Академический Документы
Профессиональный Документы
Культура Документы
This specification is subject to change without notice. REVISED & PUBLISHED: 13 OCTOBER 2009 1
TECHNICAL DATA
Indirect Evaporative Air Conditioner Models CW-H10, CW-H15
Overall
Width: 1232 1828
Height 1610 1610
Length 1985 1985
Mounting Plinth
Width 1206 1800
Length 1300 1300
This specification is subject to change without notice. REVISED & PUBLISHED: 13 OCTOBER 2009 2
TECHNICAL DATA
Indirect Evaporative Air Conditioner Models CW-H10, CW-H15
PLEASE NOTE: TECHNICAL SPECIFICATIONS ARE PROVISIONAL AT OCTOBER 2009
Water supply 15mm BSP male connec- 15mm BSP male connec-
tion, min 100 kPa, max tion, min 100 kPa, max 800
800 kPa, 20 L/min kPa, 20 L/min
Drain valve SI Extra low voltage, vertical, electric drive 40mm BSP male 40 BSP male
Heat exchanger core SI Synthetic plate type, super efficient 2 cores 3 cores
This specification is subject to change without notice. REVISED & PUBLISHED: 13 OCTOBER 2009 3
TECHNICAL DATA
Indirect Evaporative Air Conditioner Models CW-H10, CW-H15
1985
1328
152
1232
499 or
499
1828
370 499
DRAIN IN FLOOR OF
TANK ‐ STANDARD
493 121 SEELEY DRAIN
VALVE 40MM
TOP VIEW 120
49
LIFTING POINTS
(SLINGS) 452
610
1610
308 & 606
914
515 806
667 20
244
This specification is subject to change without notice. REVISED & PUBLISHED: 13 OCTOBER 2009 4
TECHNICAL DATA
Indirect Evaporative Air Conditioner Models CW-H10, CW-H15
1 3 5 A1 bl
br bl
1 2 3 4 5 6 7
2 4 6 A2 br
FAN L1 L2 L3 N E
MAIN SUPPLY
This specification is subject to change without notice. REVISED & PUBLISHED: 13 OCTOBER 2009 5
LINES OF SUPPLY AIR TEMPERATURE
30
28
PSYCHROMETRIC 30 30
CHART
26
Normal Temperature
SI Units
PROVISIONAL 30
W
ET
BU 24
SEA LEVEL LB
BAROMETRIC PRESSURE: 101.325 kPa TE
TECHNICAL DATA
MP
E RA 22
TU
RE
-°
Lines of supply temperature for 25 C 25
20
14
DIRECT EVAP - Adelaide
20
Climate Wizard - supply air
temp - 15.6 deg C 12
%
90
15 15
%
25
10
8
% 0%
15
70
10 8
% CLIMATE WIZARD - Adelaide 10
60
HUMIDITY RATIO - GRAMS MOISTURE PER KILOGRAM DRY AIR
10 % %
50 15 6
6
20 26 32 38 44 50
INLET DRY BULB TEMPERATURE
TECHNICAL DATA
Indirect Evaporative Air Conditioner Models CW-H10, CW-H15
Tables of Nominal Cooling Effect for Climate Wizard in various locations and various jurisdictions,
WHEN USED AS STAND ALONE COOLERS:
NOMINAL COOLING EFFECT FOR NAMED CITIES ‐ KW
Tdb Twb Tdew Trm Ts CW‐H10 CW‐H15
deg C deg C deg C deg C deg C KW KW
Beijing 34.5 20.9 13.9 27 17 10 14
Birm'ghm 27 18.3 13.3 24 15 9 12
Cairo 37.6 22 14.3 27 17.5 9 13
Chicago 32.4 22.5 18.1 26.7 19 8 10
Dubai 42.8 23.8 14.5 27 17 10 14
Jo'berg 28.9 17.9 11.3 24 15 9 12
Madrid 35.9 18.7 7.5 27 14 13 18
Milan 33.9 22.8 17.9 24 19.5 4 6
Paris 32.3 20.6 14.6 24 16 8 11
Phoenix 43.4 20.4 5.5 26.7 15 12 16
This specification is subject to change without notice. REVISED & PUBLISHED: 13 OCTOBER 2009 7