.7K OHM SLR-835,-835W HD-5 SBC-2R,SBC-2RW HB-85
MS4424 N/A A B,D 1 4.7K OHM SLR-835H,-835HW HD-5 SBC-2R,SBC-2RW HB-85
MS4424 N/A A B,D 1 4.7K OHM SLR-835H,-835HW HD-5 SBC-2,SBC-2W HB-85
MS4424 N/A A B,D 1 4.7K OHM SIJ-24 HD-3 SBC-2 HB-85
MS4424 N/A A B,D 1 4.7K OHM SLR-24V HD-3 SBC-2 HB-85
MS4424 N/A A B,D 1 4.7K OHM SLR-24V HD-3 SBC-2R HB-85
MS-4424B N/A A B 10 4.7K OHM SLR-835H HD-5 HSC-220R HB-72
MS-4424B N/A A B 10 4.7K OHM SLR-835H HD-5 NS4-220,NS6-220 HB-3
MS-4424, MS4424B N/A A B 15 4.7K OHM DCD-135, -190 HD-3 HSC-220L HB-64
MS-4424, MS4424B N/A A B 15 4.7K OHM DCD-135, -190 HD-3 HSC-220R HB-72
MS-4424, MS4424B N/A A B 15 4.7K OHM DCD-135, -190 HD-3 NS4-220, NS6-220 HB-3
MS-4424, MS4424B N/A A B 15 4.7K OHM DFE-135, -190 HD-3 HSC-220L HB-64
MS-4424, MS4424B N/A A B 15 4.7K OHM SIJ-24 HD-3 HSC-220R HB-72
MS-4424, MS4424B N/A A B 15 4.7K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
MS-4424, MS4424B N/A A B 15 4.7K OHM SLR-24H, -24V HD-3 HSC-220R HB-72
MS-4424, MS4424B N/A A B 15 4.7K OHM SLR-24H, -24V HD-3 NS4-220, NS6-220 HB-3
MS-4424, MS4424B N/A A B 15 4.7K OHM SLR-835 HD-3 NS4-220, NS6-220 HB-3
MS-4424, MS4424B N/A A B 15 4.7K OHM SLR-835B-2 HD-6 N/A N/A
RP-1001,-1002 N/A A B, D 20 4.7K OHM DFE-135, -190 N/A HSC-220L HB-64
RP-1001,-1002 N/A A B, D 20 4.7K OHM SLR-24H HD-3 HSC-220R HB-72
RP-1001, -1002 N/A A B, D 20 4.7K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
RP-1001,RP-1002 N/A A B, D 10 4.7K OHM DCD-135, DCD-190 HD-3 HSC-220R HB-72
RP-1001,RP-1002 N/A A B, D 10 4.7K OHM DCD-135, DCD-190 HD-3 NS4-220, NS6-220 HB-3
RP-1001,RP-1002 N/A A B, D 10 4.7K OHM SIJ-24 HD-3 HSC-220R HB-72
RP-1001,RP-1002 N/A A B, D 10 4.7K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
RP-1001,RP-1002 N/A A B, D 10 4.7K OHM SLR-24 HD-3 HSC-220R HB-72
RP-1001,RP-1002 N/A A B, D 10 4.7K OHM SLR-24 HD-3 NS4-220, NS6-220 HB-3
S200/S2000 IZ-4F,IZ-8F A B, D 15 4.7K OHM DCD-135, -190 HD-3 HSC-220L HB-64
S200/S2000 IZ-4F,IZ-8F A B, D 15 4.7K OHM DCD-135, -190 HD-3 HSC-220R HB-72
S200/S2000 IZ-4F,IZ-8F A B, D 15 4.7K OHM DCD-135, -190 HD-3 NS4-220, NS6-220 HB-3
S200/S2000 IZ-4F,IZ-8F A B, D 15 4.7K OHM DFE-135, -190 HD-3 HSC-220L HB-64
S200/S2000 IZ-4F,IZ-8F A B, D 15 4.7K OHM SIJ-24 HD-3 HSC-220R HB-72
S200/S2000 IZ-4F,IZ-8F A B, D 15 4.7K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
S200/S2000 IZ-4F,IZ-8F A B, D 15 4.7K OHM SLR-24H, -24V HD-3 HSC-220R HB-72
S200/S2000 IZ-4F,IZ-8F A B, D 15 4.7K OHM SLR-24H, -24V HD-3 NS4-220, NS6-220 HB-3
S200/S2000 IZ-4F,IZ-8F A B, D 15 4.7K OHM SLR-835 HD-3 NS4-220, NS6-220 HB-3
S200/S2000 IZ-4F,IZ-8F A B, D 15 4.7K OHM SLR-835B-2 HD-6 N/A N/A
SFP-400,-400B N/A A B, D 20 4.7K OHM DFE-135, -190 HD-3 HSC-220L HB-64
SFP-400,-400B N/A A B, D 20 4.7K OHM SLR-24H HD-3 HSC-220R HB-72
SFP-400,-400B N/A A B, D 20 4.7K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
SFP-400,-400B N/A A B, D 20 4.7K OHM DCD-135, DCD-190 HD-3 HSC-220R HB-72
SFP-400,-400B N/A A B, D 20 4.7K OHM DCD-135, DCD-190 HD-3 NS4-220, NS6-220 HB-3
SFP-400,-400B N/A A B, D 20 4.7K OHM SIJ-24 HD-3 HSC-220R HB-72
SFP-400,-400B N/A A B, D 20 4.7K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
SFP-400,-400B N/A A B, D 20 4.7K OHM SLR-24 HD-3 HSC-220R HB-72
SFP-400,-400B N/A A B, D 20 4.7K OHM SLR-24 HD-3 NS4-220, NS6-220 HB-3

UPDATED 9/11/03

Page 2 of 2
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

FIRESCAN
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
SHP 10-2171 MDL NO B/D 25 4.3K SIH-24F HD-3 HS-221D HB-4
SHP 10-2171 MDL NO B/D 25 4.3K SIH-24F HD-3 HSB-220 HB-56
SHP 10-2171 MDL NO B/D 25 4.3K SIH-24F HD-3 HSB-224 HB-53
SHP 10-2171 MDL NO B/D 25 4.3K SIH-24F HD-3 YBA-220 HB-3
SHP 10-2171 MDL NO B/D 25 4.3K SIH-24F HD-3 YBA-M224 HB-5
SHP 10-2171 MDL NO B/D 25 4.3K SLK-24F HD-3 HS-221D HB-4
SHP 10-2171 MDL NO B/D 25 4.3K SLK-24F HD-3 HSB-220 HB-56
SHP 10-2171 MDL NO B/D 25 4.3K SLK-24F HD-3 HSB-224 HB-53
SHP 10-2171 MDL NO B/D 25 4.3K SLK-24F HD-3 YBA-M220 HB-3
SHP 10-2171 MDL NO B/D 25 4.3K SLK-24F HD-3 YBA-M224 HB-5
SHP 10-2171 MDL NO B/D 25 4.3K SLK-24FH HD-3 HS-221D HB-4
SHP 10-2171 MDL NO B/D 25 4.3K SLK-24FH HD-3 HSB-220 HB-56
SHP 10-2171 MDL NO B/D 25 4.3K SLK-24FH HD-3 HSB-224 HB-53
SHP 10-2171 MDL NO B/D 25 4.3K SLK-24FH HD-3 YBA-M220 HB-3
SHP 10-2171 MDL NO B/D 25 4.3K SLK-24FH HD-3 YBA-M224 HB-5
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

G.S. BLDG. SYS.


2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
IRC-1 130022 5876 B 15 260001 SIF-24F HD-2 HS-22D HB-3
IRC-1 130022 5876 D 15 N/A SIF-24F HD-2 HS-22D HB-3
IRC-1 130022 5876 B 15 260001 SIF-24F HD-2 YBA-M22 HB-3
IRC-1 130022 5876 D 15 N/A SIF-24F HD-2 YBA-M22 HB-3
IRC-1 130022 5876 B 15 260001 SLK-24F HD-3 HS-22D HB-3
IRC-1 130022 5876 D 15 N/A SLK-24F HD-3 HS-22D HB-3
IRC-1 130022 5876 B 15 260001 SLK-24F HD-3 YBA-M22 HB-3
IRC-1 130022 5876 D 15 N/A SLK-24F HD-3 YBA-M22 HB-3
IRC-1 130022 5876 B 15 260001 SLK-24FH HD-3 HS-22D HB-3
IRC-1 130022 5876 D 15 N/A SLK-24FH HD-3 HS-22D HB-3
IRC-1 130022 5876 B 15 260001 SLK-24FH HD-3 YBA-M22 HB-3
IRC-1 130022 5876 D 15 N/A SLK-24FH HD-3 YBA-M22 HB-3
IRC-3 130082 3289A B 15 260001 SIF-24F HD-3 HS-22D HB-3
IRC-3 130082 3289A D 15 N/A SIF-24F HD-3 HS-22D HB-3
IRC-3 130082 3289A B 15 260001 SIF-24F HD-2 YBA-M22 HB-3
IRC-3 130082 3289A D 15 N/A SIF-24F HD-2 YBA-M22 HB-3
IRC-3 130082 3289A D 15 N/A SLK-24F HD-3 HS-22D HB-3
IRC-3 130082 3289A B 15 260001 SLK-24F HD-3 HS-22D HB-3
IRC-3 130082 3289A D 15 N/A SLK-24F HD-3 YBA-M22 HB-3
IRC-3 130082 3289A B 15 260001 SLK-24F HD-3 YBA-M22 HB-3
IRC-3 130082 3289A D 15 N/A SLK-24FH HD-3 HS-22D HB-3
IRC-3 130082 3289A B 15 260001 SLK-24FH HD-3 HS-22D HB-3
IRC-3 130082 3289A D 15 N/A SLK-24FH HD-3 YBA-M22 HB-3
IRC-3 130082 3289B B 15 260001 SLK-24FH HD-3 YBA-M22 HB-3
IRC-3 130108 3289B B 15 260001 SIF-24F HD-2 HS-22D HB-3
IRC-3 130108 3289B B 15 260001 SIF-24F HD-2 YBA-M22 HB-3
IRC-3 130108 3289B B 15 260001 SLK-24F HD-3 HS-22D HB-3
IRC-3 130108 3289B B 15 260001 SLK-24F HD-3 YBA-M22 HB-3
IRC-3 130108 3289B B 15 260001 SLK-24FH HD-3 HS-22D HB-3
IRC-3 130108 3289B B 15 260001 SLK-24FH HD-3 YBA-M22 HB-3
IRC-3 130108 3289B B 15 260001 SLK-24FH HD-3 YBA-M22 HB-3
IRC-3 240113 3289B B 15 260001 SIF-24F HD-2 HS-22D HB-3
IRC-3 240113 3289B B 15 260001 SIF-24F HD-2 YBA-M22 HB-3
IRC-3 240113 3289B B 15 260001 SLK-24F HD-3 HS-22D HB-3
IRC-3 240113 3289B B 15 260001 SLK-24F HD-3 YBA-M22 HB-3
IRC-3 240113 3289B B 15 260001 SLK-24FH HD-3 HS-22D HB-3
IRC-3 240113 3289B B 15 260001 SLK-24FH HD-3 YBA-M22 HB-3
IRC-3 240119 3289B B 15 260001 SIF-24F HD-2 HS-22D HB-3
IRC-3 240119 3289B B 15 260001 SIF-24F HD-2 YBA-M22 HB-3
IRC-3 240119 3289B B 15 260001 SLK-24F HD-3 HS-22D HB-3
IRC-3 240119 3289B B 15 260001 SLK-24F HD-3 YBA-M22 HB-3
IRC-3 240119 3289B B 15 260001 SLK-24FH HD-3 HS-22D HB-3
IRC-3 240119 3289B B 15 260001 SLK-24FH HD-3 YBA-M22 HB-3
IRC-3 240205 5389 B 15 PN260001 SIF-24F HD-2 HS-22D HB-3
IRC-3 240205 5389 B 15 PN260001 SIF-24F HD-2 YBA-M22 HB-3
IRC-3 240205 5389 B 15 PN260001 SLK-24F HD-3 HS-22D HB-3
IRC-3 240205 5389 B 15 PN260001 SLK-24F HD-3 YBA-M22 HB-3
IRC-3 240205 5389 B 15 PN260001 SLK-24FH HD-3 HS-22D HB-3
IRC-3 240205 5389 B 15 PN260001 SLK-24FH HD-3 YBA-M22 HB-3
LSS1, LSS4 4CLA 0.0 D 30 N/A SIF-24F HD-3 HS-220D HB-3
LSS1, LSS4 4CLA 0.0 D 30 N/A SIF-24F HD-3 HS-224D HB-5
LSS1, LSS4 4CLA 0.0 D 30 N/A SIF-24F HD-3 YBA-M224 HB-5
LSS1, LSS4 4CLA 0.0 D 30 N/A SIF-24F HD-3 YBA-M220 HB-3
LSS1, LSS4 4CLA 0.0 D 30 N/A SLK-24F HD-3 HS-220D HB-3
LSS1, LSS4 4CLA 0.0 D 30 N/A SLK-24F HD-3 HS-M224 HB-5
LSS1, LSS4 4CLA 0.0 D 30 N/A SLK-24F HD-3 YBA-M224D HB-5
LSS1, LSS4 4CLA 0.0 D 30 N/A SLK-24F HD-3 YBA-M220 HB-3
LSS1, LSS4 4CLA 0.0 D 30 N/A SLK-24FH HD-3 HS-220D HB-3
LSS1, LSS4 4CLA 0.0 D 30 N/A SLK-24FH HD-3 HS-224D HB-5
LSS1, LSS4 4CLA 0.0 D 30 N/A SLK-24FH HD-3 YBA-M224 HB-5
LSS1, LSS4 4CLA 0.0 D 30 N/A SLK-24FH HD-3 YBA-M220 HB-3
LSS1, LSS4 4ZEXP 0.0 B 30 3.9K OHM SIH-24F HD-3 HS-220D HB-3
LSS1, LSS4 4ZEXP 0.0 D 30 N/A SIH-24F HD-3 HS-220D HB-3
LSS1, LSS4 4ZEXP 0.0 B 30 3.9K OHM SIH-24F HD-3 HS-224D HB-5
LSS1, LSS4 4ZEXP 0.0 D 30 N/A SIH-24F HD-3 HS-224D HB-5
LSS1, LSS4 4ZEXP 0.0 B 30 3.9K OHM SIH-24F HD-3 YBA-M224 HB-5
LSS1, LSS4 4ZEXP 0.0 D 30 N/A SIH-24F HD-3 YBA-M224 HB-5
LSS1, LSS4 4ZEXP 0.0 B 30 3.9K OHM SIH-24F HD-3 YBA-M220 HB-3
LSS1, LSS4 4ZEXP 0.0 D 30 N/A SIH-24F HD-3 YBA-M220 HB-3
LSS1, LSS4 4ZEXP 0.0 D 30 N/A SLK-24F HD-3 HS-220D HB-3
LSS1, LSS4 4ZEXP 0.0 B 30 3.9K OHM SLK-24F SLK-24F HS-220D HB-3
LSS1, LSS4 4ZEXP 0.0 B 30 3.9K OHM SLK-24F SLK-24F HS-M224 HB-5
LSS1, LSS4 4ZEXP 0.0 D 30 N/A SLK-24F HD-3 HS-M224 HB-5
LSS1, LSS4 4ZEXP 0.0 D 30 N/A SLK-24F HD-3 YBA-M224D HB-5
LSS1, LSS4 4ZEXP 0.0 B 30 3.9K OHM SLK-24F HD-3 YBA-M224D HB-5
LSS1, LSS4 4ZEXP 0.0 D 30 N/A SLK-24F HD-3 YBA-M220 HB-3
LSS1, LSS4 4ZEXP 0.0 B 30 3.9K OHM SLK-24F HD-3 YBA-M220 HB-3
LSS1, LSS4 4ZEXP 0.0 D 30 N/A SLK-24FH HD-3 HS-220D HB-3
LSS1, LSS4 4ZEXP 0.0 B 30 3.9K OHM SLK-24FH HD-3 HS-220D HB-3
LSS1, LSS4 4ZEXP 0.0 D 30 N/A SLK-24FH HD-3 HS-224D HB-5

Page 1 of 3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

2-Wire Compatibility Listings


PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
LSS1, LSS4 4ZEXP 0.0 B 30 3.9K OHM SLK-24FH HD-3 HS-224D HB-5
LSS1, LSS4 4ZEXP 0.0 B 30 3.9K OHM SLK-24FH HD-3 HS-M224 HB-5
LSS1, LSS4 4ZEXP 0.0 D 30 N/A SLK-24FH HD-3 HS-M224 HB-5
LSS1, LSS4 4ZEXP 0.0 D 30 N/A SLK-24FH HD-3 YBA-M220 HB-3
LSS1, LSS4 4ZEXP 0.0 B 30 3.9K OHM SLK-24FH HD-3 YBA-M220 HB-3
LSS1, LSS4 MOTHERBOARD 0.0 B 30 3.9K OHM SIH-24F HD-3 HS-220D HB-3
LSS1, LSS4 MOTHERBOARD 0.0 D 30 N/A SIH-24F HD-3 HS-220D HB-3
LSS1, LSS4 MOTHERBOARD 0.0 D 30 N/A SIH-24F HD-3 HS-224D HB-5
LSS1, LSS4 MOTHERBOARD 0.0 B 30 3.9K OHM SIH-24F HD-3 HS-224D HB-5
LSS1, LSS4 MOTHERBOARD 0.0 D 30 N/A SIH-24F HD-3 YBA-M224 HB-5
LSS1, LSS4 MOTHERBOARD 0.0 B 30 3.9K OHM SIH-24F HD-3 YBA-M224 HB-5
LSS1, LSS4 MOTHERBOARD 0.0 B 30 3.9K OHM SIH-24F HD-3 YBA-M220 HB-3
LSS1, LSS4 MOTHERBOARD 0.0 D 30 N/A SIH-24F HD-3 YBA-M220 HB-3
LSS1, LSS4 MOTHERBOARD 0.0 D 30 N/A SLK-24F HD-3 HS-220D HB-3
LSS1, LSS4 MOTHERBOARD 0.0 B 30 3.9K OHM SLK-24F HD-3 HS-220D HB-3
LSS1, LSS4 MOTHERBOARD 0.0 B 30 3.9K OHM SLK-24F HD-3 HS-M224 HB-5
LSS1, LSS4 MOTHERBOARD 0.0 D 30 N/A SLK-24F HD-3 HS-M224 HB-5
LSS1, LSS4 MOTHERBOARD 0.0 D 30 N/A SLK-24F HD-3 YBA-M224D HB-5
LSS1, LSS4 MOTHERBOARD 0.0 B 30 3.9K OHM SLK-24F HD-3 YBA-M224D HB-5
LSS1, LSS4 MOTHERBOARD 0.0 D 30 N/A SLK-24F HD-3 YBA-M220 HB-3
LSS1, LSS4 MOTHERBOARD 0.0 B 30 3.9K OHM SLK-24F HD-3 YBA-M220 HB-3
LSS1, LSS4 MOTHERBOARD 0.0 D 30 N/A SLK-24FH HD-3 HS-220D HB-3
LSS1, LSS4 MOTHERBOARD 0.0 B 30 3.9K OHM SLK-24FH HD-3 HS-220D HB-3
LSS1, LSS4 MOTHERBOARD 0.0 D 30 N/A SLK-24FH HD-3 HS-224D HB-5
LSS1, LSS4 MOTHERBOARD 0.0 B 30 3.9K OHM SLK-24FH HD-3 HS-224D HB-5
LSS1, LSS4 MOTHERBOARD 0.0 D 30 N/A SLK-24FH HD-3 YBA-M224 HB-5
LSS1, LSS4 MOTHERBOARD 0.0 B 30 3.9K OHM SLK-24FH HD-3 YBA-M224 HB-5
LSS1, LSS4 MOTHERBOARD 0.0 D 30 N/A SLK-24FH HD-3 YBA-M220 HB-3
LSS1, LSS4 MOTHERBOARD 0.0 B 30 3.9K OHM SLK-24FH HD-3 YBA-M220 HB-3
LSS1/12,LSS4/12 4CLA 0.0 D 30 N/A SIH-24F HD-3 HS-220D HB-3
LSS1/12,LSS4/12 4CLA 0.0 D 30 N/A SIH-24F HD-3 HS-224D HB-5
LSS1/12,LSS4/12 4CLA 0.0 D 30 N/A SIH-24F HD-3 YBA-M224 HB-5
LSS1/12,LSS4/12 4CLA 0.0 D 30 N/A SIH-24F HD-3 YBA-M220 HB-3
LSS1/12,LSS4/12 4CLA 0.0 D 30 N/A SLK-24F HD-3 HS-220D HB-3
LSS1/12,LSS4/12 4CLA 0.0 D 30 N/A SLK-24F HD-3 HS-M224 HB-5
LSS1/12,LSS4/12 4CLA 0.0 D 30 N/A SLK-24F HD-3 YBA-M224D HB-5
LSS1/12,LSS4/12 4CLA 0.0 D 30 N/A SLK-24F HD-3 YBA-M220 HB-3
LSS1/12,LSS4/12 4CLA 0.0 D 30 N/A SLK-24FH HD-3 HS-220D HB-3
LSS1/12,LSS4/12 4CLA 0.0 D 30 N/A SLK-24FH HD-3 HS-224D HB-5
LSS1/12,LSS4/12 4CLA 0.0 D 30 N/A SLK-24FH HD-3 YBA-M224 HB-5
LSS1/12,LSS4/12 4CLA 0.0 D 30 N/A SLK-24FH HD-3 YBA-M220 HB-3
LSS1/12,LSS4/12 4ZEXP 0.0 B 30 3.9K OHM SIH-24F HD-3 HS-220D HB-3
LSS1/12,LSS4/12 4ZEXP 0.0 D 30 N/A SIH-24F HD-3 HS-220D HB-3
LSS1/12,LSS4/12 4ZEXP 0.0 D 30 N/A SIH-24F HD-3 HS-224D HB-5
LSS1/12,LSS4/12 4ZEXP 0.0 B 30 3.9K OHM SIH-24F HD-3 HS-224D HB-5
LSS1/12,LSS4/12 4ZEXP 0.0 D 30 N/A SIH-24F HD-3 YBA-M224 HB-5
LSS1/12,LSS4/12 4ZEXP 0.0 B 30 3.9K OHM SIH-24F HD-3 YBA-M224 HB-5
LSS1/12,LSS4/12 4ZEXP 0.0 D 30 N/A SIH-24F HD-3 YBA-M220 HB-3
LSS1/12,LSS4/12 4ZEXP 0.0 B 30 3.9K OHM SIH-24F HD-3 YBA-M220 HB-3
LSS1/12,LSS4/12 4ZEXP 0.0 B 30 3.9K OHM SLK-24F HD-3 HS-220D HB-3
LSS1/12,LSS4/12 4ZEXP 0.0 D 30 N/A SLK-24F HD-3 HS-220D HB-3
LSS1/12,LSS4/12 4ZEXP 0.0 D 30 N/A SLK-24F HD-3 HS-M224 HB-5
LSS1/12,LSS4/12 4ZEXP 0.0 B 30 3.9K OHM SLK-24F HD-3 HS-M224 HB-5
LSS1/12,LSS4/12 4ZEXP 0.0 D 30 N/A SLK-24F HD-3 YBA-M224D HB-5
LSS1/12,LSS4/12 4ZEXP 0.0 B 30 3.9K OHM SLK-24F HD-3 YBA-M224D HB-5
LSS1/12,LSS4/12 4ZEXP 0.0 D 30 N/A SLK-24F HD-3 YBA-M220 HB-3
LSS1/12,LSS4/12 4ZEXP 0.0 B 30 3.9K OHM SLK-24F HD-3 YBA-M220 HB-3
LSS1/12,LSS4/12 4ZEXP 0.0 D 30 N/A SLK-24FH HD-3 HS-220D HB-3
LSS1/12,LSS4/12 4ZEXP 0.0 B 30 3.9K OHM SLK-24FH HD-3 HS-220D HB-3
LSS1/12,LSS4/12 4ZEXP 0.0 B 30 3.9K OHM SLK-24FH HD-3 HS-224D HB-5
LSS1/12,LSS4/12 4ZEXP 0.0 D 30 N/A SLK-24FH HD-3 HS-224D HB-5
LSS1/12,LSS4/12 4ZEXP 0.0 D 30 N/A SLK-24FH HD-3 YBA-M224 HB-5
LSS1/12,LSS4/12 4ZEXP 0.0 B 30 3.9K OHM SLK-24FH HD-3 YBA-M224 HB-5
LSS1/12,LSS4/12 4ZEXP 0.0 B 30 3.9K OHM SLK-24FH HD-3 YBA-M220 HB-3
LSS1/12,LSS4/12 4ZEXP 0.0 D 30 N/A SLK-24FH HD-3 YBA-M220 HB-3
LSS1/12,LSS4/12 MOTHERBOARD 0.0 D 30 N/A SIH-24F HD-3 HS-220D HB-3
LSS1/12,LSS4/12 MOTHERBOARD 0.0 B 30 3.9K OHM SIH-24F HD-3 HS-220D HB-3
LSS1/12,LSS4/12 MOTHERBOARD 0.0 B 30 3.9K OHM SIH-24F HD-3 HS-224D HB-5
LSS1/12,LSS4/12 MOTHERBOARD 0.0 D 30 N/A SIH-24F HD-3 HS-224D HB-5
LSS1/12,LSS4/12 MOTHERBOARD 0.0 D 30 N/A SIH-24F HD-3 YBA-M224 HB-5
LSS1/12,LSS4/12 MOTHERBOARD 0.0 B 30 3.9K OHM SIH-24F HD-3 YBA-M224 HB-5
LSS1/12,LSS4/12 MOTHERBOARD 0.0 D 30 N/A SIH-24F HD-3 YBA-M220 HB-3
LSS1/12,LSS4/12 MOTHERBOARD 0.0 B 30 3.9K OHM SIH-24F HD-3 YBA-M220 HB-3
LSS1/12,LSS4/12 MOTHERBOARD 0.0 D 30 N/A SLK-24F HD-3 HS-220D HB-3
LSS1/12,LSS4/12 MOTHERBOARD 0.0 B 30 3.9K OHM SLK-24F HD-3 HS-220D HB-3
LSS1/12,LSS4/12 MOTHERBOARD 0.0 D 30 N/A SLK-24F HD-3 HS-M224 HB-5

Page 2 of 3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

2-Wire Compatibility Listings


PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
LSS1/12,LSS4/12 MOTHERBOARD 0.0 B 30 3.9K OHM SLK-24F HD-3 HS-M224 HB-5
LSS1/12,LSS4/12 MOTHERBOARD 0.0 B 30 3.9K OHM SLK-24F HD-3 YBA-M224D HB-5
LSS1/12,LSS4/12 MOTHERBOARD 0.0 D 30 N/A SLK-24F HD-3 YBA-M224D HB-5
LSS1/12,LSS4/12 MOTHERBOARD 0.0 D 30 N/A SLK-24F HD-3 YBA-M220 HB-3
LSS1/12,LSS4/12 MOTHERBOARD 0.0 B 30 3.9K OHM SLK-24F HD-3 YBA-M220 HB-3
LSS1/12,LSS4/12 MOTHERBOARD 0.0 D 30 N/A SLK-24FH HD-3 HS-220D HB-3
LSS1/12,LSS4/12 MOTHERBOARD 0.0 B 30 3.9K OHM SLK-24FH HD-3 HS-220D HB-3
LSS1/12,LSS4/12 MOTHERBOARD 0.0 D 30 N/A SLK-24FH HD-3 HS-224D HB-5
LSS1/12,LSS4/12 MOTHERBOARD 0.0 B 30 3.9K OHM SLK-24FH HD-3 HS-224D HB-5
LSS1/12,LSS4/12 MOTHERBOARD 0.0 D 30 N/A SLK-24FH HD-3 YBA-M224 HB-5
LSS1/12,LSS4/12 MOTHERBOARD 0.0 B 30 3.9K OHM SLK-24FH HD-3 YBA-M224 HB-5
LSS1/12,LSS4/12 MOTHERBOARD 0.0 D 30 N/A SLK-24FH HD-3 YBA-M220 HB-3
LSS1/12,LSS4/12 MOTHERBOARD 0.0 B 30 3.9K OHM SLK-24FH HD-3 YBA-M220 HB-3

Page 3 of 3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

GRINNELL
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
C200 NA 24F B 30 7628 SIH-24F HD-3 HS-224D/HSB-224 HB-5
C200 NA 24F B 30 7628 SLK-24F,-FH HD3 HS-224D HB-5
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

HOCHIKI AMERICA CORPORATION


2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
AL-1500 AL-4ZDM HP-2A B 30 4.7K DCA-135 N/A YBF-RL/4H5US HB-21
AL-1500 AL-4ZDM HP-2A B 30 4.7K DCA-135 N/A YBF-RL/4H5US HB-21
AL-1500 AL-4ZDM HP-2A B 30 4.7K DCA-190 N/A YBF-RL/4H5US HB-21
AL-1500 AL-4ZDM HP-2A B 30 4.7K DCA-190 N/A YBF-RL/4H5US HB-21
AL-1500 AL-4ZDM HP-2A B 30 4.7K DFE-135 N/A YBF-RL/4H5US HB-21
AL-1500 AL-4ZDM HP-2A B 30 4.7K DFE-135 N/A YBF-RL/4H5US HB-21
AL-1500 AL-4ZDM HP-2A B 30 4.7K DFE-190 N/A YBF-RL/4H5US HB-21
AL-1500 AL-4ZDM HP-2A B 30 4.7K DFE-190 N/A YBF-RL/4H5US HB-21
AL-1500 AL-4ZDM HP-2A B 30 4.7K SIF-24F HD-2 HS-224RB HB-14
AL-1500 AL-4ZDM HP-2A B 30 4.7K SIH-24F HD-3 HS-224RB HB-14
AL-1500 AL-4ZDM HP-2A B 30 4.7K SLK-24F HD-3 HS-224RB HB-14
AL-1500 AL-4ZDM HP-2A B 30 4.7K SLK-24FH HD-3 HS-224RB HB-14
HCP1000 N/A A B, D 30 3.9K OHM SLR-24H HD-3 HSC-220R HB-72
HCP1000 N/A A B, D 30 3.9K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
HCP1000 N/A A B, D 30 3.9K OHM DFE-135, -190 HD-3 HSC-220L HB-64
HCP1000 N/A A B, D 30 3.9K OHM DCD-135,DCD-190 HD-3 HSC-220R HB-72
HCP1000 N/A A B, D 30 3.9K OHM DCD-135,DCD-190 HD-3 NS4-220, NS6-220 HB-3
HCP1000 N/A A B, D 30 3.9K OHM SIJ-24 HD-3 HSC-220R HB-72
HCP1000 N/A A B, D 30 3.9K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
HCP1000 N/A A B, D 30 3.9K OHM SLR-24V HD-3 HSC-220R HB-72
HCP1000 N/A A B, D 30 3.9K OHM SLR-24V HD-3 NS4-220, NS6-220 HB-3
HCP1000 N/A A B, D 30 3.9K OHM SLR-835,-835H HD-5 HSC-220R HB-72
HCP1000 N/A A B, D 30 3.9K OHM SLR-835,-835W HD-5 NS4-220, -220W HB-3
HCP1000 N/A A B, D 30 3.9K OHM SLR-835,-835W HD-5 NS6-220, -220W HB-3
HCP1000 N/A A B, D 3 3.9K OHM SLR-835B-2 HD-6 N/A N/A
HCP1000 N/A A B, D 3 3.9K OHM SLR-835B-2W HD-6 N/A N/A
HCP1000 N/A A B, D 3 3.9K OHM SLR-835BH-2 HD-6 N/A N/A
HCP1000 N/A A B, D 3 3.9K OHM SLR-835BH-2W HD-6 N/A N/A
HCP1000 N/A A B, D 30 3.9K OHM SLR-835H,-835HW HD-5 NS4-220, -220W HB-3
HCP1000 N/A A B, D 30 3.9K OHM SLR-835H,-835HW HD-5 NS6-220, -220W HB-3
HCP-1000 SERIES N/A A B, D 1 3.9K OHM SLR-835,-835W HD-5 SBC-2,SBC-2W HB-85
HCP-1000 SERIES N/A A B, D 1 3.9K OHM SLR-835,-835W HD-5 SBC-2R HB-85
HCP-1000 SERIES N/A A B, D 1 3.9K OHM SLR-835,-835W HD-5 SBC-2R,SBC-2RW HB-85
HCP-1000 SERIES N/A A B, D 1 3.9K OHM SLR-835H,-835HW HD-5 SBC-2R,SBC-2RW HB-85
HCP-1000 SERIES N/A A B, D 1 3.9K OHM SLR-835H,-835HW HD-5 SBC-2,SBC-2W HB-85
HCP-1000 SERIES N/A A B, D 1 3.9K OHM SIJ-24 HD-3 SBC-2 HB-85
HCP-1000 SERIES N/A A B, D 1 3.9K OHM SLR-24V HD-3 SBC-2 HB-85
HCP-1000 SERIES N/A A B, D 1 3.9K OHM SLR-24V HD-3 SBC-2R HB-85
HCP200 SERIES N/A A B, D 30 3.9K OHM DCD-135,DCD-190 HD-3 HSC-220R HB-72
HCP200 SERIES N/A A B, D 30 3.9K OHM DCD-135,DCD-190 HD-3 NS4-220, NS6-220 HB-3
HCP200 SERIES N/A A B, D 30 3.9K OHM SIJ-24 HD-3 HSC-220R HB-72
HCP200 SERIES N/A A B, D 30 3.9K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
HCP200 SERIES N/A A B, D 30 3.9K OHM SLR-24 HD-3 HSC-220R HB-72
HCP200 SERIES N/A A B, D 30 3.9K OHM SLR-24 HD-3 NS4-220, NS6-220 HB-3
HCP200 SERIES N/A A B, D 30 3.9K OHM SLR-24H HD-3 HSC-220R HB-72
HCP200 SERIES N/A A B, D 30 3.9K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
HCP200 SERIES N/A A B, D 30 3.9K OHM DFE-135, -190 HD-3 HSC-220L HB-64
HCP200 SERIES N/A A B, D 30 3.9K OHM SLR-24V HD-3 HSC-220R HB-72
HCP200 SERIES N/A A B, D 30 3.9K OHM SLR-24V HD-3 NS4-220, NS6-220 HB-3
HCP200 SERIES N/A A B, D 30 3.9K OHM SLR-835,-835H HD-5 HSC-220R HB-72
HCP200 SERIES N/A A B, D 30 3.9K OHM SLR-835,-835W HD-5 NS4-220, -220W HB-3
HCP200 SERIES N/A A B, D 30 3.9K OHM SLR-835,-835W HD-5 NS6-220, -220W HB-3
HCP200 SERIES N/A A B, D 3 3.9K OHM SLR-835B-2 HD-6 N/A N/A
HCP200 SERIES N/A A B, D 3 3.9K OHM SLR-835B-2W HD-6 N/A N/A
HCP200 SERIES N/A A B, D 3 3.9K OHM SLR-835BH-2 HD-6 N/A N/A
HCP200 SERIES N/A A B, D 3 3.9K OHM SLR-835BH-2W HD-6 N/A N/A
HCP200 SERIES N/A A B, D 30 3.9K OHM SLR-835H,-835HW HD-5 NS4-220, -220W HB-3
HCP200 SERIES N/A A B, D 30 3.9K OHM SLR-835H,-835HW HD-5 NS6-220, -220W HB-3
HCP200 SERIES N/A A B, D 1 3.9K OHM SLR-835,-835W HD-5 SBC-2,SBC-2W HB-85
HCP200 SERIES N/A A B, D 1 3.9K OHM SLR-835,-835W HD-5 SBC-2R,SBC-2RW HB-85
HCP200 SERIES N/A A B, D 1 3.9K OHM SLR-835H,-835HW HD-5 SBC-2R,SBC-2RW HB-85
HCP200 SERIES N/A A B, D 1 3.9K OHM SLR-835H,-835HW HD-5 SBC-2,SBC-2W HB-85
HCP200 SERIES N/A A B, D 1 3.9K OHM SIJ-24 HD-3 SBC-2 HB-85
HCP200 SERIES N/A A B, D 1 3.9K OHM SLR-24V HD-3 SBC-2 HB-85
HCP200 SERIES N/A A B, D 1 3.9K OHM SLR-24V HD-3 SBC-2R HB-85

UPDATED 9/11/03
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

ISI WIRELESS
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
FMS 1000 4ZID 4ZID D 66 N/A SIF-24F HD-2 HS-220 HB-3
FMS 1000 4ZID 4ZID D 66 N/A SLK-24FH HD-3 HS-220 HB-3
FMS 1000 4ZM 4ZMB B 66 4.7K OHM SIF-24F HD-2 HS-220 HB-3
FMS 1000 4ZM 4ZMA B 15 22K OHM SIF-24F HD-2 HS-220 HB-3
FMS 1000 4ZM 4ZMB B 66 4.7K OHM SLK-24FH HD-3 HS-220 HB-3
FMS 1000 4ZM 4ZMA B 15 22K OHM SLK-24FH HD-3 HS-220 HB-3
FMS 500 4ZID 4ZID D 66 N/A SIF-24F HD-2 HS-220 HB-3
FMS 500 4ZID 4ZID D 66 N/A SLK-24FH HD-3 HS-220 HB-3
FMS 500 4ZM 4ZMA B 15 22K OHM SIF-24F HD-2 HS-220 HB-3
FMS 500 4ZM 4ZMB B 66 4.7K OHM SIF-24F HD-2 HS-220 HB-3
FMS 500 4ZM 4ZMA B 15 22K OHM SLK-24FH HD-3 HS-220 HB-3
FMS 500 4ZM 4ZMB B 66 4.7K OHM SLK-24FH HD-3 HS-220 HB-3
FMS 500-96 4ZID 4ZID D 66 N/A SIF-24F HD-2 HS-220 HB-3
FMS 500-96 4ZID 4ZID D 66 N/A SLK-24FH HD-3 HS-220 HB-3
FMS 500-96 4ZM 4ZMA B 15 22K OHM SIF-24F HD-2 HS-220 HB-3
FMS 500-96 4ZM 4ZMB B 66 4.7K OHM SIF-24F HD-2 HS-220 HB-3
FMS 500-96 4ZM 4ZMA B 15 22K OHM SLK-24FH HD-3 HS-220 HB-3
FMS 500-96 4ZM 4ZMB B 66 4.7K OHM SLK-24FH HD-3 HS-220 HB-3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

MIRCOM
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
FA-1000 N/A A B, D 30 3.9K OHM DEF-135, -190 N/A HSC-220L HB-64
FA-1000 N/A A B, D 30 3.9K OHM SLR-24H HD-3 HSC-220R HB-72
FA-1000 N/A A B, D 30 3.9K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
FA-101U N/A A B 30 3.9K OHM DCD-135 HD-3 HSC-220R HB-72
FA-101U N/A A B 30 3.9K OHM DCD-135 HD-3 NS4-220, NS6-220 HB-3
FA-101U N/A A B 30 3.9K OHM DCD-190 HD-3 HSC-220R HB-72
FA-101U N/A A B 30 3.9K OHM DCD-190 HD-3 NS4-220, NS6-220 HB-3
FA-101U N/A A B 30 3.9K OHM SIJ-24 HD-3 HSC-220R HB-72
FA-101U N/A A B 30 3.9K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
FA-101U N/A A B 30 3.9K OHM SLR-24 HD-3 HSC-220R HB-72
FA-101U N/A A B 30 3.9K OHM SLR-24 HD-3 NS4-220, NS6-220 HB-3
FA-101U, FA-1020U N/A A B, D 30 3.9K OHM DEF-135, -190 N/A HSC-220L HB-64
FA-101U, FA-1020U N/A A B, D 30 3.9K OHM SLR-24H HD-3 HSC-220R HB-72
FA-101U, FA-1020U N/A A B, D 30 3.9K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
FA-1025U N/A A B 30 3.9K OHM DCD-135 HD-3 HSC-220R HB-72
FA-1025U N/A A B 30 3.9K OHM DCD-135 HD-3 NS4-220, NS6-220 HB-3
FA-1025U N/A A B 30 3.9K OHM DCD-190 HD-3 HSC-220R HB-72
FA-1025U N/A A B 30 3.9K OHM DCD-190 HD-3 NS4-220, NS6-220 HB-3
FA-1025U N/A A B 30 3.9K OHM DFE-135, -190 N/A HSC-220L HB-64
FA-1025U N/A A B 30 3.9K OHM SIJ-24 HD-3 HSC-220R HB-72
FA-1025U N/A A B,D 30 3.9K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
FA-1025U N/A A B 30 3.9K OHM SLR-24 HD-3 HSC-220R HB-72
FA-1025U N/A A B 30 3.9K OHM SLR-24 HD-3 NS4-220, NS6-220 HB-3
FA-1025U N/A A B,D 30 3.9K OHM SLR-24H HD-3 HSC-220R HB-72
FA-102U N/A A B 30 3.9K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
FA-102U N/A A B 30 3.9K OHM DCD-135 HD-3 HSC-220R HB-72
FA-102U N/A A B 30 3.9K OHM DCD-135 HD-3 NS4-220, NS6-220 HB-3
FA-102U N/A A B 30 3.9K OHM DCD-190 HD-3 HSC-220R HB-72
FA-102U N/A A B 30 3.9K OHM DCD-190 HD-3 NS4-220, NS6-220 HB-3
FA-102U N/A A B 30 3.9K OHM SIJ-24 HD-3 HSC-220R HB-72
FA-102U N/A A B 30 3.9K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
FA-102U N/A A B 30 3.9K OHM SLR-24 HD-3 HSC-220R HB-72
FA-102U N/A A B 30 3.9K OHM SLR-24 HD-3 NS4-220, NS6-220 HB-3
FA-104/8U N/A A B, D 30 3.9K OHM DEF-135, -190 N/A HSC-220L HB-64
FA-104/8U N/A A B, D 30 3.9K OHM SLR-24H HD-3 HSC-220R HB-72
FA-104/8U N/A A B, D 30 3.9K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
FA-104/8U, 8UX N/A A B 30 3.9K OHM SLR-24H HD-3 HSC-220R HB-72
FA-104/8U, 8UX N/A A B 30 3.9K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
FA-104/8U, 8UX N/A A B 30 3.9K OHM DCD-135 HD-3 HSC-220R HB-72
FA-104/8U, 8UX N/A A B 30 3.9K OHM DCD-135 HD-3 NS4-220, NS6-220 HB-3
FA-104/8U, 8UX N/A A B 30 3.9K OHM DCD-190 HD-3 HSC-220R HB-72
FA-104/8U, 8UX N/A A B 30 3.9K OHM DCD-190 HD-3 NS4-220, NS6-220 HB-3
FA-104/8U, 8UX N/A A B 30 3.9K OHM SIJ-24 HD-3 HSC-220R HB-72
FA-104/8U, 8UX N/A A B 30 3.9K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
FA-104/8U, 8UX N/A A B 30 3.9K OHM SLR-24 HD-3 HSC-220R HB-72
FA-104/8U, 8UX N/A A B 30 3.9K OHM SLR-24 HD-3 NS4-220, NS6-220 HB-3
FA-104/BUX N/A A B, D 30 3.9K OHM DEF-135, -190 N/A HSC-220L HB-64
FA-104/BUX N/A A B, D 30 3.9K OHM SLR-24H HD-3 HSC-220R HB-72
FA-104/BUX N/A A B, D 30 3.9K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
FA-200 N/A A B, D 30 3.9K OHM DEF-135, -190 N/A HSC-220L HB-64
FA-200 N/A A B, D 30 3.9K OHM SLR-24H HD-3 HSC-220R HB-72
FA-200 N/A A B, D 30 3.9K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
FA-200 N/A A B, D 30 3.9K OHM SLR-835B-2 HD-6 N/A N/A
FA-200, FA-1000 N/A A B, D 30 3.9K OHM DCD-135 HD-3 HSC-220R HB-72
FA-200, FA-1000 N/A A B, D 30 3.9K OHM DCD-135 HD-3 NS4-220, NS6-220 HB-3
FA-200, FA-1000 N/A A B, D 30 3.9K OHM DCD-190 HD-3 HSC-220R HB-72
FA-200, FA-1000 N/A A B, D 30 3.9K OHM DCD-190 HD-3 NS4-220, NS6-220 HB-3
FA-200, FA-1000 N/A A B, D 30 3.9K OHM SIJ-24 HD-3 HSC-220R HB-72
FA-200, FA-1000 N/A A B, D 30 3.9K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
FA-200, FA-1000 N/A A B, D 30 3.9K OHM SLR-24 HD-3 HSC-220R HB-72
FA-200, FA-1000 N/A A B, D 30 3.9K OHM SLR-24 HD-3 NS4-220, NS6-220 HB-3
FA-1000 N/A A B, D 30 3.9K OHM SLR-835B-2 HD-6 N/A N/A
SERIES 100 N/A A B 30 3.9K OHM DCD-135 HD-3 HSC-220R HB-72
SERIES 100 N/A A B 30 3.9K OHM DCD-135 HD-3 NS4-220, NS6-220 HB-3
SERIES 100 N/A A B 30 3.9K OHM DCD-190 HD-3 HSC-220R HB-72
SERIES 100 N/A A B 30 3.9K OHM DCD-190 HD-3 NS4-220, NS6-220 HB-3
SERIES 100 N/A A B, D 30 3.9K OHM DEF-135, -190 N/A HSC-220L HB-64
SERIES 100 N/A A B 30 3.9K OHM SIJ-24 HD-3 HSC-220R HB-72
SERIES 100 N/A A B 30 3.9K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
SERIES 100 N/A A B 30 3.9K OHM SLR-24 HD-3 HSC-220R HB-72
SERIES 100 N/A A B 30 3.9K OHM SLR-24 HD-3 NS4-220, NS6-220 HB-3
SERIES 100 N/A A B, D 30 3.9K OHM SLR-24H HD-3 HSC-220R HB-72
SERIES 100 N/A A B, D 30 3.9K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

MODULAR PROT.
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
RP-1002M N/A A B, D 30 4.7K SIH-24F HD-3 HS-2-RB HB-10
RP-1002M N/A A B, D 30 4.7K SIH-24F HD-3 HS-22D HB-3
RP-1002M N/A A B, D 30 4.7K SIH-24F HD-3 HSB-220 HB-56
RP-1002M N/A A B, D 30 4.7K SIH-24F HD-3 HSB-224 HB-53
RP-1002M N/A A B, D 30 4.7K SIH-24F HD-3 YBA-M22 HB-3
RP-1002M N/A A B, D 30 4.7K SLK-24F HD-3 HS-2-RB HB-10
RP-1002M N/A A B, D 30 4.7K SLK-24F HD-3 HS-22D HB-3
RP-1002M N/A A B, D 30 4.7K SLK-24F HD-3 HSB-220 HB-56
RP-1002M N/A A B, D 30 4.7K SLK-24F HD-3 HSB-224 HB-53
RP-1002M N/A A B, D 30 4.7K SLK-24F HD-3 YBA-M22 HB-3
RP-1002M N/A A B, D 30 4.7K SLK-24FH HD-3 HS-2-RB HB-10
RP-1002M N/A A B, D 30 4.7K SLK-24FH HD-3 HS-22D HB-3
RP-1002M N/A A B, D 30 4.7K SLK-24FH HD-3 HSB-220 HB-56
RP-1002M N/A A B, D 30 4.7K SLK-24FH HD-3 HSB-224 HB-53
RP-1002M A B, D 30 SLK-24FH HD-3 YBA-M22 HB-3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

NAPCO
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
GEM-3200,-P9600 NA GEM-PS B 10 2.2K OHM SLR-835BH-2 HD-6 N/A N/A
GEM-P1632 NA MDL NO B 10 2.2K SLR-835B-2 HD-6 N/A N/A
GEM-P1632 NA NA B,D 10 2.2K OHM SLR-835BH-2 HD-6 N/A N/A
GEM-P3200 NA GEM-PF B 10 2.2K SLR-835B-2 HD-6 N/A N/A
GEM-P800 NA XP-S B 10 2.2K SLR-835B-2 HD-6 N/A N/A
GEM-P800,-P800E NA XP-S B 10 2.2K OHM SLR-835BH-2 HD-6 N/A N/A
GEM-P800E,P801 NA XP-S B 10 3.9K OHM SLR-835B-2 HD-6 N/A N/A
GEM-P801 NA XP-S B 10 2.2K OHM SLR-835BH-2 HD-6 N/A N/A
GEM-P816, V2,V3 GEM-P816 MDL NO B 10 2.2K OHM SLR-835BH-2 HD-6 N/A N/A
GEM-P816, V2,V3 NA XP-S B 10 2.2K OHM SLR-835B-2 HD-6 N/A N/A
GEM-P9600 NA GEM-PS B 10 2.2K SLR-835B-2 HD-6 N/A N/A
MA3000,SS5500 NA MDL NO B 10 2.2K SLR-835B-2 HD-6 N/A N/A
MA3000/SS5500 NA MDL NO B 10 2.2K OHM SLR-835BH-2 HD-6 N/A N/A
SS-P3200 NA GEM-PS B 10 2.2K OHM SLR-835BH-2 HD-6 N/A N/A
SS-P3200,-P9600 NA GEM-PS B 10 2.2K SLR-835B-2 HD-6 N/A N/A
SS-P9600 NA GEM-PS B 10 2.2K OHM SLR-835BH-2 HD-6 N/A N/A
XP-400, XP-600 NA XP-S B 10 2.2K SLR-835B-2 HD-6 N/A N/A
XP400, XP600 NA XP-S B 10 2.2K OHM SLR-835BH-2 HD-6 N/A N/A
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

NOTIFIER
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
AFM-200 MMX-2, M3-TW A BD 1 3.9K SIH-24F HD-3 HS-2-RB HB-10
AFM-200 MMX-2, M3-TW A BD 25 3.9K SIH-24F HD-3 HS-22D HB-3
AFM-200 MMX-2, M3-TW A BD 25 3.9K SIH-24F HD-3 YBA-M22 HB-3
AFM-200 MMX-2, M3-TW A BD 1 3.9K SLK-24F HD-3 HS-2-RB HB-10
AFM-200 MMX-2, M3-TW A BD 25 3.9K SLK-24F HD-3 HS-22D HB-3
AFM-200 MMX-2, M3-TW A BD 1 3.9K SLK-24FH HD-3 HS-2-RB HB-10
AFM-200 MMX-2, M3-TW A BD 25 3.9K SLK-24FH HD-3 YBA-M22 HB-3
AFP-1010 MMX-2, M3-TW A BD 1 3.9K SIH-24F HD-3 HS-2-RB HB-10
AFP-1010 MMX-2, M3-TW A BD 1 3.9K SIH-24F HD-3 HS-2-RB HB-10
AFP-1010 MMX-2, M3-TW A BD 25 3.9K SIH-24F HD-3 HS-22D HB-3
AFP-1010 MMX-2, M3-TW A BD 25 3.9K SIH-24F HD-3 YBA-M22 HB-3
AFP-1010 MMX-2, M3-TW A BD 1 3.9K SLK-24F HD-3 HS-2-RB HB-10
AFP-1010 MMX-2, M3-TW A BD 25 3.9K SLK-24F HD-3 HS-22D HB-3
AFP-1010 MMX-2, M3-TW A BD 1 3.9K SLK-24FH HD-3 HS-2-RB HB-10
AFP-1010 MMX-2, M3-TW A BD 25 3.9K SLK-24FH HD-3 YBA-M22 HB-3
AFP-200 MMX-2, M3-TW A BD 1 3.9K SIH-24F HD-3 HS-2-RB HB-10
AFP-200 MMX-2, M3-TW A BD 25 3.9K SIH-24F HD-3 HS-22D HB-3
AFP-200 MMX-2, M3-TW A BD 25 3.9K SIH-24F HD-3 YBA-M22 HB-3
AFP-200 MMX-2, M3-TW A BD 1 3.9K SLK-24F HD-3 HS-2-RB HB-10
AFP-200 MMX-2, M3-TW A BD 25 3.9K SLK-24F HD-3 HS-22D HB-3
AFP-200 MMX-2, M3-TW A BD 1 3.9K SLK-24FH HD-3 HS-2-RB HB-10
AFP-200 MMX-2, M3-TW A BD 25 3.9K SLK-24FH HD-3 YBA-M22 HB-3
AM 2020 MMX-2, M3-TW A BD 1 3.9K SIH-24F HD-3 HS-2-RB HB-10
AM 2020 MMX-2, M3-TW A BD 25 3.9K SIH-24F HD-3 HS-22D HB-3
AM 2020 MMX-2, M3-TW A BD 25 3.9K SIH-24F HD-3 YBA-M22 HB-3
AM 2020 MMX-2, M3-TW A BD 1 3.9K SLK-24F HD-3 HS-2-RB HB-10
AM 2020 MMX-2, M3-TW A BD 25 3.9K SLK-24F HD-3 HS-22D HB-3
AM 2020 MMX-2, M3-TW A BD 1 3.9K SLK-24FH HD-3 HS-2-RB HB-10
AM 2020 MMX-2, M3-TW A BD 25 3.9K SLK-24FH HD-3 YBA-M22 HB-3
MMX-2 MMX-2 A BD 25 3.9K SIH-24F HD-3 HS-220 HB-56
MMX-2 MMX-2 A BD 25 3.9K SLK-24F/FH HD-3 HS-220 HB-56
RP-1001 N/A A BD 30 4.7K SIH-24F HD-3 HS-220 HB-56
RP-1001 N/A A BD 30 4.7K SIH-24F HD-3 HSB-224 HB-53
RP-1001 N/A A BD 30 4.7K SLK-24F/FH HD-3 HS-220 HB-56
RP-1001 N/A A BD 30 4.7K SLK-24F/FH HD-3 HS-220 HB-56
RP-1001 N/A A BD 30 4.7K SLK-24F/FH HD-3 HSB-224 HB-53
RP-1002 N/A A BD 30 4.7K SIH-24F HD-3 HS-220 HB-56
RP-1002 N/A A BD 30 4.7K SIH-24F HD-3 HSB-224 HB-53
RP-1002 N/A A BD 30 4.7K SLK-24F/FH HD-3 HS-220 HB-56
RP-1002 N/A A B, D 30 4.7K SLK-24F/FH HD-3 HSB-224 HB-53
S 5000 IZ-4,IZM-8 A B, D 15 4.7K OHM DFE-135,-190 N/A HSC-220L HB-64
S 5000 IZ-4,IZM-8 A B, D 15 4.7K OHM SLR-24H HD-3 HSC-220R HB-72
S 5000 IZ-4,IZM-8 A B, D 15 4.7K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
S 5000 IZ-4,IZM-8 A B, D 20 4.7K OHM SLR-835B-2 HD-6 N/A N/A
S 5000 IZM-8 A B, D 10 4.7K OHM DCD-135,-190 HD-3 HSC-220R HB-72
S 5000 IZM-8 A B, D 10 4.7K OHM DCD-135,-190 HD-3 NS4-220, NS6-220 HB-3
S 5000 IZM-8 A B, D 10 4.7K OHM SIJ-24 HD-3 HSC-220R HB-72
S 5000 IZM-8 A B, D 10 4.7K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
S 5000 IZM-8 A B, D 10 4.7K OHM SLR-24 HD-3 HSC-220R HB-72
S 5000 IZM-8 A B, D 10 4.7K OHM SLR-24 HD-3 NS4-220, NS6-220 HB-3
S 5000 IZM-8, IZE-A A B 30 4.7K OHM SIF-24F HD-3 HS-22D HB-3
S 5000 IZM-8, IZE-A A D 30 N/A SIF-24F HD-3 HS-22D HB-3
S 5000 IZM-8, IZE-A A D 30 N/A SIF-24F HD-3 HS-220D HB-3
S 5000 IZM-8, IZE-A A B 30 4.7K OHM SIF-24F HD-3 HS-220D HB-3
S 5000 IZM-8, IZE-A A D 30 N/A SIF-24F HD-3 YBA-M22 HB-3
S 5000 IZM-8, IZE-A A B 30 4.7K OHM SIF-24F HD-3 YBA-M22 HB-3
S 5000 IZM-8, IZE-A A B 30 4.7K OHM SIF-24F HD-3 YBA-M220 HB-3
S 5000 IZM-8, IZE-A A D 30 N/A SIF-24F HD-3 YBA-M220 HB-3
S 5000 IZM-8, IZE-A A B 30 4.7K OHM SIH-24F HD-3 HS-22D HB-3
S 5000 IZM-8, IZE-A A D 30 N/A SIH-24F HD-3 HS-22D HB-3
S 5000 IZM-8, IZE-A A B 30 4.7K OHM SIH-24F HD-3 HS-220D HB-3
S 5000 IZM-8, IZE-A A D 30 N/A SIH-24F HD-3 HS-220D HB-3
S 5000 IZM-8, IZE-A A B 30 4.7K OHM SIH-24F HD-3 YBA-M22 HB-3
S 5000 IZM-8, IZE-A A D 30 N/A SIH-24F HD-3 YBA-M22 HB-3
S 5000 IZM-8, IZE-A A D 30 N/A SIH-24F HD-3 YBA-M220 HB-3
S 5000 IZM-8, IZE-A A B 30 4.7K OHM SIH-24F HD-3 YBA-M220 HB-3
S 5000 IZM-8, IZE-A A B 30 4.7K OHM SLK-24F HD-3 HS-22D HB-3
S 5000 IZM-8, IZE-A A D 30 N/A SLK-24F HD-3 HS-22D HB-3

Page 1 of 3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

2-Wire Compatibility Listings


PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
S 5000 IZM-8, IZE-A A B 30 4.7K OHM SLK-24F HD-3 HS-220D HB-3
S 5000 IZM-8, IZE-A A D 30 N/A SLK-24F HD-3 HS-220D HB-3
S 5000 IZM-8, IZE-A A D 30 N/A SLK-24F HD-3 YBA-M22 HB-3
S 5000 IZM-8, IZE-A A B 30 4.7K OHM SLK-24F HD-3 YBA-M22 HB-3
S 5000 IZM-8, IZE-A A A D 30 N/A HD-3 YBA-M220 HB-3
S 5000 IZM-8, IZE-A A B 30 4.7K OHM SLK-24F HD-3 YBA-M220 HB-3
S 5000 IZM-8, IZE-A A B 30 4.7K OHM SLK-24FH HD-3 HS-22D HB-3
S 5000 IZM-8, IZE-A A D 30 N/A SLK-24FH HD-3 HS-22D HB-3
S 5000 IZM-8, IZE-A A D 30 N/A SLK-24FH HD-3 HS-220D HB-3
S 5000 IZM-8, IZE-A A B 30 4.7K OHM SIH-24F HD-3 HS-220 HB-56
S 5000 IZM-8, IZE-A A D 30 N/A SLK-24FH HD-3 YBA-M22 HB-3
S 5000 IZM-8, IZE-A A B 30 4.7K OHM SLK-24FH HD-3 YBA-M22 HB-3
S 5000 IZM-8, IZE-A A B 30 4.7K OHM SLK-24FH HD-3 YBA-M220 HB-3
S 5000 IZM-8, IZE-A A D 30 N/A SLK-24FH HD-3 YBA-M220 HB-3
S 5000 MMX-2, M3-TW A BD 1 3.9K SIH-24F HD-3 HS-2-RB HB-10
S 5000 MMX-2, M3-TW A BD 25 3.9K SIH-24F HD-3 HS-22D HB-3
S 5000 MMX-2, M3-TW A BD 25 3.9K SIH-24F HD-3 YBA-M22 HB-3
S 5000 MMX-2, M3-TW A BD 1 3.9K SLK-24F HD-3 HS-2-RB HB-10
S 5000 MMX-2, M3-TW A BD 25 3.9K SLK-24F HD-3 HS-22D HB-3
S 5000 MMX-2, M3-TW A BD 1 3.9K SLK-24FH HD-3 HS-2-RB HB-10
S 5000 MMX-2, M3-TW A BD 25 3.9K SLK-24FH HD-3 YBA-M22 HB-3
SFB-400B N/A A BD 30 4.7K SLK-24F/FH HD-3 HSB-220 HB-56
SFB-400B N/A A BD 30 4.7K SLK-24F/FH HD-3 HSB-224 HB-53
SFB-400 N/A A BD 30 4.7K SIH-24F HD-3 HSB-220 HB-56
SFB-400 N/A A BD 30 4.7K SLK-24F/FH HD-3 HSB-224 HB-53
SFB-400B N/A A B 30 4.7K SIH-24F HD-3 HS-2-RB HB-10
SFB-400B N/A A B 30 4.7K SIH-24F HD-3 HS-22D,YBA-M22 HB-3
SFB-400B N/A A BD 30 4.7K SIH-24F HD-3 HSB-220 HB-56
SFB-400B N/A A BD 30 4.7K SIH-24F HD-3 HSB-224 HB-53
SFB-400B N/A A B 30 4.7K SLK-24F/FH HD-3 HS-2-RB HB-10
SFB-400B N/A A B 30 4.7K SLK-24F/FH HD-3 HS-22D,YBA-M22 HB-3
SLG-2000 N/A A B, D 10 4.7K OHM DCD-135,-190 HD-3 HSC-220R HB-72
SLG-2000 N/A A B, D 10 4.7K OHM DCD-135,-190 HD-3 NS4-220, NS6-220 HB-3
SLG-2000 N/A A BD 30 4.7K SIH-24F HD-3 HSB-220 HB-56
SLG-2000 N/A A BD 30 4.7K SIH-24F HD-3 HSB-224 HB-53
SLG-2000 N/A A B, D 10 4.7K OHM SIJ-24 HD-3 HSC-220R HB-72
SLG-2000 N/A A B, D 10 4.7K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
SLG-2000 N/A A BD 30 4.7K SLK-24F/FH HD-3 HSB-220 HB-56
SLG-2000 N/A A BD 30 4.7K SLK-24F/FH HD-3 HSB-224 HB-53
SLG-2000 N/A A B, D 10 4.7K OHM SLR-24 HD-3 HSC-220R HB-72
SLG-2000 N/A A B, D 10 4.7K OHM SLR-24 HD-3 NS4-220, NS6-220 HB-3
SLG-2000,XPM-8 N/A A B, D 20 4.7K OHM SLR-835B-2 HD-6 N/A N/A
SLG-400 N/A A BD 30 4.7K SIH-24F HD-3 HSB-224 HB-53
SLG-400 N/A A BD 30 4.7K SLK-24F/FH HD-3 HSB-220 HB-56
SLG-404 N/A A BD 30 4.7K SIH-24F HD-3 HSB-220 HB-56
SLG-404 N/A A BD 30 4.7K SIH-24F HD-3 HSB-224 HB-53
SLG-404 N/A A BD 30 4.7K SLK-24F/FH HD-3 HSB-220 HB-56
SLG-404 N/A A BD 30 4.7K SLK-24F/FH HD-3 HSB-224 HB-53
SYSTEM 500 IZ-4 A B 35 4.7K SIH-24F HD-3 HSB-220 HB-56
SYSTEM 500 IZ-4 A B 35 4.7K SIH-24F HD-3 HSB-224 HB-53
SYSTEM 500 IZ-4 A B 35 4.7K SLK-24F/FH HD-3 HSB-220 HB-56
SYSTEM 500 IZ-4 A B 35 4.7K SLK-24F/FH HD-3 HSB-224 HB-53
SYSTEM 500 IZ-4, IZM-8 A B, D 10 4.7K OHM DCD-135,-190 HD-3 HSC-220R HB-72
SYSTEM 500 IZ-4, IZM-8 A B, D 10 4.7K OHM DCD-135,-190 HD-3 NS4-220, NS6-220 HB-3
SYSTEM 500 IZ-4, IZM-8 A B, D 15 4.7K OHM DFE-135,-190 N/A HSC-220L HB-64
SYSTEM 500 IZ-4, IZM-8 A B, D 10 4.7K OHM SIJ-24 HD-3 HSC-220R HB-72
SYSTEM 500 IZ-4, IZM-8 A B, D 10 4.7K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
SYSTEM 500 IZ-4, IZM-8 A B, D 10 4.7K OHM SLR-24 HD-3 HSC-220R HB-72
SYSTEM 500 IZ-4, IZM-8 A B, D 10 4.7K OHM SLR-24 HD-3 NS4-220, NS6-220 HB-3
SYSTEM 500 IZ-4, IZM-8 A B, D 15 4.7K OHM SLR-24H HD-3 HSC-220R HB-72
SYSTEM 500 IZ-4, IZM-8 A B, D 15 4.7K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
SYSTEM 500 IZ-4A A B 35 4.7K SIH-24F HD-3 HSB-220 HB-56
SYSTEM 500 IZ-4A A B 35 4.7K SIH-24F HD-3 HSB-224 HB-53
SYSTEM 500 IZ-4A A B 35 4.7K SLK-24F/FH HD-3 HSB-220 HB-56
SYSTEM 500 IZ-4A A B 35 4.7K SLK-24F/FH HD-3 HSB-224 HB-53

Page 2 of 3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

2-Wire Compatibility Listings


PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
SYSTEM 500 IZ-8 A BD 35 4.7K SIH-24F HD-3 HSB-220 HB-56
SYSTEM 500 IZ-8 A BD 35 4.7K SIH-24F HD-3 HSB-224 HB-53
SYSTEM 500 IZ-8 A BD 35 4.7K SLK-24/FH HD-3 HSB-224 HB-53
SYSTEM 500 IZ-8 A BD 35 4.7K SLK-24F/FH HD-3 HSB-220 HB-56
SYSTEM 500 IZE-A A BD 35 4.7K SIH-24F HD-3 HSB-220 HB-56
SYSTEM 500 IZE-A A BD 35 4.7K SIH-24F HD-3 HSB-224 HB-53
SYSTEM 500 IZE-A A BD 35 4.7K SLK-24F/FH HD-3 HSB-220 HB-56
SYSTEM 500 IZE-A A BD 35 4.7K SLK-24F/FH HD-3 HSB-224 HB-53
SYSTEM 5000 IZE-A IZE-A B, D 35 4.7K SIH-24F HD-3 HSB-220 HB-56
SYSTEM 5000 IZM-8 IZM-8 B 35 4.7K SIH-24F HD-3 HSB-224 HB-53
SYSTEM 5000 IZE-A IZE-A B, D 35 4.7K SIH-24F HD-3 HSB-224 HB-53
SYSTEM 5000 IZE-A IZE-A B, D 35 4.7K SLK-24F/FH HD-3 HSB-220 HB-56
SYSTEM 5000 IZE-A A B, D 35 4.7K SLK-24F/FH HD-3 HSB-224 HB-53
SYSTEM 5000 IZM-8 A B 35 4.7K SIH-24F HD-3 HSB-220 HB-56
SYSTEM 5000 IZM-8 A B 35 4.7K SLK-24F/FH HD-3 HSB-220 HB-56
SYSTEM 5000 IZM-8 A B 35 4.7K SLK-24F/FH HD-3 HSB-224 HB-53
XP TRANSPONDER N/A A B, D 20 2.2K OHM DCD-135,-190 HD-3 HSC-220R HB-72
XP TRANSPONDER N/A A B, D 20 2.2K OHM DCD-135,-190 HD-3 NS4-220, NS6-220 HB-3
XP TRANSPONDER N/A A B, D 20 2.2K OHM SIJ-24 HD-3 HSC-220R HB-72
XP TRANSPONDER N/A A B, D 20 2.2K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
XP TRANSPONDER N/A A B, D 20 2.2K OHM SLR-24 HD-3 HSC-220R HB-72
XP TRANSPONDER N/A A B, D 20 2.2K OHM SLR-24 HD-3 NS4-220, NS6-220 HB-3
XP TRANSPONDER XPM-8 A B, D 60 4.7K SIH-24F HD-3 HSB-220 HB-56
XP TRANSPONDER XPM-8 A B, D 60 4.7K SIH-24F HD-3 HSB-224 HB-53
XP TRANSPONDER XPM-8 A B, D 60 4.7K SLK-24F/FH HD-3 HSB-220 HB-56
XP TRANSPONDER XPM-8 A B, D 60 4.7K SLK-24F/FH HD-3 HSB-224 HB-53

Page 3 of 3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989
PARADOX SECURITY SYSTEMS

2-Wire Compatibility Listings


PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR DETECTOR BASE MODEL BASE ID
ID STYLE DET MODEL ID
SPECTRA 1738 N/A A B 1 N/A SLR-835BH-2 HD-6 N/A N/A
SPECTRA 1738 N/A A B 1 N/A SLR-835BH-2W HD-6 N/A N/A
SPECTRA 1738EX N/A A B 1 N/A SLR-835BH-2 HD-6 N/A N/A
SPECTRA 1738EX N/A A B 1 N/A SLR-835BH-2W HD-6 N/A N/A
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

POTTER ELECTRIC
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
PFC-100 NRC N/A A B, D 25 5.1K SLK-24FH HD3 HS-221D HB4
PFC 100 RC N/A A B, D 1 5.1K SIH-24F HD-3 HS-221D HB-2
PFC 100 RC N/A A B, D 1 5.1K SIH-24F HD-3 HS-221D HB-4
PFC 100 RC N/A A B, D 25 5.1K SLK-24F HD-3 HS-21D HB-2
PFC 100 RC N/A A B, D 25 5.1K SLK-24F HD-3 HS-221 RB HB-13
PFC 100 RC N/A A B, D 25 5.1K SLK-24F HD-3 HS-221D HB-4
PFC 100 RC N/A A B, D 25 5.1K SLK-24FH HD-3 HS-21D HB-2
PFC 100 RC N/A A B, D 25 5.1K SLK-24FH HD-3 HS-221 RB HB-13
PFC-100 RC N/A A B, D 25 5.1K SIH-24F HD-3 HSB-221 HB-54
PFC-100 RC N/A A B, D 25 5.1K SIH-24F HD-3 HSB-221N HB-54
PFC-100 RC N/A A B, D 25 5.1K SIH-24F HD-3 HSB-221R HB-71
PFC-100 RC N/A A B, D 25 5.1K SLK-24F HD-3 HSB-221 HB-54
PFC-100 RC N/A A B, D 25 5.1K SLK-24F HD-3 HSB-221N HB-54
PFC-100 RC N/A A B, D 25 5.1K SLK-24F HD-3 HSB-221R HB-71
PFC-100 RC N/A A B, D 25 5.1K SLK-24FH HD-3 HSB-221 HB-54
PFC-100 RC N/A A B, D 25 5.1K SLK-24FH HD-3 HSB-221N HB-54
PFC-100 RC N/A A B, D 25 5.1K SLK-24FH HD-3 HSC-221R HB-71
PFC-2000 RC N/A A B, D 25 5.1K SIH-24F HD-3 HSB-221 HB-54
PFC-2000 RC N/A A B, D 25 5.1K SIH-24F HD-3 HSB-221N HB-54
PFC-2000 RC N/A A B, D 25 5.1K SIH-24F HD-3 HSC-221R HB-71
PFC-2000 RC N/A A B, D 25 5.1K SLK-24F HD-3 HSB-221 HB-54
PFC-2000 RC N/A A B, D 25 5.1K SLK-24F HD-3 HSB-221N HB-54
PFC-2000 RC N/A A B, D 25 5.1K SLK-24F HD-3 HSC-221R HB-71
PFC-2000 RC N/A A B, D 25 5.1K SLK-24FH HD-3 HSB-221 HB-54
PFC-2000 RC N/A A B, D 25 5.1K SLK-24FH HD-3 HSB-221N HB-54
PFC-2000 RC N/A A B, D 25 5.1K SLK-24FH HD-3 HSC-221R HB-71
PFC-4410 N/A A B, D 25 5.1K SIH-24F HD-3 HSB-221 HB-54
PFC-4410 N/A A B, D 25 5.1K SIH-24F HD-3 HSB-221N HB-54
PFC-4410 N/A A B, D 25 5.1K SLK-24F HD-3 HSB-221 HB-54
PFC-4410 N/A A B, D 25 5.1K SLK-24F HD-3 HSB-221N HB-54
PFC-4410 N/A A B, D 25 5.1K SLK-24FH HD-3 HSB-221 HB-54
PFC-4410 N/A A B, D 25 5.1K SLK-24FH HD-3 HSB-221N HB-54
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

PROTECTOWIRE
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
ACR-1600 SERIES ZM-2200 MDL NO AD 20 ELR-1A SIF-24F HD-3 HS-220D HB-3
ACR-1600 SERIES ZM-2200 MDL NO AD 20 ELR-1A SIF-24F HD-3 HS-220D HB-3
ACR-1600 SERIES ZM-2200 MDL NO AD 20 ELR-1A SLK-24F HD-3 HS-220D HB-3
ACR-1600 SERIES ZM-2200 MDL NO AD 20 ELR-1A SLK-24F HD-3 HS-220D HB-3
ACR-1600 SERIES ZM-2200 MDL NO AD 20 ELR-1A SLK-24FH HD-3 HS-220D HB-3
ACR-1600 SERIES ZM-2200 MDL NO AD 20 ELR-1A SLK-24FH HD-3 HS-220D HB-3
FS2000 ZC-91, ZC-91M MDL NO B, D 30 4.7K OHM DCD-135 HD-3 HSC-220R HB-72
FS2000 ZC-91, ZC-91M MDL NO B, D 30 4.7K OHM DCD-135 HD-3 NS4-220, NS6-220 HB-3
FS2000 ZC-91, ZC-91M MDL NO B, D 30 4.7K OHM DCD-190 HD-3 HSC-220R HB-72
FS2000 ZC-91, ZC-91M MDL NO B, D 30 4.7K OHM DCD-190 HD-3 NS4-220, NS6-220 HB-3
FS2000 ZC-91, ZC-91M MDL NO B, D 30 4.7K OHM DFE-135,-190 N/A HSC-220L HB-64
FS2000 ZC-91, ZC-91M MDL NO B, D 30 4.7K OHM SIJ-24 HD-3 HSC-220R HB-72
FS2000 ZC-91, ZC-91M MDL NO B, D 30 4.7K OHM SIJ-24 HD-3 NS4-220, NS6-220 HB-3
FS2000 ZC-91, ZC-91M MDL NO B, D 30 4.7K OHM SLR-24 HD-3 HSC-220R HB-72
FS2000 ZC-91, ZC-91M MDL NO B, D 30 4.7K OHM SLR-24 HD-3 NS4-220, NS6-220 HB-3
FS2000 ZC-91, ZC-91M MDL NO B, D 30 4.7K OHM SLR-24H HD-3 HSC-220R HB-72
FS2000 ZC-91, ZC-91M MDL NO B, D 30 4.7K SLR-24H HD-3 NS4-220 HB-3
FS2000 ZC-91, ZC-91M MDL NO B, D 30 4.7K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
FS2000 ZC-91, ZC-91M MDL NO B, D 30 4.7K OHM SLR-835B-2 HD-6 N/A N/A
FS2000 SERIES ZC-91 ZC-91 BD 30 4.7K OHM SIH-24F HD-S HS-220D HB-3
FS2000 SERIES ZC-91 ZC-91 BD 30 4.7K OHM SIH-24F HD-S HS-220D HB-3
FS2000 SERIES ZC-91 ZC-91 BD 30 4.7K OHM SLK-24F HD-3 HS-220D HB-3
FS2000 SERIES ZC-91M ZC-91 BD 30 4.7K OHM SLK-24F HD-3 HS-220D HB-3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

RADIONICS
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
D2012,D2112 2 WIRE POINT1 A 40 1.8K OHM SLR-835B-2 HD-6 N/A N/A
D2212 ZONE 1 221201 A 15 2K D262 HD-4 D261A HB-80
D2212, D2412 2 WIRE POINT1 A 40 1.8K OHM SLR-835B-2 HD-6 N/A N/A
D2212B 1 B A 15 15- D262 HD-4 D261A HB-80
D2212B ZONE 1 221201 A 15 2K D262 HD-4 D261A HB-80
D2212BE 1 B A 15 15- D262 HD-4 D261A HB-80
D2412UE 1 B A 15 15- D262 HD-4 D261A HB-80
D2812 1 B A 15 15 D262 HD-4 D261A HB-80
D2812,D2812U 2 WIRE POINT1 A 40 1.8K OHM SLR-835B-2 HD-6 N/A N/A
D4112 N/A B A 20 1.8K OHM SLK-12 HD-4 HSB-12-1 HB-80
D4112 N/A B A 20 1.8K OHM SLK-12 HD-4 HSB-12-1N HB-80
D4112 N/A 1 A 20 D104F SLK-12 HD-4 YBC-RL/12 HB-40
D6112 N/A B A 20 1.8K OHM SLK-12 HD-4 HSB-12-1 HB-80
D6112 N/A B A 20 1.8K OHM SLK-12 HD-4 HSB-12-1N HB-80
D6112 N/A 2 A 20 D104F SLK-12 HD-4 YBC-RL/12 HB-40
D7112 D125B A A 20 1.8K OHM SLK-12 HD-4 HSB-12-1 HB-80
D7112 D125B A A 20 1.8K OHM SLK-12 HD-4 HSB-12-1N HB-80
D7212 D125B A A 20 1.8K OHM SLK-12 HD-4 HSB-12-1 HB-80
D7212 D125B A A 20 1.8K OHM SLK-12 HD-4 HSB-12-1N HB-80
D7212 OWB/125B 24VDC MDL NO A 80 1.8K SIH-24F HD-3 HS224D HB-5
D7212 OWB/D125B 24VDC MDL NO A 80 1.8K SIH-24F HD-3 HS224D HB-5
D7212 OWB/D125B 24VDC MDL NO A 80 1.8K SLK-24F HD-3 HS224D HB-5
D7212,D7412 D125B D125B A 40 1.8K OHM DFE-135,-190 N/A HSC-220L HB-64
D7212,D7412 D125B D125B A 40 1.8K OHM SLR-24H HD-3 HSC-220R HB-72
D7212,D7412 D125B D125B A 40 1.8K OHM SLR-24H HD-3 NS4-100, NS6-100 HB-55
D7212,D7412 D125B D125B A 40 1.8K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
D7212,D7412 D125B D125B A 40 1.8K OHM SLR-24H HD-3 NS4-224, NS6-224 HB-5
D7212,D7412 D125B D125B A 40 1.8K OHM SLR-835B-2 HD-6 N/A N/A
D7212,D7412 ZONE 1 D125B A 40 1.8K OHM DCD-135,DCD-190 HD-3 HSC-220R HB-72
D7212,D7412 ZONE 1 D125B A 40 1.8K OHM DCD-135,DCD-190 HD-3 NS4-220, NS6-220 HB-3
D7212,D7412 ZONE 1 D125B A 40 1.8K OHM SIJ-24,SLR-24 HD-3 HSC-220R HB-72
D7212,D7412 ZONE 1 D125B A 40 1.8K OHM SIJ-24,SLR-24 HD-3 NS4-220, NS6-220 HB-3
D7412 ONBOARD W/125B MDL NO A 80 1.8K SIH-24F HD-3 HS224D HB-5
D7412 ONBOARD W/D125B MDL NO A 80 1.8K SIH-24F HD-3 HS224D HB-5
D7412 ONBOARD W/D125B MDL NO A 15 1.8K SLK-12 HD-4 YBC-AL/12 HB-40
D7412 ONBOARD W/D125B MDL NO A 80 1.8K SLK-24F HD-3 HS224D HB-5
D8112 D8112 W/D125B MDL NO A 20 1.8K OHM SLK-12 HD-4 HSB-12-1 HB-80
D8112 D8112 W/D125B MDL NO A 20 1.8K OHM SLK-12 HD-4 HSB-12-1N HB-80
D8112 N/A 2 TO 8 A 20 D108 SLK-12 HD-4 YBC-RL/12 HB-40
D8112,D9112 ZONE NO D125B A 40 1.8K OHM SLR-835B--2 HD-6 N/A N/A
D9112 D125B A A 20 1.8K OHM SLK-12 HD-4 HSB-12-1 HB-80
D9112 D125B A A 20 1.8K OHM SLK-12 HD-4 HSB-12-1N HB-80
D9112,D9412 ZONE 1 D125B A 40 1.8K OHM DCD-135,DCD-190 HD-3 HSC-220R HB-72
D9112,D9412 ZONE 1 D125B A 40 1.8K OHM DCD-135,DCD-190 HD-3 NS4-220, NS6-220 HB-3
D9112,D9412 ZONE 1 D125B A 40 1.8K OHM SIJ-24,SLR-24 HD-3 HSC-220R HB-72
D9112,D9412 ZONE 1 D125B A 40 1.8K OHM SIJ-24,SLR-24 HD-3 NS4-220, NS6-220 HB-3
D9112B,D9124 D125B D125B A 40 1.8K OHM DFE-135,-190 N/A HSC-220L HB-64
D9112B,D9124 D125B D125B A 40 1.8K OHM SLR-24H HD-3 HSC-220R HB-72
D9112B,D9124 D125B D125B A 40 1.8K OHM SLR-24H HD-3 NS4-100, NS6-100 HB-55
D9112B,D9124 D125B D125B A 40 1.8K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
D9112B,D9124 D125B D125B A 40 1.8K OHM SLR-24H HD-3 NS4-224, NS6-224 HB-5
D9112B,D9124 D125B D125B A 40 1.8K OHM SLR-835B--2 HD-6 N/A N/A
D9412 D125B D125B A 40 1.8K OHM DFE-135,-190 N/A HSC-220L HB-64
D9412 D125B D125B A 40 1.8K OHM SLR-24H HD-3 HSC-220R HB-72
D9412 D125B D125B A 40 1.8K OHM SLR-24H HD-3 NS4-100, NS6-100 HB-55
D9412 D125B D125B A 40 1.8K OHM SLR-24H HD-3 NS4-220, NS6-220 HB-3
D9412 D125B D125B A 40 1.8K OHM SLR-24H HD-3 NS4-224, NS6-224 HB-5
D9412 D125B D125B A 40 1.8K OHM SLR-835B--2 HD-6 N/A N/A
D9412 ONBOARD W/D125B MDL NO A 80 1.8K SIH-24F HD-3 HS224D HB-5
D9412 ONBOARD W/D125B MDL NO A 15 1.8K SLK-12 HD-4 YBC-AL/12 HB-40
D9412 ONBOARD W/D125B MDL NO A 80 1.8K SLK-24F HD-3 HS224D HB-5
D9412 ONBOARD W/D125B MDL NO A 80 1.8K SLK-24F HD-3 HS224D HB-5

1 of 1
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

RAULAND-BORG
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
FA3002 FA3002 LP01 A 50 3.3K SIH-24F HD-3 HS-220D HB-3
FA3002 FA3002 LP02 A 50 3.3K SIH-24F HD-3 HS-220D HB-3
FA3002 FA3002 LP01 A 50 3.3K SIH-24F HD-3 HSB-220 HB-56
FA3002 FA3002 LP02 A 50 3.3K SIH-24F HD-3 HSB-220 HB-56
FA3002 FA3002 LP01 A 50 3.3K SIH-24F HD-3 HSC-220R HB-72
FA3002 FA3002 LP02 A 50 3.3K SIH-24F HD-3 HSC-220R HB-72
FA3002 FA3002 LP01 A 50 3.3K SLK-24F HD-3 HS-220D HB-3
FA3002 FA3002 LP02 A 50 3.3K SLK-24F HD-3 HS-220D HB-3
FA3002 FA3002 LP02 A 50 3.3K SLK-24F HD-3 HSB-220 HB-56
FA3002 FA3002 LP01 A 50 3.3K SLK-24F HD-3 HSB-220 HB-56
FA3002 FA3002 LP02 A 50 3.3K SLK-24F HD-3 HSC-220R HB-72
FA3002 FA3002 LP01 A 50 3.3K SLK-24F HD-3 HSC-220R HB-72
FA3002 FA3002 LP01 A 50 3.3K SLK-24FH HD-3 HS-220D HB-3
FA3002 FA3002 LP02 A 50 3.3K SLK-24FH HD-3 HS-220D HB-3
FA3002 FA3002 LP02 A 50 3.3K SLK-24FH HD-3 HSB-220 HB-56
FA3002 FA3002 LP01 A 50 3.3K SLK-24FH HD-3 HSC-220R HB-72
FA3002 FA3002 LP02 A 50 3.3K SLK-24FH HD-3 HSC-220R HB-72
FA3002 FA3120,FA3125 CZ02 A 1 30K SIH-24F HD-3 HS-220D HB-3
FA3002 FA3120,FA3125 CZ01 A 1 20K SIH-24F HD-3 HS-220D HB-3
FA3002 FA3120,FA3125 CZ02 A 1 30K SIH-24F HD-3 HS-220D HB-3
FA3002 FA3120,FA3125 CZ01 A 1 20K SIH-24F HD-3 HSB-220 HB-56
FA3002 FA3120,FA3125 CZ01 A 1 20K SLK-24F HD-3 HS-220D HB-3
FA3002 FA3120,FA3125 CZ01 A 1 20K SLK-24F HD-3 HS-220D HB-3
FA3002 FA3120,FA3125 CZ01 A 1 20K SLK-24F HD-3 HSB-220 HB-56
FA3002 FA3120,FA3125 CZ02 A 3 30K SLK-24F HD-3 HSB-220 HB-56
FA3002 FA3120,FA3125 CZ01 A 1 20K SLK-24FH HD-3 HS-220D HB-3
FA3002 FA3120,FA3125 CZ02 A 1 30K SLK-24FH HD-3 HS-220D HB-3
FA3002 FA3120,FA3125 CZ02 A 3 30K SLK-24FH HD-3 HSB-220 HB-56
FA3002 FA3120,FA3125 CZ01 A 1 20K SLK-24FH HD-3 HSB-220 HB-56
FA3002 FA3120,FA3125 CZ02 A 3 30K SIH-24F HD-3 HSB-220 HB-56
FA3002 FA3120,FAP3125 CZ02 A 1 30K SLK-24FH HD-3 HS-220D HB-3
FA3002 FA3130,FAP3135 CZ02 A 1 30K SIH-24F HD-3 HS-220D HB-3
FA3002 FA3130,FAP3135 CZ01 A 1 20K SIH-24F HD-3 HS-220D HB-3
FA3002 FA3130,FAP3135 CZ02 A 3 30K SIH-24F HD-3 HSB-220 HB-56
FA3002 FA3130,FAP3135 CZ01 A 1 20K SIH-24F HD-3 HSB-220 HB-56
FA3002 FA3130,FAP3135 CZ02 A 1 30K SLK-24F HD-3 HS-220D HB-3
FA3002 FA3130,FAP3135 CZ01 A 1 20K SLK-24F HD-3 HS-220D HB-3
FA3002 FA3130,FAP3135 CZ01 A 1 20K SLK-24F HD-3 HSB-220 HB-56
FA3002 FA3130,FAP3135 CZ02 A 3 30K SLK-24F HD-3 HSB-220 HB-56
FA3002 FA3130,FAP3135 CZ02 A 1 30K SLK-24FH HD-3 HS-220D HB-3
FA3002 FA3130,FAP3135 CZ02 A 3 30K SLK-24FH HD-3 HSB-220 HB-56
FA3002 FA3130,FAP3135 CZ01 A 1 20K SLK-24FH HD-3 HSB-220 HB-56
FIRE PLEX FA3001 LPO1 2 A 50 1344 SIH-24F HD-3 HS-220D HB-3
FIRE PLEX FA3001 LPO1 2 A 50 1344 SLK-24F HD-3 HS-220D HB-3
FIRE PLEX FA3130,FAP3135 CZ01 A 1 1346 SLK-24F HD-3 HS-220D HB-3
FIRE PLEX FA3130,FAP3135 CZ01 A 1 1346 SIH-24F HD-3 HS-220D HB-3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

SECURTON
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
MR-2600 MR-2600 MDL NO B 29 MRD-2904 SIH-24F HD-2 HS-221D HB-4
MR-2600 MR-2600 MDL NO B 29 MRD-2904 SIH-24F HD-2 YBA-M221 HB-4
MR-2600 MR-2600 MDL NO B 25 MRD-2904 SIH-24F HD-3 HS-221D HB-4
MR-2600 MR-2600 MDL NO B 25 MRD-2904 SIH-24F HD-3 YBA-M221 HB-4
MR-2600 MR-2600 MDL NO B 22 MRD-2904 SLK-24F HD-3 HS-221D HB-4
MR-2600 MR-2600 MDL NO B 22 MRD-2904 SLK-24F HD-3 YBA-M221 HB-4
MR-2600 MR-2600 MDL NO B 22 MRD-2904 SLK-24FH HD-3 HS-221D HB-4
MR-2600 MR-2600 MDL NO B 22 MRD-2904 SLK-24FH HD-3 YBA-M221 HB-4
MR-2900 MR-2928 A B, C 34 MRD-2904 SIH-24F HD-2 HS-221D HB-4
MR-2900 MR-2928 A B, C 34 MRD-2904 SIH-24F HD-2 YBA-M221 HB-4
MR-2900 MR-2928 A B, C 26 MRD-2904 SIH-24F HD-3 HS-221D HB-4
MR-2900 MR-2928 A B, C 26 MRD-2904 SIH-24F HD-3 YBA-M221 HB-4
MR-2900 MR-2928 A B, C 24 MRD-2904 SLK-24F HD-3 HS-221D HB-4
MR-2900 MR-2928 A B, C 24 MRD-2904 SLK-24F HD-3 HS-221D HB-4
MR-2900 MR-2928 A B, C 24 MRD-2904 SLK-24F HD-3 YBA-M221 HB-4
MR-2900 MR-2928 A B, C 24 MRD-2904 SLK-24FH HD-3 YBA-M221 HB-4
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

SILENT KNIGHT
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
5204 N/A 24C B 30 7628 DFE-135,-190 N/A HSC-220L HB-64
5204 N/A 24C B 30 7628 SLR-24H HD-3 HSC-220R HB-72
5204 N/A 24C B 30 7628 SLR-24H HD-3 NS4-220, NS6-220 HB-3
5204 12 VOLT N/A N/A A 20 7628 SLK-24F HD-3 HS-224D HB-5
5204 12 VOLT N/A N/A A 20 7628 SLK-24FH HD-3 HS-224D HB-5
5207 5210 24A B 30 7628 DCD-135 HD-3 HSC-220R HB-72
5207 5210 24A B 30 7628 DCD-135 HD-3 NS4-220, NS6-220 HB-3
5207 5210 24A B 30 7628 DCD-190 HD-3 HSC-220R HB-72
5207 5210 24A B 30 7628 DCD-190 HD-3 NS4-220, NS6-220 HB-3
5207 5210 24A B 30 7628 DFE-135,-190 N/A HSC-220L HB-64
5207 5210 24A B 30 7628 SIJ-24 HD-3 HSC-220R HB-72
5207 5210 24A B 30 7628 SIJ-24 HD-3 NS4-220, NS6-220 HB-3
5207 5210 24A B 30 7628 SLR-24 HD-3 HSC-220R HB-72
5207 5210 24A B 30 7628 SLR-24 HD-3 NS4-220, NS6-220 HB-3
5207 5210 24A B 30 7628 SLR-24H HD-3 HSC-220R HB-72
5207 5210 24A B 30 7628 SLR-24H HD-3 NS4-220, NS6-220 HB-3
5207 5210 24A B 30 7628 SLR-835 HD-3 NS4-100, NS6-100 HB-55
5207 5210 24A B 30 7628 SLR-835 HD-3 NS4-220, NS6-220 HB-3
5207 5210 24A B 30 7628 SLR-835B-2 HD-6 N/A N/A
5207 5210 24A B 10 7628 SIH-24F HD-3 HS-224D/HSB-224 HB-5
5207 5210 24A B 10 7628 SLK-24F HD-3 HS-224D/HSB-224 HB-5
5207 N/A 24D B 30 7628 DCD-135 HD-3 HSC-220R HB-72
5207 N/A 24D B 30 7628 DCD-135 HD-3 NS4-220, NS6-220 HB-3
5207 N/A 24D B 30 7628 DCD-190 HD-3 HSC-220R HB-72
5207 N/A 24D B 30 7628 DCD-190 HD-3 NS4-220, NS6-220 HB-3
5207 N/A 24D B 30 7628 DFE-135,-190 N/A HSC-220L HB-64
5207 N/A 24D B 30 7628 SIJ-24 HD-3 HSC-220R HB-72
5207 N/A 24D B 30 7628 SIJ-24 HD-3 NS4-220, NS6-220 HB-3
5207 N/A 24B A 40 7628 4.7 SLK-24F HD-3 HS-224D HB-5
5207 N/A 24A B 20 7628 SLK-24F HD-3 HS-224D HB-5
5207 N/A 24B A 40 7628 4.7 SLK-24FH HD-5 HS-224C HB-5
5207 N/A 24B A 40 7628 4.7 SLK-24FH HD-5 HS-224C HB-5
5207 N/A 24A B 20 7628 SLK-24FH HD-3 HS-224D HB-5
5207 N/A 24D B 30 7628 SLR-24 HD-3 HSC-220R HB-72
5207 N/A 24D B 30 7628 SLR-24 HD-3 NS4-220, NS6-220 HB-3
5207 N/A 24D B 30 7628 SLR-24H HD-3 HSC-220R HB-72
5207 N/A 24D B 30 7628 SLR-24H HD-3 NS4-220, NS6-220 HB-3
5207 N/A 24D B 25 7628 SIH-24F HD-3 HS-224D/HSB-224 HB-5
5207 N/A 24D B 25 7628 SLK-24F HD-3 HS-224D/HSB-224 HB-5
5820, 5828XL N/A 24H B, D 12 7628 DCD-135,-190 HD-3 HSC-220L HB-64
5820, 5828XL N/A 24H B, D 12 7628 DCD-135,-190 HD-3 HSC-220R HB-72
5820, 5828XL N/A 24H B, D 12 7628 DCD-135,-190 HD-3 NS4-220, NS6-220 HB-3
5820, 5828XL N/A 24H B, D 12 7628 DFE-135,-190 N/A HSC-220L HB-64
5820, 5828XL N/A 24H B, D 12 7628 SIJ-24 HD-3 HSC-220R HB-72
5820, 5828XL N/A 24H B, D 12 7628 SIJ-24 HD-3 NS4-220, NS6-220 HB-3
5820, 5828XL N/A 24H B, D 12 7628 SLR-24H, -24V HD-3 HSC-220R HB-72
5820, 5828XL N/A 24H B, D 12 7628 SLR-24H, -24V HD-3 NS4-100, NS6-100 HB-55
5820, 5828XL N/A 24H B, D 12 7628 SLR-24H, -24V HD-3 NS4-220, NS6-220 HB-3
5820, 5828XL N/A 24H B, D 12 7628 SLR-835 HD-3 NS4-100, NS6-100 HB-55
5820, 5828XL N/A 24H B, D 12 7628 SLR-835 HD-3 NS4-220, NS6-220 HB-3
5820, 5828XL N/A 24H B, D 12 7628 SLR-835B-2 HD-6 N/A N/A
7181 N/A B B 30 7628 DCD-135 HD-3 HSC-220R HB-72
7181 N/A B B 30 7628 DCD-135 HD-3 NS4-220, NS6-220 HB-3
7181 N/A B B 30 7628 DCD-190 HD-3 HSC-220R HB-72
7181 N/A B B 30 7628 DCD-190 HD-3 NS4-220, NS6-220 HB-3
7181 N/A B B 30 7628 DFE-135,-190 N/A HSC-220L HB-64
7181 N/A B B 30 7628 SIJ-24 HD-3 HSC-220R HB-72
7181 N/A B B 30 7628 SIJ-24 HD-3 NS4-220, NS6-220 HB-3
7181 N/A B B 18 7628 SLK-12 HD-4 HSB-12-1 HB-80
7181 N/A B B 18 7628 SLK-12 HD-4 HSB-12-1 HB-80
7181 N/A B B 18 7628 SLK-12 HD-4 HSB-12-1N HB-80
7181 N/A B B 18 7628 SLK-12 HD-4 HSB-12-1N HB-80
7181 N/A B B 30 7628 SLR-24 HD-3 HSC-220R HB-72
7181 N/A B B 30 7628 SLR-24 HD-3 NS4-220, NS6-220 HB-3
7181 N/A B B 30 7628 SLR-24H HD-3 HSC-220R HB-72
7181 N/A B B 30 7628 SLR-24H HD-3 NS4-220, NS6-220 HB-3
7181 N/A 24B B, D 20 7628 SLR-835B-2 HD-6 N/A N/A
SD500-SDM NA 241 B/D 25 7628 SIH-24F HD-3 YBA-M224 HB-5

Page 1 of 3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

2-Wire Compatibility Listings


PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
SD500-SDM NA 241 B, D 25 7628 SLK-24F HD-3 HS-224D HB-5
SD500-SDM NA 241 B, D 25 7628 SLK-24FH HD-3 HS-224D HB-5
SD500-SDM NA 241 B/D 25 7628 SLR-835B-2 HD-6 N/A N/A
SK-5208,FC-5208 SK-5217,FC-5217 24J B, D 15 7628 SLR-835H HD-5 HSC-220R HB-72
SK-5208,FC-5208 SK-5217,FC-5217 24J B, D 15 7628 SLR-835H HD-5 NS4-220,NS6-220 HB-3
SK-6324 N/A 24F B 15 N/A DCD-135,-190 HD-3 HSC-220L HB-64
SK-6324 N/A 24F B 15 N/A DCD-135,-190 HD-3 HSC-220R HB-72
SK-6324 N/A 24F B 15 N/A DCD-135,-190 HD-3 NS4-220, NS6-220 HB-3
SK-6324 N/A 24F B 15 N/A DFE-135,-190 HD-3 HSC-220L HB-64
SK-6324 N/A 24F B 15 N/A SIJ-24 HD-3 HSC-220R HB-72
SK-6324 N/A 24F B 15 N/A SIJ-24 HD-3 NS4-220, NS6-220 HB-3
SK-6324 N/A 24F B 15 N/A SLR-24H, -24V HD-3 HSC-220R HB-72
SK-6324 N/A 24F B 15 N/A SLR-24H, -24V HD-3 NS4-100, NS6-100 HB-55
SK-6324 N/A 24F B 15 N/A SLR-24H, -24V HD-3 NS4-220, NS6-220 HB-3
SK-6324 N/A 24F B 15 N/A SLR-835 HD-3 NS4-100, NS6-100 HB-55
SK-6324 N/A 24F B 15 N/A SLR-835 HD-3 NS4-220, NS6-220 HB-3
SK-6324 N/A 24F B 15 N/A SLR-835B-2 HD-6 N/A N/A
SK6324 N/A 24F D 10 7628 SLR-835H HD-5 HSC-220R HB-72
SK6324 N/A 24F D 10 7628 SLR-835H HD-5 NS4-220,NS6-220 HB-3
SK-6324 N/A 24F B 1 N/A SLR-835,-835W HD-5 SBC-2,SBC-2W HB-85
SK-6324 N/A 24F B 1 N/A SLR-835,-835W HD-5 SBC-2R,SBC-2RW HB-85
SK-6324 N/A 24F B 1 N/A SLR-835H,-835HW HD-5 SBC-2R,SBC-2RW HB-85
SK-6324 N/A 24F B 1 N/A SLR-835H,-835HW HD-5 SBC-2,SBC-2W HB-85
SK-6324 N/A 24F B 1 N/A SIJ-24 HD-3 SBC-2 HB-85
SK-6324 N/A 24F B 1 N/A SLR-24V HD-3 SBC-2 HB-85
SK-6324 N/A 24F B 1 N/A SLR-24V HD-3 SBC-2R HB-85
SK-2224 NA 24F B 30 7628 SIH-24F HD-3 HS-224D/HSB-224 HB-5
SK-2224 NA 24F B 30 7628 SLK-24F, -24FH HD-3 HS-224D HB-5
SK-2224, SK4224 N/A 24FF D 15 N/A DCD-135,-190 HD-3 HSC-220L HB-64
SK-2224, SK4224 N/A 24FF D 15 N/A DCD-135,-190 HD-3 NS4-220, NS6-220 HB-3
SK-2224, SK4224 N/A 24FF D 15 N/A DFE-135,-190 HD-3 HSC-220L HB-64
SK-2224, SK4224 N/A 24FF D 15 N/A SIJ-24 HD-3 HSC-220R HB-72
SK-2224, SK4224 N/A 24FF D 15 N/A SIJ-24 HD-3 NS4-220, NS6-220 HB-3
SK-2224, SK4224 N/A 24FF D 15 N/A SLR-24H, -24V HD-3 HSC-220R HB-72
SK-2224, SK4224 N/A 24FF D 15 N/A SLR-24H, -24V HD-3 NS4-100, NS6-100 HB-55
SK-2224, SK4224 N/A 24FF D 15 N/A SLR-24H, -24V HD-3 NS4-220, NS6-220 HB-3
SK-2224, SK4224 N/A 24FF D 15 N/A SLR-835 HD-3 NS4-100, NS6-100 HB-55
SK-2224, SK4224 N/A 24FF D 15 N/A SLR-835 HD-3 NS4-220, NS6-220 HB-3
SK-2224, SK4224 N/A 24FF D 15 N/A SLR-835B-2 HD-6 N/A N/A
SK2224, SK4224 N/A 24F B 10 7628 SLR-835BH-2 HD-6 N/A N/A
SK2224, SK4224 N/A 24F B 10 7628 SLR-835H HD-5 HSC-220R HB-72
SK2224, SK4224 N/A 24F B 10 7628 SLR-835H HD-5 NS4-100,NS6-100 HB-55
SK2224, SK4224 N/A 24F B 10 7628 SLR-835H HD-5 NS4-220 HB-3
SK-2224, SK4224 N/A 24F B 30 7628 DCD-135 HD-3 HSC-220R HB-72
SK-2224, SK4224 N/A 24F B 30 7628 DCD-135 HD-3 NS4-220, NS6-220 HB-3
SK-2224, SK4224 N/A 24F B 30 7628 DCD-190 HD-3 HSC-220R HB-72
SK-2224, SK4224 N/A 24F B 30 7628 DCD-190 HD-3 NS4-220, NS6-220 HB-3
SK-2224, SK4224 N/A 24F B 30 N/A DFE-135,-190 N/A HSC-220L HB-64
SK-2224, SK4224 N/A 24F B 30 N/A SIJ-24 HD-3 HSC-220R HB-72
SK-2224, SK4224 N/A 24F B 30 N/A SIJ-24 HD-3 NS4-220, NS6-220 HB-3
SK-2224, SK4224 N/A 24F B 30 7628 SLR-24 HD-3 HSC-220R HB-72
SK-2224, SK4224 N/A 24F B 30 7628 SLR-24 HD-3 NS4-220, NS6-220 HB-3
SK-2224, SK4224 N/A 24F B 30 N/A SLR-24H HD-3 HSC-220R HB-72
SK-2224, SK4224 N/A 24F B 30 N/A SLR-24H HD-3 NS4-220, NS6-220 HB-3
SK-2224, SK4224 N/A 24F B 1 7628 SLR-835,-835W HD-5 SBC-2,SBC-2W HB-85
SK-2224, SK4224 N/A 24F B 1 7628 SLR-835,-835W HD-5 SBC-2R,SBC-2RW HB-85
SK-2224, SK4224 N/A 24F B 1 7628 SLR-835H,-835HW HD-5 SBC-2R,SBC-2RW HB-85
SK-2224, SK4224 N/A 24F B 1 7628 SLR-835H,-835HW HD-5 SBC-2,SBC-2W HB-85
SK-2224, SK4224 N/A 24F B 1 7628 SIJ-24 HD-3 SBC-2 HB-85
SK-2224, SK4224 N/A 24F B 1 7628 SLR-24V HD-3 SBC-2 HB-85
SK-2224, SK4224 N/A 24F B 1 7628 SLR-24V HD-3 SBC-2R HB-85
SK4224 N/A 24FF D 10 7628 SLR-835H HD-5 HSC-220R HB-72
SK4224 N/A 24FF D 10 7628 SLR-835H HD-5 NS4-100,NS6-100 HB-55
SK4224 N/A 24FF D 10 7628 SLR-835H HD-5 NS4-220,NS6-220 HB-3
SK4224 N/A 24FF D 30 N/A SLR-835B-2 HD-6 N/A N/A
SK5208 N/A 24J B, D 15 7628 DCD-135,-190 HD-3 HSC-220L HB-64
SK5208 N/A 24J B, D 15 7628 DCD-135,-190 HD-3 HSC-220R HB-72
SK5208 N/A 24J B, D 15 7628 DCD-135,-190 HD-3 NS4-220, NS6-220 HB-3

Page 2 of 3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

2-Wire Compatibility Listings


PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
SK5208 N/A 24J B, D 15 7628 DFE-135,-190 HD-3 HSC-220L HB-64
SK5208 N/A 24J B, D 15 7628 SIJ-24 HD-3 HSC-220R HB-72
SK5208 N/A 24J B, D 15 7628 SIJ-24 HD-3 NS4-220, NS6-220 HB-3
SK5208 N/A 24J B, D 15 7628 SLR-24H, -24V HD-3 HSC-220R HB-72
SK5208 N/A 24J B, D 15 7628 SLR-24H, -24V HD-3 NS4-100, NS6-100 HB-55
SK5208 N/A 24J B, D 15 7628 SLR-24H, -24V HD-3 NS4-220, NS6-220 HB-3
SK5208 N/A 24J B, D 15 7628 SLR-835 HD-3 NS4-100, NS6-100 HB-55
SK5208 N/A 24J B, D 15 7628 SLR-835 HD-3 NS4-220, NS6-220 HB-3
SK5208 N/A 24J B, D 15 7628 SLR-835B-2 HD-6 N/A N/A
SK5208/FC-5208 N/A 24J B, D 1 7628 SLR-835,-835W HD-5 SBC-2,SBC-2W HB-85
SK5208/FC-5208 N/A 24J B, D 1 7628 SLR-835,-835W HD-5 SBC-2R,SBC-2RW HB-85
SK5208/FC-5208 N/A 24J B, D 1 7628 SLR-835H,-835HW HD-5 SBC-2R,SBC-2RW HB-85
SK5208/FC-5208 N/A 24J B, D 1 7628 SLR-835H,-835HW HD-5 SBC-2,SBC-2W HB-85
SK5208/FC-5208 N/A 24J B, D 1 7628 SIJ-24 HD-3 SBC-2 HB-85
SK5208/FC-5208 N/A 24J B, D 1 7628 SLR-24V HD-3 SBC-2 HB-85
SK5208/FC-5208 N/A 24J B, D 1 7628 SLR-24V HD-3 SBC-2R HB-85
C6000 N/A 24E B 30 7628 DCD-135 HD-3 HSC-220R HB-72
C6000 N/A 24E B 30 7628 DCD-135 HD-3 HSC-221R HB-71
C6000 N/A 24E B 30 7628 DCD-135 HD-3 NS4-220, NS6-220 HB-3
C6000 N/A 24E B 30 7628 DCD-135 HD-3 NS4-221, NS6-221 HB-4
C6000 N/A 24E B 30 7628 DCD-135 HD-3 NS4-224, NS6-224 HB-5
C6000 N/A 24E B 30 7628 DCD-135 HD-3 NS6-11, NS4-100 HB-55
C6000 N/A 24E B 30 7628 DCD-190 HD-3 HSC-220R HB-72
C6000 N/A 24E B 30 7628 DCD-190 HD-3 HSC-221R HB-71
C6000 N/A 24E B 30 7628 DCD-190 HD-3 NS4-220, NS6-220 HB-3
C6000 N/A 24E B 30 7628 DCD-190 HD-3 NS4-221, NS6-221 HB-4
C6000 N/A 24E B 30 7628 DCD-190 HD-3 NS4-224, NS6-224 HB-5
C6000 N/A 24E B 30 7628 DCD-190 HD-3 NS6-11, NS4-100 HB-55
C6000 N/A 24E B 30 7628 SIJ-24 HD-3 HSC-220R HB-72
C6000 N/A 24E B 30 7628 SIJ-24 HD-3 HSC-221R HB-71
C6000 N/A 24E B 30 7628 SIJ-24 HD-3 NS4-220, NS6-220 HB-3
C6000 N/A 24E B 30 7628 SIJ-24 HD-3 NS4-221, NS6-221 HB-4
C6000 N/A 24E B 30 7628 SIJ-24 HD-3 NS4-224, NS6-224 HB-5
C6000 N/A 24E B 30 7628 SIJ-24 HD-3 NS6-11, NS4-100 HB-55
C6000 N/A 24E B 30 7628 SLR-24 HD-3 HSC-220R HB-72
C6000 N/A 24E B 30 7628 SLR-24 HD-3 HSC-221R HB-71
C6000 N/A 24E B 30 7628 SLR-24 HD-3 NS4-220, NS6-220 HB-3
C6000 N/A 24E B 30 7628 SLR-24 HD-3 NS4-221, NS6-221 HB-4
C6000 N/A 24E B 30 7628 SLR-24 HD-3 NS4-224, NS6-224 HB-5
C6000 N/A 24E B 30 7628 SLR-24 HD-3 NS6-11, NS4-100 HB-55

UPDATED 9/11/03

Page 3 of 3
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

SIMPLEX
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
SERIES 4010 4090-9101&-9106 MDL NO B, D 20 3.3K SIH-24F HD-3 HS-221 HB-4
SERIES 4010 4090-9101&-9106 MDL NO B, D 20 3.3K SIH-24F HD-3 HSB-221S HB-54
SERIES 4010 4090-9101&-9106 MDL NO B, D 20 3.3K SLK-24FB HD-3 HS-221 HB-4
SERIES 4010 4090-9101&-9106 MDL NO B, D 20 3.3K SLK-24FH HD-3 HS-221 HB-4
SERIES 4010 4090-9101&-9106 MDL NO B, D 20 3.3K SLK-24FH HD-3 HSB-221S HB-54
SERIES 4010 4090-9101&-9106 MDL NO B, D 20 3.3K SLK-24KB HD-3 HS-221 HB-4
SERIES 4010 4090-9101&-9106 MDL NO B, D 20 3.3K SLK-24KB HD-3 HSB-221S HB-54
SERIES 4010 4090-9101&-9106 MDL NO B, D 20 40909101 SLK-24FB HD-3 HSB-221S HB-54
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

SPECTRONICS 2-Wire Compatibility Listings

PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
324 320/LC/OS-24 MDL NO B 15 15 K SIH-24F HD-2 HS-200 D HD-20
324 320/LC/OS-24 MDL NO B 11 15 K SIH-24F HD-3 HS-200 D HD-20
324 320/LC/OS-24 MDL NO B 13 15 K SLK-24F HD-3 HS-200 D HD-20
324 320/LC/OS-24 MDL NO B 13 15 K SLK-24FG HD-3 HS-200 D HD-20
624/641 MX8/WIB MDL NO B 13 15K SLK-24F HD-3 HS-200 D HD-20
624/MX ADS MDL NO B 15 15 K SIH-24F HD-2 HS-200 D HD-20
624/MX ADS MDL NO B 11 15 K SIH-24F HD-3 HS-200 D HD-20
624/MX ADS MDL NO B 13 15 K SLK-24F HD-3 HS-200 D HD-20
624/MX ADS MDL NO B 13 15 K SLK-24FH HD-3 HS-200 D HD-20
624/MX ADS-H MDL NO B 50 4.7K SIH-24F HD-2 HS-200 D HD-20
624/MX ADS-H MDL NO B 39 4.7K SIH-24F HD-3 HS-200 D HD-20
624/MX ADS-H MDL NO B 44 4.7K SLK-24F HD-3 HS-200 D HD-20
624/MX MX/OSH MDL NO B 50 4.7K SIF-24F HD-2 HS-200 D HD-20
624/MX MX/OSH MDL NO B 40 4.7K OHM SIF-24F HD-2 HS-22D HB-3
624/MX MX/OSH MDL NO B 39 4.7K SIH-24F HD-3 HS-200 D HD-20
624/MX MX/OSH MDL NO B 44 4.7K SLK-24F HD-3 HS-200 D HD-20
624/MX MX/OSH MDL NO B 40 4.7K OHM SLK-24F HD-3 HS-22D HB-3
624/MX MX/OSH MDL NO B 44 4.7K SLK-24FH HD-3 HS-200 D HD-20
624/MX MX/OSH MDL NO B 39 4.7K SLK-24FH HD-3 HS-200 D HD-20
624/MX MX/OSH MDL NO B 40 4.7K OHM SLK-24FH HD-3 HS-22D HB-3
624/MX MX/I0-1O MDL NO B, D 22 15 k SLK-24FH HD-3 HS-200 D HD-20
624/MX MX/I01O-H MDL NO B 39 4.7K SIH-24F HD-3 HS-200 D HD-20
624/MX MX/I01O MDL NO B 39 4.7K SIF-24F HD-2 HS-200 D HD-20
624/MX MX/I01O MDL NO B 50 4.7K SIF-24F HD-2 HS-200 D HD-20
624/MX MX/I01O MDL NO B, D 19 15 K SIH-24F HD-3 HS-200 D HD-20
624/MX MX/I01O MDL NO B, D 22 15 K SLK-24F HD-3 HS-200 D HD-20
624/MX MX/I01O-H MDL NO B 44 4.7K SLK-24F HD-3 HS-200 D HD-20
624/MX MX/I01O-H MDL NO B 44 4.7K SLK-24FH HD-3 HS-200 D HD-20
624/MX MX/I0-1O-H MDL NO B 50 4.7K OHM SIH-24F HD-2 HS-22D HB-3
624/MX MX/I0-1O-H MDL NO B 40 4.7K OHM SLK-24F HD-3 HS-22D HB-3
624/MX MX/I0-1O-H MDL NO B 40 4.7K OHM SLK-24FH HD-3 HS-22D HB-3
624/MX MX/OSRP MDL NO B 15 15 K SIF-24F HD-2 HS-200 D HD-20
624/MX MX/OSRP MDL NO B 11 15 K SIH-24F HD-3 HS-200 D HD-20
624/MX MX/OSRP MDL NO B 13 15 K SLK-24F HD-3 HS-200 D HD-20
624/MX MX/OSRP MDL NO B 13 15 K SLK-24FH HD-3 HS-200 D HD-20
640 MX8/WIBH MDL NO B 50 4.7K OHM SIF-24F HD-2 HS-22D HB-3
640 MX8/WIBH MDL NO B 40 4.7K OHM SLK-24F HD-3 HS-22D HB-3
640 MX8/WIBH MDL NO B 40 4.7K OHM SLK-24FH HD-3 HS-22D HB-3
640 S2W MDL NO B 50 4.7K OHM SIF-24F HD-2 HS-22D HB-3
640 S2W MDL NO B 40 4.7K OHM SLK-24F HD-3 HS-22D HB-3
640 S2W MDL NO B 40 4.7K OHM SLK-24FH HD-3 HS-22D HB-3
640 S2WA MDL NO D 50 N/A SIF-24F HD-2 HS-22D HB-3
640 S2WA MDL NO D 40 N/A SLK-24F HD-3 HS-22D HB-3
640 S2WA MDL NO D 40 N/A SLK-24FH HD-3 HS-22D HB-3
640/641 MX8/WIB MDL NO B 15 15 K SIF-24F HD-2 HS-200 D HD-20
640/641 MX8/WIB MDL NO B 50 4.7K SIF-24F HD-2 HS-200 D HD-20
640/641 MX8/WIB MDL NO B 11 15 K SIH-24F HD-3 HS-200 D HD-20
640/641 MX8/WIB MDL NO B 39 4.7K SIH-24F HD-3 HS-200 D HD-20
640/641 MX8/WIB MDL NO B 44 4.7K SLK-24F HD-3 HS-200 D HD-20
640/641 MX8/WIB MDL NO B 44 4.7K SLK-24FH HD-3 HS-200 D HD-20
640/641 MX8/WIB MDL NO B 13 15 K SLK-24FH HD-3 HS-200 D HD-20
640/641 S2/OSS MDL NO B 15 15 K SIF-24F HD-2 HS-200 D HD-20
640/641 S2/OSS MDL NO B 11 15 K SIH-24F HD-3 HS-200 D HD-20
640/641 S2/OSS MDL NO B 13 15 K SLK-24F HD-3 HS-200 D HD-20
640/641 S21/OSS MDL NO B 13 15 K SLK-24FH HD-3 HS-200 D HD-20
640/641 S2A MDL NO D 15 15 K SIF-24F HD-3 HS-200 D HD-20
640/641 S2A MDL NO D 11 15 K SIH-24F HD-3 HS-200 D HD-20
640/641 S2A MDL NO D 13 15 K SLK-24F HD-3 HS-200 D HD-20
640/641 S2A MDL NO D 13 15 K SLK-24FH HD-3 HS-200 D HD-20
640/641 S2W MDL NO B 50 4.7K SIF-24F HD-2 HS-200 D HD-20
640/641 S2W MDL NO B 44 4.7K SLK-24F HD-3 HS-200 D HD-20
640/641 S2W MDL NO B 44 4.7K SLK-24FH HD-3 HS-200 D HD-20
640/641 S2WA MDL NO D 50 4.7K SIF-24F HD-2 HS-200 D HD-20
640/641 S2WA MDL NO D 39 4.7K SIH-24F HD-3 HS-200 D HD-20
640/641 S2WA MDL NO D 44 4.7K SLK-24F HD-3 HS-200 D HD-20
640/641 S2WA MDL NO D 44 4.7K SLK-24FH HD-3 HS-200 D HD-20
641 MX8/WIBH MDL NO B 50 4.7K OHM SIF-24F HD-2 HS-22D HB-3
641 MX8/WIBH MDL NO B 40 4.7K OHM SLK-24F HD-3 HS-22D HB-3

Page 1 of 2
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

2-Wire Compatibility Listings


PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
641 MX8/WIBH MDL NO B 40 4.7K OHM SLK-24FH HD-3 HS-22D HB-3
641 S2W MDL NO B 50 4.7K OHM SIF-24F HD-2 HS-22D HB-3
641 S2W MDL NO B 40 4.7K OHM SLK-24F HD-3 HS-22D HB-3
641 S2W MDL NO B 40 4.7K OHM SLK-24FH HD-3 HS-22D HB-3
641 S2WA MDL NO D 50 N/A SIF-24F HD-2 HS-22D HB-3
641 S2WA MDL NO D 40 N/A SLK-24F HD-3 HS-22D HB-3
641 S2WA MDL NO D 40 N/A SLK-24FH HD-3 HS-22D HB-3
FASA FASA FASA B 50 4.7K OHM SIF-24F HD-2 HB-22D HB-3
FASA FASA FASA D 50 N/A SIF-24F HD-2 HB-22D HB-3
FASA FASA MDL NO BD 50 4.7K SIF-24F HD-2 HS-200 D HD-20
FASA FASA MDL NO BD 39 4.7K SIF-24F HD-3 HS-200 D HD-20
FASA FASA FASA D 40 N/A SLK-24F HD-3 HB-22D HB-3
FASA FASA FASA B 40 4.7K OHM SLK-24F HD-3 HB-22D HB-3
FASA FASA MDL NO B 44 4.7K SLK-24F HD-3 HS-200 D HD-20
FASA FASA FASA B 40 4.7K OHM SLK-24FH HD-3 HB-22D HB-3
FASA FASA FASA D 40 N/A SLK-24FH HD-3 HB-22D HB-3
FASA FASA MDL NO BD 44 4.7K SLK-24FH HD-3 HS-200 D HD-20

Page 2 of 2
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

UPTIME
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
1A N/A ZA/B B 30 10K OHM SIF-24F HD-2 HS-21D HB-2
1A N/A ZA/B B 24 10K OHM SLK-24F HD-3 HS-21D HB-2
1A N/A ZA/B B 24 10K OHM SLK-24FH HD-3 HS-21D HB-2
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

VIKING
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
PAR-3, B-1 N/A A BD 30 71252 SIH-24F HD-3 HSB-220 HB-56
PAR-3, B-1 N/A A BD 30 71252 SIH-24F HD-3 HSB-224 HB-54
PAR-3, B-1 N/A A BD 30 71252 SLK-24F HD-3 HSB-220 HB-56
PAR-3, B-1 N/A A BD 30 71252 SLK-24F HD-3 HSB-224 HB-54
PAR-3, B-1 N/A A BD 30 71252 SLK-24FH HD-3 HSB-220 HB-56
PAR-3, B-1 N/A A BD 30 71252 SLK-24FH HD-3 HSB-224 HB-54
LIST OF COMPATIBLE CONTROL UNITS AND SMOKE DETECTORS 22-Oct-2002
LISTED AFTER MARCH 1, 1989

WORMALD
2-Wire Compatibility Listings
PANEL MODEL ZONE MODEL ZONE LOOP MAX EOL DETECTOR MODEL DETECTOR BASE MODEL BASE ID
ID STYLE DET ID
AUTOPULSE 1000 N/A SZB1 B 75 68710 SLK-24F HD-3 DB-201N HB-2
AUTOPULSE 1000 N/A SZB1 B 75 68710 SLK-24F HD-3 DBR-202N HB-7
AUTOPULSE 2000 N/A M6D1 D 45 N/A SLK-24F HD-3 DB-201N HB-2
AUTOPULSE 2000 N/A M6B1 B 75 70061 SLK-24F HD-3 DB-201N HB-2
AUTOPULSE 2000 N/A M6B1 B 75 70061 SLK-24F HD-3 DBR-202N HB-7
AUTOPULSE 3000 N/A M6D1 D 45 N/A SLK-24F HD-3 DB-201N HB-2
AUTOPULSE 3000 N/A M6B1 B 75 70061 SLK-24F HD-3 DBR-202N HB-7
AUTOPULSE 3000 N/A M6B1 B 75 70061 SLK-24F HD-3 DI-201N HD-2
AUTOPULSE 4000 N/A M20D1 D 40 N/A SLK-24F HD-3 DB-201N HB-2
AUTOPULSE 4000 N/A M20B1 B 75 70061 SLK-24F HD-3 DBR-202N HB-7
AUTOPULSE 4000 N/A M20B1 B 75 70061 SLK-24F HD-3 DI-201N HB-2
MULTIZONE 20M N/A M20D1 D 40 N/A SLK-24F HD-3 DB-201N HB-2
MULTIZONE 20M N/A M20B1 B 75 70061 SLK-24F HD-3 DBR-202N HB-7
MULTIZONE 20M N/A M20B1 B 75 70061 SLK-24F HD-3 DI-201N HB-2
MULTIZONE 20P N/A M20B1 B 75 70061 SLK-24F HD-3 DB-201N HB-2
MULTIZONE 20P N/A M20D1 D 40 N/A SLK-24F HD-3 DB-201N HB-2
MULTIZONE 20P N/A M20B1 B 75 70061 SLK-24F HD-3 DBR-202N HB-7
MULTIZONE 6P N/A M6D1 D 45 N/A SLK-24F HD-3 DB-201N HB-2
MULTIZONE 6P N/A M6B1 B 75 70061 SLK-24F HD-3 DBR-202N HB-7
MULTIZONE 6P N/A M6B1 B 75 70061 SLK-24F HD-3 DI-201N HB-2
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 3240-0410:155 Page 1 of 1

CATEGORY: Duct Smoke Detector Housing/Base

LISTEE: Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 FAX (714) 522-2268

DESIGN: Models DH-98-I, DH-98-P, DH-98-A, *DH-98-ASK, DH-98-AR, DH-98-HVI and DH-98-
HVP duct smoke detector units. Each unit consists of a smoke detector head, Models SIJ-
24DH (ionization type), SLR-24DH, ALG-DH, or ALG-EA (photoelectric type), plastic
enclosure, plastic cover, relays, electrical components, and sampling and exhaust tubes.
The smoke detector heads are not suitable for use as open area detection. Refer to
listee's data sheet for additional detailed product description and operational
considerations. For use with the following accessories: MS-RA, MS-RA/P, MS-RA/R, MS-
RA/P/R, MS-KA/R, MS-KA/P/R, AND MS-RH/KA/P/R remote alarms.

RATING: 120 VAC, 230 VAC, 24 VAC and 24 VDC

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and
in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model designation, electrical rating and UL label.

APPROVAL: Listed as duct smoke detector units for use with separately listed compatible fire alarm
control units to detect an abnormal amount of smoke density in the return air ducts of air
conditioning and ventilating system. The air velocity in the duct shall be between 300-
4000 fpm.

NOTE: For duct application only. Not suitable for open area protection.

*Rev. 04-04-08 bh

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7120-0410:153 Page 1 of 1

CATEGORY: Annunciators

LISTEE: Hochiki America, 7051 Village Dr., Suite 100, Buena Park, CA 90621
Contact: Loren Leimer (714) 670-3248 Fax (714) 522-2268

DESIGN: Model HRAM-208 remote multiplex annunciator and HRTI-1 Remote trouble Indicator.
Refer to listee's data sheet for additional detailed product description and operational
considerations.

RATING: 20-19 VDC

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and
in a manner acceptable to the authority having jurisdiction. For indoor use only.

MARKING: Listee's name, model number and UL label.

APPROVAL: Listed as annunciator panel for use with listee's separately listed compatible Model HCP-
200 Series fire alarm control unit (CSFM Listing No. 7165-0410:152).

XLF: 7120-1477:108

*Rev. 11-16-2000

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7120-0410:157 Page 1 of 1

CATEGORY: Annunciators

LISTEE: Hochiki America, 7051 Village Dr., Suite 100, Buena Park, CA 90621
Contact: Loren Leimer (714) 670-3248 FAX (714) 522-2268

DESIGN: Model HRA-1000 remote multiplex annunciator panel. The main annunciator module
provides indication for 32 zones. Each adder annunciator module provides indication for
48 additional zones. Unit includes main annunciator chassis HRAM-1032 and adder
annunciator chassis HRAX-1048. Refer to listee's data sheet for additional detailed
product description and operational considerations.

RATING: 20-29 VDC

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction. For indoor use only.

MARKING: Listee's name, model number and UL label.

APPROVAL: Listed as annunciator panel for use with listee's separately listed compatible Model HPC-
1000 fire alarm control unit (CSFM Listing No. 7165-0410:154).

XLF: 7120-1477:107

*Rev. 11-16-2000

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7120-0410:165 Page 1 of 1

CATEGORY: Annunciators

LISTEE: Hochiki America, 7051 Village Dr., Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 FAX (714) 522-2268

DESIGN: Model *FN-LCD-N Network LCD Annunciator and **Model FN-LCD-S Serial LCD
Annunciator. Connects to the control panel via the RS-485 network interface. Employs
four Form C relays that are unsupervised. **Up to 16 FN-LCD-S Serial LCD Annunciators
can be connected to one control panel. Refer to listee's data sheet for additional detailed
product description and operational considerations.

RATING: 24 VDC

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, rating, and UL label.

APPROVAL: Listed as annunciator panel for use with listee's separately listed compatible Model FireNet
4127 fire alarm control unit (CSFM Listing No. 7165-0410:159). Refer to listee’s Installation
Instruction Manual for details.

*Recert. 04-12-2007 jw

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7150-0410:156 Page 1 of 1

CATEGORY: Boxes/Pull Stations

LISTEE: Hochiki America, 7051 Village Dr., Suite 100, Buena Park, CA 90621
Contact: Loren Leimer (714) 670-3248 FAX (714) 522-2268

DESIGN: Models HMS-401U, HMS-501U noncoded fire alarm manual pull stations; and Model
HMS-DA station adapter. Refer to listee's data sheet for additional detailed product
description and operational considerations.

RATING: 30 VDC, 1A

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and
in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number and UL label.

APPROVAL: Listed as fire alarm manual pull stations for use with separately listed electrically and
functionally compatible fire alarm control units.

XLF: 7150-1477:101

10-02-2000

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7150-0410:162 Page 1 of 1

CATEGORY: Boxes/Pull Stations

LISTEE: Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 FAX (714) 522-2268

DESIGN: Models HPS-SAH, HPS/SAK, HPS-DAH, HPS-DAH/S, and HPS-SAH-WP with or without
the suffix DA-C non-coded manual pull stations. Refer to listee's data sheet for detailed
product description and operational considerations.

INSTALLATION: In accordance with listee's printed installation instructions and applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, electrical rating, and UL label.

APPROVAL: Listed as fire alarm manual pull stations for use with separately listed compatible fire alarm
control units. Model HPS-SAH-WP is suitable for outdoor use. Refer to listee’s Installation
Instruction Manual for details.

XLF: 7150-1039:101

08-24-2004

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7150-0410:164 Page 1 of 1

CATEGORY: Boxes/Pull Stations

LISTEE: Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 FAX (714) 522-2268

DESIGN: Models HPS-CP and HPS/CP/S non-coded boxes. Refer to listee's data sheet for detailed
product description and operational considerations.

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances and
in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model name, and UL label.

APPROVAL: Listed as boxes for use with separately listed compatible fire alarm control units. Refer to
listee’s Installation Instruction Manual for details.

XLF: 7150-0512:006

08-24-2004

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7150-0410:169 Page 1 of 1

CATEGORY: Boxes/Pull Stations

LISTEE: Hochiki America, 7051 Village Dr., Suite 100, Buena Park, CA 90621
Contact: Loren Leimer (714) 670-3248 Fax (714) 522-2268

DESIGN: Models DCP-AMS, DCP-AMS-LP, DCP-AMS-KL and DCP-AMS-KL-LP addressable fire


alarm manual pull boxes. “LP” suffix is a dual action box. “KL” suffix is a key lock access
box. Refer to listee's data sheet for additional detailed product description and
operational considerations.

RATING: 33 Vdc

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and
in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number and UL label.

APPROVAL: Listed as fire alarm manual pull stations for use with separately listed electrically and
functionally compatible fire alarm control units.

1-8-07 jw

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7151-0410:163 Page 1 of 1

CATEGORY: Boxes/Pull Stations for Hazardous Locations

LISTEE: Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 FAX (714) 522-2268

DESIGN: Model HPS-SA-EX/WP with or without the suffix DA-C non-coded, explosion proof,
weather proof manual pull stations. These devices consist of a switch and terminal block
mounted within an explosion proof enclosure. Refer to listee's data sheet for additional
detailed product description and operational considerations.

RATING: Electrical: 120 VAC, 10 A

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances,
and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, electrical rating, and UL label.

APPROVAL: Listed as fire alarm manual pull stations for use with separately listed compatible fire alarm
control units. Suitable for use outdoor and in Class I, Group B, C and D; Class II, Group E, F
and G hazardous locations. Refer to listee’s Installation Instruction Manual for details.

XLF: 7151-1039:104

08-24-2004

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7165-0410:152 Page 1 of 1

CATEGORY: Control Unit (Non High-Rise)

LISTEE: Hochiki America, 7051 Village Dr., Suite 100, Buena Park, CA 90621
Contact: Loren Leimer (714) 670-3248 Fax (714) 522-2268

DESIGN: Model HCP-201, HCP-202, HCP-204 and HCP-204E fire alarm control units. Non-coded;
automatic, manual, local, remote station, central station, waterflow and sprinkler
supervisory service. System components:

HCP-201,-202,-204,-204E Main Fire Alarm Assembly


HDM-204 Initiating & NAC Zones
HRM-204, HRM-208 Relay Module
HPR-100 Polarity reversal & City Tie
HDACT-100 DACT
BB-815, BB-816 Enclosure

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances,
and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, electrical rating and UL label.

APPROVAL: Listed as fire alarm control units for use with separately listed electrically and functionally
compatible initiating and indicating devices.

This control unit does not generate a temporal pattern signal. If the distinctive three-pulse
Temporal Pattern Fire Alarm Evacuation Signal (for total evacuation) in accordance with
NFPA 72, 1999 Edition is required, the control unit must be used with appliances that can
generate the temporal pattern signal. Refer to listee's Installation instructions Manual for
details.

NOTE: For Fire Alarm Verification Feature, the maximum Retard/Reset/Restart period shall not
exceed 30.0 seconds.

XLF: 07165-1477:109

*Rev. 11-16-2000

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7165-0410:154 Page 1 of 1

CATEGORY: Control Unit (Non High-Rise)

LISTEE: Hochiki America, 7051 Village Dr., Suite 100, Buena Park, CA 90621
Contact: Loren Leimer (714) 670-3248 Fax (714) 522-2268

DESIGN: HCP-1000 fire alarm control unit. Non-coded, automatic, manual, local, auxiliary, remote
station, waterflow and sprinkler supervisory service. System components:

HCP-1000 Control Unit


HBB-1024, HBB-1072 Backbox
HMCC-1024-6, -12 24-Zone Chassis
HMCC-1024-6S, -12S 24-Zone Chassis
HECH-1048 Expander Chassis
HDM-1008 8-Zone Detection Module
HSGM-1004 4-Zone NAC Module
HRM-1008 Relay Adder Module
HPR-100 Polarity Reversal and City Tie
HFA-1024TR Flush Trim Ring

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances,
and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, electrical rating and UL label.

APPROVAL: Listed as fire alarm control units for use with separately listed electrically and functionally
compatible initiating and indicating devices.

This control unit can generate a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition. Refer
to listee's Installation Manual for details.

This control unit meets the requirement of UL-864, 8th Edition Standard.

NOTE: For Fire Alarm Verification Feature (delay of fire alarm signal), the maximum
Retard/Reset/Restart period shall not exceed 30 seconds.

XLF: 7165-1477:106

*Rev. 11-16-2000

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7170-0410:170 Page 1 of 2

CATEGORY: Control Unit (High-Rise)

LISTEE: Hochiki America, 7051 Village Dr., Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 Fax (714) 522-2268

DESIGN: Model FireNet 4127 Analog Addressable fire alarm control unit. Automatic, manual, waterflow
and sprinkler supervisory service. Refer to the listee's data sheet for detailed product description
and operational considerations. System components:

MODULE PART NO. DESCRIPTION


FN-4127-BO (K6002) Control Board
FN-4127-IO (K6006) 16 Channel Input/Output Board
FN-4127-CPA-BO (K6001) Front LCD Indicator Panel
FN-4127-SLC (K6004) Loop 3, 4 Board
FN-4127-NIC (K6005) Network Card
FN-PS402 (S402) Power Supply
*FN-DAC (FN-DAC) Digital Alarm Communicator
FN-ENC (FN-ENC) Enclosures
FN-ACC (FN-ACC) Battery/Accessory Enclosure
FN-CTM (7000-00780) City Tie Module
D9068 (D9068)Bosch Digital Alarm Communication Transmitter
HMX-DP (1) Voice Evacuation System Distribution
Panel
HMX-MP (1) Voice Evacuation System Master Panel
EVX-100 (1) Audio Adjunct Module
EVX-RM (1) Remote Microphone
(1)
Evax Systems Product (CSFM Listing No. 6911-1446:100 and 6911-1446:103)

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances,
and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, electrical rating, and UL label.

APPROVAL: Listed as fire alarm control panel suitable for highrise applications when used with
separately listed electrically and functionally compatible initiating and indicating devices.
Refer to listee’s Installation Instruction Manual for details. This control unit meets the
requirements of UL-864, 9th Edition Standard.

This control unit can generate a temporal pattern Fire Alarm Evacuation signal (for total
evacuation) in accordance with NFPA 72, 2002 Edition.

NOTE: For Fire Alarm Verification Feature (delay of fire alarm signal), the maximum
Retard/Reset/Restart period shall not exceed 30 seconds.
01-28-2008 mt

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTINGS No. 7260-0410:158 Page 1 of 1

CATEGORY: Beam Smoke Detection System

LISTEE: Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 FAX (714) 522-2268

DESIGN: Model SRA-24 projected beam smoke detector. Unit consists of a transmitter/receiver unit
and a reflector unit. This device is intended for ceiling installation only between 25 to 100 ft
apart. Refer to the listee's data sheet for detailed product description and operational
considerations.

RATING: 24 V dc

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction

MARKING: Listee's name, model number, electrical ratings, and UL Label.

APPROVAL: Listed as beam smoke detector for use with separately listed compatible fire alarm control
units. Refer to listee’s Installation Instructions Manual for details.

04-14-03KK

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7260-0410:172 Page 1 of 1

CATEGORY: Beam Smoke Detection System

LISTEE: Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 Fax (714) 522-2268

DESIGN: Model SPC-24 Projected Beam, Smoke-Automatic Fire Detector. Unit consists of one emitter
unit and one receiver unit. Refer to listee's printed data sheet for additional product
description and operational consideration.

RATING: 24 VDC

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, electrical ratings, and UL Label

APPROVAL: Listed as beam smoke detectors for use with separately listed compatible fire alarm control
units.

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7270-0410:119 Page 1 of 1

CATEGORY: Heat Detector

LISTEE: Hochiki America, 7051 Village Dr., Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 Fax (714) 522-2268

DESIGN: Models AL-DFE-135 and AL-DFE-190. Refer to listee's data sheet for detailed product
description and operational considerations.

INSTALLATION: In accordance with the listee's printed installation instructions, applicable codes and
ordinances and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, temperature & electrical ratings and UL label.

APPROVAL: Listed as system heat detectors when used in conjunction with listed compatible bases
(CSFM Listing No. 7300-0410:132) and separately listed compatible control units.

NOTE: Combined Listing No. 7270-0410:117 and 7270-0410:119

*Rev. 11-16-2000

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7270-0410:147 Page 1 of 1

CATEGORY: Heat Detector

LISTEE: Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 Fax (714) 522-2268

DESIGN: Model ATG-EA electronic fixed temperature heat detector (analog) with Models YBN-NSA-4
and HSB-NSA-6 bases. Unit consists of resistors, capacitors, diodes, transistors, LED,
thermistors, mounted on a printed wiring board inside an enclosure. Refer to listee's data
sheet for additional detailed product description and operational considerations.

RATING: Electrical: 39.5 VDC


Temperature Range: 134oF - 149oF

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and
in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model designation, electrical/temperature rating and UL label.

APPROVAL: Listed as heat detector for use with separately listed compatible fire alarm control units.

*Corrected 11-06-2001

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7270-0410:151 Page 1 of 1

CATEGORY: Heat Detector

LISTEE: Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 Fax (714) 522-2268

DESIGN: Models DCD-135 and DCD-190, fixed temperature and rate of rise heat detectors. Refer to
listee's data sheet for additional detailed product description and operational considerations.

RATING: Temperature: DCD-135: 135 0 F


DCD-190: 190 0 F

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model designation, rating and UL label.

APPROVAL: Listed as fixed temperature and rate of rise heat detector for use listed bases (CSFM Listing
No. 7300-0410:132) and separately listed fire alarm control units.

*Rev. 11-16-2000

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7271-0410:135 Page 1 of 1

CATEGORY: Ionization Smoke Detector

LISTEE: Hochiki America, 7051 Village Dr., Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 Fax (714) 522-2268

DESIGN: Models SIH-24F and *SIJ-24 ionization type smoke detector. Refer to listee's data sheet for
detailed product description and operational considerations.

RATING: 24 VDC

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, electrical rating and UL label.

APPROVAL: Listed as ionization smoke detectors when used in conjunction with listed bases (CSFM
Listing No. 7300-0410:132) and separately listed compatible fire alarm control units.

NOTE: Formerly 7256-0410:110 & 135

*Rev. 11-16--2000

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7271-0410:148 Page 1 of 1

CATEGORY: Ionization Smoke Detector

LISTEE: Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 Fax (714) 522-2268

DESIGN: Model AIE-EA analog addressable ionization type smoke detector with Models YBN-NSA-4
and HSB-NSA-6 bases. Unit consists of resistors, capacitors, diodes, transistors, LED,
diodes and ionization chamber, mounted on a printed wiring board inside an enclosure.
Refer to listee's data sheet for additional detailed product description and operational
considerations.

RATING: 39.5 VDC

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and
in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model designation, electrical rating and UL label.

APPROVAL: Listed as ionization type smoke detector for use with separately listed compatible fire
alarm control units.

*Rev. 11-16-2000

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7272-0410:107 Page 1 of 1

CATEGORY: Photoelectric Smoke Detector

LISTEE: Hochiki America, 7051 Village Dr., Suite 100, Buena Park, CA 90621
Contact: Loren Leimer (714) 670-3248 Fax (714) 522-2268

DESIGN: Models SLG-12, SLG-24, SLG-24FH, SLG-24F, SLK-12, SLK-24F, SLK-24FH, SLK-
24FB, SLK-24FL, SLK-24FLB, SLK-835, SLK-835H, SLR-835, SLR-835W, SLR-835B-
2, SLR-835B-4, SLR-835B-2W, SLR-835B-4W, SLR-24, SLR-24H, SLR-24V, *SLR-
24VN, SLR-835H, SLR-835HW, SLR-835BH-2, SLR-835BH-2W, SLR-835BH-4, SLR-
835BH-4W photoelectric type smoke detectors. Unit with suffix -H or -FH employs a
supplemental heat sensor. Refer to listee's data sheet for additional detailed product
description and operational considerations.

RATING: 12 VDC and 24 VDC

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and
in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model designation, electrical rating and UL label.

APPROVAL: Listed as photoelectric smoke detectors for use with separately listed compatible fire alarm
control units when used in conjunction with listee's listed bases (CSFM Listing No. 7300-
0410:132). Models with supplemental heat sensor are not approved for use in lieu of
required heat detectors.

NOTE: Formerly 7257-0410:107

*Rev. 2-14-2003 IPI

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7272-0410:149 Page 1 of 1

CATEGORY: Photoelectric Smoke Detector

LISTEE: Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 Fax (714) 522-2268

DESIGN: Models ALG-EA and ALG-V analog addressable photoelectric type smoke detector with
Models YBN-NSA-4 and HSB-NSA-6 bases. Unit consists of resistors, capacitors,
diodes, transistors, LED, photo diode, mounted on a printed wiring board inside an
enclosure. Refer to listee's data sheet for additional detailed product description and
operational considerations.

RATING: 39.5 VDC

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model designation, electrical rating and UL label.

APPROVAL: Listed as photoelectric smoke detector for use with separately listed compatible fire alarm
control units. *Model ALG-V is suitable for in duct use in air velocities up to 4000 ft/min.

*Rev. 01-31-2008 mt

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7272-0410:173 Page 1 of 1

CATEGORY: Photoelectric Smoke Detector

LISTEE: Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 FAX (714) 522-2268

DESIGN: Models ALK-V analog addressable photoelectric type smoke detector with Models YBN-
NSA-4 and HSB-NSA-6 bases. Unit consists of resistors, capacitors, diodes, transistors,
LED, photo diode, mounted on a printed wiring board inside an enclosure. Refer to
listee's data sheet for additional detailed product description and operational
considerations.

RATING: 39.5 VDC

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model designation, electrical rating and UL label.

APPROVAL: Listed as photoelectric smoke detector for use with separately listed compatible fire alarm
control units. Also suitable for in-duct use in air velocities up to 4000 ft/min.

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: MAY 19, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7272-0410:174 Page 1 of 1

CATEGORY: Photoelectric Smoke Detector

LISTEE: Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 FAX (714) 522-2268

DESIGN: Models SLV-24, SLV-24V and SLV-24N Conventional, Photoelectric Type Smoke Detectors.
Detectors are for use with listed Models NS4-220, NS4-224, NS6-220, NS6-224, HSC-4R,
HSC-220R, and HSC-224R Bases. Refer to listee's data sheet for detailed product
description and operational considerations.

RATING: 24 Vdc

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, rating and UL label.

APPROVAL: Listed as photoelectric smoke detectors for use with listed bases as shown in “DESIGN”.

03-19-2008

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: APRIL 29, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7300-0410:132 Page 1 of 2

CATEGORY: Misc. Devices/Control Unit Accessories

LISTEE: Hochiki America, *7051 Village Dr., Suite 100, Buena Park, CA 90621-2268
Contact: Bob Misiuk (714) 670-3251 Fax (714) 690-7890

DESIGN: Detector bases (2 and 4-wire). Unit is intended for use with a separately listed compatible
detector head. Refer to listee's data sheet for detailed product description and operational
considerations. Models listed below.

HA-4W HA-4W1 HA-4WX HA-2


HA-SL HA-SR HA-SLR HA-RA2
HA-NRA2 HA-L12R HA-2R HA-22R
HA-L2 HA-L2A HA-L2R HA-L22
HA-L22A HA-L22F HA-L22R HA-L22S
HA-LA2 HA-LRA HA-LRA2 HA-LNA2
HA-LNRA2

HS-2 HS-2L HS-2D HS-21


HS-21L HS-21D HS-22 HS-22L
HS-22D HS-100 HS-200D HS-220
HS-220L HS-220D HS-221 HS-221L
HS-221D HS-221X HS-221XL HS-221XD
HS-224 HS-224L HS-224D HS-225
HS-225L HS-225D HS-2RB HS-21RB
HS-220RB HS-221RB HS-224RB HS-2RB4

HSB-2 HSB-2N HSB-12-1 HSB-12-1N


HSB-12-4 HSB-12-4N HSB-21 HSB-21N
HSB-100 HSB-200 HSB-200N HSB-220
HSB-220N HSB-221 HSB-221N HSB-221S
HSB-224 HSB-224N HSB-225 HSB-225N
HSC-4R HSC-21L HSC-220L HSC-220R
HSC-221L HSC-221R HSC-224RA HSC-224L
HSC-224R HSC-225L HSB-DCP-6 HSB-NSA-6

YBA-M2 YBA-M21 YBA-M22 YBA-M220


YBA-M221 YBA-M224 YBA-M225 YBA-M100
YBA-MAP YBA-R3 YBA-RL/4 YBA-RL/4-1
YBA-RL/4-2 YBA-RL/4-RA YBC-RL/12 YBC-RL/12-1
YBC-RL/12-2 YBC-RL/12-4 YBC-RL/4-RA YBC-RL/2NC
YBC-RL/2NBE YBJ-RL/2ND YBN-R/2NA YBN-NSA-4
NS4-100 NS4-220 NS4-221 NS4-224
NS6-100 NS6-220 NS6-221 NS6-224

Models may or may not come with suffix -W.

*Corrected. 11-06-2001
Listing No. 7300-0410:132
Page 2 of 2

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, electrical rating and UL label.

APPROVAL: Listed as bases for use with listee’s separately listed compatible smoke and heat detectors.
Refer to heat or smoke detector listings for compatibility. Models HA-2R, HA-SLR, HA-LRA2
and HSC Series w/ suffix R are also suitable for releasing device service. Model YBA-R3 is
intended for use with thermostat detector only.

NOTE: Formerly 7300-0410:100, 106, 115, 124, 125, 126, 130, 131 & 133

*Corrected 11-06-2001

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7300-0410:137 Page 1 of 1

CATEGORY: Misc. Devices/Control Unit Accessories

LISTEE: Hochiki America, 7051 Village Dr., Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 Fax (714) 522-2268

DESIGN: Models HA-EOLR, AL-HA-EOLR, HA-EOLR-12 and AL-HA-EOLR-12 end-of-line relays.


Refer to listee's data sheet for detailed product description and operational
considerations.

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes and ordinances
and in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, contact and coil rating, and UL label.

APPROVAL: Listed as end-of-line relays for use with separately listed compatible 4-wire detectors.

*Rev. 11-16-2000

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7300-0410:150 Page 1 of 1

CATEGORY: Misc. Devices/Control Unit Accessories

LISTEE: Hochiki America, 7051 Village Dr., Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 Fax (714) 522-2268

DESIGN: Control Unit Accessories Models:

DCP-RM, DCP-R2M Analog Relay Module


DCP-SCI Short Circuit Isolator
DCP-FRCME, DCP-FRCME-P, Monitor Modules
DCP-FRCME-S, DCP-FRCME-4, Monitor Modules
DCP-FRCME-S-100, DCP-FRCME-4-100 Monitor Modules
DCP-SOM Supervised Output Module
DCP-SRM Solenoid Releasing Module
DCP-DIMM Dual Input Monitor Module
*CZM Conventional Zone Module

Refer to listee's data sheet for additional detailed product description and operational
considerations.

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and
in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, electrical rating, and UL label.

APPROVAL: Listed as control unit accessories for use with separately listed compatible fire alarm control
units. Refer to listee’s Installation Instruction Manual for details.

*Rev. 06-08-04

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7300-0410:160 Page 1 of 1

CATEGORY: Misc. Devices/Control Unit Accessories

LISTEE: Hochiki America, 7051 Village Dr., Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 FAX (714) 522-2268

DESIGN: Models SBC-2, -2R, -4/12, -4/24 detector sounder base. The use of suffix “W” indicates
the color white. Unit SBC-2R employs a relay. SBC-4 models employ extra output leads
for connection to a control panel intitiating loop. Refer to listee's data sheet for additional
detailed product description and operational considerations.

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and
in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, electrical rating, and UL label.

APPROVAL: Listed as detector base for use with separately listed functionally and electrically compatible
fire alarm control units. Designed specifically for use with listee’s Models SIJ-24 (CSFM
Listing No. 7271-0410:135) Ionization Smoke Detector or Models SLR-24V, SLR-835 (CSFM
Listing No. 7272-0410:107) Photoelectric Smoke Detector. Refer to listee’s Installation
Instruction Manual for details.

NOTE: These appliances can generate a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.

10-27-03

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7300-0410:161 Page 1 of 1

CATEGORY: Misc. Devices/Control Unit Accessories

LISTEE: Hochiki America, 7051 Village Dr., Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 FAX (714) 522-2268

DESIGN: Model ASB detector sounder base. Unit has an intregral audible signal for use with spot-
type detector units. Refer to listee's data sheet for additional detailed product description
and operational considerations.

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and
in a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, electrical rating, and UL label.

APPROVAL: Listed as a detector base for use with separately listed functionally and electrically compatible
fire alarm control units. Designed specifically for use with listee’s Model ALG-V (CSFM
Listing No. 7272-0410:149) Photoelectric Smoke Detector; Model AIE-EA (CSFM Listing No.
7271-0410:148) Ionization Smoke Detector; or Model ATG-EA (CSFM Listing No. 7270-
0410:147) Heat Detector. Refer to listee’s Installation Instruction Manual for details.

NOTE: These appliances can generate a distinctive three-pulse Temporal Pattern Fire Alarm
Evacuation Signal (for total evacuation) in accordance with NFPA 72, 2002 Edition.

08-24-2004

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7315-0410:166 Page 1 of 1

CATEGORY: Power Units

LISTEE: Hochiki America, 7051 Village Dr., Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 FAX (714) 522-2268

DESIGN: Models FN-642-ULADA, FN-842-ULADA and FN-1042-ULADA Indicating Circuit Power


Supply may be followed by -R, -G, -C, or -B. Units are a regulated 12 or 24 VDC power
supply/charger used for supervision and expanded power driving capability of four
notification appliance circuits. Refer to listee's data sheet for additional detailed product
description and operational considerations.

RATING: 115 VAC primary, 12 or 24 VDC secondary

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and
in a manner acceptable to the authority having jurisdiction

MARKING: Listee's name, model number, electrical rating, and UL label.

APPROVAL: Listed as power supply units for use with separately listed compatible fire alarm control units.
Refer to listee’s Installation Instruction Manual for details.

NOTE: The system must have the secondary power supply capable of operating the system for at
least 24 hours battery standby) in the normal condition and followed by not less than 5
minutes of alarm as required by code. The battery circuit must be fully supervised.

XLF: 7315-1335:109

05-03-2005

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7315-0410:167 Page 1 of 1

CATEGORY: Power Units

LISTEE: Hochiki America, 7051 Village Dr., Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 FAX (714) 522-2268

DESIGN: Models FN-1024ULX, FN-300ULX and FN-400ULX power supply units may be followed
by -G, -R, -C, or -B. Models FN-300ULX series are designed to charge sealed lead acid
type rechargeable batteries. Refer to listee's data sheet for additional detailed product
description and operational considerations.

RATING: 115 VAC input, 12 or 24 VDC output

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances
and in a manner acceptable to the authority having jurisdiction. For fire alarm use, the
standby batteries must provide 24 hours standby power during power loss.

MARKING: Listee's name, model number, electrical rating, and UL label.

APPROVAL: Listed as power supply units for use with separately listed compatible fire alarm control
units to provide power for door holders, door strikes or similar devices. Refer to listee’s
Installation Instruction Manual for details.

NOTE: Not suitable for fire alarm indicating devices.

XLF: 7315-1335:100

05-03-2005

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7315-0410:168 Page 1 of 1

CATEGORY: Power Units

LISTEE: Hochiki America, 7051 Village Dr., Suite 100, Buena Park, CA 90621-2268
Contact: Loren Leimer (714) 670-3248 Fax (714) 522-2268

DESIGN: Models FN-600ULX-G, -R, -C, -B Power Supply Units. Refer to listee's data sheet for
additional detailed product description and operational considerations.

RATING: 115 VAC input, 12 or 24 VDC output

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and
in a manner acceptable to the authority having jurisdiction

MARKING: Listee's name, model number, electrical rating, and UL label.

APPROVAL: Listed as power supply units for use with separately listed compatible fire alarm control units.
Also suitable for use with access control systems. Authority having jurisdiction should be
consulted prior to installation.

NOTE: For fire alarm use, the standby batteries must provide at least 24 hours standby power
during power loss. The battery circuit must be fully supervised.

XLF: 7315-1335:104

05-03-2005

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division
CALIFORNIA DEPARTMENT OF FORESTRY & FIRE PROTECTION
OFFICE OF THE STATE FIRE MARSHAL
FIRE ENGINEERING - BUILDING MATERIALS LISTING PROGRAM

LISTING SERVICE
LISTING No. 7315-0410:171 Page 1 of 1

CATEGORY: Power Units

LISTEE: Hochiki America, 7051 Village Drive, Suite 100, Buena Park, CA 90621-7890
Contact: Loren Leimer (714) 670-3248 Fax (714) 522-2268

DESIGN: Models FN-642-UL2ADA-R and –C, FN-842-UL2ADA-R and –C, FN-1042-UL2ADA-R and -C
Power-limited Indicating Circuit NAC Power Supply/Charger. Refer to listee's data sheet for
additional detailed product description and operational considerations.

RATING: FN-642-UL2ADA-R and –C, FN-842-UL2ADA-R and -C: 120 VAC input, 12/24 VDC output, 2A
(on each indicating circuit)
FN-1042-UL2ADA-R and -C:115 VAC input, 24 VDC output, 2.5A (on each indicating circuit)

INSTALLATION: In accordance with listee's printed installation instructions, applicable codes & ordinances and in
a manner acceptable to the authority having jurisdiction.

MARKING: Listee's name, model number, electrical rating and UL label.

APPROVAL: Listed as a power-limited indicating circuit power supply for use with separately listed
compatible fire alarm control units and indicating devices. Authority having jurisdiction should
be consulted prior to installation.

XL: 7315-1335:112

08-27-2007 mt

This listing is based upon technical data submitted by the applicant. CSFM Fire Engineering staff has reviewed the test results
and/or other data but does not make an independent verification of any claims. This listing is not an endorsement or
recommendation of the item listed. This listing should not be used to verify correct operational requirements or installation
criteria. Refer to listee’s data sheet, installation instructions and/or other suitable information sources.

Date Issued: JUNE 5, 2008 Listing Expires June 30, 2009

Authorized By: BEN HO, Chief


Fire Engineering Division