Assume all walls are light colored and roof is also light colored. Use
1. External Wall
Area, m2
CLTDadj:
2
Area, m
QSG
QTH
Qst = 5006.6928 W
1. Infiltration Load
QS = 1.232 Q (t_o-t_i)
QL = 3000 Q (W_o-W_i)
= 0.2585 change/hour
Wo = 0.01831168
Wi= (0.622Ps)/(101.325-Ps )
; Ps = P @ 26.2℃ = 3.171 kPa
Wi= 0.009887567
Qs =(1.232)(63.75750559)(34.5-25)
Qs = 746.2178454 W
QL = 1611.30102 W
2. Ventilation Load
Qs=1.232 (Q)(t0-ti )
L/s
Qs= (1.232)(89.68)(34.5-25)
Qs= 1049.61472 W
QL=2266.42298 W
Table 5
to,°C 34.5
ti, ,°C 25
Wo (kgwater/kgair) 0.01831168
Wi (kgwater/kgair) 0.009887567
Dt 9.5
Dw 0.008424113
Qs 1049.61472
QL 2266.42298
3. Lighting Load
Qs = (lamp rating)(area)(Fu)(FB)(CLF)
Qs = (24/m2)(261.1526)(1)(1.2)(0.85)
Qs=6393.0156 W
4. Occupant Load
QS = (70)(0.75)(38)(0.96)=1915.2 W
QL = (70)(0.25)(38)(1)=665 W
QST = 1915.2 W
QLT = 665 W
5. Miscellaneous Load
Table 6
Unit
No. of Q,
Equipment/Appliances Ratings, CLF
Units Utilization watts
W
1866.6
3 Water Heater 1500 4/24 1 7
Load Partition
Wall
QS = uA∆T
u = 2.249718785
Bedrooms to Hallway
A = 198.2 m2
∆T = 32ºC - 25 ºC = 7ºC
Qs = (2.249719785)(198.2 m2)(7 ºC)
Qs = 3121.259842W
Bedrooms to CR
A = 201.152
∆T = 30ºC - 25 ºC = 5ºC
Qs = (2.249718785)(201.152 m2)(5 ºC)
Qs = 2262.677165W
Partition Door
Bedrooms to hallway
QS = uA∆T
u = 1.8867924528
A = 26.88
∆T = 32℃-25℃=7℃
QS = 355.0060872 W
EXTERNAL HEAT LOAD CALCULATION FOR SECOND AND THIRD FLOOR
Assume all walls are light colored and roof is dark colored. Use positive
1. External Wall
Area, m2
N: (3.2)(3.58+3.4+3.4+4.45)(2)-(8)(1.2x1.5) = 80.512 m2
E: (3.2)(4.117+4.39)= 27.224 m2
W: (3.2)(4.117+4.39)= 27.224 m2
S: (3.2)(3.58+3.4+3.4+3.5)(2)-(8)(1.2x1.5) = 74.432 m2
CLTDadj
N: (13-0.55)(0.65)+(25-25)+(28.5-29) = 7.5925
E: (25-0.55)(0.65)+(25-25)+(28.5-29) = 15.3925
W: (33-0.55)(0.65)+(25-25)+(28.5-29) = 20.5925
S: (22-3.33)(0.65)+(25-25)+(28.5-29) = 11.6355
Qwall, W
QS = 6668.288599 W
3. Glass Load
2
Area, m
N: (8)(1.2x1.5) = 14.4m2
E: 0 m2
W: 0 m2
S: (8)(1.2x1.5) = 14.4m2
QTH, W
N: (5.9)(14.4m2)(34.5-25) = 807.12 W
E: 0 W
W: 0 W
S: (5.9)(14.4m2)(34.5-25) = 807.12 W
QTH =1614.24 W
QSG, W
N: (115)(14.4m2)(0.59)(0.91) = 889.1064 W
E: 0 W
W: 0 W
S: (355)(14.4m2)(0.59)(0.83) = 2503.3464 W
QSG = 3392.4528 W
1. Infiltration Load
QS = 1.232 Q (to-ti)
QL = 3000 Q (W o-W i)
Qs = 702.3226781 W
QL = 1516.51861 W
2. Ventilation Load
QS = 1.232 (Q)(to-ti)
QS = 1049.61472 W
QL = (3000)( 89.68 L/s)(0.018311679-0.009887567)
QL = 2266.422979 W
3. Lighting Load
QS = (lamp rating)(A(Fu)(FB)(CLF)
QS = (24W)()(261.1526 m2)(1)(1.2)(0.85)
QS = 6393.015648 W
4. Occupant Load
Bedrooms
QS = (70)(0.75)(38)(0.96)
Qs = 1915.2 W
QL = (70)(0.25)(38)(1)
QL = 665 W
6. Partition Load
Partition Wall
Office
QS = U(A)(∆T)
U = 2.249718785 kJ/kg*K
Bedrooms to Hallway
A = 167.744 m2
∆T= 32-25 = 7 ˚C
Qs = 2641.637795 W
Bedrooms to CR
A = 200.514 m2
∆T = 30-25 = 5℃
Qs = 2.249718785(200.514 m2)( 5˚C)
Qs = 2255.500562 W
QtWALL= 4897.138357 W
Partition Door
Office
QS = U(A)(∆T)
U = 1.8867924528 kJ/kg*K
Bedrooms to Hallway
A = 28.56 m2
∆T= 32-25 = 7 ˚C
Qs = 377.2075472W
Bedrooms to CR
A = 24.99 m2
∆T = 30-25 = 5℃
Qs = 1.8867924528 (24.99 m2)( 5˚C)
Qs = 235.754717 W
QtDOOR = 612.9622642
Qt = 5510.100621
QS = U(A)(∆T)
U = 2.042900919
A = 17.176 m2
∆T = 32-25 = 70C
Qs = 2.042900919 x 17.176 x 7
Qs = 245.6220633W
QS = uA∆T
u = 1.8867924528
A = 23.52 m^2
∆T = 30℃-25℃=5℃
QS = 221.8867924 W