Вы находитесь на странице: 1из 4

feature energy saving

An introduction to energy
consumption in pumps
Saving energy is such a big topic it’s sometimes hard to know where to start. In this first
article in a planned series on energy savings in pumps, Hans Vogelesang, director of design
consultancy PumpSupport in the Netherlands, looks at the important facts and reveals
where the first savings can be achieved when determining targets.

T
here are several reasons an overcapacity of 20–30%. It has Pump manufacturers’
why one should try to save been calculated that the energy role
as much energy as possible. wasted by all the pumps operating
Of course, any saved energy means at present in the EC is 46 TWh As a socially responsible or-
a direct saving in costs, but energy on a yearly basis. What does this ganization, Europump pays a lot of
saving also contributes significantly mean? The biggest power station attention to the saving of energy with
to the improvement of our within the Netherlands is the pumps. Of course the associated pump
environment. Eemscentrale in Delfzijl, with a manufacturers are doing their best to
generating capacity of 2400 MW. develop new pumps with a higher
A study by Dena (Deutsche Energie- Even when operating 365 days efficiency rate. But in many cases
Agentur GmbH), a German energy per year, 24 hours per day at full it turns out that the largest energy
agency, revealed that in the year 2000 capacity, the electricity production saving can be achieved by simply
industry in the European Community of this station would not amount to improving the installation design.
(EC) consumed 951 TWh of energy more than 21 TWh per year. So, the With this in mind, in 2006 Europump
(1 TWh = 1 000 000 MWh) in equivalent of more than two large compiled a guide for designers of
total. About 65% of this energy was or several smaller power stations pump systems called System Efficiency.
consumed by machines driven by permanently operating are needed By following the guidelines it is
electric motors, many of which were just to generate all the energy that possible for designers to increase
pumps. is wasted by pumps in Europe. the efficiency of both their existing
pumps and future models. In many
What this represents is an enormous cases this can also lead to a considera
potential saving. Moreover, it shows ble reduction in maintenance, killing
What can be achieved?
that if designers were to make more two birds with one stone.
Centrifugal pumps account for 80% pumps more energy efficient we
of all pumps and it is a known fact would immediately need fewer power
that most centrifugal pumps have stations. Need we mention Kyoto? “If designers made
Figure 1. Example pumps more energy
A: the geodetic
When using tanks under
differential head
consists of the vertical atmospheric conditions, make efficient we would
difference in height sure that the size of their vent Ptp
between liquid openings is large enough. immediately need
surfaces in the suction
and discharge tanks.
Discharge tank fewer power stations.”
Pts
Suction tank
Hgeo
Hd - Hs Where should we start?
Pumps are usually used to make
fluids flow through pipes by an
∆p
ps pd Hd increase in pressure. This is mostly
Hs
the case when we want to transport
fluids in storage or in production
systems from one place to another. It
is also often the case when we want
to transfer heat through cooling or

28 0262 1762/08 © 2008 Elsevier Ltd. All rights reserved WORLD PUMPS January 2008
feature energy saving

heating systems, using circulating When we take a look at a typical In the case of centrifugal pumps,
water or oil as the carrier. system using examples A, B and C the differential pressure is usually
(Figures 1-3), we see that in each case referred to as the manometric (or
Of course, any such units need to meet the suction pressure can be calculated indicated) differential head Hman in
our requirements. They should be as follows: metres of liquid column. When we
neither too small nor too large. However, want to convert the difference in
what frequently happens with a pump ps = pts + Hsρg pressure to a comparable differential
that is big enough to meet requirements head, this can be done as follows:
is that we only use it part load. In where ps and pts, the pressure at the
general, the output is then much lower suction tank, are in N/m2 (1 bar = 105 Hman = ∆p/ρg = [(ptd – pts) + Hgeoρg]/ρg
than under design conditions, resulting N/m2); height Hs is in m, ρ, the density
in the consumption of an unnecessary of the fluid, in kg/m3; and g, gravitational = Hgeo + (ptd – pts)/ρg
amount of energy. Therefore, it is of acceleration, is 9.81 m/s2.
the utmost importance to determine To provide the pressure/differential
as accurately as possible the demands a The discharge pressure is calculated head at a particular capacity the pump
system has to meet on a daily basis. Once similarly: requires power, which we can calculate
this has been established, it will then be as follows:
possible to incorporate the resulting pd = ptd + Hdρg
design data into the specification P = (Q×∆p)/36ηpump
demands. The designer can then devise It is then possible to calculate the
the best system. difference in pressure the pump has where the power to the shaft P is measured
to deliver as follows: in kW; capacity Q in m3/h; ∆p in bar; and
The design specifications for a pump pump efficiency ηpump in %/100.
system mainly comprise the two ∆p = ptp + Hdρg – pts – Hsρg = (ptd – pts)
most important demands: capacity + (Hd – Hs)ρg In this case, the electrical power taken
and differential head. Generally it from the electricity supply is:
is not difficult to determine design In the calculation, (Hd – Hs) is the
capacity. But this is obviously not the vertical difference in height that has
Pelec = Q×∆p/(36ηpumpηtransηmotor)
case with differential head, because to be bridged between the two fluid
this will depend on many factors. levels. This is known as the geodetic
where ηpump, ηtrans and ηmotor are,
The required differential head partly (or static) differential head and is
respectively, the efficiency (in %/100)
depends on the counterpressure and usually denoted as Hgeo.
of the pump, the transmission (flexible
the vertical differences in height
transmission, belt transmission, flexible
you want to bridge, but will also The difference in pressure to be
coupling, etc) and the electric motor.
be affected by friction losses in the delivered by the pump is determined
piping system. Because friction losses by the differences in pressure in the
can be of great significance, we will two reservoirs and by the geodetic Let’s take an easy calculation as an
return to this subject extensively in differential head, and can be calculated example. A pump with a capacity of
the next article. using the following formula: 100 m3/h, a difference in pressure of
1 bar and an efficiency of 75% will
∆p = (ptd – pts) + Hgeoρg require an output at the pump shaft of
(100×1)/(36×0.75) = 3.7 kW.
Energy consumption
Figure 2. Example
The differential head that the B: here the geodetic
Ptp
pump has to bridge, not taking differential head
is higher than in
into account the flow losses Discharge tank
example A.
within the system, consists of the
Suction tank Pts
counterpressure and the vertical
difference in height. A pump will Hgeo
always have to bridge the difference Hd - Hs
between the lower suction-side
pressure ps and the higher discharge-
side pressure pd (see, for example, ps
∆p pd
Figure 1). So, ignoring flow losses, Hd
Hs
the pressure difference ∆p across the
pump is:

∆p = pd – ps

WORLD PUMPS January 2008 www.worldpumps.com 29


feature energy saving

In such cases, you should always


Ptp
ensure that the air in both tanks can
flow in and out freely through the
Discharge tank vent openings. If the passages are
Pts too small, an underpressure in the
Suction tank
Hgeo suction tank and/or an overpressure
Hd - Hs in the discharge tank can still build
up. This is a potentially dangerous
situation, as well as an unfavourable
∆p pd one as far as energy consumption is
ps
Hs
Hd concerned.

Another important issue is the


geodetic differential head. Let us
look again at examples A, B and
Figure 3. Example C: because of siphon action, the geodetic differential head is similar to C. The fluid levels in the tanks are
that in example A. similar in all three cases. Example A
(Figure 1) is the simplest situation.
If we set the efficiency of the transmission • the pump capacity Q as low as Here, the geodetic differential head
and the electric drive at 90%, then the possible is equal to the vertical difference in
power taken from the grid is 3.7/0.9 = ca. • the differential pressure of the height between the fluid levels in
4 kW. So, for every operating hour this pump ∆p as low as possible the suction and discharge tanks.
pump will cost us ca. 4 kWh. For a pump • the efficiency rates of the pump,
with a capacity of 50 m3/h at a difference transmission and drive all as high In example B (Figure 2) the pipe
in pressure of 1 bar this will be 2 kW and as possible. to the discharge tank is connected
2 kWh, respectively. to the top of the tank. The fluid is
Pump capacity pumped to this level after which
Note, when pumping a particular The pump capacity chosen should it pours down freely into the tank.
quantity it should be realized that this never be unnecessarily high. As Here, the geodetic differential head is
will always take a certain amount of we saw in the example above, the unnecessarily higher than in example
energy, regardless of the pump’s capacity, choice of pump capacity does not A and the system will needlessly
as the following example demonstrates. affect energy consumption when consume a lot more energy. This
transporting a particular quantity. situation must be avoided!
We want to pump 100 m3 at a difference Although with a lower pump
in pressure of 1 bar. If there is a pump capacity the engine power is lower,
available with a capacity of 100 m3/h, the pump will operate longer. So the
the pump will operate for 1 hour, have total amount of energy consumed “In order to design an
a power uptake of approximately 4 kW remains the same. However,
and therefore use approximately 4 kWh reduction of the pump capacity is energy-efficient system,
of electricity in total from the grid. But important with closed systems such
in the case of a pump with a capacity as heating and cooling systems. determine in advance
of only 50 m3/h, the power uptake will When a lesser amount of liquid with
only be approximately 2 kW. For every a higher difference in temperature is
what you want to
hour the pump operates it will consume circulated in these systems, less pump achieve.”
approximately 2 kW, but in order to energy will be required. Moreover,
pump the full 100 m3 this pump actually such circulation systems are often in
has to operate for two hours. The total continuous operation. It is possible
power used will therefore always remain to save many hours worth of energy In example C (Figure 3) the
approximately 4 kWh, regardless of the during the time these pumps are situation is a little more favourable
pump’s capacity. operating, simply by reducing the because the pipe into the discharge
chosen pump capacity. tank extends right down to the
bottom. Siphon action ensures that
the geodetic differential head is
Reduction of energy
Differential pressure now very similar to that in example
consumption
With identical pressure in both tanks A. However, this model is extra
If we look again at the formula used there is no pressure difference for vulnerable to malfunction because
to calculate the uptake of electrical the pump to overcome. In fact, this of the high point in the pipe line
power, when trying to reduce energy is often the case because we usually where air can collect. This situation
consumption we should always aim to work with open tanks at atmospheric should also be avoided as much as
keep: pressure. possible.

30 www.worldpumps.com WORLD PUMPS January 2008


feature energy saving

Optimize efficiencies that are specifically designed for the Conclusions


The efficiency rates of the pump, duty. This can be done by calculating In order to design an energy-
transmission and drive should what will happen in various efficient system it is necessary to
all be kept as high as possible. operational circumstances. Bear in determine in advance what you
This is a simple guideline but in mind that it does not pay to design want to achieve. When pumping
practice it can be difficult to make a system with the best efficiency at a particular volume, the choice of
the best choices. The efficiency design conditions if the system is the pump capacity does not make
of transmission elements such as only rarely going to be used under that much difference to the energy
flexible couplings, belt drives, etc. is these conditions. If, for instance, consumption. Although with a
of course always quite high regardless a heating system is designed for a smaller pump capacity the energy
of load. However, the situation is maximum outside temperature of consumption per hour will be lower,
more complicated when it comes to –10°C, these design conditions it will mean operating for longer.
electro-motors and pumps. When will only occur sporadically. It is However, in the case of circulation
striving for energy savings you will worthwhile determining what the systems it is actually possible to
of course want to purchase highly most common operating conditions reduce the energy consumption by
efficient pumps and electro-motors, will be at an average load profile over choosing a smaller pump capacity.
but the efficiency rate will depend the course of the year. If you then
largely on the load. design a system so that it operates To reduce energy consumption it is
most efficiently at that capacity, you also important to keep the differences
In addition to selecting your system will be certain of benefiting from a in pressure as low as possible in your
carefully, it is extremely important higher efficiency rate over a long design. Do not forget that, for a
to choose and use pumps and drives period of time. difference in pressure of 1 bar, you
will need 4 kWh of energy for each
pumped 100 m3 of fluid. So, if you
can limit the difference in pressure to
no more than 0.5 bar, you will have
reduced the energy consumption by
50% to only 2 kWh.

In order to come up with accurate


specifications for the most energy-
efficient design, with a pump with
the lowest possible capacity and
differential head, the operating
demands over a whole year should
be taken into account. These will
indicate under which circumstances
the system generally operates, so
that a system can be designed that
operates optimally under those
conditions. ■

CONTACT
Hans Vogelesang
PumpSupport (NL)
Charley Tooropstraat 38
3343 RE Hendrik Ido Ambacht
The Netherlands
Tel: +31 78 682 0602
Fax: +31 78 682 1833
E-mail: info@pumpsupport.nl
www.pumpsupport.nl

About the author


Hans Vogelesang is director of
PumpSupport, an independent
consultancy for the design of pump
systems in Hendrik Ido Ambacht, The
Netherlands. He is also a lecturer
in pump engineering at several
educational institutes.

This article was originally published in


Figure 4. Europump’s System Efficiency guide has been compiled for designers of pump Dutch in Fluids Processing Benelux.
systems. For more information please refer to www.pumpsupport.nl.

WORLD PUMPS January 2008 www.worldpumps.com 31

Вам также может понравиться