Академический Документы
Профессиональный Документы
Культура Документы
If sufficient nUmber of tests (more than about 40) Buiiding Codes Definition of Compressive
are available, the strengths will generally Strength
approximate a nonnal distribution. TIle nonnal
distribution curve is symmetric about the mean Based on tIle consideration tIillt eventual failure in
a structure occurs at tIle weakest location in a
value, X, of the data. The dispersiQn of the data can
region of higher intenlal action effects, the concrete
be measured by the sample standard deviation, S, classes are classified on the basis of the
using Eq. (1).
characteristic compressive and not on the mean
25
utb 10
15
'0 .!
~ Iii
CIl
C
5
Figure 1 Nonnal frequency curves for cOefficient of van at ions of 10, 15, and 20%. (3]
Table I: C CI
- - -- -- - - - -- ding EC2/EBCS2
4.1
C2528
C3033
1.9
2.6
48
16
20
2.2
24
2.5
12EC2
1.6
EBCS2
2.250
20
25
40
45
EBCS230
35
16
12
C6058
C5048
1.6
C2024
CI5
40
4.0
1.9
3.5
3.5EC2
20
EC2
Compressive
Average
Strength 2.9
3.8
3.2 53/ctm(N/nun2)
3.0Strength
38
43
Characteristic
/cm(N/rrun2)
Cylinder
Average
fck(N/mm2) Cylinder
Tensile Strength32
Based on the evaluations of the test results of many long, is loaded in flexure at the tilird points of a
experiments, which have shown that, the standard 600 mm span until it fails due to cracking on the
deviation for all classes of concrete other than tension face. Assuming tile concrete is linearly
C12/15 is approximately 5 N/rrun2 [6]. Thus the elastic, tile flexural tensile strength or modulus of
Euro-code recommends the following relationship f.Upture,fro is calculated from a modulus of rupture
between the characteristic and the average test using Eq. (5).
strengths:
Ir = 6M (5)
(4) bh 2
where,
Thus for a specified lllimmUIl1 characteristic M=moment
strength of concrete, which is identical to the class b = width of specimen
designation, both according to EC2 and EBCS2, h = overall deptil of specimen
the required mean strength must be greater or equal
to the value given by Eq. (4). For instance, TIle second common tensile test is tile split cylinder
according to EBCS2, concrete grade C30 with a test, in which a standard 150 lllin x 300 nun test
characteristic cube and cylinder compressive cylinder is placed on its side and loaded in
strength of 30 N/uun2 and 24 N/mm2 respectively, compression along a diameter as sho~ in Fig. 2a.
should have an average cube and cylinder In a split cylinder test, an element on. the vertical
compressive strength (/...",)not less than 38 N/mm2 diameter of the specimen is stressed in biaxial
and 32 NIIllin2 respectively. tension and compression, as shown in Fig. 2c. The-
stresses acting across the vertical diameter rangtl
Tensile Strength of Concrete from high transverse compressions at the top and
bottom to a nearly uniform tension across the rest
TIle tensile strength of concrete varies between 8% of the diameter, as shown in Fig. 2d. TIle splitting.
and 15% of its compressive strength. TIle actual tensile strength, /sp, from a split cylinder test u;
value is strongly affected by the type of test carried computed using Eq. (6).
out to detemline the tensile strength, the type of
aggregate, the compressive strength of the concrete, 2P
(6)
and the presence of a compressive stress transverse Isp = 1r Id
to the tensile stress [7].
where,
Two types of tests are widely used to determine the P = maximum applied load in the test [kN]
tensile strength of concrete. The first of tilese is tile I = length of specimen [mm] .
modulus of rupture or flexural test in which a plain d = diameter of specimen [nun]
concrete beam, generally 150nunx 150nunx750mm
study the slwnp test was used to assess the on Physical and Mechanical Characteristics of
workability of the concrete mixes and the mixes Messobo Cement Unpublished report].
were designed to result in two workability levels,
i.e. low to medium and medimn to high strength Table 2: Chemical C ....•.. ~-- - ..•.....••.•...fM
.... - - ---- - - - -- -
Calcium
Ferric
Oxideoxide
Silicate
Aluminum
Magnesium oxide
oxide
trioxide
composition
oxide Percentage 3.87
1.72
64.15
21.23
5.24
category were treated. No.
5432 1
passing 4.75mm. It was then decided to wash the After the sieve analysis of the purchased
sand until the silt content was lowered to an aggregates, the results were reviewed and blended
allowable limit of less or equal to 6%. After to satisfy the ASTM requirement
washing the sand, the silt content was reduced to an
average value of2.71% (2.53 and 2.88). Accordingly, 80% passing 19mm sieve opening
and 20% 4-lOmm aggregate were blended to obtain
Since it is not always possible to wash sands in nominal size of 19.0 to 4.75 mm (Grade B); 90%
construction sites, some tests were also carried out passing 37.5 mm sieve opening and 10% 4-lOmm
using sand containing a silt content higher than the were blended to obtain (Grade A) and 80% passing
recommended value (6%). Accordingly, four mixes 12.5mm aggregate and 20% 4-lOmm were blended
(Mix AlO, CIO, A20 and C20) were prepared using to obtain (Grade C). TIle blended aggregates sieve
a sand consisting of 8.55% silt, which is a mean analysis test results are shown in Tables A2, A3
value of 8.49, 8.83 and 8.33%. Mix AlO and ClO and A4 in the Appendix.
were prepared using a maximwn aggregate size of
20 mm and were targeted to result in C-30 and C- MIX PROGRAM
25 concrete grades, respectively. Mix A20 and C20
were prepared using a maxinllun aggregate site of Mix Design and the test Program
37.5 nun and were targeted to result in C-30 and C-
25 concrete grades, respectively. It is generally understood that mix Design is a
process in which one detennines the relative
Coarse aggregate quantities of the ingredients of concrete prior to
mixing to produce concrete of desired properties.
The coarse aggregate was obtained from the quarry Based on the DOE procedure, the quantities of the
in Addis Ababa and had three grades: 4-lOmm; 20- ingredient per cubic meter of concrete and per
40nun and 4.5-30mm. The aggregates were volume of trial Mix, 55 liters in the case
supplied relatively clean and had an absorption considered, are established. TIle total nwnber of
capacity less than 1%. The supplied aggregates specimens and considered parameters are shown in
were not of the required grading and could not be Table 4.
used to produce concrete without blending. It was
then decide to follow ASTM Standard C33-78 and Moreover, four trial batches with rnaximwn coarse
therefore the nominal size of graded aggregate 37.5 aggregate passing 37.5 and 19 aimed at concrete
to 4.75mm (Grade B); 19.0 to 4.75mm (Grade A) grades of C25 and C30 using natural sand with
and 12.5 to 4.75 mm (Grade C) were selected. higher silt content were prepared. To asses the
resulting concrete grade that could be obtained
[2]For each trial batch three cylinders for tensile splitting test which Swn up to 3x3x2= 18 cylinders.
when using cement content of 275 kg and 300 kg TIle specimens were kept in the moulds for 24
per meter cube of concrete two mixes labeled as G I hours after wltich they. were labeled and placed in a
& G2 and consisting of 28 cubes and 4 cylinders, tank filled with water for curing purpose and kept
were carried out. Tltis brings the total number of wet for two more days. TIlOse specimens to be
trial batches to 43, with 939 cubes and 90 kept air-dry before the age of testing were
cylinders. This does not include those mixes withdrawn and placed at an open place in the
prepared and tested outside the University. laboratory. TIle rest were kept in the curing tank
and wet cured until the date of testing.
Apparatus
Before testing, the specimens were removed from
In tltis research work, the following laboratory curing water tank or those which were air dry were
apparatus were used: rotating pan ntixer, slump ilmnersed in water for about 5 minutes and then all
mould, cube and cylinder moulds, vibrating table, were weighed, dimensions checked and recorded
curing tank made of concrete, balance and for density and failure stress calculation.
Universal Testing Macltine which has a capacity of
testing 1000 Ton in tension and 2000 Ton in TESTING THE CONCRETE
compression.
Cube Compression
Test Specimen Preparation
Compressive strengtll is the main measure to
Mixing of the constituent materials was carried at prescribe the quality of concrete. Before each test,
room temperature of 22±3°C and relative humidity the testing machine bearing surfaces were wiped
of 32% to 40%. The size of the batch for each mix clean and any loose grit or other extraneous
was about 70% of the rated capacity of the mixer to materials were also removed from the surface of
avoid incomplete mixing and spillage. Before using the cube, which may be in contact with the platens.
the nlixer. it was cleaned to ensure that no fresh TIle cube specimen was centrally placed on the
concrete remains from previous batch. Moreover, lower platen and it was checked to ensure that the
all necessary measures were taken to ensure that no load will be applied to two opposite faces of the
free water on the pan mixer was left and whenever cube. TIle load was continuously applied at a
it is dry it was wiped using a damp cloth. nominal rate within a range of 0.2 to 0.6 MPa per
sec, until no greater load can be sustained. TIle
For each trial mix, two sets of mixes with the same maximlUn load applied to the cube was recorded to
proportions were prepared on a given date of obtain the failure stress. TIle mean results obtained
mixing. In each mix, dry mixing was carried out and the calculated failure stresses at the ages of
for about one minute and water is added within the 3,7,14 and 28 days as either wet cured or air dried
following 30 to 60 seconds. Mixing continued for are provided in Table 6. TIle majority (over 80%)
2 ntinutes after all constituents of concrete were of the test results indicate that the target concrete
added. compressive strength was achieved and consistent
with the Code's recommendations.
When lnIXmg was completed, the workability of
each mix was measured using slump test following Tensile Splitting
standard procedure. The moulds were then placed
on the vibrating table and the fresh concrete was All three-cylinder specimens from each mix were
deposited in layers of approximately 1/3 of the wet cured for 28 days. Tempered hard board pads
respective mould content whereby each layer was (dimensions about 330 mm by 25 mm) are placed
compacted using the vibrator following standard on the bearing surfaces of the cylinder specimens
procedure. For all cases other than those indicated and loaded symmetrically and continuously until
by a remark in Table 5, 22 - 150mm cubes 3 - 100 failure at the rate of 0.02- 0.04 MPa per second.
mm cubes and 3 cylinder specimens were prepared The sununary of mean results is given in Table 6
from each trial mix to detennine a 3,7,14 and 28 and the tensile strengtll of the concrete specimens
days age strengths and tensile splitting strengtlls. is generally between 6-10% of the compressive
strengtll values.
- - _ u Tabl
u C . d .
wlc for diffi f
20A2
Fl
F2
Al
Bl
D2
Dl
E2
El
Gl
C4
C3
E332
17
DIR
D4
D3
A4
45
48
60
64
47
10
35
15
20AI
24
39
43
52
10
HI-38
H2-38
H2-20
D2R
B]R
D5
D6
E4
A3
C5
E6
E5
F4
F3
0.5]
0.45
F5
F6
0.90
0.54
0.57
0.49
0.45
1.30
1.40
30
20
25
23
14
26
78
14
1.25
12
H2-12.5
C6
Cl
C2
G2 5of
236780.42
Coarse
(mm)
Slump
Type
Agg. 1233
207
0.55
0.65
212.75
180.00
1302.00
1342.90
0.45
0.57
0.49
0.42
0.65
0.60
0.42
0.57
0.55558.00
567.80
205.00
]]90.00
160.00
195.00
190.00
1413.30
1358.06
1248.10
1430.10
1222.50
1184.92
1230"32
1303.00
]80.00
1286.40
1]43.62
1095.00
1137.90
1271.60
1313.60
37.5
471.10
61.00
614.80
624.12
641.90
633.60
730.00
528.90
527.28
549.20
563.28
697.50
598.40
1440.6
]051.5
226.25
0.45
0.49
975.7
226
1183
210
207.5 ]80
400
460
363
355.60
327.30
525.37
328.57
452.40
433.30
397.60
340.00
298.20
342.10
281.00
488.]0
370.00
359.60
170.00
1098
977
226
798.3
207
737
]62
602
732
419.00
347.00
377.80
455.60
488.00
460
397
422
434
380
503
538
618.10
19.5
]221.4
]80
1013
195
1113.20
1143.70
1318.10
1274
1063
1058
1230.30
1169
969
686.7
19.5
12.5
1070.0
702
1237626.20
195
527.30
563.30
564.90
601.5
546
761.5
764
708
628.4
675
37.5
6]
822
857
494.05
188 37.5
382.4
150
825 7.4
Water
948.4
12.5
]2.5
40
35
37.519.5
19.55+(j
coarse
40
25
45
30
25
30
35
45 12.5
25+
40+
Fine++Strength
Concrete
537.10
5+(j
111.8.90
657.10
Cement
1315\- (j
(j
(j
agg.
agg.
[Mpa]
..10
passing
Target 275.00
300.00 ratio
Max. size Mix
(kg perComposition
m3 of concrete)
-----
20.08
23.30
12.52
28.81
34.57
10.8
8.90
10.32
34.18
35.51
49.05
42.51
46.79 33.96
10.87
36.78
39.79
18.16 8.94
10.70
31.92
15.62 Tensile
Bl
F2-----
-----
34.41
D6
D5
E6
43.63
20Al
D4
D2R
H2-12.5
6.49
Al
27.30
34.90
H2-38
6.76
D2
Dl
Fl
E2
El
Cl
26.97
24.27
39.40
36.93
45.83
32.21
28.60
17.34
42.28
40.85
38.88
36.52
27.35
H2-20
E5
C6
F6
F5
G2
20A2
D3
C3
Gl 23.92
48.13
42.90
36.46
44.54
39.11
37.79
37.25
46.75
30.97
28.77
29.96
30.45
24.65
C5
22.20
23.41
336.80
34.86
45.54
41.08
40.82
35.04
35.61
35.00
40.22
Concrete
56.18
44.06
43.56
40.68
55.74
8.12
26.26
29.47
25.56
30.70
35.91
35.52
47.70
38.96
39.90
DIR
E3
E4
F4
F3
A342.30
35.75
41.06
28.56
33.36
38.68
49.28
35.99
40.37
34.77
35.08
39.93
36.59
33.71
37.12
50.91
52.62
46.35
46.95
50.37
41.03
40.44
36.62
45.48
28.44
54.83
35.34
36.61
44.56
24.48
28.65
34.83
HI-38
BIR
Cured
C2
C4 5.18
30.86 5-----
-----
Strength
-----
-----
-----
24.61
24.15
25.95
316.50
3.97
35.23
27.98
26.66
20.41
21.82
11.90
18.25
17.26
4.7
27.32
40.81
31.41
A4
36.5433.13
23.65
39.88
15.08
25.29
20.18
17.74
19.19
19.06
15.51
14.97
34.00
22.65
52.26
21.84
49.12
20.58
24.88
8.43
23.30
31.63
6.56
36.07
29.76
30.58
22.73
18.62
37.95
44.50
54.08
35.14
37.99
29.51
33.71
33.24
31.17
24.31
35.41
22.37
28.48
48.40
53.21
39.66
33.24
34.73
32.18
37.78
46.72
40.61
35.70
31.96
30.37
35.00
29.55
30.48
47.12
31.75
30.35
36.86
28.17
23.35
22.51
23.78
35.50
36.18
37.69
51.72
39.29
51.34
22.39
27.64
43.39
46.14
42.48
7.25
20.08
28.61
32.62
32.06
23.55
34.26
42.33
25.73
32.99
25.60
42.16
40.21
39.50
36.20
48.29
39.57
35.12
53.26
437.67
34.28
32.05
37.89
46.47
31.02
34.36
19.75
46.92
44.30
43.86
44.38
53.38
21.94
33.83
33.07
45.42
7Cured
39.53
51.44
36.27
48.00
29.42
34.67
25
45
30
25.79
40+0'
34.48
30+0'
40
35
Type
28 Cured
35.62
37.32
26.37
36.76
33.69
34.30
45.91
33.43
54.59
51.19
52.13
25+
40+
42.56
42.62
32.26
42.23
38.98
41.07
46.53
29.33
340+0'
30
Strength
14 days
Cured
[MFa]
-days
----
-----
4.01
18.90
17.63
18.61
19.80
015.41
19.01
5+0'
3.28
2.89
2.64
2.73
3.39
2.78
2.82
4.08
3.98
2.95
2.81
3.54
3.06
3.04
3.55
3.30
3.56
3.47
2.83
2.65
3.07
2.77
3.36
3.63
2.88
2.99
3.69
2.59
+
+0'
'+0'
+0'
5+0'
days+0'
+0'
days
4.69days 14-----
acr7 days
Targetdays
28 days
Average Compressive Strength [MFa]
Splitting
33 days
days
+ since the coarse aggregate at the time of testing was air dry its moisture content was checked to bring it to
SSD condition level. 1% extra water is added above the free water shown in this Table
++ the cement content due to teclmical reason is reduced by 3% from the original Mix label C1.
A
D
B
C 35.37
32.29
+14.2
+17.7
+4.7
49.07
41.07 Mean
7 days cube compressive strength (MFa)
Mix 28748.30
0.0
+10.3
32.06
23.30
22.73
+0.7
36.52
+9.4
26.50
22.8849.05
34.90
38.23
ESA
+13.7
29.51
AAU
42.28
days ESA to28AAU
AAU
days
label days lab. % increase:
Etll.St.
Despite a I% addition of water, a lower shunp and However, there are situations encountered at site
a higher compressive strength test results were where it may not be possible to achieve the
obtained consistently from tile Laboratory of the specified lower percentage of silt content. To
Etlliopian Standards Authority than those obtained check the effect of silt on tile strengtll of concrete,
from Addis Ababa University laboratory. These four mixes were prepared using 37.5 nun and
may be attributed to the following: i) the 19nun coarse aggregate sizes and sand witll silt
aggregates may have lost surface moisture during content in tile range of 8 to 9%. The mix
transportation and t1ms resulted in lower proportions and obtained test results are
workability. To compensate for this, extra vibration summarized in Tables 9 and 10, respectively.
A20
AIO
~
C20
CIO 19.95
115.41
8.90
13.31
Label
28.99
23.14
22.34 28
335.57
7wet
days
days
(27.30)
36.24
25.74
26.87
(30.70)
33.31
21.
(25.56)
3 days29.80
30.91
21.50 wet
wet )7 da 28
(35.62)
(22.73)
(23.30)
95(37.32
(39.90)
(25.60)
(36.20)
(35.52)
(23.55)
age Cube compressive Strength [MFa] 328.40
days (24.27)
31.40
39.62
31.5-+ (34.90)
(36.52)
(40.21) sagedays age
Mix
Table 12: Comparison of actual and predicted compo strength test values for the three aggregate sizes.
wle 0.42
0.55
0.49
0.45
48.59
37.21
43.39
37.48
39.43
46.65
35.33
34.74
40.95
49.04
44.59
47.92
33.81
35.39
41.09
45.86
38.16
39.64
44.86
44.06
49.14
0.57
Test
36.40
34.90
computed
53.30
51.77
51.79
53.81
52.90
50.13 Remark
result
35.48 usin~
using EQ.
Eq. 9a
9c
9b
J:
0,
c 70
~ 60
.3 days Cured
~>0-'ii 50 R
'(jj
III ~ 40
• l1li 7 days Cured
A 28 days Cured
~
Co
30
E
o 20
u 0.3 0.4 0.5 0.6 0.7 0.8
The cement content per cubic meter of concrete The contribution of hannless and acceptable
used in tlle mix program is plotted against the percentage of silt content in concrete produced
compressive strengtll test result and are shown in using large aggregate sizes should be, however,
Figure 4. It is observed from the figure that the studied further since it may have a pore filling
general trend is tlle required cement content effect and might contribute to slight increase in
increased proportionately with desired increased strength properties.
compressive strengtll .
.c:
C, 70
c:
-~
en •...•
60
.3 days Cured
Q) ns 50
>Cl. l1li 7 days Cured
'in ~
en •.••.•
40
A 28 days Cured
~
Q. 30
g 20
u 200 250 300 350 400 450 500 550 600
Cylinder splitting tests were used to detennine the Based on the intensive laboratol)' investigations,
tensile strength of concrete. Usually codes of tlle following conclusions are drawn:
practices provide empirical expressions to
approximate tensile strengtlls from compressive 1. The suitability of the Messebo Ordinary
strength values. Based on the test results, attempts Portland Cement (OPC) for stmctural use of
have been made to develop relations between.!sp concrete has been verified through tests and it
andfcm andj'/m andjm. However. the relations have has been found that the product can be utilized
lower correlation coefficients indicating that they to obtain concrete strength grades up to C 45.
are sensitive to variations in concrete
classes/grades and tlms not discussed further. 2. It has been found generally that the concrete
specimens produced using Messebo OPC
Effccts of silt contcnt on thc comprcssive achieved about 70% of the 28 days
strcngth of conCl'cte compressive strengths at the 7tl1 day and thus
helps in reducing form-work stripping time.
The test results indicate that reduction of silt The higher early strength development has a
content (from -9% to -3%) improves workability positive effect on subsequent construction
and has the advantage of increasing the activities.
compressive strength (by up to 28 %). This is
attributed by the fact that silts decrease the bond 3. Values of cement and aggregate content per
between aggregate and cement paste and absorbs 100 kg of cement corresponding to desired
the share of water required [or cement hydration workability have been established.
and tlms results in lower compressive strength and Accordingly. cement content in kg per m3 of
workability. One can imagine the effect of higher concrete [or different classes/grades of
silt content (15-25% which is usually the case in concrete are provided in Table 13 and
very silty sands) in compressive strength reduction proportions of total aggregate and
of concrete structural elements. corresponding percentage of fine aggregate per
100 kg of cement are provided in Table 14.
4. Excessive silt content than specified by the b) proper curing method is employed for at
code (6%) reduces the compressive strength of least 7 days to ensure sufficient hydration
hardened concrete and workability of fresh of the cement,
concrete.
c) the coarse aggregate used is basaltic
5. The recommendations given on Tables 13 and crushed stone or its equivalent and
14 can only be used in practice provided:
d) the fine aggregate is free from impurities
a) proper compaction of the concrete is with silt content not exceeding 6%.
made,
6. The relations established in Eqs. (9) and (10)
can serve as a rule of thump to approximate
desired parameters.
- ••- ---
-------- ---- •.---. -bl - --.. --- --0 r -- --- -- - ----- ---
350
320
380
400
460
490
510
430
400
350
370
450
500
Medium300
340
360
400
450
460
440450.44
Medium
150
280
Medium 0.40
0.48
0.57
0.53
00
20
50
70
Low w/c150
Low 37.5Imn
Slump}
Shimp}
SIump2
SIump2
Slump2 19.5Imn
150
ratio 1.30
12.5Imn
Maximum Low Aggregate Size
crete
a) Before concrete mix preparation, attention [1] ACI Standards for concrete mix design:
should be given to critically assess the silt 211.1-77 and 211.3.75.
content, density, absorption capacity and
grading of aggregates. [2] DOE Method of Mix Design, Department
of Environment, UK.
b) Curing is a very important factor in producing
good quality of concrete and a 7 days of curing [3] ACI Committee 214, Recommended
must be the absolute minimum curing duration Practice for Evaluation of strength Test
for structural members. Results of Concrete, (ACI 214-77),1977.
d) The additions of concrete additives, such as [6] Koenig G. and Tue N., Grundlagen des
plasticizers, should be encouraged to improve StalIlbetonbaus, Teubner Studienbucher
the property of concrete. Bauwesen. 1998.
e) Business of standard aggregate supplying and [7] Raphael J.M., Tensile strength of Concrete,
ready mix concrete production and supply ACI Journal, 1984.
should be encouraged for various reasons since
it improves quality, reduce storage [8] Neville A.M .. Properties of Concrete, 3rd
requirements, and a lesser work force ed., Longmmm Scientific & Technical
(laborers) is required on site. Series. 1986.
f) Furtller research work is proposed to establish [9] BS-12, 1989 Ordinary and Rapid hardening
mix design proportions in order to produce Portland cement.
better quality and higher grade of concrete
with other cement and aggregate types. [10] ASTM C33-78. Specifications for concrete
aggregates.
ACKNOWLEDGEMENTS
[11] KIieger P .. Effect of Mixing and Curing
The authors are indebted to Messobo Cement Temperatures on Concrete Strength, ACI
Factory for the financial support in the research Journal Proceedings, Vol. 54. No. 12, June
work and for supplying tlIe Messobo OPC free of 1958.
charge for the purpose of the research work. The
authors also appreciate the keen interest and [12] Troxell G.E., Davis H.E., and Kelly J.W.,
participation of Ato Mekonnen Fisseha and Ato Composition and Properties of Concrete, 2d
Hagos Seyoum, who were senior engineers during ed., McGraw-Hill, New York, 1968.
tlIe construction of Messebo Cement Factory, in the
research work. Dr. Fisseha Woldu is acknowledged [13] MacGregor J.G., Reinforced Concrete,
for his interest in the subject and for his Mechanics & Design, Prentice hall,
administrative support in facilitating the research Engelwood cliffs, 3rd Ed., 1997.
project. Finally the laboratory services offered by
the Ethiopian Standards Authority is also [14] Gonnerman H. F. and Lerch W., Changes
appreciated. in Characteristics of Portland Cement as
Exhibited by Laboratory Tests over tlIe
Period 1904 to 1950, ASTM Special
Publication 127, ASTM, Philadelphia, 1951.
[15] Schneider, K-J., Stahlbeton und [17] Newman K and Newman J. R, Failure
SpaJUlbeton nach EC2, 12th ed., Werner Theories aJld Design Criteria for Plain
Verlag, 1996. Concrete, Solid Mechanics llild Engineering
Design, 1972.
[16] Thomas, T. C. Hsu, P. O. Slate, G. H.
Sturman and George Winter, Micro- [18] Richart F.E., Brandtzaeg A. and Brown
cracking of Plain Concrete aJld the Shape of R L., A study of the Failure of concrete
tile Sress-Strain Curve, ACI Journal, 1963. under combined Compressive Stresses,
University of Illinois Engineering
Experiment Station, 1928.
Table AI: Sieve analysis of blended saJld, 75% passing 9.75nun llild 25% passing 600 j1m.
a) Sample 1
Sieve 518.6
22.29
596.9
578.2
3.28
00
95-100
100
488.1
538.3
482
420.196.7
531.7594.6
596.9
100
3.3
15.17
14.97
2.78
32.73
with8.78 16.4
80-100
557.9
10-30
50-85
25-60
6[%]
[87.9
575.6
2-10
73.0
12.1
2.78
50.7
97.2
13.9
49.3
18.0
sieve
Mass 163.7
82.0
75.9
43.9
30.1
51.8
13.2
Retained
Mass 27.0
111.5
434
74.9
Coarser
retained
--Sand
[g] g) 0Mass
0of
Retained
ASTM
of sieveof
Percentage
requirement
1%] Passillg
[%1
[g]
Percentage
Percentage [C33-78]
1%]
L = 500.2
b) S .----r--- -with
sIeveretained
Sieve
596.9557.3
100
518.6
420.1
538.3
Mass 10-30
531.7
578.2
2.70
8.50
00
95-100
80-100
488.1
48297.3
6488.8
32.99
Mass
[g] 2-10
574.2
591.7
596.9
100
2.7
15.22
15.06
2.92
22.62
25-60
50-85
2.92
51.0
73.6
26.4
97.1
49.0
18.0
Retained
Ig]
[%]82.0
113.1
75.3
76.1
14.4
53.1
31.7
34.7
014.6
Coarser
11.2 J of
0Retained
165
ASTM
42.5
13.5
SaJld
ofMass
of sieve
requirement
[%]
Percentage
[%]
Percentage
Passing
[g]
[%]
Percentage [C33-78]
The blended aggregates grading satisfy ASTM Stllildard C33-78 aJld used for subsequent concrete production.
Table A2 Sieve analysis of blended aggregate. 80% passing 19mm sieve openin.? and 20% [4-IO]nun.
a) Sample 1
Sieve 1427.100
1064.5
1193.5
90-100
with
Mass 100
59.12
1194.9
1202 -Aggregate
0-10
40.9
140.9
0.48
22.61989.8
190-l.3
36.53
20-55
100.0
36.1
1634.9
63.5
0.48
99.5
sieve -9.4
440
796.3
427.1
1073.9
Retained
Mass
[%]
[%]
[%] 0Mass
retained
0ASTM
ofRetained
702.3of sieveof
Coarser
[g]
[g]
Percentage
requirement
Passing
Percentage [C33-78]
[g] [%]
L: = 1948
b) Sample 2
Sieve Masssieve
1427.1
with100.0
36.73
1193.5
90-100
39.88
00
60.12
1194.9
1064.5
1202
100
Mass -723.4
20-55
63.3
0.0
2003.4
39.9-Retained
1Passing
23.39
1925.4
35.62
1.10
0-10 427.1
809.9
1669.8
1086.9
1.10
98.9
retained
[g] 0of
47-l.9
22.4
Coarser
retained
of
ASTM
Mass
Aggregate
Ig]
requirement
Percentage
Percentage sieveof
[g]
L: = 2030.6
The blended aggregates satisfy ASTM standard C33-78 for 19 to 4.75mm aggregates and used for subsequent
concrete production.
Table A3: Sieve analysis of blended aggregate, 90% passing 37.5nun sieve opening and 10% [4-IO]mm.
a) Sample 1
Sieve Masssieve
Mass
1195.1
1427.0
1064.6
1193.6
1202.8
with 0.9-of
-885.3
100.0
10-30
35-70
99.1
29.6
83.0
2408.8
0-5
2312.3
1091.9
69.7
30.3
1556.4
70.9
40.6
1685.8
16.1
12.1
1088.3
1190.80.9
95-100
0.0
99.3
0.7
0.7
29.1
17.0ASTM
0.0of sieveof
1215.2
-l83.0
361.3
27.3
1088.3
1212.7
0.0 21.9
0.0
Retained
Mass
retained
Coarser
retained
Aggregate
Percentage
requirement
[g]
[%][%]
Passing
[g]
[gl
[%]
Percentage
[%] [C33-78]
L: = 2994.0
b) Sample 2
Sieve 1195.1
1427.0
1193.6
Mass
with
[~]2629.7
24.0
72.5
75.4
1202.8 -364.4
10-30
84.7
99.4
0-5
95-100
0.0
0.6
99.4
35-70
Mass
1064.647.9
27.5-of
2144.8
24.6
1436.1
12.2
sieve
retained
1088.3
100.0
0.0
1088.3
1190.8
1209.7
0.6
I~]717.8
1081.5
1644.1
1559.5
14.7
15.3
0.6 of
441.3
0.0
16.9
Coarser
ASTMsieveof
Retained
0.0
18.9
Mass
retained
Aggregate
requirement
Percentage
[%)
[%)
[%)
[%]
[g)
Percentage
Passing [C33-78]
L = 2995.4
The blended aggregates satisfy ASTM standard C33-78 for 37.5 to 4.75mm aggregates and used for subsequent
concrete production.
Table A4: Sieve analysis of blended aggregate, 80% passing 12.5mm sieve opening and 20% [4-IO)mm.
) Samole 1
Sieve 100
578.3
425.5
Mass -1278.9
94.73
60.65
586.0100
5.28
5.27
34.08
34.08
65.92
with
sieve
Mass [~I
Retained
0Percentage
90-100
597.0 ASTM
40-70
1792.0
0-15
[5Aggregate
Coarser
[%)
[~) 0Retained
1213.7
105.4
30.4
of
586.0
Percentage
[%] ~) Mass
of sieveof
681.9
retained
Percentage
requirement
Passing
[%][%) [C33-78)
L = 2001.0
b) S
Sieve - - retained
100
with -Mass
Mass
Mass
Retained
sIeve
597.0Coarser
90-100
100
578.3
425.5
33.53
94.58
66.47
61.05
586.0
[~)0-15
40-70
5.42
5.42of
ASTM
1268.1
1222.1
108.4
671.1
586.0
[~I
Percentageof sieveof
Retained
180(1.4
5Aggregate
33.9
requirement
Percentage
Percentage
Passing
[%)
[%)
[%)
[g) [C33-78)
L = 2001.6
The aggregates grading satisfy ASTM standard C33-78 for 12.5 to 4.75mm aggregate and used for subsequent
concrete production.