AQSN SCROLL

Air cooled chillers and heat pumps with scroll compressors


Air cooled chillers and heat pumps with scroll compressors AQS

Air cooled chillers and heat pumps with scroll compressors

The new AQS series is a range of units for outdoor installation which are ideal for low-to-medium power air-conditioning systems
and particularly suitable for installations with limited water content, suitable for the production of chilled water and also hot water for
both space heating and sanitary purposes. Thanks to the innovative QuickMind control, the AQS system has been designed to work on
plants with a low water content where, unlike traditional controls, it minimizes the variations in inlet water temperature even in extremely
variable load conditions.The range is equipped with hermetic rotary Scroll compressors, ozone-friendly refrigerant R410A, axial-flow
fans, copper tubes aluminum fins coil and thermal expansion valve.

Flexible Scroll Compressor Maximum Reliability

● High efficiency scroll compressor with Unit with multi-circuit chilling section
low operation noise (two to four, depending on the size)
● Complete with an oil sump heater, designed to ensure maximum efficiency
electronic overheating protection with both at full load and part loads, assuring
centralized manual reset and a two- uninterrupted service in the event one of
pole electric motor. the two circuits fails.
● High part-load efficiency, low start-up The number of compressors
electrical current. also ensures a precise multi-step
● The scroll compressor has been expressly redesigned for use management of the cooling and heating
with the new gas and is now even more compact and silent capacity provided by each unit.
than before.

Ecological Refrigerant HFC410A Energy efficient

● Ecological gas HFC410A, no damage ● H i g h e ff i c i e n c y p a r t s i n c l u d i n g


to the ozone layer (ODP = 0) compressor, heat exchanger, refrigerant
● Thanks to its outstanding heat ● AQS units stand out for their particularly
conductivity, R410A contributes high energy efficiency index. This
towards achieving elevated system result was achieved by focusing on the
efficiency. design of both the finned condenser
● Reduces electricity consumption and coils and the evaporators.
consequently CO2 emissions. ● These construction choices have
● Refrigerant with less, reducing the both increased efficiency and provided extremely high levels of
greenhouse effect reliability while significantly increasing compressor working life.
● Excellent part load efficiency ESEER

Complete Versatility Silent Version

● AQS/N: cooling only or heat pump ● LN: low noise performances,


standard achieved by means of compressor
● AQS/N-D/R: complete with partial (D) soundproofing enclosure, reduced
or total (R) recovery configurations. fan speed and enhanced exchanger
● Noise version: B (base), LN (silent), surface on the coil's side.
HT (high temperature), HL (silent high ● SL: very low noise performances,
temperature) and SL (super silent) obtained with compressor enclosure,
versions. further reduction of the fan speed plus
increase of the coil's exchanger surface.

Innovative Fan Management System Integrated Hydronic Module (optional)

Climaveneta has designed a new The hydronic kit has been carefully
system to manage the condensing fans designed according to the various
with a complete new structure of the applications possible throughout the
ventilation section (patent pending). wide capacity range of AQS units.
This ensures outstanding performance On all versions we can select single
in terms of efficiency in all the operating or twin pumps suitable for low and high
conditions, thanks to: pressure according to the installation
● Elimination of the reciprocal needs.
dependency on adjacent circuits Automatic pump rotation system is available in the event of
● Ability to manage independent defrost cycles at different a breakdown without interrupting operation (only in units with a
times in different circuits twin pump).
● A more accurate fan speed management and, consequently,
a lower power consumption.

1
Air cooled chillers and heat pumps with scroll compressors AQS

requirements without needless compressor cycles or power


Control and Operation Management
absorption peaks. The unit pumps are intelligently managed.
W3000 advanced microcomputer intelligent control The number of hours of operation is balanced for more
system, built-in specially designed production Climaveneta efficient maintenance.
algorithm, a more prominent and reliability of energy-saving Resource priority assignment gives precedence to the unit with
units: FIFO compressor run time equalization to extend the greater efficiency: such as chillers with free-cooling function. The
life of outstanding units. Automatically adjust the output load, stand-by mode grants response to possible peaks in load.
energy saving. Adjust the operating parameters and settings, The elevated characteristics offered by the serial interface
to adapt to different environments. Protection more extended keypad are the highest currently available in the market.
components, increasing long-range and group control function.
W3000 is a special control which monitors the main Gr2000 Gr2000
operating parameters of the system, predicts the behaviour of
the plant and anticipates the units settings in order to constantly
optimise its performance.
● optimises plant operation
● minimises discharge line temperature oscillations
compared with the set point
● allows either return or delivery water temperatures to be
set as adjustment parameters.
● optimises compressor operation in the event of reduced loads
FWS Internet web server
● stores 200 alarm events; these can be downloaded to any
personal computer. Microcomputer intelligent controller can be equipped with
● detects and reports a large series of events such as: Climaveneta FWS web server, via LAN or Internet network
insufficient water content in the plant; low/high water flow in the monitoring, parameter setting and adjustment and control of
plant; low/high inlet water temperature; pump and compressor plant operation.
maintenance times; refrigerant circuit integrity alarm.
W3000 is also suitable for: interface connection with BMS
systems; interface connection with the Climaveneta Supervision
Software; remote control of the unit by modem (fixed/GSM);
control from a remote keyboard.

FWS Internet web server


A group composed of various hydronic units permits better
management for the lowest running cost.
Coordinating the units for optimized operating times
assumes fundamental importance and provides significant
advantages in terms of reliability (e.g. the compressors) while
also permitting energy savings and delivering water flows
constantly at the right temperature without fluctuation.
Resources are always used according to the user's

Electronic control features


Microprocessor W3000 Microprocessor W3000

Mufti-language menu √ Local/Remote supervision through browser and FWS OPT

Phase sequency relay √ Communication protocol OPT

Cumulative fault alarm √ Metasys Johnson Controls communication gateway OPT

Alarms log function √ Modbus communication protocol OPT

Black-Box function for alarm events √ Bacnet communication protocol OPT

Programming of daily/weekly program Par. Interface connection to Lon Works network OPT

Evaporator inlet/outlet water temperature display √ Siemens communication gateway OPT

Compressor/circuit failure display √ Remote on/off with external volt-free contact √

General unit alarms display √ Double set-point by external contact OPT

Quick Mind when stopped √ Set-point regulation from external signal (4-20 mA) OPT

Pump-down when stopped √ Continuous regulation of the compressors √

Starting compressors sequency control √ Relay manage pump OPT

Management of the compressors working hours √ Reduced load functioning from external contact OPT

Remote keyboard OPT Connection to sequencier OPT

√ Standard OPT Available on request Par. Available modifying a value of the configuration parameters

2
General Technical Data Standard
AQS

Air cooled chillers and heat pumps with scroll compressors


Model 0152 0182 0202 0252 0302 0352 0412 0452 0512 0552 0612 0704 0804 0904 1004 1104 1204 1355 1506 1656 1806

Performance
Cooling capacity (1) kW 41.1 49.2 54.5 62.7 82.1 93.8 104.7 121.3 136.8 156.5 171.3 190.6 215.9 241.2 275.6 316.7 357.2 384.1 405.6 468.7 528.0
Power input (1) kW 13.4 15.3 18.1 21.6 26.3 30.4 34.8 37.7 41.2 48.1 56.1 59.3 66.5 76.0 81.6 94.6 108.6 118.8 128.9 141.4 166.4
AQS
Evaporator water flow (1) m³/h 7.1 8.5 9.4 10.8 14.1 16.1 18.0 20.9 23.5 26.9 29.5 32.8 37.1 41.5 47.4 54.5 61.4 66.1 69.8 80.6 90.8
Evaporator water pressure drop (1) kPa 67.3 62.3 54.0 49.6 66.5 67.7 70.5 70.1 75.7 89.8 94.5 81.9 89.8 96.6 96.5 76.3 80.8 48.4 54.0 55.9 70.9
Cooling capacity (1) kW 42.7 51.1 56.6 65.1 85.2 97.3 108.6 125.9 141.9 162.4 177.7 197.8 224.0 250.3 285.9 328.6 370.6 398.5 420.8 486.3 547.8
Power input (1) kW 12.9 14.8 17.4 20.8 25.4 29.3 33.6 36.4 39.8 46.5 54.2 57.2 64.2 73.3 78.7 91.3 104.8 114.7 124.4 136.5 160.6
Evaporator water flow (1) m³/h 7.3 8.8 9.7 11.2 14.6 16.7 18.7 21.6 24.4 27.9 30.6 34.0 38.5 43.0 49.2 56.5 63.7 68.5 72.4 83.6 94.2
AQS-D Evaporator water pressure drop (1) kPa 72.5 67.0 58.1 53.3 71.6 72.9 75.9 75.4 81.5 96.6 96.5 88.2 96.6 97.5 98.5 82.1 87.0 52.1 58.1 60.2 76.3
Partial heat recovery capacity (1)(3) kW 11.9 13.7 16.1 19.3 23.5 27.1 31.1 33.6 36.8 43.0 50.1 53.0 59.4 67.8 72.8 84.5 97.0 106.1 115.1 126.3 148.5
Partial heat recovery water flow (1)(3) m³/h 2.1 2.4 2.8 3.3 4.0 4.7 5.3 5.8 6.3 7.4 8.6 9.1 10.2 11.7 12.5 14.5 16.7 18.2 19.8 21.7 25.5
Partial heat recovery water pressure drop (1)(3) kPa 7.4 9.8 13.6 19.4 14.3 19.0 24.9 20.5 24.6 22.5 30.6 26.1 32.9 34.0 39.2 42.2 55.6 17.2 20.8 21.6 26.1
Cooling capacity (4) kW 195.3 220.1 249.3 278.9 318.0 365.7
Power input (4) kW 56.9 64.5 72.1 79.8 93.7 104.6
Evaporator water flow (4) m³/h 33.6 37.9 42.9 48.0 54.7 62.9
AQS-R Evaporator water pressure drop (4) kPa 59.2 59.3 59.6 59.8 62.2 65.3
Total heat recovery capacity (4) kW 248.7 280.7 317.1 353.9 406.1 464.0
Total heat recovery water flow (4) m³/h 42.8 48.3 54.5 60.9 69.9 79.8
3

Total heat recovery water pressure drop(4) kPa 96.1 96.5 96.4 96.4 96.5 96.5
Microprocessor W3000
Compressors
Number of compressors 2 2 2 2 2 2 2 2 2 2 2 4 4 4 4 4 4 5 6 6 6
Refrigerating circuit 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2
Capacity regulating 2 2 2 2 2 2 2 2 2 2 2 4 4 4 4 4 4 5 6 6 6
Fans
Number of fans n° 4 4 4 4 6 6 8 8 10 10 10 4 4 4 6 6 6 6 6 8 8
Wind m3/s 5.28 5.07 5.07 4.90 7.63 7.35 7.85 9.88 13.09 12.77 12.77 21.25 20.10 23.30 31.87 30.15 28.50 28.50 28.50 38.00 38.00
Fan power kW 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0
Refrigerant
R410A kg 4.7 6.8 7.2 7.7 10.9 11.4 14.9 15.5 21.0 21.5 22.3 32.0 41.0 47.0 49.0 63.0 78.0 60.0 65.0 75.0 80.0
Dimensions
Length mm 1695 1695 1695 1695 2195 2195 2745 2745 3245 3245 3245 3110 3110 4110 4110 4110 4110 3610 3610 4610 4610
Width mm 1120 1120 1120 1120 1120 1120 1120 1120 1120 1120 1120 2220 2220 2220 2220 2220 2220 2220 2220 2220 2220
Height mm 1420 1420 1420 1420 1420 1420 1420 1420 1620 1620 1620 2150 2150 2150 2150 2150 2150 2430 2430 2430 2430
Operating weight kg 380 410 420 430 630 660 740 800 980 970 980 1780 1890 2070 2220 2420 2570 2990 3140 3490 3550
Noise performance (5) dB(A) 63 63 63 63 63 64 64 64 64 64 64 67 68 68 68 68 68 69 70 70 73

Remarks:1. Chilled water (in/out) 12/7℃ 4. Total heat recovery (in/out) 40/45℃, evaporator water temperature (in/out) 12/7℃

AQS
2. Condensing air (in) 35℃ 5. The noise value measured at 1 meter from the chiller
3. Partial heat recovery (in/out) 40/45℃
General Technical Data
Standard

Air cooled chillers and heat pumps with scroll compressors


AQS-N
Model 0152 0182 0202 0252 0302 0352 0412 0452 0512 0552 0612 0704 0804 0904 1004 1104 1204 1355 1506 1656 1806
Performance

Cooling capacity (1) kW 39.6 44.9 51.7 62.7 77.8 89.1 101.4 115.2 130.1 150.0 165.6 182.4 207.7 232.1 264.0 304.8 341.9 370.8 392.9 454.2 517.7
Power input (1) kW 12.6 14.7 18.2 19.1 26.5 30.5 34.0 37.8 41.5 48.3 56.4 60.5 67.4 76.8 83.0 95.8 107.9 113.4 122.7 137.8 161.7
Evaporator water flow (1) m3/h 6.8 7.7 8.9 10.8 13.4 15.3 17.4 19.8 22.4 25.8 28.5 31.4 35.7 39.9 45.4 52.4 58.8 63.8 67.6 78.1 89.0
Evaporator water pressure drop (1) kPa 62.3 51.9 48.6 49.5 59.7 61.1 66.1 63.2 68.5 82.5 88.3 75.0 83.1 89.4 90.0 70.6 74.0 45.2 50.7 52.5 68.2
AQS-N
Heating capacity (2) kW 45.0 50.5 58.5 71.0 87.5 100.9 113.9 130.3 147.0 170.6 189.8 203.6 230.3 257.6 293.1 337.0 378.3 410.1 434.2 501.7 573.9
Power input (2) kW 13.2 14.6 17.1 19.9 24.6 28.3 31.9 35.9 39.8 46.3 51.9 56.4 63.7 71.4 79.4 92.4 103.7 112.8 119.2 137.6 155.7
Evaporator water flow (1) m3/h 7.7 8.7 10.1 12.2 15.1 17.4 19.6 22.4 25.3 29.3 32.6 35.0 39.6 44.3 50.4 58.0 65.1 70.5 74.7 86.3 98.7
Evaporator water pressure drop (1) kPa 80.6 65.5 62.2 63.5 75.6 78.5 83.4 80.8 87.5 90.0 90.1 93.4 90.1 90.2 90.3 86.3 90.6 55.2 61.9 64.0 83.8
Cooling capacity (1) kW 41.1 46.6 53.6 65.0 80.7 92.4 105.2 119.5 135.0 155.6 171.8 189.3 215.5 240.9 273.9 316.2 354.7 384.7 407.6 471.2 537.1
Power input (1) kW 12.1 14.1 17.5 18.4 25.6 29.4 32.8 36.5 40.0 46.7 54.4 58.4 65.0 74.1 80.1 92.4 104.1 109.4 118.4 133.0 156.0
Evaporator water flow (1) m3/h 7.1 8.0 9.2 11.2 13.9 15.9 18.1 20.6 23.2 26.8 29.6 32.6 37.1 41.4 47.1 54.4 61.0 66.2 70.1 81.0 92.4
AQS-N-D Evaporator water pressure drop (1) kPa 67.1 55.9 52.3 53.2 64.3 65.8 71.2 68.0 73.8 88.8 95.1 80.8 89.4 96.3 90.1 76.0 79.6 48.6 54.6 56.5 73.4
Partial heat recovery capacity (1)(3) kW 11.2 13.1 16.2 17.0 23.7 27.2 30.3 33.8 37.0 43.2 50.3 54.0 60.1 68.6 74.1 85.5 96.3 101.2 109.5 123.0 144.3
Partial heat recovery water flow 3
(1)(3) m /h 1.9 2.3 2.8 2.9 4.1 4.7 5.2 5.8 6.4 7.4 8.7 9.3 10.3 11.8 12.7 14.7 16.6 17.4 18.8 21.2 24.8
Partial heat recovery water pressure drop (1)(3) kPa 6.6 9.0 13.7 15.2 14.5 19.1 23.7 20.7 24.8 22.7 30.9 27.2 33.7 34.8 40.6 43.2 54.9 15.6 18.9 20.6 24.6
Cooling capacity (4) kW 39.1 45.8 54.7 62.4 82.4 105.6 133.7 176.2 189.9 213.5 241.8 270.6 308.5 348.3
Power input (4) kW 12.8 14.2 16.6 19.1 24.5 31.9 39.6 51.3 57.1 64.5 72.1 79.8 93.7 104.6
Evaporator water flow (4) m3/h 6.7 7.9 9.4 10.7 14.2 18.2 23.0 30.3 32.7 36.7 41.6 46.5 53.1 59.9
AQS-N-R Evaporator water pressure drop kPa 47.5 65.2 53.5 69.6 57.7 65.2 60.8
(4) 56.8 54.7 62.6 64.7 67.1 65.3 67.8
AQS-N-Q
4

Total heat recovery capacity (4) kW 51.1 59.1 70.3 80.3 105.4 135.5 171.0 224.5 243.6 274.1 309.6 345.6 396.6 446.6
Total heat recovery water flow (4) m3/h 8.8 10.2 12.1 13.8 18.1 23.3 29.4 38.6 41.9 47.1 53.3 59.4 68.2 76.8
Total heat recovery water pressure drop (4) kPa 81.2 90.8 88.4 90.5 93.0 90.2 94.3 90.9 90.0 90.1 90.1 90.5 90.0 90.5
Microprocessor W3000
Compressors
Number of compressors 2 2 2 2 2 2 2 2 2 2 2 4 4 4 4 4 4 5 6 6 6
Refrigerating circuit 1 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 2 2 2
Capacity regulating 2 2 2 2 2 2 2 2 2 2 2 4 4 4 4 4 4 5 6 6 6
Fans
Number of fans n° 4 4 4 6 6 6 8 8 10 10 10 4 4 4 6 6 6 8 8 10 10
Wind m3/s 5.15 5.15 5.15 7.73 7.73 7.51 10.39 10.05 13.25 12.98 12.98 20.72 19.48 22.92 31.08 29.22 27.64 38.96 38.96 48.70 48.70
Fan power kW 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 0.25 2.1 2.1 2.1 2.1 2.1 2.1 2.0 2.0 2.0 2.0
Refrigerant
R410A kg 8.7 9 9.4 12.9 13.3 18.2 19 19.5 28.5 35.8 36.5 38 51 56 57 72 98 90 95 105 110
Dimensions
Length mm 1695 1695 1695 2195 2195 2195 2745 2745 3245 3245 3245 3110 3110 4110 4110 4110 4110 4610 4610 5610 5610
Width mm 1120 1120 1120 1120 1120 1120 1120 1120 1120 1120 1120 2220 2220 2220 2220 2220 2220 2220 2220 2220 2220
Height mm 1420 1420 1420 1420 1420 1420 1420 1420 1620 1620 1620 2150 2150 2150 2150 2150 2150 2430 2430 2430 2430
Operating weight kg 410 420 430 510 640 700 790 860 970 1030 1040 1900 2080 2270 2410 2570 2730 3380 3550 4020 4090
Noise performance dB(A) 63 63 63 63 63 64 64 64 64 64 64 67 68 68 68 68 68 69 70 70 73

AQS
Remarks:1. Chilled water (in/out) 12/7℃ 4. Partial heat recovery (in/out) 40/45℃
2. Condensing air (in) 35℃ 5. Total heat recovery (in/out) 40/45℃, evaporator water temperature (in/out) 12/7℃
3. The noise value measured at 1 meter from the chiller
Air cooled chillers and heat pumps with scroll compressors AQS

AQS Electrical Data


Power 380/400V-3-50Hz

Voltage tolerance <±10%

Voltage unbalance <3%

Maximum values Fans


Compressor(each) Fans Total unit

Model n F.L.I. F.L.A. L.R.A. F.L.I. F.L.A. F.L.I. F.L.A. S.A.

(kW) (A) (A) (kW) (A) (kW) (A) (A)

0152 2 9.7 16.2 98 1 4.4 20.4 36.8 118.6

0182 2 11.4 19.6 142 1 4.4 23.8 43.6 166

0202 2 12.8 21.3 142 1 4.4 26.6 47 167.7

0252 2 14.7 24.5 147 1 4.4 30.4 53.4 175.9

0302 2 18.7 32.2 180 1.5 6.6 38.9 71 218.8

0352 2 18.7/25.7 32.2/42.3 180/215 1.5 6.6 45.9 81.1 253.8

0412 2 25.7 42.3 215 2 8.8 53.4 93.4 266.1

0452 2 25.7/32.2 42.3/54.4 215/260 2 8.8 59.9 105.5 311.1

0512 2 32.2 54.4 260 2.5 11 66.9 119.8 325.4

0552 2 32.2/38 54.4/61.9 260/320 2.5 11 72.7 127.3 385.4

0612 2 38 61.9 320 2.5 11 78.5 134.8 392.9

0704 4 18.7/25.7 32.2/42.3 180/215 8.4 15.2 97.2 164.2 336.9

0804 4 25.7 42.3 215 8.4 15.2 111.2 184.4 357.1

0904 4 25.7/32.2 42.3/54.4 215/260 8.4 15.2 124.2 208.6 414.2

1004 4 32.2 54.4 260 12.6 22.8 141.4 240.4 446

1104 4 32.2/38 54.4/61.9 260/320 12.6 22.8 153 255.4 513.5

1204 4 38 61.9 320 12.6 22.8 164.6 270.4 528.5

1355 5 32.2/38 54.4/61.9 260/320 12 24.6 184.6 311.6 569.7

1506 6 32.2 54.4 260 12 24.6 205.2 351 556.6

1656 6 32.2/38 54.4/61.9 260/320 16 32.8 226.6 381.7 639.8

1806 6 38 61.9 320 16 32.8 244 404.2 662.3

Remarks: All parameters are the maximum, only a professional engineer electrical wiring reference. Please refer to the specific design
of electrical specifications.

F. L. I. Maximum power input Electrical source: 400/3/50


F. L. A. Maximum current absorption Voltage tolerance: 10%
L. R. A. Locked rotor current for single compressor Maximum voltage unbalance: 3%
S.A. Maximum starting current

5
Air cooled chillers and heat pumps with scroll compressors AQS

AQS/N Electrical Data


Power 380/400V-3-50Hz

Voltage tolerance <±10%

Voltage unbalance <3%

Maximum values

Compressor(each) Fans Total unit

Model n F.L.I. F.L.A. L.R.A. F.L.I. F.L.A. F.L.I. F.L.A. S.A.

(kW) (A) (A) (kW) (A) (kW) (A) (A)

0152 2 9.7 16.2 98 1 4.4 20.4 36.8 118.6

0182 2 11.4 19.6 142 1 4.4 23.8 43.6 166

0202 2 12.8 21.3 142 1 4.4 26.6 47 167.7

0252 2 14.7 24.5 147 1.5 6.6 30.9 55.6 178.1

0302 2 18.7 32.2 180 1.5 6.6 38.9 71 218.8

0352 2 18.7/25.7 32.2/42.3 180/215 1.5 6.6 45.9 81.1 253.8

0412 2 25.7 42.3 215 2 8.8 53.4 93.4 266.1

0452 2 25.7/32.2 42.3/54.4 215/260 2 8.8 59.9 105.5 311.1

0512 2 32.2 54.4 260 2.5 11 66.9 119.8 325.4

0552 2 32.2/38 54.4/61.9 260/320 2.5 11 72.7 127.3 385.4

0612 2 38 61.9 320 2.5 11 78.5 134.8 392.9

0704 4 18.7/25.7 32.2/42.3 180/215 8.4 15.2 97.2 164.2 336.9

0804 4 25.7 42.3 215 8.4 15.2 111.2 184.4 357.1

0904 4 25.7/32.2 42.3/54.4 215/260 8.4 15.2 124.2 208.6 414.2

1004 4 32.2 54.4 260 12.6 22.8 141.4 240.4 446

1104 4 32.2/38 54.4/61.9 260/320 12.6 22.8 153 255.4 513.5

1204 4 38 61.9 320 12.6 22.8 164.6 270.4 528.5

1355 5 32.2/38 54.4/61.9 260/320 16 32.8 188.6 319.8 577.9

1506 6 32.2 54.4 260 16 32.8 209.2 359.2 564.8

1656 6 32.2/38 54.4/61.9 260/320 20 41 230.6 389.9 648

1806 6 38 61.9 320 20 41 248 412.4 670.5

Remarks: All parameters are the maximum, only a professional engineer electrical wiring reference. Please refer to the specific design
of electrical specifications.

F. L. I. Maximum power input Electrical source: 400/3/50


F. L. A. Maximum current absorption Voltage tolerance: 10%
L. R. A. Locked rotor current for single compressor Maximum voltage unbalance: 3%
S.A. Maximum starting current

6
Climaveneta Italy : Climaveneta Vietnam :
36061 Bassano del Grappa (Vicenza) Italia - Via Sarson 57/c 3rd Floor Mekong Tower, 235-241 Cong Hoa Str,Ward 13
Ph. +39/0424 509 500 (r.a.) - Fax. +39/0424 509 509 Tan Binh Dist,HCMC
Ph. +848 6262 9966 - Fax. +848 6262 9977
Climaveneta France :
3, Village d’Entreprises ZA de la Couronne des Pres Climaveneta Hongkong :
Avenue de la Mauldre 78680 Epone - France Room 2003, CCT Telecom Building, 11 Washing Street,
Ph. +01 30 95 19 19 6 - Fax. +01 30 95 18 18 Shatin-Hongkong, China
Ph. +85 226 871 755 - Fax. +85 268 730 78
Climaveneta Asia :
88 Bai yun Rd, Pudong Xinghuo New dev. zone 201419 Shanghai China Climaveneta UK LTD :
Ph. 008 621 575 055 66 - Fax. 008 621 575 057 97 Highlands Rood, Shirley, Solihull, Ewst Mildands B90 4NL
Ph. +44(0) 871 663 0664 - Fax. +44(0) 871 663 1664
Climaveneta Asia - Indonesia Representative:
Jln. Jl. Anggrek Neli Murni IIA Blok C 12A Slipi, Jakarta Barat 11480, Indonesia Climaveneta Polska Sp. zo. o.
Ph. +62 21 5482941 UI. Sienkiewicza 13A, 05-120 Legionowo, Poland
jktoffice@bukakainti.com Ph. +48 22 766 34 55-57 - Fax. +48 22 784 39 09

Perum Pondok Nirwana Blok CC 39B Surabaya 60298, Indonesia Climaveneta Espana-Top Clima :
Ph. +62 31 99004529 - Fax. +62 31 8784387 Londres 67, 1 4, 08036 Barcelona, Spain
sbyoffice@bukakainti.com Ph. +34 934 195 600 - Fax. +34 934 195 602

All specification and data are subject to change without notice B218 CCU/01-01-2011EN-SH