Академический Документы
Профессиональный Документы
Культура Документы
Industrial Dehumidification:
Water Vapor Load Calculations and
System Descriptions
Accurately calculating water vapor loads in industrial environments helps
size and select systems with minimal operating costs
T
he need to control the factors. The purpose of this article tion system. This procedure pro-
amount of water vapor in is to provide information on en- duces an in-depth analysis of the
the air is felt in all indus- ergy usage, energy calculations, sensible and latent heat energy
trial, commercial, and institu- and operating energy costs to help flows. This analysis is also meant
tional facilities. Humidity control engineers evaluate industrial de- to help the engineer with the con-
is important to human health and humidification systems. I use cepts of heat of condensation, re-
activation heat, heat dump back, materials, which are solids or liq- Portable dehumidifiers
and desiccant heat. uids that can extract moisture When most people think of por-
from the air and hold it. There are table dehumidifiers, they think of
Types of dehumidification systems two classifications of sorbents: equipment that is used in the
Some of the types of equipment ● Adsorbents—which do not home, but this is no longer true.
and their moisture-removal capa- experience a phase change. Mois- These systems are being used in
bilities are illustrated in Table 1. ture is deposited on the surface of many commercial and industrial
Moisture can be removed from the the dry desiccant. Most adsor- applications. A few examples of
air by cooling it below the dew- bents are solids. their uses are: indoor pools, clean-
point temperature so condensation ● Absorbents—which change ing and restoration, locker rooms,
occurs by air-to-air heat exchang- physically, chemically, or both pump stations, libraries, restau-
ers, which bring in dryer outside during the sorption process. Most rants and bars, film and tape stor-
air, or by chemical methods. absorbents are liquids or solids age, bakeries, well houses, and
Chemical dehumidification is car- that become liquid as they absorb canning plants.
ried out through the use of sorbent moisture. The types of portable equip-
ment available are direct
TABLE 2—Capacity of portable dehumidifiers expansion (DX) reheat,
dry desiccant, and air-to-
Equipment Type Water removal1 Operating cost2 air heat exchangers—to
name a few. The water-re-
moval capacities of these
systems at ANSI B149.1
inlet air conditions (80 F
and 60 percent RH) are as
follows:
●DX reheat: 0.65 to 4.35
lb per hr; 1.88 and 12.50
gal per day, respectively.
● Dry desiccant: 6.26 lb
Note: 1 Water removal is at ANSI B149.1. Inlet air conditions of 80F and 60 percent RH relative humidity. per hr; 18 gal per day.
2 Operating cost is based on an electric rate of $0.06 per kwh
● Air changers: 15.30 lb
per hr; 44 gal per day.
(Building air is exhausted
TABLE 3—Capacity of portable dehumidifier at various through an air-to-air heat
inlet air conditions exchanger that brings in
Tdb Tdp RH W* Removal Operationg cost dry outside air. Removal
capacity is based on out-
side air at 0 F and 60 per-
cent RH.)
Table 2 is a summary of
more than 30 portable de-
humidifiers reviewed for
this article. The table il-
lustrates both the water-
removal capacity and the
operating cost of each sys-
tem. Notice that the en-
ergy-inefficient systems
use up to four times more
energy than the efficient
systems. Table 3 presents
the variation of water-va-
por removal and the oper-
ating cost at various inlet
Note: This particular unit is a high capacity energy efficient unit. Tdb is dry bulb temperature. Tdp is dew point temperature.
air conditions. This table
RH is relative humidity. Operating cost is based on an electric rate of $0.06 per kwh was based on one of the en-
*Grains of water vapor per lb of dry air ergy-efficient models.
Some DX-reheat units will
High pressure
condenser
Warm freon gas
Hot gas
DX chiller with
each system was required to dry air-cooled condenser
the air down to 35 or 36 grains of (1.5405 KW per ton) at 95 F
water vapor per lb of dry air. I Low pressure
worked with several dehumidifi- Refrigeration Compressor
cation companies to size the sys- gas
tems and determine all energy
consumption. Using the brake
horsepower provided by the com- Process air
panies, I sized the motors and cal-
anaylsis 1 2 3 4 5
culated the electrical consump- Dry bulb 70 F 53.40 F 39.73 F 42.73 F 56.3 F
tion (KW per hr) illustrated in this Wet bulb 58.8 F 52.17 F 39.73 F 41.29 F 47.90 F
article. Operating costs were then Dew point 51.26 F 51.26 F 39.73 F 39.73 F 39.73 F
Relative humidity 51.56% 92.86% 100% 89.61% 53.95%
developed using $0.06 per KWH for
W (grains WV 56 56 36 36 36
electricity and $5.00 per 106 Btu per lb dry air)
for natural gas. The operating acfm 30,000 29,059.79 28,157.15 28,326.30 29,091.51
costs were then developed into op- dscfm 29,574.27 29,574.27 29,574.27 29,574.27 29,574.27
erating cost per 1000 lb of water M (lb dry air per hr) 133,084.56 133,084.56 133,084.56 133,084.56 133,084.56
vapor removed. In some cases, I M (lb WV per hr) 1064.68 1064.68 684.44 684.44 684.44
left out proprietary information Q sensible 1,215,006 684,051 246,976 342,866 776,787
(Btu per hr)
on the systems at the request of Q latent 1,162,977 1,155,315 738,627 739,522 743,565
the manufacturers. (Btu per hr)
Each industrial dehumidifier in- Q total 2,377,983 1,839,366 985,603 1,082,388 1,520,352
cludes detailed air- and water-va- (Btu per hr)
por mass-flow analysis, psychro- Coil heat removal (information shows what occurs between Points 2 and 3)
metrics, thermodynamics, and DQ sensible (Btu per hr): 437,075
adiabatic mixing (Figs. 1 to 3) to DQ latent (Btu per hr): 416,688
help the readers understand the DQ total (Btu per hr): 853,763 (71.147 ton)
energy flows. The psychrometrics Water vapor removed (lb per hr): 380.24
and thermodynamics used in the
diagrams follow the principals of 1 DX with heat pipe dehumidifier.
7.82 bhp
Plate-and-frame Condenser Air inlet
chilled
heat exchanger water
pump DX chiller with
Cold dry
desiccant 45 F air-cooled
Cooler Evaporator condenser
DQ = 1,006,00 (Btu per hr) 55 F (1.10 KW per ton)
Low pressure
Recirculated desiccant
Refrigeration gas
2 Compressor
4
Dried 845,500
process air Wet regen Flue
exhaust air Plate-and-frame gas (Btu
outlet Mist Wet per hr)
heat exchanger
eliminator desiccant
180 F HWR Hot
1 Mist Heater water
220 F
eliminator boiler
Air Filter DQ = 676,400 (Btu per hr)
Wet 1.48 bhp
process 0.648 Filter Hot water Natural gas
air inlet bhp pump combination air
Packing
Cond. fan spheres Regen
13.07 bhp Regenerator 3
Packing fan air inlet
blocks
7 bhp Wet desiccant
cond. Diffuser
Weak wet to heater
desiccant desiccant
pump to regen
0.7 bhp
Conditioner Hot dry desiccant Regenerator regen desiccant
air DP = 1.3 in. WC to conditioner air DP = 2.1 in. WC pump
to a vapor as it passes through the through the coil. ton) of heat from the inlet process
restriction in the valve. Then the An example of a DX dehumidifi- air and passes it to the dehumidi-
liquid, with some bubbles of flash cation system is illustrated in Fig. fier process air leaving the system.
vapor, enters the evaporator coil. 1. The system includes a heat-pipe The advantage is reduced cooling
The liquid refrigerant in the coil heat exchanger and an air-cooled load and a leaving air condition
evaporates and, in doing so, ab- condenser system. The heat pipe that is not at or near saturation.
sorbs heat from the air passing removes 538,616 Btu per hr (44.88 The operating cost in Table 4 is
$20.03 per 1000 lb of water vapor TABLE 4—DX with heat pipe dehumidification
removed at a process-air-leaving operating cost to remove 1000 lb of water vapor.
condition of 56.3 F and 36 grains
per lb (53.9 percent RH). Dehumidi- Operating cost Electric usage
fication reheat systems will use 1) Process air fan $2.74 per 1000 17.36 KW per hr
the high-pressure, high- tempera- 2) Compressors $16.17 per 1000 102.49 KW per hr
ture gas leaving the compressor in 3) Condenser fans $1.12 per 1000 7.11 KW per hr
a coil system to reheat the process 4) Total $20.03 per l000 lb WV 126.96 KW/hr
air leaving the dehumidifier. Most @ process air discharge
common residential dehumidifiers of 56.3 F and
use this configuration. It is impor- 36 grains WV per lb dry air
tant for designers to consider a) Electricity price: $0.06 per KWH
waste energy usage, heat wheels, b) DX cooling with no energy recovery has a cost of $26.37 per 1000 lb WV with a process air discharge
or heat pipes for reheat because re- of 42.7 F and 36 grains WV per lb dry air.
heat can add a significant “added”
cost to the operating cost of a DX Rotating dry desiccant wheel ically have low vapor pressure at
system. Dry desiccants are adsorbent their surface and, therefore, ad-
A standard DX system with no materials that attract moisture be- sorb moisture from the air. When
heat pipe has an operating cost of cause of the electrical field at the moisture is removed from the pro-
$26.37 per 1000 lb of water vapor desiccant surface. The field attracts cess air stream, it produces heat
removed—at a process-air-leaving water molecules that have a net op- of sorption (or heat of adsorption),
condition of 42.7 F and 36 grains posite charge. Some of the solid ad- which is composed of latent heat
per lb (89.7 percent RH). sorbents used in dry desiccant sys- of condensation of the removed
tems are illustrated in Table 5. moisture plus additional chemical
Sorption is the adsorption pro- heat. The heat of sorption of the
TABLE 5—Types of dry cess by which a desiccant removes moisture removed from the air is
solid adsorbents. water vapor directly from the air. converted to sensible heat. The
1) Silica gel The ability of an adsorbent to at- amount of heat released is usually
2) Titanium gel tract moisture depends on the dif- around 1080 Btu per lb WV re-
3) Dry lithium chloride ference in vapor pressure between moved to 1312 Btu per lb WV re-
4) Zeolites the desiccant surface and air. The moved. The actual amount de-
5) Synthetic zeolites (molecular sieves) vapor-pressure difference drives pends on the type of desiccant.
6) Activated alumina moisture from the high vapor- The heat of sorption (sensible
7) Synthetic polymers pressure area to the low vapor- heat) is energy that is passed to
pressure area. Dry desiccants typ- continued on page 56
continued from page 54 pressure exceeds the vapor pres- A typical layout of a rotary dry
the process air stream, which sure of the reactivation air, mois- desiccant system is illustrated in
raises the discharge air tempera- ture leaves the desiccant. This Fig. 2. The operating costs of the
ture of the process air stream. process is called reactivation. system are listed in Table 6. The
As the moisture content of the The reactivation section, which operating cost for the example in
desiccant rises, so does the water- constitutes less than half of the Fig. 1 is $15.87 per 1000 lb of wa-
vapor pressure at the desiccant desiccant wheel, uses flexible ter vapor removed with a leaving
surface. At some point, the vapor seals to seal it from the adsorption air condition of 93.6 F and 35
pressure at the desiccant surface or process side to minimize cross grains per lb. If the air is too hot
will be the same as the air, and contamination. The typical leak- and has to be cooled to 55 F and 35
moisture adsorption will end. The age rate is 1 to 2 percent. grains per lb, the operating cost
desiccant is then taken out of the Following reactivation, the hot increases to $34.24 per 1000 lb
process air stream and is placed desiccant rotates back into the WV. Reactivation heat represents
into the reactivation air stream (a process air where the process air 86 percent of the operating cost
scavenger air stream consisting of cools the desiccant which lowers for the direct-fired unit and 88
outside air or building air). The the desiccant vapor pressure, so it percent for the indirect-fired unit.
reactivation air stream is typi- can collect more moisture from This represents a great opportu-
cally heated to a temperature of the balance of the process air nity for the designer to use low-
190 to 375 F. The combination of stream. Some of the equations cost hot water from cogeneration;
the heat and moisture raises the used by the rotating dry desiccant the use of low-cost steam; or con-
vapor pressure at the desiccant manufacturers are shown in the densate, refrigeration reject heat,
surface. When the surface vapor accompanying sidebar. or waste exhaust to preheat the
cant). In desiccant dehumidifica- regeneration process (sometimes the regenerator heat consumption
tion, this heat (approximately called heat dump back). The by about 15 percent.
1080 to 1320 Btu per lb water va- amount of heat and dump back is
por removed) is transformed to typically in the range of 50 to 350 Conclusion
the air, raising the air dry bulb Btu per lb water vapor removed. Table 8 is a summary of the op-
temperature, and therefore, in- Table 7 is a review of the oper- erating costs for each of the large,
creasing the load on the chilled ating costs associated with the industrial dehumidifiers using
water system. The chilled water system in Fig. 3. The total operat- the electricity cost of $0.06 per
system must be sized to remove ing cost is $28.43 per 1000 lb of KWH and the natural gas cost of
the latent heat of condensation water vapor removed from the $5.00 per 10 6 Btu. One can see
(heat of sorption), the air sensible process air. You will note that the that the dry desiccant systems
heat, and the residual heat natural gas cost is 37 percent of have the lowest energy operating
load added by the regeneration the total cost. Therefore, it pays to cost of all the systems, but they
process. find a source of waste heat to re- also have the highest discharge
To remove the water extracted duce these costs. Some possible air temperatures.
from the air and keep the liquid sources are condenser-rejected If elevated process air tempera-
desiccant at a fixed concentration, heat, solar heat, or a natural gas ture is not acceptable, the liquid
a small percentage of the condi- engine-driven chiller, which pro- desiccant or DX with heat pipe
tioner-desiccant pump flow (typi- duces hot water (engine heat) as would be the choice (at 55 to 56 F
cally around 15 percent) is trans- well as chilled water at a reduced discharge air temperature).
ferred to the regeneration system. cost. The operating cost of a liquid The outcome of this study will
The weak desiccant solution is desiccant dehumidification sys- change, depending upon the ac-
pumped up to a heating system tem combined with a natural gas tual energy costs for that area. In
(plate-and-frame heat ex- engine-driven chiller is $19.85 per the United States, natural gas
changer), which raises the tem- 1000 lb of water vapor removed. costs vary from $2.40 to $7.90 per
perature and vapor pressure of This combination represents a 30 106 Btu and electricity goes from
the liquid desiccant. The hot des- percent reduction in operating $0.018 to $0.15 per KWH . What
iccant is then sprayed at a scav- energy costs. this says is that every system
enger air stream (outside air or Another option to save energy on must be evaluated based on the
building air) with a lower vapor liquid desiccant systems is to in- energy costs for that region. Also,
pressure that forces the water va- stall a liquid-to-liquid-type heat the evaluation of operating costs
por out of the desiccant and into exchanger (some call this an inter- should include maintenance and
this air, which is exhausted out- changer) placed between the warm capital amortization.
side. The dry desiccant returns to desiccant leaving the regenerator Each system is unique, and
the regenerator sump. The desic- and the cool desiccant entering the they all offer ways to reduce en-
cant is still a little warm, and its regenerator. By doing so, less en- ergy operating costs. For example,
vapor pressure is still a little ergy is needed to regenerate the the liquid desiccant system oper-
high—until it flows back to the desiccant because it is warmer ating cost dropped 30 percent
conditioner and is cooled by the than when it left the regenerator. (from $28.43 to $19.85 per1000 lb
chilled water heat exchanger. The heat exchanger will typically WV removed) by incorporating a
Therefore, the cooling system reduce the heat dump back to the natural gas engine-driven chiller
must be sized to include this conditioner-cooling consumption and using the hot water jacket
residual heat load added by the by about 65 percent and reduces heat to preheat the regenerator
Industrial
Dehumidification:
Air Flow Diagrams &
Water Vapor Load Equations
I
n designing dehumidification systems, one of the
most important tasks is to quantify the water vapor
design are difficult to find, loads that must be removed by the system. Two
qualified individuals may arrive at different total
and terminology is not moisture loads for the same building. Some of these
differences occur from abbreviated or approximate
standard. This article equations that were developed to make the calculations
easier. However, these approximate equations lose
provides a thorough accuracy when air temperatures are higher or lower than
the conditions assumed when the approximate equations
were developed. This article will clarify some of these
review of both. equations and present alternative equations that are
more precise across a larger range of
conditions.
This article will also explain the air
22,315 cfm 24,715
55 F 42 F flows used in proposals from dehu-
20 GR Conditioned space 15 GR midification companies as well as the
55 F DB, 30 percent RH, System proposed flow diagrams from dehu-
20 GR per lb fan
midification equipment suppliers.
I have discovered a great amount of
uncertainty over the air flows in these
5100 cfm Cooling diagrams.
55 F 17,215 cfm coil
20 GR 55 F
20 GR DEHUMIDIFICATION INDUSTRY
Makeup air EQUATIONS AND TERMS
2400 cfm 7500 cfm 7500 cfm 24,715 cfm Dehumidification manufacturers
50 F/49 F 53 F 96 F 68 F like to develop air flow diagrams of
50 GR 30 GR 4 GR 15 GR
Dehumidifier
*William Acker is a member of HPAC’s
FIGURE 1 Dry desiccant systems flow diagram. Editorial Advisory Board.
their entire systems. Mass flow analysis is used in these midifier (or conditioner) 20,833 scfm is the same as the
diagrams because mass flow does not change if there is a flow leaving; therefore, this is a dry air mass flow. If the
temperature or pressure change. Mass flows can also be entering flow is fan industry 20,833 scfm, the leaving flow
added and subtracted. The actual air flows or acfm (cu ft would have dropped to 20,754 scfm due to the removal of
per min) will change if the temperature or pressure water vapor (79 scfm or 355.41 lb of water vapor per hr).
changes. Also, acfm values cannot be added or sub- The next section on fan industry scfm will help you to un-
tracted because they are at different air densities. The derstand the difference between fan and dehumidifica-
dehumidification industry chose a type of mass flow tion scfm terms.
analysis that is flow in dry standard cu ft per min (dscfm) The equations used by the dehumidification industry
at a common air density of 0.075 lb dry air per dry stan- to convert the actual air flows to dry standard air flows are
dard cu ft. The acfm flows are converted to these flows listed below:
for illustration in the air system diagrams (shown in Fig.
(lb dry air)
1 and Fig. 2). (dry std cu ft)
dry air mass flow
dscfm = min (1)
As mentioned earlier, dscfm air flow is a flow at a com- lb dry air
min
mon air density of 0.075 lb dry air per dry standard cu ft. I 0.075
dry std cu ft
Example 1:
Air pressure = 29.921 in. Hg This article will continue in HPAC’s July issue. Part II will
Air temperature = 70 F cover moisture from air leakage, water vapor load from
Relative humidity = 100 percent makeup air, and water vapor removed by dehumidifiers.
By WILLIAM ACKER*, President, from air flow. Approximate equations can be fairly accurate
Acker & Associates, Green Bay, Wis. as long as the air conditions are close to 70 F air temperature.
For more information on water vapor permeation loads,
T
his is the second article of a two-part series on in- consult the June 1998 issue of HPAC Engineering. The next
dustrial dehumidification. The first article in the few sections will compare approximate and exact equations
series, which covered air flow, can be read in for selected water vapor sources.
HPAC Engineering’s May 1999 issue.
MOISTURE FROM AIR LEAKAGE
WATER VAPOR LOADS DUE TO AIR FLOW Equations (8) to (12) can be used to calculate moisture for
Water vapor loads on industrial buildings come from air leakage through cracks, holes, and conveyor openings.
many sources. Listed below are a few of these sources of Equations (8) to (11) were taken from engineering books or
water vapor: from manuals prepared by dehumidification companies. No-
❒ People tice that the engineering units do not properly cancel out,
❒ Permeation through walls, roofs, and floors which is why they are considered approximate equations.
❒ Moisture from products and packaging materials
(grains WV) ft min
❒ Evaporation from open tanks or wet surfaces M = Velocity × 60 × Area (sq ft)
hr min hr
❒ Product dryer leakage
(lb wet air) grains WV
❒ Open combustion ×d × (Wo − Wi ) (8)
(cu ft wet air) lb dry air
❒ Air flow
(cu ft wet air) min (lb wet air)
• Air leakage through cracks and holes = acfm × 60 ×d
min hr (cu ft wet air)
• Air leakage through conveyor openings
grains WV
• Intermittent door openings × (Wo − Wi ) (9)
lb dry air
• Building-to-building air infiltration
• Makeup air (cu ft wet air) min
= acfm × 60
In many cases, water vapor loads by air flow are a major min hr
(lb wet air) grains WV
contributor to the total building vapor load. In the research × 0.075 × (Wo − Wi ) (10)
(cu ft wet air) lb dry air
work for this article, I came across a number of approximate
equations that are used to calculate the water vapor load (grains WV) (cu ft wet air) grains WV
M = acfm × 4.5 × (Wo − Wi ) (11)
hr min lb dry air
*William Acker is a member of HPAC Engineering’s Editorial Advisory Where:
Board. W o = The higher moisture level of the air outside the
room that is entering with the air flow. It is an absolute hu- Equations (13) and (14). In this example, equations (13)
midity term. (ASHRAE calls this the Humidity Ratio.) and (14) produced water vapor loads that were 7.27 and
Wi = Moisture level of the air inside the room which in 12.63 percent above the exact equation (12) water vapor
this case is at a lower absolute humidity. (ASHRAE calls load. The error is a direct result of the assumed entering air
this the Humidity Ratio.) specific volume. Note that the makeup air specific volume
(lb wet air)
will vary with the entering air psychrometric properties.
d = Is the density of moist air entering the room Therefore, you cannot select a standard value for specific
(cu ft wet air)
volume and expect the equation to be exact. For this reason,
Equation (12) can be used for the same calculations. It is equations (13) and (14) are approximate equations. Equa-
an exact equation because the engineering units convert to tions (13) and (14), which can be found in many engineer-
grains of water vapor per hr. ing books and dehumidification manuals, will be fairly accu-
rate as long as the entering makeup air is close to the
(grains WV) (cu ft wet air) min 1
M = acfm × 60 × selected specific air volume.
hr min hr (cu ft wet air)
v
(lb dry air) (grains WV) (cu ft wet air) min
M = acfm × 60
grains WV hr min hr
× (Wo − Wi ) (12)
lb dry air lb dry air grains WV
× × (Wo − Wi ) (13)
(cu ft wet air) 14 cu ft wet air lb dry air
v Specific volume of the air flowing into the
=
(lb dry air) (grains WV) (cu ft wet air) min
room. This value can be found in psychro- M = acfm × 60
metric charts or calculated. When using the charts, the hr min hr
combined air barometric and static pressure should equal the lb grains WV
× 0.075 × (Wo − Wi ) (14)
total air pressure of the chart. cu ft lb dry air
Equations (11) and (12) are applied and compared in the (grains WV) (cu ft wet air) min
M = acfm × 60
example below to show how results from approximate and hr min hr
exact equations can vary under different conditions. Equa- 1 grains WV
× × (Wo − Wi ) (12)
tion (11), which is approximate, calculates a water vapor (cu ft wet air) lb dry air
v
load 20.18 percent over the exact equation (12). Equation (lb dry air)
(11) is more accurate if the entering air flow is close to 70 F.
Engineers preferring the exact equation will need a psychro- Example conditions:
metric chart to obtain the entering air specific volume, or a Inside room conditions
psychrometric computer program that can calculate the air Air pressure: 29.921 in. Hg
mixture properties. Dry bulb temperature: 70 F
Example conditions: Moisture level: 35 grains WV/lb dry air
Room conditions Relative humidity: 32.38 percent
Air pressure: 29.921 in. Hg Entering makeup air
Dry bulb temp: 70 F Air pressure: 29.921 in. Hg
Moisture level: 35 grains WV/lb dry air Dry bulb temperature: 100 F
Relative humidity: 32.38 percent Moisture level: 280 grains WV/lb dry air
Entering air flow conditions Relative humidity: 93.67 percent
Air pressure: 29.921 in. Hg Specific volume: 15.01722 cu ft wet air/lb dry air
Dry bulb temp: 120 F Air flow acfm: 2000 cu ft per min
Moisture level: 420 grains WV/lb dry air Example calculations:
Relative humidity: 76.44 percent 1
2000 cfm × 60 × × (280 − 35) = 2, 100, 000 grains WV per hr (13)
Specific volume: 16.02379 cu ft wet air/lb dry air 14
Air flow acfm: 200 cu ft per min 2000 cfm × 60 × 0.075 × (280 − 35) = 2, 205, 000 grains WV per hr (14)
Example calculations: 1
2000 cfm × 60 × × (280 − 35)
cu ft wet air grains WV 15.01722
200 × 4.5 × (420 − 35)
min lb dry air = 1, 957, 753 grains WV per hr (12)
grains WV
= 346, 500 (11) WATER VAPOR REMOVED BY DEHUMIDIFIERS
hr
cu ft wet air min lb dry air Dehumidification systems remove water vapor from the
200 × 60 ×
min hr 16.02379 cu ft wet air process air that travels through the unit. This section looks
grains WV grains WV at the equations used to determine the humidity ratio of the
× (420 − 35) = 288, 321 (12)
lb dry air hr process air entering and leaving the unit as well as equations
used to estimate the amount of water vapor removed when
WATER VAPOR LOAD FROM MAKEUP AIR the inlet and discharge humidity ratios and air flow are
Equation (12) can also be used to calculate the water va- known. Note that some of the equations are the same as the
por load from makeup air. Let’s compare it to approximate equations used in preceding sections. The equations listed as
60
HPAC
ENGINEERING
July 1999 • Heating/Piping/AirConditioning
TABLE 1 Into dehumidifier Dehumidifier discharge
Air pressure 29.921 in. Hg 29.921 in. Hg
Air temperature 200 F
lb dry air grains WV
× 0.075 × (Wo − Wi ) (16)
Relative humidity 50 percent dry std cu ft lb dry air
= 19, 493 × 60 × 0.075 × (2809 − 35)
Humidity ratio 280 grains WV 35 grains WV per lb dry air
per lb dry air = 243, 334, 670
Moist air density 0.051216 lb wet air Note: Uses the dehumidification industry dscfm flow entering
per cu ft wet air the dehumidifier.
Specific volume 27.3599 cu ft wet air (grains WV) (lb dry air) grains WV
per lb dry air M =M × (Wo − Wi ) (17)
hr hr lb dry air
acfm flow 40,000 cu ft wet air lb dry air
per min = 87,719.78 × (2809 − 35)
hr
Dry air mass flow 87,719.78 lb dry air per hr 87,719.78 lb dry air per hr = 243, 334, 670
Water vapor flow 35,197.64 lb water Note: This equation can be found in examples of the
vapor per hr ASHRAE Handbook of Fundamentals; in Modern Heating
and Ventilating Systems Design, by George E. Clifford; and
Fan industry scfm 27,315 std cu ft per min
in Fan Engineering, by Buffalo Forge.
Dehumidification 19,493 dry std cu ft
industry dscfm per min 19,493 dry std cu ft per min CONCLUSION
Many of the flow diagrams presented in articles, books,
approximate can be very accurate if the process air flow tem- engineering manuals, and proposals from dehumidification
perature is close to 70 F (Table 1). companies do not indicate the engineering units for the
In this series of equations and calculations, approximate flows in the diagrams. As indicated in this article, the flows
equations (15) and (11) produced water vapor removals that are illustrated in cfm or scfm with no explanation. In most
were 40 and 105 percent above the exact equations (16) and cases, the flows are in dry standard cubic feet per minute.
(17). The approximate equations can be fairly accurate if Over the years, I have been contacted by many engineers
the air entering the dehumidifier is close to 70 F. Engineers over the issue of calculated water vapor load variances from
that desire greater accuracy can use the psychrometric chart different equations. In most cases, the approximate equa-
to get the specific volume needed to make the conversion tions are equations that have been shortened to make the
from acfm to dscfm or purchase psychrometric programs that calculations easier for engineers. If you have any questions
can calculate the value for them. on your equations, check the engineering units to make sure
that they properly cancel out to grains of water vapor per hr,
(grains WV) (std cu ft air) min
M = scfm × 60 or lb of water vapor per hr. HPAC
hr min hr
lb wet air grains WV
× 0.075 × (Wo − Wi ) (15) BIBLIOGRAPHY
std cu ft air lb dry air
1) Acker, W., Water Vapor Migration and Condensation
= 27,314.98 × 60 × 0.075 × (2809 − 35)
Control in Buildings, HPAC Engineering, June 1998.
= 340, 972, 895 2) Acker, W., Industrial Dehumidification Water Vapor
Note: This equation uses the fan industry scfm flow entering Load Calculations and System Descriptions, HPAC Engineer-
the dehumidifier. The engineering units do not properly cancel ing, March 1999.
out on the right side of the equation. This is why the equation 3) Clifford, G. E., Modern Heating and Ventilating Systems
accuracy is listed as approximate. Design, Prentice Hall, Englewood Cliffs, N.J., 1992.
(grains WV) (cu ft wet air) min
4) Fan Engineering, 8th Ed., Edited by Robert Jorgensen,
M = acfm × 60 Buffalo Forge, Buffalo, N.Y., 1983.
hr min hr
lb wet air grains WV
5) 1997 ASHRAE Handbook: Fundamentals, American
× 0.075 × (Wo − Wi ) (10) Society of Heating, Refrigerating, and Air-Conditioning
cu ft std air lb dry air
(grains WV)
Engineers, Inc., Atlanta, Ga.
(cu ft wet air)
M = acfm × 4.5
hr min
The author would like to thank his wife, Sandra, for her patience and as-
grains WV
× (Wo − Wi ) (11) sistance during the preparation of these articles. He would also like to
lb dry air thank Nels Strand, the author’s mentor and close friend for over 20
= 40, 000 × 4.5 × (2809 − 35) years.
= 499, 320, 000
Mr. Acker has 25 years of experience in industrial HVAC. He has de-
Note: This equation appears in some dehumidification publica- veloped many computer programs, which include psychrometrics and
tions. Because the engineering units do not properly cancel out on the thermodynamics of air flows, water vapor permeation, and condensation
right side of the equation, it is considered an approximate equation. analysis of walls and roofs, ductwork heat loss and heat gain for air flow
and flue gas flow, and boiler efficiency and boiler emissions to mention a
(grains WV) (dry std cu ft) min few. Questions or comments about this article may be directed to the
M = dscfm × 60
hr min hr author at 920-465-3548.