Safety Limits Stops on Safety Limit: Stops on Safety Limit: Stops on Safety Limit: Stops on Safety Limit: Stops on Safety Limit:
2 1 or 2 2 1 2
Refer to “Analyzing Safety Limits” to
eliminate all non refrigeration problems
Freeze Cycle
Discharge Pressure If discharge pressure is High or Low refer to freeze cycle high or low discharge pressure problem checklist
______ ________ ________
and eliminate problems and/or components not listed on this table before proceeding.
1 minute Middle End
into cycle
Freeze Cycle If suction pressure is High or Low refer to freeze cycle high or low suction pressure problem checklist
Suction Pressure and eliminate problems and/or components not listed on this table before proceeding.
______ ________ ________ Suction pressure is Suction pressure is Suction pressure is Suction pressure is Suction pressure is
1 minute Middle End High Low or Normal Normal or High High High
Harvest Valve Temperature One harvest valve inlet is All harvest valve inlets are All harvest valve inlets are All harvest valve inlets are All harvest valve inlets are
Hot Cool enough to hold Cool enough to hold Cool enough to hold Cool enough to hold
Wait 5 minutes into the freeze cycle.
-and- and and- and- and-
Compare temperatures of compressor
approaches the temperature the compressor discharge the compressor discharge the compressor discharge the compressor discharge
discharge line and harvest valve inlets.
of a Hot compressor line is Hot. line is Cool line is Hot. line is Cool
discharge line. enough to hold hand on. enough to hold hand on.
Discharge Line Temperature Discharge line
Record freeze cycle discharge line Discharge line temperature Discharge line temperature Discharge line temperature Discharge line temperature less than
temperature at the end of the freeze cycle 150°F (65°C) 150°F (65°C) less than temperature 150°F (65°C) 150°F (65°C) at the end
or higher at the end of the or higher at the end of the 150°F (65°C) at the end of or higher at the end of of the freeze cycle
freeze cycle freeze cycle the freeze cycle the freeze cycle or
or Compressor shell is
_________°F (°C) Compressor shell is frosted
frosted
Evaporator Outlet Evaporator outlet Evaporator outlet Evaporator outlet Evaporator outlet Evaporator outlet
temperatures are temperatures are temperatures are temperatures are temperatures are
Temperature Comparison within 10°F of each other within 10°F of each other
NOT within NOT within within 10°F of each other
Attach and insulate temperature probes 10°F of each other 10°F of each other
between evaporator outlet and 90° elbow
or
Within 10°F of each other
and above 32°F
Final Analysis Low On Charge
Harvest Pressure Valve
Enter total number of boxes checked in Harvest Valve Leaking -Or- TXV Flooding Compressor
Leaking
each column. TXV Starving