Calculation power load

Equipment Power
Power Need
Name of the panel factor
Capacity Factor(Kc) Active Reactive Calculation Setting
(CosФ)
(KW) power (KW) power (KVAR) current (A) current (A)

AL 100 0.8 0.85 80 49.57 135.847122162 160


AK 60 1 0.8 60 45 108.253175473 125
1ATXB/(Fire pump) 6 1 0.8 6 4.5 10.8253175473 32
1ATSB 3 1 0.8 3 2.25 5.4126587737 16
Conductor section & dimension and length

Conductor Voltage Voltage


section(underground)/ length(m) length*1.2 Drop(factor)/ drop(mV)
(mm²) (mV/A/m)
70 87.159 104.5908 0.6 0.917863
50 32.635 39.162 0.87 2.776927
6 21.162 25.3944 6.8 8.568818
2.5 21.162 25.3944 16 10.08096