CONTRACTOR : SUPPLIER
PROJECT :
ACS With Control & Protection Panel
for
Nicaragua ENATREL 138kV Substation & Transmission Line Project
DESIGNED BY DATE TITLE :
MAY. 2016.
LIST OF CONTENTS
1.0 Introduction.............................................................................................................1
3.0 References...............................................................................................................4
1.1 This protective relay setting calculation results will be applied to the protection and control panels
which are installed on the NICARAGUA ENATREL 138kV Substation & Transmission Line
Project.
1.2 The relay setting calculation was carried out in accordance with NICARAGUA power system data,
relay setting criteria and relay setting examples provided by ENATREL besides the technical
references listed in this report.
1.3 PCM current differential relay and communication assisted protection (POTT) scheme setting
calculations for 138kV transmission line protection need the technical data on the protective
equipment at the other ends of transmission line which is not currently available (CT ratios,
ZONE reach settings, etc.) Therefore, the relay settings must be reviewed with the related data or
settings before put these relays into operation.
1.4 For 138/24.9kV transformer neutral overcurrent element setting (51N on HV or LV winding
neutrals), transformer neutral currents on both 138kV bus and 24.9kV bus 1-phase-to-ground fault
is necessary. Therefore 51N settings should be reviewed when the fault current data is available.
1.5 Backup protection relays such as 51 or 51N require operating time coordination with neighboring
relays in the system. Operating time coordination for those relays, therefore, should be reviewed
and settings be changed, if necessary, when the related relay settings are available.
1.6 If the system configuration or equipment is changed, relay settings should be reviewed for
appropriateness.
-1-
2.0 Protective Relay List
2.1 EL SAUCE S/S
Protection and
Relay Type Protection Function Remarks
Control Panel
Protection and
Relay Type Protection Function Remarks
Control Panel
138/24.9kV
SEL-751A 51, 51N
TR. (20MVA)
Note 1 : As electrical data for 138kV MALPAISILLO line was not finalized yet, 138kV PENSA line data
was used for the relay setting calculation. (ENATREL`s request)
Note 2 : As no current will flow on these relays on the 138kV SEBACO T/L fault (Positive–sequence source
impedance of ESTELI S/S to SEBACO S/S is infinite),proper setting calculations for current
elements and distance elements are not possible. ( only 87L, 79, 50BF elements are enabled.)
-2-
2.3 OCOTAL S/S
Protection and
Relay Type Protection Function Remarks
Control Panel
Protection and
Relay Type Protection Function Remarks
Control Panel
138/24.9kV
SEL-751A 51, 51N
TR. (20MVA)
Protection and
Relay Type Protection Function Remarks
Control Panel
21/21N, 79(1 pole),
138kV SEL-421
25, 50BF
OCOTAL
T/L SEL-351A 51/51G
-3-
3.0 References
3.1 IEEE RED BOOK Std 141-1993 :
IEEE recommended practice for electric power distribution for industrial plants.
IEEE recommended practice for protection and coordination for industrial and commercial
power system.
-4-
4. Minimum Coordination Time
In general, coordination time margin of time–delayed relays required to have operating
selectivity between upstream relays and downstream relays in a power system can be calculated
as follows;
T margin = T T T T
Where;
T : Relay overtravel time (in case of induction disc type relays, taken as 100ms)
T : Safety margin including relay tolerance and setting errors (taken as 117ms)
Then;
For digital relays which have no overtravel time of 100ms, Coordination time margin can be
reduced to as low as 215ms
-5-
5.0 Relay Settings for EL SAUCE S/S
5.1 138/24.9kV TR. Protection (SEL-787)
5.1.1 Configuration
(a) Maximum Transformer Capacity (MVA)
- Range : OFF, 0.2-5000.0 MVA
MVA = 20 MVA
-IN = 83.68A
√
- CT ratio : 100-200 / 1A
- Selecting maximum CT ratio ;
CTR1 = 200
-IN = 463.75A
√ .
- CT ratio : 800-1600 / 5A
- Selecting 800/5 ratio ;
CTR2 = =160
CTR2 = 160
SLP1 = 20 %
-9-
5.1.3 Breaker Failure
(a) 52A Interlock in BF Logic (52ABF)
- Select : Y, N
52ABF = N
- 10 -
5.2 138/24.9kV TR. Protection (SEL-751A)
5.2.1 Main
(a) Phase (IA, IB, IC) CT RATIO (CTR)
- Range : 1 to 5000
- IN = 83.68
√
- CT ratio : 100-200/1 A
- Selecting maximum CT ratio ;
CTR = 200
51P1P = 0.63 A
- 11 -
on 24.9kV bus 3-phase fault.
Meltiples of pickup 4.25
.
TD 0.230
51P1TD = 0.23
51N1P = 0.33 A
TD = 0.800
51N1TD = 0.80
* 51N1TD setting should be reviewed and changed, if necessary, when fault current
data is available.
- 12 -
5.3 ELSAUCE S/S138kV CARLOS FONSECA LINE PROTECTION
(SEL-411L)
5.3.1 Line Configuration
(a) Current Transformer Ratio – Input W (CTRW)
- Range : 1 to 50000
- Line current capacity = 730 A
- CT ratio : 800 / 1600 – 1 A
- Selecting maximum CT ratio ;
CTRW = 1600
PTRY = 1380
PTRZ = 1380
- 13 -
Z1MAG 23.0032 26.6703
Z1MAG = 26.67 Ω
Z0MAG = 86.09Ω
(k) Enable Residual Ground Instantaneous / Definite – Time O/C Elements (E50G)
- Select : N, 1 - 4
- 15 -
- For backup ground directional O/C protection ;
E50G = 1
(c) Maximum Primary Current Rating for Remote Relay 1CT (87CTP1R)
- Range : 1 to 50000
- As CT primary nominal current for remote relay 1 is not given,
set to 1600A (same as that for local relay) temporarily.
87CTP1R = 1600 A
- 17 -
(f) Pickup value for Phase Differential Element (87LPP)
- Range : 0.10 to 2.00 (pu), OFF
- Setting criteria;
Set to T/L charging current with safety margin of 3, not to operate
on inrush charging current during energization.
87LLP 0.2916A/km 49.3705km 3 1600 0.0270 pu
For increased sensitivity, on internal 3-phase fault set to 20% of 3 phase fault
current on EL SAUCE S/S 138kV bus fault.
87LLP 3680 A 0.2 1/1600 0.46 pu
Set to full load current for security on CT open condition.
87LLP 730 A 1/1600 0.45 pu
87LPP = 0.46
XP2 = 40.11
- 20 -
XP3 = 60.16
XP4 =150.50
where :
M = per-unit reach of XG1
R = RG1
| | = positive – sequence T/L reactance
| | j22.3648 j25.9302
0.85 1 , R =77.790 Ω
.
- 23 -
Z2D 0.3 sec 60 18 cyc
Z2D = 18 cyc
- 24 -
(d) CLSMON or 1 Pole Open Delay (CLOEND)
- Range : 0.000 to 16000.000 (cyc), OFF
- Turn off CLOEND (CLSMON Delay) since this method is not used.
CLOEND = OFF
R1R7=69.24
- 26 -
116.44∠79.48°
Where;
.
Angle_R6 2 tan ≒2 tan 97.17°
.
.
Angle_R7 2 tan ≒2 tan 80.12°
.
- 27 -
√
50P1P = 0.68 A
50P2P=0.46A
- 28 -
(c) Level 2 Torque Control Equation (67P2TC)
- Range : SELogic
67P2TC = 1
- 30 -
(d) Echo Duration Time Delay (EDURD)
- Range : 0.000 to 16000.000 (cyc)
- Assuming a 3cycles circuit breaker at the remote terminal and
A 1-cycle channel delay;
EDURD = 4.000 cyc.
50FP1 = 0.27A.
- 31 -
(e) Breaker Failure initiate Seal-in Delay (BFISP1)
- Range : 0.000 to 1000.000 (cyc)
BFISP1 = 0.0 cyc.
- 32 -
(e) Breaker 1 Reclose Supervision Delay (BK1CLSD)
- Range : 1 to 99999 cyc.
- If circuit breaker 1 reclose supervision conditions fail to occur
within 300 cycles after the three-pole open interval time delay
expires BK1CLSD will assert, and the auto-reclose goes to lockout.
BK1CLSD = 300 cyc.
- 33 -
(k) Reclosing Voltage Check (EVCK)
- Select : Y, N
EVCK = Y
27LP = 11.5 V
59LP = 46.2 V
- 34 -
- Set to 90% of rated voltage
0.9 51.9
√
25VL = 51.9 V
25VH = 63.5 V
25SFBK1 = 0.021 Hz
- 35 -
(i) Maximum Angle Difference 2 (ANG2BK1)
- Range : 3.0 to 80.0 (deg.)
- Set ANG2BK1 to 20 degrees for manual closing of CB.
ANG2BK1 = 20 deg.
- 36 -
5.4 EL SAUCE S/S 138kV CARLOS FONSECA LINE PROTECTION
(SEL-421)
5.4.1 Line Configuration
(a) Current Transformer Ratio – Input W (CTRW)
- Range : 1 to 50000
- Line current capacity = 730 A
- CT ratio : 800 / 1600 – 1 A
- Selecting maximum CT ratio ;
CTRW = 1600
PTRY = 1380
PTRZ = 1380
- 37 -
1 23.0032 26.6703
Z1MAG = 26.67 Ω
Z0MAG = 86.09Ω
(i) Enable Residual Ground Instantaneous / Definite – Time O/C Elements (E50G)
- Select : N, 1 - 4
- For backup ground directional O/C protection ;
E50G = 1
- 39 -
(j) Enable Negative-Sequence Instantaneous / Definite – Time O/C Elements (E50Q)
- Select : N, 1 - 4
- To disable 67Q1T (Zone-1 OOS unblocking during unbalanced faults) ;
E50Q = N
- 40 -
(r) Enable Advanced Settings (EADVS)
- Select : Y, Y1, N
EADVS = N
Z2 ′2
Therefore, above Z2 setting is acceptable
XP2 34.592 40.106
XP2 = 40.11
XP4 =150.50
- 42 -
(h) Zone 4 Resistance (RP4)
- Range : 0.25 to 250.00 (ohms, sec)
- Same setting as RP3.
RP4 = 51.35
where :
M = per-unit reach of XG1
R = RG1
| | = positive – sequence T/L reactance
| | j22.3648 j25.9302
0.85 1 , R =77.790 Ω
.
- 43 -
- Appling a safety margin of 50% is recommended because single pole
Tripping is enabled.
RG1 0.5 77.790Ω 38.895
RG1=38.90
- 44 -
RG4=51.35
- 45 -
5.4.7 Switch-Onto-Fault Scheme
(a) Single-Pole Switch-Onto-Fault (ESPSTF)
- Single-pole tripping is applied and the ability to single-pole trip
When SOTF is enabled help improve transient power system stability
ESPSTF = Y
- 46 -
5.4.8 Out-of-step Reset Tripping/Blocking
(a) Block Zone1 (OOSB1)
- Select : Y, N
OOSB1 = Y
- 47 -
.
1 7 1 6 17.89 51.35 69.24
.
R1R7=69.24
116.44∠79.48°
Where;
.
Angle_R6 2 tan ≒2 tan 97.17°
.
.
Angle_R7 2 tan ≒2 tan 80.12°
.
- 48 -
. .
OSBD 0.568
° °
50P1P = 0.68 A
- 49 -
(c) Level 1 Torque Control Equation (67P1TC)
- Range : SELogic
67P1TC = F32P
50P2P = 0.46A
- 50 -
(b) Level 1 Time Delay (67G1D)
- Range : 0.000 to 16000.000 (cyc)
- According to ENATREL relay setting criteria;
67G1D = 90.000 cyc
- 51 -
(c) Three-Pole Open Dropout Delay (3POD)
- Range : 0.000 to 60.000 (cyc)
3POD = 0.5 cyc
- 52 -
Attachment 1 : Impedance Characteristics of Distance Protection elements and Out-of-step
- 53 -
5.5 EL SAUCE S/S 138kV MALPAISILLO LINE PROTECTION
(SEL-411L)
5.5.1 Line Configuration
(a) Current Transformer Ratio – Input W (CTRW)
- Range : 1 to 50000
- Line current capacity = 730 A
- CT ratio : 800 / 1600 – 1 A
- Selecting maximum CT ratio ;
CTRW = 1600
PTRY = 1380
PTRZ = 1380
- 54 -
1 35.7942 41.5005
Z1MAG = 41.50 Ω
Z0MAG = 154.42Ω
(k) Enable Residual Ground Instantaneous / Definite – Time O/C Elements (E50G)
- Select : N, 1 - 4
- 56 -
- For backup ground directional O/C protection ;
E50G = 1
(c) Maximum Primary Current Rating for Remote Relay 1CT (87CTP1R)
- Range : 1 to 50000
- As CT primary nominal current for remote relay 1 is not given,
set to 1600A (same as that for local relay) temporarily.
87CTP1R = 1600 A
- 58 -
(f) Pickup value for Phase Differential Element (87LPP)
- Range : 0.10 to 2.00 (pu), OFF
- Setting criteria;
Set to T/L charging current with safety margin of 3, not to operate
on inrush charging current during energization.
87LLP 0.2899A/km 76.3129km 3 1600 0.04148 pu
For increased sensitivity on internal 3-phase fault, set to 20% of 3 phase fault
current on EL SAUCE S/S 138kV bus fault.
87LLP 3680 A 0.2 1/1600 0.46 pu
Set to full load current for security on CT open condition.
87LLP 730 A 1/1600 0.45 p. u
87LPP = 0.46
Z2 ′2
Therefore, above Z2 setting is acceptable
XP2 41.8487 48.5202
XP2 = 48.52
XP4 =84.26
where :
M = per-unit reach of XG1
R = RG1
| | = positive – sequence T/L reactance
| | j34.8128 j40.3626
0.85 1 , R =121.088 Ω
.
- 63 -
- Same setting as RP2
RG2=33.02
- 64 -
(b) Zone2 Time Delay (Z2D)
- Range : 0.000 to 16000.000(cyc), OFF
- According to the ENATREL relay setting criteria;
Z2D 0.3 sec 60 18 cyc
Z2D = 18 cyc
- 65 -
(c) 52A Pole Open Time Delay (52AEND)
- Range : 0.000 to 16000.000 (cyc), OFF
- Select the 52A option and set the delay (52AEND) shorter
than the reclose open interval.
52AEND = 10.000 cyc
- 66 -
(d) Block Zone4 (OOSB4)
- Select : Y, N
OOSB4 = N
R1R7=73.18
- 67 -
X1T7 X1T6 R1R7 R1R6 65.90 23.0 88.9
X1T7=88.9
119.34∠79.52°
Where;
.
Angle_R6 2 tan ≒2 tan 112.83°
.
.
Angle_R7 2 tan ≒2 tan 91.48°
.
- 68 -
5.5.10 Phase Instantaneous/Definite-Time Overcurrent
5.5.10.1 Phase Instantaneous Overcurrent 1
(For backup Phase Directional O/C Protection)
(a) Level 1 Pick-up (50P1P)
- Range : 0.05 to 20.00 (A, sec), OFF
- According to ENATREL relay setting criteria;
50P1P = 0.68 A
- 69 -
Full-load current : 730A 0.456A
50P2P = 0.46 A
- 70 -
(b) Zone/Level 4 Directional Control (DIR4)
- Select : F, R
DIR4 = F
50FP1 = 0.25 A.
- 72 -
RTPU1 = 5.0 cyc.
- 74 -
(j) Three-Pole Reclaim Time Delay (3PRCD)
- Range : 1 to 99999 (cyc.)
- Set the reclaim time following a three-pole auto-reclose cycle
equal to 900 cycles
3PRCD = 900 cyc.
27LP = 11.5 V
59LP = 46.2 V
- 75 -
- Select A-phase voltage from the line source for the synchronism
check reference
SYNCP = VAY
25VL = 51.9 V
25VH = 63.5 V
25SFBK1 = 0.021 Hz
- 76 -
(h) Maximum Angle Difference 1 (ANG1BK1)
- Range : 3.0 to 80.0 (deg.)
- Set ANG1BK1 to 20 degrees for auto-reclosing
ANG1BK1 = 20 deg.
- 77 -
5.6 EL SAUCE S/S 138kV MALPAISILLO LINE PROTECTION (SEL-421)
5.6.1 Line Configuration
(a) Current Transformer Ratio – Input W (CTRW)
- Range : 1 to 50000
- Line current capacity = 730 A
- CT ratio : 800 / 1600 – 1 A
- Selecting maximum CT ratio ;
CTRW = 1600
PTRY = 1380
PTRZ = 1380
- 78 -
Z1MAG = 41.50 Ω
Z0MAG = 154.42 Ω
- 79 -
(c) Enable Distance Element Common Time Delay (ECDTD)
- Select : Y, N
ECDTD = Y
(i) Enable Residual Ground Instantaneous / Definite – Time O/C Elements (E50G)
- Select : N, 1 - 4
- For backup ground directional O/C protection ;
E50G = 1
Z2 ′2
Therefore, above Z2 setting is acceptable
XP2 41.8487 48.5202
XP2 = 48.52
- 82 -
(e) Zone 3 Reactance (XP3)
- Range : 0.25 to 320.00 (ohms, sec)
- As Zone3 element is used to prevent unwanted tripping during current
reversals (reverse looking for POTT scheme), Zone3 fault coverage
must be greater the Zone2 fault coverage at the remote terminal.
- However, as Zone2 setting at the remote terminal is currently unavailable,
set to 120% of Zone2 setting at the local terminal.
XP3 48.52 1.2 58.224
XP3 = 58.22
XP4 = 84.26
- 83 -
5.6.4 Quad Ground Distance Element Reach
(a) Enable Adaptive Resistive Element (ARESE)
- Select : Y, N
ARESE = Y
where :
M = per-unit reach of XG1
R = RG1
| | = positive – sequence T/L reactance
| | j34.8128 j40.3626
0.85 1 , R =121.088 Ω
.
- 84 -
RG1 0.5 60.044 30.022
RG1= 30.02
- 85 -
5.6.5 Zero-Sequence compensation Factor
(a) Zone1 ZSC Factor Magnitude (KOM1)
- Range : 0.000 to 10.000, AUTO
KOM1 = AUTO
- 87 -
(b) Block Zone2 (OOSB2)
- Select : Y, N
OOSB2 = Y
R1R7= 58.14
119.34∠79.52°
Where;
.
Angle_R6 2 tan ≒2 tan 112.83°
.
.
Angle_R7 2 tan ≒2 tan 91.48°
.
- 89 -
(j) Latch Out-of-Step Blocking (OSBLTCH)
- Select : Y, N
OSBLTCH = Y
50P1P = 0.68 A
- 90 -
5.6.9.2 Phase Instantaneous Overcurrent 2 (To initiate SOTF trip)
(a) Level 2 Pick-up (50P2P)
- Range : 0.05 to 20.00 (A, sec), OFF
- Set to 50 percent of the fault current for a close in internal fault
(refer to instruction manual P.3.326)
- Considering;
3phase fault : 2020A 0.5 0.631A
50P2P = 0.46A
- 91 -
(c) Level 1 Torque Control Equation (67G1TC)
- Range : SELogic
67G1TC = 32GF
- 92 -
5.6.14 Trip Schemes (POTT Trip Scheme)
(a) Zone 3 Reverse Block Time Delay (Z3RBD)
- Range : 0.000 to 16000.000 (cyc)
- Assuming a circuit breaker opening time of 3cycles, a communication
channel reset rime of 1 cycle, and remote Zone 2 relay rest time of 1 cycle;
Z3RBD = 5 cyc
- 93 -
Attachment 2 : Impedance Characteristics of Distance Protection elements and Out-of-step
- 94 -
6.0 Relay Settings for ESTELI S/S
6.1 138/24.9kV TR. Protection (SEL-787)
6.1.1 Configuration
(a) Maximum Transformer Capacity (MVA)
- Range : OFF, 0.2-5000.0 MVA
MVA = 20 MVA
-IN = 83.68 A
√
- CT ratio : 100-200 / 1 A
- Selecting maximum CT ratio ;
CTR1 = 200
-IN = 463.75 A
√ .
- CT ratio : 800-1600 / 5 A
- Selecting 800/5 ratio due to the setting range limit of SEL-451 relay which uses
same CT for winding 2 CT of the relay;
CTR2 = = 160
CTR2 = 160
- 96 -
TAP2 = Auto. (2.90A)
SLP1 = 20 %
- 97 -
(i) Restraint current Slope 1 limit (IRS1)
- Range : 1.0 - 20.0 (Restraint current in multiple of tap)
IRS1 = 6.0
- 98 -
6.1.3 Breaker Failure
(a) 52A Interlock in BF Logic (52ABF)
- Select : Y, N
52AF = N
- 99 -
6.2 138/24.9kV TR. Protection (SEL-751A)
6.2.1 Main
(a) Phase (IA, IB, IC) CT RATIO (CTR)
- Range : 1 to 5000
- IN = 83.68
√
51P1P = 0.63 A
- 100 -
on 24.9kV bus 3-phase fault.
Meltiples of pickup 3.88
.
TD 0.215
51P1TD = 0.22
51N1P = 0.33 A
TD = 0.664
51N1TD = 0.66
* 51N1TD setting should be reviewed and changed, if necessary, when fault current
data is available.
- 101 -
6.3 138/24.9kV TR. Protection (SEL-451)
6.3.1 General Global Settings
(a) Number of Breakers in Scheme (NUMBK)
- Select : 1, 2
- To be able to use Ix for 51N (refer to instruction Manual R.1.61)
NUMBK = 2
- 102 -
IN 463.75
√ .
CTRW = 160
CTRX = 20
- 103 -
51S1P 1.25 3.623
√ .
51S1P = 3.62 A
. .
- ∙ . ∙ . 0.6
.
TD 0.134
51S1TD = 0.14
51S2P = 9.27 A
- 104 -
51S2C = C1
TD 0.222
51S2TD = 0.23
50FP1 = 2.89 A
- 105 -
(d) Breaker Failure Initiate Dropout Delay – BK1 (BFIDO1)
- Range : 0.000 to 1000.000 (cyc. in steps of 0.125)
- Disable this feature because this application is not a dual circuit breaker scheme.
BFIDO1 = 0.000 cyc.
- 106 -
6.4 ESTELI S/S 138kV SEBACO LINE PROTECTION (SEL-411L)
6.4.1 Line Configuration
(a) Current Transformer Ratio – Input W (CTRW)
- Range : 1 to 50000
- Line current capacity = 730 A
- CT ratio : 800 / 1600 – 1 A
- Selecting maximum CT ratio ;
CTRW = 1600
PTRY = 1380
PTRZ = 1380
Z1MAG = 23.77 Ω
- 107 -
(g) Positive – sequence Line Impedance Angle (Z1ANG)
- Range : 5.00 to 90.00 deg.
Z1ANG = 77.81 deg.
Z0MAG = 78.76 Ω
- 108 -
(e) Enable Mho Ground Distance Zones (E21MG)
- Select : N, 1 – 5
E21MG = N
(l) Enable Residual Ground Instantaneous / Definite – Time O/C Elements (E50G)
- Select : N, 1 - 4
E50G = N
- 110 -
(v) Enable Advanced Settings (EADVS)
- Select : Y, Y1, N
EADVS = N
(c) Maximum Primary Current Rating for Remote Relay 1CT (87CTP1R)
- Range : 1 to 50000
- As CT primary nominal current for remote relay 1 is not given,
set to 1600A (same as that for local relay) temporarily.
87CTP1R = 1600 A
- 113 -
(c) Breaker Close Failure Delay (BKCFD)
- Range : 1 to 99999 (cyc), OFF
- If circuit breaker fails to close within 10 seconds after the reclose
Command is received, the auto-reclose logic goes to lockout.
BKCFD = 600 cyc.
- 114 -
(i) Three-Pole Open Interval Delay (3POID1)
- Range : 1 to 99999 (cyc.)
- Set the three-pole open interval time equal to 30 cycles.
3POID1 = 30 cyc.
27LP = 11.5 V
59LP = 46.2 V
- 116 -
6.5 ESTELI S/S 138kV SEBACO LINE PROTECTION (SEL-421)
No settings for SEL-421 relay because no current will flow on this relay on the 138kV SEBACO line
fault.
- 117 -
7.0 Relay Settings for OCOTAL S/S
7.1 138/24.9kV TR. Protection (SEL-787)
7.1.1 Configuration
(a) Maximum Transformer Capacity (MVA)
- Range : OFF, 0.2-5000.0 MVA
MVA = 20 MVA
-IN = 83.68 A
√
- CT ratio : 100-200 / 1 A
- Selecting maximum CT ratio ;
CTR1 = 200
-IN = 463.75 A
√ .
- CT ratio : 800-1600 / 5 A
- Selecting 800/5 ratio
CTR2 = = 160
CTR2 = 160
SLP1 = 20 %
- 121 -
7.1.3 Breaker Failure
(a) 52A Interlock in BF Logic (52ABF)
- Select : Y, N
52ABF = N
- 122 -
7.2 138/24.9kV TR. Protection (SEL-751A)
7.2.1 Main
(a) Phase (IA, IB, IC) CT RATIO (CTR)
- Range : 1 to 5000
- IN = 83.68
√
51P1P = 0.63 A
- 123 -
on 24.9kV bus 3-phase fault.
Meltiples of pickup 3.25
.
TD 0.215
51P1TD = 0.19
51N1P = 0.33 A
- 124 -
8.0 Relay Settings for SAN RAMON S/S
8.1 138/24.9kV TR. Protection (SEL-787)
8.1.1 Configuration
(a) Maximum Transformer Capacity (MVA)
- Range : OFF, 0.2-5000.0 MVA
MVA = 20 MVA
-IN = 83.68 A
√
- CT ratio : 100-200 / 1 A
- Selecting maximum CT ratio ;
CTR1 = 200
-IN = 463.75 A
√ .
- CT ratio : 800-1600 / 5 A
- Selecting 800/5 ratio due to the setting range limit of SEL-451 relay which uses
same CT for winding 2 CT of the relay;
CTR2 = = 160
CTR2 = 160
- 126 -
TAP2 = Auto. (2.90A)
SLP1 = 20 %
- 127 -
- Range : 1.0 - 20.0 (Restraint current in multiple of tap)
IRS1 = 6.0
- 128 -
8.1.3 Breaker Failure
(a) 52A Interlock in BF Logic (52ABF)
- Select : Y, N
52ABF = N
- 129 -
8.2 138/24.9kV TR. Protection (SEL-751A)
8.2.1 Main
(a) Phase (IA, IB, IC) CT RATIO (CTR)
- Range : 1 to 5000
- IN = 83.68
√
51P1P = 0.63 A
- 130 -
on 24.9kV bus 3-phase fault.
Meltiples of pickup 3.95
.
TD 0.218
51P1TD = 0.22
51N1P = 0.33 A
TD = 0.767
51N1TD = 0.77
* 51N1TD setting should be reviewed and changed, if necessary, when fault current
data is available.
- 131 -
8.3 138/24.9kV TR. Protection (SEL-451)
8.3.1 General Global Settings
(a) Number of Breakers in Scheme (NUMBK)
- Select : 1, 2
- To be able to use Ix for 51N (refer to instruction Manual R.1.61)
NUMBK = 2
- 132 -
IN 463.75
√ .
CTRW = 160
CTRX = 20
- 133 -
51S1P 1.25 3.623
√ .
51S1P = 3.62 A
. .
- ∙ . ∙ . 0.6
.
TD 0.136
51S1TD = 0.14
51S2P = 9.27 A
- 134 -
51S2C = C1
TD 0.222
51S2TD = 0.23
50FP1 = 2.89 A
- 136 -
9.0 Relay settings for YALAGUINA S/S
9.1 YALAGUINA S/S 138kV OCOTAL LINE PROTECTION (SEL-421)
9.1 Line Configuration
(a) Current Transformer Ratio – Input W (CTRW)
- Range : 1 to 50000
- Line current capacity = 730 A
- CT ratio : 800 / 1600 – 1 A
- Selecting maximum CT ratio ;
CTRW = 1600
PTRY = 1380
PTRZ = 1380
- 137 -
Z1MAG = 12.31 Ω
Z0MAG = 34.33 Ω
- 138 -
(c) Enable Distance Element Common Time Delay (ECDTD)
- Select : Y, N
ECDTD = Y
ECVT = Y
(i) Enable Residual Ground Instantaneous / Definite – Time O/C Elements (E50G)
- Select : N, 1 - 4
E50G = N
- 139 -
(k) Enable Directional Control (E32)
- Select : Y, AUTO
E32 = AUTO
- 140 -
9.1.3 Quad Phase Distance Element Reach
(a) Zone 1 Reactance (XP1)
- Range : 0.25 to 320.00 (ohms, sec), OFF
- XP1 12.31 0.85 10.4635
XP1 = 10.46
XP2 = 14.77
RP2 = 29.41
- 141 -
XP3 = 150.13
where :
M = per-unit reach of XG1
R = RG1
| | = positive – sequence T/L reactance
- 142 -
| | j10.3277 j11.9741 j13.8830
0.85 1 , R =41.649 Ω
.
- 143 -
9.1.6 Distance Element Common Time Delay
(a) Zone1 Time Delay (Z1D)
- Range : 0.000 to 16000.000(cyc), OFF
Z1D =0.000 cyc
- 144 -
52AEND = 10.000 cyc
50P1P = 0.24A
- 145 -
(c) Level 1 Torque Control Equation (67P1TC)
- Range : SELogic
67P1TC = 1
- 147 -
(b) Number of Three-Pole Recloses (N3PSHOT)
- Select : N, 1 – 4
- As per ENATREL`s request ;
N3PSHOT = N
- 148 -
(h) Three-Pole Line Open Failure Delay (3PRIH)
- Range : 1 to 99999 (cyc.), OFF
3PRIH = 15 cyc.
27LP = 11.5 V
59LP = 46.2 V
- 150 -
9.2 YALAGUINA S/S 138kV OCOTAL LINE PROTECTION (SEL-351A)
9.2.1 General settings
(a) Phase (IA, IB, IC) CT Ratio (CTR)
- Range : 1 to 6000
- CT ratio : 800 / 1600 – 1 A
- Selecting maximum CT ratio ;
CTR = 1600
-PT ratio ∶
√ √
PTR = 1380
VNOM = 57.74V
- 151 -
Z0ANG = 77.69 deg.
51PP = 0.08A
51GP = 0.02 A
TD = 0.225
51GTD = 0.23
- 153 -