Академический Документы
Профессиональный Документы
Культура Документы
http://www.zhwld.com
1
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
Foreword
1. Model description
The structural type of the MMPR-610Hb series protection is Hb. MMPR-610Hb
2. Standards referenced
General specification for static protection, security and automatic
equipment, DL 478-2001
Technical code for relaying protection and security automatic equipment
GB/T 14285-2006
Protective relay and automatic equipment design rules of power equipment
GB50062-92
3. Caution
Negative sequence voltage involved in this series of protection is combined with
phase voltage, all of low voltage component depend on line voltage in compound
voltage block, if one of the three line voltages is lower than low voltage setting, low
voltage component will operates and unblock over current protection.
There are 4 standard curves of inverse protection involved in this series of protection,
if the fault current is higher than 15 times of rated current, the inverse protection
component as if the current is 15 times of rated current.
The appearance should be inspected before power is applied, to ensure that the
panel is OK without scratch, the screws are tightened, the device is grounded firmly,
all screws of plug-ins are tightened and in good contact.
When power is applied, the “Run” indicator on the panel should flash, digital tube
displays primary measuring result in cycle, protection and measuring data are
displayed on the lcd in cycle.
The terminal D25~D28 are measuring circuit of 4~20mA DC signal, when testing,
signal should be supplied by special equipment, direct apply signal of relay protection
tester is prohibited(Can be selected or not).
2
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
When the device is equipped with ungrounded system, terminal D07,D08 are zero
sequence small current input terminal, the ac current input should be limited to within
2A, the measuring current input should be limited to 6A, pay attention to the signal
input when testing to avoid large signal applied so as to avoid damage to
components.
Operating circuit inside the device is only applicable to DC power supply, if AC power
is used, it should be applied with rectifier and filter.
It is prohibited to plug or unplug the plug-ins, in order to avoid damage to the device.
It is prohibited to do digital output test when the device is running with primary
equipments.
1.
.. Product
........description
..........
1.1 Scope of application
The MMPR-610Hb microcomputer motor protection applies to the protection and
monitoring of medium and high-voltage motors with voltage ratings of 3kV~10kV. It can be
used for the integrated protection of large and medium motors of different capacities, and
also for the dual configuration of main protection and backup protection of ultra-large
motors.
3
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
4
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
Power consumption
DC circuit: <10W(normal operation);<15W(protection operation).
AC voltage circuit:<0.5VA/ phase
AC current circuit:<1VA/ phase(In=5A);<0.5VA/ phase(In=1A).
Overload capability
AC voltage circuit: 1.2Un, continuous operation
Current measuring circuit: 1.2Un, continuous operation
Protective current circuit: 2In, continuous operation
10In, allowing 10s
40In, allowing 1s
5
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
Measuring accuracy
AC current: Class 0.2
AC voltage: Class 0.2
4~20mA DC quantity input: ≤±1%
Power: Class 0.5
Integral energy: Class 1 (active), Class 2 (reactive)
Frequency: ≤±0.02Hz
SOE resolution: ≤2ms
Impulse width of impulse quantity: ≥10ms
4~20mA DC quantity output: ≤±1%
Environmental conditions
Ambient temperature:
Operating:-20℃~+55℃。
Storage:-25℃~+70℃, rainproof and snow-proof rooms with relative humidity not
greater than 80%, ambient air free of acid, alkaline or other corrosive and explosive gas;
no excitation quality is applied at the limits, the device shall not have any irreversible
change; after temperature restoration, the device shall operate properly.
Relative humidity: The average relative humidity of the most humid month shall not
be greater than 90%, the average minimum temperature of this month not lower than 25℃
and there shall be no surface condensation; at the highest temperature of +40℃, the
average maximum humidity shall not exceed 50%.
6
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
7
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
2.
.. Function
.........of.device
......
2.1 Prolonged start time protection(Start Time Over)
When the maximum phase current of the motor rises from zero to above 10% of Ie (Ie is
the motor’s rated current, the same below), the device begins to time, until the current drops to
120% of Ie, this time is known as the motor’s start time (as Tstart). When the start time Tstart
exceeds setting value of the motor’s start time, the protection will operate on the trip. After the
end of starting, the motor’s prolonged start time protection will be switched off. During the
motor’s starting process, the mark “motor starting” is displayed in the lowest line on the LCD.
The value of current Ia can be seen in the report during 30s of motor’s starting.
The motor starting process is shown in Figure 2-1
120%
Ie
120%
Ie
10%
10%
Tstart Tstart
8
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
Instantaneous
Ia≥Instantaneous
protection on/off
≥ Protection output
Ib≥Instantaneous T
sequence
Ic≥Instantaneous
Figure 2-3 Operation logic diagram of negative sequence definite time limit over-current
protection
To avoid any protection mis-operation arising from the asynchronism of the 3 phases
upon closing of the circuit breaker, the set delay should not be less than 0.2s.
As stipulated by the IEC (IEC255-4), the following 4 standard characteristic equations of
the inverse time limit component are usually used:
0.14
t= τp
General inverse time limit: ( I / I p ) 0.02 − 1 (1)
13.5
Unusual inverse time limit: t= τp (2)
(I / I p ) −1
80
Extreme inverse time limit: t= τp (3)
(I / I p )2 −1
120
Long inverse time limit: t= τp (4)
(I / I p ) −1
Where: Ip is the setting value of the negative sequence inverse time limit over-current
starting current; τp is the negative sequence inverse time limit over-current time constant,
9
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
within the range of 0~1s; the inverse time limit characteristic can be selected by the setting
value of the negative sequence inverse time limit over-current curve (1: general inverse time
limit; 2: unusual inverse time limit; 3: extreme inverse time limit; 4: long inverse time limit).
Zero-sequence
over-current on/off
I0>zero-sequence Protection output
T
settings sequence
L Note: When the overload trip is switched on, the overload alarm is switched off
automatically.
Ia1>overload settings
Ib1>overload settings Overload
≥ protection on/off
Ic1>overload settings Protection output
& T
sequence
After motor’s start
10
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
τ1
t=
K1 ( I1 / I e ) + K 2 ( I 2 / I e ) 2 − 1.05 2
2
Underload
Motor’s start over
on/off
Circuit breaker at closed position
& T
Protection
Ia≤Underload settings
output
&
Ib≤Underload settings
Ic≤Underload settings
11
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
and reaches the setting delay, the protection operates on the trip. The protection is via
switch position block and PT failure block. The operation logic diagram of protection is
shown in Figure 2-7.
Umax<Uddy
&
Under-voltage
protection on/off T Protection output
PT failure block &
PT failure sequence
To avoid any potential protection mis-operation arising from closing of the circuit breaker,
the set delay should not be less than 0.2s.
2.8.2 Over-voltage protection(Overvoltage PROT)
When any line voltage of the bus is greater than the over-voltage protection setting value,
the setting delay is reached; the over-voltage protection will operate on trip. The protection is
blocked at switch position. The operation logic diagram of the over-voltage protection is shown
in Figure 2-8.
Circuit breaker at
closed position
Over-voltage on/off
/ T Protection output
& sequence
Umax〉
Ugdy
12
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
Max{Ia,Ib,Ic}<Igfh
MaxU<30V
&
Max{Ia,Ib,Ic}>0.1*Ie
≥
U2>8V PT failure on/off
& &
PT failure component
V-V wiring
• • • ≥
| U a + U b + U c |> 7V
|MaxU-MinU|>18V &
MaxU<7V MaxU=Max(Uab,Ubc,Uca)
Max{Ia,Ib,Ic}>0.1*Ie & MinU=Min(Uab,Ubc,Uca)
13
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
0.1Ie). In case of CT failure in any phase, the sum of the 3 phase currents is not zero (greater
than 0.1Ie). To differentiate from ground fault, the following judgment is required:
①In the 3 phase currents, the current value of the phase with the minimum current is zero (less
than 0.1Ie).
②The value of the phase with the maximum current is not zero (greater than 0.1Ie), and its
current value is less than the setting value of the overload current.
¾ Protection CT 2-phase wiring
The current of one phase is greater than 0.15Ie and less than the setting value of overload
current , and current of another phase is less than 0.08 Ie, then, it is judged as CT failure.
60 f
Namely, n= (r / min)
P
14
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
The judgment criterion of the synchronous motor out-of-step protection is the protection
current relative to the setting value IDZ.
When the circuit breaker is closed, out-of-step occurs and the out-of-step protection
setting delay is reached, the out-of-step operation will operate on the trip. In case of the current
disappears, the out-of-step protection will return.
IDZ
For the positive or negative rotate motor, the protection device provides positive and
After the normal-reverse function switched on, the device judges motor’s
15
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
on-the-spot phase changing. The device can automatically adjust the calculation of
negative sequence current and power to adapt the motor’s normal-reverse.(Note: When
the motor is at phase changing state, the motor should be off. It is regarded as the motor
The device has soft starting function, which is suitable for the self-starting control of
Circuit breaker
closure
&
QF2 open
QF2 closure
Pattern 1 r e t u r n
successfully
&
Current < Irqdset &
&
Former current >
Irqdset
Send command of
Soft start closing B29-B30
Start time on/off QF2
outputs,return
failure,
after 500ms, check
QF trip
QF2 position after
Pattern 2 3s.
Start time
During motor’s start process, record the effective value of protection current Ia1 for
reference of analysis of motor’s start process. The device records 150 effective values of
protection current Ia1, which is at intervals to record for 200ms. It can be looked up in the
report menu.
2.18 Impulse energy/integral energy
¾ Impulse energy(Can be selected or not)
The impulse circuit of the device uses an internal power supply; passive energy impulses
are input from the outside; and accumulation of impulse energy is finished by the software.
¾ Integral energy
The software accumulates active and reactive powers into active and reactive energy in
16
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
real time.
2.19 Fault recorder(Wave Record)
See the communication coding table for the protection voltage and current waveform data
collected by the recording unit.
3.
.. Setting of parameters and setting values of the device
3.1 System parameters
Parameter Range Description
Settings of setting value zone number
Setting value zone
number(Setting Zone 0-7 Set step:1(factory default 0)
No.)
Communication settings
RS485
address(RS485 1-99 Set step:1(factory default 1)
Address)
Set step:1(factory default 1)
RS485 baud
0-5 0:2.4KB;1:4.8KB;2:9.6KB;3:19.2KB;4:
rate(RS485 Baudrate)
38.4KB;5:115.2KB;
Pulse confirmation
1-1000ms Set step:1(factory default 1)
time(Pulse Input Time)
17
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
00:Ungrounded
Neutral point
01:Major grounding
grounding mode(Earth 0-1
(It is provided in the unground method if there is no
Mode)
special instruction.)
Out-of-step
0.50-100.00s Set step:0.01s(factory default 10s)
cycle(Out-Of-Step CY)
FC block delay(FC Block
0-5000ms Set step:1 ms (factory default 200ms)
Delay)
DA1~2 adjustment
0.5-1.5 Adjust D/A channel 1~2(4-20mA)parameters
factor
Pulse energy setting
Pulse 1 0-4294967295
Set step: 1
Pulse 2 0-4294967295
Press “confirm” for reservation, and revert to last
Pulse 3 0-4294967295
menu.
Pulse 4 0-4294967295
18
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
Channel data 1~12 0.5-5 Channel data 1-12 are corresponded to the
channel factor of analog quantity 1-12.
Channel data 13~14 0.5-5 Channel data 13,14 are corresponded to channel
factor of DC quantity 1,2.
19
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
20
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
21
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
22
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
Overload protection(Overload)
Overload current(Overload
(0.1-20)In Set step:0.01A(factory default 20In)
Current)
Overload delay(Overload
0.00-100.00s Set step:0.01s(factory default 100s)
Time)
Overheat protection(Motor Over Heat)
Heating time
1.0-1000.0s Set step:0.1s(factory default 100s)
constant(Heating T)
Radiating time
0.10-10.00 Set step:0.01(factory default 10)
constant(Diffusion T)
K1 0-1 Set step:0.01(factory default 1)
K2 0-10 Set step:0.01s(factory default 6)
Overheat alarm
50.00-100.00% Set step:0.01%( factory default 80%)
coefficient(Alarm Coeff.)
23
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
24
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
25
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
4.
.. Description
............of.binary
.......input,
.....output
..
....and analog
..........quantity
.......
4.1 Monitoring of analog quantities
Analog quantities can be monitored under the [Protection Data Display], [Measured Data
Display] and [Impulse Energy] menus in the [State Display] menu, press the “i“, “j“ keys to
flip over. The factory precision of the device has been calibrated. The protection current is
calibrated at double the rated current and the measuring current at a single rated current. The
list is as follows:
L Note: for protection CT 3-phase, PT Y-Y wiring; due to the under-frequency unloading
protection of this device, the frequency display is put in the protection data.
Analog quantity
Analog quantity name Test method
terminal
Protective Phase A Add double the rating, displayed deviation
Terminals D01,D02
current (Ia) not exceeding 1%
26
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
Analog quantity
Analog quantity name Test method
terminal
exceeding 3%
Terminals D09、D10;
voltage by polarity
Terminals D09,D10;
voltage by polarity
C16(common terminal of Impulse 1(MC1) Connect each point once, add 1 to the count
impulse +24V)
C16(common terminal of Impulse 2(MC2) Connect each point once, add 1 to the count
impulse +24V)
C16(common terminal of Impulse 3(MC3) Connect each point once, add 1 to the count
impulse +24V)
C16(common terminal of Impulse 4(MC4) Connect each point once, add 1 to the count
impulse +24V)
27
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
28
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
to flip over.
Binary output terminals Binary output name Test method
B15-B16 Device Failure
B17-B18 Trip Signal
B19-B20 Alarm Signal
B21-B22 Output 4
B23-B24 Output 5
B25-B26 PROT Output 1
B27-B28 PROT Output 2 Select open and close menu, use “+”,
“-” key to operate and test the
B29-B30 Softstart Output
corresponding terminals. B31-B32
B31-B32(Common
and B34-B35 are common open
open) Output 9
terminals that should close.
B32-B33
B34-B35(Common
open) Output 10
B35-B36
A22-A23 Remote Close
A22-A24 Remote Trip
29
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
5.
.. Operation
..........instructions
...........
5.1 Control panel of device
128*64 matrix LCD (The LCD will go off after a period of absence of keyboard operation;
the LCD will be illuminated automatically when any key is pressed or in case of
protection trip or alarm.)
Signal indicator: operation, communication, operation, alarm, reclosure, fault (of the
device)
Circuit breaker state indication: indicating the current state of the circuit breaker (“Open”,
“Close” position indication)
Remote/local selection signal, local opening/closing button
Key pad: ¿, À, ½, ¾, Cancel, -, +, Enter, Revert
The 6-bit nixie tube displays the primary measured values in real time: IA, IB, IC, Uab,
Ubc, Uca, P, Q, Cosφ. (Please set the PT, CT transformation ratios properly in the System
Parameters menu). The maximum display range of the power on the nixie tube is: 99999.
L Note: Measurement IA: AA, measurement IB: bA, measurement
IC: CA, voltage Uab: AbkV, voltage Ubc: bCkV,
voltage Uca: CAkV, active power: PkW, reactive power:
qkvar, power factor: H
5.2 Instructions for use of key pad and LCD display
During the device’s normal operation, it will display the measuring current, voltage,
power, time and operation state of motor (indicating motor’s normal-reverse) in cycle.
Press the “Enter” key to enter the main menu, which is a multi-level tree menu. Press the
30
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
“i“, “j“ keys to move the cursor to the desired entry, press the “Enter” key to enter this
entry, and press the “Cancel” key to return to the next higher level of screen. If this screen
is still a menu, continue to press the “i“, “j“ key to select the desired entry, press the
“Enter” key to enter the next level of screen, and press the “Cancel” key to return to the
next higher level of menu. If there is no menu screen, be sure to press the “Cancel” key to
return to the next higher level of menu. The main menu is shown at the center of the
The main interface displays the primary operating parameters in turn. The maximum
displayed value of the primary is 6000.0A. For systems with a rated current of 5A, the set
CT transformation ratio shall not exceed 2000. If the primary power is greater than
1000kW, the display unit is MW, otherwise is kW.
LNote 1:Only the motor’s protective and monitoring device has this item.
LNote 2:The system parameters such as basic parameters, output matrix and D/A
settings are variable with the different devices. See the device description.
LNote 3:The setting menu is shown in the device description.
z State Display
The [State Display] menu contains 8 submenus, including protection data, measuring
data, binary input, impulse energy, angle display, harmonic data, DC measurement and
trip statistics. It is described as follows:
1.1Protection data ↑ ↓
Ia=□□□.□□A Protection current
Ib=□□□.□□A Bus line voltage
Ic=□□□.□□A Positive sequence current of protection
Uab=□□□.□□V Negative sequence current of protection
Ubc=□□□.□□V Zero sequence current of high-voltage side
Uca=□□□.□□V (analog)
I1=□□□.□□A Positive sequence voltage
I2=□□□.□□A Negative sequence voltage
I0=□□. □□□A Zero sequence voltage(analog)
U1=□□□.□□V Reverse power
U2=□□□.□□V Frequency
U0=□□□.□□V Zero sequence current(calculation value)
Pn=□□□□.□W Zero sequence voltage(calculation value)
F=□□□.□□Hz
I0js=□□□.□□A
U0js=□□□.□□V
32
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
L Note: In the standard configurations, the input circuit has the connection to an
external 220VDC control power supply. When no DC control power supply or control
system is available on site, but a 110VDC control power supply is available, a 110VDC
control power supply may be used for direct connection through local hardware
adjustment, or the 24V power supply of the device may be used as the input power supply
(when the input common terminal is +24V, terminal number: B14, Terminal B01 is kept
float). However, this must be specified upon ordering.
Pulse Energy ↑↓
MC1:□□□□□□□□□□
MC2:□□□□□□□□□□
Externalimpulseenergy inputcounting(4-way)
MC3:□□□□□□□□□□
MC4:□□□□□□□□□□
+□□□□□□□·□□□kWh
Accumulation of the device’s real-time active and reactive calculations
+□□□□□□□·□□□kvh
overtime,+forpositivedirection,-fornegativedirection
-□□□□□□□·□□□kWh
-□□□□□□□·□□□kvh
Phase Angle↑ ↓
Phaseanglerelativeto Ua,Uaas0° by default.Whenwiring methodis
Ua: 0 0 0 ·0 0°
VV,itdisplayslinevoltagesrelativeto Uab,the same as follows
Ub:□□□·□□°
Uc:□□□·□□°
Ia:□□□·□□°
Ib:□□□·□□° Phaseangleof protectioncurrentrelativetoUa
Ic:□□□·□□°
IA:□□□·□□°
IB:□□□·□□° Phaseangleof measuringcurrentrelativetoUa
IC:□□□·□□°
33
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
Harmonic↑ ↓
I2: □□□·□□%
I3: □□□·□□%
I4: □□□·□□%
2~11stharmonicsfor whichanalogchannelshavebeenselectedin system
I5: □□□·□□%
。。。。
。。
I11: □□□·□□%
DC Input
DC1:□□□·□□mA
ExternalDCinput 4~20mA(2-way)
DC2:□□□·□□mA
Trip statistics
Total: □□□□ times
z Signal revert
In the [Signal Revert] menu, press the “Enter” key, the signal relay and the “Operation”
indicator on the panel will be reset.
z Report Display
The [Report Display] menu includes 4 submenus, including trip report, remote signal
report, event report and clear report. Event recording includes: device self-check fault,
device setting value modification, system parameter modification and setting zone
number modification, etc. Trip report can be recorded for the last 50 events, remote signal
report for 100, event report for 30 at most. Beyond this, the latest report will overwrite the
earliest one. Press the “Enter” key to enter the corresponding [To view xx report, please
enter report number: 00 ] menu, and enter any figure within storage volume, press the
“Enter” key to display the contents of that report. The screen is as follows:
Press À key to see the specific operation value. Press ¿ and À keys to flip over.
Operation values
34
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
Ia = □□□·□□ A
Ib = □□□·□□ A Protection current
Ic = □□□·□□ A
Uab = □□□·□□ V
Ubc = □□□·□□ V Bus line voltage
Uca = □□□·□□ V
I1 = □□□·□□ A Positive sequence, negative sequence, zero sequence of
z Output test
After entering the [Output Test] menu, the correct password is required to enter the
[Output Test] menu. It displays the following:
4.Output test ↑ ↓
Device Failure
Trip Signal
Device Failure
Alarm signal
Press “Enter” key
Output 4
Output 5 ——————> On Off
PROT Output 1
<——————
PROT Output 2
Softstart Output Press “Cancel” key
Output 9
Output 10
(Note: After signal relay closed, press the “Revert ” key or enter the【Signal revert】
menu, press “Enter” to make the signal relay reverted. When the test is performed on
the 6 protection outputs, the starting relay will be in the “Closed” state automatically.
The “+”, “-” keys are used for switching between the “Close/Open” control.)
35
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
z System parameters
After entering the [System Parameters] menu, the correct password is required to
enter the [System Parameters] menu. It displays the following:
5.Parameters↑ ↓
Setting Zone No.
Comm. Setting
B.Parameters
D/A Setting
Pulse Energy
Trip Times Clear
Com. Setting ↑ ↓
RS485 Address
Communication address of device 01~99
□□
RS485 Baudrate
□□ 00:2.4KB;01:4.8KB;02:9.6KB;03:19.2KB;
Pulse Input Time 04:38.4KB;05:115.2KB
□□□□ms Confirmation time of 4-way impulse energy,
IP Address >10ms, < impulse width of kilowatt-hour meter
□□□. □□□. □□□. □□□
Subnet Mask
□□□. □□□. □□□. □□□ For Ethernet communication
KW Default
□□□. □□□. □□□. □□□
36
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
¾ Setting of basic parameters (see the description of the protection device for basic
parameters)
B.Parameters
Rating Current
□□ Setting the CT secondary current rating 00:
PT Ratio 1A;01:5A
□□□ Setting the PT transformation ratio 1~1500
CT Ratio
□□□ Setting the CT transformation ratio 1~5000
CT Wiring Mode
□□
Setting the CT secondary wiring mode 00:
PT Wiring Mode
3-phase;01:2-phase
□□
Setting the PT secondary wiring mode 00:YY;
Harmonic Channel 01:VV
□□ Setting analog quantity channels 0~12 for
。。
。。。。 harmonic monitoring, select 0 to exit from the
harmonic calculation function.
¾ D/A setting
The device has two 4~20mA outputs. The DA1~DA2 adjustment factor is used to
adjust the accuracy of the channel output. The DA1~DA2 channel selection is used to
select the corresponding analog quantity channel (see the description of the protection
device for specific reference quantities). In the accuracy test, make sure the field ground
is in good contact; otherwise the accuracy might be affected.
¾ Impulse energy setting
Energy base numbers can be set, including Impulse 1, Impulse 2, Impulse 3, Impulse
4, positive active energy, positive reactive energy, negative active energy and negative
reactive energy.
¾ Clear trip count
It is used to clear the trip count.
z Settings
After entering the password, you can enter the [Settings] menu. See the settings
description of the protection device for the detailed description.
z Clock setting
A battery-back real-time clock is provided in the device, which can perform time
adjust remotely via the communication network or in-site time adjust in the [Time Setting]
menu.
37
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
7. Clock setting
Date:20□□-□□-□□
Time: □□:□□:□□
Enter this menu and press the “Enter” key, the clock will stop refreshing and a cursor will appear. Move the
cursor to the desired position for modification by pressing the “½“, “¾“ keys, modify to the desired value with
the “+”, “-” keys. Press the “Enter” key to complete setting. If the “Cancel” key is pressed, the setting will be
z Password
The [Password] menu is used to modify the password for entry into the Settings,
System parameters and Output Test submenus. The initial password is provided by the
factory. The universal password is “1000”.
Input Password Move the cursor to the desired position for modification by
pressing the “½“, “¾“ keys, modify to the desired password with
0 0 0 0 the “+”, “-” keys. Press the “Enter” key to enter the new password
setting menu as above; press the “Cancel” key to cancel the setting.
38
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
6.
.. Check
......of.protection
...........function
.......
6.1 Check of prolonged start time protection(Start Time Over)
Wire as Figure 6-1, switch on the prolonged start time protection. Set motor’s rated
current and starting time according to motor’s nameplate parameters or real measuring
value. The current (>1.2Ie)is input, when the motor’s starting time is exceeded, the
protection will operate. The terminals B17-B18, B25-B26, B27-B28 should be shorted.
MMPR-610Hb
Ia D01
A01
Ib D03
Power supply
Ic D05
A02
Ia’(Ib’,Ic’) D02(D04,D06)
Figure 6-1
6.2 Check of 2-section over-current protection(Overcurrent)
Wire as Figure 6-1, switch on instantaneous over-current protection. The current 1 of
instantaneous over-current (at starting) and current 2 of instantaneous over-current (after
starting) are be set separately. If the fault current is input at starting time or after starting time,
the protection will operate. The terminals B17-B18, B25-B26, B27-B28 should be shorted.
Switch on FC block alarm, 50ms is added up to instantaneous over-current protection delay at
this moment. When the fault current exceeds FC breaking current, (the current setting value
should be greater than over-current setting value), FC block instantaneous over-current
protection will operate. Locked time can be set in the system parameters.
Locked rotor protection is provided after starting, which checking way is the same as
instantaneous over-current after starting.
Setting value of
instantaneous 1.2 Ie 2 Ie 5 Ie 10 Ie
over-current (A)
Instantaneous 10 5 2 1
over-current
delay (s)
Current 1 of
instantaneous
over-current
( at starting
time)(A)
39
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
Current 2 of
instantaneous
over-current
( after starting
time) (A)
Instantaneous
over-current
time (s)
6.3 Check of negative sequence over-current protection(NS Overcurrent)
Negative sequence current is derived from protection current calculation. Wire as
Figure 6-1.
6.3.1 Negative sequence over-current definite time limit(NS OC DT)
Switch on negative sequence over-current definite time limit protection, inputting
currents of 3-phase in negative sequence mode. See the following table and set,
measuring operation current value for record.
Setting value of negative
0.2 Ie 0.4 Ie 0.6 Ie 0.8 Ie
sequence current (A)
Negative sequence
10 5 2 1
current delay (s)
Negative sequence
current operation value
(A)
Negative sequence
current operation time (s)
6.3.2 Negative sequence over-current inverse time limit(NS OC IT)
Switch on negative sequence over-current inverse time limit, select one curve in
inverse time limit modes(01:Standard inverse time limit;02:Unusual inverse time limit;
03:Extreme inverse time limit;04:Long inverse time limit), the time constant Tp of inverse
time limit is set as 0.50s and the current Ip of inverse time limit is set as 5A. See the
following table and set. When over-current inverse time limit protection operates, the
measuring terminals B17-18, B25-26, B27-B28 should be shorted.
40
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
Ip=5A,τp=0.5s Actual
operation time
02:Unusual Reference 6.750s 3.375s 1.688s
inverse time limit operation time
Ip=5A,τp=0.5s Actual
operation time
03:Extreme Reference 13.333s 5.000s 1.667s
inverse time limit operation time
Ip=5A,τp=0.5s Actual
operation time
04:Long inverse Reference 60.000s 30.000s 15.000s
time limit operation time
Ip=5A,τp=0.5s Actual
operation time
MMPR-610Hb
I0 D07
A01
Power supply
A02
I0’ D08
Figure 6-2
See the following table and set, measuring the operation current value for record. If
the zero sequence over-current protection operates, the measuring terminals B17-18,
B25-26, B27-B28 should be shorted. If zero sequence over-current alarm is provided, the
measuring terminals B19-B20 should be shorted.
Setting value of zero
0.20 0.50 1.00 1.50
sequence current A)
Setting value of zero
5 3 2 1
sequence current delay
41
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
(s)
Operation value (A)
Operation time(s)
100
1000
42
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
than the setting value of underload, the underload protection will operate. The underload
protection can be switched On/Off on alarm or trip. When it operates on the trip, the
measuring terminals B17-B18, B25-26, B27-B28 should be shorted; When it operates on
the alarm, the measuring terminals B19-B20 should be shorted.
MMPR-610Hb
Ia(Ib,Ic) D01(D03,D05)
A01
Ia’(Ib’,Ic’) D02(D04,D06)
Power supply
B01
A02
Auxiliary contact of breaker
B02
Figure 6-3
6.8 Check of voltage protection(Voltage PROT)
6.8.1 Check of under-voltage protection(Undervoltage PRO)
Under-voltage protection uses the maximum line voltage for judgment. In case of PT
failure, the under-voltage protection will be blocked. Wire as Figure 6-4, and switch on
under-voltage protection, PT failure and PT failure block are switched on.
MMPR-610Hb
Ua(Ub,Uc) D15(D17,D19)
A01
Ua’(Ub’,Uc’) D16(D18,D20)
Power supply
B01
A02
Auxiliary contact of breaker
B02
Figure 6-4
See the following table and set, measuring the operation voltage value for record.
When the under-voltage operates, the measuring terminals B17-B18, B25-B26, B27-B28
should be shorted. When PT failure occurs, the under-voltage will be blocked.
Setting value of
95 90 85 80
under-voltage (V)
Under-voltage delay
10 5 2 1
(s)
43
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
Operation value of
under-voltage (V)
Operation time of
under-voltage (s)
6.8.2 Check of over-voltage protection(Overvoltage PROT)
Over-voltage protection uses the maximum line voltage for judgment. Wire as Figure
6-4, and switch on the under-voltage protection.
See the following table and set, measuring the operation voltage value for record.
When the over-voltage operates, the measuring terminals B17-B18, B25-B26, B27-B28
should be shorted.
Setting value of
105 110 115 120
over-voltage (V)
Over-voltage delay
10 5 2 1
(s)
Over-voltage
operation value (V)
Over-voltage
operation time (s)
6.9 Check of logic control protection(Joint Trip PROT)
Switch on all the logic control protection, the delay is set as 0s.
Terminal B01 is connected to negative pole of DC220V, and terminals B07, B08, B09, B10
is connected to the positive pole of DC220V separately, then the logic control protection
will operate separately. The measuring terminals B17-18, B25-26, B27-28 should be
shorted.
6.10 Check of non-electric quantity protection(Non-electric)
Wire as Figure 6-5, and switch on non-electric quantity protection. Take non-electric
quantity 1 protection for example.
MMPR-610Hb
Power supply
Figure 6-5
44
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
See the following table and set, measuring the DC operation value and keep a
record in the table. When the protection operates, the measuring terminals B17-18,
B25-26, B27-28 should be shorted.
Setting value of
non-electric quantity 1 5 10 15 18
(mA)
Non-electric quantity 1
10 5 2 1
delay (s)
Non-electric quantity 1
operation value (mA)
Non-electric quantity 1
operation time (s)
45
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
MMPR-610Hb
Ia D01
A01
Ia’ D02
Power supply
Ua(Ub) D15(D18)
A02
Ua’(Ub’) D16(D17)
Figure 6-6
See the following table and set, measuring the operation value for record. When the
under-frequency unloading protection operates, the measuring terminals B17-18,
B25-B26, B27-B28 should be shorted.
Setting value of
49.5 49 48.5 48
under-frequency (Hz)
Setting value of
0.5 0.5 1 1
under-current (A)
Setting value of
10 20 30 60
under-voltage (V)
Setting value of slip
3 4 5 7
block (Hz/s)
46
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
Setting value of
under-frequency operation 0.5 1 2 3
delay (s)
Operation value of
under-frequency (Hz)
Operation time of
under-frequency (s)
Slip block value
(Hz/s)
47
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
QF
High-voltage
resistor or QF2
reactor
Figure 6-7
48
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
Net1
D01 Ia Ia' D02
B02
B03 D03 Ib Ib' D04
B04
Net2
B05
ON
D05 Ic Ic' D06
B06
B07 D07 I0 I0' D08
COM1
OFF B08
B09 COM2 D09 IA IA' D10
B10
Run
B11 QF2 Node D11 IB IB' D12
B12
Debug
D13 IC IC' D14
A01 B13 Input 12
49
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
reaker
b Circuit
Ua Ua' Ub Ub' Uc Uc' U0 U0' Ia Ia' Ib Ib' Ic Ic1' I0 I0' IA IA' IB IB' IC IC'
AC plug-in
DCSIn1-
DCSIn2+
DCSIn2-
M
M
P
R
-
6
1
0
H
b
Ethernet port
Net1
microcomputer motor protection monitoring device
Power supply+
Ethernet port
Net2 Power supply-
Shielded ground
Debugging port
Shielded ground
Power off
1 Operating
circuit
Power plug-in unit
1 failure
CPU plug-in unit
1
Trip
I/O plug-in unit
1 position
Shielded ground
Closing
2 position
Output contact 10
Output contact 10
Output contact 10
PROT Output 2
PROT Output 1
PROT Output 2
Output contact 9
Alarm signal
Output contact 9
PROT Output 1
Output contact 9
Alarm signal
normally closed
normally closed
common terminal
common terminal
2 Closing position
normally open
normally open
Softstart
monitoring
Softstart
Output 4
Output 5
Output 4
Output 5
2 Trip coil
Output
Output
Trip position
2
Positive active pulse monitoring
Pulse 1( ) Closing coil
Positive reactive
pulse Pulse 2( 2) -
Negative active pulse
Remote control
Pulse 3( )
Negative reactive common terminal
pulse Remote control
Pulse 4( 4)
closure
Pulse common +24V Manual closure
Device Failure
Device Failure
Nor.Rev.Func.
Joint Trip 4
Joint Trip 3
Earth Switch
Joint Trip 2
input
Trolley Test
Input common
Trolley Run
Trip Signal
Trip Signal
Device panel+
terminal-
QF2 Node
DCS1+
(24V+)
Input 12
Breaker
Spring
Remote control
DCS1- trip
DCS2+ Manual trip input
DCS2- +
Note:
1.As shown in the figure, ZK(remote/local changeover switch)and KK(manual operating switch)are installed on
the panel,when remote/local changeover switch and manual operating switch of device panel are used,terminal A21 is
connected to + WC.
2.As shown in the figure,PT secondary is wye-connected,when it is in V-V wiring,terminals D15,D20 are connected
to phase A of PT secondary,terminals D16,D17 to phase B of PT secondary,terminals D18,D19 to phase C of PT
secondary.
device
50
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
Traditional operating circuits are started by current, while a voltage maintaining circuit
realizes electric trip prevention. An anti-trip relay will be selected depending on the current
of the trip/closing circuit of the circuit breaker. However, this has poor generality and can
hardly be realized for circuit breakers with low trip and closing currents (such as 10kV
circuit breakers from AEG Company in Germany, whose trip and closing currents are not
greater than 0.2A). To simplify wiring and design finalization, and to improve the generality
Small bus
Fuse
SHJ DL HQ
TBJ1 HBJ
A20 A16
HBJ TBJ2
TCJ1 TBJ
Closing circuit
1LP
Tn3
Jn
Tn4
ZK KK SHJ
2 4 5 8 A15
A24
ZK YHJ A19
1 3 A22
YTJ
A23
ZK KK STJ
6 8 6 7 A17
Trip circuit
Tn1
Jn
2LP
Tn2
TCJ2
DL
STJ TQ
TCJ
A20 A18
HWJ
A13
TWJ DL
A14
HWJ
A11 A12
TWJ
A09 A10
HWJ TWJ
A07 A08
operations, ZK is a changeover switch, used for changeover of local and remote control.
When ZK is at the “Remote” position, the power of the remote control circuit will be
switched on, i.e., Terminal A22 of the device is connected to +KM, and the power of the
manual operating circuit is cut off, disabling manual closing and manual trip. On the
contrary, when ZK is at the “Local” position, the power of the manual operating circuit is
51
User’s manual of MMPR-610Hb microcomputer motor protection and monitoring device
WLD[K]-JY-222-2010
L Note: The dotted line outlines the internal circuit of the protection device. All our
devices marked with “anti-trip circuit” are designed on this operating circuit.
Terminals Tn1, Tn2 corresponding to the protection relay Jn are determined by the
corresponding protection output control word. Jn can be any one or more of Protection
outputs 1-8.
Whether local or remote control, the precondition to jump is Terminal A15 of the device is
always connected to +WC. After manual or remote controlled closing, if a short-circuit fault
occurs, the protection will operate to trip the circuit breaker. Though Terminal A15 of the
device is connected to +WC, the closing circuit is disconnected by TBJ1 and will not be closed
52