Академический Документы
Профессиональный Документы
Культура Документы
58ZAV
Downflow/Horizontal Induced-Combustion Furnaces
Visit www.carrier.com
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 PC 101 Catalog No. 535-768 Printed in U.S.A. Form 58ZAV-12SI Pg 1 10-00 Replaces: 58ZAV-10SI
Tab 6a 8a
28 1⁄2″ VENT CONNECTION
1⁄2″ DIA
20″ D 2″
4 3⁄16″ THERMOSTAT
13⁄16″ 13⁄16″ WIRE ENTRY
INLET
7⁄8″ DIA
ACCESSORY
2 15⁄16″
7⁄8″ DIA HOLE
POWER ENTRY
39 7⁄8″
1 1⁄2″ DIA
7⁄8″ DIA
R.H. GAS ENTRY
9 1⁄8″
ACCESSORY
16 1⁄16″ 7⁄8″ DIA 1″ TYP
1 3⁄4″ DIA HOLE 10 1⁄4″
GAS ENTRY ACCESSORY
OUTLET 1 1⁄16″
11⁄16″ E 13 5 ⁄16″
2 1⁄8″ 5⁄8″ TYP
10 1⁄4″
19″ 8 1⁄4″ A 11⁄16″
1 1⁄16″
11⁄16″
2 1⁄8″
NOTE: ADDITIONAL 7⁄8″ DIA K.O.’s ARE AIRFLOW DIMPLES TO DRILL HOLES
LOCATED IN THE TOP PLATE FOR HANGER BOLTS (4 PLACES)
AND BOTTOM PLATE IN HORIZONTAL POSITION
NOTE: Minimum return-air openings at furnace, based on metal duct. If flex duct is used,
see flex duct manufacturer's recommendations for equivalent diameters.
a. For 800 CFM–16-in. round or 141⁄2 x 12-in. rectangle.
b. For 1200 CFM–20-in. round or 141⁄2 x 191⁄2-in. rectangle.
c. For 1600 CFM–22-in. round or 141⁄2 x 231⁄4-in. rectangle.
d. For airflow requirements above 1800 CFM, must use entire return air opening.
A99288
Fig. 1—Dimensional Drawing
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS 3. After touching the chassis you may proceed to service the
PROCEDURE control or connecting wires as long as you do nothing that
recharges your body with static electricity (for example; DO
NOT move or shuffle your feet, DO NOT touch ungrounded
objects, etc.).
Electrostatic discharge can affect electronic components.
Take precautions during furnace installation and servicing to 4. If you touch ungrounded objects (recharge your body with
protect the furnace electronic control. Precautions will pre- static electricity), firmly touch furnace again before touching
vent electrostatic discharges from personnel and hand tools control or wires.
which are held during the procedure. These precautions will 5. Use this procedure for installed and uninstalled (ungrounded)
help to avoid exposing the control to electrostatic discharge furnaces.
by putting the furnace, the control, and the person at the same
6. Before removing a new control from its container, discharge
electrostatic potential.
your body’s electrostatic charge to ground to protect the
1. Disconnect all power to the furnace. DO NOT TOUCH THE control from damage. If the control is to be installed in a
CONTROL OR ANY WIRE CONNECTED TO THE CON- furnace, follow items 1 through 5 before bringing the control
TROL PRIOR TO DISCHARGING YOUR BODY’S ELEC- or yourself into contact with the furnace. Put all used AND
TROSTATIC CHARGE TO GROUND. new controls into containers before touching ungrounded
2. Firmly touch a clean, unpainted, metal surface of the furnace objects.
chassis which is close to the control. Tools held in a person’s 7. An ESD service kit (available from commercial sources) may
hand during grounding will be satisfactorily discharged. also be used to prevent ESD damage.
2
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
This forced air furnace is equipped for use with natural This furnace is approved for DOWNFLOW and HORIZONTAL
gas at altitudes 0-10,000 ft (0-3,050m). installations.
An accessory kit, supplied by the manufacturer,shall be
used to convert to propane gas use or may be required for Clearance arrows
some natural gas applications. do not change with
This furnace is for indoor installation in a building furnace orientation. 1"
constructed on site.
This furnace may be installed on combustible flooring in
TOP / PLENUM
alcove or closet at minimum clearance from combustible
material.
This furnace may be used with a Type B-1 Vent and may
be vented in common with other gas-fired appliances. 0" 1"
*#
††
BA E
† For installation on non-combustible floors only. CK
E
S ID
For installation on combustible flooring only when N AC
UR
installed on special base, Part No. KGASB0201ALL, F
T
Coil Assembly, Part No. CD5 or CK5, or Coil Casing, ON
FR
Part No. KCAKC. S
E
RV
# For furnaces wider than 14.25 inches (362mm) may E
IC
E
be 0 inches. S ID FR
30"
ON
Ø 18 inches front clearance required for alcove. T
##
MIN
* 1" #
* Indicates supply or return sides when furnace is in
the horizontal position. Line contact only permissible
Ø
BOTTOM
between lines formed by intersections of the Top and
two Sides of the furnace jacket, and building joists,
Clearance in inches
"#
studs or framing.
†1
## For single wall vent type 6 inches.
For Type B-1 vent type 3 inches.
† † Clearance to Back 0 inches in downflow and Vent Clearance to combustibles:
For Single Wall vents 6 inches.
horizontal (attic/alcove & crawlspace) positions and For Type B-1 vent type 1 inch .
3 inches in horizontal closet positions.
322286-101 REV. F (LIT)
A99262
Fig. 2—Clearances to Combustibles
3
Locate the furnace as close to the chimney/vent and as near the
center of the air distribution system as possible. The furnace
should be installed as level as possible.
Provide ample space for servicing and cleaning. Always comply
with the minimum fire protection clearances shown on the unit
rating plate. This furnace shall not be installed directly on
carpeting, tile, or any combustible material other than wood
flooring. The furnace may be installed on combustible flooring
when installed with the accessory downflow subbase, which is
available from your distributor or branch when required.
LOCATION RELATIVE TO COOLING EQUIPMENT — The
cooling coil must be installed parallel with or on the downstream
side of the furnace to avoid condensation in the heat exchangers.
When installed parallel with a furnace, dampers or other means
used to control the flow of air must prevent chilled air from
entering the unit. If the dampers are manually operated, they must
be equipped with means to prevent operation of either unit unless
A93042 the damper is in the full-heat or full-cool position.
HAZARDOUS LOCATIONS
DO NOT install the furnace on its back; safety control Air for combustion must not be contaminated by halogen
operation will be adversely affected. Failure to follow this compounds, which include fluoride, chloride, bromide, and
warning could result in fire, personal injury, or death. iodide. These elements are found in aerosol sprays, deter-
gents, bleaches, cleaning solvents, salts, air fresheners, and
This furnace must be installed so the electrical components are other household products.
protected from water.
4
c. If furnace is installed on a raised platform to provide a
return-air plenum, and return air is taken directly from
The operation of exhaust fans, kitchen ventilation fans, hallway or space adjacent to furnace, all air for combustion
clothes dryers, or fireplaces could create a NEGATIVE must come from outdoors.
PRESSURE CONDITION at the furnace. Make-up air MUST 2. Air from outside the structure requires 1 of the following
be provided for the ventilation devices, in addition to that methods:
required by the furnace.
a. If combustion air is taken from outdoors through 2 vertical
All fuel-burning equipment must be supplied with air for combus- ducts, the openings and ducts MUST have at least 1 sq in.
tion of the fuel. Sufficient air MUST be provided to ensure there of free area per 4000 Btuh of total input for all equipment
will not be a negative pressure in the equipment room or space. In within the confined space. (See Fig. 4 and Table 2.)
addition, a positive seal MUST be made between the furnace b. If combustion air is taken from outdoors through 2 hori-
cabinet and the return-air duct to avoid pulling air from the burner zontal ducts, the openings and ducts MUST have at least 1
area and blocked vent safeguard opening. sq in. of free area per 2000 Btuh of total input for all
The requirements for combustion and ventilation air depend upon equipment within the confined space. (See Fig. 4 and Table
whether the furnace is located in an unconfined or confined space. 2.)
UNCONFINED SPACE — An unconfined space must have at c. If combustion air is taken from outdoors through a single
least 50 cu ft for each 1000 Btuh of input for all the appliances opening or duct (horizontal or vertical) commencing within
(such as furnaces, clothes dryer, water heaters, etc.) in the space. 12 in. of the top of the confined space, opening and duct
If the unconfined space is of unusually tight construction, air for MUST have at least 1 sq in. of free area per 3000 Btuh of
the total input for all equipment within the confined space
For Example: and not less than the sum of the areas of all vent connectors
MINIMUM SQ FT in the confined space. (See Fig. 4 and Table 2.) Equipment
58ZAV FURNACE
WITH clearances to the structure shall be at least 1 in. from the
INPUT BTUH
7-1/2 FT CEILING sides and back and 6 in. from the front of the appliances.
46,000 307
When ducts are used, they must be of the same cross-sectional area
69,000 460
as the free area of the openings to which they connect. The
92,000 613 minimum dimension of ducts must not be less than 3 in. (See Fig.
115,000 767 4.)
135,000 920
AIR DUCTS
Step 1—General Requirements
combustion and ventilation MUST come from either the outdoors
or spaces freely communicating with the outdoors. Combustion The duct system should be designed and sized according to
and ventilation openings must be sized the same as for a confined accepted national standards such as those published by: Air
space as defined below. Return air must not be taken from the Conditioning Contractors Association (ACCA), Sheet Metal and
room unless an equal or greater amount of air is supplied to the Air Conditioning Contractors National Association (SMACNA) or
room. American Society of Heating, Refrigerating and Air Conditioning
Engineers (ASHRAE). Or consult factory The Air Systems Design
CONFINED SPACE Guidelines reference tables available from your local distributor.
A confined space is defined as a space whose volume is less than The duct system should be sized to handle the required system
50 cu ft per 1000 Btuh of total input ratings of all appliances design CFM at the design static pressure.
installed in that space. A confined space MUST have provisions When a furnace is installed so that the supply ducts carry air to
for supplying air for combustion, ventilation, and dilution of flue areas outside the space containing the furnace, the return air must
gases using 1 of the following methods. (See Fig. 3, 4, and Table also be handled by a duct(s) sealed to the furnace casing and
2.) terminating outside the space containing the furnace.
NOTE: In determining free area of an opening, the blocking Secure ductwork with proper fasteners for type of ductwork used.
effect of louvers, grilles, and screens must be considered. If free Seal supply- and return-duct connections to furnace with code
area of louver or grille design is unknown, assume that wood approved tape or duct sealer.
louvers have a 20 percent free area and metal louvers or grilles Flexible connections should be used between ductwork and
have a 60 percent free area. Screens, when used, must not be furnace to prevent transmission of vibration. Ductwork passing
smaller than 1/4-in. mesh. Louvers and grilles must be constructed through unconditioned space should be insulated to enhance
so they cannot be closed. system performance. When air conditioning is used, a vapor
The size of the openings depends upon whether air comes from barrier is recommended.
outside of the structure or an unconfined space inside the structure. Maintain a 1-in. clearance from combustible materials to supply air
1. All air from inside the structure requires 2 openings (for ductwork for a distance of 36 in. horizontally from the furnace. See
structures not usually tight): NFPA 90B or local code for further requirements.
a. Each opening MUST have at least 1 sq in. of free area per Step 2—Ductwork Acoustical Treatment
1000 Btuh of total input for all equipment within the Metal duct systems that do not have a 90 degree elbow and 10 ft
confined space, but not less than 100 sq in. per opening. of main duct to the first branch take-off may require internal
(See Fig. 3 and Table 2.) The minimum dimension of air acoustical lining. As an alternative, fibrous ductwork may be used
openings shall not be less than 3 in. if constructed and installed in accordance with the latest edition of
b. If building is constructed unusually tight, a permanent SMACNA construction standard on fibrous glass ducts. Both
opening directly communicating with the outdoors shall be acoustical lining and fibrous ductwork shall comply with NFPA
provided. See item 2 below. 90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
5
DUCTS TO
OUTDOORS
1 SQ IN.
PER 4000
BTUH*
CONFINED
BTUH* IN DOOR TO
SPACE
OR WALL OUTSIDE OUTDOORS
INTERIOR
HEATED UNCONFINED
SPACE SPACE 1 SQ IN.
PER 4000
6″ MIN BTUH*
(FRONT) †
1 SQ IN.
1 SQ IN. E G
PER 2000 B
PER 1000 BTUH* 12″
BTUH* IN DOOR 12″ MAX C MAX
OR WALL
12″ MAX
12″ MAX
SUPPLY AIR DUCT
TO 1 SQ IN.
OUTDOORS PER 4000
SUPPLY AIR BTUH
*Minimum dimensions of 3 in.
* Minimum opening size is 100 sq in. with NOTE: Use any of the following
minimum dimensions of 3 in. combinations of openings:
† Minimum of 3 in. when type B-1 vent is used. A&B C&D D&E F&G
A93387 A93388
Fig. 3—Confined Space: Air for Combustion and Fig. 4—Confined Space: Air for Combustion and
Ventilation from an Unconfined Indoor Space Ventilation from Outdoors
Table 2—Minimum Free Area Of Combustion Air Opening
AIR FROM UNCON-
OUTDOOR AIR THROUGH OUTDOOR AIR THROUGH OUTDOOR AIR THROUGH
58ZAV FINED INDOOR
VERTICAL DUCTS HORIZONTAL DUCTS SINGLE DUCT
FURNACE SPACE
INPUT Free Area Free Area of Round Free Area of Round Free Area of Round
(BTUH) of Opening Opening and Duct Pipe Opening and Duct Pipe Opening and Duct Pipe
(Sq In.) (Sq In.) (In. Dia) (Sq In.) (In. Dia) (Sq In.) (In. Dia)
46,000 100 11.50 4 23.0 6 15.33 5
69,000 100 17.25 5 34.5 7 23.00 6
92,000 100 23.00 6 46.0 8 30.67 7
115,000 115 28.75 7 57.5 9 38.33 7
135,000 135 33.75 7 67.5 10 45.00 8
* Free area shall be equal to or greater than the sum of the areas of all vent connectors in the confined space. Opening area must be increased if other gas appliances
in the space require combustion air.
Step 3—Supply Air Connections supply/outlet or air conditioning coil casing (when used). DO NOT
DOWNFLOW FURNACES cut main furnace casing to attach supply side air duct, humidifier,
or other accessories. All accessories MUST be connected external
Connect supply-air duct to supply-air opening on furnace. The
to furnace main casing.
supply-air duct attachment must ONLY be connected to furnace
supply/outlet or air conditioning coil casing (when used), when Step 4—Return Air Connections
installed on non-combustible material. When installed on combus- The return-air duct must be connected to return-air opening
tible material, supply-air duct attachment must ONLY be con- provided as shown in Fig. 1. DO NOT cut into casing sides or back
nected to an accessory subbase or factory approved air condition- to attach any portion of return-air duct. Bypass humidifier connec-
ing coil casing. DO NOT cut main furnace casing to attach supply tions should be made at ductwork or coil casing sides exterior to
side air duct, humidifier, or other accessories. All accessories furnace.
MUST be connected external to furnace main casing.
HORIZONTAL FURNACES
Connect supply-air duct to supply air opening on furnace. The
supply-air duct attachment must ONLY be connected to furnace
6
A
PLENUM
OPENING
B D
FLOOR
OPENING
C
A96283
Fig. 5—Floor and Plenum Opening Dimensions
→
Do not install furnace on its back. Safety control operation
FRONT
will be adversely affected. Never connect return-air ducts to
back of furnace. Failure to follow this warning could result in
fire, personal injury, or death.
COMBUSTIBLE COMBUSTIBLE
FLOORING FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
SHEET METAL PLENUM
PLENUM
FLOOR FLOOR
OPENING OPENING
A96285 A96284
Fig. 6—Furnace, Plenum, and Subbase Installed Fig. 7—Furnace, Plenum, and Coil Assembly or
on a Combustible Floor Coil Box Installed on a Combustible Floor
GAS TYPE-B
ENTRY VENT
IN
6″ M 30-IN. MIN
WORK AREA
24″
SHEET
METAL
24″
MANUAL SHUTOFF
GAS VALVE
SEDIMENT
TRAP
A97516
Fig. 8—Typical Attic Installation
8
If coil assembly CD5, CK5, or Coil Box KCAKC is used, Table 4 for horizontal applications. Horizontal filter retainers must
install as shown in Fig. 7. be field supplied. See Fig. 12 for downflow applications.
Step 6—Horizontal Attic Installation Step 9—Gas Piping
Gas piping must be installed in accordance with national and local
codes. Refer to the current edition of the NFGC.
Do not install the furnace on its back; safety control operation
Canadian installations must be installed in accordance with NSC-
will be adversely affected. Never connect return-air ducts to
NGPIC and all authorities having jurisdiction.
the sides or back of the furnace. Failure to follow this warning
could result in fire, personal injury, or death. Refer to Table 5 for recommended gas pipe sizing. Risers should
be used to connect to the furnace and to the meter.
The furnace can be installed horizontally on either the left-hand
(LH) or right-hand (RH) side. A typical attic installation is shown
in Fig. 8.
CONSTRUCT A WORKING PLATFORM If a flexible connector is required or allowed by the authority
having jurisdiction, black iron pipe shall be installed at the
Construct working platform on location where all required furnace
gas valve and extend a minimum of 2 in. outside the furnace
clearances are met. (See Fig. 2 and 8.)
casing.
INSTALL FURNACE
1. Position furnace in desired location.
2. Connect gas supply pipe. See Fig. 8 for typical piping entry.
3. Install field-supplied filter retainers as indicated in Fig. 11 and Use the proper length of pipes to avoid stress on the gas
Table 4 before connecting return-air duct to furnace. control manifold. Failure to follow this warning could result
in a gas leak, causing fire, explosion, personal injury, or
4. Connect supply- and return-air ducts. death.
5. Install 24- X 24-in. sheet metal shield on platform in front of
louvered control panel as shown in Fig. 8.
Step 7—Horizontal Crawlspace Installation
The furnace can be installed horizontally with either the LH or RH Connect the gas pipe to the furnace using a backup wrench to
side up. In a crawlspace, furnace can either be hung from floor avoid damaging gas controls.
joist (see Fig. 10) or installed on suitable blocks or pad. (See Fig.
9.) The furnace can be suspended from each corner by hanger bolts
(4 each 3/8-in. all-thread rod) cut to desired length, 1- X 3/8-in. flat
washer, 3/8-in. lockwasher, and 3/8-in. nut. Dimples are provided Never purge a line into a combustion chamber. Never use
for hole locations. (See Fig. 1.) matches, candles, flame, or other sources of ignition to check
for gas leakage. Use a soap-and-water solution to check for
gas leaks. Failure to follow this warning could result in fire,
explosion, personal injury, or death.
9
3⁄8-IN. ROD
ANGLE
IRON OR
EQUIVALENT
(B)
(A)
(B)
(A)
(A) ROD LOCATION (B)
USING DIMPLE
LOCATORS (A) (B)
(SEE DIMENSIONAL 3/8-IN.
HEX NUT
DWG FOR & WASHER (4)
LOCATIONS) REQD PER ROD
NOTES: 1. A 1 In. clearance minimum between top of
furnace and combustible material.
(A) PREFERRED ROD LOCATION
2. The entire length of furnace must be
(B) ALTERNATE ROD LOCATION supported when furnace is used in horizontal
position.
A96633
Fig. 10—Horizontal Crawlspace Installation on Hanger Rods
Step 10—Electrical Connections
115-V WIRING
;;;
Refer to the unit rating plate or Table 6 for equipment electrical
;;; ;;
;;;
requirements. The control system requires an earth ground for
proper operation.
;;;;;;;;
AIRFLOW
; ;;;;; Do not connect aluminum wire between disconnect switch
and furnace. Use only copper wire.
;; ;
12″
Make all electrical connections in accordance with the current
4″ D edition of the National Electrical Code (NEC) ANSI/NFPA
70-1999, and any local codes or ordinances that might apply. For
FIELD-SUPPLIED Canadian installations, all electrical connections must be made in
FILTER RETAINERS accordance with Canadian Electrical Code CSA C22.1, or authori-
A82173 ties having jurisdiction.
Fig. 11—Horizontal Filter Arrangement NOTE: Proper polarity must be maintained for 115-v wiring. If
polarity is incorrect, control status code indicator light will flash
→Table 4—Filter Retainer (In.) rapidly and furnace will not operate.
10
;;;;AIRFLOW
INSTALLATION
;;;;
;;;;
;;;;
;;;;
POSITION
OF FILTERS
RETURN-AIR
;;;;
;;;;
;;;;
;;;;
PLENUM GAS
SUPPLY
MANUAL
SHUTOFF
VALVE
(REQUIRED)
SEDIMENT
TRAP
UNION
A89414
Fig. 13—Typical Gas Pipe Arrangement
ACCESS DOOR
ACCESSORIES
1. Electronic Air Cleaner (EAC)
11
Two quick-connect terminals marked EAC-1 and EAC-2 are
provided for EAC connection. (See Fig. 14.) These terminals
are energized with 115-v, (1.5-amp maximum) during blower This furnace is equipped with 2 manual reset limit switches in
motor operation. the gas control area. The switches will open and shut off
2. Humidifier (HUM) power to the gas valve if a flame rollout or an overheating
condition occurs in the gas control area. DO NOT bypass the
A quick-connect terminal (HUM) and screw terminal (COM)
switches. Correct inadequate combustion air supply problem
are provided for 24-v humidifier connection. (See Fig. 16.)
and reset the switches.
HUM terminal is energized with 24-v (0.5-amp maximum)
after inducer pressure switch closes.
SEQUENCE OF OPERATION
24-V THERMOSTAT
G TERMINALS
R
Y
W
TEST/TWIN Com HUMIDIFIER TERMINAL
24V (24-VAC 0.5 AMP MAX)
HUM
LED OPERATION &
DIAGNOSTIC LIGHT
HARNESS CONNECTOR
SEC-1
24-V TRANSFORMER SEC-2
3-AMP FUSE
SPARE-1
COOL
HEAT BLOWER SPEED
SELECTION TERMINALS
SPARE-2
EAC-1 (BLACK)
NOTE 2
W C R G Y THERMOSTAT
FIVE WIRE TERMINALS FIELD-SUPPLIED
THREE-WIRE DISCONNECT
HEATING-ONLY
208/230- OR
BLOWER DOOR SWITCH 460-V
THREE
W PHASE
BLK BLK
C R
WHT WHT
O
N 208/230-V
GND GND T SINGLE
R G PHASE
115-V FIELD- AUXILIARY O
SUPPLIED J-BOX L C GND
DISCONNECT NOTE 1
Y
CONDENSING
UNIT
24-V TWO
TERMINAL WIRE
BLOCK
FURNACE NOTES: 1. Connect Y-terminal in furnace as shown for proper blower operation.
2. Some thermostats require a "C" terminal connection as shown.
3. If any of the original wire, as supplied, must be replaced, use
same type or equivalent wire.
A98521
Fig. 15—Heating and Cooling Application Wiring Diagram
13
(WHEN USED) (WHEN USED) TO 115VAC FIELD DISCONNECT SCHEMATIC DIAGRAM
SW2 G NOTE #14 NOTE #11 (WHEN USED)
BLOWER R DSS BVSS ALS PRS LGPS L1 L2 (NATURAL GAS & PROPANE)
PCB NOTE #9 OFF NOTE #4
Y EQUIPMENT GROUND
(NOT ON ALL MODELS)
DELAY SW1 ORN ORN ORN ORN ORN
W ILK L2
COM LO
BLOWER OFF DELAY SPARE-2
SELECTION CHART MED LO
HUM YEL HEAT MED HI
NOTE #14 NOTE #13
90 SEC TEST/TWIN HI START
SPARE-1
LED L1 HI/LO NOTE #7 OL
135 SEC BLWR
BLU LS COOL
CAP
NOTE #15
180 SEC RED COM COM BLWM
PL1 3 2 1 EAC-1
225 SEC (WHEN USED) NOTE #11 GV
HSIR EAC-2
6 5 4 WHT FL
FSE
9 8 7 1 1 HSI
GVR RED
FRS1 FRS2 GRN/YEL
PL2 2 PL5 2 IDM
SEC-1 GRN/YEL NOTE #5
SEC-2 IDR
HI/LO BLU BLK
RELAY PR1 115VAC PR2 1
WHT
TRAN
RED
3 PL3
24 VAC-3A WHT (COM) TRAN
FU1 FUSE 24VAC
BLK (HI) GRN/YEL 2
BLOWER NOT USED
HSIR IDR BLWR SPEED COOL SPARE-1 BRN
OL TEST/TWIN FU1 NOTE #6
SELECT
YEL (MED HI) SEC-2 FRS1 FRS2
START CAP SEC-1
L2 NOTE #7 NOTE #12
HEAT SPARE-2 GVR-2 7
PL3 HUM
PL2 EAC-1 (WHEN USED)
1 PR2 BLU (MED LO) FL
120 VAC 1 BRN 1 NOTE #11
2 LS
L1 PR1 BLWM R
1.5 AMP
2 3 COM RED (LO)
EAC-2 NOTE #13
NOTE #13 LGPS PRS
WHT (COM) W
(WHEN USED)
WHT
WHT 4 PL1
BLK
BLK
BLK
BLK
HSIR BLWR HI/LO (WHEN USED)
WHT
FUSED DISCONNECT IDR GVR NOTE #14
PL5 SWITCH (WHEN REQ’D) DSS BVSS
WHT ILK
1 2 JB NOTE #4
14
IDM
L1 3
BLK BLK FU2 ALS
HSI GRN/YEL NOTE #14 (WHEN USED)
WHT NEUTRAL CPU NOTE #15
GVR-1
2 GV
GND
Y
LEGEND 8
NOTE #5
ALS AUXILIARY LIMIT SWITCH, OVERTEMP. -MANUAL RESET, SPST-(N.C.) G
BLWR BLOWER MOTOR RELAY, SPST-(N.O.) PCB PRINTED CIRCUIT BOARD
BLWM BLOWER MOTOR PL1 9-CIRCUIT CONNECTOR 5 FSE
BVSS BLOCKED VENT SHUTOFF SWITCH, SPST - (N.C.) PL2 2-CIRCUIT PCB CONNECTOR
CAP CAPACITOR PL3 3-CIRCUIT IDM CONNECTOR
6 NOT USED
CPU MICROPROCESSOR AND CIRCUITRY COM
PL5 2-CIRCUIT HSI/PCB CONNECTOR 9 NOT USED
DSS DRAFT SAFEGUARD SWITCH
EAC-1 ELECTRONIC AIR CLEANER CONNECTION (115 VAC 1.5 AMP MAX.) PRS PRESSURE SWITCH, SPST-(N.O.) NOTES:
EAC-2 ELECTRONIC AIR CLEANER CONNECTION (COMMON) TEST/TWIN COMPONENT TEST & TWIN TERMINAL
FL FUSIBLE LINK
1. If any of the original equipment wire is replaced use wire rated for 105°C.
TRAN TRANSFORMER-115VAC/24VAC 2. Inducer (IDM) and blower (BLWM) motors contain internal auto-reset thermal overload switches (OL).
FRS FLAME ROLLOUT SW. -MANUAL RESET, SPST-(N.C.)
FSE FLAME PROVING ELECTRODE JUNCTION 3. Blower motor speed selections are for average conditions, see installation instructions for details on
FU1 FUSE, 3 AMP, AUTOMOTIVE BLADE TYPE, FACTORY INSTALLED
optimum speed selection.
UNMARKED TERMINAL 4. Use only copper wire between the disconnect switch and the furnace junction box (JB).
FU2 FUSE OR CIRCUIT BREAKER CURRENT INTERRUPT DEVICE
(FIELD INSTALLED & SUPPLIED) PCB TERMINAL 5. This wire must be connected to furnace sheetmetal for control to detect flame.
GV GAS VALVE-REDUNDANT OPERATORS FACTORY WIRING (115VAC)
6. Replace only with a 3 amp fuse.
GVR GAS VALVE RELAY, DPST-(N.O.) 7. Yellow lead not on all motors.
FACTORY WIRING (24VAC) 8. Blower-on delay, gas heating 45 seconds, cooling or heat pump 2 seconds.
HI/LO BLOWER MOTOR SPEED CHANGE RELAY, SPDT
HSI HOT SURFACE IGNITOR (115 VAC) FIELD WIRING (115VAC) 9. Blower-off delay, gas heating 90, 135, 180 or 225 seconds, cooling or heat pump 90 seconds.
HSIR HOT SURFACE IGNITOR RELAY, SPST-(N.O.) FIELD WIRING (24VAC)
(135 seconds only on some models)
HUM 24VAC HUMIDIFIER CONNECTION (.5 AMP. MAX.) 10. Ignition-lockout will occur after four consecutive unsuccessful trials-for-ignition. Control will auto-reset
CONDUCTOR ON PCB after three hours.
IDM INDUCED DRAFT MOTOR
IDR INDUCED DRAFT RELAY, SPST-(N.O.) FIELD WIRING TERMINAL 11. When used, auxiliary limit switch (ALS) is on some downflow models only. When used, FL is on
ILK BLOWER ACCESS PANEL INTERLOCK SWITCH, SPST-(N.O.) upflow models only.
FIELD GROUND 12. Some models may have spade quick connect terminals.
JB JUNCTION BOX
EQUIPMENT GROUND 13. Factory connected when LGPS is not used.
LED LIGHT-EMITTING DIODE FOR STATUS CODES
LGPS LOW GAS PRESSURE SWITCH, SPST-(N.O.) FIELD SPLICE 14. Factory connected when BVSS is not used. BVSS used when Chimney Adapter Accessory Kit is
LS LIMIT SWITCH, AUTO RESET, SPST(N.C.)
installed.
PLUG RECEPTACLE 15. Gas valve leads are interchangeable on single stage valves.
OL AUTO-RESET INTERNAL MOTOR OVERLOAD TEMP. SW. 322869-101 REV. H
A00304
→Fig. 16—Furnace Wiring Diagram
When the thermostat "calls for cooling," R-G and R-Y circuits This feature helps diagnose a system problem in case of a
close. The R-Y circuit starts the outdoor condensing unit and component failure. To initiate component test procedure, short
combined R-Y and R-G circuits start the furnace blower motor (jumper) the TEST 3/16-in. quick connect terminal on control
on cooling speed. The EAC-1 terminal is energized with 115v (adjacent to diagnostic light) and the COM-24V terminal on
whenever the blower is operating on cooling speed. furnace thermostat connection block for approximately 2 sec.
When the thermostat is satisfied, R-G and R-Y circuits are (See Fig. 14.)
broken. Furnace blower and EAC continue operating on NOTE: Component test feature will not operate if any thermostat
cooling speed for an additional 90 sec. signal is present at control.
3. Continuous blower mode Component test sequence is as follows.
NOTE: EAC-1 terminal is energized with 115v whenever blower a. Momentarily jumper TEST and COM-24V terminals until
is operating. LED goes off.
When the R-G circuit is made, the blower motor operates on b. LED will display previous status 4 times.
heating speed. During a call for heat, the blower stops,
c. Inducer motor starts and continues to run for entire com-
allowing the furnace heat exchangers to heat up more quickly,
ponent test.
then restarts at the end of the 45-sec blower on delay period.
If jumper is on pin 6 and pin 9, the blower on delay period is d. Hot surface igniter is energized for 15 sec, then de-
66 sec. energized.
The blower reverts to continuous operation after the heating e. Blower motor operates on cooling speed for 10 sec, then
cycle is completed. stops.
When the thermostat "calls for cooling," the blower operates f. Blower motor operates on heating speed for 10 sec, then
on cooling speed. When the thermostat is satisfied, the blower stops.
operates an additional 90 sec before reverting back to con- g. Inducer motor stops.
tinuous operation on heating speed.
3. To operate furnace, follow procedures on operating instruction
4. Heat pump mode label attached to furnace.
When installed with a heat pump, the furnace control auto- 4. With furnace operating, set thermostat below room tempera-
matically changes the timing sequence to avoid long blower ture and observe that furnace goes off. Set thermostat above
off time during demand defrost cycles. When the W-Y or room temperature and observe that furnace restarts.
W-Y-G thermostat inputs are received at the same time, the
ADJUSTMENTS
control changes the blower to heating speed or starts the
blower if it was off, and begins a heating cycle. The blower 1. Set gas input rate
remains on until the end of the prepurge period, then shuts off Furnace gas input rate on rating plate is for installations at
until the end of the ignition warm up and trial for ignition altitudes up to 2000 ft. Furnace input rate must be within ±2
periods (a total of 24 sec). The blower then comes back on at percent of input on furnace rating plate.
heating speed. a. Determine natural gas orifice size and manifold pressure
When the W input signal disappears, the control begins the for correct input.
normal inducer post-purge period and the blower changes to (1.) Obtain average yearly gas heat value (at installed
cooling speed after a 1-sec delay. If the W-Y-G signals altitude) from local gas supplier.
disappear at the same time, the blower remains on for the
(2.) Obtain average yearly gas specific gravity from local
selected heating blower off delay period and the inducer goes
gas supplier.
through its normal post-purge period. If the W-Y inputs
should disappear, leaving the G signal input, the control goes (3.) Verify furnace model. Table 7 can only be used for
into continuous blower and the inducer remains on for the model 58ZAV Furnaces.
normal post-purge period. (4.) Find installation altitude in Table 7.
Anytime the control senses false flame, the control locks out NOTE: For Canada altitudes of 2000 to 4500 ft, use U.S.A.
of the heating mode. This occurs because the control cannot altitudes of 2001 to 3000 ft in Table 7.
sense the W input due to the false flame signal and, as a result, (5.) Find closest natural gas heat value and specific gravity
sees only the Y input and goes into cooling mode blower off in Table 7.
delay. All other control functions remain in standard format.
(6.) Follow heat value and specific gravity lines to point of
NOTE: EAC-1 terminal is energized whenever blower operates. intersection to find orifice size and manifold pressure
HUM terminal is only energized when gas valve is energized. settings for proper operation .
START-UP PROCEDURES
1. Purge gas lines—After all connections have been made, purge EXAMPLE: (0—2000 ft altitude)
the lines and check for leaks. Heating value = 1050 Btu/cu ft
Specific gravity = 0.62
Therefore: Orifice No. 43*
Manifold pressure 3.6-in. wc
Never purge a line into a combustion chamber. Never use * Furnace is shipped with No. 43 orifices. In this example
matches, candles, flame, or other sources of ignition to check all main burner orifices are the correct size and do not need
for gas leakage. Use a soap-and-water solution to check for to be changed to obtain proper input rate.
gas leaks. Failure to follow this warning could result in fire,
explosion, personal injury, or death.
(7.) Check and verify burner orifice size in furnace.
2. Component test—The furnace control allows all components, NEVER ASSUME ORIFICE SIZE. ALWAYS
except gas valve, to be run for a short period of time. CHECK AND VERIFY.
15
→Table 7—Model 58ZAV Orifice Size† and Manifold Pressure for Correct Input
(Tabulated Data Based on 23,000 BTUH Per Burner, Derated 4 Percent per 1000 Ft Above Sea Level)*
AVG GAS SPECIFIC GRAVITY OF NATURAL GAS
ALTITUDE
HEAT VALUE 0.58 0.60 0.62 0.64 0.66
RANGE
AT ALTITUDE Orifice Manifold Orifice Manifold Orifice Manifold Orifice Manifold Orifice Manifold
(FT)
(BTU/CU FT) No. Pressure No. Pressure No. Pressure No. Pressure No. Pressure
850 41 3.6 41 3.7 41 3.8 40 3.6 40 3.8
875 42 3.8 41 3.5 41 3.6 41 3.7 41 3.8
900 42 3.5 42 3.7 42 3.8 41 3.5 41 3.6
U.S.A. and Canada
16
→Table 7—Model 58ZAV Orifice Size† and Manifold Pressure for Correct Input (Continued)
(Tabulated Data Based on 23,000 BTUH Per Burner, Derated 4 percent per 1000 Ft Above Sea Level)*
AVG GAS SPECIFIC GRAVITY OF NATURAL GAS
ALTITUDE
HEAT VALUE 0.58 0.60 0.62 0.64 0.66
RANGE
AT ALTITUDE Orifice Manifold Orifice Manifold Orifice Manifold Orifice Manifold Orifice Manifold
(FT)
(BTU/CU FT) No. Pressure No. Pressure No. Pressure No. Pressure No. Pressure
700 43 3.7 43 3.8 42 3.2 42 3.3 42 3.4
725 43 3.4 43 3.6 43 3.7 43 3.8 42 3.2
750 43 3.2 43 3.3 43 3.4 43 3.5 43 3.6
775 43 3.0 43 3.1 43 3.2 43 3.3 43 3.4
5001 800 43 2.8 43 2.9 43 3.0 43 3.1 43 3.2
U.S.A. Only
17
→Table 7—Model 58ZAV Orifice Size† and Manifold Pressure for Correct Input (Continued)
(Tabulated Data Based on 23,000 BTUH Per Burner, Derated 4 percent per 1000 Ft Above Sea Level)*
AVG GAS SPECIFIC GRAVITY OF NATURAL GAS
ALTITUDE
HEAT VALUE 0.58 0.60 0.62 0.64 0.66
RANGE
AT ALTITUDE Orifice Manifold Orifice Manifold Orifice Manifold Orifice Manifold Orifice Manifold
(FT)
(BTU/CU FT) No. Pressure No. Pressure No. Pressure No. Pressure No. Pressure
575 43 3.0 43 3.1 43 3.2 43 3.3 43 3.4
600 43 2.7 43 2.8 43 2.9 43 3.0 43 3.1
9001 625 43 2.5 43 2.6 43 2.7 43 2.8 43 2.8
U.S.A. Only
b. Adjust manifold pressure to obtain input rate. (3.) After correct manifold pressure is obtained, replace
(1.) Remove regulator adjustment seal cap. (See Fig. 18.) gas valve regulator adjustment screw cap and verify
adjusted gas input rate using method outlined in item
(2.) Turn adjusting screw, counterclockwise (out) to de-
c.
crease manifold pressure or clockwise (in) to increase
manifold pressure. (4.) Burner flame should be clear blue, almost transparent.
(See Fig. 19.)
NOTE: This furnace has been approved for a manifold pressure
of 3.2-in. wc to 3.8-in. wc when installed at altitudes up to 2000 ft. c. Verify natural gas input rate by clocking gas meter.
For altitudes above 2000 ft, the manifold pressure can be adjusted NOTE: High-Altitude Adjustment
from 2.0-in. wc to 3.8-in. wc. United States
At installation altitudes above 2000 ft, this furnace has been
approved for a 4 percent derate for each 1000 ft above sea level.
DO NOT bottom out gas valve regulator adjusting screw. See Table 8 for derate multiplier factor.
This can result in unregulated manifold pressure and result in
excess overfire and heat exchanger failures. Table 8—Altitude Derate Multiplier for U.S.A.
ALTITUDE % OF DERATE MULTIPLIER
NOTE: If orifice hole appears damaged or it is suspected to have (FT) DERATE FACTOR FOR U.S.A*
been redrilled, check orifice hole with a numbered drill bit of 0—2000 0 1.00
correct size. Never redrill an orifice. A burr-free and squarely 2001—3000 8—12 0.90
aligned orifice hole is essential for proper flame characteristics. 3001—4000 12—16 0.86
4001—5000 16—20 0.82
5001—6000 20—24 0.78
6001—7000 24—28 0.74
7001—8000 28—32 0.70
8001—9000 32—36 0.66
9001—10,000 36—40 0.62
* Derate multiplier factor is based on midpoint altitude for altitude range.
EXAMPLE:
92,000 Btuh input furnace installed at 4300 ft.
Furnace Input Derate Furnace Input Rate
BURNER Rate at X Multiplier = at Installation
ORIFICE
Sea Level Factor Altitude
92,000 0.82 75,440
Canada
A93059 At installation altitudes from 2000 to 4500 ft, this furnace must be
derated 10 percent by an authorized Gas Conversion Station. To
determine correct input rate for altitude, see example above and
DO NOT redrill orifices. Improper drilling (burrs, out-of- use 0.90 as derate multiplier factor.
round holes, etc.) can cause excessive burner noise and
misdirection of burner flames. This can result in flame a. Turn off all other gas appliances and pilots.
impingement of burners and heat exchangers, causing b. Start furnace and let operate for 3 minutes.
failures.. c. Measure time (in sec) for gas meter test dial to complete 1
revolution.
18
Table 9—Gas Rate (Cu Ft/Hr)
SECONDS SIZE OF TEST DIAL SECONDS SIZE OF TEST DIAL
FOR 1 1 2 5 FOR 1 1 2 5
REVOLUTION cu ft cu ft cu ft REVOLUTION cu ft cu ft cu ft
10 360 720 1800 50 72 144 360
11 327 655 1636 51 71 141 355
12 300 600 1500 52 69 138 346
13 277 555 1385 53 68 136 340
14 257 514 1286 54 67 133 333
15 240 480 1200 55 65 131 327
16 225 450 1125 56 64 129 321
17 212 424 1059 57 63 126 316
18 200 400 1000 58 62 124 310
19 189 379 947 59 61 122 305
20 180 360 900 60 60 120 300
21 171 343 857 62 58 116 290
22 164 327 818 64 56 112 281
23 157 313 783 66 54 109 273
24 150 300 750 68 53 106 265
25 144 288 720 70 51 103 257
26 138 277 692 72 50 100 250
27 133 267 667 74 48 97 243
28 129 257 643 76 47 95 237
29 124 248 621 78 46 92 231
30 120 240 600 80 45 90 225
;;;;
31 116 232 581 82 44 88 220
32 113 225 563 84 43 86 214
A00238
33 109 218 545 86 42 84 209
34 106 212 529 88 41 82 205 →Fig. 17—Redundant Automatic Gas Control
35 103 206 514 90 40 80 200 Valve
36 100 200 500 92 39 78 196
37 97 195 486 94 38 76 192 BURNER FLAME
38 95 189 474 96 38 75 188
39 92 185 462 98 37 74 184 BURNER
40 90 180 450 100 36 72 180
41 88 176 439 102 35 71 178
42 86 172 429 104 35 69 173
43 84 167 419 106 34 68 170
44 82 164 409 108 33 67 167
45 80 160 400
110 33 65 164
46 78 157 391
112 32 64 161
47 76 153 383
116 31 62 155
48 75 150 375
120 30 60 150
49 73 147 367
R Y W G
If Model 58ZAV 115-22 is installed in 0.50-in. wc or lower
static pressure ductwork, evaporator coil condensate blow off
can occur during cooling operation. When installed in this
manner, do not use high blower speed tap for cooling.
10 TURNS
Table 10—Speed Selector
FACTORY-
COLOR SPEED FROM UNIT 24-V
ATTACHED TO
CONTROL TERMINALS
Black High COOL
Yellow (When EXAMPLE: 5.0 AMPS ON AMMETER = 0.5 AMPS FOR THERMOSTAT
Medium-High SPARE 10 TURNS AROUND JAWS ANTICIPATOR SETTING
present)
Blue Medium-Low HEAT
A96316
Red Low SPARE
White Common L2/COM Fig. 19—Amp Draw Check With Ammeter
CHECK SAFETY CONTROLS
The flame sensor, gas valve, and pressure switch were all checked
in the Start-up Procedures section as part of normal operation.
1. Check primary limit control.
Recheck temperature rise. It must be within limits specified
This control shuts off the combustion control system and
on unit rating plate. Recommended operation is at midpoint of
energizes the circulating-air blower motor if the furnace
rise or above.
overheats.
3. Set thermostat heat anticipator. The preferred method of checking the limit control is to
The thermostat heat anticipation must be set to match the amp gradually block off the return air after the furnace has been
draw of the electrical components in the R-W circuit. Accurate operating for a period of at least 5 minutes. As soon as the
amp draw readings can be obtained at thermostat subbase limit has shut off the burners, the return-air opening should be
terminals R and W. Fig. 19 illustrates an easy method of unblocked. By using this method to check the limit control, it
obtaining the actual amp draw. The amp reading should be can be established that the limit is functioning properly and
taken after the blower motor has started. See the thermostat operates if there is a motor failure.
manufacturer’s instructions for adjusting the heat anticipator 2. Check blocked vent safeguard switch.
and for varying the heating cycle length.
The purpose of this control is to permit the safe shutdown of
NOTE: When using an electronic thermostat, set cycle rate for 3 the furnace during certain blocked vent conditions.
cycles per hr.
a. Disconnect power to furnace and remove vent connector
from furnace outlet collar. Be sure to allow time for vent
pipe to cool down before removing.
b. Restore power to furnace and set room thermostat above
room temperature.
c. After normal start-up, allow furnace to operate for 2
minutes, then block flue outlet 100 percent. Furnace should
cycle off within 2 minutes.
d. Remove blockage and reconnect vent pipe to furnace outlet
collar.
e. Wait 5 minutes and then reset blocked vent safeguard
switch.
3. Check pressure switch.
This control proves operation of draft inducer blower.
a. Turn off 115-v power to furnace.
b. Remove control door and disconnect inducer motor lead
wires from wire harness.
c. Turn on 115-v power to furnace.
20
d. Set thermostat to "call for heat" and wait 1 minute. When g. If furnace operates for 4 minutes, check/replace limit
pressure switch is functioning properly, hot surface igniter switch(es).
should NOT glow and control diagnostic light flashes a h. Turn off 115-v power to furnace.
status 31. If hot surface igniter glows when inducer motor
is disconnected, shut down furnace immediately. Deter- i. Remove blower access door.
mine reason pressure switch did not function properly and j. Reconnect red motor lead, reset switch, and replace door.
correct condition.
k. Turn on 115-v power to furnace.
e. Turn off 115-v power to furnace.
f. Reconnect inducer motor wires, replace control door, and CHECKLIST
turn on 115-v power to furnace. 1. Put away tools, instruments, and clean up debris.
4. Check auxiliary limits (when used).
2. Verify manual reset switches have continuity.
a. Turn off 115-v power to furnace.
3. Ensure blower and control access doors are properly installed.
b. Remove blower access door.
4. Cycle test furnace with room thermostat.
c. Disconnect red motor lead at blower speed selector. Mark
terminal for proper reconnection. 5. Check operation of accessories per manufacturer’s instruc-
tions.
d. Replace blower access door.
e. Turn on 115-v power to furnace. Be sure room thermostat 6. Review User’s Manual with owner.
is calling for heat. 7. Leave literature packet near furnace.
f. Allow furnace to operate until auxiliary limit activates, but
DO NOT operate furnace longer than 4 minutes.
21
CHECKLIST—INSTALLATION
LOAD CALCULATION CHECKLIST—START-UP
22
23
SERVICE TRAINING
Classroom Service Training plus "hands-on" the products in our labs can mean
increased confidence that really pays dividends in faster troubleshooting, fewer
callbacks. Course descriptions and schedules are in our catalog.
Copyright 2000 CARRIER Corp. • 7310 W. Morris St. • Indianapolis, IN 46231 58zav12si
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4 PC 101 Catalog No. 535-768 Printed in U.S.A. Form 58ZAV-12SI Pg 24 10-00 Replaces: 58ZAV-10SI
Tab 6a 8a