Вы находитесь на странице: 1из 6

CONSTANT LOSS PRESSURE METHOD

Air volume required 6885 m3/h

Local type: 1 - Quiet, 2 - Commercial, 3 - Industrial: 1 Ap(mm.cda/m)=

Supply duct

Stretch Lenght Fitt. Volume Diameter Vel. lo


Initial End Mts Num. m3/h mm m/s mmcda/m
A B 2.54 1.00 3480.00 482 5.29 0.07
B C 1.0 1.00 2538 429 4.88 0.07
1.0 1.00 1903 378 4.70 0.07
1.0 1.00 1269 337 3.95 0.06
1.0 1.00 634 266 3.16 0.05
1.0 1.00 308 219 2.28 0.04

Return duct

Nº Orig. Lenght Fitt. Volume Diameter Vel. mmcda/m


A B 2.5 1.00 360 219 2.66 0.05
B C 1.0 1.00 288 219 2.13 0.03
C D 1.0 1.00 72 122 1.71 0.04
Total loss pressure mm.c.a.:

Most desfavorable stretch total loss pressure

Supply ductwork 6.02 mm.c.a


Diffuser 0.92 mm.c.a
Filter 6.12 mm.c.a
Weatherproof louvre 1.12 mm.c.a

Total

Total 139.0 Pa 14.2 mm.c.a

Return ductwork 1.25 mm.c.a


Grille 0.34 mm.c.a
Filter 5.10 mm.c.a
weatherproof cowling 0.00 mm.c.a

Volume Diameter Vel.


360 315 1.28

Total 65.7 Pa Total 6.7 mm.c.a

DIAGRAM
ESSURE METHOD

Ap(mm.cda/m)= 0.05

loss pressure mm.c.a Material


Per Fitt. Per Stretch Total Accumulated m2
2.17 0.17 2.35 2.35 15.35
1.84 0.07 1.90 4.25 13.7
1.70 0.07 1.77 6.02 12.1
1.18 0.06 1.24 4.92 10.8
0.74 0.05 0.80 3.81 8.6
0.38 0.04 0.41 2.45 7.1

Material total of suppy m2. 0.0

Per Fitt. Per Stretch Total Accumulated m2


0.52 0.12 0.64 0.64 7.1

0.33 0.03 0.36 1.00 7.1


0.21 0.04 0.25 1.25 4.0
Material total of return m2. 18.2

Supply and returt m2 18

% additional 20% 4

Total m2 21.8

Accumulated
supply system
total loss
pressure #REF!
mm.c.a
Accumulated return system total loss pressure 2.00
mm.c.a

AM