DESIGN & CONSTRUCTION

MANAGEMENT:

Drawings for:
a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000
a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484

1 GENERAL NOTES 2 GENERAL CONTRACTOR NOTES


A. 'DOCUMENTS', AS USED HEREIN, SHALL COMPRISE THE ENTIRE INTEGRATED SET OF ALL WRITTEN INSTRUMENTS RELATED 1. BUILDING PERMIT AND CERTIFICATE OF OCCUPANCY:
TO THE PROJECT, INCLUSIVE OF, BUT NOT EXCLUSIVE TO, ALL CONTRACTS, SUBCONTRACTS, DRAWINGS, SKETCHES,
MEMORANDA, ADDENDA, SPECIFICATIONS, MANUALS, POLICIES, RULES AND REGULATIONS, LANDLORD DESIGN CRITERIA,
A. THE GC SHALL CONTACT THE NEXTORE P.M. OR THE PERMIT EXPEDITOR TO SECURE THE PERMIT. PERMIT SHALL BE 4000 Luxottica Place Mason, Ohio 45040
MOUNTED IN A VISIBLE, LOCATION AT THE SITE. PERMITS SHALL BE PAID FOR BY THE GC AND SUBMITTED TO TENANT
SUBMITTALS, SHOP DRAWINGS, PERMITS, APPROVALS, REGULATIONS AND CODES. 'PROJECT', AS USED HEREIN, SHALL REFER TO
AS A NET COST.
Construction for:
THE ENTIRE SCOPE OF PROVIDING A FINISHED FACILITY, READY AND USEABLE FOR ITS INTENDED PURPOSE. GC SHALL BE
RESPONSIBLE TO VISIT THE SITE PRIOR TO SUBMISSION OF BID. ANY DISCREPENCIES FROM PLANS SHALL BE CONVEYED TO THE B. THE GC SHALL ARRANGE FOR ALL REQUIRED INSPECTIONS.

CHARLESTON CHURCH STREET


NEXTORE PROJECT MANAGER PRIOR TO BID SUBMISSION. SUBMISSION OF BID SHALL CONSTITUTE ACKNOWLEDGEMENT AND C. THE GC SHALL DETERMINE IF THE INSPECTORS WILL BE CHECKING LAB / LENS PROCESSING ROOM EQUIPMENT FOR UL
ACCEPTANCE OF EXISTING CONDITIONS. OR ETL LABELS AND NOTIFY THE CONSTRUCTION MANAGEMENT TEAM NO LATER THAN 4 WEEKS BEFORE "PUNCH".
B. ALL MATERIALS AND/OR LABOR FOR THE PROJECT WHICH IS SHOWN ON THE DRAWINGS AND SPECIFICATIONS OR IS D. IF REQUIRED, A "TEMPORARY C OF O" OR BUILDING DEPARTMENT APPROVAL SHALL BE RECEIVED TO SET DOWN
REASONABLY INFERABLE THEREIN AS BEING NECESSARY TO PRODUCE A FINISHED PROJECT, SHALL BE PROVIDED BY GENERAL EQUIPMENT.
CONTRACTOR, WHETHER OR NOT THE WORK IS EXPRESSLY COVERED IN THE DOCUMENTS. THIS APPLIES TO ALL WORK, WITH
THE EXCEPTION OF THOSE ITEMS INDICATED N.I.C. ("NOT IN CONTRACT") OR BY OTHERS. THE DESIGN INTENT OF THE DRAWINGS 2. DIMENSIONS:

CHARLESTON , SC
SHALL ALWAYS BE THE GOAL. THE WORD 'HOLD' REFERS TO A CRITICAL DIMENSION AND MUST BE ADHERED TO. IF THESE DIMENSIONS CAN NOT BE MET,
C. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR ALL COORDINATION BETWEEN SUBCONTRACTORS, SUPPLIERS, SUBMIT IN WRITING & CALL NEXTORE P.M. FOR DIRECTION.
VENDORS OR ANY OTHER PARTIES SUPPLYING GOODS OR SERVICES TO THE PROJECT. NO EXTRA COMPENSATION WILL BE GIVEN

4000 Luxottica Place Mason, Ohio 45040


TO ANY PARTY WHO HAS BID FROM AN INCOMPLETE SET OF DOCUMENTS OR WITH INSUFFICIENT FAMILIARITY WITH THE 3. ON-SITE COMMUNICATION:

A Subsidiary of the Luxottica Group


PROJECT OR THE SPECIFIC REQUIREMENTS THEREOF. IN THE EVENT OF INCONSISTENCIES OR DISCREPANCIES BETWEEN THE A. THE GC SHALL CONTACT THE NEXTORE P.M. TO RESOLVE ALL FIELD ISSUES.
DOCUMENTS, CODES, CRITERIA OR REQUIREMENTS, THE MOST STRINGENT SHALL APPLY. THE GENERAL CONTRACTOR SHALL
NOTIFY THE NEXTORE PROJECT MANAGER IMMEDIATELY OF SUCH DISCREPANCIES OR INCONSISTENCIES. B. GC TO HAVE CELL PHONE WITH VOICEMAIL CAPABILITIES.
C. GC TO HAVE LAPTOP ON SITE WITH WIFI CAPABILITIES.
D. IT IS THE RESPONSIBILITY OF THE G.C. TO VERIFY BOTH EXISTING SITE CONDITIONS AND DIMENSIONS WITHIN 24 HOURS OF D. GC TO HAVE PRINTER ON SITE.
STARTING ANY PROJECT. THE G.C. SHALL NOTIFY THE CONSTRUCTION MANAGER IMMEDIATELY OF ANY DISCREPANCIES PRIOR TO
INITIATING CONSTRUCTION. 4. CHANGE ORDERS:
NO ADDITIONAL COSTS OR DESIGN CHANGES WILL BE ACCEPTED WITHOUT THE WRITTEN APPROVAL OF THE NEXTORE P.M.
E. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING A CURRENT SET OF CONSTRUCTION DRAWINGS ON
SITE AT ALL TIMES DURING CONSTRUCTION. THE GENERAL CONTRACTOR SHALL INDICATE ON THESE PLANS ALL APPROVED AND THE EXECUTION OF THE NEXTORE CHANGE ORDER PROCEDURE, PRIOR TO THE COMMENCEMENT OF SUCH WORK.
CHANGES TO THE WORK. THIS SET OF DRAWINGS SHALL BE UPLOADED VIA PROJECT READY IN PDF FORMAT TO THE NEXTORE CHANGE ORDER WORK COMPLETED WITHOUT SIGNED APPROVAL TO DO SAME, IS DONE SO AT THE GC'S RISK.
PROJECT MANAGER UPON COMPLETION OF THE PROJECT. THESE DRAWINGS SHALL BE MARKED UP TO REPRESENT A COMPLETE
5. SUBCONTRACTOR COORDINATION:
PLANS TO NEXTORE PROJECT MANAGER AT PUNCH.
THE GC MUST BE PRESENT AT ALL TIMES FOR THE DURATION OF CONSTRUCTION. THE GC SHALL GIVE SUBCONTRACTORS
F. IF ANY ERRORS, DISCREPANCIES OR OMISSIONS APPEAR OR ARE EVIDENT ON ANY OF THE DOCUMENTS, THE GENERAL APPROPRIATE NOTICE BEFORE REQUIRING THEM ON SITE, COORDINATE INSTALLATION DATES, AND COMMUNICATE SITE
CONTRACTOR, SUBCONTRACTOR, VENDOR OR SUPPLIER SHALL IMMEDIATELY NOTIFY THE NEXTORE PROJECT MANAGER. SPECIFIC DETAILS. THE GC SHALL COORDINATE THE INSTALLATION SCHEDULE AND DIVISION OF WORK WITH THE NEXTORE
P.M. SUBCONTRACTORS SHOULD CONTACT THE GC FOR SCHEDULE CLARIFICATIONS.
4 LANDLORD'S ADDRESS 5 JOB SITE ADDRESS 6 KEY PLAN 7 VICINITY PLAN
G. NO MATERIAL SUBSTITUTIONS WILL BE ALLOWED UNLESS SUBMITTED IN WRITING AND APPROVED IN WRITING BY THE
NEXTORE PROJECT MANAGER. NORTH NORTH
MILLWORK / CASEWORK: GC SHALL COORDINATE CRITICAL DIMENSIONS PRIOR TO WALL CONSTRUCTION AND HAVE THE LANDLORD CHURCH STREET HOLDINGS (RAVENEL ASSOC.) NAME CHURCH STREET SQUARE
H. THE GENERAL CONTRACTOR SHALL, ON OR BEFORE THE SOONER OF: WITHIN 10 WORKING DAYS OF CONTRACT AWARD AREA READY PRIOR TO FIXTURE DELIVERY. READY SHALL BE DEFINED AS FLOORING DOWN THRU-OUT THE RETAIL AND CHARLESTON
OR THE START OF THE PROJECT, PROVIDE TO NEXTORE AND KEEP CURRENT, A LIST OF ALL SUBCONTRACTORS TO BE USED ON OPTOMETRIC DOCTOR (OD) RECEPTION, LIGHTING SOFFITS BUILT OUT, DRYWALLED, FINISHED, PAINTED AND LIGHTING SR. TENANT COORD. DAVID REESE STREET ADDRESS 73 S. MARKET STREET CHURCH STREET
THE PROJECT. THE GENERAL CONTRACTOR SHALL ALSO PROVIDE A COPY OF THIS LIST TO THE NEXTORE PROJECT MANAGER AT FIXTURES INSTALLED, ALL WALLS IN THE RETAIL AND OD RECEPTION MUST BE FINISHED AND PAINTED, ALL ELECTRICAL AND
CONSTRUCTION COMPLETION, AND A COPY IS TO BE INCLUDED IN THE CLOSEOUT PACKAGE FROM THE GENERAL CONTRACTOR. STREET ADDRESS CITY, STATE, ZIP PROJECT LOCATION:
MECHANICAL ROUGH-OUTS MUST BE COMPLETED, STORE MUST BE SECURED FROM THE OUTSIDE. ONCE THE 960 MORRISON DRIVE, SUITE 100 CHARLESTON, SC 29401
EXISTING STREET
I. THE GENERAL CONTRACTOR SHALL INSPECT, VERIFY AND INVENTORY ALL SHIPMENTS OF NEXTORE SUPPLIED MATERIALS, PRE-CONSTRUCTION MILLWORK DROP / INSTALL DATE HAS BEEN ESTABLISHED, ANY CHANGES TO THE ESTABLISHED DATE LEVEL SUNGLASS HUT
CITY, STATE, ZIP CHARLESTON, SC 29403
INCLUDING THOSE TO AND FROM ANY OFF SITE WAREHOUSE FACILITIES. THIS INCLUDES VERIFYING PACKING LISTS AGAINST MUST BE COMMUNICATED AT LEAST 7 DAYS PRIOR.
ORDER FORMS AND BILLS OF LADING, AND NOTING AND REPORTING ANY DAMAGES OR SHORTAGES TO THE NEXTORE PROJECT
MANAGER. IF NOT DONE WITHIN 24 HOURS OF DELIVERY, THE GENERAL CONTRACTOR SHALL BEAR ANY AND ALL ASSOCIATED PHONE 843-768-9480 EXT. 3911
6. DATA-POS / PHONES:
COSTS, INCLUDING EXPEDITED FREIGHT CHARGES, TO MEET THE CONSTRUCTION SCHEDULE. THE GENERAL CONTRACTOR IS
RESPONSIBLE FOR FILING DAMAGE REPORTS AND MAINTAINING PACKING MATERIALS FOR RETURN SHIPMENT OF DAMAGED A. NEW T.I. & RELO STORES: BACKBOARD TO BE INSTALLED WITHIN 7 CALENDAR DAYS OF THE CONSTRUCTION START DATE. EMAIL dreese@ravenelassociates.com
ITEMS. ACCESS TO BACKBOARD SHALL BE AFFORDED TO ALL TENANT VENDORS. TELEPHONE, ELECTRIC AND DATA CABLING
INSTALLED ONE WEEK BEFORE "PUNCH" FOR HARDWARE INSTALLATION AND TESTING. CONTACT NEXTORE P.M. IF
J. THE GENERAL CONTRACTOR SHALL KEEP ALL HANDBOOKS, MANUALS, WARRANTY DOCUMENTS AND MISCELLANEOUS NEEDED.
PAPERWORK, INCLUDING ALL PACKING SLIPS AND BILLS OF LADING IN A MARKED BINDER. THIS BINDER IS TO BE TURNED OVER TO 4-SGH4.0-G001-REV00 5-SGH4.0-G001-REV00
THE STORE GENERAL MANAGER AT PROJECT COMPLETION. COPIES OF THOSE ITEMS AND DOCUMENTS REQUIRED FOR
INCLUSION IN THE CLOSEOUT PACKAGE SHALL BE MADE BY THE GENERAL CONTRACTOR AS NEEDED FOR THIS SUBMISSION. B. REMODEL STORES: GC TO COORDINATE ALL TEMPORARY AND PERMANENT DATA AND PHONE CABLING DURING THE
OPEN REMODEL. KEEPING STORE POS AND PHONE SYSTEMS ON LINE AND ACTIVATED AT ALL TIMES. COORDINATE
K. THE GENERAL CONTRACTOR SHALL DELIVER TO THE NEXTORE PROJECT MANAGER A COPY OF THE CERTIFICATE OF WORK WITH TENANT LOW VOLTAGE VENDOR.
OCCUPANCY (C OF O), LIEN WAIVERS, WARRANTIES, GUARANTEES AND EQUIPMENT OPERATION MANUALS. THE ORIGINAL
CERTIFICATE OF OCCUPANCY IS TO BE LEFT WITH THE STORE GENERAL MANAGER.
7. ELECTRICAL AND LIGHTING DELIVERIES
8 STORE INFO. 9 JURISDICTION Revisions:
Mark Date By
L. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE CLEAN UP AND DISPOSAL OF ALL TRASH AND DEBRIS GC SHALL BE RESPONSIBLE FOR THE COORDINATION OF DELIVERIES, FOR THE OFF-LOADING OF SAME, AND TO VERIFY /
GENERATED BY ALL TRADES. GC. TO REMOVE/DISPOSE OF ALL BOXES/CRATES/TRASH OF TENANT SUPPLIED AND INSTALLED REPORT ANY DAMAGE AND FOR THE SAFE STORAGE OF ALL MATERIALS RECEIVED. THE GC SHALL VERIFY THE VOLTAGE AND 1 11-28-18
ITEMS, INCL. DISPLAY FIXTURES & HARDWARE. DAILY CLEAN REQUIRED. STORE CONTACT SUNGLASS HUT
COMPATIBILITY OF ALL EQUIPMENT, FIXTURES AND MILLWORK PRIOR TO CONNECTION. DEPARTMENT LANDLORD COMMENTS / PERMIT SET
CITY OF CHARLESTON
M. THESE CONSTRUCTION DOCUMENTS ARE NOT TO BE SCALED. ALL DIMENSIONS ARE TO FINISH FACE OF WALL, UNLESS STREET ADDRESS 73 S. MARKET STREET PERMIT CENTER
OTHERWISE NOTED 8. METER INSTALLATION (WATER / ELECTRIC / GAS):
UTILITY ACCOUNT TRANSFER / SETUP (FOR CORPORATE NEW AND RELOCATION STORES ONLY): CITY, STATE, ZIP CHARLESTON , SC 29401 STREET ADDRESS 2 GEORGE STREET
N. THESE DRAWINGS ARE NOT TO BE ALTERED IN ANY WAY WITHOUT THE WRITTEN AUTHORIZATION FROM NEXTORE OR GC SHALL CONTACT THE NEXTORE RETAIL STORE MAINTENANCE HOTLINE (513)765-3500 UPON ARRIVAL AT THE SITE. GC
NEXTORE'S ARCHITECT. WILL NOT BE RESPONSIBLE FOR ANY UTILITY COSTS DURING CONSTRUCTION. GC TO CONTACT NEXTORE TO CONVERT PHONE CITY, STATE, ZIP
- CHARLESTON, SC 29401
O. THE GENERAL CONTRACTOR SHALL MAINTAIN EGRESS AT ALL TIMES DURING STORE OPERATION / CONSTRUCTION. METERS TO NEXTORE NAME IMMEDIATELY UPON CONSTRUCTION START UP. GC TO PROVIDE THE FOLLOWING
P. THE GENERAL CONTRACTOR SHALL COORDINATE CONSTRUCTION TIMES AND NOISE REQUIREMENTS WITH LANDLORD INFORMATION WHEN CALLING: EMAIL - PHONE 843-577-5550
PRIOR TO CONSTRUCTION START, NO EXTRA COSTS WILL BE ALLOWED TO ACCOMMODATE ANY RESTRICTIONS OR LIMITATIONS. A. STORE ADDRESS AND SPACE #
B. UTILITY COMPANY (S) NAME AND PHONE # (I.E., GAS, ELECTRIC, WATER AND POSSIBLY SEWER)
Q. UPON COMPLETION OF CONSTRUCTION, IT SHALL BE THE RESPONSIBILITY OF THE GENERAL CONTRACTOR TO CLEAN ALL 8-SGH4.0-G001-REV00 9-SGH4.0-G001-REV00 6-SGH4.0-G001-REV00
SURFACES / FIXTURES PER MANUFACTURER'S INSTRUCTIONS AND TO EMPLOY THE SERVICES OF A PROFESSIONAL CLEANING C. METER AND SOCKET # (IF USED)
COMPANY TO ASSURE DELIVERY TO THE TENANT OF AN ABSOLUTELY CLEAN STORE. (2) CLEANINGS REQUIRED. (1) PRIOR TO D. EXPECTED "PUNCH" DATE (TIMING FOR NEW INSTALLATION OR UTILITY ACCOUNT TRANSFER WILL BE EXECUTED ON/OR
PUNCH & (1) AT TURNOVER. THE FINAL CLEANING IS TO BE PERFORMED NO MORE THAN ONE DAY PRIOR TO THE TURN OVER. IF BEFORE THE "PUNCH" DATE).
AN UNTIDY STORE IS TURNED OVER, NEXTORE RESERVES THE RIGHT, WITHOUT NOTICE TO THE GENERAL CONTRACTOR, TO
EMPLOY PROFESSIONAL CLEANING SERVICES AND DEDUCT THE COST PLUS 15% FROM THE BALANCE OF THE GENERAL
CONTRACTOR.
9. TURNOVER PROCEDURE:
A. THE GC SHALL CALL THE THE NEXTORE P.M. TO CONFIRM THE TURNOVER DATE NO LATER THAN 10 WORKING DAYS
10 CODE INFORMATION 11 PROJECT DIRECTORY 12 DRAWING INDEX
R. THE GENERAL CONTRACTOR SHALL PROVIDE PROTECTIVE COVERING FOR ALL EQUIPMENT, FINISHES, MERCHANDISE, BEFORE TURNOVER.
ACTIVE
CARPET, ETC., INCLUDING THE WORK OF OTHERS, THROUGHOUT THE DURATION OF THE PROJECT. B. ALL CONSTRUCTION ITEMS, INCLUDING ITEMS ON THE INSTALLATION SCHEDULE ARE TO BE COMPLETED BEFORE CONSTRUCTION TYPE: ASSUMED II B NOTE TO BUILDING DEPARTMENT REGARDING SHEET # DRAWING TITLE
REVISION #
TURNOVER DAY.
S. THE GENERAL CONTRACTOR SHALL COORDINATE ALL ACTIVITIES WITH THE LANDLORD PRIOR TO THE START OF
C. THE GC AND NEXTORE P.M. TO CONDUCT THE PUNCH WALKTHROUGH, NOTING ALL DEFICIENCIES AND TIMING FOR EXISTING OCCUPANCY: M (MERCANTILE) MINIMUM PLUMBING FIXTURES: DESIGN AND CONSTRUCTION MANAGEMENT
CONSTRUCTION, AND COORDINATE WITH THE LANDLORD, ALL INTERRUPTION OF SERVICES. ANY SHUT DOWNS SHALL BE THE
RESPONSIBILITY OF THE GENERAL CONTRACTOR RESOLUTION.
D. A "SUBSTANTIAL COMPLETION" DOCUMENT WILL BE DISTRIBUTED TO THE GC. THE GC SHALL REMAIN ON SITE UNTIL PROPOSED OCCUPANCY: M (MERCANTILE) NO CHANGE -THE OCCUPANT LOAD FOR THIS MERCANTILE TENANT SPACE IS 15
NEXTORE
ARCHITECTURAL
T. THE GENERAL CONTRACTOR SHALL INSTALL A LANDLORD AND CODE COMPLIANT TEMPORARY BARRICADE AS REQUIRED ALL "PUNCH LIST" ITEMS ARE COMPLETE AND THE NEXTORE PM HAS APPROVED ITEMS CONFIRMING COMPLETION OF BUILDING: PERSONS. -A SINGLE UNISEX RESTROOM IS DESIGNATED TO REMAIN. NEXTORE Architect / Engineer of Record
BY THE LANDLORD OR NEXTORE PROJECT MANAGER, UNLESS THE PLANS SPECIFICALLY CALL OUT FOR THIS WORK TO BE BY 2015 SOUTH CAROLINA BUILDING CODE G001 GENERAL INFORMATION / COVER SHEET 1
THE "PUNCH LIST" BY GC. -NO ADDITIONAL PLUMBING FIXTURES ARE EXISTING 4000 LUXOTTICA PLACE
OTHERS. 6 CREAMERY BROOK
E. A COPY OF THE "CONFIRMED COMPLETION OF PUNCH LIST" WILL BE GIVEN TO THE NEXTORE P.M. BY THE GC. MECHANICAL: 2015 SOUTH CAROLINA MECHANICAL CODE MASON, OH 45040 G002 RESPONSIBILITY SCHEDULE
EAST GRANBY, CT 06026
U. GENERAL CONTRACTOR SHALL INSTALL A TEMPORARY ENTRANCE WITH DOORS, FRAMES AND LOCKS, UNLESS THE PLANS
FIRE: -4031. FOOT NOTE "E" 513.765.6000
SPECIFICALLY CALL OUT FOR THIS WORK TO BE BY OTHERS. 10. SETDOWN FOR NEW CORPORATE STORES: 2015 SOUTH CAROLINA FIRE CODE A MOP SINK IS NOT REQUIRED WITH OCCUPANT LOAD OF 15 OR G003-G006 SPECIFICATIONS
NEXTORE'S NEW STORE TEAM WILL DELIVER ALL REMAINING OWNER FURNISHED ITEMS TO THE STORE ON THE EVENING OF PLUMBING: 2015 SOUTH CAROLINA PLUMBING CODE FEWER.
V. ALL CONSTRUCTION SHALL CONFORM TO ALL APPLICABLE CODES AND ORDINANCES, THE LANDLORD'S TENANT DESIGN EX. FLOOR PLAN / SELECTIVE DEMOLITION
CRITERIA, THE LANDLORD'S CONSTRUCTION RULES AND REGULATIONS, NEXTORE STANDARD SPECIFICATIONS, NEXTORE'S "TURNOVER" DAY. THE GC SHALL BE ON SITE ON THE DAY AFTER "TURNOVER", WITH ONE (1) PLUMBER AND ONE (1) AD100
STANDARD CONSTRUCTION CRITERIA AND ACCEPTED BEST CONSTRUCTION PRACTICES. THE GENERAL CONTRACTOR SHALL BE ELECTRICIAN TO ASSIST THE SETDOWN TEAM TO RESOLVE ANY ISSUES. THE GC SHALL SUPPLY DUMPSTER FOR REMOVAL OF ELECTRICAL 2014 NATIONAL ELECTRICAL CODE (NFPA 70) -403.2 EXCEPTION #2
RESPONSIBLE TO FILE ANY NEEDED "NOTICE OF COMMENCEMENT" OR OTHER FILINGS RELATED TO THE PROJECT IN THE SETDOWN DEBRIS. SEPARATE FACILITIES ARE NOT REQUIRED IN MERCANTILE
NOTE: AD200 EX. CEILING PLAN / SELECTIVE DEMOLITION 1
APPROPRIATE OFFICES AND SHALL BE RESPONSIBLE TO POST SUCH NOTICES AT THE JOB SITE. ENERGY: 2009 INTERNATIONAL ENERGY CONSERVATION CODE ANY QUESTIONS REGARDING THESE CONSTRUCTION DOCUMENTS SHOULD BE
OCCUPANCIES WITH OCCUPANT LOAD OF 100 OR FEWER. A100 FIXTURE - FLOOR PLAN
11. SOUND SYSTEM: DIRECTED TO THE NEXTORE PROJECT MANAGER FOR APPROPRIATE DIRECTION
W. ALL WOOD CONSTRUCTION, INCLUDING BLOCKING, SHALL BE FIRE RESISTANT TREATED (FRT). ALL NEW FRAMING AT THE ACCESSIBILITY CODE: 2017 ICC A117.1 ACCESSIBLE & USEABLE BUILDINGS
STOREFRONT AND / OR ABOVE THE CEILING SHALL BE NON-COMBUSTIBLE. A. THE GC SHALL BE RESPONSIBLE TO CONTACT NEXTORE PROJECT MANAGER 4 WEEKS PRIOR TO THE SCHEDULED DATE -SECTION 410.2 OF COMMUNICATION.
& FACILITIES (EFFECTIVE JUNE 1, 2017) A101 CONSTRUCTION FLOOR PLAN 1
TO ARRANGE FOR INSTALLATION. DRINKING FOUNTAIN NOT REQUIRED OCCUPANT LOAD 15 OR FEWER
X. THE GENERAL CONTRACTOR SHALL, PRIOR TO BEGINNING ANY WORK, COORDINATE WITH THE LANDLORD OR ANY B. REMODELS AND RELOCATIONS: THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE REMOVAL, STORAGE A102 REFLECTED CEILING PLAN
AUTHORITY HAVING JURISDICTION, AND BEAR THE COSTS FOR, ALL EXPLORATIONS / X-RAYS REQUIRED FOR CUTTING/CORING AND REINSTALLATION OF SYSTEM (INCLUDING CD PLAYERS AND SPEAKERS) AT NEXTORE STORES DURING
OF THE SLAB OR EXCAVATING. NOTE: THE LOCATION OF THE EXISTING RESTROOM IS LOCATED IN A
DURATION OF CONSTRUCTION. A103 FINISH PLAN - FINISH SCHEDULE 1
NON-SALES PORTION OF THE TENANT SPACE. THE EXISTING
Y. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE TO COORDINATE ALL THEIR WORK AND THE WORK OF THEIR RESTROOM IS AVAILABLE TO THE PUBLIC UPON REQUEST. IT IS
SUBCONTRACTORS WITH THE STRUCTURE AND SHELL BUILDING ELEMENTS. THE GENERAL CONTRACTOR SHALL IMMEDIATELY 12. SECURITY ALARM TRANSFER/MODIFICATION SPRINKLERED: YES (EXISTING SYSTEM TO REMAIN) A104 ELECTRIC / DATA DIMENSIONAL PLAN
ARCHITECT OF RECORD UNDERSTANDING THAT THE LOCATION OF THE
NOTIFY THE NEXTORE PROJECT MANAGER OF ANY DISCREPANCIES BETWEEN THESE DRAWINGS AND THE BUILDING SHELL. A. ALARM TRANSFER / MODIFICATION - GC SHALL CONTACT THE SECURITY VENDOR DURING ANY POINT IN FIRE ALARM: NO EXISTING RESTROOM IS ACCEPTABLE DUE TO THIS IS A REMODEL NEXTORE PROJECT MGR. NEXTORE PROJECT PLANNER
A200 INTERIOR ELEVATIONS-SALES AND NON SALES
Seal
CONSTRUCTION THE GC DETERMINES THEY WILL NEED TO DISABLE OR RELOCATE ANY ALARM SYSTEM COMPONENTS. SHERRI LESSARD 1
Z. THE GENERAL CONTRACTOR SHALL PROVIDE ALL FIRE EXTINGUISHERS, CONCEALED BLOCKING AND SIGNAGE FOR SAME AS SCOPE OF WORK PROJECT WITH NO CHANGE OF TENANT, USE AND BRUNELLA LEE BIONDI
REQUIRED. QUANTITIES, SIZES AND LOCATIONS SHOWN IN THE DRAWINGS ARE ONLY SUGGESTED QUANTITIES, SIZES AND GC SHALL AWAIT INSTRUCTIONS FROM THE "NEXTORE SECURITY LIAISON" BEFORE TAKING ANY ACTION ON THE FIRE EXTINGUISHERS: YES 470-330-3863 860-431-9668
OR OCCUPANCY A400 SECTIONS & DETAILS 1
LOCATIONS, THE MOST STRINGENT REQUIREMENT OF ANY BODY HAVING JURISDICTION SHALL PREVAIL. SECURITY SYSTEM. bbiondi@nextoreretail.com slessard@nextoreretail.com
EXISTING SUNGLASS HUT LOCATED ON LEVEL ONE (STREET
B. CAMERAS - GC SHALL CONTACT THE "NEXTORE LOSS PREVENTION MANAGER" TO COORDINATE THE REINSTALLATION A401 SECTIONS & DETAILS
AA. THE GENERAL CONTRACTOR SHALL DESIGN, INSTALL, LOCATE, RELOCATE, RECONFIGURE THE FIRE SPRINKLER AND FIRE LEVEL) OF 3 LEVEL BUILDING
OF SECURITY CAMERAS ON REMODEL OR RELOCATION STORES THAT ALREADY HAVE CAMERAS IN PLACE AND ARE
ALARM SYSTEMS AS REQUIRED BY THE INTENT OF THESE CONSTRUCTION DOCUMENTS OR ANY CODE OR BODY HAVING
JURISDICTION OVER THE WORK. ALL FIRE SPRINKLER AND FIRE ALARM SYSTEM WORK SHALL BE 'DESIGN BUILD' BY THE GENERAL BEING DISTURBED DURING CONSTRUCTION. A402 CEILING DETAILS
CONTRACTOR, UNLESS CALLED OUT TO BE PERFORMED SPECIFICALLY BY OTHERS IN THE DOCUMENTS (SEE FIRE SPRINKLER EGRESS: OCCUPANT LOAD:
SYSTEM / FIRE ALARM SYSTEM NOTES. GC TO COORDINATE WITH LANDLORD REQUIRED VENDOR. 13. AIR BALANCE REPORTS:
AB. THE GENERAL CONTRACTOR SHALL, WITHOUT EXCEPTION, PROVIDE AND INSTALL ANY AND ALL DUST PROTECTION,
REQUIRED DURING CONSTRUCTION.
G.C. RESPONSIBLE TO OBTAIN CERTIFIED AIR BALANCING REPORT FROM A VENDOR INDEPENDENT FROM THE HVAC
CONTRACTOR.
LEVEL ONE SALES =
LEVEL ONE NON-SALES=
621/60 = 11
409/300 = 2 NEXTORE STORE DESIGNER
ELECTRICAL
CARLY SHAVER
AC. GENERAL CONTRACTOR TO PROVIDE ALL FLOOR PREPARATION AS NEEDED TO ASSURE COMPLIANCE WITH FINISHED MEZZANINE LEVEL = 408/300 = 2
FLOORING MANUFACTURER SPECIFICATIONS. 2-SGH4.0-G001-REV00 860-431-???? E001 ELECTRICAL SPEC. AND NOTES
15 OCCUPANTS
cshaver@nextoreretail.com
AD. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ALL CEILING WORK WITH THE MEP E200 ELECTRICAL DEMOLITION PLAN
DRAWINGS. LEVEL ONE 1030 S.F.
Architect / Engineer Job No.:
E201 ELECTRICAL LIGHTING PLAN
AE. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR THE COORDINATION OF ALL LIGHTING WITH THE ELECTRICAL
DRAWINGS / REFLECTED CEILING PLAN. 3 LANDLORD NOTES MEZZANINE LEVEL
GROSS
408 S.F.
1438 S.F.
E202 ELECTRICAL POWER & SYSTEMS PLAN
030
AF. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING AND INSTALLING ALL LIGHT FIXTURES SUPPORTS, - Nextore Store Design Revision No.:
INCLUDING ANY AND ALL SEISMIC REQUIREMENTS. FP200 FIRE PROTECTION PLANS
EGRESS WIDTH PER OCCUPANT:
AG. THE GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR MAINTAINING REQUIRED FIRE RATINGS AND FIRE PROOFING IN
ALL INSTANCES.
.2 INCHES PER PERSON (SPRINKLERED)
1.) EGRESS COMPONENTS (SPRINKLERED) 11-SGH4.0-G001-REV00 12-SGH4.0-G001-REV00
DES REV 02
AH. ALL PENETRATIONS OF DEMISING WALLS, ROOF AND FLOOR SHALL BE FIRE SAFE / PROOF PER CODES / LANDLORD .2 INCHES PER OCCUPANT x 15 OCCUPANTS = 3 INCHES (REQUIRED)
REQUIREMENTS. THE MOST STRINGENT REQUIREMENT SHALL PREVAIL.
Nextore project
AI. THE GENERAL CONTRACTOR SHALL RECEIVE, UNLOAD, AND PROVIDE SAFE STORAGE OF ALL NEXTORE / NEXTORE SUPPLIED TOTAL EGRESS WIDTH PROVIDED: = 33" (EXISTING ENTRY DOOR) Number 77889
AND / OR INSTALLED MATERIAL. TRASH REMOVAL OF ALL BOXES / CRATES CONTAINING NEXTORE / NEXTORE SUPPLIED AND /
OR INSTALLED MATERIAL, INCLUDING BUT NOT LIMITED TO FLOORING, MILLWORK, LIGHTING, HARDWARE, ACCESSORIES,
EQUIPMENT, ETC. SHALL BE BY THE GENERAL CONTRACTOR.
EXIT ACCESS
MAX TRAVEL: 75 FEET SPRINKLERED
14 SCOPE OF WORK 15 SIGNAGE TAKEOFF SCHED. Brand Design Type:

SGH 4.1 - TIER B GOLD


AJ. NOTICE OF INCIDENT: THE GENERAL CONTRACTOR SHALL, VIA ELECTRONIC MEDIUM AND NEXTORE STANDARD
NOTIFICATION AND REPORTING FORMS, IMMEDIATELY NOTIFY THE NEXTORE PROJECT MANAGER OF ANY INCIDENT INVOLVING EXIT AND EXIT ACCESS DOORWAYS REMOVE AND REPLACE SALES AREA DISPLAY FIXTURES CODE DESCRIPTION QUANTITY
THE PROJECT WHICH RESULTS IN CONTACT WITH ANY FEDERAL, STATE OR LOCAL GOVERNMENT AGENCY OR AS CALLED OUT IN SPACES WITH ONE EXIT OR EXIT ACCESS DOORWAY REMOVE AND REPLACE CASH DESK ISSUED FOR:
NEXTORE'S OR THE LANDLORDS RULES, REGULATIONS OR POLICIES. OCCUPANCY: M MAX OCCUPANT LOAD = 49 RB-F-RN-MP
REMOVE AND REPLACE OF SALES AREA FLOORING AND WALL BASE (VERIFY CODE RAYBAN LIT SIGN - SEE ELEV 01 X Construction
AK. WEEKLY PROGRESS PHOTOS, DAILY REPORTS, SAFETY INSPECTIONS, SCHEDULE UPDATES, CHANGE ORDER LOGS, RFI LOGS, PAINT SALES AREA WALLS W/ ELEV.
AND TOOL BOX TOPICS SHALL BE SUBMITTED TO THE NEXTORE PROJECT MANAGER VIA PROJECT READY AS REQUIRED IN THE 10-SGH4.0-G001-REV00 REMOVE SALES AREA ACOUSTICAL CEILING TILES AND EXISTING LIGHT FIXTURES
DOCUMENTS OR DIRECTED BY THE NEXTORE PROJECT MANAGER.
(EXISTING GRID TO REMAIN)
AL. NEW SALES AREA ACOUSTICAL CEILING TILES AND LIGHTING.
WHILE CONSTRUCTION IS IN PROGRESS. ALL DISTURBANCES TO SURROUNDING BUSINESSES AND AREAS MUST BE KEPT TO A ELECTRICAL WORK FOR NEW LIGHTING AND DISPLAY FIXTURES Title
MINIMUM. WORK DURING AN OPEN REMODEL IS TYPICALLY PERFORMED "AFTER NORMAL OPERATING HOURS." GC MUST
COORDINATE WITH NEXTORE PROJECT MANAGER AND OR STORE OPERATIONS MANAGER PRIOR TO CONSTRUCTION START.
THERE SHALL BE NO UP-CHARGE SUBMITTED, ALLOWED, OR CONSIDERED FOR ANY SUCH AFTER HOURS WORK.
13 COMMENTS EXISTING PLUMBING SYSTEM TO REMAIN. ENSURE PROPER WORKING ORDER
ONLY WORK PROPOSED.
15-SGHNX-G001-REV00
GENERAL
EXISTING HVAC SYSTEM TO REMAIN. ENSURE PROPER WORKING ORDER ONLY
SAFETY:
SAFETY OF ALL EMPLOYEES, ASSOCIATES AND CUSTOMERS SHALL BE THE NUMBER ONE PRIORITY FOR ALL CONTRACTORS ON
WORK PROPOSED. INFORMATION
ANY NEXTORE PROJECT. OSHA REQUIREMENTS SHALL BE INCORPORATED INTO THE SCOPE OF WORK EVEN THOUGH THEY MAY
COVER SHEET
NOT BE LISTED SEPARATELY. CONTRACTOR SHALL MAINTAIN A COPY OF THEIR SITE SPECIFIC SAFETY PLAN ON SITE AT ALL TIMES
16 DEFERRED SUBMITTALS
Date Sheet
IF REQUIRED TO BE SUBMITTED UNDER SEPARATE COVER 11-28-18
Drawn By
- MINOR MODIFICATIONS PROPOSED TO EXISTING SPRINKLER SYSTEM

Checked By
STAFF G001
1-SGH4.0-G001-REV00 3-SGH4.0-G001-REV00 13-SGH4.0-G001-REV00 14-SGH4.0-G001-REV00 16-SGH4.0-G001-REV00
STAFF
DESIGN & CONSTRUCTION
MANAGEMENT:

1 RESPONSIBILITY SCHEDULE 2 RESPONSIBILITY SCHEDULE


NOTE: THE GENERAL CONTRACTOR SHALL VERIFY ALL ITEMS ON THIS SCHEDULE NOTE: THE GENERAL CONTRACTOR SHALL VERIFY ALL ITEMS ON THIS SCHEDULE
T= TENANT MW= MILLWORKER T= TENANT MW= MILLWORKER a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000
FOR ACCURACY PRIOR TO BEGINNING CONSTRUCTION. ANY DISCREPANCIES FOR ACCURACY PRIOR TO BEGINNING CONSTRUCTION. ANY DISCREPANCIES
SHALL BE REPORTED TO NEXTORE PROJECT MANAGER IMMEDIATELY.
GC= GENERAL CONTRACTOR N/A= NOT APPLICABLE SHALL BE REPORTED TO NEXTORE PROJECT MANAGER IMMEDIATELY.
GC= GENERAL CONTRACTOR N/A= NOT APPLICABLE a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484

LL= LANDLORD V = VENDOR LL= LANDLORD V = VENDOR


DIVISION 01000 - GENERAL SUPL RCV. INSTL EX'G RELO REMARKS DIVISION 15000 - MECHANICAL SUPL RCV. INSTL EX'G RELO REMARKS

BUILDING PERMIT T GC GC SHALL AMEND / PICK UP PERMIT & PAY ADD'TL FEES; FEES BILLABLE TO NEXTORE AT NET COST; VIA CHANGE ORDER #1 ACCESS PANELS GC GC GC PROVIDE NEW ACCESS PANEL IN SALES AREA GYP. BD. CEILING
PROFESSIONAL CLEAN-UP, FINAL CLEANING GC GC (2) CLEANINGS REQUIRED. (1) PRIOR TO PUNCH & (1) AT TURNOVER ROOF WORK GC GC GC
DEMOLITION GC GC FIELD VERIFY EXISTING CONDITIONS AND SEE PLANS FOR SCOPE HVAC DISTRIBUTION, DUCTWORK, DIFFUSERS GC GC GC SEE PLANS FOR MINOR SCOPE OF WORK
TEMPORARY FACILITIES / UTILITIES GC GC PLUMBING FIXTURES
OTHER PERMITS, FEES GC GC INCLUDING ALL LOCAL PEST CONTROL REQUIREMENTS, PERMITS, VERIFY REQUIREMENTS FLOOR DRAINS / PIPING / SUPPORTS
TEMPORARY BARRICADES (W/ LUX BRAND SPECIFIC LOGO) T T BY BOSTON BARRICADE WATER AND SEWER CONNECTION
TEMPORARY BARRICADES (W/ LUX BRAND SPECIFIC LOGO) GC GC WHEN VENDOR OTHER THAN BOSTON BARRICADE IS TO BE USED SPRINKLER SYSTEM MODIFICATIONS GC GC GC MODIFICATIONS TO SPRINKLER SYSTEM AS REQUIRED FOR NEW SALES AREA GYP. BD. CEILING

TRASH REMOVAL AND DUMPSTERS GC GC


VERIFY TOWN AND LANDLORD REQUIREMENTS. GC. TO REMOVE/DISPOSE OF ALL BOXES/CRATES/TRASH OF TENANT SUPPLIED AND INSTA-HOT WATER HEATERS GC GC GC Construction for:
INSTALLED ITEMS, INCL. DISPLAY FIXTURES & HARDWARE. DAILY CLEAN REQUIRED. AIR CURTAIN GC GC GC
CUTTING AND PATCHING GC GC GC TOILET ROOM EXHAUST FAN SEE PLANS FOR MINOR SCOPE OF WORK
RELOCATION OF EXISTING FIXTURES GC GC TO VERIFY UPON ARRIVAL ON JOB SITE THAT THE SITE HAS BEEN CLEARED OF ALL FIXTURES IN ORDER TO PERFORM AREA HVAC UNIT(S) & CURBS -RTU, VAV, HAV, ETC. SEE PLANS FOR MINOR SCOPE OF WORK
CONSTRUCTION. G.C. SHALL COORDINATE W NEXTORE PM FOR EXACT SCOPE PER PROJECT. CONTROLS FOR HVAC UNIT(S) SEE PLANS FOR MINOR SCOPE OF WORK
SECURITY (ASSET PROTECTION COORDINATION) GC IF OVERNIGHTS REQUIRED, GC SHALL PAY APPROVED VENDOR & COORDINATE OVERNIGHT POWER W NEXTORE PM.
INSURANCE GC GC TO ADD ADDITIONAL INSURED PARTIES, SUCH AS BRAND AND OR LUXOTTICA, ON CERTIFICATE OF LIABILITY INSURANCE. CURBS, SUPPORTS, FOR CONDENSING UNITS GC GC GC
CERTIFICATES NEED TO BE SENT TO THE NEXTORE PROJECT MANAGER. SMOKE EVACUATION SYSTEM & CONTROLS GC GC GC
TEMPORARY CONSTRUCTION WINDOW VINYL GC GC GC IF REQUIRED GC TO ITEMIZE COST DUCT SMOKE DETECTORS
SERVICE & BALANCE EXISTING RTU'S

4000 Luxottica Place Mason, Ohio 45040


DIVISION 03000 - CONCRETE SUPL RCV. INSTL EX'G RELO REMARKS ZONE CONTROL DAMPERS W/ THERMOSTAT

A Subsidiary of the Luxottica Group


CONCRETE SLAB (NEW OR PATCH FILL) GC GC GC GC TO FIELD VERIFY EXIST. COND. TO DETERMINE EXTENT OF SCOPE. GC TO REPORT TO PROJECT MANAGER. STRUCTURAL SUPPORTS FOR VAV'S GC GC GC
CUTTING OF EXISTING SLAB-TRENCHING OR CORE DRILLING GC GC GC COORD. W/ LANDLORD & AFFECTED TENANTS. VERIFY W LL OPERATIONS PRIOR TO ANY CORING OR TRENCHING. STRUCTURAL SUPPORTS FOR AIR HANDLERS GC GC GC
STRUCTURAL CONCRETE & REINFORCING GC GC GC WATER METER
SIDEWALK / ENTRY
BOTTLED WATER UNIT T T T
DIVISION 04000 - MASONRY SUPL RCV. INSTL EX'G RELO REMARKS WATER COOLER AND/OR DRINKING FOUNTAIN GC GC GC
CLEANING OF MASONRY GC GC GC FIRE SPRINKLER MAIN
CONCRETE MASONRY UNIT WALLS GC TO FIELD VERIFY FOR ANY DEFECTS WHICH REQUIRE ATTENTION
DIVISION 16000 - ELECTRICAL SUPL RCV. INSTL EX'G RELO REMARKS

DIVISION 05000 - MISC. METALS SUPL RCV. INSTL EX'G RELO REMARKS CONNECTION AND WIRING @ MILLWORK THROUGHOUT GC GC GC
BASE BUILDING STRUCTURAL STEEL ELECTRICAL SERVICE, FEEDERS, CONDUIT, METERS
STRUCTURAL STEEL AS REQUIRED FOR TENANT BUILD-OUT GC GC GC IF APPLICABLE IN PROJECT ELECTRICAL PANELS / TRANSFORMERS GC GC GC SEE PLANS FOR MINOR SCOPE OF WORK
METAL FABRICATIONS GC GC GC IF APPLICABLE IN PROJECT ELECTRICAL WIRING, CIRCUITING, RECEPTACLES, SWITCHES GC GC GC
EXPANSION JOINTS GC GC GC IF APPLICABLE IN PROJECT RECEPTACLES IN MILLWORK GC GC GC (WIRING AND FINAL CONNECTIONS BY GC)
DECORATIVE METALS GC GC GC GC TO PROVIDE ITEMIZED PRICING FOR SUPPLY, PAINT, & INSTALL EMERGENCY LIGHTING T GC GC
EXIT SIGNS T GC GC
DIVISION 06000 - WOOD & PLASTICS SUPL RCV. INSTL EX'G RELO REMARKS FIRE ALARM SYSTEM GC GC GC
BLOCKING / BACK PLATES (INCL. FOR FIXTURES, SHELVES, SIGNS) GC GC GC FIRE RETARDENT WOOD AND OR METAL PER AUTHORITY HAVING JURISDICTION / LL NEW LIGHT FIXTURES & LAMPS T GC GC
ROUGH CARPENTRY, FIRE RETARDANT LUMBER & PLYWD GC GC GC REPLACEMENT OR MATCHING EXISTING LIGHT FIXTURES & LAMPS GC GC GC
FLOOR PROTECTION (IF REQUIRED) GC GC GC DURABLE PROTECTION REQUIRED. PROVIDE WALK-OFF MAT AT BOTH SIDE OF ENTRY POINT(S) OF CONSTRUCTION AREA SOUND SYSTEM SPEAKERS V V V
FINISH CARPENTRY GC GC GC TELEPHONE CONDUIT TO SPACE
FLOOR PREP GC GC GC TELEPHONE WIRING TO SPACE
TENANT TELEPHONE EQUIPMENT T T T G.C. TO COORDINATE RELOCATION TO NEW CASHDESK
TELEPHONE WIRING T T T WIRING TO BE PLENUM RATED
DIVISION 07000 - THERMAL & MOISTURE PROTECTION SUPL RCV. INSTL EX'G RELO REMARKS
CONDUITS - DATA, COMMUNICATION, ALARMS, PHONES GC GC GC
SEALANTS, INSULATION, FIRE CAULKING & BLOCKING GC GC GC PROVIDE AS REQUIRED FOR SCOPE OF WORK
SPRAYED FIRE RESISTIVE MATERIALS GC GC GC EXISTING IF APPLICABLE WIRELESS EQUIPMENT T T T
THROUGH PENETRATIONS FIRE STOP SYSTEM GC GC GC AS REQUIRED FOR NEW EQUIPMENT AND DEVICES
JACK TERMINATION & FACEPLATE - DATA GC GC GC Revisions:
BATT INSULATION AND/OR SOUND ATTENUATION GC GC GC BACKBOARD TERMINATION - DATA GC GC GC AS REQUIRED FOR NEW EQUIPMENT AND DEVICES Mark Date By
WATERPROOF MEMBRANE GC GC GC EXISTING IF APPLICABLE JACK TERMINATION & FACEPLATE - PHONE GC GC GC AS REQUIRED FOR NEW EQUIPMENT AND DEVICES
BACKBOARD TERMINATION - PHONE T T T 1 11-28-18
DIVISION 08000 DOORS & WINDOWS SUPL RCV. INSTL EX'G RELO REMARKS
FLOOR BOX ( FLUSH MOUNTED FLOOR OUTLETS) GC GC GC SEE ELECTRICAL DRAWINGS IF ANY NEW ARE REQUIRED LANDLORD COMMENTS / PERMIT SET
NEW DOORS, FRAMES, HARDWARE GC GC GC UNLESS NOTED OTHERWISE. (SEE DOOR SCHEDULE SHEET A101) ELECTRIC METER, SEPARATE COORDINATE WITH UTILITY AND/OR LANDLORD, AS APPLICABLE.
PANIC / SECURITY ALARM GC GC GC IF EGRESS DOOR REQUIRED TRACK LIMITERS T GC GC
ALL DOOR LOCK CORES AND KEYS T GC GC REMODEL PROJECT. SEE PLANS FOR SCOPE OF WORK SECURITY - FACILITY (HARDWARE & WIRING FOR CAMERA) T GC GC GC TO COORDINATE W VENDOR
ACCESS DOORS AND FRAMES GC GC GC TRAFFIC COUNTER EXISTING TO REMAIN
MILLWORK MIRRORS T GC MW DATA AND PHONE DISCONNECT/RECONNECT AT REMODELS GC GC GC G.C. TO COORDINATE - WORK COMPLETED BY TENANT LOW VOLTAGE VENDOR.
OVERHEAD ROLLING GRILLE GC GC GC GC TO PROVIDE ITEMIZED PRICING FOR SUPPLY & INSTALL WHEN APPLICABLE IN PROJECT FOR RELO CASHWRAPS/FITTING COUNTERS GC GC GC
SECURITY GRILLE T T T POS AND DATA WIRING (TEMPORARY) GC GC GC
SECURITY ALARM & SYSTEM T GC T POS AND DATA WIRING (PERMANENT) GC GC GC WIRING TO BE PLENUM RATED
EXTERIOR & INTERIOR METAL STOREFRONT CLADDING T T T GC TO PROVIDE ITEMIZED PRICING FOR SUPPLY & INSTALL WIRING TO WIRELESS ACCESS POINTS GC GC GC
NEW STOREFRONT ALUMINUM FRAME OR CHANNELS T T T GC TO PROVIDE ITEMIZED PRICING FOR SUPPLY & INSTALL BACKBOARD TERMINATION - DATA GC GC GC
NEW STOREFRONT GLAZING T T T GC TO PROVIDE ITEMIZED PRICING FOR SUPPLY & INSTALL BACKBOARD TERMINATION - PHONE T T T
NEW STOREFRONT DOOR HARDWARE T T T GC TO PROVIDE ITEMIZED PRICING FOR SUPPLY & INSTALL BUZZER AT REAR DOOR GC GC GC
SECURITY FILM T T T PRODUCT SECURITY SYSTEM GC GC GC GC TO COORDINATE W VENDOR
RESTROOM MIRRORS GC GC GC GC TO VERIFY IF EXISTING MIRROR WILL BE REPLACED LOW VOLTAGE TEST REPORT GC GC GC

DIVISION 09000 - FINISHES SUPL RCV. INSTL EX'G RELO REMARKS


2-SGH4.0-G002-REV02
DEMISING PARTITIONS (STUDS & INSTALLATION) GC GC GC SEE PLANS FOR EXISTING CONDITIONS
DEMISING PARTITIONS (GYPSUM WALLBOARD) SEE PLANS FOR EXISTING CONDITIONS. G.C. TO PATCH AND REPAIR AS REQUIRED.
Architect / Engineer of Record
GC GC GC
DRYWALL CEILING, WALLS, ENCLOSURES & REQ'D FRAMING GC GC GC
ACOUSTICAL CEILING TILES & GRID GC GC GC
PAINTING, FINISHING, VARNISH, SEALER, ETC. GC GC GC
FLOOR TRANSITIONS/VINYL TILE GC GC GC
PORCELAIN / CERAMIC FLOOR TILE T GC GC
GROUT AND THINSET FOR TILE & ACCESSORIES GC GC GC
WALLCOVERING WC-40 T GC GC
FAUX BRICK WALL PANELS T GC GC
RAY-BAN METAL SOFFIT T T T G.C. TO PROVIDE ALTERNATE PRICING FOR SUPPLY & INSTALL.
RAY-BAN DIAMONDPLATE PLATFORM & FRAMING GC GC GC
STOREFRONT BULKHEAD - MALL GC
WALL BASE GC GC GC
FIBERGLASS REINFORCE PANELS (FRP) GC GC GC
STOREFRONT CONCRETE PANELS GC GC GC
MALL FLOORING GC GC GC WHEN REQUIRED. GC TO OBTAIN FROM LANDLORD OR MATCH WITH LANDLORD APPROVAL. Seal

DIVISION 10000 - SPECIALTIES SUPL RCV. INSTL EX'G RELO REMARKS

RETAIL WALL SIGNAGE T T T G.C. TO COORDINATE SIGN INSTALLATION


GRAPHIC HOLDER T GC GC SEE FIXTURE PLAN FOR MORE INFORMATION
GRAPHICS T GC T SEE FIXTURE PLAN FOR MORE INFORMATION
ACCESSIBILITY SIGNAGE T GC GC SEE FIXTURE PLAN FOR MORE INFORMATION
STORAGE AREA SHELVES & SURFACE MTD. STANDARDS T T T
FIRE EXTINGUISHERS GC GC GC SUGGESTED LOCATION ON PLAN - VERIFY LOCAL REQUIREMENTS
GLAZING FILM - GRAPHIC T T T
STOREFRONT SIGNAGE T T T
STOREFRONT DISPLAY HANGING GRID T GC GC
GLAZING FILM - SOLAR CONTROL T T T N/A
AWNINGS T T T Architect / Engineer Job No.:
RESTROOM ACCESSORIES & HARDWARE GC GC GC
CHAIR RAIL T GC GC
030
LED PANELS & ACCESSORIES T GC T GC TO PROVIDE SECURE AREA FOR STORAGE. GC TO DISPOSE OF PACKAGING FOLLOWING VENDOR UNPACKAGEING. DATA & POWER BY GC. Nextore Store Design Revision No.:
GC TO PROVIDE DATA LINE CONDUIT FROM LED PANELS TO COMPUTER.
STOREFRONT DECORATIVE METAL T T T G.C. TO PROVIDE ALTERNATE PRICING FOR SUPPLY & INSTALL.

DIVISION 12000 - FURNISHINGS SUPL RCV. INSTL EX'G RELO REMARKS


DES REV 02
MILLWORK (RETAIL) T GC T RECEIVED & OFFLOADED BY G.C. / UNCRATED & INSTALLED BY TENANT. CONSULT NEXTORE PM FOR POSSIBLE INSTALLATION REQ.
Nextore project
POS EQUIPMENT T T T G.C. TO COORDINATE RELOCATION TO NEW CASHDESK
Number 77889
MERCHANDISE PROPS T T T
FURNITURE (CHAIRS, BENCHES, TABLES, ETC.) T GC T Brand Design Type:
STAPLES PURCHASED ITEMS T T T
SGH 4.1 - TIER B GOLD
WALK-OFF MAT GC GC GC NOT USED
TOILET ACCESSORIES GC GC GC NEW TOILET ACCESSORIES PROVIDED FOR EXISTING TOILET ROOM
MANAGER'S COUNTER(S) EXISTING NO WORK ISSUED FOR:
X Construction
MILLWORK (EMPLOYEE AREA) T GC GC
REFRIGERATOR & MICROWAVE T GC GC
DISPLAY MONITORS T T T

1-SGH4.0-G002-REV02 Title

RESPONSIBILITY
SCHEDULE

Date Sheet
11-28-18
Drawn By

Checked By
STAFF G002
STAFF
DESIGN & CONSTRUCTION

SPECIFICATIONS (1 OF 4) MANAGEMENT:

DIVISION 01000 - GENERAL REQUIREMENTS C. CODES AND STANDARDS 01542 CRANES AND HOISTS 3. GENERAL CONTRACTOR IS RESPONSIBLE FOR PATCHING, REPAIRING AND DIVISION 04000 - MASONRY a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000

01000 GENERAL NOTES 1. ALL WORK, MATERIALS, AND INSTALLATION SHALL BE IN STRICT PART 1 - GENERAL LEVELING OF THE EXISTING FLOOR SLAB, REPAIR OF DEMISING WALLS AND NO WORK UNDER THIS SECTION a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484

PART 1 - GENERAL ACCORDANCE WITH ALL ORDINANCES, STATE AND LOCAL BUILDING CODES, A. GENERAL CONTRACTOR AND/OR SUB-CONTRACTOR ARE RESPONSIBLE ROOF DECK AFTER COMPLETION OF ALL DEMOLITION AND PRIOR TO THE
A. DRAWINGS AND SPECIFICATIONS ARE INTENDED TO BE LATEST EDITION. SEE TITLE SHEET FOR SPECIFIC EDITIONS. AND SHALL INCLUDE IN THEIR BIDS ALL NECESSARY EQUIPMENT INCLUDING COMMENCEMENT OF NEW CONSTRUCTION.COORDINATE WITH LANDLORD DIVISION 05000 - METALS
COMPLIMENTARY. SPECIFIC INFORMATION MAY BE FOUND IN EITHER OR 2. DESIGN LOADS: LOADS AND CODE RESTRICTIONS FOR ALL DESIGN CRANES, HOISTS, SCAFFOLDING, PLATFORMS, ETC., REQUIRED FOR ERECTION RESPONSIBILITY IN PERFORMING ANY AND ALL ROOF WORK. 05120 STRUCTURAL STEEL
BOTH. CONSIDERATIONS SHALL CONFORM TO THE LOCAL AND STATE CODES AND OF BUILDING COMPONENTS, EQUIPMENT AND ALL TENANT SUPPLIED ITEMS AS PART 1 - GENERAL
B. BIDDING CONTRACTORS SHALL INCLUDE ALL LABOR, MATERIALS, ALL GOVERNING CODES. LOCATED ON PLANS. CONTRACTOR SHALL PAY ALL RELATED FEES, PERMITS, A. PROVIDE ALL LABOR, MATERIAL AND EQUIPMENT NECESSARY FOR
DIVISION 03000 - CONCRETE
SCAFFOLDING, CRANES, EQUIPMENT FASTENERS ETC. NECESSARY FOR ETC. PROTECTION OF THE PUBLIC AND EXISTING IN-PLACE WORK IS THE COMPLETE INSTALLATION OF STEEL FRAMING AND SUPPORT MEMBERS,
COMPLETION AND FINAL COMPLETE TURNOVER OF AN OPERATIONAL RETAIL D. TRASH REMOVAL RESPONSIBILITY OF THE GENERAL CONTRACTOR. 03300 CAST-IN-PLACE CONCRETE ANGLES, PLATES, ANCHOR BOLTS REQUIRED FOR THE CONNECTION, SETTING
Construction for:
FACILITY. 1. ALL TRADES SHALL CONFINE CONSTRUCTION WORK TO WITHIN LEASED PART 1 - GENERAL AND BEARING OF COMPLETE STRUCTURE AS SHOWN ON THE DRAWINGS OR
C. THE TENANT HAS INDICATED AN INTENTION TO USE AMERICAN PREMISES AS MUCH AS POSSIBLE AND SHALL WORK IN AN ORDERLY MANNER 01700 CLEANING / ADJUSTING / MAINTENANCE / WARRANTIES A. PROVIDE AND INSTALL CONCRETE AS INDICATED ON THE DRAWINGS. SPECIFIED HEREIN.
INSTITUTE OF ARCHITECTS DOCUMENT A-107 "GENERAL CONDITIONS OF THE REMOVING TRASH AND DEBRIS FROM PROJECT ON A DAILY BASIS INCLUDING PART 1 - GENERAL B. SEE STRUCTURAL DOCUMENTS FOR ADDITIONAL SPECIFICATIONS /
B. CONCRETE WORK SHALL CONFORM TO THE LATEST EDITION OF
CONTRACT FOR CONSTRUCTION" AS PART OF THE CONTRACT DOCUMENTS TRASH AND DEBRIS GENERATED BY TENANT SUPPLIED AND/OR INSTALLED A. FINAL CLEANING STANDARDS.
"AMERICAN CONCRETE INSTITUTE" CODES AND STANDARDS INCLUDING ACI
FOR THIS WORK. ITEMS. AT NO TIME WILL PIPES, WIRES, BOARD, OR OTHER CONSTRUCTION 1. REMOVE WASTE AND SURPLUS MATERIALS, RUBBISH AND C. THE STRUCTURE IS DESIGNED TO BE SELF-SUPPORTING AND STABLE
301, ACI 315, AND ACI 318.
D. ALL PERSONS INTENDING TO PROVIDE GOODS OR SERVICES IN MATERIALS CROSS PUBLIC AREAS WHERE HARM COULD BE CAUSED TO THE CONSTRUCTION DEBRIS FROM SITE. GENERAL CONTRACTOR TO AFTER THE PROJECT IS FULLY COMPLETED. IT IS THE CONTRACTOR'S SOLE
CONNECTION w/THE WORK ARE ADVISED TO READ AND UNDERSTAND THE PUBLIC. PROVIDE A PROFESSIONAL CLEANING SERVICE TO EXECUTE FINAL CLEANING C. CONCRETE STRENGTHS ARE AS FOLLOWS: CLASS 1 3000 PSI INTERIOR RESPONSIBILITY TO DETERMINE ERECTION PROCEDURE AND SEQUENCE AND
APPLICABLE ADA DOCUMENTS PRIOR TO PROCEEDING. 2. MALL DOORS ARE NOT TO BE PROPPED OPEN BY CONSTRUCTION PRIOR TO TURN-OVER. SEE TITLE SHEET, "GENERAL NOTES", FOR ADDITIONAL SLABS (OR MIN.REQUIRED PER LANDLORD SPECIFICATIONS.) TO INSURE STABILITY OF THE BUILDING AND ITS COMPONENT PARTS AND

4000 Luxottica Place Mason, Ohio 45040


A Subsidiary of the Luxottica Group
E. THE TENANT HAS AWARDED SEPARATE CONTRACTS FOR SOME WORKERS AT ANY TIME. INFORMATION. D. REINFORCEMENT (PER LANDLORD REQUIREMENTS) ADEQUACY OF TEMPORARY SUPPORT DURING ERECTION. THIS INCLUDES THE
CONSTRUCTION WORK THAT WILL BE CONDUCTED SIMULTANEOUSLY WITH 3. THERE WILL BE NO STORAGE OF MATERIAL OR RUBBISH IN CORRIDORS B. ADJUSTING E. BONDING AGENT (IF REQUIRED) ADDITION OF WHATEVER TEMPORARY BRACING, GUY OR TIE DOWNS MIGHT BE
WORK UNDER THIS CONTRACT. GENERAL CONTRACTOR MUST COOPERATE OR OTHER LANDLORDAREAS AT ANY TIME. IF DEBRIS IS FOUND IN THIS AREA, 1. ADJUST OPERATING PRODUCTS AND EQUIPMENT TO ENSURE SMOOTH 1. "SONOBOND" EPOXY CONCRETE BONDING AGENT OR EQUAL NECESSARY. SUCH MATERIAL IS NOT SHOWN ON DRAWINGS. IF APPLIED,
WITH ALL OTHER CONTRACTORS SO THAT WORK UNDER THOSE CONTRACTS IT WILL BE REMOVED AT THE EXPENSE OF THE CONTRACTOR THAT IS AND UNHINDERED OPERATION. a. MANUFACTURER: CHEMTREX, INC. THEY SHALL BE REMOVED AS CONDITIONS PERMIT AND SHALL REMAIN
MAY BE CARRIED OUT SMOOTHLY, WITHOUT INTERFERING WITH, OR DELAYING RESPONSIBLE. C. OPERATION AND MAINTENANCE DATA 889 VALLEY PARK DRIVE CONTRACTOR'S PROPERTY.
WORK UNDER THIS CONTRACT. 4. ALL SUB TRADES SHALL COORDINATE REMOVAL OF DEBRIS AND 1. SUBMIT DATA BOUND IN 8-1/2x11 INCH TEXT PAGES, THREE D SIDE RING D. PROVIDE OPENINGS AND SPECIAL FRAMING REQUIRED BY OTHER
SHAKOPEE, MINNESOTA 55379-1854
F. PRIOR TO START OF CONSTRUCTION, GENERAL CONTRACTOR SHALL GARBAGE GENERATED BY THEIR TRADES WITH THE G.C. BINDER WITH DURABLE PLASTIC COVERS. TRADES. MECHANICAL FRAMING LOADS, OPENINGS, AND STRUCTURE RELATED
ARRANGE A MEETING WITH LANDLORD'S CONSTRUCTION REPRESENTATIVE TO 5. THE G.C. SHALL BE RESPONSIBLE FOR THE REMOVAL OF ALL DEBRIS 2. PREPARE BINDER COVER WITH PRINTED TITLE "OPERATION AND TO MECHANICAL REQUIREMENTS ARE SHOWN FOR BIDDING PURPOSES ONLY.
REVIEW AND ESTABLISH ALL LANDLORD REQUIREMENTS. THIS INCLUDES, BUT IS INCLUDING PACKAGING MATERIAL OF MILLWORK. MAINTENANCE INSTRUCTIONS", WITH TITLE OF PROJECT, LOCATION AND DATE, 2. CONSULT MANUFACTURER FOR APPLICATION PROCEDURE. CONTRACTOR SHALL OBTAIN WRITTEN SIGN-OFF FROM MECHANICAL AND
NOT LIMITED TO, THE FOLLOWING: ALL CONSTRUCTION, SCHEDULES, AND SUBMIT TO TENANT'S CONSTRUCTION MANAGER. ASTM C881 OTHER TRADES FOR SPECIFIC REQUIREMENTS BEFORE PROCEEDING WITH SUCH
E. ROOF CUTTING AND PATCHING
WORKMAN PARKING, DELIVERY AND STORAGE OF MATERIALS, SAFETY D. WARRANTIES AND BONDS WORK. ARCHITECT'S OR ENGINEER'S APPROVAL OF ERECTION AND SHOP
1. CUTTING AND PATCHING FOR ALL ROOF OPENINGS SHALL BE
PROTECTION, TRASH REMOVAL, SECURITY, AND DOCUMENTS REQUIRED FOR 1. EXECUTE AND ASSEMBLE TRANSFERABLE WARRANTY DOCUMENTS FROM F. VAPOR BARRIER DRAWINGS SHALL NOT RELIEVE CONTRACTOR FROM THIS RESPONSIBILITY.
PERFORMED BY LANDLORDS ROOFING CONTRACTOR, IF SO REQUIRED BY THE
FINAL LANDLORD SIGN-OFFS. GENERAL CONTRACTOR IS TO NOTIFY TENANT'S SUBCONTRACTORS, SUPPLIERS, AND MANUFACTURERS. 1. SLAB ON GRADES TO RECEIVE 6 MIL. CLEAR OR BLACK POLYETHYLENE E. VERIFY THE EXACT SIZE AND LOCATION OF ALL OPENINGS PRIOR TO
LANDLORD, ENGAGED BY TENANTS GENERAL CONTRACTOR.
CONSTRUCTION MANAGER IMMEDIATELY OF ANY ITEM THAT MAY AFFECT THE FILM WITH MINIMUMOF 12" OVERLAP. TAPE ALL SEAMS. FABRICATION OF STEEL FRAMING MEMBERS.
2. THE LANDLORDS ROOFING CONTRACTOR WILL, AT SUBTRADES WRITTEN
DESIGN INTENT OF THE DRAWINGS, OR RESULT. END OF DIVISION F. SHOP DRAWINGS: SUBMIT SHOP DRAWINGS TO ARCHITECT INDICATING
REQUEST AND COST, PROVIDE THE OPENINGS, ANCHORING DEVISES, CURBS,
G. ANY ITEMS DIRECTED BY LANDLORD, INSPECTORS, OR ANY OTHER PART 2 - PREPARATION / EXECUTION SHOP AND ERECTION DETAILS, INCLUDING CUTS, CONNECTIONS, HOLES,
FLASHINGS, PATCHING, ETC., AS REQUIRED FOR TENANTS EQUIPMENT SO AS
AUTHORITY THAT AFFECTS THE DESIGN INTENT OF THE DRAWINGS, OR DIVISION 02000 - SITE WORK A. CONCRETE CONTRACTOR SHALL ASSUME FULL RESPONSIBILITY FOR THREADED FASTENERS AND WELDS.
TO MAINTAIN THE INTEGRITY AND GUARANTEE OF THE ROOF. ALL SUBTRADES
RESULTS IN ADDITIONAL COSTS OR SCHEDULE DELAYS SHOULD NOT BE STRENGTH, CONSISTENCY PROPORTIONS AND HANDLING OF CONCRETE. G. PRE-ASSEMBLE ITEMS IN SHOP TO GREATEST POSSIBLE EXTENT TO
SHALL INCLUDE THE COST OF SUCH OPENINGS, ETC. IN THEIR PROPOSALS TO 02060 BUILDING DEMOLITION
PERFORMED UNTIL RECEIPT OF APPROVAL BY TENANT'S CONSTRUCTION B. VERIFY THAT COMPACTED GRANULAR BASE IS IN PLACE AND READY TO MINIMIZE FIELD SPLICING AND ASSEMBLY. DISASSEMBLE UNITS ONLY AS
TO THE GENERAL CONTRACTOR DURING BIDDING. SUBTRADES SHALL PART 1 - GENERAL
MANAGER. ALL CHANGES MUST IMMEDIATELY BE SUBMITTED IN WRITING TO SUPPORT PAVINGAND IMPOSED LOADS. NECESSARY FOR SHIPPING AND HANDLING LIMITATIONS. CLEARLY MARK UNITS
COORDINATE WITH THE LANDLORD AND/OR ROOFING CONTRACTOR AND A. SELECTIVE DEMOLITION
TENANT'S CONSTRUCTION MANAGER FOR REVIEW. SUBMISSION SHALL C. VERIFY GRADIENT AND ELEVATIONS OF BASE ARE CORRECT. THICKNESS FOR RE-ASSEMBLY AND COORDINATE INSTALLATION.
ALSO REIMBURSE HIM FOR SAME. 1. THIS SECTION IS INCLUDED FOR GENERAL REFERENCE OF WORK TO BE
INCLUDE A GENERAL DESCRIPTION OF THE WORK REQUESTED, SIGNED BY THE AND REINFORCING AS SHOWN ON DRAWINGS. H. WELDING PROCEDURES, WELDERS, WELDING OPERATIONS AND TACKERS Revisions:
3. ROOF REPAIRS OR PENETRATIONS REQUIRED BY REMOVAL OR REMOVED BY THE GENERAL CONTRACTOR.
REQUESTING AUTHORITY. IN ADDITION, SUBMISSION MUST INCLUDE A COST D. IMMEDIATELY AFTER PLACEMENT, PROTECT PAVEMENT FROM SHALL BE QUALIFIED IN ACCORDANCE WITH AWS-D1.1- "STRUCTURAL Mark Date By
RELOCATION OF EXISTING EQUIPMENT OR INSTALLATION OF NEW EQUIPMENT 2. CONSULT DEMOLITION PLANS INCLUDED WITH PROJECT DOCUMENTS
BREAKDOWN AND THE IMPACT TO THE CONSTRUCTION SCHEDULE. MECHANICAL INJURY. WELDING CODE". 1 11-28-18
(CUTTING OF ROOF AND DECK MATERIAL AND/OR REPAIR OF THE SAME) SHALL FOR ADDITIONAL NOTES AND SITE SPECIFIC ITEMS. E. DEPOSIT CONCRETE WITHIN ANY ONE SECTION CONTINUOUSLY SO I. FABRICATOR SHALL BE A MEMBER OF AMERICAN INSTITUTE OF STEEL LANDLORD COMMENTS / PERMIT SET

01005 CONTRACTORS USE OF THE PREMISES. BE COORDINATED WITH THE LANDLORD'S REPRESENTATIVE. 3. DEMOLITION INCLUDES REMOVAL OF THE EXISTING INTERIORS, IF THAT NO CONCRETE WILL BE PLACED ON OLDER CONCRETE WHICH HAS SET CONSTRUCTION.
PART 1 - GENERAL F. DELIVERIES REQUIRED, BUT NOT LIMITED TO INTERIOR PARTITIONS, CABINETS, SUSPENDED SUFFICIENTLY TO RESULT IN SEAMS AND PLANES OF WEAKNESS WITHIN J. FABRICATE STRUCTURAL STEEL IN ACCORDANCE WITH AISC
A. THE GENERAL CONTRACTOR AND ALL CONTRACTORS BIDDING ON THIS 1. GENERAL CONTRACTOR IS RESPONSIBLE FOR UNLOADING ALL TENANT CEILING TILE, ELECTRICAL, MECHANICAL, ETC., AS REQUIRED, AS SHOWN OR AS SECTION. "SPECIFICATIONS FOR DESIGN, FABRICATION AND ERECTION OF STRUCTURAL
PROJECT SHALL VISIT THE JOB SITE TO FAMILIARIZE THEMSELVES WITH ACTUAL PROVIDED ITEMS AT THE JOB SITE INCLUDING A HEAVY AMOUNT OF DIRECTED. F. PLACE SLABS FOR FULL THICKNESS IN ONE OPERATION, WITHOUT STEEL FOR BUILDINGS" AND "CODE OF STANDARD PRACTICE".
JOB CONDITIONS AND TO CHECK FOR ANY INTERFERENCE BETWEEN THEIR MILLWORK WHICH IS TENANT SUPPLIED. THESE TENANT SUPPLIED ITEMS SHALL 4. ALL ITEMS INDICATED OR REQUIRED TO BE DEMOLISHED OR REMOVED CHANGES IN PROPERTIES; SCREED TO PROPER ELEVATION; FLOAT AND LIGHTLY
WORK AND THAT OF OTHER TRADES AND/OR APPARENT VIOLATIONS OF BE THE G.C.'S RESPONSIBILITY TO UNLOAD, STORE, AND DELIVER TO PROPER TO BE LEGALLY DISPOSED OF IN COORDINATION AND COMPLIANCE WITH ALL TROWEL. UNLESS OTHERWISE SPECIFIED, WHEN CONCRETE HAS SET 1. UNLESS OTHERWISE SHOWN, FABRICATOR SHALL DESIGN / DETAIL
LOCAL, STATE, OR FEDERAL CODES, LAWS, ORDINANCES, AND REGULATIONS STORE AREAS WHEN REQUIRED. SEE TITLE SHEET, "GENERAL NOTES", FOR LANDLORD PROCEDURES AND REGULATIONS. SUFFICIENTLY TO RING UNDER TROWEL, GIVE SLAB SECOND TROWELING TO CONNECTIONS IN CONFORMANCE WITH AISC STANDARD FOR FORCES AND
BEFORE ENTERING INTO A CONTRACT WITH EITHER THE GENERAL ADDITIONAL NOTES, PROCEDURES, AND RESPONSIBILITIES. 5. ALL ITEMS INDICATED TO BE RELOCATED OR REINSTALLED TO BE PRODUCE SMOOTH, DENSE SURFACE. DUSTING OF SURFACES WITH CEMENT IS MOMENTS SHOWN.
CONTRACTOR AND/OR TENANT. 2. THE GENERAL CONTRACTOR IS RESPONSIBLE TO COORDINATE CLEANED, SERVICED AND PREPARED FOR PROPER RE-USE. ANY ITEMS STORED PROHIBITED. % OPTIMUM DENSITY. PROVIDE MIN. 6" COMPACTED 2. WHERE FASTENING SPACINGS OR SIZES ARE NOT SHOWN, CONTRACTOR
1. ALL ITEMS SHALL BE INCLUDED IN THE BASE BID TO ACHIEVE THE FINAL ACCEPTABLE HOURS FOR DELIVERY AND LOCATION OF DELIVERY OF BUILDING DURING CONSTRUCTION ARE TO BE PROTECTED TO AVOID DAMAGE OR THEFT G. COMPACT SUB GRADE FOR SLABS ON GRADE TO 95 CRUSHED GRAVEL SHALL USE SPACINGS AND SIZES OF BOLTS, SCREWS, WELDS, ETC., WHICH WILL
PRODUCT INDICATED IN DRAWINGS. THIS INCLUDES, BUT IS NOT LIMITED TO, PRODUCTS AND TENANTS ITEMS WITH LANDLORD'S REPRESENTATIVE. 6. ALL ITEMS INDICATED AS EXISTING TO REMAIN , SHALL BE CLEANED, SUB-BASE AT ALL AREAS TO RECEIVE NEW CONCRETE. DEVELOP THE FULL STRENGTH OF THE MEMBERS BEING FASTENED. THUS
THE FOLLOWING: CONCRETE FLOOR PREP, FLOOR SLAB X-RAYING, DEMISING SERVICED AND PREPARED FOR PROPER CONTINUED RE-USE. PROTECT ALL H. FINISHES FAILURE DUE TO OVER-STRESSING MUST OCCUR IN THE MEMBERS BEFORE
WALL GYPSUM BOARD EXTENT AND CONDITION, REQUIRED FIRE PROOFING, 01041 PROJECT COORDINATION ITEMS SUFFICIENTLY DURING CONSTRUCTION TO AVOID DAMAGE OR THEFT. 1. GIVE TYPICAL INTERIOR FLOOR SLABS A STEEL TROWEL FINISH WITH OCCURRING IN THE FASTENINGS.
ELECTRICAL PANELS, ELECTRICAL, WATER, SEWER, VENTS AND TELEPHONE PART 1 - GENERAL 7. COOPERATE AND COORDINATE WITH LANDLORD, THE TENANTS OF THE CLASS A TOLERANCE (TRUE PLANES WITHIN 1/8 IN 10 FT. AS DETERMINED BY A PART 2 - PREPARATION / EXECUTION Architect / Engineer of Record
CONDUITS, ANY LANDLORD REQUIRED FIRE PROTECTION SYSTEM OR TIE-INS A. ALL PROJECT COORDINATION SHALL BE THROUGH TENANT'S ADJACENT SPACES AND THE TENANT, IN SCHEDULING WORK IN ORDER TO 10 FOOT STRAIGHTEDGE PLACED ANYWHERE ON SLAB IN ANY DIRECTION). A. PRE-ASSEMBLE ITEMS IN SHOP TO GREATEST POSSIBLE EXTENT TO
TO BLDG. MANAGEMENT SYSTEMS, FIRE EXTINGUISHERS, AND STRUCTURAL CONSTRUCTION MANAGER AS LISTED ON TITLE SHEET. CAUSE THE LEAST INCONVENIENCE TO PERSONNEL AND PROPERTY. I. PROVIDE SAW CUT CONTROL JOINTS 1/8" WIDTH x 1" DEEP AT MAXIMUM MINIMIZE FIELD SPLICING AND ASSEMBLY. DISASSEMBLE UNITS ONLY AS
REQUIREMENTS FOR TENANT'S EQUIPMENT. B. COMPLY WITH CONSTRUCTION MANAGER'S PROCEDURES FOR 8. SEE MECHANICAL AND ELECTRICAL PLANS FOR SPECIFIC DEMOLITION 400 SQUARE FOOT AREA. NECESSARY FOR SHIPPING AND HANDLING LIMITATIONS. CLEARLY MARK UNITS
2. GENERAL CONTRACTOR SHALL NOTIFY THE ARCHITECT AND TENANT IN INTRA-PROJECT COMMUNICATIONS; SUBMITTALS, REPORTS AND RECORDS, ITEMS UNDER THOSE TRADES. J. APPLY BONDING AGENT (AS SPECIFIED) TO ADJACENT CONCRETE FOR RE-ASSEMBLY AND COORDINATE INSTALLATION.
WRITING BEFORE ENTERING INTO A CONTRACT WITH THE TENANT IF ANY SCHEDULES, COORDINATION DRAWINGS, RECOMMENDATIONS; AND SURFACES IMMEDIATELY PRIOR TO PLACEMENT OF CONCRETE. B. SHOP CONNECTIONS SHALL BE WELDED.
INTERFERENCE OR VIOLATIONS APPEAR AND DEPARTURE FROM THE DESIGN PART 2 - PREPARATION / EXECUTION
RESOLUTION OF AMBIGUITIES AND CONFLICTS, INCLUDING REQUESTS FOR K. EXPANSION JOINT MATERIAL: 1/2" PRE MOLDED ASPHALT IMPREGNATED C. FIELD CONNECTIONS: HIGH STRENGTH FASTENERS SHALL BE USED FOR
INTENT OF THE DOCUMENTS IS REQUIRED. A. ARRANGE WITH THE LANDLORD A CONVENIENT TIME TO PERFORM
SUBSTITUTIONS AND CHANGE ORDERS. FIBERBOARD, SAME DEPTH AS CONCRETE. BOLTED CONNECTIONS.
3. FAILURE TO PROVIDE ARCHITECT AND TENANT'S CONSTRUCTION DEMOLITION WORK AND INSTALL TEMPORARY PROTECTED MEANS OF EGRESS
01200 PRICE, PAYMENT, AND CONTRACT FROM REQUIRED EXITS. INCLUDE TEMPORARY LIGHTING AND SAFETY DEVICES, 1. STRUCTURAL STEEL FY 36 KSI STEEL, ASTM A36.
MANAGER WITH THE AFOREMENTIONED NOTIFICATION SHALL RESULT IN THE 03732 CONCRETE REPAIR 2. STRUCTURAL STEEL TUBING: FY 46 KSI COLD-FORMED TUBING EXCEPT
GENERAL CONTRACTOR BEING HELD RESPONSIBLE TO COMPLETE ALL WORK PART 1 - GENERAL ALL IN ACCORDANCE WITH GOVERNING STATE AND LOCAL CODES AND
A. BIDDING CONTRACTORS SHALL PREPARE A BID, WHICH SHALL BE PART 1 - GENERAL ROUND, ASTM A500-68, GRADE B.
REQUIRED TO MEET THE DESIGN INTENT OF THE CONTRACT DOCUMENTS AT LAND-LORD REQUIREMENTS.
SUBMITTED IN ACCORDANCE WITH INSTRUCTIONS TO BIDDERS CONTAINED A. THE EXTENT OF CONCRETE REPAIR WORK INCLUDES REMAINING FLOOR 3. STEEL PIPE: ASTM A53, GRADE B.
HIS/HER OWN COSTS WITH NO ADDITIONAL EXPENSES (EXTRAS) BEING B. THE CONTRACTOR SHALL REMOVE, REPAIR, RESTORE, AND REPLACE Seal
WITHIN BID DOCUMENT PACKAGE. AREAS AFTERDEMOLITION PROVIDING A LEVEL FLOOR THROUGHOUT TO 4. ANCHOR BOLT: CONFORM TO ASTM A307.
INCURRED BY THE TENANT. EXTRAS WILL NOT BE ALLOWED FOR JOB SITE WHERE ANY SUCH WORK IS NECESSARY OR AS INDICATED ON THE DRAWINGS.
B. PAYMENT SCHEDULE FOR PROJECT WILL BE ON A MONTHLY SUBMITTAL RECEIVE FUTURE FINISHES. 5. WELDING ELECTRODES: ASTM A233, E-70 OR BETTER.
CONDITIONS THAT WERE READILY VISIBLE OR DETERMINED. CUT ALL NECESSARY OPENINGS, AND PATCH/REPAIR/SEAL SAME TO DEGREE
OF AIA DOCUMENT #G702 AND #G703 "APPLICATION AND CERTIFICATE FOR B. COMPLY WITH MANUFACTURER'S REQUIREMENTS FOR INSTALLATION OF 6. HIGH STRENGTH THREADED FASTENERS: ASTM A325 OR A-490.
4. ALL SUB TRADES SHALL COORDINATE THEIR WORK WITH THE WORK OF NECESSARY TO SATISFY ALL REQUIREMENTS. INSOFAR AS POSSIBLE, ALL
PAYMENT" UNLESS OTHERWISE REQUESTED BY TENANT. ITEMS AND FINISHES BY OTHER TRADES, INCLUDING THOSE ITEMS AND 7. METAL STUDS: SIZE ACCORDING TO CONSTRUCTION DOCUMENTS x 20
OTHERS OR WITH EXISTING CONDITIONS OCCURRING ABOVE OR BELOW THE PROTRUSIONS, MARKS, CRACKS OR OTHER EVIDENCE OF A DEFICIENT OR
C. CONTRACT SHALL BE AIA DOCUMENT #A107 "STANDARD FORM OF FINISHES PROVIDED AND/OR INSTALLED BY TENANT. GAUGE STEEL AT 16" O.C. TRACKS TO BE ANCHORED BY MEDIUM POWER
LEASED PREMISES AND SHALL MAKE CHANGES FROM TIME TO TIME AS DAMAGED CONDITION SHALL BE ELIMINATED, UNLESS SPECIFICALLY NOTED
AGREEMENT BETWEEN OWNER AND CONTRACTOR". C. FLOOR LEVELER CONCRETE TO BE INSTALLED AT LOW AREAS, HOLES ACTUATED FASTENERS @ 24" O.C.
REQUESTED TO ACCOMMODATE SUCH WORK OR CONDITIONS AT NO CHARGE OTHERWISE. ANY PARTS WHICH ARE SPLIT, CRACKED, CHIPPED, SPALLED,
AND DEPRESSIONS. PATCH CRACKS AND BROKEN CONCRETE WITH FLOOR 8. EXTERIOR / INTERIOR METAL STUDS: SIZE ACCORDING TO
TO TENANT. BROKEN, MISSING, OR OUT OF LINE OR ADJUSTMENT, MECHANICALLY OR
01400 QUALITY/GUARANTEE PATCH TROWELED SMOOTH IN ACCORDANCE WITH MANUFACTURER'S CONSTRUCTION DOCUMENTS X 25 GAUGE AT 16" O.C..
5. CONTRACTORS SIGNS OR SIGNS OF ANY KIND MAY NOT BE DISPLAYED STRUCTURALLY UNSAFE OR UNSOUND, BENT, TORN OR OTHERWISE DEFICIENT
PART 1 - GENERAL INSTRUCTIONS AND LANDLORD SPECIFICATIONS. UNDERLAYMENT 9. SHOP PAINT PRIMER: STANDARD PRIMER:
ON BARRICADES OR INJURED IN ANY MANNER, SHALL BE REMOVED, REPLACED, RESTORED OR
A. ALL WORK SHALL BE EXECUTED BY TRADESMEN AND MECHANICS COMPOUND TO BE FREE FLOWING, SELF-LEVELING, PUMPABLE, AND a. SSPC PAINT 15
6. THE G.C. SHALL BUILD ON SITE A TEMPORARY LOCKABLE STORAGE AREA. REPAIRED. LANDLORD'S REPRESENTATIVE, ARCHITECT, AND TENANT'S
QUALIFIED, THROUGH EXPERIENCE, IN THEIR RESPECTIVE TRADES. SAID CEMENT-BASED FOR APPLICATIONS FROM ONE INCH THICK TO FEATHERED b. TNEMEC 1009 GRAY METAL PRIMER Architect / Engineer Job No.:
G.C. SHALL ACCEPT ALL TENANT SUPPLIED ITEMS AND STORE THEM SAFELY IN CONSTRUCTION MANAGER MUST BE NOTIFIED IMMEDIATELY OF ANY 030
CONTRACTORS SHALL REMOVE AND REPLACE WITHOUT DELAY AND WORK EDGES. c. MARTIN-SENOUR CO. #664 RED OXIDE ZINC CHROMATE PRIMER
SUCH SPACE. STRUCTURAL OR SAFETY DEFECTS, AND ONLY THE TENANT'S CONSTRUCTION
CONTRARY TO THE CONTRACT DOCUMENTS WHEN SPECIFICALLY DIRECTED. MANAGER IF THE DEFECT(S) ARE LIMITED TO COSMETIC FINISHES. PART 2 - PREPARATION / EXECUTION d. PRATT AND LAMBERT NOXIDE 107, ONE DAY PRIMER-GRAY. E. STEEL Nextore Store Design Revision No.:
A. LAYOUT OF WORK B. GENERAL CONTRACTOR AND/OR SUB CONTRACTOR SHALL GUARANTEE A. CONCRETE REPAIR SHALL BE CLEAN AND FREE FROM OIL, DIRT, LOOSE MILL SCALE AND ANY
C. EXERCISE EXTREME CARE DURING DEMOLITION SO AS NOT TO DAMAGE
1. IMMEDIATELY AFTER DEMOLITION, GENERAL CONTRACTOR TO
ADVISE TENANT OF ANY DISCREPANCIES IN OVERALL WIDTH, LENGTH,
HIS WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR FROM DATE
OF ACCEPTANCE BY THE OWNER. OR DISRUPT ANYUTILITY OR SPRINKLER LINES WHICH MIGHT PASS THROUGH
1. DO NOT PROCEED WITH WORK UNTIL VISITING THE SITE AND
DETERMINING CONDITIONS TO DECIDE METHODS OF REPAIR. COORDINATE
OTHER SUBSTANCE THAT WOULD IMPAIR WELDING, PERFORMANCE OF
FRICTION-TYPE BOLTED.
DES REV 02
AVAILABLE CEILING HEIGHTS, COLUMN LOCATIONS, STOREFRONT, UTILITY THIS SPACE TO SERVICE OTHER MALL SPACES OR TENANTS. GENERAL WITH TENANT'S CONSTRUCTION MANAGER. Nextore project
LOCATIONS, ETC. 01426 PROCEDURES CONTRACTOR WILL BEAR SOLE RESPONSIBILITY OF ANY SUCH DISRUPTION OR 2. REMOVE AND DISPOSE OF EXISTING FLOOR FINISHES WHERE INDICATED 05400 METAL FRAMING Number 77889
2. EXERCISE PROPER PRECAUTION TO VERIFY ALL EXISTING PART 1 - GENERAL DAMAGE. ON DEMOLITION PLAN. LIGHT GAUGE (COLD-FORMED) METAL FRAMING Brand Design Type:
CONDITIONS AND LAYOUT OF CONTRACTOR TO NOTIFY TENANT OF ANY A. ALL ITEMS SHALL BE INSTALLED USING STANDARD PROFESSIONAL D. ALL ABANDONED ELECTRICAL AND TELEPHONE CONDUIT, PLUMBING 3. THOROUGHLY CLEAN FLOOR SLAB REMOVING CONDITIONS THAT WILL PART 1 - GENERAL SGH 4.1 - TIER B GOLD
DISCREPANCIES IMMEDIATELY. CONTRACTOR IS RESPONSIBLE FOR ANY PRACTICES USING FASTENERS, ADHESIVES AND METHODS REQUIRED BY LINES, DRAIN LINES, AND ALL MECHANICAL ITEMS SHALL BE CAPPED AT AFFECT BOND INCLUDING RESIDUE FROM REMOVAL OF ADHESIVES, A. FURNISH AND INSTALL A COMPLETE SYSTEM OF LIGHT GAUGE FRAMING
ERROR RESULTING FROM FAILURE TO EXERCISE SUCH PRECAUTION. SUCH MANUFACTURER AND INDUSTRY MANUALS. SOURCE AND REMOVED IN A MANNER TO MEET ALL LANDLORD AND CODE UNDERLAYMENTS, STAINS, OILS, ETC. MEMBERS FOR INTERIOR WALL PARTITIONS AND CEILING SUSPENSION ISSUED FOR:
ERROR WILL NOT BE CONSIDERED SUBSEQUENTLY AS A BASIS FOR EXTRA REQUIREMENTS, UNLESS DIRECTED OTHERWISE. 4. REMOVE HIGH FLOOR LEVELS AND LOOSE CONCRETE. COMPONENTS. X Construction

COMPENSATION. 01510 TEMPORARY UTILITIES E. GENERAL CONTRACTOR RESPONSIBILITIES 5. ROUGH IN CONCRETE IN AREAS WHERE PATCHING IS REQUIRED, SUCH 1. SYSTEM TO INCLUDE ALL TOP AND BOTTOM RUNNERS, BRACES, CLIP
3. GENERAL CONTRACTOR IS TO LAYOUT WORK AND BE RESPONSIBLE PART 1 - GENERAL 1. GENERAL CONTRACTOR IS TO NOTIFY TENANT IMMEDIATELY OF ANY AS CRACKED, SPALLED, OR HOLES DUE TO REMOVAL OF EXISTING WORK. ANGLES, ACCESSORIES, FASTENERS, ETC. FOR EACH TYPE OF FRAMING AS
FOR ALL LINES, MEASUREMENTS OF THE BUILDING, UTILITIES, AND OTHER A. GENERAL CONTRACTOR TO VERIFY PROVISIONS FOR TEMPORARY SEVERE DISCREPANCIES OR IRREGULARITIES DISCOVERED DURING DEMOLITION 6. GRIND HIGH SPOTS. SHOWN ON DRAWINGS. Title
WORK EXECUTED UNDER THE CONTRACT. UTILITIES INCLUDING ELECTRICITY, LIGHTING, HEAT, VENTILATION, TELEPHONE WHICH MIGHT AFFECT THE CURRENT STORE DESIGN. GENERAL CONTRACTOR 7. AT LOCATIONS OF CONSTRUCTION JOINTS IN EXISTING SLAB, CONTINUE a. INSTALL METAL FRAMING SYSTEMS IN ACCORDANCE WITH
4. SHOULD A CONTRACTOR FIND DISCREPANCIES IN, OR OMISSIONS SERVICE, WATER AND SANITARY FACILITIES. G.C. TO INCLUDE A FULL TIME IS TO PAY SPECIAL ATTENTION TO AVAILABLE HEIGHT FOR INTENDED CEILING JOINTS THROUGH NEW FLOOR IN LEVELING AREA. SAW CUT JOINT OR PLACE MANUFACTURER'S INSTALLATION INSTRUCTIONS AND RECOMMENDATIONS. SPECIFICATIONS
FROM THE DRAWINGS OR SPECIFICATIONS, OR SHOULD HE BE IN DOUBT ELEVATION, MECHANICAL DUCTWORK AND RECESSED LIGHTING. B. QUALITY ASSURANCE - DESIGN AND ANALYSIS OF STRUCTURAL
AS TO THEIR MEANING, HE SHALL AT ONCE NOTIFY THE ARCHITECT AND
PHONE AND FAX ON SITE CAPABLE OF INCOMING CALLS DURING ENTIRE
2. GENERAL CONTRACTOR IS TO ERECT CONSTRUCTION BARRICADES AND
1/16" WIDE METAL BAR IN THE JOINT LOCATION COINCIDENT WITH EXISTING.
PROPERTIES SHALL COMPLY WITH AISI "SPECIFICATION FOR THE DESIGN OF
1 OF 4
CONSTRUCTION PERIOD. 8. TRENCH ONLY AT SLAB ON GRADE. VERIFY AND GET APPROVAL OF
TENANT. DEBRIS/DUCT SCREENS PER LANDLORD'S SPECIFICATIONS. CONTACT TRENCH OR CORE LOCATIONS WITH THE LANDLORDS REPRESENTATIVE AND COLD-FORMED STRUCTURAL STEEL MEMBERS".
LANDLORD'S REPRESENTATIVE PRIOR TO THE COMMENCEMENT OF ALL MALL STRUCTURE PRIOR TO COMPLETING ANY WORK. CORES TO BE SEALED C. MATERIALS: Date Sheet
DEMOLITION WORK. WATERPROOF. SEE SECT. 07200 "INSULATION AND WATERPROOFING" FOR 1. 18 GAUGE AND LIGHTER COMPONENTS: FABRICATE COMPONENTS OF 11-28-18
Drawn By
COMMERCIAL QUALITY STEEL SHEET, ASTM A446 FOR GALVANIZED FINISH WITH
ADDITIONAL WATERPROOFING INFORMATION.
A MINIMUM YIELD POINT OF 33,000 PSI.
STAFF G003
CLEAN AREAS REMOVING ALL WASTE MATERIAL, BROOM CLEAN. Checked By

STAFF
DESIGN & CONSTRUCTION

SPECIFICATIONS (2 OF 4) MANAGEMENT:

2. 16 GAUGE AND HEAVIER COMPONENTS: FABRICATE COMPONENTS b. CERTIFICATES: FURNISH AFFIDAVIT IF REQUIRED BY CODE OFFICIAL PART 2 - PREPARATION / EXECUTION b. MANUFACTURERS: KAWNEER COMPANY, INC. , NORCROSS, GA D. IT IS THE GLAZING CONTRACTORS SOLE RESPONSIBILITY TO VERIFY a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000

OF STRUCTURAL QUALITY STEEL SHEET, ASTM A446 FOR GALVANIZED STATING THAT MATERIALS HAVE BEEN TREATED IN ACCORDANCE WITH A. REMOVE LOOSE MATERIALS AND FOREIGN MATTER WHICH MIGHT UNITED STATES ALUMINUM CORP., ROCK HILL SC THAT THE GLASS IS SIZED TO WITHSTAND DEAD LOADS, POSITIVE AND a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484

FINISH WITH A MINIMUM YIELD POINT OF 50,000 PSI. SPECIFICATIONS AND THAT MOISTURE CONTENT, AFTER TREATMENT, IMPAIR ADHESION OF SEALANT. c. FINAL FINISHES MUST MATCH EXACTLY. COLORS TO BE AS NEGATIVE LIVE LOADS, ACTING NORMAL TO PLANE OF GLASS AS
3. METAL STUDS: AISI "C" TYPE STRUCTURAL STUDS; SIZES, GAUGES DOES NOT EXCEED SPECIFIED LIMITS; INCLUDE CHEMICAL USED AND B. CLEAN AND PRIME JOINTS IN ACCORDANCE WITH SPECIFIED ON FINISH SCHEDULE. CALCULATED IN ACCORDANCE WITH LOCAL AND STATE CODES.
AND SPACINGS SHOWN OR REQUIRED IF NOT SHOWN; WITH 1-5/8" RETENTION OBTAINED FOR PRESSURE TREATED MATERIAL. INCLUDE THE MANUFACTURER'S INSTRUCTIONS. B. ALUMINUM GLAZING FRAME. E. MATERIAL FOR INTERIOR STOREFRONT GLASS:
(41MM) MINIMUM FLANGE WIDTH, 1/2" (13MM) MINIMUM RETURNS AND "QUALITY MARK" OF ASSOCIATION HAVING JURISDICTION OVER THE C. PROTECT ELEMENTS SURROUNDING THE WORK OF THIS SECTION 1. KAWNEER (SEE PARAGRAPH 3 OF THIS SECTION) TRIFAB II 451 SERIES, 1. CLEAR GLASS - ASTM C1048, FT-FULLY TEMP., QUALITY-q3 GLAZING
PRE-PUNCHED HOLES FOR UTILITY INSTALLATION. TREATMENT. FROM DAMAGE OR DISFIGURATION. (MULLION, RAIL, POST AND BASE SIZES AS PER PLANS AND DETAILS) FOR SELECT.
a. 18-22 GAUGE (0.05" / 1.2MM - 0.03" / 0.8MM): ASTM A446/A446M c. DELIVER TREATED MATERIALS BUNDLED AND MARKED TO IDENTIFY D. INSTALL SEALANT IN ACCORDANCE WITH MANUFACTURER'S INFILL WITH 1/2" CLEAR TEMPERED GLASS. 2. THICKNESS AS SHOWN ON PLAN.
GRADE A; MINIMUM YIELD STRESS OF 33 KSI (228 MPA). TREATMENT. INSTRUCTIONS. 2. PROVIDE AND INSTALL ALL INTERNAL SUPPORT FRAMING, RELATED 3. EACH INDIVIDUAL PANE TO RECEIVE TEMPERED STAMP INDICATING
Construction for:
b. 12-16 GAUGE (0.11"/2.7MM - 0.06"/1.5MM): ASTM A446/A446M d. STORE TREATED MATERIALS FOR EASY IDENTIFICATION AND E. INSTALL JOINT BACKING. FLASHINGS, ANCHORAGE AND ATTACHMENT DEVICES. SUCH.
GRADE A; MINIMUM YIELD STRESS OF 40 KSI (276 MPA). PROTECT FROM MOISTURE; PROVIDE WELL VENTILATED DRY STORAGE. F. APPLY SEALANT WITHIN RECOMMENDED APPLICATION 3. MANUFACTURERS: KAWNEER COMPANY, INC., NORCROSS, GA F. MATERIAL FOR EXTERIOR STOREFRONT IN METAL GLAZING SYSTEM.
4. TRACK: ASTM A446/A446M GRADE A; MINIMUM YIELD STRESS OF 33 e. HANDLE TREATED MATERIALS IN ACCORDANCE WITH AWPA TEMPERATURE RANGES. CONSULT MANUFACTURER WHEN SEALANT UNITED STATES ALUMINUM CORP., ROCK HILL, SC 1. INSULATED GLASS UNITS - LOW E - TYPE SG-B - ASTM E774 AND
KSI (228 MPA); FORMED STEEL: CHANNEL SHAPED; SAME WIDTH AND STANDARDS. IN ADDITION TO USED IN TREATMENT, FURNISH ADDITIONAL CANNOT BE APPLIED WITHIN THESE TEMPERATURE RANGES. 4. FINAL FINISH MUST MATCH EXACTLY COLORS AS SPECIFIED ON E773 DOUBLE PANE WITH GLASS ELASTOMER EDGE SEAL; OUTER PANE OF
GAUGE AS ADJACENT STUDS. EXCEPTION: TOP AND BOTTOM TRACK MATERIAL FOR FIELD TREATMENT \ MATERIAL OF CUTS. FINISH SCHEDULE, IF EXACT COLOR IS NOT AVAILABLE THROUGH CLEAR GLASS, INNER PANE OF LOW E CLEAR GLASS ON CLEAR COLOR
(RUNNERS) REQUIRING ATTACHMENT OF METAL PANELS SHALL BE f. FIELD CUTS AND HOLES: FIELD-TREAT IN ACCORDANCE WITH AWPA END OF DIVISION MANUFACTURER PAINT CONTRACTOR SHALL FIELD PAINT. GLASS.
MINIMUM 14 GAUGE (0.08"/1.9MM). M-4. C. GLAZING a. PROVIDE TEMPERED GLASS UNITS WHERE INDICATED ON PLAN OR
5. FASTENINGS: DIVISION 08000 - DOORS AND WINDOWS 1. EXTERIOR - 1/2" CLEAR INSULATED GLASS FOR INFILL INTO GLAZING AS REQUIRED BY JURISDICTIONAL CODES.

4000 Luxottica Place Mason, Ohio 45040


A Subsidiary of the Luxottica Group
a. MANUFACTURER'S RECOMMENDED SELF-DRILLING, SELF-TAPPING TELEPHONE AND ELECTRICAL PANEL BACK BOARDS. 08100 HOLLOW METAL DOORS AND FRAMES FRAME.
SCREWS, BOLTS, NUTS AND WASHERS. NON-CORROSIVE. PART 1 - GENERAL PART 2 - PREPARATION / EXECUTION
b. ANCHORAGE DEVICES: POWER ACTUATED FASTENERS, DRILLED PART 2 - PREPARATION / EXECUTION A. INSTALL ALL DOORS, FRAMES, HARDWARE AND RELATED PARTS PART 2 - PREPARATION / EXECUTION A. VERIFY THAT OPENINGS FOR GLAZING ARE CORRECTLY SIZED AND
EXPANSION BOLTS, OR SCREW WITH SLEEVES. AND MATERIALS AS INDICATED ON DRAWINGS AND RESPONSIBILITY A. VERIFY DIMENSIONS, TOLERANCES AND ATTACHMENTS AND SHIMS WITHIN TOLERANCE.
c. WELDING: COMPLY WITH AWS D1.1 "STRUCTURAL WELDING CODE". A. SET MEMBERS LEVEL AND PLUMB, IN CORRECT POSITION. SCHEDULE. TO PERMIT SUFFICIENT ADJUSTMENTS TO ACCOMMODATE B. VERIFY THAT SURFACES OF GLAZING CHANNELS OR RECESSES ARE
A. MANUFACTURERS: B. COORDINATE PARAPET AND FLASHING NAILER INSTALLATION WITH B. LABELED DOORS: WHERE REQUIRED, PROVIDE U.L. LABEL DOORS IRREGULARITIES. CLEAN, FREE OF OBSTRUCTIONS THAT MAY IMPEDE MOISTURE
1. MILCOR / DIVISION OF INRYCO, INC. BY BOSTWICK STEEL FRAMING, INSTALLATION OF ROOFING. SEE SECTION 01005, E, "ROOF CUTTING AND AND FRAMES PER APPLICABLE STATE AND LOCAL BUILDING CODES. SUCH B. INSTALL PER MANUFACTURER'S RECOMMENDATIONS AND MOVEMENT, WEEPS ARE CLEAR, AND READY TO RECEIVE GLAZING.
THE CECO ALLIED STRUCTURAL INDUSTRIES; DIETRICH INDUSTRIES OR PATCHING". TO RECEIVE LABELS ATTACHED STATING RATINGS. PROCEDURES. C. CUT GLASS PANES TO ACCURATE SIZES ALLOWING FOR EDGE
EQUAL. C. INSTALL TELEPHONE AND ELECTRICAL PANEL BACK BOARDS WITH C. FABRICATE AND ERECT TRUE, PLUMB AND SQUARE AS SPECIFIED C. ALL JOINTS BETWEEN FRAMING AND BUILDING STRUCTURE SHALL BE CLEARANCES AND TOLERANCES.
PLYWOOD SHEATHING MATERIAL WHERE REQUIRED. SIZE THE BACK AND AS DETAILED AND PER MANUFACTURER'S RECOMMENDATIONS. SEALED TO PROVIDE WATERTIGHT INSTALLATION. D. INSTALL SEALANTS RECOMMENDED BY MANUFACTURER WHICH ARE
06100 WOOD BLOCKING AND CURBING BOARD BY 12 INCHES BEYOND SIZE OF ELECTRICAL PANEL. D. INTERIOR HOLLOW METAL DOORS AND FRAMES FOR INSTALLATION D. INSTALL SEALANT AND BACKING MATERIALS AT PERIMETER OF COMPATIBLE WITH MATERIALS THEY WILL BE IN CONTACT WITH.
PART 1 - GENERAL AT DRYWALL AND METAL STUD PARTITIONS. FRAME. E. REMOVE GLAZING MATERIALS FROM FINISH SURFACES.
A. PROVIDE AND INSTALL WOOD FURRING, BLOCKING, GROUNDS AND 06210 MILLWORK AND FINISH CARPENTRY 1. DOORS - 1 3/4" THICK FLUSH MOUNTED "TYPE B" AS F. REMOVE LABELS AFTER WORK IS COMPLETE. CLEAN GLASS AND
IN-WALL BLOCKING FOR SUPPORT OF GRAB BARS, FIXTURES, EQUIPMENT, PART 1 - GENERAL MANUFACTURED BY STEELCRAFT. SURFACES TO BE PHOSPHATIZED AND 08710 DOOR HARDWARE ADJACENT SURFACES.
CASEWORK, HARDWARE, TRIM AND SIMILAR WORK. A. FURNISH AND INSTALL FINISHED TRIM, CABINETRY, COUNTERS, RECEIVE ONE COAT BAKED ON PRIMER READY TO RECEIVE PAINT. PART 1 - GENERAL
1. BLOCKING AND GROUNDS AT STOREFRONT GLAZING , LOCATIONS DOORS, AND ALL FINISH ITEMS SUCH AS LAMINATES AND FINISH DOOR a. SEE DOOR SCHEDULE FOR REQUIRED HARDWARE. A. FURNISH AND INSTALL FINISH HARDWARE FOR INTERIOR AND 08835 MIRROR
AT WEATHER AREAS, AND IN CONTACT WITH CONCRETE SHALL BE HARDWARE, AS INDICATED AND DETAILED ON PLANS. b. PROVIDE 8 GA. REINFORCEMENT AT HINGES, AND 14 GA. EXTERIOR DOORS, ROLLING GRILLES AND WINDOWS. PART 1 - GENERAL
PRESSURE TREATED. B. SEE DRAWINGS AND RESPONSIBILITY SCHEDULE FOR DETAILS, SIZES, REINFORCEMENT AT LOCK AND CLOSERS. B. SEE DOOR SCHEDULE FOR SPECIFIC ITEMS, MANUFACTURERS AND A. FURNISH AND INSTALL CUSTOM FITTED MIRRORS INCLUDING
2. USE NON-COMBUSTIBLE FIRE RETARDANT TREATED (F.R.T.) WOOD DIMENSIONS. 2. FRAMES - 2" FRONT FACE - 16 GA. HOLLOW METAL WITH MODEL NUMBERS. MASTIC AND ATTACHMENT CLIPS AS SIZED AND DETAILED IN DRAWINGS
ELSEWHERE AS REQUIRED BY STATE AND LOCAL CODES, INCLUDING ANY C. FOLLOW AWI (ARCHITECTURAL WOODWORK INSTITUTE) CONTINUOUSLY WELDED CORNERS. SURFACES TO BE PHOSPHATIZED C. FOLLOW DHI (DOOR AND HARDWARE INSTITUTE) STANDARDS AND AND RESPONSIBILITY SCHEDULE. REFER TO TOILET ROOM ACCESSORIES
WOOD STUDS, BLOCKING, FURRING, PLYWOOD, TRIM AND GROUNDS. ARCHITECTURAL WOODWORK QUALITY STANDARDS. AND RECEIVE ONE COAT BAKED ON PRIMER READY TO RECEIVE PAINT. GUIDELINES AND AWI (AMERICAN WOODWORKING INSTITUTE) FOR TENANT-PROVIDED MIRRORS IN LAVATORY. VERIFY WITH TENANT'S
NEW LUMBER TO BEAR GRADE AND TREATMENT OF ASSOCIATION UNDER a. PROVIDE 8 GA. REINFORCEMENT AT HINGES AND 14 GA. STANDARDS FOR HARDWARE INSTALLED ON WOOD DOORS. PROJECT MANAGER. Revisions:
WHICH IT WAS PRODUCED. PART 2 - PREPARATION / EXECUTION REINFORCEMENT AT LOCK AND CLOSERS. D. FIRE RATED HARDWARE SHALL FOLLOW GUIDELINES AS B. CONSULT NAMM (NATIONAL ASSOCIATION OF MIRROR Mark Date By

a. PRESERVATIVE TREATMENT FOR WOOD SPECIFIED ELSEWHERE. A. DO NOT DELIVER OR INSTALL ITEMS UNTIL BUILDING AND ROOMS b. INSTALL ADJUSTABLE JAMB ANCHOR 4" DOWN FROM HEAD AND ESTABLISHED BY: MANUFACTURING) FOR TIPS FOR CARE AND HANDLING OF MIRRORS. 1 11-28-18

1) PERFORMANCE REQUIREMENTS: RECEIVING SUCH ARE COMPLETED AND THOROUGHLY DRY AND FREE OF WELDED-IN BASE ANCHOR AT EACH JAMB. 1. NFPA 80 - FIRE DOORS AND WINDOWS. C. PRODUCT: LANDLORD COMMENTS / PERMIT SET

a) MOISTURE CONTENT: AFTER TREATMENT, THE MAXIMUM MOISTURE EXCESSIVE MOISTURE. 2. NFPA 101 - LIFE SAFETY CODE. 1. CLEAR FLOAT TYPE WITH COPPER/SILVER COATING. UNLESS NOTED
CONTENT OF WOOD MATERIALS SHALL NOT EXCEED THE FOLLOWING: B. MILLWORK AND CABINETRY MAY BE SHOP OR FIELD ASSEMBLED AT PART 2 - PREPARATION /EXECUTION 3. NFPA 252 - FIRE TESTS OF DOOR ASSEMBLIES. OTHERWISE, ALL EDGES SHALL BE POLISHED.
i. LUMBER, 2 INCHES AND LESS IN THICKNESS: 19 PERCENT. CONTRACTORS OPTION. A. INSTALL FRAMES IN ACCORDANCE WITH SDI-100. 4. UL 10B - SAFETY FIRE TESTS OF DOOR ASSEMBLIES. D. MIRROR ADHESIVE: CHEMICALLY COMPATIBLE WITH MIRROR
ii. PLYWOOD: 15 PERCENT C. INSTALL ITEMS IN A RIGID, STRAIGHT, PLUMB, LEVEL MANNER B. COORDINATE WITH WALL CONSTRUCTION FOR ANCHOR 5. UL 305 - SAFETY PANIC HARDWARE. COATING AND WALL SUBSTRATE.
b) FLAME SPREAD: FIRE RETARDANT TREATED MATERIALS TO HAVE FLAME ACCURATELY FITTED AND SCRIBED TO ABUTTING SURFACES. PLACEMENT. E. FURNISH OWNER WITH MAINTENANCE DATA, MAINTENANCE
SPREAD RATING OF 25 OR LESS IN A 30 MINUTE TEST WITH NO EVIDENCE D. COUNTERSINK NAILS AND SCREW HEADS AND PATCH AND SAND C. COORDINATE INSTALLATION OF FRAMES WITH INSTALLATION OF PROCEDURES, MANUFACTURERS WARRANTIES AND SPECIAL TOOLS. PART 2 - PREPARATION / EXECUTION
OF SIGNIFICANT PROGRESSIVE COMBUSTION, ASTM E 84, ADDITIONALLY, SMOOTH. DOORS AND HARDWARE AS SPECIFIED IN DOOR SCHEDULE AND ON F. FINISHES: AS NOTED ON PLANS AND SCHEDULES. A. VERIFY AREAS RECEIVING MIRRORS ARE WITHIN TOLERANCES AND
FLAME FRONT NOT TO PROGRESS MORE THAN 10 1/2 FEET BEYOND E. CUTTING AND REPAIRING OF THIS WORK FOR ACCOMMODATION DRAWINGS. G. KEYING ARE READY TO RECEIVE MATERIAL.
CENTER LINE OF BURNER AT ANY TIME. OF WORK BY OTHERS SHALL BE DONE AS PART OF MILLWORK FOLLOW DOOR HARDWARE INSTITUTE (DHI) GUIDELINES. 1. GENERAL CONTRACTOR TO COORDINATE KEYING AND MASTER B. PLACE PLUMB AND LEVEL WITHOUT VISIBLE DISTORTION.
c) SMOKE DEVELOPED: INTERIOR FINISH AND TRIM MATERIALS, WHERE RESPONSIBILITY. KEYING WITH CONSTRUCTION MANAGER. C. STORE, PROTECT, AND INSTALL MIRRORS IN ACCORDANCE WITH
SPECIFIED, TO HAVE FIRE RETARDANT TREATMENT CONFORMING TO F. FINISH WOODWORK SHALL BE DRESSED AND SANDED, FREE FROM 08110 INSULATED STEEL DOORS 2. GENERAL CONTRACTOR TO INSTALL CONSTRUCTION CORES NAMM.
ABOVE REQUIREMENTS FOR "FLAME SPREAD" PLUS SMOKE DEVELOPED MACHINE AND TOOL MARKS, ABRASIONS, RAISED GRAIN OR OTHER PART 1 - GENERAL DURING CONSTRUCTION AND REPLACE WITH PERMANENT AT END OF D. SET MIRRORS WITH EDGE CLEARANCE FREE OF SURROUNDING
RATING OF 25 OR LESS, ASTM E 84. DEFECTS. A. NON-RATED THERMALLY INSULATED STEEL DOORS AT EXTERIOR JOB PRIOR TO TURN-OVER. CONSTRUCTION INCLUDING COUNTERTOPS OR BACKSPLASHES.
G. PROTECT FINISHED WORK UNTIL ACCEPTANCE BY TENANT. OPENINGS. H. SEE SECTION ON ALUMINUM ENTRANCES FOR HARDWARE SPECIFIC E. REMOVE LABELS AFTER WORK IS COMPLETE. Architect / Engineer of Record
b. CERTIFICATES: FURNISH AFFIDAVIT IF REQUIRED BY CODE OFFICIAL
1. DOORS THERMALLY INSULATED L-16 WITH POLYSTYRENE CORE TO THOSE DOORS F. CLEAN MIRRORS AND ADJACENT SURFACES.
STATING THAT MATERIALS HAVE BEEN TREATED IN ACCORDANCE WITH
SPECIFICATIONS AND THAT MOISTURE CONTENT, AFTER TREATMENT, 06424 LAMINATES (R=7.7): SDI-100 GRADE AS MANUFACTURED BY STEELCRAFT, CINCINNATI, I. MANUFACTURERS:
PART 1 - GENERAL OHIO, OR EQUAL. FRAMES TO BE PHOSPHATIZED AND RECEIVE ONE COAT 1. HINGES: STANLEY FBB 179 AVERAGE FREQUENCY, OR EQUAL. END OF DIVISION
DOES NOT EXCEED SPECIFIED LIMITS; INCLUDE CHEMICAL USED AND
RETENTION OBTAINED FOR PRESSURE TREATED MATERIAL. INCLUDE THE A. INSTALL HIGH PRESSURE LAMINATES AS SPECIFIED IN FINISH BAKED ON PRIMER READY TO RECEIVE PAINT. EXTERIOR DOORS TO RECEIVE TAMPERPROOF BUTTS AND/OR LATCH
SCHEDULE AND AS DETAILED IN DRAWINGS. a. SEE DOOR SCHEDULE FOR REQUIRED HARDWARE. GUARDS. 09120 CEILING SUSPENSION SYSTEMS
"QUALITY MARK" OF ASSOCIATION HAVING JURISDICTION OVER THE
TREATMENT. b. PROVIDE 14 GA. REINFORCEMENT AT CLOSER AND LOCKS AND 8 2. LOCKSETS/LATCHES: SCHLAGE D-SERIES, SPARTA DESIGN w/ROSE, PART 1 - GENERAL
c. DELIVER TREATED MATERIALS BUNDLED AND MARKED TO IDENTIFY PART 2 - PREPARATION / EXECUTION GA. REINFORCEMENT AT HINGES. OR EQUAL. LOCKSETS TO RECEIVE INTERCHANGEABLE CORE CYLINDERS A. PROVIDE ACOUSTICAL PANEL CEILINGS WITH EXPOSED SUSPENSION
TREATMENT. A. FOLLOW MANUFACTURERS GUIDELINES AND RECOMMENDATIONS 2. FRAME - 12 GA. COLD ROLLED STEEL, ARC WELDED AT CORNERS TO ACCEPT "BEST CORE". SEE KEYING NOTES THIS SECTION. GRID, AS SHOWN ON THE DRAWINGS.
FOR ADHESIVE AND SUBSTRATE PREPARATION. AND GROUND SMOOTH AS MANUFACTURED BY STEELCRAFT OR EQUAL. 3. CLOSERS: NORTON - POWER ADJUSTABLE CLOSER FOR BARRIER B. SUSPENSION SYSTEM AND ACOUSTIC PANELS AS LISTED ON
d. STORE TREATED MATERIALS FOR EASY IDENTIFICATION AND
B. SEE MILLWORK SECTION FOR TYPICAL NOTES AND REFERENCES. FRAMES TO BE PHOSPHATIZED AND RECEIVE ONE COAT BAKED ON FREE OPERATION. SERIES 8301 BF OR EQUAL. REFLECTED CEILING PLAN SHEET AND RESPONSIBILITY SCHEDULE.
PROTECT FROM MOISTURE; PROVIDE WELL VENTILATED DRY STORAGE.
PRIMER READY TO RECEIVE PAINT. 4. THRESHOLDS, SWEEPS AND WEATHER STRIPPING: C. REFER TO DRAWINGS FOR LOCATION OF SPECIFIED MATERIALS AND
e. HANDLE TREATED MATERIALS IN ACCORDANCE WITH AWPA
END OF DIVISION a. PROVIDE 14 GA. REINFORCEMENT AT CLOSER AND LOCKS AND 8 THERMAL BARRIER SADDLE THRESHOLD - PEMKO #252X2AFG, FINISHES. WHERE REQUIRED BY CODES, CEILING ASSEMBLIES ARE TO Seal
STANDARDS. IN ADDITION TO USED IN TREATMENT, FURNISH ADDITIONAL
GA. REINFORCEMENT AT HINGES. MAXIMUM HEIGHT 1/2", OR EQUAL. CONFORM WITH UNDERWRITERS LABORATORIES DESIGN FOR ONE HOUR
MATERIAL FOR FIELD TREATMENT \ MATERIAL OF CUTS. DIVISION 07000 - THERMAL AND MOISTURE PROTECTION b. INSTALL MINIMUM THREE (3) JAMB ANCHORS AND BASE ANCHORS DOOR BOTTOM SWEEP - PEMKO #315CN, OR EQUAL. FIRE RATED ASSEMBLIES.
f. FIELD CUTS AND HOLES: FIELD-TREAT IN ACCORDANCE WITH AWPA 07200 INSULATION AND WATERPROOFING
M-4. EACH SIDE. RIGID JAMB WEATHERSTRIP - PEMKO #303AV, OR EQUAL.
PART 1 - GENERAL 5. STOPS, KICKPLATES AND SILENCER; PART 2 - PREPARATION / EXECUTION
A. FOR INSULATION REQUIRED AT DUCKWORK, PLUMBING LINES, ETC. PART 2 - PREPARATION / EXECUTION WALL STOP - IVES #407, OR EQUAL A. AT TIME OF COMPLETION, DELIVER TWO PACKAGES OF ACOUSTICAL PANELS
3. TELEPHONE AND ELECTRICAL PANEL BACK BOARDS. SEE MECHANICAL / ELECTRICAL SPECIFICATIONS AND DRAWINGS. A. INSTALL FRAMES IN ACCORDANCE WITH SDI-100. FLOOR STOP - IVES #436, OR EQUAL TO THE TENANT OF EACH TYPE OF MATERIAL USED, FOR FUTURE REPLACEMENT USE.
B. BATT INSULATION B. COORDINATE WITH MASONRY WALL CONSTRUCTION FOR ANCHOR DOOR SILENCER - IVES #20, OR EQUAL B. COMPLY WITH ASTM C 635 FOR INTERMEDIATE - DUTY CLASS SYSTEM. SIZE
06100 WOOD BLOCKING AND CURBING 1. FURNISH AND INSTALL 3 1/2" MIN. THERMAL BATT TYPE INSULATION PLACEMENT. KICKPLATE - IVES #8400, 8" HIGH X FULL WIDTH OF DOOR, OR ATTACHMENT DEVICES FOR FIVE (5) TIMES DESIGN LOAD. HANGER WIRE SHALL BE
PART 1 - GENERAL AT EXTERIOR WALLS OR AS SOUND ATTENUATION BLANKET WHERE GALVANIZED CARBON STEEL, ASTM A641, SOFT TEMPER, PRE-STRETCHED, 12 GA
C. COORDINATE INSTALLATION OF FRAMES WITH INSTALLATION OF EQUAL SCREW TO MATCH KICKPLATE. ONE-WAY VIEWER (PEEP) - IVES
SHOWN AND AS SPECIFIED ON DRAWINGS. MINIMUM.
A. PROVIDE AND INSTALL WOOD FURRING, BLOCKING, GROUNDS AND HARDWARE SPECIFIED IN DOOR SCHEDULE. #696, OR EQUAL. Architect / Engineer Job No.:
2. EXTEND FROM FLOOR TIGHT TO ROOF DECK ABOVE. C. COMPLY WITH MANUFACTURER'S PRINTED INSTRUCTIONS AND WITH
IN-WALL BLOCKING FOR SUPPORT OF GRAB BARS, FIXTURES, EQUIPMENT, FOLLOW DOOR HARDWARE INSTITUTE (DHI) GUIDELINES. 030
3. FURNISH AND INSTALL .004 MIL. VISQUEEN VAPOR BARRIER AT GOVERNING REGULATIONS, FIRE-RESISTANCE RATING REQUIREMENT AND WITH
CASEWORK, HARDWARE, TRIM AND SIMILAR WORK. PART 2 - PREPARATION / EXECUTION INDUSTRY STANDARDS APPLICABLE TO THE WORK. Nextore Store Design Revision No.:
1. BLOCKING AND GROUNDS AT STOREFRONT GLAZING , LOCATIONS EXTERIOR WALLS ON WARM SIDE OF STUDS. 08400 ALUMINUM ENTRANCES AND STOREFRONTS A. COORDINATE THE WORK WITH OTHER DIRECTLY AFFECTED
AT WEATHER AREAS, AND IN CONTACT WITH CONCRETE SHALL BE C. GENERAL CONTRACTOR TO PROVIDE AND INSTALL PART 1 - GENERAL SECTIONS INVOLVING MANUFACTURE OR FABRICATION OF INTERNAL D. INSTALL SUSPENSION SYSTEM TO COMPLY WITH ASTM C 636, WITH
PRESSURE TREATED. WATERPROOFING MEMBRANE OVER ENTIRE FLOOR OF REST ROOMS A. THIS SECTION INCLUDES ALL ALUMINUM/GLASS DOORS, DOOR REINFORCEMENT FOR DOOR HARDWARE AND RECESSED ITEMS. HANGERS SUPPORTED ONLY FROM BUILDING STRUCTURAL MEMBERS. DES REV 02
2. USE NON-COMBUSTIBLE FIRE RETARDANT TREATED (F.R.T.) WOOD BELOW FINISH FLOORING AND UP WALL A MIN. 4". (ONLY WHERE REST HARDWARE SPECIFICALLY SUPPLIED BY DOOR MANUFACTURER, EXTRUDED B. VERIFY THAT DOORS AND FRAMES ARE READY TO RECEIVE WORK LOCATE HANGERS NOT LESS THAN 6" FROM EACH END AND SPACE 4'-0"
ELSEWHERE AS REQUIRED BY STATE AND LOCAL CODES, INCLUDING ANY ROOMS ARE LOCATED ABOVE ANOTHER FLOOR.) APPLY PER ALUMINUM GLAZING FRAMES COMPLETE WITH ACCESSORIES AND GLASS AND DIMENSIONS ARE AS INDICATED. ALONG EACH CARRYING CHANNEL OR DIRECT-HUNG RUNNER. SECURE
Nextore project
Number 77889
WOOD STUDS, BLOCKING, FURRING, PLYWOOD, TRIM AND GROUNDS. MANUFACTURERS INSTRUCTIONS AND CAULK AS REQ'D. TO MATCH AS DETAILED ON THE DRAWINGS AND RESPONSIBILITY SCHEDULE. C. INSTALL HARDWARE IN ACCORDANCE WITH MANUFACTURER'S WIRE HANGERS BY LOOPING AND WIRE TYING, EITHER DIRECTLY TO Brand Design Type:
NEW LUMBER TO BEAR GRADE AND TREATMENT OF ASSOCIATION UNDER ADJACENT FINISHES. 1. ALUMINUM/TEMPERED GLASS ENTRANCE DOORS SHALL BE INSTRUCTIONS. STRUCTURES OR TO INSERTS, EYE-SCREWS, OR OTHER DEVICES WHICH
D. G.C. SHALL SLEEVE, FIRESTOP, FLASH AND CAULK ALL SGH 4.1 - TIER B GOLD
WHICH IT WAS PRODUCED. KAWNEER (SEE PARAGRAPH 2 OF THIS SECTION) SERIES 350 (SIZES OF D. USE TEMPLATES PROVIDED BY HARDWARE ITEM MANUFACTURER. ARE SECURE AND APPROPRIATE FOR SUBSTRATE.
a. PRESERVATIVE TREATMENT FOR WOOD SPECIFIED ELSEWHERE. PENETRATIONS OF FLOORS SO THAT ODORS OR LIQUIDS WILL NOT VERTICAL STILE AND TOP RAIL AS PER PLANS AND DETAILS) SINGLE E. ADJUST HARDWARE FOR SMOOTH OPERATION. E. INSTALL EDGE MOLDINGS AT PERIMETER OF ACOUSTICAL CEILING ISSUED FOR:
1) PERFORMANCE REQUIREMENTS: PENETRATE THE SLAB AT THESE OPENINGS. SUCH SLEEVES SHALL BE ACTING WITH 1/2" TEMPERED GLASS INFILL SET WITH ELASTOMERIC AREA AND AT LOCATIONS WHERE NECESSARY TO CONCEAL EDGES OF X Construction

a) MOISTURE CONTENT: AFTER TREATMENT, THE MAXIMUM MOISTURE INSTALLED ACCORDING TO THE LANDLORD STANDARD DETAILS GASKETS. 08800 GLAZING ACOUSTICAL UNITS.
CONTENT OF WOOD MATERIALS SHALL NOT EXCEED THE FOLLOWING: a. HARDWARE - TO INSURE SINGLE SOURCE RESPONSIBILITY, THE PART 1 - GENERAL F. INSTALL ACOUSTICAL PANELS IN COORDINATION WITH
i. LUMBER, 2 INCHES AND LESS IN THICKNESS: 19 PERCENT. 07900 JOINT SEALERS / CAULKING FOLLOWING SHALL BE PROVIDED AND INSTALLED BY THE DOOR SUPPLIER A. FURNISH AND INSTALL A COMPLETE SYSTEM OF GLASS, GLAZING SUSPENSION SYSTEM, WITH EDGES CONCEALED BY SUPPORT OF Title
ii. PLYWOOD: 15 PERCENT PART 1 - GENERAL / INSTALLER CHANNELS, SEALANT, SETTING BLOCKS AND ACCESSORIES AS SHOWN SUSPENSION ,MEMBERS, SCRIBE AND CUT PANELS TO FIT ACCURATELY AT
b) FLAME SPREAD: FIRE RETARDANT TREATED MATERIALS TO HAVE FLAME A. PROVIDE AND INSTALL EXPANSION JOINT MATERIAL, SEALANTS HINGING - TOP PATCH AND BOTTOM PIVOTS AND DETAILED ON THE DRAWINGS AND RESPONSIBILITY SCHEDULE. BORDERS AND PENETRATIONS.
SPREAD RATING OF 25 OR LESS IN A 30 MINUTE TEST WITH NO EVIDENCE AND JOINT BACKING FOR JOINTS BETWEEN DISSIMILAR MATERIALS. CLOSERS - NORTON SERIES 1600 - ONE PER DOOR LEAF B. SEE PLANS AND ELEVATIONS FOR SIZE AND NUMBER OF PANES. G. INSTALL HOLD-DOWN CLIPS IF REQUIRED BY CODE.
SPECIFICATIONS
OF SIGNIFICANT PROGRESSIVE COMBUSTION, ASTM E 84, ADDITIONALLY, 1. SILICONE SEALANTS (TYPE S): ASTM C920, SINGLE COMPONENT, PUSH/PULL - KAWNEER "F-2" C. FOLLOW RECOMMENDATIONS FOR INSTALLATION CONTAINED IN H. GWB CEILINGS AND SOFFITS TO BE GIVEN A FLAT AND SMOOTH 2 OF 4
FLAME FRONT NOT TO PROGRESS MORE THAN 10 1/2 FEET BEYOND NON-SAGGING, NON-STAINING, NON-BLEEDING; FOR USE AS GENERAL LOCKS - DEADLOCK: "BEST CORE" THE FGMA (FLOAT GLASS MANUFACTURERS ASSOCIATION) GLAZING AND FINISH TO ACCEPT PAINT FINISH. REFER TO SECTION 09250 "GYPSUM
CENTER LINE OF BURNER AT ANY TIME. CAULKING. COLOR TO MATCH ADJACENT SURFACES. MANUFACTURER BY THRESHOLD - MILL FINISH ALUMINUM MAXIMUM 1/2" HIGH SEALANT MANUALS AS WELL AS SIGMA (SEALED INSULATED GLASS BOARD SYSTEMS". Date Sheet
c) SMOKE DEVELOPED: INTERIOR FINISH AND TRIM MATERIALS, WHERE GE SILICONES OR EQUAL.2. JOINT BACKING: ROUND, OPEN CELL MANUFACTURE. ASSOCIATION) FOR INSULATED GLASS. 11-28-18
SPECIFIED, TO HAVE FIRE RETARDANT TREATMENT CONFORMING TO POLYETHYLENE FOAM ROD. Drawn By

ABOVE REQUIREMENTS FOR "FLAME SPREAD" PLUS SMOKE DEVELOPED Checked By


STAFF G004
RATING OF 25 OR LESS, ASTM E 84.
STAFF
DESIGN & CONSTRUCTION

SPECIFICATIONS (3 OF 4) MANAGEMENT:

09250 GYPSUM BOARD SYSTEMS D. LAY OUT TILE PATTERN SYMMETRICALLY WITH EVEN JOINT ON ALL 09700 LAMINATED WOOD FLOORING 10800 TOILET ROOM ACCESSORIES a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000

LEVEL 5 GYPSUM BOARD FINISH SPECIFICATION: FLOOR AND WALL SURFACES. ALIGN JOINTS WITH MALL PATTERN, WHERE PART 1 - GENERAL PART 1 - GENERAL a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484

A. ALL JOINTS AND INTERIOR ANGLES SHALL HAVE TAPE EMBEDDED IN APPLICABLE. A. WOOD LAMINATE FLOORING: REFER TO FINISH AND RESPONSIBILITY A. TENANT TO SUPPLY A.D.A. APPROVED TOILET ACCESSORIES AND
JOINT COMPOUND AND TWO SEPARATE COATS OF JOINT COMPOUND E. CUT AND DRILL TILE AS REQUIRED WITHOUT MARRING TILE, GRIND SCHEDULE FOR SIZES, COLORS, AND MANUFACTURERS. GRAB BARS INCLUDING ALL SET SCREWS AND ANCHORS REQUIRED FOR
APPLIED OVER ALL FLAT JOINTS AND ONE SEPARATE COAT OF JOINT AND FIT AROUND FIXTURES, ETC.. LEAVE COMPLETED WORK FREE FROM B. PREP FLOOR AS RECOMMENDED BY THE MANUFACTURER. COMPLETE INSTALLATION.
COMPOUND APPLIED OVER INTERIOR ANGLES. FASTENER HEADS AND CRACKED, BROKEN, OR DAMAGED TILE. C. INSTALL COMPLETE PER MANUFACTURER'S SPECIFICATIONS,
ACCESSORIES SHALL BE COVERED WITH THREE SEPARATE COATS OF JOINT F. ALL TRANSITIONS BETWEEN NEW AND EXISTING OR UNLIKE FINISHES INCLUDING ALL TRANSITION STRIPS AND EXPANSION JOINTS AS REQUIRED PART 2 - PREPARATION / EXECUTION
COMPOUND. A THIN SKIM COAT OF JOINT COMPOUND OR A MATERIAL SHALL BE FLUSH AND SMOOTH. NO REDUCER STRIPS PERMITTED IN FOR PROPER INSTALLATION. A. G.C. SHALL INSTALL TOILET ACCESSORY UNITS ACCORDING TO
MANUFACTURED ESPECIALLY FOR THIS PURPOSE, SHALL BE APPLIED TO STOREFRONT AREA. MANUFACTURER'S INSTRUCTIONS, USING FASTENERS AND IN WALL
Construction for:
THE ENTIRE SURFACE. THE SURFACE SHALL BE SMOOTH AND FREE OF H. PROTECT HEAVILY TRAVELED, NEWLY TILED AREAS AS REQUIRED. PART 2 - PREPARATION / EXECUTION BLOCKING AS RECOMMENDED BY UNIT MANUFACTURER. INSTALL UNITS
TOOL MARKS AND RIDGES. NOTE: IT IS RECOMMENDED THAT THE I. INSTALL TILES USING THINSET METHOD WITH 1/16" JOINTS AT REFER TO SECTION 03732 "CONCRETE REPAIR / PREPARATION". AND TO PLUMB AND LEVEL, FIRMLY ANCHORED IN LOCATIONS AND AT HEIGHTS
PREPARED SURFACE BE COATED WITH A DRYWALL PRIMER PRIOR TO THE WALLS AND FLOORS. SECTION 07200 "INSULATION AND WATERPROOFING" INDICATED, IN A TAMPERPROOF MANNER WITH SPECIAL HANGERS,
APPLICATION OF FINISH PAINT. J. SEAL/WAX ALL TILE PER MANUFACTURER'S SPECIFICATIONS. TOGGLE BOLTS, OR SCREWS.
PART 1 - GENERAL A. GENERAL CONTRACTOR TO RECEIVE AND STORE MATERIAL. G.C. END OF DIVISION
A. FURNISH AND INSTALL ALL GYPSUM DRYWALL AND SYSTEMS 09650 VINYL RESILIENT TILE FLOORING MUST OPEN BOXES A MINIMUM OF 48 HOURS IN ADVANCE OF
COMPLETE WITH PARTITION FRAMING, CEILING SUSPENSION SYSTEMS PART 1 - GENERAL INSTALLATION TO ACCLIMATE PRODUCT TO TEMPERATURE AND DIVISION 11000 - EQUIPMENT
AND RELATED ACCESSORIES, PARTS, MATERIALS, ETC. AS SHOWN ON A. G.C. TO SUPPLY AND INSTALL 1/8" X 12" X 12" VINYL RESILIENT TILES, HUMIDITY OF AREA TO RECEIVE INSTALLATION. 11001 EQUIPMENT

4000 Luxottica Place Mason, Ohio 45040


A Subsidiary of the Luxottica Group
DRAWINGS AND AS SPECIFIED. INSTALL ALL MATERIALS PER AS SHOWN AND SPECIFIED ON THE DRAWINGS. B. PREPARE SUBFLOOR OR EXISTING FLOOR SYSTEM AS PART 1 - GENERAL
MANUFACTURERS SPECIFICATIONS AND RECOMMENDATIONS. B. INSTALL 4" HIGH X 1/8" THICK, TOP SET, COVED VINYL BASE, AT ALL RECOMMENDED BY MANUFACTURER. A. CONTRACTOR SHALL COORDINATE ALL EQUIPMENT WORK AND
B. GYPSUM DRYWALL: ALL GYPSUM BOARD TO BE 5/8" TYPE "X" AS WALLS IN AREAS TO RECEIVE VINYL TILE FLOORING, AS SPECIFIED ON C. INSTALL POLYETHYLENE FILM ON CONCRETE SUBFLOOR. PLACEMENT WITH THE WORK OF ALL OTHER TRADES AND MAKE
NOTED ON NEW CONSTRUCTION PLAN. REST ROOMS TO RECEIVE DRAWINGS. D. INSTALL "WHISPERWALK". ADJUSTMENTS AS REQUIRED TO ACCOMMODATE LOCATIONS OF
MOISTURE RESISTANT GYPSUM BOARD. C. SEE FINISH SCHEDULE FOR SPECIFIC COLORS AND MANUFACTURER. E. INSTALL LAMINATE FLOORING AS A "FLOATING" FLOOR. BEGIN EQUIPMENT.
C. FASTENERS: DRYWALL SCREWS OF PROPER SIZE AND TYPE PER INSTALLATION ALONG WALL WITH TONGUE FACING WALL ACCORDING B. ALL EQUIPMENT WORK SHALL COMPLY WITH ALL GOVERNING
MANUFACTURERS RECOMMENDATIONS. PART 2 - PREPARATION / EXECUTION TO MANUFACTURER'S PROCEDURES. APPLY GLUE TO GROOVES WITH BUILDING CODES AND LOCAL
D. PROVIDE MATERIALS, JOINT COMPOUNDS, TRIM, EDGES, BEADS, ETC. REFER TO SECTION 03732 "CONCRETE REPAIR / PREPARATION". AND TO PLANKS IN PLACE ON FLOOR. ENSURE JOINTS ARE COMPLETELY SEALED C. EQUIPMENT SHALL BE FURNISHED, UNLOADED, UNPACKED OR
FROM A SINGLE SOURCE SUPPLIER. ALL TRIM SHALL CONSIST OF A SECTION 07200 "INSULATION AND WATERPROOFING" WITH GLUE. DO NOT NAIL, SCREW OR FASTEN FLOORING TO SUBFLOOR. UNCRATED AND PLACED ACCORDING TO THE CONSTRUCTION
TAPERED, GROOVED, AND PREPUNCHED FIN FOR SCREW ATTACHMENT A. PREP SLAB AS REQUIRED TO RECEIVE NEW VINYL TILE. F. PROVIDE ADEQUATE EXPANSION SPACE AT PERIMETER, COLUMNS, DOCUMENTS.
AND TO ACCEPT BONDING AGENT. ALL BUTT JOINTS ARE TO BE NEAT B. FILL ALL CRACKS, JOINTS, ETC. IN SUB-FLOOR WITH CRACK FILLER AND AT ALL ALL OTHER OBSTRUCTIONS.
WITH TIGHT JOINTS, AND ALL CORNERS ARE TO BE MITERED. ALL EDGES, APPROVED BY FLOORING MANUFACTURER. INSTALL ALL MATERIALS WITH G. INSTALL SPECIFIED BASE OR TRIM AT PERIMETER, COLUMNS, AND AT PART 2 - PREPARATION / EXECUTION
BEADS AND TRIM TO BE PRE-FINISH ALUMINUM. WATERPROOF TYPE ADHESIVES AS RECOMMENDED BY FLOORING ALL OTHER OBSTRUCTIONS. A. GENERAL CONTRACTOR'S INSTALLATION OF TENANT SUPPLIED
E. JOINT TREATMENT: U.S. GYPSUM OR GOLD BOND SYSTEM OF MANUFACTURER FOR MATERIALS AND SURFACES INVOLVED. H. NO FLOORING TO BE EXPOSED UNTIL LAST DAY OF FIXTURING AND EQUIPMENT IS TO BE INCLUDED IN GENERAL BID.
COMPOUNDS AND PERFORATED TAPE. C. SLOPE FLOOR TILE TO DRAINS. SUBSTRATE MUST ALSO BE SLOPED MERCHANDISE INSTALLATION. B. GENERAL CONTRACTOR SHALL NOTIFY THE CONSTRUCTION
1. ERECT GWB IN A SINGLE LAYER IN THE MOST ECONOMICAL TO DRAIN. I. FLOOR CLEANUP: FOLLOWING COMPLETION OF WORK BY OTHER MANAGER IMMEDIATELY OF ANYDAMAGE TO THE EQUIPMENT PRIOR TO
DIRECTION WITH ALL VCT SHALL BE CLEANED, SEALED, AND WAXED BY G.C. PRIOR TO TRADES, THE PROTECTIVE COVERING PLACED AFTER INSTALLATION INSTALLATION.
ENDS AND EDGES OCCURRING OVER FIRM BEARING. TURNOVER. SHOULD BE REMOVED; FOLLOWED BY SWEEPING, VACUUMING AND/OR C. GENERAL CONTRACTOR SHALL BE RESPONSIBLE FOR FINAL HOOKUP
2. WALLS, CEILINGS AND SOFFITS, AND ALL TRANSITIONS IN SAME, DRY MOPPING TO REMOVE ALL LOOSE DEBRIS. OF ALL EQUIPMENT, INCLUDING ALL MECHANICAL, PLUMBING AND
09652 WOOD FLOORING ELECTRICAL WORK.
SHALL BE PART 1 - GENERAL
GIVEN A SMOOTH FINISH. 09910 PAINTING AND FINISHING D. ALL EQUIPMENT MANUALS, INSTRUCTION BOOKLETS AND
A. FINISHED WOOD FLOOR AS SPECIFIED IN FINISH AND PART 1 - GENERAL WARRANTY INFORMATION SHALL BE NEATLY BOUND AND TURNED OVER Revisions:
3. CORNER BEADS SHALL BE APPLIED TO ALL EXTERNAL ANGLES IN RESPONSIBILITY SCHEDULES. INSTALLED PER MANUFACTURER'S PRINTED
STRICT ACCORDANCE WITH THE MANUFACTURERS DIRECTIONS. INSTALL A. THE INTENT IS TO PROVIDE A SATISFACTORY FINISH TO ALL PARTS OF THIS TO THE CONSTRUCTION MANAGER PRIOR TO THE TURNOVER. Mark Date By
INSTRUCTIONS AND RECOMMENDATIONS. PROJECT. FINISH APPEARANCE MUST BE UNIFORM, SMOOTH, AND FREE OF ANY E. STEAM PRESS SUPPLIED BY TENANT SHALL BE INSTALLED BY G.C.'S
CASING BEADS AT ALL EDGES OF DRYWALL WORK EXCEPT WHERE B. MATERIALS SHALL BE LISTED WITH UNDERWRITERS LABORATORIES
1 11-28-18

TERMINATION IS COVERED BY OTHER FINISH. CASING BEADS SHALL BE RUNS, SAGS, AND DEFECTIVE BRUSHING OR SPRAYING. COVER ALL SURFACES CERTIFIED STEAM FITTER/PLUMBER FOR FINAL CONNECTIONS. LANDLORD COMMENTS / PERMIT SET

AS TO FIRE AND SLIP RESISTANCE. THOROUGHLY IF THE NUMBER OF COATS RECOMMENDED BY MANUFACTURER DOES
MITERED AT CORNERS AND INSTALLED NEATLY, FINISHED WITH C. ARCHITECTURAL TRIM, i.e. REDUCER STRIPS, BANDS, PICKETS, ETC., NOT ACCOMPLISH THE INTENT, THEN APPLY ADDITIONAL COATS UNTIL COVERAGE
COMPOUND. 11110 MISCELLANEOUS
SHALL BE OF SAME MANUFACTURER AND FINISH AS WOOD FLOOR. IS SATISFACTORY. SEE FINISH SCHEDULE FOR PAINT COLORS, MANUFACTURER, ETC. PART 1 - GENERAL
4. JOINTS BETWEEN BOARDS SHALL BE REINFORCED WITH TAPE B. USE ONLY THE PAINT AND RELATED MATERIALS SPECIFIED BY THE
EXCEPT WHERE CONTROL JOINTS ARE REQUIRED. TAPE FIELD JOINTS, A. GENERAL CONTRACTOR TO INSTALL TRAFFIC COUNTING SYSTEM
PART 2 - PREPARATION / EXECUTION MANUFACTURER. SEE FINISH SCHEDULE FOR SPECIFIC COLORS. ALTERNATES ARE
INTERIOR CORNER JOINTS AND WALL TO CEILING JOINTS. FILL JOINTS PER MANUFACTURER'S SPECIFICATIONS.
REFER TO SECTION 03732 "CONCRETE REPAIR / PREPARATION". AND TO NOT PERMITTED.
WITH JOINT FILLING COMPOUND AND EMBED TAPE THEREIN. COVER TAPE 1. THE SYSTEM'S TRANSMITTER AND REFLECTOR ARE TO BE INSTALLED
SECTION 07200 AT EACH PUBLIC ENTRANCE, 52" A.F.F., AS INDICATED IN DRAWINGS.
WITH BEDDING COMPOUND AND TAPER TO FEATHER EDGES. FILL SCREW "INSULATION AND WATERPROOFING" PART 2 - PREPARATION / EXECUTION
HEAD DEPRESSIONS WITH JOINT FILLING COMPOUND AND FEATHER THE DOOR SWING NOR ANY OTHER OBSTRUCTION SHOULD BLOCK THE
A. GENERAL CONTRACTOR TO BROOM CLEAN FLOORING AS IT IS A. CLEAN ALL SURFACES TO BE PAINTED FREE OF LOOSE DIRT AND DUST BEFORE "BEAM" PATH.
EDGES. ALLOW TO DRY. INSTALLED. PROTECT FLOORING IMMEDIATELY WITH BROWN KRAFT WORK IS STARTED. WASH ALL METAL SURFACES WITH MINERAL SPIRITS BEFORE
5. COVER TAPED AND FILLED JOINTS AND FILLED SCREW HEAD 2. THE SYSTEM'S RECEIVER IS TO BE INSTALLED IN CASH-DESK
PAPER AND INSTALL MASONITE, ORIENTED STRAND BOARD OR OTHER APPLYING FINISHES. WHERE RUST OR SCALE IS PRESENT, WIRE BRUSH OR SAND
DEPRESSIONS WITH TOPPING COMPOUND APPLIED IN THREE COATS. CLEAN BEFORE APPLYING FINISH. CABINETRY.
PROTECTIVE FLOOR PANELS OVER ENTIRE WOOD FLOOR. B. GENERAL CONTRACTOR TO INSTALL FULL HEIGHT, WHITE CORNER
PERMITTING THE PREVIOUS COAT TO DRY PRIOR TO INSTALLING THE B. NO FLOORING TO BE EXPOSED UNTIL LAST DAY OF FIXTURING AND B. PAINTED DRYWALL TO RECEIVE ONE COAT LATEX PRIMER AND TWO COATS
SUBSEQUENT COAT. OF SPECIFIED GUARDS WITH WHITE ADHESIVE WHERE INDICATED ON DRAWINGS.
PROP INSTALLATION. Architect / Engineer of Record
6. SAND JOINT AND SCREW HEAD AREAS LIGHTLY BETWEEN COATS C. FLOOR CLEAN-UP: FOLLOWING COMPLETION OF WORK BY OTHER
PAINT. TINT PRIMER TO APPROXIMATE SHADE OF THE FINAL COAT. TOUCHUP ALL
AND AFTER THE FINAL COAT SO THAT A SMOOTH LEVEL SURFACE IS SUCTION SPOTS OR HOT SPOTS AFTER APPLICATION OF FIRST COAT AND BEFORE END OF DIVISION
TRADES, THE PROTECTIVE COVERING PLACED AFTER INSTALLATION APPLYING SECOND COAT, TO PRODUCE AND EVEN RESULT IN THE FINISH COAT. DRY
PRODUCED WITH THE PAPER SURFACE OF THE WALLBOARD FREE OF SHOULD BE REMOVED; FOLLOWED BY SWEEPING, VACUUMING AND/OR
SCUFFING. ALL COATS THOROUGHLY BEFORE APPLYING SUCCEEDING COATS. FOLLOW
DRY MOPPING TO REMOVE ALL LOOSE DEBRIS. MANUFACTURER'S RECOMMENDATIONS FOR RECOAT TIME. SEAL ALL DRYWALL
F. PATCH AND/OR REPAIR EXISTING DRYWALL TO REMAIN TO LIKE
SURFACES BEHIND MIRRORS.
NEW CONDITION. LEVEL ANY UNEVEN OR ROUGH SPOTS AND FINISH 09680 CARPET C. PUTTY ALL NAIL HOLES, COUNTERSUNK SCREWS, BOLTS, CRACKS, ETC. BEFORE
SMOOTH. BULGES AND VISUAL DEPRESSIONS ARE NOT ACCEPTABLE. PART 1 - GENERAL APPLYING FINISH.
G. INSTALL CEMENTITIOUS BACKER BOARD AT ALL AREAS TO RECEIVE TILE OR
MARBLE, OR AS SHOWN ON =DRAWINGS.
A. CONDITION CARPET AND ADHESIVES FOR AT LEAST 48 HOURS AT A D. SAND ALL WOOD SURFACES SMOOTH AND EVEN BEFORE APPLYING FINISH.
H. ACCESS PANELS: MINIMUM TEMPERATURE OF 65 DEGREES FAHRENHEIT. THE FLOOR E. BEFORE STARTING FINISH WORK, REMOVE HARDWARE, ACCESSORIES, PLATES,
1. G.C. SHALL PROVIDE AND INSTALL ACCESS PANELS AS REQUIRED BY SHOULD ALSO BE CONDITIONED AT A TEMPERATURE ABOVE 65 DEGREES F LIGHTING FIXTURES AND SIMILAR ITEMS, OR PROVIDE AMPLE PROTECTION FOR SUCH
LANDLORD AND SITE CONDITIONS (COORDINATE SIZE REQUIREMENTS, NUMBER OF FOR AT LEAST 24 HOURS PRIOR TO INSTALLATION. THE FLOOR MUST BE ITEMS.
PANELS REQUIRED AND LOCATIONS WITH LANDLORD AND ALL MECHANICAL SWEPT FREE OF DUST AND DEBRIS. F. PAINT ALL EXPOSED PIPING, ACCESS DOORS, VENTS, FIRE EXTINGUISHER Seal
TRADES). B. NEW CONCRETE MUST BE CURED PREFERABLY FOR 90 DAYS BEFORE CABINETS, EQUIPMENT MOUNTING BOARDS, ETC. TO MATCH ADJACENT WORK
2. ACCESS PANELS SHALL BE FLUSH TYPE (NO EXPOSED FLANGES) STYLE AS UNLESS OTHERWISE NOTED OR DIRECTED.
INSTALLING CARPET. CHECK THE SLAB FOR ALKALINITY, WHICH SHOULD BE
MANUFACTURED BY: INTEX FORMS INC. - GLASS FIBER (GFRG) FLUSH ACCESS G. SAND ENAMELED FINISHES APPLIED TO WOOD OR METAL BETWEEN COATS
PANEL
LESS THAN 9.0 pH IF NECESSARY, NEUTRALIZE THE FLOOR WITH AN ACID
WITH FINE SANDPAPER TO PRODUCE EVEN SMOOTH FINISH.
PHONE NUMBER: 650-654-7855 WASH OF 10 PARTS WATER TO ONE PART MURIATIC ACID AND RINSE H. MAKE FINISH WORK UNIFORM, SMOOTH, FREE OF RUNS, SAGS AND
THOROUGHLY. A SEALER SHOULD BE USED TO INSURE A GOOD BONDING DEFECTIVE BRUSHING OR SPRAYING. MAKE EDGES ADJOINING OTHER
(SIZE AS REQUIRED) SURFACE. EXISTING CONCRETE MAY REQUIRE RESEALING TO ASSURE A MATERIALS OR COLORS SHARP AND CLEAN WITHOUT OVERLAPPING.
3. PANELS TO BE FACTORY PRIMED (WHITE) READY TO RECEIVE FINAL FINISH PROPER SURFACE. I. SEAL TOPS, BOTTOMS AND EDGES OF ALL DOORS.
PAINT BY G.C. C. REMOVE, REPLACE OR PATCH OLD VINYL TILE OR LINOLEUM, STRIP J. CONTRACTOR TO LEAVE ONE QUART EACH COLOR OF PAINT FOR
OLD WAX BY MOPPING WITH AMMONIA AND WATER, AND FILL IN GROUT FUTURE TOUCH-UP.
09300 TILE AND MARBLE LINES ON CERAMIC FLOORS WITH A LATEX FLASHING COMPOUND, AS
PART 1 - GENERAL K. PRIOR TO CONTRACTOR LEAVING SITE AND AFTER ALL FIXTURES Architect / Engineer Job No.:
APPLICABLE. ARE INSTALLED AND STORE IS CLEANED, CONTRACTOR TO WALK SITE 030
A. MARBLE/CERAMIC/QUARRY TILE: REFER TO FINISH AND D. REMOVE ANY FINISHES, WAXES, PAINT, ETC. FROM WOOD FLOORS.
RESPONSIBILITY SCHEDULE FOR SIZES, COLORS, AND MANUFACTURERS. AND TOUCH-UP PAINT DAMAGED DURING FINAL DAYS OF PROJECT. Nextore Store Design Revision No.:
THE SURFACE MUST BE LEVEL AND CRACKS MAY REQUIRE A FLASHING
B. INSTALL GROUT AS RECOMMENDED BY THE TILE MANUFACTURER. COMPOUND. PLYWOOD OR PARTICLE BOARD MAY BE NECESSARY TO
COLOR OF WALL GROUT TO BE INDICATED ON THE FINISH SCHEDULE. IF OFFSET UNEVEN FLOORS, BUT MUST BE PRIMED PRIOR TO INSTALLATION.
END OF DIVISION DES REV 02
NO COLOR IS INDICATED, A GROUT TO MATCH TILE IS TO BE USED. E. CUT-BACK ADHESIVE MUST BE FLASHED OVER. USING A NOTCHED
C. ALL CERAMIC TILE BASES INSTALLED SHALL BE SANITARY COVE TYPE. DIVISION 10000 - SPECIALTIES Nextore project
TROWEL, PATCH AND LET CURE. SMOOTH OVER WITH A SECOND COAT Number 77889
REFER TO FINISH SCHEDULE FOR SPECIFICATIONS. 10520 FIRE PROTECTION
OF PATCH, USING THE FLAT SIDE OF THE TROWEL TO FILL IN THE RIDGES. Brand Design Type:
ALLOW THE NEWLY FLASHED FLOOR TO CURE. PART 1 - GENERAL
PART 2 - PREPARATION / EXECUTION A. PROVIDE MULTI-PURPOSE CHEMICAL FIRE EXTINGUISHERS CAPABLE OF SGH 4.1 - TIER B GOLD
F. CARPET CONTRACTOR TO ESTABLISH HIS OWN TAKEOFFS AND
REFER TO SECTION 03732 "CONCRETE REPAIR / PREPARATION". AND TO EXTINGUISHING CLASS A, B, AND C FIRES, IN QUANTITIES AND LOCATIONS REQUIRED
COORDINATE HIS TAKEOFFS WITH THE AMOUNT SHIPPED BY TENANT AND ISSUED FOR:
SECTION 07200 "INSULATION AND WATERPROOFING" BY LOCAL FIRE MARSHALL. (COORDINATE IN FIELD.) MANUFACTURER: J.L.
CONTACT THE CONSTRUCTION COORDINATOR OF ANY DISCREPANCIES. INDUSTRIES; COSMIC SERIES OR EQUAL.
X Construction
G. INSTALL PER FLOOR AND WALL FINISH PLAN AND PROVIDE TENANT
A. BEFORE SETTING ANY TILE, THE CONTRACTOR SHALL ASSURE WITH SEAM LAYOUT PRIOR TO CUTTING / INSTALLATION. H. FILL ALL
HIMSELF THAT NO TILES WILL HAVE TO BE REMOVED AFTER INSTALLATION PART 2 - PREPARATION / EXECUTION
CRACKS, JOINTS, ETC. IN SUB-FLOOR WITH CRACK FILLER APPROVED BY
TO ACCOMMODATE THE WORK OF OTHER TRADES. ALL CUTTING, A. INSTALL MOUNTING BRACKETS AT HEIGHTS TO COMPLY WITH APPLICABLE Title
CARPET MANUFACTURER. REGULATIONS OF GOVERNIN AUTHORITIES.
FITTING, DRILLING AND GRINDING OF THE WORK, WHERE NECESSARY IN H. PROVIDE DIRECT GLUEDOWN INSTALLATION USING MATERIAL AND
RELATION TO THE WORK OF OTHER TRADES, SHALL BE PERFORMED SO METHODS RECOMMENDED BY CARPET MANUFACTURER. SEAL ALL SEAMS
B. SECURE MOUNTING BRACKETS TO STRUCTURE, SQUARE AND PLUMB, TO SPECIFICATIONS
COMPLY WITH MANUFACTURER'S INSTRUCTIONS.
THAT THE WORK WILL BE NEATLY AND ACCURATELY DONE AND CUT WITH SEAM ADHESIVE. 3 OF 4
EDGES SHALL BE UNIFORM. C. ALL SALES AREAS AND PUBLIC AREAS TO HAVE RECESSED BRASS CABINETS
PROVIDED AND INSTALLED BY G.C.
B. CONFORM TO REQUIREMENTS UNDER AMERICAN NATIONAL
Date Sheet
STANDARDS INSTITUTE ANSI A-137.1 FOR CERAMIC TILE MATERIAL AND 11-28-18
ANSI A-108 FOR INSTALLATION. Drawn By

C. INSTALL PER LANDLORD'S SPECIFICATIONS, WHERE APPLICABLE. STAFF G005


Checked By

STAFF
DESIGN & CONSTRUCTION

SPECIFICATIONS (4 OF 4) MANAGEMENT:

DIVISION 15000A - PLUMBING DIVISION 15000B - MECHANICAL DIVISION 16000 - ELECTRICAL 1. BRANCH CIRCUIT LOAD CENTERS SHALL BE DEAD FRONT TYPE, WITH a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000
PART 1 - GENERAL I. GENERAL PROVISIONS MAIN LUGS OR MAIN OVERCURRENT DEVICE AS INDICATED, BRANCH a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484

PART I - GENERAL OVERCURRENT DEVICES AS NOTED AND AN EQUIPMENT GROUND BAR, ALL IN
A. GENERAL CONDITIONS, CODES & STANDARDS A. GENERAL CONDITIONS, CODES & STANDARDS A. GENERAL CONDITIONS, CODES & STANDARDS A FLUSH MOUNTED SHEET STEEL ENCLOSURE. MINIMUM SHORT CIRCUIT
1. ALL WORK SHOWN ON THE PLUMBING DOCUMENTS IS TO BE PROVIDED AND INSTALLED BY 1. ALL WORK SHOWN ON THE ELECTRICAL DOCUMENTS IS TO BE PROVIDED AND CAPACITY SHALL BE 10,000 AMPS SYMMETRICAL FOR 120/208V, AND 14,000
THE PLUMBING CONTRACTOR, UNLESS NOTED OTHERWISE. 1. ALL WORK SHOWN ON THE MECHANICAL DOCUMENTS IS TO BE PROVIDED AND INSTALLED BY THE ELECTRICAL CONTRACTOR, UNLESS NOTED OTHERWISE. AMPS SYMMETRICAL FOR 277/480V APPLICATION UNLESS NOTED OTHERWISE.
2. ALL WORK TO MEET APPLICABLE CODES AS LOCALLY ENFORCED. NO WORK ON THE INSTALLED BY THE PLUMBING CONTRACTOR, UNLESS NOTED OTHERWISE. 2. ALL WORK TO MEET APPLICABLE CODES AS LOCALLY ENFORCED. NO WORK ON THE LOAD CENTERS MUST BE SELECTED TO FIT IN A STANDARD STUD WALL.
DRAWINGS IS TO BE INSTALLED WHERE IT CONFLICTS WITH LOCAL CODE ENFORCEMENT. 2. ALL WORK TO MEET APPLICABLE CODES AS LOCALLY ENFORCED. NO WORK ON THE DRAWINGS IS TO BE INSTALLED WHERE IT CONFLICTS WITH LOCAL CODE ENFORCEMENT. 2. LOAD CENTERS SHALL BE AS MANUFACTURED BY SQUARE D, GENERAL
COORDINATE WITH THE LOCAL INSPECTOR PRIOR TO INSTALLATION. DRAWINGS IS TO BE INSTALLED WHERE IT CONFLICTS WITH LOCAL CODE ENFORCEMENT. COORDINATE WITH THE LOCAL INSPECTOR PRIOR TO INSTALLATION.
COORDINATE WITH THE LOCAL INSPECTOR PRIOR TO INSTALLATION.
ELECTRIC, ITE/SIEMENS AND WESTINGHOUSE/CUTLER HAMMER.
3. GENERAL CONTRACTOR SHALL PAY FOR AND OBTAIN ALL NECESSARY LICENSES, PERMITS 3. ELECTRICAL CONTRACTOR SHALL PAY FOR AND OBTAIN ALL NECESSARY LICENSES, Construction for:
AND INSPECTIONS REQUIRED TO PROCEED WITH THE WORK. THIS SHALL INCLUDE ALL
A. FIXTURES AND LAMPS
3. GENERAL CONTRACTOR SHALL PAY FOR AND OBTAIN ALL NECESSARY LICENSES, PERMITS AND INSPECTIONS REQUIRED TO PROCEED WITH THE WORK. THIS SHALL INCLUDE
REQUIRED COORDINATION WITH THE LOCAL UTILITY COMPANIES AND THEIR ASSOCIATED PERMITS AND INSPECTIONS REQUIRED TO PROCEED WITH THE WORK. THIS SHALL INCLUDE ALL REQUIRED COORDINATION WITH THE LOCAL UTILITY COMPANIES AND THEIR 1. ALL FIXTURES AND LAMPS ARE FURNISHED BY TENANT, INSTALLED BY
FEES OR COSTS. ALL REQUIRED COORDINATION WITH THE LOCAL UTILITY COMPANIES AND THEIR ASSOCIATED FEES OR COSTS. ELECTRICAL CONTRACTOR.
ASSOCIATED FEES OR COSTS. 4. THE ELECTRICAL CONTRACTOR SHALL PROVIDE ALL LABOR, MATERIAL, EQUIPMENT AND
B. SCOPE OF WORK TOOLS NECESSARY TO COMPLETE THE ELECTRICAL WORK AS SHOWN ON THE DRAWINGS PART 3 - EXECUTION
B. SCOPE OF WORK OR SPECIFIED HEREIN. D. GENERAL MISCELLANEOUS
1. ONLY MAJOR EQUIPMENT IS SHOWN ON THE DRAWINGS. THE PLUMBING CONTRACTOR
5. TEMPORARY ELECTRICAL SERVICE, LIGHTING, AND RELATED WIRING SHALL BE PROVIDED 1. ALL CONDUIT RUN IN FINISHED AREAS SHALL BE CONCEALED. 2.
SHALL BID AND CONSTRUCT A COMPLETE AND OPERATIONAL SYSTEM. MISCELLANEOUS
2. PROVIDE TYPEWRITTEN DIRECTORY CARDS WITH BRANCH CIRCUIT

4000 Luxottica Place Mason, Ohio 45040


EQUIPMENT REQUIRED TO COMPLETE THE WORK IS IN THE PLUMBING CONTRACTOR'S SCOPE 1. ONLY MAJOR EQUIPMENT IS SHOWN ON THE DRAWINGS. THE MECHANICAL TO OSHA REQUIREMENTS FOR THE USE OF ALL TRADES DURING CONSTRUCTION.

A Subsidiary of the Luxottica Group


- ASSUME NO WORK OR EQUIPMENT IS PROVIDED BY OTHERS UNLESS STATED AS SUCH. CONTRACTOR SHALL BID AND CONSTRUCT A COMPLETE AND OPERATIONAL SYSTEM. IDENTIFICATION FOR BRANCH CIRCUIT PANELBOARDS. PANELBOARDS, FEEDER
2. DURING BIDDING: MISCELLANEOUS EQUIPMENT REQUIRED TO COMPLETE THE WORK IS IN THE MECHANICAL DEVICES, DISTRIBUTION EQUIPMENT AND STARTERS SHALL BE FIELD MARKED
CONTRACTOR'S SCOPE - ASSUME NO WORK OR EQUIPMENT IS PROVIDED BY OTHERS B. SCOPE OF WORK
2.1. VERIFY THE EXISTING CONDITIONS AND COMPENSATE FOR ANY VARIATIONS IN THE TO WARN QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC FLASH HAZARDS
SCOPE AS A RESULT. UNLESS STATED AS SUCH.
IN ACCORDANCE WITH NEC 110.16.
2.3. WHERE THERE IS A CONFLICT THAT CANNOT BE RESOLVED BY THE GENERAL 2. DURING BIDDING: 1. ONLY MAJOR EQUIPMENT IS SHOWN ON THE DRAWINGS. THE ELECTRICAL 3. INSTALL HANDLE GUARDS ON ALL BREAKERS FOR NIGHT LIGHTING,
CONTRACTOR, ADVISE ENGINEER PROMPTLY FOR A RESOLUTION. DO NOT PROVIDE WORK 2.1. VERIFY THE EXISTING CONDITIONS AND COMPENSATE FOR ANY VARIATIONS IN THE CONTRACTOR SHALL BID AND CONSTRUCT A COMPLETE AND OPERATIONAL SYSTEM.
WHEN THERE IS UNCERTAINTY ON WHAT WORK IS TO BE PERFORMED.
EMERGENCY AND SIMILAR CIRCUITS.
SCOPE AS A RESULT. MISCELLANEOUS EQUIPMENT REQUIRED TO COMPLETE THE WORK IS IN THE ELECTRICAL
3. AS PART OF THE BIDDING PROCESS, REPORT TO THE TENANT ANY ERRORS OR UNCLEAR CONTRACTOR'S SCOPE - ASSUME NO WORK OR EQUIPMENT IS PROVIDED BY OTHERS 4. ALL FLUSH MOUNTED ;LOADCENTERS SHALL HAVE (3) 3/4" EMPTY
2.3. WHERE THERE IS A CONFLICT THAT CANNOT BE RESOLVED BY THE GENERAL
DIRECTIONS THAT YOU HAVE IDENTIFIED. CONTRACTOR, ADVISE ENGINEER PROMPTLY FOR A RESOLUTION. DO NOT PROVIDE UNLESS STATED AS SUCH. CONDUITS INSTALLED TO ABOVE ACCESSIBLE CEILING FOR FUTURE USE.
WORK WHEN THERE IS UNCERTAINTY ON WHAT WORK IS TO BE PERFORMED. 2. DURING BIDDING: 5. THE FINAL LOCATIONS OF ALL EQUIPMENT, OUTLETS, ETC. SHALL BE
C. DOCUMENTS 3. AS PART OF THE BIDDING PROCESS, REPORT TO THE TENANT ANY ERRORS OR UNCLEAR SUBJECT TO REASONABLE CHANGES IN LOCATION UP TO THE TIME OF
2.1. VERIFY THE EXISTING CONDITIONS AND COMPENSATE FOR ANY VARIATIONS IN THE
DIRECTIONS THAT YOU HAVE IDENTIFIED. SCOPE AS A RESULT.
ROUGHING-IN, AT NO ADDITIONAL COST TO THE TENANT.
1. SUBSTITUTIONS
B. GROUNDING
1.1. THE MANUFACTURERS AND MODEL NUMBERS INDICATED IN THE CONTRACT 2.3. WHERE THERE IS A CONFLICT THAT CANNOT BE RESOLVED BY THE GENERAL
DOCUMENTS ARE FOR THE PURPOSE OF DESCRIPTION AND TO ESTABLISH A BASE LEVEL OF C. DOCUMENTS CONTRACTOR, ADVISE ENGINEER PROMPTLY FOR A RESOLUTION. DO NOT PROVIDE
1. GROUNDING OF THE ELECTRICAL SYSTEM SHALL BE BY MEANS OF AN
QUALITY. THE GENERAL CONTRACTOR'S BID WILL CONTEMPLATE THE USE OF THE 1. SUBSTITUTIONS WORK WHEN THERE IS UNCERTAINTY ON WHAT WORK IS TO BE PERFORMED. INSULATED GROUNDING CONDUCTOR INSTALLED WITH ALL FEEDERS AND
EQUIPMENT AND MATERIALS EQUIVALENT TO THOSE INDICATED. 1.1. THE MANUFACTURERS AND MODEL NUMBERS INDICATED IN THE CONTRACT BRANCH CIRCUIT CONDUCTORS IN ALL CONDUITS AND SUPPLEMENTAL AS
3. AS PART OF THE BIDDING PROCESS, REPORT TO THE TENANT ANY ERRORS OR UNCLEAR
2. MISCELLANEOUS ITEMS NECESSARY TO COMPLETE THE SYSTEMS CAN BE OF ANY DOCUMENTS ARE FOR THE PURPOSE OF DESCRIPTION AND TO ESTABLISH A BASE LEVEL REQUIRED TO MEET CODE (SUCH AS ARTICLE 517).
DIRECTIONS THAT YOU HAVE IDENTIFIED.
RECOGNIZED MANUFACTURE PROVIDED THESE ITEMS MEET MINIMUM STANDARDS AS SET IN OF QUALITY. THE GENERAL CONTRACTOR'S BID WILL CONTEMPLATE THE USE OF THE C. TESTS
THESE SPECIFICATIONS. EQUIPMENT AND MATERIALS EQUIVALENT TO THOSE INDICATED. 1. TEST FOR GROUNDS, SHORT CIRCUITS, AND PROPER FUNCTION OF ALL
2. MISCELLANEOUS ITEMS NECESSARY TO COMPLETE THE SYSTEMS CAN BE OF ANY C. DOCUMENTS
D. CONSTRUCTION COORDINATION EQUIPMENT AFTER INSTALLATION IS COMPLETE. FAULTS IN THE INSTALLATION
RECOGNIZED MANUFACTURE PROVIDED THESE ITEMS MEET MINIMUM STANDARDS AS SET
SHALL BE CORRECTED AT NO COST TO THE TENANT.
IN THESE SPECIFICATIONS.
1. DURING BIDDING YOU VISITED THE SITE. WORK WITH THE GENERAL CONTRACTOR TO 1. SUBSTITUTIONS D. DEMOLITION
COORDINATE ANY CONFLICTS WITH EXISTING CONDITIONS. THIS WORK SHALL BE PROVIDED 1.1. THE MANUFACTURERS AND MODEL NUMBERS INDICATED IN THE CONTRACT 1. DEMOLITION OF EXISTING ELECTRICAL EQUIPMENT, IF APPLICABLE, SHALL Revisions:
AT NO ADDITIONAL COST TO THE TENANT. D. CONSTRUCTION COORDINATION Mark Date By
DOCUMENTS ARE FOR THE PURPOSE OF DESCRIPTION AND TO ESTABLISH A BASE LEVEL BE PART OF THE ELECTRICAL WORK AS INDICATED ON THE DRAWINGS.
2. GENERAL CONTRACTOR SHALL LOCATE, IDENTIFY AND PROTECT ANY EXISTING SERVICES OF QUALITY. THE GENERAL CONTRACTOR'S BID WILL CONTEMPLATE THE USE OF THE 1 11-28-18
WHICH ARE REQUIRED TO BE MAINTAINED OPERATIONAL AND SHALL EXERCISE EXTRA 1. DURING BIDDING YOU VISITED THE SITE. WORK WITH THE GENERAL CONTRACTOR TO EQUIPMENT AND MATERIALS EQUIVALENT TO THOSE INDICATED. LANDLORD COMMENTS / PERMIT SET
CAUTION IN THE PERFORMANCE OF ALL WORK TO AVOID DISTURBING SUCH FACILITIES. ALL COORDINATE ANY CONFLICTS WITH EXISTING CONDITIONS. THIS WORK SHALL BE
2. MISCELLANEOUS ITEMS NECESSARY TO COMPLETE THE SYSTEMS CAN BE OF ANY
COSTS FOR REPAIR OF DAMAGES TO SUCH SERVICES SHALL BE PAID BY THE GENERAL PROVIDED AT NO ADDITIONAL COST TO THE TENANT.
RECOGNIZED MANUFACTURE PROVIDED THESE ITEMS MEET MINIMUM STANDARDS AS SET
CONTRACTOR CAUSING THE DAMAGE. 2. GENERAL CONTRACTOR SHALL LOCATE, IDENTIFY AND PROTECT ANY EXISTING IN THESE SPECIFICATIONS.
SERVICES WHICH ARE REQUIRED TO BE MAINTAINED OPERATIONAL AND SHALL EXERCISE
PART 2 - MATERIALS EXTRA CAUTION IN THE PERFORMANCE OF ALL WORK TO AVOID DISTURBING SUCH
A. GENERAL FACILITIES. ALL COSTS FOR REPAIR OF DAMAGES TO SUCH SERVICES SHALL BE PAID BY THE D. CONSTRUCTION COORDINATION
GENERAL CONTRACTOR CAUSING THE DAMAGE.
1. PROVIDE STOP VALVES AT EVERY FIXTURE ON BOTH HOT AND 1. DURING BIDDING YOU VISITED THE SITE. WORK WITH THE GENERAL
COLD WATER SUPPLY LINES. VALVES, ESCUTCHEONS, FITTINGS, ETC. MUST CONTRACTOR TO COORDINATE ANY CONFLICTS WITH EXISTING CONDITIONS.
II. INSULATION
BE CHROME PLATED. WHERE EXPOSED, CHROME PLATED PIPE IS TO BE THIS WORK SHALL BE PROVIDED AT NO ADDITIONAL COST TO THE TENANT.
USED. 2. GENERAL CONTRACTOR SHALL LOCATE, IDENTIFY AND PROTECT ANY
A. GENERAL
2. ALL ABOVE GROUND PIPING SHALL BE INSULATED WITH FIBERGLASS EXISTING SERVICES WHICH ARE REQUIRED TO BE MAINTAINED OPERATIONAL
PIPING INSULATION WITH AN ALL SERVICE JACKET AND SELF SEALING LAP AND SHALL EXERCISE EXTRA CAUTION IN THE PERFORMANCE OF ALL WORK TO
1. EXTEND INSULATION WITHOUT INTERRUPTION THROUGH WALLS,
(ASJ/SSL). AVOID DISTURBING SUCH FACILITIES. ALL COSTS FOR REPAIR OF DAMAGES TO
FLOORS, HANGERS AND SIMILAR PENETRATIONS.
2.1 DOMESTIC HOT AND COLD WATER PIPING UP TO 3/4 INCH DIAMETER SUCH SERVICES SHALL BE PAID BY THE GENERAL CONTRACTOR CAUSING THE Architect / Engineer of Record
2. MAINTAIN ACCESS TO BALANCING DAMPERS AND VALVES.
- 1/2 INCH THICK. DAMAGE.
3. INSULATION SHALL BE BY OWENS-CORNING, KNAUF, OR MANVILLE.
2.2 FITTINGS AND VALVES SHALL BE INSULATED WITH PRE-MOLDED 4. ALL DUCTWORK AND PIPING SHALL BE INSULATED
FIBERGLASS FITTINGS AND COVERED WITH A PRE-FORMED PVC FITTING PART 2 - PRODUCTS
COVER. A. WIRING DEVICES
VI. AIR DISTRIBUTION
1. DUPLEX RECEPTACLES SHALL BE GROUNDING TYPE, NEMA 5-20R, RATED
PART 3 - EXECUTION FOR 20 AMPS, 125 VOLTS, WITH PROVISIONS FOR BACK AND SIDE WIRING.
A. AIR DISTRIBUTION
1.1. SPECIFICATION GRADE DUPLEX RECEPTACLE SHALL BE HUBBELL #5362
A. GENERAL SERIES OR APPROVED EQUAL, HEAVY DUTY, WHITE.
1. DUCTWORK (ROUND OR RECTANGULAR OR SPIRAL) SHALL BE OF
1.3. GROUND FAULT CIRCUIT INTERRUPTER (GFI) DUPLEX RECEPTACLES SHALL
GALVANIZED STEEL CONSTRUCTION AND SHALL BE INSTALLED IN
1. THE ENTIRE PLUMBING INSTALLATION, MATERIALS, EQUIPMENT, ETC. BE PROVIDED WHERE INDICATED.
ACCORDANCE WITH THE LATEST EDITION OF THE SMACNA MANUAL AND
SHALL CONFORM TO THE REQUIREMENTS OF THE LOCALLY ENFORCED 2. SWITCHES SHALL BE TOGGLE OPERATED, QUIET TYPE, RATED FOR 20
SEALED.
CODES AND STANDARDS. AMPS, 120/277 VOLTS, WITH PROVISIONS FOR BACK AND SIDE WIRING. THREE Seal
2. CHANGES IN DUCT SIZES SHALL BE MADE BY UNIFORM TAPER SECTION
1.1. VERIFY FINAL ROUGH IN WITH ARCHITECT PRIOR TO WALL WAY AND FOUR WAY SWITCHES SHALL BE PROVIDED WHERE INDICATED.
WITH A MAXIMUM INCLUDE ANGLE OF DIVERGENCE OF 15DEGREES.
INSTALLATION. 2.1. SINGLE POLE SWITCHES SHALL BE LEVITON #1221 SERIES OR APPROVED
3. FINAL CONNECTIONS TO DIFFUSERS MAY BE MADE WITH FLEXIBLE
2. PIPING IS TO BE INSTALLED CONCEALED - SURFACE MOUNTED EQUAL, SILENT ACTUATING, 20-AMP, 120/277V, WHITE.
DUCTWORK BUT IT'S USE IS LIMITED TO STRAIGHT HORIZONTAL OR VERTICAL
PIPING IN FINISHED AREAS IS NOT ACCEPTABLE. 2.2. THREE POLE SWITCHES SHALL BE LEVITON #1223 SERIES OR APPROVED
RUNS. ALL CHANGES OF DIRECTION IN A DUCT SYSTEM (GALVANIZED OR
3. ALL EXPOSED OR ACCESSIBLE P-TRAPS MUST BE PROVIDED WITH FLEXIBLE) SHALL BE MADE WITH AN APPROPRIATE GALVANIZED ELBOW. EQUAL, SILENT ACTUATING, 20-AMP, 120/277V, WHITE.
BOTTOM CLEANOUT PLUGS. 3. DIMMERS SHALL BE LEVITON SLIDING DIMMER SWITCH, OF A RATING,
MAXIMUM LENGTH OF ANY FLEXIBLE DUCT IS 5'-0".
4. INSULATE EXPOSED P-TRAPS, HOT AND COLD VALVES AND PIPING VOLTAGE AND WATTAGE SUITABLE FOR LOAD SERVED. COLORS OF DEVICES
4. FLEXIBLE DUCTS TO DIFFUSERS: MAXIMUM LENGTH OF FLEXIBLE DUCT
SERVING HANDICAPPED LAVATORIES. AND COVERPLATES SHALL WHITE.
TO DIFFUSER TO BE 5'-0".
5. IF SPACE ABOVE CEILING IS INDICATED TO BE A RETURN AIR 4. COMBINATION WALL DIMMER/OCCUPANT SENSOR SHALL BE LUTRON
PLENUM. CONSTRUCTION MATERIALS ABOVE CEILING SHALL BE VIII. TESTING AND BALANCING MAESTRO 0-10V DIMMER WITH INTEGRAL PASSIVE INFRARED OCCUPANT Architect / Engineer Job No.:
NONCOMBUSTIBLE, OR HAVE A MAXIMUM 25 FLAME SPREAD AND 50 SENSING, AVAILABLE IN 1-WAY OR 3-WAY CONFIGURATIONS. COLOR TO BE 030
SMOKE DEVELOPMENT FINISH RATING. WIRING SHALL BE LABELED PLENUM A. SYSTEM TO BE TESTED AND BALANCED WITH A REPORT SHOWING WHITE. VERIFY LOAD SERVED IS COMPATIBLE PRIOR TO ORDERING. Nextore Store Design Revision No.:
RATED TYPE PER NFPA 70. ACTUAL AIR FLOWS AT NEWLY INSTALLED DIFFUSERS. AIR FLOW TO BE WITHIN 5. WIRING DEVICES SHALL BE SPECIFICATION GRADE.
6. ALL CLEANOUTS ARE TO BE INSTALLED FLUSH WITH THE FINISHED 6. COVERPLATES FOR POWER, DATA & TELEPHONE SHALL BE LEVITON OR
FLOOR OR WALL.
15% OF THE DESIGN VALUE SHOWN ON THE DRAWINGS. WHERE THIS AIR
QUANTITY CANNOT BE MET, ADJUST UPSTREAM DAMPERS UNTIL IT IS MET. APPROVED EQUAL, WHITE, PLASTIC. DES REV 02
LIGHTING CONTRACTORS SHALL BE IN NEMA 1 ENCLOSURE, NORMALLY OPEN
Nextore project
B. INSULATION ELECTRICALLY HELD, 120V, COIL, 20A. REFER TO PLANS FOR NUMBER OF POLES. Number 77889
1. EXTEND INSULATION WITHOUT INTERRUPTION THROUGH WALLS, LIGHTING AND RECEPTACLE LOAD CENTERS (PANELS). Brand Design Type:
FLOORS, HANGERS AND SIMILAR PENETRATIONS. SGH 4.1 - TIER B GOLD
2. MAINTAIN ACCESS TO VALVES
ISSUED FOR:
X Construction

Title

SPECIFICATIONS
4 OF 4
Date Sheet
11-28-18
Drawn By

Checked By
STAFF G006
STAFF
DESIGN & CONSTRUCTION
MANAGEMENT:

1 KEY NOTES # 2 GENERAL NOTES


A. THE G.C. SHALL TAKE ALL NECESSARY PRECAUTIONS TO ENSURE THE SAFETY OF THE PUBLIC AND/OR I. IN ACCORDANCE WITH THE DRAWINGS, THOSE ITEMS WHICH ARE REMOVED, AND ARE NOT
1. EXISTING STOREFRONT, ENTRY DOORS AND DISPLAY WINDOWS TO REMAIN. WORKMEN ON THE JOB AND TO PREVENT ACCIDENTS OR INJURY TO ANY PERSON ON, ABOUT, OR RELOCATED OR REUSED, SHALL BE DISPOSED OF BY THE G.C.
ADJACENT TO THE PREMISES. THE G.C. SHALL COMPLY WITH ALL LAWS, ORDINANCES, CODES, RULES a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000
2. REMOVE ALL INTERIOR MILLWORK DISPLAY FIXTURES, MIRRORS AND SIGNS. FIELD VERIFY EXISTING ELECTRICAL, COORDINATE WITH ELECTRICAL DRAWINGS TO AND REGULATIONS RELATIVE TO SAFETY AND THE PREVENTION OF ACCIDENTS. J. ANY EXISTING DOORS AND FRAMES TO BE REMOVED UNLESS NOTED OTHERWISE ON PLANS; REFER TO a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484

REMOVE OR RELOCATE AS NECESSARY FOR NEW FIXTURES. WHERE REQUIRED REMOVE BACK TO NEAREST J-BOX AND MAKE SAFE. PATCH AND REPAIR WALLS AS DOOR SCHEDULE.
REQUIRED. B. THIS DEMOLITION PLAN IS TO BE USED IN CONJUNCTION WITH THE ENTIRE SET OF WORKING
DRAWINGS. DO NOT REMOVE OR DEMOLISH ANYTHING WITHOUT VERIFYING AND COORDINATING K. ANY EXISTING RECEPTACLES TO REMAIN UNLESS NOTED OTHERWISE ON PLANS; REFER TO ELECTRICAL
3. REMOVE ALL EXISTING SALES AREA FLOOR FIXTURES . FIELD VERIFY EXISTING ELECTRICAL, COORDINATE WITH ELECTRICAL DRAWINGS REMOVE OR RELOCATE AS WITH ALL GENERAL TRADES AS TO HOW THEY RELATE TO THE OVERALL PROJECT. DRAWINGS.
NECESSARY FOR NEW FIXTURES.
C. THE G.C. SHALL BE RESPONSIBLE FOR REMOVING OR DEMOLISHING EXISTING CONSTRUCTION WHICH L. REMOVE ALL WALL VINYL FROM WALLS (AS REQUIRED) AND PREP WALLS FOR NEW FINISHES.
4. EXISTING CASH DESK TO BE REMOVED. ELECTRICAL, TEL, AND DATA TO BE REUSED IF APPLICABLE. FIELD VERIFY CONDUIT STUB-UP LOCATION COORDINATE WITH WILL INTERFERE WITH THEIR NEW WORK AND ANY TEMPORARY BRACING OR PERMANENT SUPPORT
NEW CASHDESK LOCATION, RELOCATE IF NECESSARY. STRUCTURES. M. G.C. TO INSPECT ALL EXISTING WALLS TO REMAIN AND ENSURE THAT THEY ARE UP TO CURRENT
SPECIFICATIONS AND PREPARED FOR QUALITY FINISH.
5. REMOVE EXISTING SALES AREA FLOORING AND WALL BASE THROUGH OUT THE SALES AREA. SLAB IS TO BE CLEAN, SMOOTH, AND LEVEL, READY FOR NEW D. WHEN EXISTING ELECTRICAL SERVICE, POWER, AND LIGHTING IS REMOVED, STUB BACK AND CAP AS
FLOORING. REQUIRED IN AREAS BETWEEN EXISTING CONDITIONS AND NEW WORK.
N. G.C. TO PROVIDE AND INSTALL TEMPORARY BARRICADE PER DETAIL. SUBJECT TO CHANGE PER Construction for:
6. EXISTING TOILET ROOM TO REMAIN. E. REMOVE EXISTING FLOORING MATERIAL, CAP EXISTING MECHANICAL, PLUMBING AND ELECTRICAL REQUIREMENTS. GC TO ITEMIZE COST OF BARRICADE.
SERVICES FLUSH WITH EXISTING SLAB AS REQUIRED, TYPICAL THROUGHOUT; REFER TO RESPONSIBILITY
7. EXISTING ELECTRICAL EQUIPMENT TO REMAIN. SCHEDULE ON SHEET G002 FOR FLOORING PREPARATION.
O. PRIOR TO INSTALLATION OF NEW FLOOR, GC TO VERIFY EXISTING FLOOR CONDITIONS MEETS AND ARE
8. EXISTING DISPLAY FIXTURES, WALL MOUNT DISPLAYS, WALL FINISHES, GRAPHICS, ETC. TO BE REMOVED THROUGHOUT UNLESS NOTED OTHERWISE TYPICAL. F. AT THE G.C.'S OPTION, DEMOLISH OR REMOVE MORE OR LESS EXISTING WORK, PROVIDED THAT SUCH IN COMPLIANCE WITH ANSI STANDARD FOR THIN SET TILE AND THE LATEST EDITION OF TILE COUNCIL
VARIATION WILL EXPEDITE THE PROJECT AND NOT INCREASE THE EXPENSE TO THE OWNER OR OF AMERICA. IF THERE ARE ISSUES OR DEFICIENCIES, CONTACT NEXTORE PROJECT MANAGER PRIOR TO
9. PATCH AND REPAIR WALL SURFACES TO RECEIVE NEW FINISHES AS REQUIRED. VIOLATE ANY CODES. THESE OPTIONS SHALL BE SUBJECT TO THE NEXTORE'S PROJECT MANAGER'S INSTALLATION.
APPROVAL.
10. EXISTING RECESSED FLOOR OUTLET. REFERENCE FIXTURE PLAN AND ELECTRICAL DRAWINGS FOR POSSIBLE RE-USE. IF FLOOR DEVICE IS NOT RE-USED IT IS TO BE
COMPLETELY REMOVED G. COORDINATE ANY SYSTEMS SHUTDOWNS WITH LANDLORD & INCLUDE COSTS OF SHUTDOWN IN THE
BID.

4000 Luxottica Place Mason, Ohio 45040


A Subsidiary of the Luxottica Group
11. EXISTING PLUMBING FIXTURES TO REMAIN.
H. EXCEPT AS NOTED, G.C. SHALL INCLUDE COSTS TO CUT, PATCH AND/OR REPAIR EXISTING WORK AND
12. EXISTING DOOR TO REMAIN. REFERENCE DOOR SCHEDULE FOR WORK REQUIRED. EXISTING FACILITIES WHICH MAY BE DISTURBED DURING INSTALLATION OF NEW WORK IN BID
PACKAGES.
13. G.C. TO INSTALL SUNGLASS HUT VINYL WINDOW BARRICADE. COORDINATE WITH NEXTORE CONSTRUCTION MANAGER IF REQUIRED. 2-SGH4.0-AD100-REV00

14. EXISTING STOREFRONT SIGNAGE TO REMAIN.

15. EXISTING METAL STUD AND GYP. BD. PARTITION TO BE REMOVED.

16. EXISTING SHELVING AND STANDARDS TO BE REMOVED.


3 EXISTING WALL TYPES 4 BARRICADE NOTES
EXISTING TENANT SEPARATION CONSTRUCTION TO REMAIN. PATCH
17. LEASE LINE AND REPAIR AS REQUIRED TO MAINTAIN ANY EXISTING FIRE RATINGS BARRICADE & BARRICADE GRAPHICS:
BARRICADE GRAPHICS ARE TO BE PROVIDED AND INSTALLED BY THE TENANT UPON COMPLETION OF
18. PROPOSED LOCATION OF CONSTRUCTION BARRICADE (VERIFY IF BARRICADE IS REQUIRED FOR STOREFRONT RECLAD SCOPE OF WORK). VERIFY SUPPLY AND THE BARRICADE INSTALLATION, OR UPON FULL EXECUTION OF THE TENANT LEASE.
INSTALL RESPONSIBILITIES WITH NEXTORE CONSTRUCTION MANAGER AND LANDLORD. BARRICADE GRAPHICS ARE TO BE SUBMITTED TO THE TENANT COORDINATOR FOR APPROVAL PRIOR TO
EXISTING INTERIOR WALLS TO REMAIN INSTALLATION. ALL GRAPHICS ARE TO BE ORDERED THROUGH BOSTON BARRICADE.
19. EXISTING FIRE EXTINGUISHER TO BE RELOCATED SEE PLANS. ENSURE PROPER WORKING ORDER. ANY REQUIRED BARRICADE AND OR GRAPHICS TO BE SUPPLIED BY VENDOR OTHER THAN BOSTON
BARRICADE DUE TO LANDLORD REQUIREMENTS, SHALL BE COORDINATED, SUPPLIED, AND INSTALLED BY
GENERAL CONTRACTOR.
20. EXISTING DOOR TO BE REMOVED. SEE PLANS FOR WORK REQUIRED.
INTERIOR PARTITIONS OR ELEMENTS TO BE REMOVED
21. EXISTING FLOORING TO REMAIN.
3-SGH4.0-AD100-REV00 4-SGH4.0-AD100-REV01
22. EXISTING THERMOSTAT TO BE RELOCATED, REFER TO FIXTURE PLAN FOR NEW LOCATION

23. EXISTING FIRE EXTINGUISHER TO REMAIN ENSURE PROPER WORKING ORDER.

24. EXISTING MECHANICAL UNIT TO REMAIN. G.C. TO INCLUDE IN BID COSTS FOR ROUTINE MAINTENANCE / SERVICE TO ENSURE PROPER WORKING ORDER.

25. EXISTING FLOOR MOUNTED DIFFUSER TO REMAIN.

26. EXISTING ELECTRICAL DEVICES TO REMAIN.


Revisions:
Mark Date By
1-SGH4.0-AD100-REV00
1 11-28-18
LANDLORD COMMENTS / PERMIT SET

REFERENCE A104
FOR ELECTRICAL
ADJACENT TENANT ROUGH-IN PLAN
17
15
14

19
12 24 21 6 11 21

12
2
12 TYP.

23 17 Architect / Engineer of Record


13
26 12 10

TYP.
WHERE 23
EXISTING - sunglass hut
SHOWN -LEVEL ONE
-FULLY SPRINKLERED 14
DOWN

12 -SPACE 73
2 -1030 SQ. FT.
TYP.
10

ADJACENT TENANT
10
4 3
21

1 Seal

UP
13

EXTERIOR
25 21
5 8 9

EXISTING - sunglass hut 7 2


-MEZZANINE
TYP.
-FULLY SPRINKLERED
-SPACE 73 3
-408 SQ. FT.
2

Architect / Engineer Job No.:


22 030
10 3
25 Nextore Store Design Revision No.:
20
2 2
TYP. TYP. 13
DES REV 02
Nextore project
Number 77889
Brand Design Type:

17
SGH 4.1 - TIER B GOLD

ISSUED FOR:
ADJACENT TENANT X Construction

EXISTING MEZZANINE FLOOR PLAN / DEMOLITION EXISTING FIRST FLOOR PLAN / DEMOLITION Title

2 SCALE: 1/4" = 1'-0"


1 SCALE: 1/4" = 1'-0" EXISTING FLOOR
PLAN /
DEMOLITION
Date Sheet
11-28-18
Drawn By

Checked By
STAFF AD100
STAFF
DESIGN & CONSTRUCTION
MANAGEMENT:
1 KEY NOTES # 2 CEILING FIXTURE LEGEND
1. EXISTING EXTERIOR SIGNAGE TO REMAIN.
EX/F
2. EXISTING STOREFRONT CEILING TO REMAIN. TRACK LIGHT FIXTURE AND TRACK TO BE 1 X 4 STRIP LIGHT FIXTURE TO REMAIN
REMOVED
3. EXISTING SECTION OF TRACK AND LIGHT FIXTURE TO BE REMOVED FROM THE STOREFRONT GYP. BD. CEILING.
a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000
PATCH AND REPAIR GYP. BD. AS REQUIRED. EX-L a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484
DOWNLIGHT FIXTURE TO BE REMOVED DOWNLIGHT FIXTURE TO REMAIN
4. REMOVE EXISTING MARKETING GRID FROM STOREFRONT CEILING.
5. REMOVE AND REPLACE EXIT SIGN.
EXIT FIXTURE TO BE REMOVED
EXISTING TOILET ROOM EXHAUST FAN TO REMAIN
6. EXISTING TRAFFIC COUNTER TO REMAIN.
7. REMOVE EXISTING ACOUSTICAL CEILING IN SALES AREA. S
C SECURITY CAMERA TO BE REMOVED
8. REMOVE EXISTING SALES AREA LIGHTING, REMOVE ELECTRICAL BACK TO NEAREST J-BOX AND MAKE SAFE.
EXISTING TRAFFICE COUNTER TO REMAIN
9. REMOVE EXISTING TRACK LIGHTING, REMOVE ELECTRICAL BACK TO NEAREST J-BOX AND MAKE SAFE. AUDIO SPEAKER TO BE REMOVED
10. REMOVE EXISTING AUDIO SPEAKERS. COORDINATE WITH REFLECTED CEILING PLAN FOR NEW LOCATIONS.
MOTION DETECTOR TO BE REMOVED Construction for:
11. REMOVE EXISTING SECURITY CAMERAS. COORDINATE WITH REFLECTED CEILING PLAN FOR NEW LOCATIONS.
12. EXISTING HVAC DIFFUSERS TO BE RELOCATED, REFER TO REFLECTED CEILING PLAN EXISTING SUPPLY AIR DIFFUSER TO BE REMOVED

13. EXISTING TOILET ROOM GYP. BD. CEILING TO REMAIN.


14. EXISTING TOILET ROOM LIGHT FIXTURES AND EXHAUST FAN TO BE REMAIN. SEE REFLECTED CEILING PLAN.
15. EXISTING STOREFRONT LIGHTING THIS AREA TO REMAIN UNLESS NOTED OTHERWISE. EXISTING RETURN AIR DIFFUSER TO BE REMOVED
16. EXISTING MARKETING GRID AT STOREFRONT CEILING TO REMAIN.
17. EXISTING EXIT SIGN TO REMAIN.
18. EXISTING ACOUSTICAL TILE CEILING GRID (ONLY) IN SALES AREA TO REMAIN, REPLACE TILES (CEILING TO BE

4000 Luxottica Place Mason, Ohio 45040


A Subsidiary of the Luxottica Group
MODIFIED AT RAY BAN AREA).
19. EXISTING SALES AREA LIGHTING TO REMAIN.
20. EXISTING SALES AREA TRACK LIGHTING TO REMAIN.
21. EXISTING AUDIO SPEAKERS TO REMAIN.
2-SGH4.0-AD200-REV00
22. EXISTING HVAC DIFFUSERS TO REMAIN. U.N.O. REFERENCE MECHANICAL DRAWINGS
23. EXITING FIRE ALARM PULL/HORN TO REMAIN.
24. EXISTING CEILING OUTLETS TO REMAIN.
25. EXISTING SPRINKLER HEADS TO REMAIN. SEE PLANS FOR SCOPE OF WORK - INSTALL NEW COVERS.
26. EXISTING ACOUSTICAL TILE CEILING GRID AND TILES, THIS AREA, TO REMAIN U.N.O.
27. EXISTING LIGHT FIXTURES, THIS AREA, TO REMAIN U.N.O. REFERENCE ELECTRICAL DRAWINGS FOR RELAMP
REQUIREMENTS.
28. EXISTING PERIMETER WALL TRIM IN SALES AREA TO BE REMOVED. PATCH AND REPAIR EXISTING WALL SURFACE
29. REMOVE EXISTING CEILING GRID SHOWN DASHED (HATCHED AREA). SEE PLANS FOR EXTENT OF DEMOLITION
REQUIRED
30. EXISTING EMERGENCY LIGHT TO BE REMAIN.
31. EXISTING GYP. BD. CEILING TO REMAIN.
32. EXISTING DISPLAY GRID TO BE REMOVED

1-SGH4.0-AD200-REV00

REVISION #1

NOTE: AFTER REMOVAL OF CEILING NOTE: WITHIN ONE DAY OF POSSESSION OF TENANT Revisions:
Mark Date By
TILES IN SALES AREA G.C. TO VERIFY SPACE G.C. TO VERIFY EXISTING HORIZONTAL BAND
EXISTING CONDITIONS AND REPAIR TRIM / BUILD-OUT BTM. AT AT +/-8'-10" A.F.F. CAN BE 1 11-28-18
LANDLORD COMMENTS / PERMIT SET

AREAS SHOWING EVIDENCE OF REMOVED. IF THIS CONSTRUCTION CAN NOT BE


LEAKS (WATER LINES, SANITARY REMOVED NOTIFY NEXTORE CONST. MGR.
LINES, CONDENSATION, ETC.) IMMEDIATELY FOR DIRECTIVE

ADJACENT TENANT
REFER TO CONSTRUCTION PLAN
FOR EXTENTS OF DEMOLITION

29

1
EX

REFER TO CONSTRUCTION PLAN FOR EXTENTS OF DEMOLITION


22 25 26 27 EX EX 5 EX

EX
13 14 22 25 27 31 Architect / Engineer of Record
12 8 15
12
EXISTING WINDOW TO
WALL
REMAIN (TYP.) EX
9 6 2

EXISTING AWNING
TO REMAIN

34'-6"
EX EX EX EX EX
EX 12
8
WALL

29 8 10 11

1
17 9
EX
EX
9
Seal
EX EX EX EX

ADJACENT TENANT
8 8

8
22 25 26 27
EX

EXTERIOR
EX EX 32
9 18 24 25

22 25 27 31 9
30 11 EX EX
8
EX
15'-10"

30 22 Architect / Engineer Job No.:

EXISTING
030
BLADE SIGN
9 Nextore Store Design Revision No.:
11'-4"

TO REMAIN
8'-812"

8 8
EX

EX EX EX
10
EX 9 DES REV 02
8
17
Nextore project
22 9 9 Number 77889
EX
EX WALL Brand Design Type:

SGH 4.1 - TIER B GOLD


11
ISSUED FOR:
X Construction
11"

Title
ADJACENT TENANT
EXISTING STOREFRONT
GLAZING SYSTEM TO
EXISTING STOREFRONT
FINISHES TO REMAIN
EXISTING STOREFRONT
SIGNAGE TO REMAIN
EXISTING STOREFRONT
GLAZING SYSTEM AND
EXISTING STOREFRONT
SIGNAGE TO REMAIN
EXISTING CEILING
REMAIN (TYP.) (TYP.) ENTRY DOOR TO REMAIN
PLAN /
DEMOLITION
EXTERIOR ELEVATION EXISTING MEZZANINE CEILING PLAN / SELECTIVE DEMO EXISTING FIRST FLOOR CEILING PLAN / SELECTIVE DEMO Date
3 SCALE: 1/4" = 1'-0"
2 SCALE: 1/4" = 1'-0"
1 SCALE: 1/4" = 1'-0"
11-28-18
Drawn By
Sheet

Checked By
STAFF AD200
STAFF
DESIGN & CONSTRUCTION
MANAGEMENT:

A EQUIPMENT ACCESSORY SCHEDULE B TOILET ACCESSORY SCHEDULE 1 FIXTURE PLAN - KEY NOTES # 2 GENERAL NOTES
SUPPLY INSTALL SUPPLY INSTALL 1. INSTALL WALL FIXTURES SEQUENTIALLY STARTING AT THIS POINT. FIELD VERIFY LENGTH OF A. G.C. TO REFERENCE FIXTURE CONTRACTORS SHOP DRAWINGS FOR INSTALLATION
MARK DESCRIPTION MODEL # MANUFACTURER REMARKS MARK DESCRIPTION MODEL # MANUFACTURER REMARKS
BY BY BY BY WALL REQUIRED FOR FIXTURE INSTALLATION. REPORT TO PROJECT MANAGER. COORDINATE INSTRUCTIONS FOR ALL FIXTURES, WALL CABINETS, BASE CABINETS, AND COUNTERTOPS. G.C.
SIX TIER BOX STYLE - 1 WIDE - 6 FEET HIGH WITH ELECTRICAL DRAWINGS FOR ELECTRICAL REQUIREMENT OF FIXTURES. TO COORDINATE WITH FIXTURE CONTRACTOR TO ENSURE PROPER FIT OF ALL COMPONENTS. a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000
LOCKERS(#) EMPLOYEE LOCKERS 36168BLK SALSBURY
- 18 INCHES DEEP - BLACK
1 42" GRAB BAR B-5806x42 BOBRICK a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484
2. INSTALL ALL SALES AREA FLOOR FIXTURES AS DIMENSIONED, COORDINATE WITH ELECTRICAL B. G.C. TO ENSURE FIXTURES ARE PROTECTED DURING CONSTRUCTION.
SAFE SMALL DROP SLOT SAFE UC-025K SENTRYSAFE BOLTED TO FLOOR BY G.C. 2 36" GRAB BAR B-5806x36 BOBRICK DRAWINGS FOR ELECTRICAL / DATA FLOOR BOX LOCATIONS. ALL UNDER FLOOR ELECTRICAL
TO BE IN CONDUIT. (TYP.)
MICRO MICROWAVE OVEN M01108SST AVANTI 3 VERTICAL GRAB BAR B-5806x18 BOBRICK
3. INSTALL CASH WRAP AS INDICATED. CASH WRAP PROVIDES A COUNTER SURFACE 36" WIDE C. G.C. TO PROVIDE ADEQUATE BRACING, AS REQUIRED, IN WALLS TO SUPPORT WALL CABINETS
FRIDGE 3.3 CU. FT. REFRIGERATOR RM3361B AVANTI COLOR: BLACK 4 MIRROR B-165 1836 BOBRICK ABOVE LAV. 33 1/2" A.F.F WITH A CLEAR FLOOR AREA OF 30" X 48" FOR PARALLEL APPROACH AS REQUIRED AND FIXTURES.
FOR ACCESSIBLE CHECK OUT. COORDINATE WITH ELECTRICAL DRAWINGS FOR CASH WRAP
W x D x H PIPP SHELVING STORAGE SHELVING PIPP W = WIDTH, D = DEPTH, H = HEIGHT 5 MIRROR B-165 2460 BOBRICK RESTROOM DOOR, ADD EXTRA SCREWS FOR SUPPORT ELECTRICAL, PHONE AND DATA. SEE DETAIL "D" THIS SHEET. D. G.C. TO FURNISH AND INSTALL LOCKSET OPERATIONAL BY TENANT ONLY.
MOP SINK SERVICE SINK #Z1996-24-SDL-HH ZURN 6 TOILET TISSUE DISPENSER B-543 BOBRICK 4. INSTALL NEW TECH RACK UNDER CASH WRAP COUNTER. E. G.C. TO SIGN FOR PACKAGES WITH A NOTE "SUBJECT TO CONCEALED DAMAGES" ON IT.
WATER COOLER BOTTLED WATER COOLER #GNB210-CD OR GNW210 NEXUS 7 (2) UTILITY HOOKS B-2116 BOBRICK X2 HOOKS, REFER TO PLAN FOR LOCATION 5. INSTALL DIGITAL SCREEN, PROVIDE ELECTRICAL AND DATA SEE ELECTRICAL.
F. E = EXISTING TO REMAIN.
8 HOOK STRIP B-232x24 BOBRICK 6. EXISTING THERMOSTAT KEYPAD TO BE RELOCATED / REPLACED WITH NEW BLACK PAD. REFER M = EXISTING TO BE RELOCATED. Construction for:
TO DEMOLITION PLAN F= FUTURE EQUIPMENT
9 MOP HOLDER B-223x24 BOBRICK
7. 2A-10BC FIRE EXTINGUISHERS AS DIRECTED BY THE FIRE MARSHAL. (SUGGESTED LOCATIONS G. REFER TO ELEVATION SHEETS A200-A201 FOR ACCESSIBILITY ACCESS SIGNAGE WHEN
10 PAPER TOWEL HOLDER KT1024 SIMPLE HUMAN STAPLES #180969 ON PLAN.) APPLICABLE.
11 RETRACTABLE LAVATORY FAUCET 7038.101 AMERICAN STANDARD 8. G.C. TO SUPPLY AND INSTALL DRAWING PLAN TUBE HOLDER, SEE DETAIL THIS SHEET
9. EXISTING TOILET ROOM TO REMAIN.
10. PROVIDE AND INSTALL NEW SERVICE SINK ON LEGS. SEE PLUMBING DRAWINGS
11. EXISTING ELECTRICAL EQUIPMENT TO REMAIN. U.N.O. SEE ELECTRICAL DRAWINGS

4000 Luxottica Place Mason, Ohio 45040


A Subsidiary of the Luxottica Group
12. NEW FRIDGE AND MICROWAVE
A-SGH4.0-A100-REV00 B-SGH4.0-A100-REV00 2-SGH4.0-A100-REV00
13. NEW SAFE, BOLT TO FLOOR
14. NEW TECH RACK

C TOILET ACCESSORY MOUNTING HEIGHTS 15. DIAMOND PLATE PLATFORM THIS AREA, SEE PLAN AND DETAILS
D ADA ACCESSIBLE CHECK OUT COUNTER
16. EXISTING RESTROOM TO RECEIVE NEW ACCESSORIES: VERTICAL GRAB BAR, MIRROR ABOVE
LAV. AND MIRROR ON DOOR (SEE DETAIL "C" THIS SHEET FOR ADDITIONAL INFORMATION).
17. NEW PIPP SHELVING G.C. TO INSTALL BLOCKING AS REQUIRED 3'-0" CLEAR
PLAN VIEW 2'-0"
18. ILLUMINATED SIGNAGE

CL CENTER UTILITY 19. NEW FIXTURES AND EQUIPMENT ARE NOT PROVIDED IN THIS AREA
HOOK AND
20. INSTALL FIXTURE CENTERED ON GLAZING AS SHOWN

5"
3'-0" 3'-4" MIRROR
ON DOOR 21. INSTALL THE FOLLOWING NEW ACCESSORIES IN THE EXISTING RESTROOM: VERTICAL GRAB
MIN
BAR, MIRROR ABOVE LAV., AND MIRROR ON DOOR (REFERENCE "TOILET ACCESSORY

ED
ED

ED

ED

ED

ED

ED
MOUNTING HEIGHTS" #3, #4 AND #5 THIS SHEET)
3'-6" 1'-0" 24" 12"
22. SUSPENDED WAYFARER SUNGLASSES PROP. REFERENCE 9/A401

US
US

US

US

US

US

US
6'-2"
MIN MIN

2'-912"
6'-0"
3'-4" B.O. 7"-9"

4'-0"

4'-0"

4'-0"

2'-6"
T
T

T
3'-4"
MAX.

MAX.
3'-0"

3'-0"

O
O

O
1'-7"
MIN.
EQ. EQ.
1-SGH4.0-A100-REV00
N

N
1 2 3 4 5 6 7 8 9 10
1'-4" MIN 4'-0"
GRAB BAR GRAB BAR 1'-6" MAX GRAB BAR MIRROR MIRROR & UTILITY HOOK TOILET TISSUE DISPENSER UTILITY HOOK HOOK STRIP MOP HOLDER PAPER TOWEL DISPENSER
SECTION PLAN

C-SGH4.0-A100-REV00 C-SGH4.0-A100-REV00 Revisions:


Mark Date By

1 11-28-18

E DRAWING PLAN TUBE HOLDER LANDLORD COMMENTS / PERMIT SET

PROVIDE CABINET DRAWER TYPE HANDLE ON TOP NOTE:


CAP TO EASE THE REMOVING OF THE CAP, OR AS UPON COMPLETION OF PROJECT
COORDINATED WITH CONSTRUCTION MANAGER. GENERAL CONTRACTOR MUST RUN
A NEW PRINT SET OF THE AS-BUILT
STORE DRAWINGS 26'-47
8"
12'-31
8"
1/4" DIAMETER THRU BOLT WITH TOGGLE (ARCHITECTURAL, MECHANICAL,
LEASE DIMENSION
(TYP. OF 2) GWB ELECTRICAL & PLUMBING) AND LEASE DIMENSION
PLACE PRINTS INTO THE PLAN TUBE MECHANICAL UNISEX RAYBAN
48" A.F.F.
HOLDER. LABEL (W/ CLEAR TAPE) ROOM RESTROOM #1 DEPT.
LABEL 2X4
3"

6" STATING: "THIS TUBE CONTAINS 105 103 101 15

LEASE DIMENSION
STORE DRAWINGS AND IS NOT TO
3/4"x2" POPLAR PLYWOOD PAN HEAD
BE REMOVED WITHOUT THE

1'-412"
TRIM PAINT (WHITE) SCREWS 02113-00
CONSENT OF THE STORE

02113-00

FE
MANAGER". TENANT G.C. TO
SUPPLY AND INSTALL DRAWING 7
02101-00 02431-00
32"

1/2" DIA. HOLE

DIG-0005T-00-LOC1 02434-00
TUBE ASSEMBLY WHERE INDICATED 19 02110-00 02100-00

02101-00 02100-00 02110-00 02101-00


14 G.A. MTL.STRAP 02113-00
IN BTM CAP ON PLANS OR AS DIRECTED BY P.M.
(TYP. OF 2)
18
Architect / Engineer of Record
9 16 2"
WALL

RB-F-RN-MP
6" DIA. PVC TUBE MOUNTED 1
3"

FE
PVC BOTTOM CAP GLUED IN PLACE, G.C.
TO DRILL 1/2" DIA. HOLE IN CENTER OF 7

02101-00 02110-00 02110-00 02110-00


ELEVATION BOTTOM CAP SCALE: 1" = 1'-0" 5

3'-0"

02432-00 02100-00
DOWN
04438-00
Seal

02113-00

04327-00

04435-00
2"
1
36 x 12 x 96
PIPP SHELF
LEASE DIMENSION

LEASE DIMENSION
04437-00

LEASE DIMENSION
5"
2

4"

4"
32'-83

32'-83

3'-1"
22

4"
1 A200 4

31'-41
19

00
17

36 x 12 x 96
PIPP SHELF

0-
UP

20

04434-00
3

02
20

04811-00
3'-0"

1'-95
8" 04437-00

DIG-0003L-00-LOC2
3 2

04435-00
36 x 12 x 96
PIPP SHELF
A200 5 TYP.
11 6
04438-00
1'-6"
CENTERLINE OF Architect / Engineer Job No.:
CASHWRAP AND
17 030

36 x 12 x 96
PIPP SHELF
5 BACKWRAP. SEE A101

04305-00
Nextore Store Design Revision No.:

04835-00

1'-2"
DES REV 02

04303-00
TECH
14

MICROWAVE
12 Nextore project

FRIDGE
8"

DIG-0006T-00-LOC3
6 5 Number 77889

04465-00
04466-00

04463-00

04462-00

04462-00

04463-00
Brand Design Type:

SAFE
13
04404-00 04423-00 04404-00 04424-00 SGH 4.1 - TIER B GOLD
17 7 04451-00
ALIGN

FE
36 x 12 x 96 36 x 12 x 96
ISSUED FOR:
PIPP SHELF PIPP SHELF X Construction

BACK OF BACK OF 8 RETAIL


HOUSE HOUSE SALES AREA
104 102 100 1"
Title
1
F.D. 4'-0" 2'-11
8" 2'-11
8" 4'-0" 4'-0"
FIXTURE - FLOOR
31'-81
8"
PLAN
LEASE DIMENSION

FIXTURE - MEZZANINE FLOOR PLAN FIXTURE - FIRST FLOOR PLAN Date Sheet
2 SCALE: 1/4" = 1'-0"
1 SCALE: 1/4" = 1'-0"
11-28-18
Drawn By

Checked By
STAFF A100
STAFF
DESIGN & CONSTRUCTION
MANAGEMENT:
A DOOR SCHEDULE 1 KEYED NOTES #

SUPPLY FINISHED SIZE DOOR FRAME 1. LEASE LINE.


DESCRIPTION LATCH FUNCTION FIRE DOOR JAMB HEAD 2. EXISTING STOREFRONT SYSTEM TO REMAIN. SEE PLANS AND ELEVATIONS FOR SCOPE OF WORK INFORMATION.
SYM. FIN./ FIN./ THRESH. REMARKS
USE / TYPE WIDTH HGHT. THK. MAT. MAT. DEVICE LOCK LABEL TYPE TYPE TYPE 3. EXISTING TENANT SEPARATION WALL. G.C. SHALL PATCH/ REPAIR GYP BD. AS REQUIRED. MAINTAIN REQUIRED RATING. G.C. TO
INSTALL COLOR COLOR a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000
PROVIDE AND INSTALL METAL SECURITY MESH WHEN TENANT SEPARATION WALL STOPS SHORT OF DECK, U.N.O. a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484
GC EXISTING ENTRY DOORS 4. CONCRETE MUST BE LEVEL AND CLEAN OF ANY FOREIGN MATERIALS PRIOR TO INSTALLING NEW FINISHED FLOORING. G.C. TO
100 3'-0" 8'-8 1/2" EXIST. EXIST. EXIST. EXIST. EXIST. YES EXIST. EXIST. A EXIST. EXIST. EXISTING EXTERIOR DOOR TO REMAIN. G.C. TO ENSURE PROPER WORKING ORDER OF DOOR AND HARDWARE.
GC (EXTERIOR) PERFORM CONCRETE MOISTURE VAPOR EMISSIONS TEST BEFORE INSTALLING ANY FLOORING - REFER TO SPECIFICATIONS FOR
MOISTURE TEST PROCEDURES.
GC FRAMELESS
ENTRY DOORS MATCH SEE HWRE SEE 5. LINE OF NEW SOFFIT ABOVE.
101 (2) 3'-0" ? 2" 1/2" TEMP. PRE-FINISH ALUM. NO NONE B N/A -
GC (INTERIOR) STOREFRONT SCHEDULE SECTION
GLASS 6. ELECTRICAL DISTRIBUTION EQUIPMENT. REFER TO ELECTRICAL DRAWINGS.
PAINT JAMB, CLOSER AND HINGES FROM EZYJAMB 7. PHONE BOARD. REFER TO ELECTRICAL DRAWINGS.
G.C. PAINT
SALES TO WOOD FRAME- MATCH SEE SEE
102 3'-0" 7'-0" 1 3/4" MATCH NO NONE NONE NONE E NOTE:EZYJAMB" INSWING ISD -CONCEALED CLOSER ON "PULL-SIDE" PER "EZYJAMB RECOMMENDATIONS 8. SEE ACCESSIBILITY SIGNAGE, REFER TO DETAIL 10/A401.
GC NON-SALES SOLID CORE LESS WALL 8/A400 8/A400
WALL -FIELD CUT RABBET AND MORTISE OF DOOR AS REQUIRED 9. TRANSFORMER ABOVE. REFER TO ELECTRICAL DRAWINGS.
ACRYLIC
G.C. 10. FOR RESTROOM ACCESSORIES, REFER TO SHEET A100.
103
EXISTING UNISEX
3'-0" EXIST. EXIST. EXIST. EXIST. EXIST. EXIST. EXIST. EXIST. EXIST. EXIST. GC TO INSTALL COAT HOOK AND MIRROR ON INSIDE SIDE OF DOOR. SEE FIXTURE PLAN. G.C. TO ENSURE PROPER WORKING ORDER OF DOOR AND HARDWARE. Construction for:
GC RESTROOM #1 11. 3'-0" CLEAR FLOOR SPACE IN FRONT OF ELECTRICAL PANELS.
12. G.C. TO PROVIDE CONTINUOUS 1X6 F.R.T. WOOD FURRING FOR PIPP SHELVING. CENTERLINE OF BLOCKING TO BE MOUNTED AT
G.C. PAINT 7'-10" A.F.F. SECURE FURRING TO WALL STUDS WITH (3) #12 X 2 1/2" LONG STEEL SCREWS @ EACH STUD LOCATION. (IF WALL IS
104 ACCESS PANEL 2'-0" 2'-0" - PAINTABLE MATCH - - NO TWIST NONE NONE N/A N/A N/A -
GC CONCRETE BLOCK, USE HILTI HIT HY20 1/2" DIA. X 6" EMBEDMENT @ 16" O.C.-STAGGERED) SECURE EACH LEG OF SHELVING TO
CEILING
FURRING WITH (2) #12 X 2" LONG STEEL HEX HEAD SCREWS - DRYWALL SCREWS ARE PROHIBITED.
PAINT
G.C. PAINT 13. 5'-0" ACCESSIBLE TURNING RADIUS.
HOLLOW HOLLOW MATCH EXTERIOR SEE HWRE
105 SERVICE DOOR 3'-0" 7'-0" 1 3/4" MATCH NONE D 3 VARIES -
GC METAL METAL WALL ONLY SCHEDULE 14. ACCESSIBLE MANEUVERING SPACE. (TYP.)
WALL ACRYLIC
15. LINE OF EXISTING MALL SOFFIT ABOVE STOREFRONT.
G.C. TO INSPECT EXISTING DOOR HARDWARE AND COMPARE WITH APPLICABLE HARDWARE SPECIFIED HEREIN
1. IF EXISTING HARDWARE IS COMPATIBLE WITH THAT SPECIFIED BELOW, RETAIN EXISTING AND REPLACE MISSING OR DAMAGED COMPONENTS PER SPECIFIED ITEMS, AS APPLICABLE. 16. G.C. TO PATCH/REPAIR WALL AT AREAS OF ANY WALL DEMOLITION.

4000 Luxottica Place Mason, Ohio 45040


A Subsidiary of the Luxottica Group
2. IF EXISTING HARDWARE IS NOT COMPATIBLE WITH THAT SPECIFIED, RETAIN EXISTING HARDWARE AND CONSULT OWNER AND ARCHITECT FOR DIRECTION ON NEED FOR MODIFICATION OR REPLACEMENT 17. G.C. TO INFILL EXISTING WALL TO MATCH EXISTING CONSTRUCTION.
3. G.C. TO COORDINATE WITH STOREFRONT VENDOR FOR NEW STOREFRONT DOOR. HARDWARE - SEE SPECIFICATIONS BELOW. 18. HATCHED AREA INDICATES EXTENT OF TRENCHING. COORDINATE TRENCH LOCATION WITH SHEET A104 & ELEC. SHEETS
A-SGH40-A101-REV 02 19. SUSPENDED WAYFARER SUNGLASSES PROP, REFER TO DETAIL 9/A401.
20. G.C.. TO ENSURE PLUMBING FIXTURES ARE IN GOOD WORKING ORDER.

REVISION #1
21. RAY BAN SIGN PER SHOP DRAWINGS (WALL MOUNT).

B HARDWARE SCHEDULE C DOOR TYPES 22.


23.
CENTERLINE OF BACKWRAP AND CASHWRAP.
1/2" F.R.T. PLY. IN-WALL BLOCKING FOR LED SCREENS AND BRACKETS. SEE 14/A401.
24. GC TO SUPPLY AND INSTALL 1/2" F.R.T. PLY. IN-CEILING BLOCKING FOR SALES FLOOR PERIMETER WALL FIXTURES.

RESTOOM #1
NON-SALES
EXISTING V.I.F. G.C. TO REPLACE IF REQUIRED TO BE IN LIKE NEW CONDITION

(EXTERIOR)

(INTERIOR)

SALES TO

SERVICE
ACCESS
CLOSER 25. RAY BAN PLATFORM BY G.C.. SEE DETAIL 2/A401.

DOORS

DOORS

UNISEX

PANEL
ENTRY

ENTRY

DOOR
FURNISH & INSTALL BY G.C.
26. EXISTING DOOR TO REMAIN ENSURE PROPER WORKING ORDER.
FURNISH BY TENANT & INSTALL BY G.C.
27. INDICATES BEARING STUD LOCATION, SEE FRAMING PLAN.
FURNISH & INSTALL BY LANDLORD. METAL FRAME
28. AT FRAMING LAYOUT STAGE G.C. TO VERIFY BEARING STUD CAN BE INSTALLED THIS LOCATION AS SHOWN.

ED

ED

ED
101 102 103 104 105 PEEP HOLE PUSH 29. PARTIAL HEIGHT CONSTRUCTION THIS AREA. SEE ELEVATIONS AND DETAILS
VIEWER PLATE

US

US

US
1
EXISTING (VERIFY REPLACE, OR PROVIDE IF REQUIRED) A101 (OPP. SIDE)

7'-0"

7'-0"

7'-0"
T

T
HINGES

O
PIVOT HINGES: SPECIFIED BY DOOR MANUFACTURER

N
HINGES: BOMMER 1 1/2 PAIR PER LEAF, 4-1/2" X 4-1/2", NO. BB5004N STANDARD WEIGHT, AVERAGE FREQUENCY, PANIC KICK
PLATE

3'-2"

3'-2"
FULL MORTISE, BALL BEARING HINGE, FINISH: STAINLESS STEEL
HARDWARE
HINGES: BOMMER OR EQUAL, 2 PAIR PER LEAF, 4-1/2" X 4-1/2", NO. BB5004N HEAVY WEIGHT BALL BEARING WITH (OPP. SIDE)
NON-REMOVABLE PIN, FINISH 620 OR US15A
ROKYORK RY-50 - ( QUANTITY PER DOOR = 3 )
2 GENERAL NOTES
A. COORDINATE SLAB CUTTING AND CORE DRILLING WITH MALL OPERATIONS MANAGER PRIOR TO BEGINNING WORK.
EXISTING (VERIFY REPLACE, OR PROVIDE IF REQUIRED) A B C D E B. PREPARE THE FLOOR SLAB AND PROCURE MATERIALS REQUIRED AT THE ENTRANCE TO PRODUCE A FLUSH CONDITION
FRAMELESS GLASS DOOR HARDWARE SET BY STOREFRONT VENDOR. (U.N.O.) GLASS WITH EXPOSED EDGES, TO BE FLAT POLISHED;
FINISH SATIN CLEAR ANODIZED. BOTTOM RAIL: 6" HIGH. FINISH TO MATCH STOREFRONT
BETWEEN THE TENANT STORE CLOSURE LINE AND THE EXISTING MALL FLOORING, AS REQUIRED.
NARROW STYLE, SINGLE ACTING DOOR; FINISH SATIN CLEAR ANODIZED BOTTOM RAIL: 6" HIGH. FINISH TO MATCH STOREFRONT. C-SGH40-A101-REV 01 C. INSTALL ALL FINISH FLOORING (I.E.: CARPET, WOOD, TILE) AND ALL FINISH WALL MATERIALS BEHIND AND UNDER ALL
TOP RAIL: FULL TOP RAIL: 4" HIGH. FINISH TO MATCH STOREFRONT MILLWORK, U.N.O.
ENTRIES & EXITS

STORE ID, SPACE, BUILDING ADDRESS NUMBERS (PER TENANT CRITERIA) D. ADEQUATE ACCESS PANELS OR DOORS SHALL BE INCORPORATED INTO TENANT WORK FOR INSPECTION SERVICE AND
Revisions:
PUSH/PULLS: (2) PR., 12" VERTICAL PULL WITH 28" HORIZONTAL PUSH REPLACEMENT OF BOTH LANDLORD AND TENANT EQUIPMENT. COORDINATE PLACEMENT WITH LANDLORD'S ON-SITE
Mark Date By
REPRESENTATIVE.
PUSH PLATE: HAGER HINGE CO.: #40R, 4"W X 16"H, FINISH US26D 11-28-18
E. PROVIDE 3/4" FIRE RETARDANT PLYWOOD BEHIND ALL ELECTRICAL AND TELEPHONE PANELS, PAINT TO MATCH WALL COLOR 1

FINISH PRIOR TO HARDWARE INSTALLATION. LANDLORD COMMENTS / PERMIT SET


PULL: HAGER HINGE CO.: #4L, WROUGHT DOOR PULL 1" DIA. X 12"H, FINISH US26D

PUSH/PULLS: (2) PR., - ASSA ABLOY - ROCKWOOD - MEZZOTEK 12" PUSH/PULL - BRUSHED ALUMINUM
REVISION #1 F. PROVIDE EXPANSION BETWEEN ALL NEW WALLS AND THE EXISTING ROOF STRUCTURE ABOVE, U.N.O OR DETAILED IN
ALL REQUIRED HARDWARE BY GC

DRAWING.
PEEPHOLE G. PATCH/REPAIR ALL SURFACES (WALLS, FLOOR, CEILING, ETC.) AFFECTED BY DEMOLITION WORK, AS REQUIRED.
NOTE: LANDLORD HAS INDICATED THE
EXISTING (VERIFY REPLACE, OR PROVIDE IF REQUIRED) EXISTING ENTRY DOORS AND H. TRANSITIONS BETWEEN DISSIMILAR FLOOR MATERIALS TO BE SMOOTH AND FLUSH. REFER TO SHEET A-502 FOR FOR
LOCK & LATCHSETS

WINDOWS WILL BE REPLACED BY APPLICABLE FLOOR TRANSITION DETAILS.


BOTTOM RAIL CYLINDER LOCK. BEST CYLINDER ABLE TO ACCEPT 7 PIN INSTA-KEY CORE. PROVIDED BY LUXOTTICA. LANDLORD AT A DATE T.B.D.... I. ALL FINISH MATERIALS SHALL BE INSTALLED PER MANUFACTURER'S STANDARD WRITTEN DETAILS AND SPECIFICATIONS. REFER
LOCKSET: STANDARD 3 POINT LOCKING; (2) FLUSH BOLT - INACTIVE LEAF; (1) THROW BOLT - ACTIVE LEAF: (1) THUMB TURN - INTERIOR; UNDER SEPARATE PERMIT BY
TO SPECIFICATIONS FOR ADDITIONAL INFORMATION.
(1) "BEST" CYLINDER - EXTERIOR LANDLORD
CORBIN RUSSWIN MODEL #CL3620 NZD (LEVER STYLE); FINISH #BHMA 626 OR SCHLAGE EQUAL; PUSH BUTTON ON J. PROVIDE A LEVEL 4 GYP. BD. FINISH ON ALL NEW AND EXISTING WALLS, U.N.O.
INSIDE AND KEY ON OUTSIDE K. SEAL CONTROL JOINTS IN CONCRETE FLOORS.
LOCK CORES; BEST LOCK CORP.; 9K SERIES 2-SGH40-A101-REV00
REVISION #1
EXISTING (VERIFY REPLACE, OR PROVIDE IF REQUIRED, U.N.O.)

HEAD CLOSER: CONCEALED CLOSER LCN 5030 WITH A HOLD OPEN POSITION OF 90 DEGREES, SINGLE ACTION. NOTE: PATCH AND REPAIR WALLS
CLOSERS

CLOSER ON PULL SIDE OF DOOR PROVIDED BY EZYJAMB


AFTER HORIZONTAL BAND REMOVAL 3 GENERAL ACCESSIBILITY AND LIFE SAFETY:
CORBIN RUSSWIN DC4610 SERIES PARALLEL ARM WITH HOLD OPEN. EVERY EXIT DOOR SHALL BE OPERABLE FROM THE INSIDE WITHOUT THE USE OF A KEY, TOOL, OR SPECIAL KNOWLEDGE OR EFFORT.

EXISTING (VERIFY REPLACE, OR PROVIDE IF REQUIRED) 4 SPECIAL LOCKING DEVICES SHALL BE OF AN APPROVED TYPE. Architect / Engineer of Record
KICKPLATES

FRAMING EXIT DOORS (INCLUDING EXISTING DOORS) SHALL NOT BE LESS THAN 36" IN WIDTH HAND NOT LESS THAN 6'-8" IN HEIGHT.
A400 PLAN
KICKPLATE (MATCH STYLE OF EXISTING SURROUNDING DOOR HARDWARE) PROJECTIONS INCLUDING PANIC HARDWARE, SHALL NOT REDUCE THE OPENINGS TO LESS THAN 32" IN CLEAR WIDTH.
STANLEY DOOR SYSTEM; FULL WIDTH X 10"H X 1/8" STAINLESS STEEL INSTALLED 1" FROM BOTTOM OF HEIGHT OF THRESHOLDS AT EXIT DOORS SHALL BE 1/2" MAXIMUM.-
8'-0" 8"
DOOR ON PUSH SIDE 1 3 13 14 3 7 CARPET PILE HEIGHT SHALL BE 1/2" MAXIMUM.
EXISTING (VERIFY REPLACE, OR PROVIDE IF REQUIRED) 25 A400 1 AISLES LEADING TO REQUIRED EXITS SHALL HAVE A MINIMUM WIDTH OF 44".-
DOOR STOPS

GLASS DOORS, ADJACENT PANELS, AND ALL GLAZED OPENINGS WITHIN 24" OF ADJACENT FLOORS SHALL BE TEMPERED GLASS.
WALL STOP (MATCH STYLE OF EXISTING SURROUNDING DOOR HARDWARE)
PROVIDE EXIT SIGNS AND DIRECTIONAL EXIT SIGNS AT LOCATIONS SHOWN ON THE FLOOR PLAN. EXIT SIGNS SHALL HAVE A
IVES MODEL #FS13US26 CAST BRASS, CHROME PLATED (OR EQUAL) 7 2 MAXIMUM 6" HIGH BY 3/4" STROKE BLOCK LETTERS ON A CONTRASTING BACKGROUND.

FE
A400 A400
28 EXIT SIGNS SHALL BE INTERNALLY ILLUMINATED BY TWO ELECTRIC LAMPS OR SHALL- BE OF APPROVED SELF-LUMINOUS TYPE. IF TWO
(2) IVES FS13 FLOOR DOME STOP. FINISH #US26D 3
MECHANICAL UNISEX LAMPS ARE USED, POWER SUPPLY TO ONE OF THE LAMPS SHALL BE PROVIDED BY THE PREMISES WIRING SYSTEM. POWER SUPPLY TO

8"
A400
26 10

5
NATIONAL GUARD PRODUCTS: #162 DKB - HEAD & JAMB; #15 DKBN OR APPROVED EQ. AT BOTTOM 6 27
THRES-

THE OTHER LAMP SHALL BE FROM STORAGE BATTERIES. THE SYSTEM SHALL BE INSTALLED IN ACCORDANCE WITH THE NATIONAL
HOLDS

1'-11
THRESHOLD: PEMKO #175A - ALUMINUM; ALLOY 6063-76
ROOM RESTROOM #1 A400 11
105 103 29 ELECTRIC CODE.
A401 100
25 EMERGENCY LIGHTING SHALL BE PROVIDED FROM AN EMERGENCY POWER SYSTEM AND SHALL PROVIDE A VALUE OF ONE FOOT
EXIST.
5 CANDLE AT FLOOR LEVEL.
B-SGH40-A101-REV 01
21 RAYBAN 2
20 DEPT. ALL DOORS TO BE OPERABLE IN THE DIRECTION OF EGRESS TRAVEL AT ALL TIMES. Seal
FE

103 6 101

2"
8 A400 3-SGH40-A101-REV 0.0

12'-31
7
SIM. 1
A400 EXIST. 1'-11 58"
5
26
25
11
4 COMPLIANCE NOTES FOR DOORS
A401
1. DOORS: GENERAL SHALL MEET THE REQUIREMENTS OF THE BUILDING CODE & CURRENT EDITION OF THE LIFE SAFETY CODE.
DOWN

EXIST.
2. REGARDLESS OF THE OCCUPANT LOAD SERVED, EXIT DOORS SHALL BE OPERABLE FROM THE INSIDE WITHOUT ANY SPECIAL
2 KNOWLEDGE OR EFFORT, MANUALLY OPERATED EDGE OR SURFACE MOUNTED FLUSH BOLTS AND SURFACE BOLTS OR ANY OTHER
A400
TYPE OF DEVICE THAT MAY BE USED TO CLOSE OR RESTRAIN THE DOOR OTHER THAN BY OPERATION OF THE LOCKING DEVICE SHALL
27 NOT BE USED. WHERE EXIT DOORS ARE SUED IN PAIRS AND APPROVED AUTOMATIC FLUSH BOLTS ARE USED THE DOOR LEAF HAVING
Architect / Engineer Job No.:
AND AUTOMATIC FLUSH BOLTS SHALL HAVE NO DOOR KNOB OR SURFACE MOUNTED HARDWARE. THE UNLATCHING OF ANY LEAF

8"
12 4 16
16 SHALL NOT REQUIRED MORE THAN ONE OPERATION.
030

PIPP SHELVING, BLOCKING REQUIRED


3. DOOR HARDWARE. HANDLES, PULLS, LATCHES, LOCKS AND OTHER OPERATING DEVICES ON ACCESSIBLE DOORS SHALL HAVE A SHAPE Nextore Store Design Revision No.:
19

5'-6"
3 THAT IS EASY TO GRASP WITH ONE HAND AND DOES NOT REQUIRED TIGHT GRASPING, TIGHT PINCHING OR TWISTING OF THE WRIST
UP

RETAIL
12'-0"
14
SALES AREA
100
2 TO OPERATE LEVER-OPERATED MECHANISMS, PUSH-TYPE MECHANISMS, AND U-SHAPED HANDLES ARE ACCEPTABLE DESIGNS. WHEN
SLIDING DOORS ARE FULLY OPEN, OPERATING HARDWARE SHALL BE EXPOSED AND USABLE FROM BOTH SIDES. HARDWARE REQUIRED
DES REV 02
1 A401 FOR ACCESSIBLE DOOR PASSAGE SHALL BE MOUNTED NO HIGHER THAN 48" (1220 MM) ABOVE FINISHES FLOOR.
Nextore project
4. CLEAR WIDTH. DOOR WAYS SHALL HAVE A MINIMUM CLEAR OPENING OF 32 IN. (815 MM) WITH THE DOOR OPEN 90 DEGREES, Number 77889
3 6 MEASURED BETWEEN THE FACE OF THE DOOR AND THE OPPOSITE STOP OR MOLDINGS..
12 22 Brand Design Type:
5 WALL LEGEND BACK OF
HOUSE
BACK OF
HOUSE CENTERLINE OF 5. MANEUVERING CLEARANCES AT DOORS. FLOOR WITHIN THE REQUIRED CLEARANCES SHALL BE LEVEL AND CLEAR.
SGH 4.1 - TIER B GOLD
104 102 23 CASHWRAP AND 6. THRESHOLDS AT DOORWAYS. THRESHOLDS AT DOORWAYS SHALL NOT EXCEED 3/4 IN. (19 MM) IN HEIGHT FOR EXTERIOR SLIDING
BACKWRAP. SEE A101
CENTER LINE NEW WALL W/ SOUND BATTS DOORS OR 1/2 IN. (13MM) FOR OTHER TYPES OF DOORS. RAISED THRESHOLDS AND FLOOR LEVEL CHANGES AT ACCESSIBLE
3'-0" ISSUED FOR:
DOORWAYS SHALL BE BEVELED WITH A SLOPE NO GREATER THAN 1:2. X Construction
MIN.
LEASE LINE EXISTING WALLS 7. DOOR CLOSURES, IF A DOOR HAS A CLOSER, THEN THE SWEEP PERIOD OF THE CLOSER SHALL BE ADJUSTED SO THAT FROM AN OPEN
7 5"
1'-98
A400 POSITION OF 70 DEGREES, THE DOOR WILL TAKE AT LEAST 3 SECONDS TO MOVE TO A POINT 3 IN. (75 MM) FROM THE LATCH,
TECH

NEW WALLS NEW/EXTG. BULKHEAD 14 MEASURED TO THE LEADING EDGE OF THE DOOR.
3
29 Title
MICROWAVE

A400 8. DOOR OPENING FORCES. THE MAXIMUM FORCE FOR PUSHING OR PULLING OPEN A DOOR SHALL BE AS FOLLOWS:
FRIDGE

WALL TYPES DOOR NUMBER 102


14
DETAIL
#
CONSTRUCTION
1'-10"

#
# 13 3 (1) FIRE DOORS SHALL HAVE THE MINIMUM OPENING FORCE ALLOWABLE BY THE APPROPRIATE ADMINISTRATIVE AUTHORITY.
29
SAFE

SHEET # A400
A401

12
(2)
(a)
(2) OTHER DOORS.
EXTERIOR HINGED DOORS: (RESERVED).
FLOOR PLAN
DOORS SHOWN FULLY OPEN TO DOORS SHOWN PARTIALLY OPEN
FE

7
A400 1 3 (b) INTERIOR HINGED DOORS: 5 LBF (22.2N).
DOORS, HARDWARE, JAMBS, ETC. EXISTING DOORS, HARDWARE, (c) SLIDING OR FOLDING DOORS: 5 LBF (22.2N). Date Sheet
JAMBS, ETC. 11-28-18
THESE FORCES DO NOT APPLY TO THE FORCE REQUIRED TO RETRACT LATCH BOLTS OR DISENGAGE OTHER DEVICES THAT MAY HOLD THE
Drawn By
1 DOOR IN A CLOSED POSITION.
3
MEZZANINE CONSTRUCTION PLAN FIRST FLOOR CONSTRUCTION PLAN
7
A400
Checked By
STAFF A101
5-SGH40-A101-REV 0.0
2 SCALE: 1/4" = 1'-0"
1 SCALE: 1/4" = 1'-0"
4-SGH40-A101-REV 0.0
STAFF
DESIGN & CONSTRUCTION
GENERAL CONTRACTOR= GC
MANAGEMENT:
2 GENERAL NOTES 1 KEYED NOTES # 4 SUNGLASS HUT NXT -LIGHTING SCHEDULE TENANT= T
VENDOR = V

A. EMERGENCY (EM) LUMINAIRES SHALL BE CIRCUITED WITH AN "UNSWITCHED HOT" TO PROVIDE CONTINUOUS POWER TO BATTERY PACK EVEN SYMBOL MARK DESCRIPTION REMARKS SUPPLIED INSTALLED
1. EXISTING A.C.T. CEILING TO REMAIN. BARREL TRACK HEAD, 25W LED, WHITE
WHEN LUMINAIRE IS OFF. STW25 STB25 STW25
2. INSTALL NEW LIGHT FIXTURES AS INDICATED. (TYP)
B. ALL NIGHT-LIGHT (NL) LUMINARES SHALL BE CIRCUITED AHEAD OF ANY SWITCHING STW35 STB35 STB35 BARREL TRACK HEAD, 35W LED, BLACK
C. IT SHALL BE THE G.C.'S RESPONSIBILITY TO UNLOAD INVENTORY AND STORE LIGHTING PACKAGE. THE G.C. SHALL ALSO SHIP ANY EXCESS 3. INSTALL NEW TRACK LIGHT FIXTURES AS INDICATED ON NEW TRACK SECTIONS AS DIMENSIONED. (TYP). NOTE: PENDANT MOUNT a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000
STTW(L) SINGLE CIRCUIT TRACK. REFER TO PLANS FOR RUN LENGTHS. PROVIDE FEEDS, CONNECTORS, CURRENT LIMITERS
6 Creamery Brook, East Granby, CT 06026 +1 (516) 393-2484
MATERIALS BACK TO THE ELECTRICAL PACKAGE DISTRIBUTOR. TRACK LIGHTS REQUIRED FOR THIS LOCATION SEE DETAIL 3/A102. (WHITE) AS NEEDED FOR COMPLETE ENERGY CODE
a p

LIGHTING
D. EXIT LIGHTS AT THE STOREFRONT SHALL BE CEILING MOUNTED AND CENTERED OVER OPENINGS. EXIT/EMERGENCY LIGHTS AT DOOR TO COMPLIANCE SYSTEM. "J-STYLE" TRACK.
4. INSTALL NEW EXIT SIGN (TYP) COORDINATE FINISH WITH CEILING COLOR.
NON-SALES AREAS SHALL BE CEILING MOUNTED AND CENTERED ABOVE DOOR. IF PLAN LOCATIONS ARE NOT ACCEPTABLE, IMMEDIATELY STT(LENGTH IN FEET) STTB(L) SINGLE CIRCUIT TRACK. REFER TO PLANS FOR RUN LENGTHS.
5. - (BLACK)
CONTACT NEXTORE PROJECT MANAGER FOR DIRECTION.
E. WHERE DRYWALL CEILINGS ARE USED IN THE SALES AREA, G.C. SHALL ARRANGE CIRCUITS TO AVOID THE USE OF JUNCTION BOXES IN 6. AUDIO SPEAKERS INSTALLED BY VENDOR. (TYP) WIRE RACEWAY ABOVE GYP. CEILING BY G.C.
G.C. TO INCLUDE IN BID ALL REQUIRED FASTENING
INACCESSIBLE LOCATIONS. THE USE OF JUNCTION BOXES ABOVE DRYWALL CEILINGS SHALL BE LIMITED TO LOCATIONS NEAR ACCESS FRAMES 7. NEW SECURITY CAMERAS INSTALLED BY VENDOR, G.C. TO COORDINATE INSTALL. (TYP)
HARDWARE NOT INCLUDED WITH TRACK LIGHT SS4 1 X 4 FLUORESCENT STRIP LIGHT FIXTURE
USED FOR DIFFUSERS AND RETURN AIR GRILLES OR ACCESS PANELS AS LOCATED ON PLANS. IF PLAN LOCATION IS NOT ACCEPTABLE, 8. INSTALL WIRELESS ACCESS POINT, REFER TO ELECTRICAL SHEETS FOR ADDITIONAL INFORMATION
PENDANT MOUNT SUSPENSION KIT
IMMEDIATELY CONTACT NEXTORE PROJECT MANAGER FOR DIRECTION.
9. EXISTING TRAFFIC COUNTER REMAIN.
F. G.C.'S BID SHALL INCLUDE THE INSTALLATION OF ALL LUMINARES AND ASSOCIATED LAMPS FURNISHED BY NEXTORE. G.C. IS RESPONSIBLE TO EBU1 EMERGENCY LIGHT
ENSURE THE ADJUST ABILITY OF ALL DIRECTIONAL FIXTURES AFTER INSTALLATION AND SHALL AIM THE FIXTURES PER DIRECTION FROM G.C. 10. EXISTING HVAC SUPPLY DIFFUSER TO BE RELOCATED, REFER TO AD200 AND ELEVATION 1/A200.
LIGHT FIXTURE SPECIFICATIONS MAY VARY, IF THIS IS THE CASE, CONTRACTOR SHALL CALL THE LIGHTING DISTRIBUTOR FOR EXACT 11. PROVIDE AND INSTALL ACCESS PANELS FOR SIGN POWER WHERE INDICATED. PROVIDE ADDITIONAL ACCESS PANELS WHERE REQUIRED.
G2L
SALES AREA CEILING SPECIFICATION OF LIGHTING FIXTURES. IF THE CEILING SYSTEMS ARE FIRE RATED, G.C. SHALL CLOSELY COORDINATE FIXTURE REQUIREMENTS ACCESS PANELS TO BE 24"X24" "STEALTH" NO EXPOSED FLANGE TYPE ACCESS PANELS. 2X2 LAY-IN WITH FROSTED LENS
WITH NEXTORE.
G2L-EM Construction for:
12. START CEILING TILE CENTERED ON ROOM UNLESS OTHERWISE DIMENSIONED
G. G.C. SHALL MAKE ALL FINAL CONNECTIONS AS REQUIRED FOR A FULLY COMPLETE AND OPERABLE SYSTEM. G2L
H. G.C. SHALL VERIFY THE VOLTAGE AND COMPATIBILITY OF ALL EQUIPMENT, FIXTURES AND MILLWORK PRIOR TO CONNECTION. 13. EXISTING CEILING GRID TO REMAIN, PROVIDE NEW CEILING TILES.
I. CEILING GRID SHALL BE CENTERED IN ROOM UNLESS OTHERWISE NOTED. 14. EXISTING CEILING TILES AND GRID TO REMAIN. REPLACE ANY DAMAGED OR SOILED TILES WITH NEW MATCHING EXISTING ADJACENT
PENDANT MOUNT
J. DOWN LIGHTS SHALL BE CENTERED IN TILE UNLESS OTHERWISE NOTED. TILES.
TRACK LIGHTING M2 LED DOWNLIGHT
K. SEE SHEET A402 FOR CEILING DETAILS
15. EXISTING LIGHT FIXTURE. SEE ELECTRICAL DRAWINGS.
HVAC AIR DEVICES SHOWN FOR REFERENCE AND
16. EXISTING TRACK LIGHTING FIXTURES, RELAMP. 24x24 -S 24" x 24" SUPPLY DIFFUSER
2-SGH4.0-A102-REV00 COORDINATION. REFER TO MECHANICAL PLANS
17. EXISTING EXIT SIGN FOR MORE INFO. (TYP.)
B.O. LAY-IN CEILING

18. AUDIO SPEAKERS INSTALLED BY VENDOR. (TYP.) WIRE RACEWAY ABOVE EXISTING CEILING GRID WITH NEW TILES.

B.O. TRACK (REQUIRES DESIGN APPROVAL)

4000 Luxottica Place Mason, Ohio 45040


19. PAINT EXPOSED PORTIONS OF DIFFUSERS TO MATCH ADJACENT CEILING FINISH AT SALES AREA (VERIFY IF REQUIRED WITH NEXTORE
SPRINKLER SYSTEM NOTES
16'-7"

A Subsidiary of the Luxottica Group


CONSTRUCTION MANAGER).
24x24-R 24" x 24" RETURN DIFFUSER
20. EXISTING CEILING OUTLET. INSTALL NEW DEVICE AND COVERPLATE TO MATCH CEILING FINISH.
REFERENCE FP100 FOR SPRINKLER INFORMATION 21. EXISTING LINEAL DIFFUSERS, SEE MECHANICAL (TYP.)

HVAC
22. EXISTING HVAC SUPPLY AND RETURN DIFFUSERS.
10'-6"

23. NEW WALL MOUNTED LIT RAY BAN SIGN (REFER TO ELEVATION 1/A200 FOR SIGN LOCATION). GC TO VERIFY MOUNTING
12x12-S 12x12-S 12" x 12" SUPPLY DIFFUSER
REQUIREMENTS PER SIGN SHOP DRAWINGS.
24. EXISTING SPRINKLERS IN RAY BAN CEILING TO RECEIVE NEW BLACK COVER.
25. PAINT TILES AND GRID THIS AREA WITH APPROPRIATE PAINT MATCHING P-41 (BLACK). 12x12-R 12x12-R 12" x 12" RETURN DIFFUSER
26. INSTALL FALSE CEILING GRID TEES AT PERIMETER OF RAY-BAN CEILING (PAINT P-41)
27. ALL EXISTING CEILING DEVICES (ELECTRICAL OR MECHANICAL) TO BE PROFESSIONALLY CLEANED AND ARE TO BE IN GOOD WORKING
ORDER
28. EXISTING RELOCATED LIGHT FIXTURE. SEE EXISTING CEILING PLAN AND ELECTRICAL DRAWINGS
TR-AC024 ACCESS PANEL

TR-AC024
29. SEE DETAILS A & B A103 FOR LAY-IN CEILING INSTALL DETAILS
30. SUSPENDED WAYFARER SUNGLASSES PROP. SEE DETAIL 9/A401.
31. INDICATES PARTIAL HEIGHT CONSTRUCTION BELOW. SEE PLANS AND ELEVATIONS

PENDANT MOUNT TRACK LIGHT DETAIL FSP FIRE SPRINKLER

3
FSP

MISCELLANEOUS
SCALE: 1/4" = 1'-0"
S1 SPEAKER
3-SGH4.0-A102-REV00 1-SGH4.0-A102-REV00 S1
C1
C1 SECURITY CAMERA
ADDENDUM #1 EXIT SIGN
11-27-18 X1(G) X1(R)
X1(COLOR)
(G) = GRTEEN LETTERS (R) = RED LETTERS

WHEN "-EX" IS WRITTEN IN MARK,


-EX -EX
FIXTURE IS CONSIDERED EXISTING.
Revisions:
TC
SHOPPERTRAK - ORBIT FLUSH MOUNT Mark Date By
TC CEILING MOUNTED TRAFFIC COUNTER
ENCLOSURE TO BE INSTALLED
1 11-28-18
LANDLORD COMMENTS / PERMIT SET

NOTE:
G.C. TO VERIFY EXISTING CEILING GRID WIDTH OF 15/16"
4-SGH4.0-A102-REV00
C EXIST. C C-41 MIN. (PROVIDE MEASUREMENT OF 1/32" TOLERANCE) TO
EXIST. GYP. BD. CEIL. GYP. CEIL. @ NEXTORE CONST. MGR. WITHIN ONE DAY OF POSSESSION
@ 7'-11 3/4" A.F.F. 7'-10 1/2" A.F.F. OF TENANT SPACE. THIS DIMENSION IS CRITICAL
MECHANICAL UNISEX RAYBAN REGARDING NEW CEILING TILE INSTALLATION
ROOM RESTROOM #1 DEPT. 11 31
EXIST. A.C.T. CEIL. A401
105 C EXIST. 103 101 4
@ 6'-10 1/2" A.F.F.
NOTE:
5 GYPSUM CEILING & CUSTOMER WALL FACING FINISH
THIS PLAN INDICATES SUGGESTED FINISHING LEVEL DEFINITION - LEVEL 5
X1(R) LOCATIONS ONLY OF SECURITY LEVEL 5 - THE HIGHEST QUALITY FINISH IS THE MOST EFFECTIVE METHOD TO PROVIDE A UNIFORM SURFACE AND MINIMIZE THE POSSIBILITY OF JOINT
Architect / Engineer of Record
9
14 15 27 EX CAMERAS AND SPEAKERS. G.C. MUST PHOTOGRAPHING AND OF FASTENERS SHOWING THROUGH THE FINAL DECORATION. THIS LEVEL OF FINISH IS REQUIRED WHERE GLOSS, SEMIGLOSS
OBTAIN CONFIRMED SPEAKER AND OR ENAMEL ARE SPECIFIED, OR WHEN FLAT JOINTS ARE SPECIFIED OVER AN UNTEXTURED SURFACE, OR WHERE CRITICAL LIGHTING CONDITIONS
EX

E2 STOREFRONT
15 27 OCCUR. THE PREPARED SURFACE SHALL BE COATED WITH A DRYWALL PRIMER PRIOR TO THE APPLICATION OF FINAL DECORATION. ALL JOINTS AND
E2 CAMERA LOCATIONS FROM NEXTORE INTERIOR ANGLES SHALL HAVE TAPE EMBEDDED IN JOINT COMPOUND AND IMMEDIATELY WIPED WITH A JOINT KNIFE OR TROWEL, LEAVING A THIN
E2 C EXIST.
22 E2 M2 CONSTRUCTION MANAGER PRIOR TO COATING OF JOINT COMPOUND OVER ALL JOINTS AND INTERIOR ANGLES. TWO SEPARATE COATS OF JOINT COMPOUND SHALL BE APPLIED OVER
22 EXISTING ENTRY
E2 CONSTRUCTION START. ALL FLAT JOINTS AND ONE SEPARATE COAT OF JOINT COMPOUND APPLIED OVER INTERIOR ANGLES. FASTENER HEADS AND ACCESSORIES SHALL BE
E2 EX ALCOVE LIGHTING COVERED WITH THREE SEPARATE COATS OF JOINT COMPOUND. A THIN SKIM COAT OF JOINT COMPOUND SHALL BE TROWEL APPLIED TO THE ENTIRE
10 AND FINISH TO SURFACE. EXCESS COMPOUND IS IMMEDIATELY SHEARED OFF, LEAVING A FILM OR SKIM COATING OF COMPOUND COMPLETELY COVERING THE
EXISTING GYP. BD. WALL E2 10 19
3 15 REMAIN, G.C. TO PAPER. AS AN ALTERNATIVE TO A SKIM COAT, A MATERIAL MANUFACTURED ESPECIALLY FOR THIS PURPOSE MAY BE APPLIED. THE SURFACE MUST
CEILING 8'-3" RESTORE TO LIKE-NEW BE SMOOTH AND FREE OF TOOL MARKS AND RIDGES. THE PREPARED SURFACE SHALL BE COVERED WITH A DRYWALL PRIMER PRIOR TO THE
23 E2 27 CONDITION APPLICATION OF THE FINAL DECORATION. THE FOLLOWING MATRIX HELPS DEFINE THE EXPECTED APPEARANCE OF EACH LEVEL AND BASIC

2"
EX EX 11

12'-11
EX E2
M2E REQUIREMENTS FOR ACHIEVING THAT LEVEL. ADDITIONAL GUIDELINES ARE OFFERED FOR MEETING THE SPECIFIED FINISH LEVEL USING SHEETROCK
A401 E2
BRAND PRODUCTS AND APPLICATION TECHNIQUE.
E2
22 E2
10 E2 S1
EXISTING GYP. BD. WALL E2 Seal

3'-1"
CEILING 7'-3"
17 M2
3
EX E2
EX E2
E2 E2
EX
EXISTING E2
T1
GYP. BD.
OPEN SOFFIT E2
7'-11"
30 M3
20
8'-0"
EX E2

EX EX
2'-5" 8 E2

14
15 27
15 E2
SALES AREA LAY-IN CEILING NOTE: Architect / Engineer Job No.:
27 M2 E2
EXISTING CEILING GRID DESIGNATED 030
EX
2 T3 FOR RE-USE TO BE PROFESSIONALLY
4'-7" CLEANED (TYPICAL THROUGHOUT). Nextore Store Design Revision No.:
22 22 13
SOFFIT 27 EXISTING GRID TO BE PAINTED P-43
19
M2E
7 FIELD VERIFY EXISTING TO REMAIN DES REV 02
EX
22 TYP. LAY-IN CEILING GRID (2X2) PRIOR TO
ORDERING NEW TILES Nextore project
EX
22 18
Number 77889
31
WALL TYP. S1 Brand Design Type:
SEE 14'-5" 9"
1/A200 SGH 4.1 - TIER B GOLD
T2
EX
EX E1 E1 E1 E2 E1 E1 E3 E1 E1 20
17 ISSUED FOR:
SAFE

3 X Construction
4'-0"

LEVEL 5 - PAINT FINISH OVER GYPSUM BOARD


ALL APPROPRIATELY PREPARED GYPSUM BOARD SURFACES SHALL HAVE ONE COAT OF DRYWALL PRIMER APPLIED TO YIELD A PROPERLY PAINTED Title
BACK OF BACK OF RETAIL SURFACE. TWO SEPARATE COATS OF TOPCOAT MATERIAL SHALL BE APPLIED OVER THE DRYWALL PRIMER TO YIELD A PROPERLY PAINTED SURFACE.
HOUSE
104 C EXIST.
EXIST. A.C.T. CEIL.
HOUSE
102 C EXIST.
EXIST. GYP. BD.
SALES AREA
100 C ACT-40B C P-43
EXISTING CEILING
GRID @ 16'-7" TO
PAINT SHALL BE APPLIED TO THE MIL FILM THICKNESS AND APPLICATION CONDITIONS SPECIFIED BY THE PAINT MANUFACTURER. NOTE THAT THIS
LEVEL IS RECOMMENDED WHERE THE BEST PAINT FINISH IS REQUIRED, SUCH AS UNDER CRITICAL LIGHTING CONDITIONS OR WHEN PAINTS THAT REFLECTED
@ 7'-7" A.F.F. CEIL. @ 8'-9" A.F.F.
BE PAINTED CEILING PLAN
MINIMIZE JOINT AND FASTENER PHOTOGRAPHING AND PROVIDES THE MOST UNIFORM FINAL FINISH.
REFLECTED MEZZANINE CEILING PLAN REFLECTED FIRST FLOOR CEILING PLAN
2 SCALE: 1/4" = 1'-0"
1 SCALE: 1/4" = 1'-0"
Date
11-28-18
Sheet

Drawn By

Checked By
STAFF A102
5-SGH4.0-A102-REV00
STAFF
DESIGN & CONSTRUCTION
GENERAL NOTE: ALL SPECS MAY NOT BE USED IN EVERY STORE.
MANAGEMENT:
SGH4.0 / 4.1 - FINISH SCHEDULE GENERAL NOTES

INSTALLED
1 2 KEY NOTES 3

RECEIVED
SUPPLIED
FOLLOW ALL MANUFACTURERS INSTALLATION AND #
MAINTENANCE INSTRUCTIONS

ITEM MARK DESCRIPTION MFG./PHONE # MODEL #/COLOR ALT. #1 REMARKS 1. EXISTING MALL TILE. PATCH AND REPAIR AT POINT OF CLOSURE, INSTALL TRANSITION STRIP TO NEW TILE FLOORING AS REQUIRED. A. G.C. IS RESPONSIBLE FOR ANY PREPARATION OF THE FLOOR SLAB AND PROCUREMENT OF MATERIALS REQUIRED TO PRODUCE A
FLUSH CONDITION BETWEEN THE STORE LEASE LINE AND THE EXISTING EXTERIOR OF FLOORING.
INTERIOR ACRYLIC LATEX 2. INSTALL NEW SALES AREA PORCELAIN TILE FLOORING.
WALL SHEEN: SATIN CEILING SHEEN: FLAT B. G.C. IS RESPONSIBLE FOR INSTALLING ALL FINISH FLOORING. G.C. IS ALSO RESPONSIBLE FOR ALL FINISH MATERIALS BEHIND AND
PAINT P-40 ACRYLIC PAINT - (LIGHT GREY) BENJAMIN MOORE (866) 708-9180 NONE GC GC GC
COLOR: 1464 LIGHT PEWTER DOORS & TRIM SHEEN: SEMI-GLOSS 3. INSTALL RAY BAN FEATURE AREA (PFT-40) PORCELAIN TILE FLOORING. INSTALL (RFT-41 ON TOP OF PFT-40) UNDER ALL MILLWORK. p
a 4000 Luxottica Place, Mason, OH 45040 +1 (513) 765-6000
INTERIOR ACRYLIC LATEX WALL SHEEN: SATIN CEILING SHEEN: FLAT 4. INSTALL NEW SALES AREA BASE. C. REFER TO ARCHITECTURAL SPECIFICATIONS / FINISHES SCHEDULE THIS SHEET & REFER TO GENERAL NOTES ON SHEET G100 a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484
PAINT P-41 ACRYLIC PAINT - (BLACK) SHERWIN WILLIAMS (800) 474-3794 NONE GC GC GC D. ALL TENANT FURNISHED ITEMS (MATERIAL AND LABOR) TO BE SCHEDULED, COORDINATED AND SUPERVISED BY G.C.
COLOR: TRICORN BLACK SW 6258 DOORS & TRIM SHEEN: SEMI-GLOSS
5. PATCH, REPAIR, PREP AND APPLY FINISH ON ANY EXISTING WALLS. E. REFER TO DOOR SCHEDULE FOR DOOR FINISHES. PREP EXISTING DOORS PRIOR TO RE-FINISHING.
INTERIOR ACRYLIC LATEX WALL SHEEN: SATIN CEILING SHEEN: FLAT F. WHEN INSTALLING A NEW FLOOR, GC TO VERIFY EXISTING FLOOR CONDITIONS MEETS AND ARE IN COMPLIANCE WITH ANSI
PAINT P-43 ACRYLIC PAINT - WHITE BENJAMIN MOORE (866) 708-9180 NONE GC GC GC 6. INSTALL & PAINT RAY BAN FEATURE AREA WALL COVERING AS INDICATED. SEE ELEVATIONS.
COLOR: PM-1 SUPER WHITE DOORS & TRIM SHEEN: SEMI-GLOSS STANDARD FOR THIN SET TILE AND THE LATEST EDITION OF TILE COUNCIL OF AMERICA. IF THERE ARE ISSUES OR DEFICIENCIES,
INTERIOR ACRYLIC LATEX WALL SHEEN: SATIN CEILING SHEEN: FLAT 7. G.C. TO PROVIDE AND INSTALL WATERPROOF MEMBRANE THIS ROOM PER LANDLORD REQUIREMENTS. VERIFY REQUIREMENTS AND CONTACT NEXTORE PROJECT MANAGER PRIOR TO INSTALLATION.
PAINT P-44 ACRYLIC PAINT (DARK GREY) SHERWIN WILLIAMS (800) 474-3794 NONE GC GC GC ANY REQUIRED ON SITE INSPECTIONS WITH LANDLORD DURING PRE-CONSTRUCTION MEETING
APPLIED WALL FINISHES

COLOR: GAUNLET GRAY SW 7019 DOORS & TRIM SHEEN: SEMI-GLOSS G. IF THE CONCRETE WAS PREVIOUSLY SEALED, IT WILL NEED TO BE STRIPPED.
BRICK REALCAST BRICK PANEL, 8. SALES / NON-SALES AREA DOOR TO BE PAINTED. DIRECTIONS:
BWP-41 DIMENSIONAL FAUX BRICKS WALL THEORY (866) 666-0309 NONE GC GC GC
WALL PANEL MATTHEW@WALLTHEORY.COM MEDIUM GREY, RAL7030 TEST FOR OLD SEALER ON THE FLOOR. APPLY A FEW DROPS OF MURIATIC ACID TO THE AREA. IF IT FIZZES, THERE IS NO SEALER
9. BACK OF HOUSE & RESTROOM WALL SHEEN TO BE FLAT.
STOREFRONT SMOOTH CIMENTO - MDF 10. EXITING FLOORING AT ENTRY TO REMAIN, G.C. TO PATCH AND REPAIR AS REQUIRED. IF NO SEALER IS PRESENT, CLEAN THE SURFACE BY APPLYING UNITEX POWERHOUSE DEGREASER DILUTED AT 64 OZ PER GALLON
FC-40 FAUX CONCRETE CASTINGS (INTERIOR) CIMENTO NONE G.C. TO INSTALL PER MANUFACTURER'S SPECIFICATIONS. T GC GC
SURROUND SIZE: 3/4" x 24"x48" COLOR: C05 ANTHRACITE OF WATER WITH A MOP TO A SMALL AREA OF THE FLOOR. USE A FLOOR MACHINE WITH A GREEN PAD TO CLEAN THE AREA. PICK
11. FLOOR TRANSITIONS TO HAPPEN AT C.L. OF DOORS, WHEN IN CLOSED POSITION. (UNLESS OTHERWISE NOTED)
STOREFRONT (866) 666-0309 REALCAST CONCRETE INDUSTRIAL GREY G.C. TO PROVIDE AND INSTALL PER MANUFACTURER'S UP SLURRY WITH A WET/DRY VACUUM. Construction for:
FC-41 FAUX CONCRETE CASTINGS (EXTERIOR) WALL THEORY NONE GC GC GC 12. TERRAZZO AND CERAMIC FLOOR SURFACE MUST BE THOROUGHLY SANDED TO REMOVE ALL GLAZE AND WAXES. REMOVE OR IF SEALER IS PRESENT, STRIP THE FLOOR USING UNITEX MELTDOWN PLUS STRIPPER DILUTED AT 32 OZ PER GALLON OF WATER.
SURROUND MATTHEW@WALLTHEORY.COM SIZE: 24"x48" STYLE: FLAT SPECIFICATIONS.
REPLACE ALL LOOSE TILES AND CLEAN THE GROUT LINES. USE A GOOD QUALITY PORTLAND CEMENT BASED LEVELING COMPOUND APPLY TO THE FLOOR USING A MOP. SCRUB THE FLOOR WITH A FLOOR MACHINE AND BLACK PAD OR STEEL WIRE BRUSH. PICK UP
FIBERGLASS F.R.P. WALL PANELS ACCESSORIES: INSIDE CORNER - #M350, OUTSIDE CORNER - #M360,
FRP-40 MARLITE (800) 377-1221 P 100 WHITE NONE DIVIDERS - #M365, EDGING - #M370 GC GC GC TO FILL ALL GROUT LINES AND OTHER DEPRESSIONS SLURRY WITH A WET/DRY VACUUM. NEUTRALIZE FLOOR BY APPLYING BY MOP EASY PAK NEUTRALIZER DILUTED AT 1 PACKET PER 3
REINFORCED PLASTIC 4'-0" X 8'-0" X 1/8"
GALLONS OF WATER.
PROCOUSTIC UTILIZE PROCOAT PRODUCT LINE FOR CLEANING / PREPARING / PAINT.
13. TRANSITION: TS-42 (SEE 6/A401)
PROCOAT PC-41 PROCOAT PROCOAT (781) 767-2270 NONE GC GC GC TO ETCH CONCRETE THAT HAS NEVER BEEN SEALED: VENTILATE THE AREA. BE SURE TO WEAR PERSONAL PROTECTIVE EQUIPMENT
MATCH P-40 (THIS SCHEDULE) GRID ONLY WHEN NEW TILE USED, GRID & TILE WHEN EXISTING. 14. TRANSITION: TS-41 (SEE 5A/A401) INCLUDING A RESPIRATOR. USING A MOP APPLY MURIATIC ACID TO FLOOR. LET THE FLOOR DRY FOR AT LEAST 24 HOURS BEFORE
15. TRANSITION: TS-43 (SEE 8/A401) SEALING.
WARNING: ALWAYS FOLLOW LABEL DIRECTIONS, AND NEVER MIX PRODUCT UNLESS SPECIFIED IN THE LABEL DIRECTIONS. EACH
16. FULL TILE START SITUATION REACTS DIFFERENTLY AND RESULTS MAY VARY.
PRIMED AND SPRAY PAINTED FOR HIGH QUALITY FINISH.
HARDWOOD BASE HWB-40 1X1 HARDWOOD BASE (DRY: 3/4"X3/4") BY G.C. NONE COLOR TO MATCH WALL THAT THE BASE IS SET ON ( SEMI GLOSS ). GC GC GC 17. FORMGLAS CONCREET (FC-40) RETURNED TO GLAZING

4000 Luxottica Place Mason, Ohio 45040


BASE

A Subsidiary of the Luxottica Group


CDC DISTRIBUTORS 18. MP-40 ALUMINUM DIAMOND PLATE ( SEE 2/A401)
VINYL BASE VB-40 4" H - VINYL BASE JOHNSONITE COLOR: 38-PEWTER NONE - GC GC GC
(513) 560-1040 19. CEILING DEPRESSION TO BE PAINTED P-41 REVISION #1
20. G.C. TO INCLUDE IN BID COST FOR SPECIALTY VENDOR TO APPLY NEW FINISH TO EXISTING DOOR / WINDOW FRAMES (WOOD FINISH)
ON INTERIOR. VERIFY ALLOWABLE FINISHES WITH LANDLORD PRIOR TO INSTALLATION.
PORCELAIN TILE TRANSCERAMICA P612503 GROUT THICKNESS: 1/8" TILE PATTERN: STRAIGHT (STACK BOND)
FLOOR TILE PFT-40 (800) 828-9074 NONE T GC GC 2-SGH4.0-A103-REV00 3-SGH4.0-A103-REV00
(60CM X 120CM 8MM, 23 5/8" X 47 1/8" ) MFG.: ARIOSTEA TEKNO STONE LIGHT GREY, MATTE GROUT SPECIFICATION: MAPEI 02 PEWTER BY G.C.
PORCELAIN TILE TRANSCERAMICA PIETRE ARDESIA NERA GROUT THICKNESS: 1/8" TILE PATTERN: STRAIGHT (STACK BOND)
FLOOR TILE PFT-41 MFG.: FABRICA MARMI E (800) 828-9074 NONE T GC GC
(60CM X 120CM 8MM, 23 5/8" X 47 1/8" ) GRANITI
HONED FINISH GROUT SPECIFICATION: MAPEI 10 BLACK BY G.C.
FLOORING

VINYL COMPOSITION TILE INTERIOR MATERIALS


FLOOR TILE VFT-40
12" x 12" x 1/8"
ARMSTRONG (888) 276-7876
STANDARD EXCELON IMPERIAL TEXTURE
COLOR: 51861 - SOFT WARM GRAY
NONE TILE PATTERN: STRAIGHT (STACK BOND) GC GC GC 4 WALL LEGEND 5 FINISH SYMBOL KEY 6 FIRE RATINGS
NEW YORK COLLECTION; BLACK BASE W/ SIZE: 36" x 72" (DOUBLE DOOR) 36"x36" (SINGLE DOOR)
WALK-OFF MAT WM-40 ULTRA ENTRY MAT MATS INC. 800-628-7462 NONE TRANSITION REQUIRED GC GC GC
CHARCOAL CENTER LINE NEW WALL W/ SOUND BATTS MATERIAL FLAME SPREAD SMOKE DENSITY
CONCRETE CONCRETE STAIN 1 GAL. #PFC-75 TAR BLACK SOLID COLOR F XXXX = FLOOR G XXXX = GLAZING
CS-40 BEHR PREMIUM HOME DEPOT EQUAL INSTALL PER MANUFACTURER'S SPECIFICATIONS GC GC GC
STAIN SOLID COLOR INTERIOR/EXTERIOR CONCRETE STAIN LEASE LINE EXISTING WALLS PLASTIC LAMINATE 80 (BONDED) 95 (BONDED)
B XXXX = BASE
CARPET 26 - 75 450 OR LESS
NEW WALLS NEW/EXTG. BULKHEAD W XXXX = WALL
VINYL TILE 0.45 450 OR LESS
GYPSUM BOARD
C-40 PAINTED CEILING - - PAINT P-40 (FLAT) NONE CEILING SHEEN: FLAT GC GC GC
CEILING T XXXX = TRIM LAY-IN CEILING 25 10
FINISHES

GYPSUM BOARD
CEILING

C-41 PAINTED CEILING - - PAINT P-41 (FLAT) NONE CEILING SHEEN: FLAT GC GC GC = CEILING (SEE RCP FOR FRP 150 245
CEILING C XXXX
LOCATION)
ACOUSTICAL 24" x 24" ACOUSTICAL TILE & SUSPENSION LYRA TEGULAR - 24"x24"x1" - 8360PB ARMSTRONG PRELUDE XL 15/16" SUSPENSION SYSTEM IN: VINYL BASE 0.45 450 OR LESS
ACT-40A ARMSTRONG (877) 276-7876 NONE BLIZZARD WHITE (WH) GC GC GC
CEILING SYSTEM COLOR: WHITE (WH) HIGH PRESSURE LAMINATE 45 130
EXISTING SUSPENSION GRID. INSTALL NEW LYRA TEGULAR CEILING PANELS
ACOUSTICAL 24" x 24" ACOUSTICAL TILE & SUSPENSION LYRA TEGULAR - 24"x24"x1" - 8360PB 4-SGH4.0-A103-REV00 5-SGH4.0-A103-REV00 6-SGH4.0-A103-REV01
ACT-40B ARMSTRONG (877) 276-7876 GC TO SPECIFY CEILING GRID WIDTH WHEN ORDERING. GC TO PAINT GC GC GC
CEILING SYSTEM COLOR: WHITE (WH) EXISTING GRID P-43 (FLAT)
ACOUSTICAL 24" x 48" ACOUSTICAL TILE & SUSPENSION MARS CLIMAPLUS -SQUARE EDGE - 88185 USG DONN BRAND AX 15/16" ACOUSTICAL SUSPENSION SYSTEM -
ACT-42 U.S. GYPSUM (800) 950-3839 NONE GC GC GC
CEILING SYSTEM COLOR: WHITE (WH) WHITE

Revisions:
TRANSITION STRIPS

JOHNSONITE / ROD SEABOLT Mark Date By


TRANSITION TS-40 TRANSITION STRIP (PORCELAIN TO VINYL) PART # CTA-XX-K / #20 CHARCOAL NONE BETWEEN PORCELAIN TILE & VINYL GC GC GC
CDC DISTRIBUTORS (513) 560 - 1040
1 11-28-18
TRANSITION STRIP (WALK-OFF TO PORCELAIN SCHLUTER
TRANSITION TS-41 (800) 472-4588 NONE - GC GC GC LANDLORD COMMENTS / PERMIT SET
TILE) WWW.SCHLUTER.COM STAINLESS STEEL
SCHLUTER SCHLUTER - DECO, ALUMINUM (-A) 1/4" THICK STOREFRONT ENTRY BETWEEN RETAIL TILE AND MALL TILE HEIGHT AS F EXIST F PFT-40
TRANSITION TS-42 TRANSITION STRIP (HARD TILE TO HARD TILE) (800) 472-4588 NONE APPROPRIATE FOR FLOORING TRANSITION, GC GC GC
WWW.SCHLUTER.COM ALUMINUM EDGE
B EXIST B NONE

W EXIST. W P-41
F EXIST
GLASS GL-40 EXTRA CLEAR TEMPERED - - - - THICKNESS DETERMINED BY PROJECT REQUIREMENTS GC GC GC
C EXIST. C C-41
B EXIST
GLAZING

DIFFUSER FILM WHITE


UV-FILM UVF-40 3M DIFFUSER FILM 3M SCOTCHSHIELD (888) 364-3577 NONE SINGLE SIDED (INTERIOR ONLY) T T T
3635-70 (60% TRANSMISSION)
USE 3M RECOMMENDED FOR CLEANING GLASS PRIOR TO MECHANICAL W EXIST. UNISEX RAYBAN
SAFETY & SECURITY FILM ULTRA SERIES APPLICATION ROOM RESTROOM #1 DEPT. F MP-40 18 F PFT-41
SECURITY FILM SF-40 3M SCOTCHSHIELD (888) 364-3577 NONE T T T
8 MIL. MODEL: ULTRA S800 105 C EXIST. 103 101
HATCHED
AREA

METAL PLATE MP-40 ALUMINUM DIAMOND PLATE - 14 GA. DIAMONDLIFE (888) 983-4327 NATURAL ALUMINUM DIAMOND PLATE NONE - GC GC GC
GC RESPONSIBLE FOR NEW AND OR REFURBISH OF CONSTRUCTION FOR
METAL POWDER COATED PRISMATICPOWDERS
MF-40 866-774-7628 COLOR: RAL-9005 (GLOSSY) NONE STOREFRONT VENDOR TO APPLY FINISHES. GC GC GC TS-41
MISC.

FINISH METAL & CLADDING .COM G.C. TO PROVIDE ALTERNATE PRICING FOR SUPPLY / INSTALL. F WM-40
METAL POWDER COATED PRISMATICPOWDERS COLOR: BLACK JACK (FLAT) 14 Architect / Engineer of Record
MF-41 866-774-7628 NONE GC GC GC W BWP-41
FINISH METAL & CLADDING .COM USS-1522
6 FULL
TILE 10
1-SGH41-A103-REV08
ALIGN START

FULL TILE
TILE WITH
WALK-OFF MAT
REVISION #1

16 ALIGN START TILE

DOWN
WITH EXISTING
EXTERIOR WALL

Seal

2 4 5

UP
Architect / Engineer Job No.:
030
Nextore Store Design Revision No.:

DES REV 02
11 13
Nextore project
TS-42 Number 77889
Brand Design Type:

SGH 4.1 - TIER B GOLD


8
ISSUED FOR:
X Construction

BACK OF BACK OF RETAIL


HOUSE HOUSE SALES AREA
EXISTING PORCELAIN TILE
104 F EXIST 102 F EXIST 100 F PFT-40
FLOORING IN NON-SALES AREA
Title
B EXIST B EXIST B HWB-40

W EXIST. W EXIST. SEE ELEVATIONS SHEET A200 W P-40 W P-44 FINISH PLAN AND
C EXIST. C EXIST. SEE RCP SHEET A102 C ACT-40B SCHEDULE
Date Sheet
11-28-18
MEZZANINE FINISH PLAN FIRST FLOOR FINISH PLAN Drawn By

2 SCALE: 1/4" = 1'-0"


1 SCALE: 1/4" = 1'-0"
Checked By
STAFF A103
STAFF
DESIGN & CONSTRUCTION
MANAGEMENT:

a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000


a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484

Construction for:

4000 Luxottica Place Mason, Ohio 45040


A Subsidiary of the Luxottica Group
Revisions:
Mark Date By

1 11-28-18
LANDLORD COMMENTS / PERMIT SET

2
1 GENERAL NOTES
A. DIMENSIONS SHOWN ARE DIAGRAMATIC. G.C. TO VERIFY EXACT
4'-113
4" QUANTITY & LOCATION IN FIELD WITH ELECTRICAL ENGINEERING
DRAWINGS AND FIXTURE SHOP DRAWINGS.
MECHANICAL UNISEX RAYBAN B. ALL RETAIL SALES AREA RECEPTACLES SHOWN ON THIS PLAN TO BE
ROOM RESTROOM #1 DEPT. 1'-5 1/2" A.F.F., OR 1'-7 1/2" A.F.F. UNO. COORDINATE WITH
105 103 101 ELEVATIONS, ELECTRICAL ENGINEERING DRAWINGS AND FIXTURE
SHOP DRAWINGS FOR RECEPTACLE HEIGHTS.

C. RECEPTACLES IN ALL OTHER AREAS TO BE 1'-6" A.F.F., UNO.


COORDINATE WITH ELEVATIONS, ELECTRICAL ENGINEERING
DRAWINGS AND FIXTURE SHOP DRAWINGS FOR RECEPTACLE
HEIGHTS.
6
Architect / Engineer of Record

2"
6

4'-21
1
TYP.

TYP.
1 2
2 KEY NOTES #

1. MOUNT RECEPTACLE HORIZONTALLY AT 2 1/2" ABOVE PLATFORM THIS


AREA.

2"
6'-01
NOTE:
2. REFERENCE ELECTRICAL DRAWINGS TO VERIFY DEVICE LOCATIONS AT
FIXTURE SHOP DRAWINGS MUST BE REVIEWED RAY BAN AREA. DIMENSIONS SHOWN ARE APPROXIMATE
9 PRIOR TO CONSTRUCTION START TO VERIFY
3. BACKWRAP WALL. REFERENCE ELECTRICAL SHEETS FOR DEVICE
DEVICE INSTALL LOCATIONS AND QUANTITIES REQUIREMENTS THIS AREA.
AND TYPE REQUIRED (NO EXCEPTIONS).
4. LED WALL. REFERENCE INTERIOR ELEVATIONS AND DETAIL A AND B THIS
1 SHEET.
1'-93
4"
TYP. 5. CONVENIENCE OUTLET. INSTALL AT 1'-6" A.F.F. Seal
6. REFERENCE ELECTRICAL SHEETS FOR DEVICE REQUIREMENTS THIS AREA.

7. EXISTING FLOOR OUTLET. REFERENCE ELECTRICAL DRAWINGS.


8. FLOOR POWER AND OR DATA. REFERENCE ELECTRICAL DRAWINGS

4"
3'-01
8
9. MONITOR/DIGITAL DISPLAY. REFERENCE ELECT. DRAWINGS. (VERIFY
6 3 RECEPTACLE INSTALL HEIGHT WITH SHOP DRAWINGS.

4"
3'-03
8 INSTALL FIXTURE
8 CENTERED ON
GLAZING AS SHOWN
3 ELECTRICAL SYMBOLS
Architect / Engineer Job No.:
8 DUPLEX RECEPTACLE, (CLG) DENOTES CEILING MOUNTED 030
CENTERLINE OF
3'-0"
CASHWRAP AND
BACKWRAP. SEE Nextore Store Design Revision No.:
A101 TO LOCATE. QUAD RECEPTACLE, (CLG) DENOTES CEILING MOUNTED

DES REV 02
DATA, (CLG) DENOTES CEILING MOUNTED
TECH

Nextore project
Number 77889
MICROWAVE
FRIDGE

FLOOR MOUNTED QUAD RECEPTACLE


Brand Design Type:

SGH 4.1 - TIER B GOLD


SAFE

9 FLOOR MOUNTED DATA


ISSUED FOR:
X Construction
FLOOR MOUNTED DEVICE. SEE ELECTRICAL
DRAWINGS FOR ADDITIONAL INFORMATION

BACK OF BACK OF RETAIL


HOUSE HOUSE SALES AREA Title
104 102

3'-01 2'-11 3'-01


100

2'-03
4 FLOOR POWER / DATA NOTES ELECTRIC / DATA
F.D. 2" 2" 4" 4'-0" 4"

(3'-31
NOTE: INTENT IS FOR EXISTING FLOOR BOX LOCATIONS TO BE RE-USED WHERE APPLICABLE. REFERENCE
DEMOLITION PLAN AND ELECTRICAL DRAWINGS FOR ADDITIONAL INFORMATION
DIMENSIONAL PLAN
2
NOTE: FLOOR BOX DIMENSIONS ARE BASED ON CURRENT FURNITURE LAYOUT. E.C. IS RESPONSIBLE FOR CORE
ELECTRIC / DATA - MEZZANINE FLOOR PLAN ELECTRIC / DATA - FIRST FLOOR PLAN DRILLING AND OR TRENCHING , REMOVAL OF CONCRETE, AND PATCHING OPENING WITH NEW CONCRETE Date Sheet
2 SCALE: 1/4" = 1'-0"
1 SCALE: 1/4" = 1'-0"
FOR INSTALLATION OF CONDUITS AND FLOOR BOXES. E.C. SHALL CONFIRM PLACEMENT OF FURNITURE PRIOR
TO TRENCHING AND OR CORE DRILLING FLOOR AND CONFIRM ALL DIMENSIONS TO BE ACCURATE. (TYP. OF
11-28-18
Drawn By
ALL). IF REQUIRED E.C. SHALL BE RESPONSIBLE FOR X-RAY OF EXISTING FLOOR. ALL FLOOR WORK SHALL BE
DONE AFTER HOURS SO NOT TO DISTURB TENANTS.
Checked By
STAFF A104
STAFF
DESIGN & CONSTRUCTION
MANAGEMENT:
EXISTING MECHANICAL GRILLES
TO EXTEND THROUGH NEW
CONSTRUCTION AS REQUIRED.
UNISEX RAYBAN APPROXIMATE EXISTING W P-41
RESTROOM #1 DEPT. LOCATIONS SHOWN. G.C. TO
103 101 FIELD VERIFY EXISTING LOCATIONS
W P-40
AND CLEAN TO LIKE-NEW a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000
SHADING INDICATES CONDITION. PAINT TO MATCH a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484
02113-00 IN-WALL BLOCKING, ADJACENT WALL FINISH

02113-00
2'-0"

FE
SEE DETAIL 14/A401.

F.D.
02101-00 02431-00

DIG-0005T-00-LOC1 02434-00
02110-00 02100-00

02101-00 02100-00 02110-00 02101-00


02113-00
PAINT LINE W BWP-41 ILLUMINATED

16'-7"
RB-F-RN-MP SIGNAGE SEE
SHOP DRAWINGS

RB-F-RN-MP

T.O. FURR-OUT. SEE DTLS.


W P-44

Construction for:

+/-9'-6"

B.O. SIGN
02101-00 02110-00 02110-00 02110-00
W P-40

8'-6"
2"
2"

7'-101
7'-101
PAINT LINE

02432-00 02100-00
B HWB-40

4"
04835-00 DIG-0003L-00-LOC2 02432-00 DIG-0005T-00-LOC1 02434-00 02431-00

4000 Luxottica Place Mason, Ohio 45040


04438-00 02113-00 02110-00 02110-00 02110-00 02110-00 02113-00
F MP-40

A Subsidiary of the Luxottica Group


- P-44

02113-00

04327-00

04435-00
02101-00 02100-00 02101-00 02100-00 02101-00

36 x 12 x 96
PIPP SHELF
DOOR RAY BAN PLATFORM,
SEMI-GLOSS REFER TO FINISH PLAN
04437-00 ELEVATION AND DETAIL 11/A401
2
1 SCALE: 1/4"=1'-0"

00
36 x 12 x 96

0-
PIPP SHELF
1 A200 4

20

04434-00
02

04811-00
3

04437-00

DIG-0003L-00-LOC2

04435-00
36 x 12 x 96
PIPP SHELF
04438-00
W P-40
A200 5
W P-41 W P-40

36 x 12 x 96
PIPP SHELF
6

04305-00
SHADING INDICATES IN-WALL

04835-00
BLOCKING, SEE DETAIL 13/A401.

04303-00
TECH

W BWP-41
PAINT LINE PAINT LINE

16'-7"
MICROWAVE

+/-9'-6" T.O. FURR-OUT. SEE DTLS.

+/-9'-6" T.O. FURR-OUT. SEE DTLS.


FRIDGE

DIG-0006T-00-LOC3

04465-00
04466-00

04463-00

04462-00

04462-00

04463-00
W P-44 W P-44
SAFE

04404-00 04423-00 04404-00 04424-00


04451-00
FE W P-40 W P-40

7'-1012"

7'-1012"

7'-1012"
36 x 12 x 96 36 x 12 x 96 Revisions:
PIPP SHELF PIPP SHELF Mark Date By
PAINT LINE PAINT LINE
1 11-28-18
BACK OF RETAIL B HWB-40 B HWB-40
HOUSE SALES AREA LANDLORD COMMENTS / PERMIT SET

102 100

4"

4"
04424-00 04404-00 04451-00 04423-00 04404-00

DIG-0006T-00-LOC3
04465-00

04463-00

04462-00

04462-00

04463-00

04466-00
02110-00 02434-00 02101-00 02431-00 02113-00
02113-00 02110-00 02100-00
F MP-40
RAY BAN PLATFORM,
FLOOR PLAN REFERENCE ELEVATION REFER TO FINISH PLAN ELEVATION
A SCALE: 1/4"=1'-0"
2 SCALE: 1/4"=1'-0"
AND DETAIL 11/A401 3 SCALE: 1/4"=1'-0"

REVISION #1
NOTE: SEE FINISH
PLAN FOR NOTE
REGARDING
EXISTING WOOD
FINISH (LANDLORD
APPROVAL Architect / Engineer of Record
W P-40 REQUIRED PRIOR
TO ANY
MODIFICATIONS
TO EXISTING
WOOD FINISH)
W P-40

PAINT LINE
16'-7"

W EXIST.
+/-9'-6" T.O. FURR-OUT. SEE DTLS.

+/-9'-6" T.O. FURR-OUT. SEE DTLS.

W P-44

W P-40
W EXIST. W EXIST.

8'-9"

8'-9"
2"
7'-101

PAINT LINE Seal


4'-0" MAX.

4'-0" MAX.
B HWB-40
4"

B EXIST. B EXIST.
04435-00 04434-00 04435-00 04303-00

3/4" F.R.T. PLY. PAINT 3/4" F.R.T. PLY.


FOR PIPP (SEMI-GLOSS), FOR PIPP
ELEVATION ELEVATION SHELVING (TYP.) MATCH EXISTING ELEVATION SHELVING (TYP.)
4 SCALE: 1/4"=1'-0"
5 SCALE: 1/4"=1'-0"
6 SCALE: 1/4"=1'-0"

Architect / Engineer Job No.:


030
Nextore Store Design Revision No.:

DES REV 02
Nextore project
Number 77889
Brand Design Type:

SGH 4.1 - TIER B GOLD

ISSUED FOR:
X Construction

Title

INTERIOR
ELEVATIONS
Date Sheet
11-28-18
Drawn By

7
NOT USED
8
NOT USED
9
NOT USED
10
NOT USED
11
NOT USED Checked By
STAFF A200
STAFF
DESIGN & CONSTRUCTION
MANAGEMENT:

BEARING STUDS. SEE HIGH BOX BEAM 3" X 3" X 16 GA. FRAMING
FRAMING PLAN ANGLE WITH (4) #12 TEK
SCREWS EA. LEG. EA SIDE
BOX BEAM ABV. SEE a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000
OF BEAM
FRAMING PLAN a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484

LOW BOX BEAM

SEE PLAN
Construction for:
DIAGONAL METAL STUD
DIAGONAL METAL STUD BRACING TO BRACING TO STRUCTURE
STRUCTURE ABOVE, AS REQ'D. ABOVE AS REQUIRED FASTEN
FASTEN AT 48" O.C. (TYPICAL) AT 48" O.C. (TYPICAL) A B C
NOTE: HEIGHT OF EXISTING
CEILING HORIZONTAL BUMP-OUT
REFER TO REFLECTED CEILING PLAN CEILING CONSTRUCTION MUST BE FIELD DETAIL
FOR CEILING HEIGHTS & TYPE. REFER REFLECTED CEILING PLAN
FOR CEILING HEIGHTS
VERIFIED TO DETERMINE HEIGHT
OF NEW GYP. BRD.. A 5

4000 Luxottica Place Mason, Ohio 45040


6"

6"
SCALE: N.T.S.

A Subsidiary of the Luxottica Group


CONSISTENT HEIGHT IS REQUIRED
THROUGHOUT TENANT SPACE.
REFERENCE PLAN AND INTERIOR
ED
ELEVATIONS F.R.T. BLOCKING 5A 5B
3 5/8" x 20 GA. METAL STUDS AT METAL STUDS AT 16" O.C. w/ AS REQUIRED A400 A400
16" O.C. w/ 5/8" TYPE "X" GYP. 5/8" TYPE "X" GYP. BD. 9'-6" A.F.F. (SEE NOTE ABOVE) 16 GA. TRACK (TOP AND
BD. BOTH SIDES EXTEND GYP. BD. EXTEND GYP. TBD. TO 6" BOTTOM)
TO 6" ABOVE FINISHED CEILING ABOVE FINISHED CEILING
US

HEIGHT HEIGHT
ICC - ESR-3064 SALES AREA FIXTURE
WHERE OCCURS. SEE PLAN. "LOW"
NOTE: WALLS SHALL BE PLUMB 16 GA. TRACK
PROVIDE BLOCKING FOR
TO WITHIN 1/4" TOP & DISPLAY FIXTURE AS #12 TEK SCREWS
BOTTOM AT MILLWORK REQUIRED NOTE: 5C AT EA. STUD
NOTE: WALLS SHALL BE PLUMB LOCATIONS EXISTING WITHIN (1) DAY OF A400 (2) 3 58" X 18 GA.
T

TO WITHIN 1/4" TOP & BOTTOM CONSTRUCTION


AT MILLWORK LOCATIONS POSSESSION OF BEARING STUDS.
TENANT SPACE G.C. TO TYPICAL WHERE
O

"HIGH"
VERIFY BEARING STUD SHOWN. BRACE TOP
2 1/2" X 20 GA. METAL STUDS AT TO STRUCTURE ABOVE BOX BEAM - SEE PLAN AND
16" O.C. w/ 5/8" TYPE "X" GYP.
CAN BE INSTALLED THIS
SECTIONS FOR SIZES
LOCATION AS SHOWN
N

BD. AS SHOWN (2) 8" X 16 GA. STEEL


JOISTS. SEE ADJ. JAMB ASSEMBLY (SEE PLAN
DETAIL
DETAIL FOR # OF STUDS SIZE
NOTE: WALLS SHALL BE PLUMB AND STRUCTURAL
TO WITHIN 1/4" TOP & BOTTOM (2) 8" X 18 GA. STEEL #12 TEK SCREWS STUD ORIENTATION)
AT MILLWORK LOCATIONS JOISTS. SEE ADJ. AT EA. STUD
DETAIL
16 GA. TRACK NOTE: Revisions:
BASE PER ROOM FINISH SCHEDULE. BASE PER ROOM FINISH SCHEDULE. BASE PER ROOM FINISH 5B FASTEN BUILT-UP MEMBERS
SCHEDULE. REFER TO Mark Date By
REFER TO SHEET A103 REFER TO SHEET A103 1/2" DIA. EXPANSION BOLTS X 2 TOGETHER AT 12" O.C. MAX.
SHEET A103 A400 3/8" EMBEDMENT. (MIN. 2 PER WITH #12 TEK SCREWS 1 11-28-18
BEARING STUD LOCATION, LANDLORD COMMENTS / PERMIT SET
TYP.)
FRAMING PLAN BUILT UP BOX BEAM
REVISION #1

WALL SECTION WALL SECTION WALL SECTION FRAMING PLAN AND DETAILS
1 SCALE: 3/4"=1'-0" TYPICAL INTERIOR WALL
2 SCALE: 3/4"=1'-0" ONE-SIDE GYP. BD.
3 SCALE: 3/4"=1'-0"
4 SCALE: N.T.S.

(2) 1/2" x 4 7/8" PLY.


DOUBLE STUD @ DOOR BLOCKING. TYP.
JAMBS (TYP.) OPPOSITE SIDE
METAL STUD SIZE SCHEDULE
EZY JAMB
ISD IN-SWING SIZE DESIGNATION @ 16" O.C. @ 24" O.C. INTERIOR, NON-LOAD BEARING, AND FURRING STUDS Architect / Engineer of Record
DOOR FRAME
(888) 399-5262 SEE NOTES 1 5/8" 162S125-18 9'-6" 8'-3"

EXTERIOR AND LOAD BEARING STUDS 2 1/2" 250S162-18 12'-6" 10'-9"

+1 3/8" FOR R.O.


1 34"

DOOR WIDTH
IN-SWING DOOR
2 1/2" 250S162-33 12'-6" 10'-9" 250S162-27 13'-0" 11'-6"

DOOR 250S162-33 13'-0" 11'-6" 3 5/8" 362S162-18 16'-0" 13'-6"


(SEE DOOR SCHEDULE)

SALES SIDE
250S162-33 13'-10" 12'-0" 362S162-27 17'-3" 15'-0"
(4) ROCYORK CONCEALED 3 5/8" 362S162-33 16'-0" 13'-6" 4" 400S162-18 17'-3" 14'-3"
HINGES RY-80
(888) 399-5262 362S162-33 17'-3" 15'-0" 400S162-27 18'-6" 16'-3"

NOTE: 362S162-33 17'-11" 15'-7" 6" 600S162-18 20'-0" 15'-0"


TAPERED MUD GC TO OBTAIN JAMB, HINGES, 362S162-33 18'-6" 16'-9" 600S162-27 25'-3" 22'-0"
(TYP.) AND CLOSER FROM EZY JAMB Seal
CEILING
REFER REFLECTED CEILING PLAN FOR PROPER FIT & 362S162-43 19'-3" - MILLS / GAUGE CONVERSION
METAL FRAMING (TYP) ALIGNMENT.
FOR CEILING HEIGHTS 362S162-54 20'-0" - Mills Gauge
-SEE PLAN

SEE PLAN 362S162-68 22'-0" - 18 25


EXISTING DEMISING WALL
6" 600S162-33 20'-0" 15'-0" 27 22

DOOR HEAD / JAMB DETAIL 600S162-33 25'-3" 22'-0" 33 20

FAUX BRICK WALL OVER EXISTING


DEMISING WALL
EXISTING DEMISING WALL.
G.C. TO PREPARE WALL FOR
8 SCALE: 3"=1'-0"
600S162-33

600S162-33
26'-1"

26'-8"
22'-10"

23'-8"
43

54
18

16
QUALITY FINISH ON TENANT SIDE.
REPAIR OR REPLACE GYP. AS NOTES: 600S162-43 28'-0" - 68 14 Architect / Engineer Job No.:
REQUIRED. 1. BLOCKING FOR UPPER WALL HUNG CABINETS (UP TO 2 SHELVES) BASE CABINETS, FULL HEIGHT
MAINTAIN EXISTING FIRE RATING, CABINETS, HANDRAILS, GUARDRAILS, GRAB BARS, WALL HUNG EQUIP., ETC. MAX. WEIGHT 250 600S162-54 30'-0" - 030
INCLUDING DUCT WORK, LBS./FT. FOR SUPPORT OF ITEMS 60 LBS. AND LESS, SEE
NOTE: WALLS SHALL BE PLUMB 2. SEE TYPICAL WALL FRAMING FOR GAUGE OF STUDS, VERIFY LENGTH, HEIGHT, LOCATION OF 600S162-68 32'-0" - Nextore Store Design Revision No.:
CAULKING, ETC.
TO WITHIN 1/4" TOP & BOTTOM BLOCKING PLATE AND NUMBER.
AT MILLWORK LOCATIONS
NOTE: WALLS SHALL BE PLUMB
TO WITHIN 1/4" TOP & BOTTOM
3. USE #12 SELF TAPPING SHEET METAL SCREWS WHEN ATTACHING ITEMS TO BLOCKING PLATE.
4. WALL STUD FLANGES ARE CONTINUOUS AT BACKING STUD OR PLATE PLATE.
1. HEIGHTS LISTED ARE MAXIMUM UNBRACED HEIGHT. CONFIRM STUD SIZES, LOADS, AND SPANS WITH STUD MANUFACTURER.
2. EXTERIOR AND LOAD BEARING STUDS SHALL BE STRUCTURAL STUDS ONLY. DES REV 02
TENANT ADJACENT SPACE AT MILLWORK LOCATIONS DOUBLE STUD @ SIDES 3. "EQUIVALENT" STUDS MAY BE SUBSTITUTED FOR INTERIOR AND NON-LOAD BEARING STUDS.
Nextore project
OF OPENINGS 4. RUNNER/TRACK GAUGES TO MATCH STUD GAUGE.
YP Number 77889
.T
" O.C 5. WALLS OVER 12'-0" HIGH TO BE LATERALLY BRACED @ 8'-0" VERTICAL WITH 1 1/2", 16 GA. COLD-ROLLED CHANNELS CLIP ANCHORED TO METAL STUDS.
16 Brand Design Type:
NOTE: INSTALL
IN-WALL BLOCKING AT
SGH 4.1 - TIER B GOLD
LOCATIONS REQUIRED
BY FIXTURE VENDOR ISSUED FOR:
X Construction
LANDLORD NOTES:
NOTCH AT VERTICAL NOTHING SHALL BE ATTACHED TO SUSPENDED FROM, OR
STUDS, TYP. PENETRATED THROUGH THE FLOOR OR ROOF DECK ABOVE.
TENANT IS REQUIRED TO FRAME, BRACE, AND/OR SUSPEND AS
Title
BASE PER ROOM FINISH SCHEDULE. MTL STUDS TYP. REQUIRED TO/FROM THE TOP CHORD OF JOISTS OR STRUCTURAL
REFER TO SHEET A103
BASE PER ROOM FINISH SCHEDULE.
REFER TO SHEET A103
STEEL WHICH EXIST ABOVE TENANT'S SPACE. SECTIONS
6" X 18 GA BACKING ANY WALL FRAMED TO STRUCTURAL FRAMING WILL NEED TO USE
STUD ATTACHED TO DEFLECTION TRACK. TYP. &
STUDS W/ (3) #12-14
F.H.S.D.S. DETAILS
NOTE: AT WALL MOUNT SALES MIRROR LOCATIONS PROVIDE F.R.T. Date Sheet
WOOD BLOCKING IN METAL BLOCKING AS SHOWN 11-28-18
Drawn By
WALL SECTION WALL SECTION IN-WALL BLOCKING DETAIL A400
6 SCALE: 3/4"=1'-0" INTERIOR WALL
7 SCALE: 3/4"=1'-0" EXISTING DEMISING WALL
9 SCALE: N.T.S.
Checked By
STAFF

STAFF
ALL DECORATIVE METAL AND METAL TUBE TO
DESIGN & CONSTRUCTION
BE POWDER COAT FINISHED MF-40. (SEE FINISH MANAGEMENT:
1'-11 58"
LOCATE LIGHT & TRACK PER SCHEDULE ON SHEET A103)
CEILING PLAN. 2" MINIMUM WHEN
PROVIDED NEAR DECORATIVE

D
8"
METAL CEILING TRIM.
2" W P-41 C.L. OF POST

ED
E
THESE DIMENSIONS
MIN. MUST BE VERIFIED
FROM GYP. BD. HWB-40 a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000
WITH NEXTORE (HOLD) a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484
18GA 4" W METAL BACKING BY GC.
PFT-40

S
SEE SHEET A101 FOR C.L. CONST. MGR.
LOCATION END OF RAYBAN W BWP-41 TRANSITION STRIP (TS-41) PER

3"
4
PARTITION BUILD-OUT
PLANS AND SCHEDULES INSTALL

US U
BEYOND
7"
1'-08 91
8"
CARPET ON SUBFLOOR TO
.063 ALUM. CLAD PAINTED MF-41
WALL BASE DETAIL \ SALES FIELD VERIFY EXISTING ALIGN CARPET PILE HEIGHT WITH
4

2"
OVER ADHESIVE OVER MTL. TUBE
ALIGN FRONT OF BACK OF PLATFORM SCALE: 3"=1'-0" CONDITIONS TO DETERMINE ADJACENT FINISHED TILE
(BY STOREFRONT VENDOR)
FLOORING

T
PLATFORM WITH ALUM. DIAMOND PLATE MP-40 FROM GRP. BD. TRANSITION / TRIM REQUIRED
END OF BUILD-OUT OVER 1/2" F.R.T. PLY. OVER
2" 2 1/2" 20 GA. MTL STUD
AT THRESHOLD
PORC. TILE ON THIN SET MORTAR BED
(HOLD)
T
Construction for:

O SE D
O
2 1/2" 20 GA. MTL. STUD

8"
31
U
FRAMING @ 16" O.C.

N
(OPEN REAR - POST SIDE)

T
LAY DOWN CARPET PER PLANS
W P-40 AND SCHEDULES

NO
N

VB-40

4"
VFT-40 FEATHER AS REQUIRED TO ALIGN
CONTINUOUS CONTINUOUS B HWB-40
SALE AREA SALE AREA LINE OF CONCRETE SLAB
1)

4000 Luxottica Place Mason, Ohio 45040


PORCELAIN TILE PORCELAIN TILE 10
EA

A Subsidiary of the Luxottica Group


(PFT-40) (PFT-40) W P-41
S (SE
A RIE
HV
DETAIL DETAIL DETAIL 9"
NG
T
WALL BASE DETAIL \ STOCK FLOOR TRANSITION DETAIL
1 SCALE: 3"=1'-0"
2 SCALE: 3"=1'-0"
3 SCALE: 1/2"=1'-0"
LE 5 SCALE: 3"=1'-0"
5A SCALE: 6"=1'-0"
1-SGH4.0-A401-REV02 2-SGH4.0-A401-REV03 3-SGH4.0-A401-REV03 TS-41 CARPET TO PORCELAIN

HANG-UPS UNLIMITED HANG-UPS UNLIMITED


310-453-3806 310-453-3806
CEILING TOGGLE EYE TE-10 TOGGLE EYE TE-10 NOTE:
INSTALL ABOVE CEILING
PROVIDED AND INSTALLED PROVIDED AND INSTALLED ALL SIGNAGE SHALL CONFORM WITH ADA
BLOCKING AS REQUIRED
BY GC. (TYP. OF 4) BY GC. (TYP. OF 4) ACCESSIBILITY GUIDELINES, INCLUDING

ED
BUT NOT LIMITED TO PROPORTION,
G.C. TO VERIFY THICKNESS OF EXISTING COLOR CONTRAST AND RELIEF AND
TILE IN NON-SALES AREA AS REQUIRED SEE ATTACHMENT GRADE 2 BRAILLE REQUIREMENTS.
FOR FLOOR TRANSITION
DETAIL ABOVE

EXIST. WAYFARER ATTACHMENT POINT.


GC TO ALIGN CEILING TOGGLE EYE W/
8" MIN.
US
DOOR LEAF DOOR FRAME 1/8" FERRULE AND STOP SET BY GC
(TYP.)
LEVER HANDLE
TRANSITION POINT

1/16" WIRE ROPE BY GC

TENANT TILE
RESTROOM

TRANSITION ON THIN SET EXIST. WAYFARER 3"


TRANSITION STRIP ATTACHMENT POINT

T
(TS-42)
STRIP (TS-40): MORTAR BED

60"
RESTROOM
SALES AREA TILE
1"
2
TENANT TILE
(NON-SALES AREA) ON
THIN SET MORTAR BED
NEW / EX. V.C.T.
FLOORING
O HANGING WAYFARER
GLASSES BRAILLE SIGN PER 2010
ADA REQ'TS
Revisions:
Mark Date By
N
NOTE: 16'-7" CEILING HEIGHT.
UNISEX RESTROOM SIGNAGE 1 11-28-18
VENDOR TO PROVIDE ADDITIONAL SUSPENSION WIRES ATTACHMENT DETAIL LANDLORD COMMENTS / PERMIT SET
AS REQUIRED TO PROVIDE STABLE INSTALL OF PROP

7'-7" MIN.
A.F.F.

FLOOR TRANSITION DETAIL FLOOR TRANSITION DETAIL WAYFARER GLASSES INSTALL DETAIL DISABLED ACCESS SIGNAGE
6 SCALE: 6"=1'-0"
7 SCALE: 6"=1'-0"
9 SCALE: N.T.S.
10 SCALE: N.T.S.
TS-42 HARD TILE TO HARD TILE TS-40 HARD TILE TO V.C.T.

Architect / Engineer of Record


W P-41 ANCHOR PLATES ARE 12 GAUGE STEEL AND 6" WIDE. (LENGTH VARIES).
FURNISHED WITH STAINLESS STEEL MACHINE SCREWS TO ACCOMMODATE WALL
FINISHES TO 1 1/2" THICK. ANCHOR PLATES SECURED TO STUDS BY WELDING,
WIRING OR SELF THREADING SCREWS.
RAY BAN SIGN. SEE GRAB BARS
SHOP DRAWINGS LOCATE GRAB BARS AS NOTED IN RESTROOM ELEVATIONS ON A3.0.

THE DIAMETER OR WIDTH OF THE GRIPPING SURFACE IS REQUIRED TO BE 30 MM -


45MM, OR THE SHAPE IS TO PROVIDE AN EQUIVALENT GRIPPING SURFACE. IF
"HIGH" BOX BEAM. GRAB BARS ARE MOUNTED ADJACENT TO A WALL, THE SPACE BETWEEN THE
SEE
SEE FRAMING PLAN. WALL AND THE GRAB BARS IS TO BE 35MM - 45MM.
2/A401
G.C. TO REVIEW CENTERLINE OF 20
SIGN INSTALL GRAB BARS SHALL NOT ROTATE WITHIN THEIR FITTINGS.
GA. 6" BACKING
DRAWINGS PRIOR PLATE. ABOVE GYP.
TO INSTALLING GRAB BARS AND ANY SURFACE ADJACENT TO THEM CAN NOT HAVE ANY SHARP
CONTINUOUS
FRAMING THIS 7'-10 1/2" OR ABRASIVE ELEMENTS. EDGES ARE TO HAVE A MINIMUM RADIUS OF 1/8 INCH.
@ SOFFIT Seal
AREA A.F.F. BENDING STRESS IN A GRAB BAR OR SEAT INDUCED BY THE MAX. BENDING
MOMENT FROM THE APPLICATION OF A 250 LB. POINT LOAD SHALL BE LESS THAN
THE ALLOWABLE STRESS FOR THE MATERIAL OF THE GRAB BAR OR SEAT.
C C-41
SHEAR STRESS INDUCED IN A GRAB BAR BY THE APPLICATION OF 250 LBF POINT
9'-0" IN-WALL 1/2" x 8" F.R.T. BLOCKING BY GC

D
LOAD SHALL BE LESS THAN THE ALLOWABLE SHEAR STRESS FOR THE MOUNTING
BRACKET OR OTHER SUPPORT IS CONSIDERED TO BE FULLY RESTRAINED, THEN
DIRECT AND TORSIONAL SHEAR STRESSES SHALL NOT EXCEED THE ALLOWABLE

E
W BWP-41
SEAR STRESS.

S
SHEAR FORCE INDUCED IN FASTENER OR MOUNTING DEVICES FROM THE
APPLICATION OF A 250 LB. POINT LOAD SHALL BE LESS THAN THE ALLOWABLE

6'-8" (VERIFY WITH FIXTURE SHOP DRAWINGS)


LATERAL LOAD OF EITHER FASTENER OR MOUNTING DEVICE OR THE SUPPORTING

IN-WALL 1/2" x 8" F.R.T. BLOCKING BY GC


STRUCTURE, WHICHEVER HAS THE SMALLER ALLOWABLE LOAD.

U TENSILE FORCE INDUCED IN A FASTENER BY A DIRECT TENSION FORCE OF A 250


LB. POINT LOAD, PLUS THE MAX. MOMENT FROM THE APPLICATION OF A 250 LB.
POINT LOAD, SHALL BE LESS THAN THE ALLOWABLE WITHDRAWAL LOAD
Architect / Engineer Job No.:
030

T
BETWEEN THE FASTENER AND SUPPORTING STRUCTURE. Nextore Store Design Revision No.:
1'-8" TO C.L. OF IN-WALL

F.R.T. BLOCKING BY GC

GRAB BAR AND ANY WALL OR OTHER SURFACE ADJACENT TO IT SHALL BE FREE
OF ANY SHARP OR ABRASIVE ELEMENTS. EDGES SHALL HAVE A MINIMUM RADIUS DES REV 02
O
OF 1/8".
1/2" x 16"

Nextore project
77889

N
Number

Brand Design Type:

SGH 4.1 - TIER B GOLD


FRENCH CLEAT
BY MILLWORKER ISSUED FOR:
(TYP.) X Construction

F PFT-40 Title

SECTIONS
&
2
A401 DETAILS
Date Sheet
11-28-18
Drawn By

11
DETAIL
12
DETAIL
13
DETAIL
14
DETAIL
15
GRAB BAR DETAIL Checked By
STAFF A401
SCALE: 3/4"=1'-0" TIER A (PLATINUM) SCALE: 3/4"=1'-0" TIER A (PLATINUM) REV01 SCALE: 3/4"=1'-0" TIER B (GOLD) SCALE: 3/4"=1'-0" SCALE: N.T.S.
RAY-BAN PERIMETER WALL FIXTURE TYPICAL SECTION / DETAIL PERIMETER WALL FIXTURE TYPICAL SECTION / DETAIL FOR BLOCKING PERIMETER WALL FIXTURE TYPICAL SECTION / DETAIL FOR BLOCKING BACKWRAP WALL FIXTURE TYPICAL SECTION / DETAIL FOR BLOCKING STAFF
13-SGH41-A401-REV01
DESIGN & CONSTRUCTION
DESCRIPTION: 1.0 REFERENCE DOCUMENTS: 3.0 INSTALLATION: 4.0 ALTERNATE CEILING FRAMING MANAGEMENT:
THE CEILING CONSISTS OF HANGER WIRES ATTACHED TO THE STRUCTURE ABOVE, MAIN RUNNERS 1.1 ASTM STANDARDS 3.1 WIRE HANGERS SHALL BE ATTACHED TO, OR PRE-INSTALLED IN STRUCTURE CAPABLE OF SUPPORTING THE CEILING FOR LIMITED CEILING WIDTHS, ALTERNATE FRAMING CONSISTING OF FURRING CHANNEL OR METAL JOIST SECTIONS MAY BE
ATTACHED TO THE HANGERS, AND CROSS FURRING ATTACHED TO THE MAIN RUNNERS. WEIGHT, PLUS SAFETY MARGIN, WITHOUT DEFLECTION. THE HANGER ATTACHMENT SHALL DEVELOP FULL INSTALLED AS A SIMPLE SPAN BETWEEN RUNNERS ATTACHED TO OPPOSITE WALLS. THIS SYSTEM MAY BE USED ON
APPROPRIATE GYPSUM OR CEMENT BOARD PANELS ARE SCREW ATTACHED TO RECEIVE FINAL 1.1.1 ASTM C-754 INSTALLATION OF STEEL FRAMING TO RECEIVE SCREW ATTACHED GYPSUM PANELS HANGER STRENGTH. HANGERS SHALL BE STRAIGHT AND WITHIN A RATION OF 1;6 OF PLUMB. AVOID HANGER CEILING THAT DO NOT REQUIRE PENETRATIONS LARGE ENOUGH TO INTERRUPT THE FRAMING, AND DO NOT CARRY
DECORATION SUCH AS DRYWALL TREATMENT, VENEER PLASTER, ACOUSTICAL TILES, ACRYLIC PLASTER 1.1.2 ASTM C-840 APPLICATION AND FINISHING OF GYPSUM BOARD (SEC.15) SPLICES. HANGER WIRES SHALL NOT CONTACT MECHANICAL OR ELECTRICAL ITEMS ABOVE THE CEILING. HEAVY FIXTURE LOADS.
SYSTEM, AND CERAMIC TILE. 1.1.3 ASTM C-841 INSTALLATION OF INTERIOR LATHING AND FURRING (SECS. 7.2 & 7.4) HANGER WIRES SHALL BE INSTALLED AT 4' OC, AND SHALL BE LOCATED WITHIN 6" OF THE ENDS OF MAIN
1.1.4 ASTM C-844 APPLICATION OF GYPSUM BASE TO RECEIVE GYPSUM VENEER PLASTER (SEC.15) RUNNERS. 4.1 MATERIAL: a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000
a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484

1.2 RELATED STANDARDS: 3.2 MAIN RUNNERS SHALL BE SPACED AT 4' OC. MAIN RUNNERS SHALL BE LOCATED WITHIN 6" OF PARALLEL WALLS. 4.1.1 RUNNERS: SHALL BE THE SAME SIZE AND GAUGE AS FRAMING MEMBERS. ANGEL RUNNER MAY BE USED TO
ATTACH HANGER WIRES TOT HE MAIN RUNNERS WITH A SADDLE TIE THAT PREVENTS SETTLING, UPLIFT, OR SUPPORT HAT CHANNEL FRAMING.
1.2.1 GA 216 APPLICATION AND FINISHING OF GYPSUM BOARD (SEC.12) TWISTING OF THE MAIN RUNNERS. SPLICE FURRING WITH A NESTED 12" LAP AND A DOUBLE WRAP WIRE TIE AT 4.1.2 FRAMING: THE FOLLOWING TABLE LISTS THE MAXIMUM SINGLE SPAN FOR FRAMING MEMBERS INSTALLED AT 16"
1.2.2 GA 600 FIRE-RESISTANCE DESIGN MANUAL EACH END. MAIN RUNNERS SHALL BE INSTALLED TO WITHIN +/- 1/8" OF A FLAT PLANE. OR 24" OC TO RECEIVE SINGLE LAYER CEILING PANELS.
1.2.3 GWB-1 NORTHWEST WALL & CEILING BUREAU GUIDE SPECIFICATION FOR GYPSUM WALLBOARD.
1.2.4 VP-1 NORTHWEST WALL & CEILING BUREAU GUIDE SPECIFICATION FOR VENEER PLASTER SYSTEMS. 3.3. CROSS FURRING SHALL BE SADDLE TIED TO MAIN RUNNERS WITH #16 GAUGE WIRE OR TWO STRANDS OF #18 GAUGE MEMBERS MAX. SINGLE SPAN
1.2.5 ICBO EVALUATION REPORT ER-4071 WIRE OR APPROVED CLIPS. SPLICE FURRING WITH AN 8" NESTED LAP SCREWED OR WIRE TIED AT EACH END. 7/8" X 25 GA HAT CHANNEL 4'-0"
1.2.6 MANUFACTURERS SPECIFICATIONS FOR THE APPLICATION OF CEMENT BOARD TO CEILINGS. THE REQUIRED FURRING SPACING IS 24" OC FOR 5/8" THICK GYPSUM PANELS AND 16" OC FOR 1/2" THICK 1-5/8" X 25 GA C SECTION 5'-0"
GYPSUM PANELS. FOR OTHER COMBINATIONS AND THICKNESS OF GYPSUM PANELS OR FOR CEMENT BOARD 2-1/2" X 25 GA C SECTION 6'-0"
APPLICATIONS, SEE THE APPROPRIATE RELATED REFERENCE STANDARD OR MANUFACTURES SPECIFICATIONS. 3-1/2" X 25 GA C SECTION 8'-0"
2.0 MATERIALS:
3.4 WHEN THE STRUCTURE FROM WHICH THE CEILING IS SUSPENDED IS CAPABLE OF MOVEMENT INDEPENDENT OF THE Construction for:
2.1 HANGER WIRE FOR CEILINGS WEIGHING 4 LBS PSF OR LESS SHALL BE #12 GA DIAMETER GALVANIZED, SOFT ANNEALED STRUCTURE SUPPORTING ABUTTING WALL AND PARTITIONS, THE CEILING FRAMING SHALL NOT BE ATTACHED 4.2 INSTALLATION:
STEEL WIRE. TO OR IN CONTACT WITH THE WALLS. INSTALL GYPSUM OR CEMENT PANELS TO THE CEILING WITH LONG
DIMENSIONS PERPENDICULAR TO FURRING MEMBERS. PANEL ENDS SHALL OCCUR OVER FURRING MEMBERS 4.2.1 ATTACH RUNNERS TO WALLS WITH 2 FASTENERS AT EACH WALL STUD
2.2 HANGER WIRE FOR CEILINGS WEIGHING UP TO 10 LBS SHALL BE #9 GA GALVANIZED, SOFT ANNEALED STEEL WIRE. UNLESS DICTATED BY OTHERWISE BY FIRE OR SOUND RATED SYSTEMS.
4.2.2 CUT FRAMING MEMBERS TO WITHIN 1/4" OF CEILING WIDTH
2.3 MAIN RUNNERS (CARRIERS) SHALL BE 1-1/2 X 16 GAUGE COLD ROLLED CHANNELS WEIGHING 475 LBS. PER THOUSAND 3.5 ACCESSORIES: ACCESSORIES APPROPRIATE TO THE CEILING TYPE SHALL BE SUED, AND BE INSTALLED ACCORDING TO
LINEAL FEET. GALVANIZED OR CORROSION INHIBITING COATING FOR EXTERIOR OR HUMID CONDITIONS. THE RELATED REFERENCE STANDARD. 4.2.3. ATTACH FRAMING TO RUNNERS WITH SCREWS AT BOTH TOP AND BOTTOM FLANGES
COMMON USES:
2.4 FURRING SHALL BE 7/8" X 25 GAUGE HAT SHAPED SECTIONS. GALVANIZED OR CORROSION INHIBITING COATING FOR 3.6 GENERAL INFORMATION: LARGE SUSPENDED CEILINGS, MORE THAN 50 LINEAL FT. IN ONE DIMENSION OR MORE THAN
SUSPENDED GYPSUM BOARD OR CEMENT BOARD CEILINGS ARE PRIMARILY USED TO PROVIDE FLAT EXTERIOR OR HUMID CONDITIONS. 25OO SF, SHOULD NOT CONTACT ABUTTING WALLS OR COLUMNS. CONTROL JOINTS SHOULD BE USED TO 5.0 FINISHING
PLANE CEILINGS IN MOST TYPES OF BUILDINGS. THESE MAY BE DESIGNED TO PROVIDE FIRE

4000 Luxottica Place Mason, Ohio 45040


MAINTAIN PANEL DIMENSIONS OF 50 LF. OR LESS, AND TO DIVIDE CEILING AREAS INTO MAXIMUMS OF 2500 SF.

A Subsidiary of the Luxottica Group


PROTECTION, CONCEALMENT, AND ACOUSTICAL TREATMENT. 2.5 TIE WIRE SHALL BE 16 GAUGE AND/OR 18 GAUGE GALVANIZED, SOFT ANNEALED STEEL WIRE. FRAMING SHOULD BE BROKEN OR SPLICED AT CONTROL JOINTS. FLEXIBLE SEALANT OR FOAM TAPE MAY BE 5.1 APPLICATION OF PANELS AND FINISHING SHALL BE IN ACCORDANCE WITH THE APPROPRIATE RELATED SPECIFICATION.
INSTALLED BETWEEN THE CASING BEAD AND THE ABUTTING SURFACES. ADDITIONAL CARRIERS AND FURRING
LIMITATIONS: CHANNELS AND HANGER WIRES SHALL BE INSTALLED TO FRAME AROUND CEILING PENETRATIONS, SUCH AS
LIGHT FIXTURES, ACCESS PANELS AND DUCT WORK. FOR CEILING WEIGHING MORE THAN 7LB. PER SF, USE 20
CARE MUST BE TAKEN IN CHOOSING THE CEILING SURFACE FOR AREAS EXPOSED TO HIGH HUMIDITY. GA FURRING AT REDUCED SPACING.
IT IS DIFFICULT TO ADAPT THIS FRAMING SYSTEM TO CURVED, BARREL VAULT, OR DOME TYPE
CEILINGS. LIMITED ACCESS CAN BE PROVIDED WITH THE INSTALLATION OF ACCESS PANELS. THE
LEVELS OF ABUSE AND PENETRATION RESISTANCE IS NOT THAT OF A SUSPENDED METAL LATH AND TYPICAL HANGER
PLASTER CEILING. SPACING 4'-0" O.C. 1-1/2" CHANNEL 4'-0"
MAX. O.C. MAX.

ADVANTAGES:

PROVIDES FLAT, MONOLITHIC CEILING SURFACES AT THE LEAST COST. CAN BE ADAPTED TO SEVERAL
GYPSUM ASSOCIATION AND U.L. FIRE RATED FLOOR/CEILING ASSEMBLIES. ACOUSTICAL TILE AND
ACOUSTICAL PLASTER PROVIDE GOOD SOUND ABSORPTION.
1/2" or 5/8"
GYPSUM BASE OR
GYPSUM PANELS
VERSATILITY: REGULAR OR
FOIL-BACK MAX.
THESE CEILINGS ARE BEST INSTALLED IN FLAT PLANES. HOWEVER, INSTALLING FACETED CEILINGS OF SPACING 16" OR
VARIOUS SHAPES AND AT ANY ANGLE, ALLOWS NUMEROUS DESIGN OPTIONS. THE USE OF CEMENT 24"O.C.
BOARD PANELS ALLOWS THE USE OF THIS SYSTEM IN HIGH HUMIDITY AREAS. A VARIETY OF TEXTURES
METAL FURRING
ARE AVAILABLE. CHANNEL CLIP

MAX SPACING 24"


STRUCTURAL DESIGN: O.C.

1. HANGERS: SIZES BASED ON STATIC LOADS DEVELOPED BY STANDARD MAXIMUM CEILING


SUSPENDED GYPSUM BOARD CEILING
1
SPACING AND LIMITED TO A SAFETY FACTOR OF 6.5, BUT NO LESS THAN 12 GAUGE WIRE. CEILING
WEIGHT DETERMINES THE SIZE AND SPACING OF HANGER WIRE.
NO SCALE
2. RUNNERS AND CROSS FURRING: DEFLECTION IS LIMITED TO I/360 OF THE SHORTEST SPAN UNDER
THE CEILING LOAD.
Revisions:
Mark Date By

1 11-28-18
LATERAL FORCE BRACING (FIGURES 2 AND 3) (FIGURES 5a AND 5b)
FIGURE 2 LANDLORD COMMENTS / PERMIT SET
LATERAL FORCE BRACING CEILINGS CONSTRUCTED OF LATH AND PLASTER OR GYPSUM BOARD, SCREW OR NAIL HANGER AND PERIMETER WIRES MUST BE PLUMB WITHIN 1 IN 6 UNLESS (FIGURE PLUMB 1/6
ATTACHED TO SUSPENDED MEMBERS THAT SUPPORT A CEILING ON ONE LEVEL 5a) COUNTER SLOPING WIRES ARE PROVIDED (FIGURE 5b). SOURCE: ASTM C 636
EXTENDING FROM WALL TO WALL SHALL BE EXEMPT FROM THE LATERAL FORCE BRACING SECTION 2.1.4
REQUIREMENTS. SOURCE: CISCA ZONES 3-4
HANGER WIRES SHALL BE 12 GAGE AND SPACED 4 FEET ON CENTER OR 10 GAGE MAXIMUM
LATERAL FORCE BRACING IS THE USE OF VERTICAL STRUTS (COMPRESSION POSTS) AND SPACED 5 FEET ON CENTER. SOURCE: ASTM C 636 8"
SPLAY WIRES (SEE FIGURE 2). FOR CEILING WITHOUT RIGID BRACING, SPRINKLER HEAD PENETRATIONS SHALL HAVE A 2
INCH OVERSIZE RING, SLEEVE OR ADAPTER THROUGH THE CEILING TILE TO ALLOW FREE
ANY CONNECTION DEVICE AT THE SUPPORTING CONSTRUCTION SHALL BE CAPABLE
MOVEMENT OF AT LEAST 1 INCH IN ALL HORIZONTAL DIRECTIONS. FLEXIBLE HEAD
FOR CEILING AREAS EXCEEDING 1,000 SQUARE FEET, HORIZONTAL RESTRAINT OF THE OF CARRYING NOT LESS THAN 100 POUNDS. SOURCE: CISCA ZONES 3-4
CEILING TO THE STRUCTURAL SYSTEM (LATERAL FORCE BRACING) SHALL BE PROVIDED. DESIGN THAT CAN ACCOMMODATE 1 INCH FREE MOVEMENT SHALL BE PERMITTED AS AN
SOURCE: ASCE 7-05 SECTION 13.5.6.2.2 c POWDER DRIVEN SHOT-IN-ANCHORS ARE AN APPROVED METHOD OF ATTACHMENT ALTERNATE. SOURCE: ASCE 7-05 13.5.6.2.2 e
FOR HANGER WIRES. SOURCE: STATE OF OREGON, BUILDING CODES DIVISION
LATERAL FORCE BRACING SHALL BE 12 FEET ON CENTER (MAXIMUM) AND BEGIN NO
12 GAGE SPLAYED GLOSSARY FOR THIS DOCUMENT (REGIONAL TERMINOLOGY MAY VARY)
FARTHER THAN 6 FEET FROM WALLS. SOURCE: CISCA SEISMIC ZONES 3-4 TERMINAL ENDS OF EACH MAIN BEAM AND CROSS TEE MUST BE SUPPORTED FIGURE 5a
BRACE WIRES WITHIN 8 INCHES OF EACH WALL WITH A PERIMETER WIRE (SEE FIGURE 4 & 5b).
SEISMIC SPLAY WIRES ARE TO BE FOUR 12 GAGE WIRES ATTACHED TO THE MAIN BEAM. SOURCE: CISCA ZONES 3-4
3" (76mm) CROSS TEES LATERAL FORCE BRACING PERIMETER WIRES
FROM THE PLANE OF THE CEILING. SOURCE: CISCA SEISMIC ZONES 3-4 WIRES SHALL NOT ATTACH TO OR BEND AROUND INTERFERING MATERIAL OR THE CROSS MEMBER THAT THE BRACING METHOD USED HANGER WIRES PLACED
EQUIPMENT. A TRAPEZE OR EQUIVALENT DEVICE SHALL BE USED WHERE INTERLOCK WITH THE MAIN TO PREVENT CEILING UPLIFT WITHIN EIGHT INCHES OF THE
BEAMS, ALSO KNOWN AS OR RESTRICT LATERAL SURROUNDING WALLS.
SEISMIC SPLAY WIRES SHALL BE ATTACHED TO THE GRID AND TO THE STRUCTURE IN SUCH OBSTRUCTIONS PRECLUDE DIRECT SUSPENSION. TRAPEZE SUSPENSIONS SHALL CROSS RUNNERS OR CROSS MOVEMENT DURING A
CROSS TEE MAIN BEAM
A MANNER THAT THEY CAN SUPPORT A DESIGN LOAD OF NOT LESS THAN 200 POUNDS BE A MINIMUM OF BACK-TO-BACK 1-1/4" COLD-ROLLED CHANNELS FOR SPANS T-BARS. SEISMIC EVENT. LATERAL PLENUM Architect / Engineer of Record
OR THE ACTUAL DESIGN LOAD, WITH A SAFETY FACTOR OF 2, WHICHEVER IS GREATER EXCEEDING 48 INCHES. SOURCE: CISCA ZONES 3-4 FORCE BRACING CONSISTS OF THE SPACE ABOVE A
DIFFUSER VERTICAL STRUTS AND SPLAY SUSPENDED CEILING.
(FIGURE 6b). SOURCE: CISCA ZONES 3-4 A CIRCULAR OR WIRES.
ANGLE
ANGLE RECTANGULAR METAL GRILL SLACK WIRE
"POWDER DRIVEN SHOT-IN-ANCHORS" WHEN USED FOR SEISMIC APPLICATION AS PART USED FOR THE PASSAGE OF MAIN BEAM A 12 GAGE WIRE THAT IS NOT
AIR FROM A DUCTED SYSTEM. THE PRIMARY SUSPENSION TIGHT OR TAUT.
FIGURE 3 OF THE PRESCRIPTIVE PATH IN SEISMIC DESIGN CATEGORIES D, E AND F SHALL HAVE AN LIGHT FIXTURES WEIGHING LESS THAN 10 POUNDS SHALL HAVE ONE 12 GAGE MEMBER SUPPORTED BY
THIS DOCUMENT PROVIDES THE IBC-REFERENCED STANDARDS FOR THE MAXIMUM RECOMMENDED LENGTHS FOR ICC-ES APPROVAL FOR SEISMIC APPLICATIONS AND SHALL REQUIRE "SPECIAL INSPECTION" HANG WIRE CONNECTED FROM THE FIXTURE TO THE STRUCTURE ABOVE. THIS ESSENTIAL SERVICE BUILDINGS HANGER WIRES, ALSO KNOWN SPREADER OR SPACER BAR
INSTALLATION OF SUSPENSION SYSTEMS FOR ACOUSTICAL LAY-IN VERTICAL STRUTS IRRESPECTIVE OF THE TYPE OF OCCUPANCY CATEGORY THE STRUCTURE IS IN. ANCHORS WIRE MAY BE SLACK. SOURCE: CISCA SEISMIC ZONES 3-4 ANY BUILDINGS DESIGNED TO AS THE MAIN RUNNER, A BAR WITH NOTCHES TO
FOR KICKER WIRES (SPLAYED WIRES INSTALLED FOR PURPOSES OTHER THAN SEISMIC BE USED BY PUBLIC AGENCIES CARRYING TEE, CARRYING PREVENT THE SUSPENSION
CEILINGS. INCORPORATION OF THIS DOCUMENT WILL PROVIDE A MORE FIGURE 5b COUNTER SLOPING AS A FIRE STATION, POLICE RUNNER OR MAINS. SYSTEM FROM SEPARATING,
UNIFORM STANDARD FOR INSTALLATION AND INSPECTION. THIS RESTRAINT) ARE EXEMPT FROM REQUIREMENT. SOURCE: STATE OF OREGON, BUILDING LIGHT FIXTURES WEIGHING MORE THAN 10 POUNDS AND LESS THAN 56 LBS. STATION, EMERGENCY ALSO CALLED A STABILIZER
DOCUMENT IS DESIGNED TO ACCOMPLISH THE INTENT OF THE CODES DIVISION. SHALL HAVE TWO 12 GAGE WIRES ATTACHED AT OPPOSING CORNERS OF THE OPERATIONS CENTER, STATE MOLDING/CLOSURE ANGLE BAR.
1/2" EMT conduit up to 5'-10" LIGHT FIXTURE TO THE STRUCTURE ABOVE. THESE WIRES MAY BE SLACK. PATROL OFFICE, SHERIFF'S A LIGHT GAUGE METAL ANGLE
INTERNATIONAL BUILDING CODE (IBC) WITH REGARD TO THE SPLAY WIRES ARE TO BE WITHIN 2 INCHES OF THE CONNECTION OF THE VERTICAL STRUT SOURCE: CISCA SEISMIC ZONES 3-4 OFFICE, OR EMERGENCY OR CHANNEL FASTENED TO SPLAY WIRES
REQUIREMENTS FOR SEISMIC DESIGN CATEGORY D, E, AND F FOR 3/4" EMT conduit up to 7'-8" VERTICAL HANGER WIRE ATTACHMENT COMMUNICATION DISPATCH THE PERIMETER WALL OR WIRES INSTALLED AT AN
TO SUSPENDED CEILING. SOURCE: CISCA SEISMIC ZONES 3-4 CENTER. PARTITION TO SUPPORT THE ANGLE RATHER THAN
SUSPENDED CEILINGS AND RELATED ITEMS. UNLESS SUPPORTED BY 1" EMT conduit up to 9'-9" LIGHT FIXTURES WEIGHING MORE THAN 56 LBS. SHALL BE SUPPORTED BY PERIMETER ENDS OF AN PERPENDICULAR TO THE GRID.
ENGINEERING, THE SUSPENSION SYSTEM SHALL BE INSTALLED PER THE RIDGED BRACING MAY BE USED IN LIEU OF SPLAY WIRES. SOURCE: ASCE SECTION 13.5.6.2.2 DIRECTLY FROM THE STRUCTURE ABOVE. THESE WIRES MUST BE TAUT. SOURCE: GRID ACOUSTICAL CEILING GRID
THE MAIN BEAMS AND CROSS VERTICAL STRUTS
REQUIREMENTS FOR SEISMIC DESIGN CATEGORY (SDC) D, E AND F PER c CISCA SEISMIC ZONES 3-4 SHOT-IN-ANCHOR 3/4"
TEES OF THE SUSPENSION PERIMETER CLIPS THE RIGID VERTICAL MEMBER
Single 1-5/8" metal stud (20 gauge) up to 12'-0"
THE IBC. MANUFACTURERS' RECOMMENDATIONS SHOULD BE SYSTEM. PROPRIETARY ANGLE BRACKET USED IN LATERAL FORCE
FOLLOWED. Back-to-back 1-5/8" metal stud up to 15'-0" CEILINGS WITH PLENUMS LESS THAN 12 INCHES TO STRUCTURE ARE NOT REQUIRED TO PENDANT MOUNTED FIXTURES SHALL BE DIRECTLY SUPPORTED FROM THE STRUCTURAL CONCRETE 5/8" ATTACHED DIRECTLY TOT EH BRACING OF THE SUSPENSION Seal
(20 gauge) HAVE LATERAL FORCE BRACING. SOURCE: PORTLAND BUILDING DEPARTMENT STRUCTURE ABOVE USING A 9 GAGE WIRE OR AN APPROVED ALTERNATE SUPPORT HANGER WIRE WALL MOLDING/CLOSURE SYSTEM. ALSO KNOWN AS A
MAX 10 OR 12 GAGE SOFT ANGLE WHICH ALLOWS FOR COMPRESSION POSTS,
Single 2-1/2" metal stud (20 gauge) up to 13'-6" WITHOUT USING THE CEILING SUSPENSION SYSTEM FOR DIRECT SUPPORT. CEILING CLIP ANNEALED WIRE USED AS 3/4" MOVEMENT IN THE SEISMIC PODS, SEISMIC
VERTICAL STRUTS MUST BE POSITIVELY ATTACHED TO THE SUSPENSION SYSTEMS AND THE SOURCE: CISCA SEISMIC ZONES 3-4 PRIMARY SUPPORT FOR THE EVENT OF SEISMIC ACTIVITY STRUTS. COMMON
GENERAL RECOMMENDATIONS Back-to-back 2-1/2" metal stud up to 15'-0" STRUCTURE ABOVE. SOURCE: CISCA 3-4 3 TURNS GRID SYSTEM. ALSO CALLED AND INTERLOCKS PROPERLY MATERIALS ARE ELECTRICAL
REFERENCED SOURCES PER HIERARCHY: 2009 IBC (INTERNATIONAL BUILDING CODE), (25 gauge) TANDEM FIXTURES MAY UTILIZE COMMON WIRES. VERTICAL HANGER WIRE SUSPENSION WIRES. WITH ENDS OF GRID SYSTEM. CONDUIT (EMT), METAL
STUDS OR PROPRIETARY
AMERICAN SOCIETY OF TESTING MATERIALS (ASTM C 635, ASTM C 636, ASTM E 580/ASTM E 580M), THE VERTICAL STRUT MAY BE EMT CONDUIT, METAL STUDS OR A PROPRIETARY PRODUCTS.
SOURCE: PORTLAND BUILDING DEPARTMENT COMPRESSION POST (SEE FIGURE 3) FIGURE 6a
AMERICAN SOCIETY OF CIVIL ENGINEERS (ASCE7-05) AND CEILINGS AND INTERIOR SYSTEMS
CONSTRUCTION ASSOCIATION (CISCA). NOTE: PLENUM AREAS GREATER THAN 15'-0" WILL REQUIRE
ENGINEERING CALCULATIONS. CEILINGS WITH INTERSTITIAL SPACES LESS THAN 12 INCHES TO FRAMING ARE NOT TERMINALS OR SERVICES WEIGHING 20 LBS. BUT NOT MORE THAN 56 LBS. MUST
REQUIRED TO HAVE LATERAL FORCE BRACING HAVE TWO 12 GAGE WIRES CONNECTING THEM TO THE CEILING SYSTEM HANGERS
PARTITIONS THAT ARE TIED TO THE CEILING AND ALL PARTITIONS GREATER THAN 6 FEET IN HEIGHT
OR THE STRUCTURE ABOVE. THESE WIRES MAY BE SLACK. SOURCE: CISCA SPLAYED SEISMIC BRACING WIRE ATTACHMENT
SHALL BE LATERALLY BRACED TO THE STRUCTURE. BRACING SHALL BE INDEPENDENT OF THE CEILING SEISMIC ZONES 3-4
SPLAY BRACING SYSTEM. SOURCE: ASCE 7-05 SECTION 13.5.8.1
(FIGURES 4a AND 4b) TERMINALS OR SERVICES WEIGHING MORE THAN 56 LBS. MUST BE DRILL-IN EXPANSION
FOR FURTHER INFORMATION ON BRACING OF NON-LOAD BEARING PARTITIONS REFER TO NWCB INDEPENDENTLY SUPPORTED DIRECTLY FROM THE STRUCTURE ABOVE. THESE ANCHOR CEILINGS WITHOUT SEISMIC BRACING: WHERE EXISTING CEILINGS ARE WITHOUT
FIGURE 4a SEISMIC BRACING, THE CEILING SYSTEM SHALL BE BROUGHT INTO SUBSTANTIAL Architect / Engineer Job No.:
TECHNICAL DOCUMENT #200-501 WALL MOLDINGS (PERIMETER CLOSURE ANGLES) ARE REQUIRED TO HAVE A WIRES MUST BE TAUT. SOURCE; CISCA SEISMIC ZONES 3-4
ATTACHED WALL MOLDING REQUIREMENTS COMPLIANCE WITH CURRENT CODE REQUIREMENTS WHEN 50% OR MORE OF THE 030
HORIZONTAL FLANGE 2 INCHES WIDE. ONE END OF THE CEILING GRID SHALL BE STRUCTURAL CONCRETE CEILING TILE IS ALTERED, REPAIRED OR REPLACED AS PART OF A GENERAL SPACE
ALL MAIN BEAMS ARE TO BE HEAVY DUTY (HD). SOURCE ASCE 7-05 SECTION 13.5.6.2.2 a ATTACHED TO THE WALL MOLDING, THE OTHER END SHALL HAVE A 3/4 INCH (FIGURE 7) STEEL STRAP 1" WIDE x 2" ALTERATION, OR IF ALL OF THE CEILING SYSTEM IS REMOVED. Nextore Store Design Revision No.:
CLEARANCE FROM THE WALL AND FREE TO SLIDE. SOURCE: ASCE 7-05 SECTION
LONG x 12 GAGE MINIMUM
ALL CROSS TEES SHALL BE CAPABLE OF CARRYING THE DESIGN LOAD WITHOUT EXCEEDING maximum 8" (202 mm) 13.5.6.2.2 b FOR CEILING AREAS EXCEEDING 2,500 SQUARE FEET, A SEISMIC SEPARATION
3 TURNS -SUBSTANTIAL COMPLIANCE MEANS INSTALLATION OF THE FOLLOWING
DEFLECTION EQUAL TO 1/360 OF ITS SPAN. SOURCE CISCA ZONES 3-4
WALL WHERE SUBSTANTIATING DOCUMENTATION HAS BEEN PROVIDED TO THE LOCAL
JURISDICTION, PERIMETER CLIPS MAY BE SUED TO SATISFY THE REQUIREMENTS
JOINT OR FULL HEIGHT WALL PARTITION THAT BREAKS THE CEILING SHALL BE
PROVIDED UNLESS ANALYSES ARE PERFORMED OF THE CEILINGS BRACING
SYSTEM, CLOSURE ANGLES AND PENETRATIONS TO PROVIDE SUFFICIENT
SPLAYED SEISMIC BRACING WIRE ITEMS WHERE REQUIRED IN NEW CONSTRUCTION:
-LATERAL FORCE BRACING (SPLAYED WIRES)
-COMPRESSION STRUTS
DES REV 02
FOR THE 2-INCH CLOSURE ANGLE. SOURCE: STATE OF OREGON, BUILDING FIGURE 6b
CLEARANCE. SOURCE: ASCE 7-05 SECTION 13.5.6.2.2 d -SLACK WIRES ON ALL LIGHT FIXTURES AND AIR TERMINALS
CODES DIVISION Nextore project
THESE RECOMMENDATIONS ARE INTENDED FOR SUSPENDED THE LAYOUT AND LOCATION OF THE SEISMIC SEPARATION JOINT SHALL BE PER THE -THIS REQUIREMENT DOES NOT TRIGGER THE NEED FOR:
Number 77889
THE GRID SHALL BE ATTACHED AT TWO ADJACENT WALLS (POP RIVETS OR DESIGNER OF RECORD AND NOTED ON THE PLANS. IF A SEISMIC SEPARATION
CEILINGS INCLUDING GRID, PANEL OR TILE, LIGHT FIXTURES AND APPROVED METHOD). SOFFITS EXTENDING TO A POINT AT LEAST LEVEL WITH THE -2 INCH CLOSURE ANGLE AS SPECIFIED IN SECTION II Brand Design Type:
JOINT IS REQUIRED BY THE DESIGNER, THE DESIGNER MAY USE THE GENERIC JOINT -SEISMIC SEPARATION JOINTS
AIR TERMINALS WEIGHING NO MORE THAN 4LBS PER SQUARE BOTTOM PLANE OF THE GRID AND INDEPENDENTLY SUPPORTED AND LATERALLY DETAILED IN THIS DOCUMENT OR A PROPRIETARY JOINT. THE AMOUNT OF FREE
minimum -1 INCH MOVEMENT IN ALL DIRECTIONS AROUND SPRINKLER PENDANTS SGH 4.1 - TIER B GOLD
FOOT. SOURCE ASCE 7-05 SECTION 13.5.6.1 BRACED TO THE STRUCTURE ABOVE ARE DEEMED TO BE EQUIVALENT TO WALLS. MOVEMENT (GAP DESIGN) SHALL BE A MINIMUM OF 3/4 INCH. SOURCE: STATE
2" (50 mm)
SOURCE: STATE OF OREGON, BUILDING CODES DIVISION OF OREGON, BUILDING CODES DIVISION. -THESE UPGRADES ARE NOT REQUIRED WHEN:
ALL WIRE TIES ARE TO BE THREE TIGHT TURNS AROUND ITSELF -REMOVING PORTIONS OF TILES OR PANELS AND/OR GRID TO ALTER ISSUED FOR:
maximum 3" WITHIN THREE INCHES. TWELVE GAGE HANGER WIRE SPACED 4 (FIGURE 4b) IN LIEU OF SEISMIC SEPARATION JOINTS, THE CEILING MAY BE DIVIDED INTO X Construction
(76 mm) DUCTWORK, SPRINKLER PIPE, ETC.
FOOT ON CENTER (FIGURE 1). SOURCE ASTM C 636 ITEM 2.3.4 FIGURE 4b AREAS LESS THAN 2500 SQUARE FEET BY THE USE OF PARTITIONS OR SOFFITS
-PORTIONS OF A CEILING ARE REMOVED ONLY TO FACILITATE THE
SPREADER (SPACER) BARS SHALL BE USED TO PREVENT THE ENDS OF THE MAIN AS FOLLOWS: PARTITIONS SHALL EXTEND A MINIMUM OF 6 INCHES ABOVE THE
UNATTACHED WALL MOLDING REQUIREMENTS INSTALLATION OF SPRINKLER PIPING
BEAMS AND CROSS TEES AT PERIMETER WALLS FROM SPREADING OPEN DURING A LEVEL OF THE PLANE OF THE GRID AND SHALL BE INDEPENDENTLY BRACED TO THE
CHANGES IN CEILING PLANES WILL REQUIRE POSITIVE BRACING. SEISMIC EVENT. PERIMETER WIRES SHALL NOT BE IN LIEU OF SPREADER BARS. STRUCTURE ABOVE. SOFFITS SHALL EXTEND TO A POINT AT LEAST LEVEL WITH THE
SOURCE: ASCE 7-05 13.5.6.2.2 f SOURCE: CISCA SEISMIC ZONES 3-4 BOTTOM PLANE OF THE GRID AND SHALL BE INDEPENDENTLY SUPPORTED AND Title
maximum 8" (202 mm) LATERALLY BRACED TO THE STRUCTURE ABOVE. SOURCE: STATE OF OREGON

WALL
SPREADER BARS ARE NOT REQUIRED AT PERIMETERS WHERE RUNNERS ARE
ATTACHED DIRECTLY TO CLOSURE ANGLES.
BUILDING CODES DIVISION
CEILING
CEILINGS WITHOUT COMPRESSION STRUTS: WHERE EXISTING CEILINGS HAVE SEISMIC
OTHER THAN PARTITIONS AND SOFFITS, SEISMIC JOINTS MAY NOT BE USED AS
WIRE TYING IS AN ACCEPTABLE ALTERNATIVE TO SPREADER BARS. PART OF A FIRE RATED CEILING ASSEMBLY UNLESS SUBSTANTIATING 3/4" POP
FLANGE BRACING BUT DO NOT HAVE COMPRESSION STRUTS AT THE CENTER OF THE
SPLAYED WIRES, THE ADDITION OF COMPRESSION STRUTS WILL ONLY BE REQUIRED
DETAILS
Spreader bar or other suitable DOCUMENTATION IS PROVIDED. SOURCE: STATE OF OREGON BUILDING CODES FIGURE 7 MINIMUM RIVET
SPREADER BARS ARE NOT REQUIRED IF A 90 DEGREE INTERSECTING CROSS OR DIVISION. WHEN AND WHERE THE GRID IS REPLACED, ALTERED, RAISED OR LOWERED.
system required to keep perimeter MAIN IS WITHIN 8 INCHES OF THE PERIMETER WALL.
components from spreading apart
minimum 3/4" Date Sheet
minimum (19 mm) at
WHERE SUBSTANTIATING DOCUMENTATION HAS BEEN PROVIDED TO THE LOCAL
JURISDICTION, PERIMETER CLIPS MAY BE USED TO SATISFY THE REQUIREMENTS SUSPENSION SYSTEMS FOR ACOUSTICAL LAY-IN CEILINGS 11-28-18

2
Drawn By
2" (50 mm) unattached walls FOR SPREADER BARS. SOURCE: STATE OF OREGON, BUILDING CODES DIVISION
NO SCALE Checked By
STAFF A402
STAFF
DESIGN & CONSTRUCTION
MANAGEMENT:
GENERAL NOTES 1 ELECTRICAL SYMBOLS DIVISION 16000 - ELECTRICAL RECOGNIZED MANUFACTURE PROVIDED THESE
ITEMS MEET MINIMUM STANDARDS AS SET IN
1. BRANCH CIRCUIT LOAD CENTERS SHALL BE
DEAD FRONT TYPE, WITH MAIN LUGS OR MAIN
PART I - GENERAL THESE SPECIFICATIONS. OVERCURRENT DEVICE AS INDICATED, BRANCH
A. IT SHALL BE THE E.C.'S RESPONSIBILITY TO UNLOAD INVENTORY AND STORE LIGHTING (ALL SYMBOLS SHOWN ARE NOT NECESSARILY USED ON THE DRAWINGS) OVERCURRENT DEVICES AS NOTED AND AN
A. GENERAL CONDITIONS, CODES & STANDARDS
PACKAGE. THE E.C. SHALL ALSO SHIP ANY EXCESS MATERIALS BACK TO THE ELECTRICAL EQUIPMENT GROUND BAR, ALL IN A FLUSH
1. ALL WORK SHOWN ON THE ELECTRICAL D. CONSTRUCTION COORDINATION
PACKAGE DISTRIBUTOR. HOMERUN TO PANEL AND CIRCUIT INDICATED MOUNTED SHEET STEEL ENCLOSURE. MINIMUM
DOCUMENTS IS TO BE PROVIDED AND INSTALLED
XX-## SHORT CIRCUIT CAPACITY SHALL BE 10,000 AMPS
BY THE ELECTRICAL CONTRACTOR, UNLESS NOTED a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000
B. EXIT LIGHTS AT THE STOREFRONT SHALL BE CEILING MOUNTED AND CENTERED OVER 1. DURING BIDDING YOU VISITED THE SITE. WORK SYMMETRICAL FOR 120/208V, AND 14,000 AMPS
OTHERWISE. a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484
OPENINGS. EXIT/EMERGENCY LIGHTS AT DOOR TO NON-SALES AREAS SHALL BE CEILING CIRCUIT WITH THE GENERAL CONTRACTOR TO SYMMETRICAL FOR 277/480V APPLICATION UNLESS
PANEL 2. ALL WORK TO MEET APPLICABLE CODES AS NOTED OTHERWISE. LOAD CENTERS MUST BE
MOUNTED AND CENTERED ABOVE DOOR. IF PLAN LOCATIONS ARE NOT ACCEPTABLE, COORDINATE ANY CONFLICTS WITH EXISTING
LOCALLY ENFORCED. NO WORK ON THE SELECTED TO FIT IN A STANDARD STUD WALL.
CONDITIONS. THIS WORK SHALL BE PROVIDED AT
IMMEDIATELY CONTACT NEXTORE PROJECT MANAGER FOR DIRECTION. INFLOOR/UNDERFLOOR CONDUIT/WIRE DRAWINGS IS TO BE INSTALLED WHERE IT
CONFLICTS WITH LOCAL CODE ENFORCEMENT.
NO ADDITIONAL COST TO THE TENANT. 2. LOAD CENTERS SHALL BE AS MANUFACTURED
STORE #1843
C. WHERE DRYWALL CEILINGS ARE USED IN THE SALES AREA, E.C. SHALL ARRANGE CIRCUITS TO
AVOID THE USE OF JUNCTION BOXES IN INACCESSIBLE LOCATIONS. THE USE OF JUNCTION
J JUNCTION BOX COORDINATE WITH THE LOCAL INSPECTOR PRIOR 2. GENERAL CONTRACTOR SHALL LOCATE,
IDENTIFY AND PROTECT ANY EXISTING SERVICES
BY SQUARE D, GENERAL ELECTRIC, ITE/SIEMENS
AND WESTINGHOUSE/CUTLER HAMMER.
CHARLESTON CHURCH STREET
BOXES ABOVE DRYWALL CEILINGS SHALL BE LIMITED TO LOCATIONS NEAR ACCESS FRAMES DUPLEX RECEPTACLE - 125 VOLT, 2 POLE, 3 WIRE, GROUNDING
TO INSTALLATION.
3. ELECTRICAL CONTRACTOR SHALL PAY FOR WHICH ARE REQUIRED TO BE MAINTAINED C. FIXTURES AND LAMPS
73 S. MARKET STREET
USED FOR DIFFUSERS AND RETURN AIR GRILLES OR ACCESS PANELS AS LOCATED ON PLANS.
IF PLAN LOCATION IS NOT ACCEPTABLE, IMMEDIATELY CONTACT NEXTORE PROJECT MANAGER
TYPE, 20 AMPERE, MOUNTED AT 18" AFF UNLESS OTHERWISE
NOTED:
AND OBTAIN ALL NECESSARY LICENSES, PERMITS
AND INSPECTIONS REQUIRED TO PROCEED WITH
OPERATIONAL AND SHALL EXERCISE EXTRA
CAUTION IN THE PERFORMANCE OF ALL WORK TO 1. ALL FIXTURES AND LAMPS ARE FURNISHED BY CHARLESTON , SC 29401
AVOID DISTURBING SUCH FACILITIES. ALL COSTS TENANT, INSTALLED BY ELECTRICAL CONTRACTOR..
FOR DIRECTION. "2" INDICATES CIRCUIT NUMBER THE WORK. THIS SHALL INCLUDE ALL REQUIRED
"E" EXISTING TO REMAIN COORDINATION WITH THE LOCAL UTILITY FOR REPAIR OF DAMAGES TO SUCH SERVICES
D. E.C. SHALL RELAMP ALL FIXTURES PRIOR TO STORE OPENING BUT NOT DURING HEAVY "WP" INDICATES WEATHERPROOF COVER COMPANIES AND THEIR ASSOCIATED FEES OR SHALL BE PAID BY THE GENERAL CONTRACTOR D. FIRE ALARM SYSTEM Construction for:
"D" DEDICATED CIRCUIT COSTS. CAUSING THE DAMAGE.
CONSTRUCTION PERIOD. 1. ALL WORK RELATED TO THE FIRE ALARM
"GFI" INDICATES GROUND FAULT CIRCUIT INTERRUPTER TYPE 4. THE ELECTRICAL CONTRACTOR SHALL PROVIDE SYSTEM IS BY THE ELECTRICAL CONTRACTOR.
E. LIGHTING CIRCUITS UP TO 100'-0" IN LENGTH SHALL UTILIZE #12 CONDUCTORS MINIMUM. "R" INDICATES RECESSED ALL LABOR, MATERIAL, EQUIPMENT AND TOOLS PART 2 - PRODUCTS OWNER'S REPRESENTATIVE WILL PROVIDE
LIGHTING CIRCUITS FROM 101'-0" TO 150'-0" IN LENGTH SHALL UTILIZE #10 CONDUCTORS NECESSARY TO COMPLETE THE ELECTRICAL WORK A. WIRING DEVICES SPECIFICS ON THE SYSTEM.
MINIMUM. LIGHTING CIRCUITS FROM 151'-0" TO 250'-0" IN LENGTH SHALL UTILIZE #8 DOUBLE DUPLEX RECEPTACLE - 125 VOLT, 2 POLE, 3 WIRE, AS SHOWN ON THE DRAWINGS OR SPECIFIED
GROUNDING TYPE, 20 AMPERE, MOUNTED AT 18" AFF UNLESS 1. DUPLEX RECEPTACLES SHALL BE GROUNDING
CONDUCTORS MINIMUM. LIGHTING CIRCUITS ABOVE 251'-0" IN LENGTH SHALL UTILIZE #6 HEREIN. PART 3 - EXECUTION
OTHERWISE NOTED. TYPE, NEMA 5-20R, RATED FOR 20 AMPS, 125
CONDUCTORS MINIMUM. 5. TEMPORARY ELECTRICAL SERVICE, LIGHTING, AND VOLTS, WITH PROVISIONS FOR BACK AND SIDE A. GENERAL MISCELLANEOUS
RELATED WIRING SHALL BE PROVIDED TO OSHA WIRING.
F. E.C.'S BID SHALL INCLUDE THE INSTALLATION OF ALL LUMINAIRES AND ASSOCIATED LAMPS DUPLEX RECEPTACLE - 125 VOLT, 2 POLE, 3 WIRE, 20 AMPERE REQUIREMENTS FOR THE USE OF ALL TRADES 1. ALL CONDUIT RUN IN FINISHED AREAS SHALL
FURNISHED BY NEXTORE. E.C. IS RESPONSIBLE TO ENSURE THE ADJUST ABILITY OF ALL MOUNTED IN FLOOR BOX. 1.1. SPECIFICATION GRADE DUPLEX RECEPTACLE BE CONCEALED. 2.

4000 Luxottica Place Mason, Ohio 45040


DURING CONSTRUCTION.
SHALL BE HUBBELL #5362 SERIES OR APPROVED

A Subsidiary of the Luxottica Group


DIRECTIONAL FIXTURES AFTER INSTALLATION AND SHALL AIM THE FIXTURES PER DIRECTION "CLG" INDICATES MOUNTED IN CEILING 2. PROVIDE TYPEWRITTEN DIRECTORY CARDS
EQUAL, HEAVY DUTY, WHITE.
FROM G.C. LIGHT FIXTURE SPECIFICATIONS MAY VARY, IF THIS IS THE CASE, CONTRACTOR COMBINATION DUPLEX RECEPTACLE AND VOICE/DATA OUTLET WITH BRANCH CIRCUIT IDENTIFICATION FOR
B. SCOPE OF WORK 1.3. GROUND FAULT CIRCUIT INTERRUPTER (GFI) BRANCH CIRCUIT PANELBOARDS. PANELBOARDS,
SHALL CALL THE LIGHTING DISTRIBUTOR FOR EXACT SPECIFICATION OF LIGHTING FIXTURES. IF MOUNTED IN FLOOR BOX.
DUPLEX RECEPTACLES SHALL BE PROVIDED FEEDER DEVICES, DISTRIBUTION EQUIPMENT AND
THE CEILING SYSTEMS ARE FIRE RATED, E.C. SHALL CLOSELY COORDINATE FIXTURE
DOUBLE DUPLEX RECEPTACLE - 125 VOLT, 2 POLE, 3 WIRE, 20 1. ONLY MAJOR EQUIPMENT IS SHOWN ON THE WHERE INDICATED. STARTERS SHALL BE FIELD MARKED TO WARN
REQUIREMENTS WITH NEXTORE.
AMPERE MOUNTED IN FLOOR BOX. DRAWINGS. THE ELECTRICAL CONTRACTOR SHALL 2. SWITCHES SHALL BE TOGGLE OPERATED, QUIET QUALIFIED PERSONS OF POTENTIAL ELECTRIC ARC
G. E.C. SHALL MAKE ALL FINAL CONNECTIONS AS REQUIRED FOR A FULLY COMPLETE AND BID AND CONSTRUCT A COMPLETE AND TYPE, RATED FOR 20 AMPS, 120/277 VOLTS, WITH FLASH HAZARDS IN ACCORDANCE WITH NEC
OPERABLE SYSTEM. COMMUNICATIONS FLOOR BOX OPERATIONAL SYSTEM. MISCELLANEOUS PROVISIONS FOR BACK AND SIDE WIRING. THREE 110.16.
EQUIPMENT REQUIRED TO COMPLETE THE WORK IS WAY AND FOUR WAY SWITCHES SHALL BE 3. INSTALL HANDLE GUARDS ON ALL BREAKERS
H. E.C. SHALL VERIFY THE VOLTAGE AND COMPATIBILITY OF ALL EQUIPMENT, FIXTURES AND S SWITCH - SINGLE POLE TOGGLE TYPE - 120/277 VOLT, 1-HP IN THE ELECTRICAL CONTRACTOR'S SCOPE - PROVIDED WHERE INDICATED. FOR NIGHT LIGHTING, EMERGENCY AND SIMILAR
MILLWORK PRIOR TO CONNECTION. RATED, 20 AMPERE, MOUNTED AT 48" AFF UNLESS OTHERWISE ASSUME NO WORK OR EQUIPMENT IS PROVIDED 2.1. SINGLE POLE SWITCHES SHALL BE LEVITON CIRCUITS.
NOTED: BY OTHERS UNLESS STATED AS SUCH. #1221 SERIES OR APPROVED EQUAL, SILENT 4. ALL FLUSH MOUNTED ;LOADCENTERS SHALL
I. ALL MOUNTING HEIGHTS FROM THE CENTERLINE OF THE BOX TO THE FINISHED FLOOR ARE AS ACTUATING, 20-AMP, 120/277V, WHITE.
"3" INDICATES THREE WAY SWITCH 2. DURING BIDDING: HAVE (3) 3/4" EMPTY CONDUITS INSTALLED TO
FOLLOWS, UNLESS NOTED OTHERWISE ON PLAN: SWITCHES-48", ABOVE ACCESSIBLE CEILING FOR FUTURE USE.
"4" INDICATES FOUR WAY SWITCH 2.1. VERIFY THE EXISTING CONDITIONS AND 2.2. THREE POLE SWITCHES SHALL BE LEVITON
ELECTRICAL/TELEPHONE/DATA OUTLETS-18", TOP OF PANELBOARDS-6'-6", TIMECLOCKS-5'-0". #1223 SERIES OR APPROVED EQUAL, SILENT
"C" INDICATES SWITCH MOUNTED 8" ABOVE COUNTER COMPENSATE FOR ANY VARIATIONS IN THE 5. THE FINAL LOCATIONS OF ALL EQUIPMENT,
FOR ALL LENS PROCESSING ROOM OUTLET MOUNTING HEIGHTS SEE EQUIPMENT WIRING SCOPE AS A RESULT. ACTUATING, 20-AMP, 120/277V, WHITE.
"OS" INDICATES OCCUPANCY SENSOR SWITCH OUTLETS, ETC. SHALL BE SUBJECT TO REASONABLE
SCHEDULE. "D" INDICATES 0-10V DIMMER SWITCH - WATTAGE AS INDICATED ON CHANGES IN LOCATION UP TO THE TIME OF
2.3. WHERE THERE IS A CONFLICT THAT CANNOT BE 3. DIMMERS SHALL BE LEVITON SLIDING DIMMER
PANEL SCHEDULE. EACH BRANCH CIRCUIT SHALL INCLUDE A RESOLVED BY THE GENERAL CONTRACTOR, SWITCH, OF A RATING, VOLTAGE AND WATTAGE ROUGHING-IN, AT NO ADDITIONAL COST TO THE
J. FLEXIBLE CONDUIT SHALL BE USED FOR ALL FINAL CONNECTIONS TO MILLWORK, INTERIOR
SEPARATE NEUTRAL CONDUCTOR ADVISE ENGINEER PROMPTLY FOR A RESOLUTION. SUITABLE FOR LOAD SERVED. COLORS OF DEVICES TENANT.
LIGHTING FIXTURES, AND EQUIPMENT. MAXIMUM LENGTH OF FLEXIBLE CONDUIT SHALL BE "M" INDICATES A MASTER SWITCH THAT OVERRIDES THE OTHER SWITCHES DO NOT PROVIDE WORK WHEN THERE IS AND COVERPLATES SHALL WHITE. B. GROUNDING
12'-0". CONNECTED TO IT. UNCERTAINTY ON WHAT WORK IS TO BE 4. COMBINATION WALL DIMMER/OCCUPANT 1. GROUNDING OF THE ELECTRICAL SYSTEM
K. IF INSTALLATION VARIES FROM THE CONTRACT DRAWINGS, THE GENERAL CONTRACTOR WILL "OSD" INDICATES 0-10V DIMMER SWITCH WITH INTEGRAL PIR OCCUPANCY PERFORMED. SENSOR SHALL BE LUTRON MAESTRO 0-10V SHALL BE BY MEANS OF AN INSULATED
SENSOR - WATTAGE AS INDICATED ON PANEL SCHEDULE. EACH BRANCH DIMMER WITH INTEGRAL PASSIVE INFRARED
BE RESPONSIBLE FOR OBTAINING "AS BUILT" DRAWINGS FROM THE SUBCONTRACTORS AND 3. AS PART OF THE BIDDING PROCESS, REPORT TO GROUNDING CONDUCTOR INSTALLED WITH ALL
CIRCUIT SHALL INCLUDE A SEPARATE NEUTRAL CONDUCTOR. 1 OR 3 OCCUPANT SENSING, AVAILABLE IN 1-WAY OR
SUBMITTING SAME TO NEXTORE PROJECT MANAGER. THE TENANT ANY ERRORS OR UNCLEAR FEEDERS AND BRANCH CIRCUIT CONDUCTORS IN
WAY AS INDICATED. 3-WAY CONFIGURATIONS. COLOR TO BE WHITE.
DIRECTIONS THAT YOU HAVE IDENTIFIED. ALL CONDUITS AND SUPPLEMENTAL AS REQUIRED
L. IT IS THE E.C.'S RESPONSIBILITY TO PROPERLY BALANCE ALL BRANCH CIRCUITS BETWEEN VERIFY LOAD SERVED IS COMPATIBLE PRIOR TO TO MEET CODE (SUCH AS ARTICLE 517).
OS CEILING MOUNTED OCCUPANT SENSOR ORDERING.
THE PHASES OF THE SYSTEM (WITH-IN 10%). C. DOCUMENTS C. TESTS
5. WIRING DEVICES SHALL BE SPECIFICATION
M. ALL WORK SHALL BE IN STRICT ACCORDANCE WITH NATIONAL ELECTRICAL CODE AND ALL AD
1. TEST FOR GROUNDS, SHORT CIRCUITS, AND
LIGHT FIXTURE: "AD" INDICATES FIXTURE TYPE "a" INDICATES GRADE.
LOCAL CODES AND ORDINANCES. PROPER FUNCTION OF ALL EQUIPMENT AFTER
a SWITCH CONTROL. REFER TO LUMINAIRE SCHEDULE FOR 1. SUBSTITUTIONS 6. COVERPLATES FOR POWER, DATA & INSTALLATION IS COMPLETE. FAULTS IN THE
DESCRIPTION. 1.1. THE MANUFACTURERS AND MODEL NUMBERS TELEPHONE SHALL BE LEVITON OR APPROVED INSTALLATION SHALL BE CORRECTED AT NO COST Revisions:
N. ALL OUTLETS IN THE LENS PROCESSING ROOM ARE TO BE LABELED WITH PANEL AND CIRCUIT
INDICATED IN THE CONTRACT DOCUMENTS ARE EQUAL, WHITE, PLASTIC. TO THE TENANT.
NUMBER. TL Mark Date By
TRACK AND TRACK MOUNTED LIGHT FIXTURE (DESIGNATIONS FOR THE PURPOSE OF DESCRIPTION AND TO 7. LIGHTING CONTRACTORS SHALL BE IN NEMA 1 D. DEMOLITION
O. THE E.C. SHALL VERIFY THE VOLTAGE AND COMPATIBILITY OF ALL EQUIPMENT, FIXTURES AND #T-S VARY - SEE PLANS) ESTABLISH A BASE LEVEL OF QUALITY. THE ENCLOSURE, NORMALLY OPEN ELECTRICALLY 1 11-28-18
GENERAL CONTRACTOR'S BID WILL 1. DEMOLITION OF EXISTING ELECTRICAL
MILLWORK PRIOR TO CONNECTION. HELD, 120V, COIL, 20A. REFER TO PLANS FOR
EQUIPMENT, IF APPLICABLE, SHALL BE PART OF THE
LANDLORD COMMENTS / PERMIT SET
RECESSED DOWNLIGHT. DESIGNATIONS VARY - SEE PLANS. CONTEMPLATE THE USE OF THE EQUIPMENT AND NUMBER OF POLES.
D MATERIALS EQUIVALENT TO THOSE INDICATED. ELECTRICAL WORK AS INDICATED ON THE
P. SEE DATA RISER ON THIS SHEET FOR ADDITIONAL INFORMATION. B. LIGHTING AND RECEPTACLE LOAD CENTERS
ILLUMINATED "EXIT" SIGN LIGHTING FIXTURE. CEILING MOUNTED DRAWINGS.
2. MISCELLANEOUS ITEMS NECESSARY TO (PANELS)
Q. PROVIDE POWER, TELEPHONE AND DATA CONDUIT WITHIN FLOOR, BETWEEN FIXTURE AND OR WALL MOUNTED. PROVIDE DIRECTIONAL ARROWS AS COMPLETE THE SYSTEMS CAN BE OF ANY
NEAREST WALL AS INDICATED ON PLANS. METHOD OF CORE DRILLING SHALL BE PER BUILDING INDICATED ON FLOOR PLANS.
REQUIREMENTS. ALL CORE DRILL REQUIREMENTS SHALL BE VERIFIED WITH LANDLORD.
CONTRACTOR SHALL SIZE CONDUIT PER NEC. PROVIDE FOR X-RAY OF FLOOR WHERE TC LIGHTING TIME CLOCK
REQUIRED BY THE LANDLORD.
DATA OUTLET: MOUNTED AT 18" AFF UNLESS OTHERWISE
NOTED. PROVIDE SINGLE GANG BOX WITH PLASTER RING AND
FIELD VERIFY ALL CONDITIONS
3/4" CONDUIT TO ABOVE THE ACCESSIBLE CEILING. "W"
INDICATES WALL MOUNTED AT 54" AFF, "C" INDICATES MOUNTED DESIGN DRAWINGS ARE SCHEMATIC. THE GENERAL CONTRACTOR SHALL VISIT THE SITE PRIOR TO
CODE NOTES 8" ABOVE COUNTER. CLG INDICATES CEILING MOUNTED. BIDDING OR AWARD OF CONTRACT TO INSPECT EXISTING FIELD CONDITIONS. THIS CONTRACT SHALL
INCLUDE ALL LABOR AND MATERIALS NECESSARY FOR FIELD MODIFICATIONS DUE TO EXISTING
FOLLOW APPLICABLE CODES AS A MINIMUM OF WORK. C IP CAMERA LOCATION. CONDITIONS.
WORK SHOWN ON THE DRAWINGS IS INTENTED TO
MEET OR EXCEED CODE AND SHALL NOT BE THE GENERAL CONTRACTOR SHALL CONTACT THE ARCHITECT, ENGINEER OR OWNER PRIOR TO BIDDING
INTERPRETED OTHERWISE. SWITCHED WIRING FOR INTERPRETATIONS AND CLARIFICATIONS OF THE DESIGN AND INCLUDE IN HIS BID ALL COSTS TO
MEET THE DESIGN INTENT. CLARIFICATIONS MADE BY THE ARCHITECT, ENGINEER OR OWNER AFTER
BRANCH CIRCUIT WIRING
MEANS OF EGRESS ILLUMINATION LEVEL SHALL NOT BE BIDDING WILL BE FINAL AND SHALL BE IMPLEMENTED AT GENERAL CONTRACTORS COST.
LESS THAN 1 FC AT THE WALKING SURFACE AND SHALL HOMERUN Architect / Engineer of Record
BE EQUIPPED WITH THE CODE MINIMUM BATTERY BACK BIDDING GENERAL CONTRACTORS SHALL HAVE A WORKING KNOWLEDGE OF LOCAL CODES AND
UP WHERE REQUIRED. MINIMUM SHALL BE 90 MINUTES
MOTOR ORDINANCES AND SHALL INCLUDE IN THEIR BIDS THE COSTS FOR ALL WORK INSTALLED IN STRICT
WHERE THE APPLICABLE CODES REQUIRE LESS THAN
90 MINUTES OF BACK UP. ACCORDANCE WITH GOVERNING CODES, THE PLANS AND SPECIFICATIONS NOT WITHSTANDING. THE
CONTRACTOR SHALL ALERT ARCHITECT, ENGINEER OR OWNER OF ANY APPARENT DISCREPANCIES
EXIT SIGNS SHALL BE ILLUMINATE AT ALL TIMES AND BETWEEN GOVERNING CODES AND DESIGN INTENT. Michael Romes, PE
EQUIPPED WITH THE CODE MINIMUM BATTERY BACK UP
WHERE REQUIRED. MINIMUM SHALL BE 90 MINUTES 2441 Crown Pointe Blvd
WHERE THE APPLICABLE CODES REQUIRE LESS THAN
90 MINUTES OF BACK UP.
Suamico, WI 54173
(920) 445-5007

Seal

11/28/18
Architect / Engineer Job No.:
030
Nextore Store Design Revision No.:

DES REV 02
Nextore project
Number 77889
Brand Design Type:

SGH 4.1 - TIER B GOLD

ISSUED FOR:
X Construction

Title

ELECTRICAL
SPECS AND
NOTES
Date Sheet
11-28-18
Drawn By

Checked By
STAFF E001
MPR
DESIGN & CONSTRUCTION
MANAGEMENT:
GENERAL DEMOLITION NOTES
1. IN EVERY INSTANCE OF DEMOLITION AND/OR REMODELING, THE E.C. SHALL FIGURE A COMPLETE JOB
AS NONE OTHER SHALL BE ACCEPTED.
a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000
2. THE DRAWINGS ARE TO BE USED ONLY AS A GUIDELINE FOR DEMOLITION. THE E.C. MUST VISIT THE a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484

SITE PRIOR TO BIDDING TO VERIFY ALL WORK REQUIRED FOR A COMPLETE JOB & INCLUDE THE COST
OF SUCH WORK IN HIS BID.
STORE #1843
3. THE E.C. SHALL MAINTAIN EXISTING SERVICES TO & IN THE EXISTING AREA AS REQUIRED.
CHARLESTON CHURCH STREET
4. IF NECESSARY, THE E.C. SHALL PROVIDE TEMPORARY SERVICES IN THE EXISTING AREAS. 73 S. MARKET STREET
5. THE E.C. SHALL DISCONNECT & REMOVE ELECTRIC SERVICE TO ALL MECHANICAL EQUIPMENT BEING CHARLESTON , SC 29401
REMOVED AS A RESULT OF THE REMODELING.

6. ELECTRICAL EQUIPMENT & DEVICES SHALL BE REMOVED COMPLETE INCLUDING CONDUIT & WIRE.
Construction for:

7. FLUSH MOUNTED WALL OUTLETS SHALL BE REMOVED AND THE WALL PATCHED AND FINISHED TO
INFORMATION IS BASED ON EXISTING MATCH THE ADJACENT WALL FINISHES.
DRAWINGS. VERIFY ALL WORK IN 8. ANY EXISTING CONDUIT, WIRING AND/OR ELECTRICAL & MECHANICAL DEVICES BEING DISTURBED BY
THE WORK SHALL BE REWORKED BY THIS CONTRACTOR AS REQUIRED TO RETURN TO ITS FORMER
FIELD.ADVISE NEXTORE PROJECT EXISTING OPERATING CONDITION.
MANAGER OF ANY DISCREPANCIES. 9. ANY CIRCUITS FEEDING THROUGH DEVICES OR EQUIPMENT BEING RELOCATED, REWORKED, OR

4000 Luxottica Place Mason, Ohio 45040


ABANDONED & SERVING OTHER ELECTRICAL DEVICES, AND/OR EQUIPMENT SHALL BE MAINTAINED

A Subsidiary of the Luxottica Group


BY PROVIDING J-BOXES OR OTHER ACCEPTABLE METHOD AS REQUIRED.

10. ALL WALLS, CEILINGS, FLOORS, ETC., BEING DISTURBED BY THE WORK SHALL BE RETURNED TO
1 XX KEY NOTES - ELECTRICAL DEMOLITION PLAN FINISHED CONDITIONS TO MATCH EXISTING BY THE E.C. & HE SHALL DO HIS OWN CUTTING &
PATCHING AS NECESSARY UNDER HIS CONTRACT.
1. RELAMP EXISTING STRIP FIXTURE WITH NEW LED LAMPS. LAMPS SUPPLIED BY NEXTORE, INSTALLED BY EC.
2. EXISTING FAN/LIGHT COMBO TO REMAIN. RECONNECT TO NEW PANEL A. SEE SHEET E202 FOR MORE 11. EXISTING MATERIALS SHALL BE TURNED OVER TO THE OWNER. IF NOT REQUIRED BY OWNER, THE E.C.
INFORMATION. SHALL REMOVE THESE MATERIALS FROM THE PREMISES.
3. EXISTING EXIT SIGN TO REMAIN.
4. EXISTING WATER HEATER POWER TO REMAIN. RECONNECT TO NEW PANEL A. SEE SHEET E202 FOR MORE 12. NO CONDUIT, BOXES, WIRING, OR CABLES SHALL BE INSTALLED WITHIN 1 1/2" OF THE LOWEST POINT
INFORMATION. OF THE UNDERSIDE OF THE ROOF DECKING, NOR SHALL THEY BE INSTALLED CONCEALED WITHIN
5. EXISTING RECEPTACLE TO REMAIN. METAL-CORRUGATED ROOF DECKING. THE E.C. SHALL BE RESPONSIBLE TO REPLACE AND/OR REWORK
6. RELAMP EXISTING EMERGENCY FIXTURE WITH NEW LED LAMPS. LAMPS SUPPLIED BY NEXTORE, INSTALLED EXISTING CONDUIT, BOXES, WIRING, AND CABLING THAT IS NOT IN COMPLIANCE WITH THIS
BY EC.
REQUIREMENT.
7. DISCONNECT AND REMOVE EXISTING DOWNLIGHT. SALVAGE EXISTING CIRCUIT FOR REUSE.
8. EXISTING SWITCHBANK TO REMAIN.
9. DISCONNECT AND REMOVE EXISTING EMERGENCY DOWNLIGHT. SALVAGE EXISTING CIRCUIT FOR REUSE. 13. ALL CONDUIT AND CABLING SHALL BE PROPERLY SUPPORTED AS REQUIRED BY THE NATIONAL
10. DISCONNECT POWER AND LOW VOLTAGE CABLING TO EXISTING CASHWRAP. SALVAGE CIRCUITS AND ELECTRICAL CODE. THE E.C. SHALL BE RESPONSIBLE TO REPLACE AND/OR REWORK EXISTING CONDUIT
CABLING FOR REUSE WITH NEW CASHWRAP. UTILIZE EXISTING CONDUIT RUNS TO MINIMIZE TRENCHING AND/OR CABLING THAT IS NOT IN COMPLIANCE WITH THIS REQUIREMENT.
NEEDED. COORDINATE WITH NEXTORE PROJECT MANAGER FOR CONDUIT AND BOX INSTALLATION
LOCATIONS. 14. E.C. SHALL FIELD VERIFY SLAB ON GRADE FLOOR CONSTRUCTION TYPE PRIOR TO CUTTING. UNDER
11. EXISTING TRAFFIC COUNTER TO REMAIN. NO CIRCUMSTANCES SHALL THE CONTRACTOR CUT A STRUCTURAL FLOOR SLAB THICKER THAN FOUR
12. RELAMP EXISTING LIGHTING IN THIS AREA WITH NEW LED LAMPS, UNLESS NOTED OTHERWISE. LAMPS
(4") INCHES WITHOUT PRIOR WRITTEN APPROVAL FROM ENGINEER OF RECORD. NOTIFY ENGINEER OF
SUPPLIED BY NEXTORE, INSTALLED BY EC. GC TO FIELD VERIFY AND PROVIDE INFO TO NEXTORE
PMROJECT MANAGER. RECORD OF ANY SLAB THICKNESS GREATER THAN FOUR (4") INCHES PRIOR TO PROCEEDING WITH
13. IF EXISTING RECEPTACLES OR J-BOXES, ON THIS WALL, ARE NOT POSITIONED CORRECTLY FOR THE NEW ANY SAW CUTTING.
CASEWORK LAYOUT, REMOVE J-BOX AND INSTALL IN CORRECT LOCATION. SALVAGE EXISTING CIRCUIT
FOR REUSE.
14. DISCONNECT AND RELOCATE EXISTING THERMOSTAT. SEE SHEET E202 FOR NEW LOCATION.
15. EXISTING LIGHT SWITCH TO REMAIN.
16. DISCONNECT AND REMOVE EXISTING SECURITY CAMERA. Revisions:
17. EXISTING CEILING MOUNTED RECEPTACLE TO REMAIN. MAINTAIN EXISTING CIRCUIT AND CONTROL. Mark Date By
18. DISCONNECT AND REMOVE EXISTING SPEAKER.
19. DISCONNECT AND REMOVE EXISTING FLOORBOX. SALVAGE EXISTING CIRCUIT FOR REUSE. 1 11-28-18
20. EXISTING DATA/POWER RECEPTACLE TO REMAIN. LANDLORD COMMENTS / PERMIT SET
21. DISCONNECT AND REMOVE EXISTING TRACK AND TRACK HEADS. SALVAGE EXISTING CIRCUIT FOR REUSE.
22. DISCONNECT AND REMOVE EXISTING EXIT SIGN. SALVAGE EXISTING CIRCUIT FOR REUSE.
23. EXISTING DUCT SMOKE DETECTOR TO REMAIN.
24. RELAMP EXISTING DOWNLIGHT WITH NEW LED LAMPS. LAMPS SUPPLIED BY NEXTORE, INSTALLED BY EC.
GC TO FIELD VERIFY AND PROVIDE INFO TO NEXTORE PMROJECT MANAGER.

13
4 (TYP)

Architect / Engineer of Record


WH
22
1
2
7 7
Michael Romes, PE
23 21
15 11 2441 Crown Pointe Blvd
15
21
Suamico, WI 54173
24
(920) 445-5007
18 19

5
7 7 7
5
16 Seal
13
(TYP)
21
3
9

21
7 7
10 19 19

11/28/18
EXIS. PANEL P1 21 Architect / Engineer Job No.:
6
5 21 030
5 16
12 7 7 Nextore Store Design Revision No.:
5
(TYP) 6

5
12
(TYP)
DES REV 02
5
19 Nextore project
21 Number 77889
14 Brand Design Type:
8 T 21

7 9 18 7
SGH 4.1 - TIER B GOLD

3
ISSUED FOR:
X Construction
17
21 21

20 Title
16
ELECTRICAL
13
DEMOLITION
(TYP) PLAN
Date Sheet
11-28-18
MEZZ. DEMO 1ST FLOOR DEMO Drawn By
1 SCALE: 1/4" = 1'-0"
2 SCALE: 1/4" = 1'-0" STAFF E200
Checked By

MPR
DESIGN & CONSTRUCTION
MANAGEMENT:
3 3 3

4
1
2 5 a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000
2 a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484

FURNISH INSTALLED
DVD-R INSIDE 3 TAG EQUIPMENT BY: BY:
TECH RACK CAMERA 1 1 WALL SHELF VENDOR VENDOR STORE #1843
2 AMPLIFIER VENDOR VENDOR
QUADRUPLEX
RECEPTACLE
(QUANTITY
ON PLAN) 3 SPEAKER WIRE VENDOR VENDOR CHARLESTON CHURCH STREET
4 SPEAKER VENDOR VENDOR 73 S. MARKET STREET
5 SPEAKER BAFFLE VENDOR VENDOR
CHARLESTON , SC 29401
SOUND SYSTEM RISER
E007 Construction for:
MONITOR

ENERGY CODE - COMMISSIONING


1. EXTEND CABLE TO PROPOSED HEAD END EQUIPMENT
LOCATION. PROVIDE ENOUGH EXCESS CABLE TO 1. COMMISSIONING AGENT TO CONFIRM THE FOLLOWING IN THE OFFICE AREA:
REACH ANY WALL IN BACK ROOM. COIL AND MARK
CABLE AS CCTV. HEAD END EQUIPMENT LOCATION 1.1. OCCUPANCY SENSORS DETECT MOTION AND ENERGIZE THE LOCAL SWITCHING.
MUST BE WITHIN 10' OF THE 'NETWORK SWITCH 1.2. OCCUPANCY SENSORS DE-ENERGIZE AFTER NO MOTION IS DETECTED AFTER A

4000 Luxottica Place Mason, Ohio 45040


ACCESS'. 30 MINUTE DELAY.

A Subsidiary of the Luxottica Group


2. FOR CAMERAS, PROVIDE WHITE PLENUM RATED CAT
6 CABLING. COIL 15' OF CABLING AT EACH CAMERA 2. COMMISSIONING AGENT TO CONFIRM THE FOLLOWING IN THE SALES AREA:
LOCATION FOR CONNECTIONS. 2.1. SIGNS, PERIMETER SHELVING AND SALES FLOOR DISPLAY CABINETS ARE
3. PROVIDE RJ-45 CONNECTORS AT CAMERA ENERGIZED AND DE-ENERGIZED WITH THE TIMER SWITCH OR CONTACTOR
LOCATIONS ONLY. CONNECTORS NOT NEEDED AT CONTROLLED BY TIMECLOCK.
THE HEAD END EQUIPMENT LOCATION.

CCTV SYSTEM RISER


E005 E012 ENERGY CODE - COMMISSIONING SMALL
PROJECTS

1 XX KEY NOTES - ELECTRICAL LIGHTING PLAN


1. FIXTURE TO BE PLUGGED INTO RECEPTACLE. VERIFY LOCATION OF RECEPTACLE AND LIGHT FIXTURE
WITH NEXTORE PROJECT MANAGER PRIOR TO ROUGH IN.
2. LOCATION OF WIRELESS ACCESS POINT. EC SHALL PROVIDE DATA CABLE FROM TECH RACK TO 24" ABOVE
CEILING FOR CONNECTION TO WIRELESS ACCESS POINT. PROVIDE MINIMUM 6 FT COILED CABLE AT BOTH
ENDS.
3. MAINTAIN EXISTING CONTROL.
4. ROUTE THROUGH EXISTING SWITCH BANK.
5. FIXTURE HAS EMERGENCY BALLAST/DRIVER. PROVIDE UNSWITCHED CONNECTION, ALONG WITH THE
SWITCHED CONNECTION, FOR THE BATTERY TO SENSE A POWER FAILURE.
6. LOCATION OF EXISTING SWITCHBANK.
7. LOCATION OF NEW SECURITY CAMERA. PULL NEW CAT6 WIRING FROM TECH RACK TO SECURITY CAMERA.
TERMINATION IS BY VENDOR. VERIFY LOCATION WITH NEXTORE PROJECT MANAGER PRIOR TO ROUGH IN.
SEE DETAIL E005.
Revisions:
8. LOCATION OF EXISTING TRAFFIC COUNTER. EC SHALL PROVIDE DATA CABLE FROM TECH RACK TO 24" Mark Date By
ABOVE CEILING FOR CONNECTION TO SHOPPERTRAK SYSTEM(BY OTHERS). PROVIDE MINIMUM 6 FT
1 11-28-18
COILED CABLE AT BOTH ENDS.
9. NEW SPEAKER LOCATION. SPEAKERS, WIRING AND ACCESSORIES ARE SUPPLIED AND INSTALLED BY THE LANDLORD COMMENTS / PERMIT SET

SOUND SYSTEM VENDOR. COORDINATE WORK WITH THE VENDOR PRIOR TO CEILING INSTALLATION.
10. INSTALL OWNER FURNISHED AUDIO SYSTEM INCLUDING CABLE, BACK BOXES, SPEAKERS AND VOLUME
CONTROL PROVIDE 3/4" CONDUITS FOR ALL WIRING IF REQUIRED FOR ACCESSIBILITY, LOCAL CODE OR
LANDLORD REQUIREMENTS. INCLUDE ALL WORK REQUIRED FOR A COMPLETE SYSTEM IN BID. WHERE A
FIRE ALARM SYSTEM IS PRESENT, PROVIDE RELAY TO DISCONNECT POWER TO MUSIC SYSTEM WHEN FIRE
ALARM SYSTEM IS IN ALARM. SEE DETAIL E007.
11. CONNECT NEW EXIT SIGN TO EM/NL/EX CIRCUIT.
12. REVISE BREAKERS AS REQUIRED FOR NEW 100 AMP, 3 POLE BREAKER FOR POWER TO NEW PANEL A. SEE
PANEL SCHEDULES FOR MORE INFORMATION.
13. RECONNECT TO NEW PANEL A. SEE PANEL SCHEDULES ON SHEET E202 FOR MORE INFORMATION.

RAYBAN
DEPT. Architect / Engineer of Record
101

CB2R
CB2B CB2R
Michael Romes, PE
UNISEX 7
(1) CAT6 8 2441 Crown Pointe Blvd
EX
RESTROOM #1 E2
A-5
13
103
E2 (TYP)
M2
EX
11 Suamico, WI 54173
E2
E2 X1RW (920) 445-5007
E2

CB2B
EX
E2 P1-8
EX
E2 3 4

E2
EX 5
E2 Seal
E2 M2E

CB2R
DO NOT INSTALL JUNCTION BOXES (WITH OR WITHOUT COVERS) E2
E2
VISIBLE TO THE PUBLIC IN THE SALES AND PUBLIC BACK OF E2
HOUSE AREAS. IF THIS IS DONE, THE GC IS REQUIRED TO E2

T-12
REMOVE THE JUNCTION BOX AT HIS/HER EXPENSE. E2 M2

CB1B
EX
E2
E2 E2

PIPP SHELF
36 x 12 x 96
E2
P1-3
3 4
E2 11/28/18
1 (1) CAT6

T-8
M3 Architect / Engineer Job No.:
EX 2 E2

PIPP SHELF
36 x 12 x 96
030
WI-FI E2
EXIS. PANEL P1 Nextore Store Design Revision No.:
12
E2
DES REV 02

PIPP SHELF
36 x 12 x 96

SCREEN 4X55
EX M2 E2

BACK OF
EX HOUSE Nextore project
102 Number 77889

PIPP SHELF
36 x 12 x 96
NEW PANEL "A" Brand Design Type:
5
EX M2E SGH 4.1 - TIER B GOLD
EX 7A 9 10 RETAIL
6 SALES AREA ISSUED FOR:

TECH
3 4 (TYP)
100 X Construction
P1-6

MICROWAVE
EX

FRIDGE
T-14
EX
E1 E1 E1 E2 E1 E1 E3 E1 E1

SAFE
Title

NEW CURRENT ELECTRICAL


LIMITING SUBPANEL 36 x 12 x 96
PIPP SHELF
36 x 12 x 96
PIPP SHELF
LIGHTING
PLAN
Date Sheet
11-28-18
Drawn By
LIGHTING
1 SCALE: 1/4" = 1'-0" Checked By
STAFF E201
MPR
BOX CALL OUT ON PLANS
DESIGN & CONSTRUCTION
(1) CAT6
TRAFFIC COUNTER MANAGEMENT:
RECESSED RECESSED FURNITURE (1) CAT6
WIRELESS ACCESS POINT
LEAVE 10FT (3) CAT6
POKE CASH WRAP
COILED AT 24" AFF
THRU TECH AT BACK OF (1) CAT6 PER OUTLET SHOWN
FITTING MICROWAVE HOUSE (1) CAT6 PER LED MONITOR
DIGITAL LED WALL
DIGITAL MONITOR
WIREMOLD
FRIDGE LOCATIONS. (3) CAT6
S1PTFIT LEAVE 4FT COILED BACKWRAP DIGITAL DISPLAY a 4000 Luxottica Place, Mason, OH 45040 p +1 (513) 765-6000
EVOLUTION 6AT POKE THRU (1) CAT6 TO EACH CAMERA + 15FT COIL
PLAN VIEW SURVEILLANCE CAMERA (NEW) a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484
IN CASH DESK AT
SERIES POKE THRU
CASH DESK
FLOOR
BOX
PLAN VIEW LOCATIONS.
STORE #1843
TECH RACK
SYSTEMONE FLOOR BOX HUBBELL
CFBS1R4PFB W/CUP
SYSTEMONE
FLOOR BOX (VERIFY LOCATION ON CHARLESTON CHURCH STREET
HUBBELL S1PFB 2 OUTLETS WITH (4) USB PORTS -
PLANS - IT CAN BE
WALL MOUNTED,
KEY: NOTE: TERMINATE EACH END OF
EACH CABLE, LABEL BOTH ENDS
73 S. MARKET STREET
SUB
HUBBELL USB15X2W
FIVE 1" CONDUITS FROM ABOVE CEILING (WHERE
FLOOR MOUNTED,
AND/OR MOUNTED IN
(#) CAT6 AND TEST, EXCEPT FOR
SURVEILLANCE CAMERAS, WHICH
CHARLESTON , SC 29401
PLATES CABLE TYPE
CEILING IS NOT PRESENT, TO 12" BELOW DECK) TO THE CASHWRAP) DO NOT REQUIRE TERMINATION.
SYSTEMONE TWO DUPLEX SYSTEMONE 24"W X 8" D SHELF 8X8X4 BOX BEHIND TECH RACK FOR CABLE QUANTITY
SUB-PLATE RECEPTACLES AND SUB-PLATE VOICE/DATA/CCTV WIRING. Construction for:
S1R4SP2X2DUPLEX ONE DATA OUTLET HUBBELL S1SPFFAL
CEILING
NOTE: THIS IS A TYPICAL DETAIL. ACTUAL DEVICES WILL VARY IN
QUANTITY AND LOCATION. ALTHOUGH MOST CASES ARE ADDRESSED,
REQUEST CLARIFICATION WHERE UNSURE.
COVER / MICRO
FLANGE
CFBS1R4CVRALU 6CTC2AL (CARPET) / 4"

5'-0"
TYPICAL SUNGLASS HUT
(CARPET) 6CT2AL (TILE) EMPTY DEVICE BOX WITH 43" 4" E024

4'-0"
FRIDGE MICROWAVE AND FRIDGE CONDUIT TO ABOVE CEILING COMMUNICATIONS RISER
FURNISHED AND INSTALLED BY (WHERE THERE ISN'T A CEILING, TO
FLOOR BOX SCHEDULE

4000 Luxottica Place Mason, Ohio 45040


E008 TENANT. 12" BELOW DECK) FOR SPEAKER

A Subsidiary of the Luxottica Group


WIRING. SPEAKER WIRING IS SHELF FOR SOUND SYSTEM EQUIPMENT. SHELF
SUPPLIED AND INSTALLED BY THE SUPPLIED AND INSTALLED BY THE SOUND SYSTEM

18"
DUPLEX OUTLET ON DEDICATED 20A CIRCUIT SOUND SYSTEM VENDOR. VENDOR. OUTLET TO BE SEPARATELY CONTROLLED
WITH A RELAY FOR FIRE ALARM CONNECTION (TO 1 ELECTRICAL LEGEND
5
SHUT DOWN POWER TO SOUND SYSTEM WHEN FIRE # DESCRIPTION

6'-3"
ALARM IS ACTIVATED). 04
LABEL
01
LABEL

1 MC CABLE, 12/2 w/GROUND, 12 AWG


05 02
LABEL LABEL

06 03
LABEL LABEL

3
36 IN WIDE X 96 IN HIGH X INCH DEEP FIRE
4
2 MC CABLE, 12/3 w/GROUND, 12 AWG
8 6 9 3 4X4 JUNCTION BOX
RETARDANT PLYWOOD BACKBOARD.

ELEVATION 10" PROVIDE 8 INCH X 8 INCH X 4 INCH DEEP FLUSH


MOUNTED JUNCTION BOX WITH BUSHED HOLE AND
4

5
SEAL-TITE FLEXIBLE CONDUIT WHIP
FROM POKE THRU TO J-BOX.
DUPLEX 20A RECEPTACLE
QUAD OUTLET ON DEDICATED 20A SCREW COVER. CENTER AT 16 INCHES AFF BEHIND 6 DOUBLE DUPLEX, 20A RECEPTACLE
10 4 3
MICROWAVE, REFRIGERATOR, USB CIRCUIT FOR VOICE/DATA/CCTV
E010 ELEVATION
EQUIPMENT
TECH RACK FOR CATEGORY 6 CABLES. TERMINATE
COMMUNICATIONS CONDUITS AT BOX AND EXTEND
CABLES TO TECH RACK.
USE STUB UPS FOR
ALL BRANDS,
7
8
9
FED BY CIRCUIT #1
FED BY CIRCUIT #2
SINGLE GANG BOX WITHOUT A COVER
EXCEPT FOR THOSE

24"
FOR DATA (DATA WIRING BY EC).

8"
TECH RACK - 24" WIDE X 36" HIGH (NOMINAL) INSTALLED IN A 10 ONE INCH CONDUIT STUB FROM FLOOR
CABINET WITH DOOR FURNISHED AND INSTALLED BY HOST LOCATION BOX/POKE THROUGH WITH PULL STRING
TENANT. (EG, MACY'S).
FLOOR FOR A HOST ELECTRICAL CONTRACTOR IS TO PROVIDE AND
GROUND BAR - PROVIDE #1/0 LOCATION, USE A INSTALL ALL ELECTRICAL EQUIPMENT SHOWN
COPPER TO SERVICE GROUND. HATCHED FOR
FURNITURE FEED IN THE DETAILS. NO WORK IS PROVIDED BY

8"
= OK ELEC
FITTING WITH A THE CASEWORK MANUFACTURER.
FLOOR MOUNTED TECH RACK(TR)/COMM. BOARD ELEVATION
E014 E014 621 " 3'-121 "
FLOOR BOX OR
POKE THRU. ALL POWER WIRING IS TO BE IN METAL
RACEWAY. SECURE RACEWAY TO INSIDE OF
FURNITURE. COORDINATE WORK WITH THE GC.

SGH - CASHDESK 0811 E206


E206 ELECTRICAL INFORMATION Revisions:
Mark Date By

1 11-28-18
LANDLORD COMMENTS / PERMIT SET

D
D

SE

SE
SE
D

D D D
SE SE SE
SE

SE

SE

ES

ES
ES
ES ES
ES
ES

ES

ES

EC

EC
S D C
D K HE RE
EC

EC

EC

EC EC EC

R
R

R R R

C C E

E
ED

LO IT L

C TA TYL

YL
E E E
E

E
ED

C SW TY
YL YL YL
YL

YL

YL

U CK D

2.5"
ST
H

E
C ED

2.5"

S
ST ST ST
H

ST

ST

ST
ED

LO H
IT
C

K
2.5"

C ITC
LO H
H

IT

C
K K K
K

K
C ITC

SW A
C

LO
C

C C TA C
SW

AT

SW

N
IT

A
LO

LO

LO LO A LO N
SW
SW

U D
C

C C D C
U

LABEL

LABEL

LABEL
LABEL

LABEL

LABEL

01
LABEL

LABEL

LABEL
LABEL

LABEL

LABEL

01
LABEL

LABEL

LABEL

+2.5" +2.5" +2.5"


01
LABEL

LABEL

LABEL

+2.5" +2.5" +2.5"


+2.5" +2.5" +2.5"

26.5" 26.5" 2'-8" 3'-1" 46" 46"

+2.5" +2.5"
+2.5" +2.5" +2.5" +2.5"

+2.5" +2.5"
+2.5"
DO NOT INSTALL JUNCTION BOXES (WITH OR WITHOUT COVERS)
VISIBLE TO THE PUBLIC IN THE SALES AND PUBLIC BACK OF
RAYBAN WALL UNIT 1 - 3 COLUMN RAY BAN WALL UNIT 2 - 3 COLUMN RAY BAN WALL UNIT 3 - 4 COLUMN
E620 ELECTRICAL INFORMATION E620 E621 ELECTRICAL INFORMATION E621 E622 ELECTRICAL INFORMATION E622
HOUSE AREAS. IF THIS IS DONE, THE GC IS REQUIRED TO
A-1,3 Architect / Engineer of Record
REMOVE THE JUNCTION BOX AT HIS/HER EXPENSE. (1) CAT6
A-2

WH 02113-00
EX
1 KEY NOTES - ELECTRICAL POWER/SYSTEMS PLAN Michael Romes, PE

02113-00
XX
UNISEX 02101-00 02431-00
2441 Crown Pointe Blvd

DIG-0005T-00-LOC1 02434-00
02110-00 02100-00
1. PROVIDE ACCESSIBLE JUNCTION BOX AND DISCONNECT SWITCH FOR 20A SIGNAGE CIRCUIT. SWITCH RESTROOM #1

02101-00 02100-00 02110-00 02101-00


02113-00 RAYBAN
SHALL SHUT-OFF SIGNAGE CIRCUIT. DISCONNECT SWITCH SHALL BE LOCATED ABOVE CEILING. PROVIDE 103 DEPT. Suamico, WI 54173

E621
A-2
LABEL FOR SWITCH PURPOSE. 101
2. PROVIDE 8 INCH X 8 INCH X 4 INCH DEEP FLUSH MOUNTED JUNCTION BOX WITH BUSHED HOLE AND SCREW (920) 445-5007

RB-F-RN-MP
E620
COVER. CENTER AT 16 INCHES AFF BEHIND TECH RACK FOR CATEGORY 6 CABLES. TERMINATE EX
COMMUNICATIONS CONDUITS AT BOX AND EXTEND CABLES TO TECH RACK. TECH RACK TO BE FLOOR
MOUNTED. CONNECT TO AVAILABLE EXISTING 20A CIRCUIT.
3. PROVIDE UN-SWITCHED, DEDICATED 120V, 20A CIRCUIT FROM EXISTING PANEL TO SERVE NEW DIGITAL (1) CAT6 S
SIGNAGE AT BACKWRAP. ROUTE CAT6 CABLE FROM OUTLET TO TECH RACK, AND LABEL/TERMINATE BOTH J

02101-00 02110-00 02110-00 02110-00


1 P1-3
ENDS. SEE ARCHITECTURAL SHEETS FOR DIMENSIONS AND VERIFY EXACT MOUNTING LOCATION WITH
NEXTORE PROJECT MANAGER PRIOR TO ROUGH IN.
EX
6 7
Seal
4. PROVIDE NEW FLOOR BOX STYLE "RECESSED". INDICATED FLOOR BOX WILL BE SERVED BY ONE
A-2
SWITCHED CIRCUIT. SEE DETAIL E008.

02432-00 02100-00
5. POWER NEW CASHWRAP. CONDUITS TO BE ONE 1" FOR POWER AND TWO 1-1/2" FOR COMMUNICATIONS.
PROVIDE NEW CAT6 CABLING TO TECH RACK. E622
P1-3
6. MAINTAIN EXISTING CONTROL.
7. ROUTE THROUGH EXISTING SWITCHBANK. (1) CAT6 6 7
8. NEW LOCATION OF EXISTING THERMOSTAT. REPROGRAM AS REQUIRED. COVER TO BE BLACK. 6 7
9. EXISTING SWITCHBANK LOCATION. P1-3
04438-00

3"
1'-34
10. VERIFY OUTLET MOUNTING LOCATIONS WITH NEXTORE PROJECT MANAGER PRIOR TO ROUGH IN.

04327-00

04435-00
02113-00
11. REVISE BREAKERS AS REQUIRED FOR NEW 100 AMP, 3 POLE BREAKER FOR POWER TO NEW PANEL A. SEE

PIPP SHELF
36 x 12 x 96
PANEL SCHEDULES FOR MORE INFORMATION.
12. PROVIDE NEW CEILING MOUNTED RECEPTACLE FOR DISPLAY WINDOW. CONNECT TO EXISTING CEILING 4
11/28/18

3'-041 "
04437-00
RECEPTACLE CIRCUIT IN THE AREA. 12

Architect / Engineer Job No.:

00
PIPP SHELF

0-
36 x 12 x 96
030

20

04434-00
CL

02
4

04811-00
A-2,4

3"
3'-04
EXIS. PANEL P1 Nextore Store Design Revision No.:
11 (3) CAT6 04437-00
A-2

DIG-0003L-00-LOC2
DES REV 02

04435-00
PIPP SHELF
36 x 12 x 96
(3) CAT6

SCREEN 4X55
E206 4
A-8
EX BACK OF 5 04438-00

3'-4"
HOUSE EX A-4 2'-5" Nextore project

3"
3 10
77889

4'-64
102 Number
3

PIPP SHELF
EX

36 x 12 x 96
(1) CAT6

04305-00
NEW PANEL "A" Brand Design Type:

SGH 4.1 - TIER B GOLD

04835-00
E024
A-9 9
EX
11'-821 " ISSUED FOR:

04303-00
TECH
2 E014 X Construction
A-7

MICROWAVE
RETAIL

FRIDGE
A-10

DIG-0006T-00-LOC3
E010 SALES AREA EX
A-12 P1-5 100

04465-00
04466-00

04463-00

04462-00

04462-00

04463-00
SAFE
CL
6 7 Title

8
04404-00 04423-00
04451-00
04404-00 04424-00
ELECTRICAL
36 x 12 x 96
EX
PIPP SHELF
36 x 12 x 96
EX
PIPP SHELF
POWER &
SYSTEMS PLAN
(1) CAT6
Date Sheet
11-28-18
Drawn By
POWER E202
1 SCALE: 1/4" = 1'-0" Checked By
STAFF

MPR
DESIGN & CONSTRUCTION
MANAGEMENT:
SCOPE: REQUIRED SYSTEM ACCESSORIES. MAIN DRAIN TEST CONTRACT SHALL INCLUDE ALL LABOR MATERIALS BEGIN. APPROVED DRAWINGS MUST BE AT THE
OVERVIEW: THE WORK SHOWN ON THIS DRAWING OPERATIONAL TEST OF CONTROL VALVES, NECESSARY FOR FIELD MODIFICATIONS DUE TO JOB SITE DURING CONSTRUCTION. PROVIDE A
IS REFLECTING THE GENERAL SCOPE OF WORK DURING BIDDING, THE CONTRACTOR SHALL MEET WHILE UNDER SYSTEM PRESSURE. EXIS. CONDITIONS. COPY OF THE APPROVAL LETTER TO THE
FOR THE FIRE PROTECTION CONTRACTOR. WITH THE LOCAL FIRE DEPARTMENT AND ARCHITECT.
ACTUAL AND FINAL DESIGN, INCLUDING ANY LANDLORD TO REVIEW ALL DRAWINGS AND TO PENETRATIONS OF FIRE RATED ASSEMBLIES TO BE THE CONTRACTOR SHALL CONTACT THE
SUBMITTALS AND ALL RELATED COSTS, ARE TO BE DETERMINE THE CRITERIA AND ALL RELATED FIRE-CAULKED PER AN UL LISTED DETAIL, TO BE ARCHITECT, ENGINEER OR OWNER PRIOR TO SPRINKLER SHOP DRAWINGS SHALL BE SUBMITTED
BORNE BY THE FIRE PROTECTION CONTRACTOR. DETAILS AS REQUIRED TO MEET THE APPROVAL OF SHOWN ON THE SHOP DWGS. BIDDING FOR INTERPRETATIONS AND TO THE OWNER AND THE LOCAL FACTORY MUTUAL p
a 4000 Luxottica Place, Mason, OH 45040 +1 (513) 765-6000
THE FIRE DEPARTMENT FOR THE DESIGN AND CLARIFICATIONS OF THE DESIGN AND INCLUDE IN OFFICE TO RECEIVE THEIR APPROVAL BEFORE a 6 Creamery Brook, East Granby, CT 06026 p +1 (516) 393-2484
THE SCOPE OF THIS INSTALLATION IS TO MODIFY INSTALLATION OF THE SPRINKLER SYSTEM AND DESIGN APPROACH: HIS BID ALL COSTS TO MEET ANY INSTALLATION CAN BEGIN. APPROVED
THE EXISTING SPRINKLER SYSTEM THROUGHOUT COVERAGE. CONTRACTORS FAILURE TO VERIFY INDICATE A HYDRAULICALLY CALCULATED FIRE THE DESIGN INTENT. CLARIFICATIONS MADE BY DRAWINGS MUST BE AT THE JOBSITE DURING
THE TENANT SPACE AND INSTALL NEW SPRINKLER REQUIREMENTS AND CRITERIA DURING BIDDING PROTECTION SPRINKLER SYSTEM IN ACCORDANCE THE ARCHITECT, ENGINEER OR OWNER AFTER CONSTRUCTION.
HEADS FOR THIS TENANT FROM THE EXISTING SHALL NOT RELIEVE THE CONTRACTOR OF WITH LANDLORD'S INSURANCE UNDERWRITERS BIDDING WILL STORE #1843
DISTRIBUTION SYSTEM. DURING BIDDING, VISIT
PROJECT FACILITY AND REVIEW THE DRAWINGS
COMPLYING WITH THE CRITERIA WITHOUT
ADDITIONAL COST TO THE OWNER.
FIRE RATING INSPECTION BUREAU AND ALL CODES.
SUBMIT SHOP DRAWINGS. VERIFY AVAILABLE
BE FINAL AND SHALL BE IMPLEMENTED AT THE
CONTRACTORS COST.
PLUMBING, HEATING AND ELECTRICAL
CONTRACTOR TO COORDINATE EQUIPMENT, DUCT,
CHARLESTON CHURCH STREET
FOR ALL OTHER TRADES TO DETERMINE EXISTING WATER SUPPLY STATIC, RESIDUAL PSI, AND GPM PIPING, AND CONDUIT INSTALLATIONS TO ASSURE 73 S. MARKET STREET
CONDITIONS AND THE SCOPE AND EXTENT OF THE ALL FIRE PROTECTION WORK SHALL BE GOVERNED OF FLOW NUMBERS WITH MALL OPERATIONS BIDDING CONTRACTORS SHALL HAVE A WORKING PROPER CLEARANCES AND NEEDED ROOM TO
REQUIRED WORK. REFER TO SPECIFICATION BY ALL APPLICABLE PORTIONS OF DIVISION 1 AND DIRECTOR PRIOR TO BID KNOWLEDGE OF LOCAL CODES AND ORDINANCES INSTALL RESPECTIVE SYSTEMS. ALL CHARLESTON , SC 29401
SECTION 15300 FOR ADDITIONAL CRITERIA. HEADS DIVISION 15 OF THE SPECIFICATIONS. AND SHALL INCLUDE IN THEIR BIDS THE COSTS CONTRACTORS TO COORDINATE PIPE
SHOWN ON DRAWINGS ARE SCHEMATIC ONLY. PIPING TO BE STEEL WITH COMPATIBLE FITTINGS FOR ALL WORK INSTALLED IN STRICT PENETRATIONS THROUGH WALLS AND ROOF,
FIRE PROTECTION CONTRACTOR IS RESPONSIBLE PIPE SUPPORTS: HANGERS, CLAMPS, RODS, AND PER NFPA 13. USE SCH-40 FOR BRANCHLINES, AND ACCORDANCE WITH GOVERNING CODES, THE PATCH TO MEET CODES. Construction for:
FOR THE EXACT PLACEMENT AND CODE OTHER ACCESSORIES OF AN APPROVED TYPE AND SCH-10 FOR MAINS. OTHER DEVICES AND PLANS AND SPECIFICATIONS NOT WITHSTANDING.
COMPLIANCE. COORDINATE WITH ALL OTHER IN SUFFICIENT NUMBER TO PROPERLY SUPPORT MATERIALS TO BE PER NFPA 13. THE CONTRACTOR SHALL ALERT ALL EQUIPMENT INSTALLATIONS, INCLUDING
TRADES. ALL PIPING SHALL BE FURNISHED AND INSTALLED. ARCHITECT, ENGINEER OR OWNER OF ANY RELATED DUCTS, PIPING, VENTS, WIRING,
PIPING SHALL BE SUPPORTED BY ROUND THE LANDLORD REQUIRES NOTICE PRIOR TO APPARENT DISCREPANCIES BETWEEN GOVERNING CONTROLS, VALVES, ETC..., SHALL COMPLY WITH
WHERE APPLICABLE, ALL PIPING SHALL BE WROUGHT U-TYPE APPROVED ADJUSTABLE PERFORMING WORK ON THE EXISTING SPRINKLER CODES AND NATIONAL ELECTRICAL CODE (NEC) ARTICLE 110,
CONCEALED ABOVE HUNG CEILINGS AND WITHIN HANGERS. SYSTEM. SPRINKLER CONTRACTOR SHALL BE DESIGN INTENT. PARA. 110-16, SUB. a., AND ARTICLE 384, PAR. 384-4.
CHASES AND FURRED-IN PASSAGES. PIPING AND RESPONSIBLE FOR COORDINATION WITH EACH DISCIPLINE SHALL BE RESPONSIBLE FOR THE
SPRINKLER HEADS SHALL BE COORDINATED WITH SPRINKLER SYSTEM SHALL BE ENGINEERED BY LANDLORD AND FOR ALL ASSOCIATED COSTS WITH LAYOUT OF ALL MECHANICAL, ELECTRICAL, PROVISIONS SET FORTH IN THE ABOVE NEC
LIGHTS, DUCTS, ETC. NO STRUCTURAL MEMBER INDIVIDUAL QUALIFIED BY THE STATE. DRAIN DOWNS AND REFILLING OF THE SPRINKLER PLUMBING, AND FIRE PROTECTION WORK SHALL BE ARTICLES.
SHALL BE CUT OR DRILLED WITHOUT FIRST SYSTEM. CAREFULLY PLANNED AND COORDINATED WITH
OBTAINING WRITTEN PERMISSION FROM THE ALL SPRINKLER HEADS LOCATED IN CEILING TILE EACH OTHER AND ARCHITECTURAL REFLECTED

4000 Luxottica Place Mason, Ohio 45040


A Subsidiary of the Luxottica Group
ENGINEER OR OWNERS REPRESENTATIVE. SHALL BE CENTERED IN 2X2 TILE. LANDLORD'S SPRINKLER CONTRACTOR MUST BE CEILING PLANS TO ENSURE THAT CEILING HEIGHTS
USED FOR ALL SPRINKLER & ASSOCIATED WORK. INDICATED WILL BE MAINTAINED. NOTIFY
OBTAIN AND PAY FOR ALL NECESSARY PERMITS, BUILDING IS MERCANTILE OCCUPANCY. COORDINATE WITH GC. FOR INSTALLER INFO ARCHITECT IN ADVANCE IF POTENTIAL CONFLICTS
APPROVALS, INSPECTIONS AND TESTS MAY EXIST. MODIFICATIONS TO WORK IN PLACE
ASSOCIATED WITH THIS WORK. PROVIDE SHOP ACCEPTANCE TESTING SHALL INCLUDE: VERIFY ALL CONDITIONS IN FIELD PRIOR TO BIDS. DUE TO FAILURE TO PROPERLY
DRAWINGS AND HYDRAULIC CALCULATIONS AS HYDRO-TESTING OF PIPING AT 200 PSI FOR 2 COORDINATE LAYOUTS WITH OTHER TRADES
REQUIRED FOR APPROVALS FROM STATE AND HOURS, DESIGN DRAWINGS ARE SCHEMATIC. THIS SHALL BE AT THE CONTRACTORS EXPENSE.
LOCAL AUTHORITIES. OBTAIN ALL APPROVALS OPERATIONAL TEST OF FLOW SWITCH, VIA THE CONTRACTOR SHALL VISIT THE SITE PRIOR TO
PRIOR TO UNDERTAKING ANY WORK. INSPRS TEST CONNECTION. BIDDING OR AWARD OF THE CONTRACT TO SPRINKLER SHOP DRAWINGS SHALL BE SUBMITTED
OPERATIONAL TEST OF TAMPER SWITCHES. INSPECT EXIS. FIELD CONDITIONS. THIS TO THE LOCAL FIRE MARSHALL AND RECEIVE
PROVIDE ALL REQUIRED SIGNS. PROVIDE ALL THEIR APPROVAL BEFORE ANY INSTALLATION CAN

Revisions:
Mark Date By

1 11-28-18
LANDLORD COMMENTS / PERMIT SET

1 XX KEY NOTES - FIRE PROTECTION PLAN


1. EXISTING SPRINKLER HEAD TO REMAIN.
2. EXISTING SPRINKLER PIPING TO REMAIN.

RAYBAN
2 DEPT. Architect / Engineer of Record
101

02113-00

Michael Romes, PE

02113-00
UNISEX 1
RESTROOM #1 02101-00 02431-00
2441 Crown Pointe Blvd

DIG-0005T-00-LOC1 02434-00
103 EXIS. ∅1" 02100-00
02110-00 @17'-0" A.F.F.

02101-00 02100-00 02110-00 02101-00


02113-00
2 2
Suamico, WI 54173
1 1 (920) 445-5007

02101-00 02110-00 02110-00 02110-00 RB-F-RN-MP


Seal

02432-00 02100-00
1

EXIS. TURNS DOWN


04438-00
TO STREET LEVEL

04327-00

04435-00
02113-00
PIPP SHELF
36 x 12 x 96
EXIS. ∅1" @17'-10" A.F.F.
2 2
04437-00
11/28/18
1 2 1 Architect / Engineer Job No.:

00
PIPP SHELF

0-
36 x 12 x 96
030

20

04434-00
02

04811-00
Nextore Store Design Revision No.:
04437-00

DIG-0003L-00-LOC2
DES REV 02

04435-00
PIPP SHELF
36 x 12 x 96

SCREEN 4X55
EXIS. ∅6" SPRINKLER MAIN
BACK OF @ 16'-7" A.F.F. 04438-00
HOUSE Nextore project
102 Number 77889

PIPP SHELF
36 x 12 x 96

04305-00
Brand Design Type:

SGH 4.1 - TIER B GOLD

04835-00
RETAIL
SALES AREA ISSUED FOR:

04303-00
TECH
EXIS. ∅1" @17'-0" 100 X Construction
1 2 A.F.F. 2

MICROWAVE
FRIDGE

DIG-0006T-00-LOC3
2 1 1

04465-00
04466-00

04463-00

04462-00

04462-00

04463-00
SAFE
Title
04404-00 04423-00 04404-00 04424-00
04451-00 FIRE
36 x 12 x 96
PIPP SHELF
36 x 12 x 96
PIPP SHELF
PROTECTION
PLANS
Date Sheet
2
11-28-18
Drawn By
FIRE PROTECTION PLAN FP200
1 SCALE: 1/4" = 1'-0" Checked By
STAFF

MPR