ISSUE : SHEET OF
PROJECT : QUANTITY
OPERATING CONDITIONS
TEMPERATURE MIN. : ( ) °c OPER. : ( AMB ) °c DESIGN : ( )C
2
PRESSURE OPER. : ( ) kg/cm DESIGN : ( ) kg/cm2 HYDRO TEST : ( ) kg/cm2
FLUID HANDLED ■ WATER AND/OR □ SEA WATER
■ FOAM-WATER SOLUTION
INSTALLATION ■ OUTDOOR AND/OR ■ INDOOR
DESIGN FEATURES
TANK TYPE □ HORIZONTAL
□ VERTICAL □ ATMOSPHERIC □ INTERNAL BLADDER
TANK CAPACITY LITER ( * GALON )
□ PRESSURE PROPORTIONER □
PRESSURE SIDE PROPORTIONER
□
(2) SIZE
□ □ 1-1/2" □ 2" □ 2-1/2"
□ □ 4"
□ ANSI □ KS □ R.F □ F.F
□ 150LBS □ 300LBS □ 10K □ 20K
(3) PROPORTIONING □ 3% □ 6% □ 3% x 6%
(4) ACCESSORIES
□ BLANCED DIAPHRAGM CONTROL VALVE
□ PNEUMATIC □
MOTER OPERATED □ MANUAL
□ GENERAL □
WEATHER PROOF □ EXPLOSION PROOF
□ BALL□
BYTTERFLY
□ GATE
□ FOAM FLUSH-IN & FLUSH OUT CONNECTOR
□ FOAM SKID CONTROL PANEL
□ GENERAL □
WEATHER PROOF □ EXPLOSION PROOF
□ PRESSURE RELIEF VALVE
2
3
4
^SHINWHA FOAM TANK (2/2) JOB NO. :
Fire Specialist DATA SHEET RFQ. NO. :
ISSUE : SHEET
01
MATERIALS
02
PUMP CASING CAST IRON CAST STEEL STAINLESS STEEL
03
BALANCED DIAPHRAGM CONTROL VALVE BRASS BRASS
□ STAINLESS STEEL
04
CONTROL VALE CAST IRON
□ CAST STEEL
□ STAINLESS STEEL
05
FOAM SKID CONTROL PNAEL CARBON STEEL STAINLESS STEEL
06
PRESSURE RELIEF VALVE BRASS BRASS STAINLESS STEEL
07
FOAM SUCTION & DISCHARGE PIPE, FITTING, VALVE CARBON STEEL STAINLESS STEEL
08
WATER LINE & FOAM SOLUTION DISCHARGE LINE CARBON STEEL
□ STAINLESS STEEL
09
ACCESSORIES
□
3 11 12
LEVEL GAUGE □ VENT VALVE □ FILLING CAP
□ DRAIN VALVE □
WATER INLET PIPING
□14 NAME PLATE □ ACCESS LADDER □ EXPLANATION BOARD FOR OPERATING PROCEDURE
15
TEST & INSPECTION
16
DIMENSION INSPECTION
■ WITNESS □
REVIEW MATERIAL INSPECTION
□ WITNESS ■ REVIEW
17
VISUAL INSPECTION
■ WITNESS □
REVIEW PERFORMANCE TEST
□ YES ■ NO
18
FINISH UNIT WEIGHT
19
PAINTING ( *)
13 COLOR
2
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
48
49
BLADDER TANK
PROPORTIONING SYSTEM
TECHNICAL DATA :
TANK MOUNTING TYPE Vertical or Horizontal
FACTORY TEST
18 Bar (261 PSI)
PRESSURE
The bladder tank proportioning system operates on same principle as that of a balance pressure proportioning system. In
bladder system, the bladder is used as diaphragm to separate the water and foam concentrate within the tank. The
foam concentrate is injected into the ratio controller utilising water pressure.
The system is also supplied with foam concentrate control valve as an optional item. The valve allows concentrate flow
only when minimum of 3.0 kg/sq.cm. water pressure is established in the system. For pressure drop and flow
characteristics refer catalogue of ratio controller.
After few initial successful tests an authorised person must be trained to perform inspection and testing of the system. It is
recommended to carry out physical inspection of the system regularly, the inspection should verify that no damages
have taken place to any component and all the valves are in their proper position as per the system requirement. The
system should be fully tested at least once in a year and in accordance with applicable NFPA/TAC code or in
accordance to the guidelines of the organisation having local jurisdiction.
Do not turn off the system or any valve to repair or test the system, without placing a roving Fire Patrol in the area
covered by the system. The patrol should continue until the system is put back in service. Also inform the local
security personnel and the control room so that a false alarm is not signalled.
CAUTION
1. Do not weld on the tank as it may damage the bladder.
3. Sight glass is not pressure tight, so before taking concentrate level reading, tank pressure must be released.
4. The bladder tank is to be installed under a shade to avoid direct sunlight on the equipment.
NOTE
1. The foam concentrate is to be filled in the bladder very carefully to avoid rupture of the bladder. The filling
guideline provided with the equipment must be adhered to strictly.
2. Air supply with regulator (0 to 1.0 kg/sqcm) required during filling procedure, to be provided by user/ installer
3. Water supply at 0-1.5 kg/sqcm required for tank filling during commissioning , to be provided by installer/user.
FOAM
SOLUTION
OUTLET
MATERIAL OF CONSTRUCTION
SR.NO. DESCRIPTION SPECIFICATION
1 VALVE SS / BRONZE
FOAM CONCENTRATE SS / BRONZE
2 SHUT OFF VALVE
3 WATER SHUT OFF VALVE SS / BRONZE
4 LEVEL INDICATOR GLASS/ ACRYLIC
5 PRESSURE GAUGE 0-16 KG/ SQCM
6 CHECK VALVE SS/ BRONZE
7 SPOOL PIECE CARBON STEEL
8 RATIO CONTROLLER BRONZE
9 BLADDER THERMOPLASTIC
RUBBER
10 TANK CARBON STEEL
11 NAME PLATE BRASS
12 WATER LINE PIPING CARBON STEEL
13 FOAM CONCENTRATE SS
PIPING
4—M16 ANCHOR BOLT ft NUT
N O T E
ONE FINISH(RED)CQATING
P L A N ( s none )
FOUNDATION
BLADDER WfflK
1 riKi 400 GAL
WATER INLET BALL VALVE 1 U*B
FOAM OUTLET BALL VALVE SCS13
1 l^B
SAFETY VALVE SCPHe
1 IB
LEVEL GAUGE TUBE TEFLON
1 3/4B
PRESSURE GAUGE 2 "flS&L/rrf
-
N O T E
BLASTING
ONE FINISH(RED)COATING
DESIGN DATA
DESIGN PRESSURE ID KG/Cn
□PERATING PRESSURE 7 KG/Cn
TEST PRESSURE 15 KG/Cn
CAPACITY 1514 LIT
CHIRR, ALLOWANCE 1 nm
JOINT EFF. SHELL 95% HEAD !□□%
EMPTY 660
WEIGHT (KG) OPERATING 1500
TEST 2160
NOMENCLATURE
MAT' L SPECIFICATION
SHELL PLATE SS400 1 9t
PART LIST
PROUCTNAME FOAM TANK (1500 LITER)
CHECKD
3RD
DESIGN
APPR
VIEW
SCALE
DATE
M SHIN WHA YSFT-1500-2 MODEL NC
PRDPDRTIDNER W/HDUSING
Specialist
YS-FTVPP-1500
Fire
REVISION NO DWG. NO
0SHINWHA Fire Specialist
90*
M SHIN WHA
Specialist
Fire
£240
1640
L
J ^m
T m s
1
1=1
/
2
1440
^ =s s=
“ T4
E ioeo 4-M16 x 300L ANCHDR BDLT 8. NUT
P L A N < s i none)
1, PAINTING i INSIDE i EPOXY COATING AFTER SAND
BLASTING
LEVEL
5 GAUGE TUBE 1
PRESSURE
6 GAUGE 2
SHELL
7 SIDE DRAIN VALVE 1 BRONZE 1B(BALL)
CONCENTRATE
8 VENT VALVE 1 BRONZE 1B< BALL)
FILL LINE
9 MASTER VALVE 1 BRONZE 1B<BALL)
CONCENTRATE
10 F ILL8.DRAIN 1 BRONZE 1B<BALL)
VENT
11 VALVE 1 BRONZE 1B<BALL)
VENTURI
12 1 BRONZE
A1U6
CONCENTRATE
13 CONTROLLER 1 #4U
GAI ' V
FILL14CUP 1 STS304 65A x 25A
BRACKET
15 SS400
2 C100x50x5t
NAME
16 PLATE 1
CHECK
17 VALVE CAST 1 1/2B
1 STEEL
PART LIST
F O U N D AT I O N F O R P U M P S K I D F O U N D AT I O N F O R F O A M TA N
K
PROUCT NAME FOUNDATION
DESIGN CHECKD APPR VIEW 3RD
SCALE 1:1
DATE 2002. 5.15REVISION NO 0
DWG. NO YSFT-4500—102 MODEL NC YS-FTHPSP-4500
FLUSH
14 CONNECTIONS) STS304
2“, KS 10K, FF
FLUSH
13 C0NNECTI0NI1) STS3042", KS 10K, FF
CONTROL PANEL -
12
MOTOR/PUMP -
11
PROPORTIONER
10 STPG
BALANCE
9 VALVE BrC
SAFETY VALVE BrC
8
PRESSURE
7 GAUGE - PT 1/2"
MOTER
6 DPER. VALVE STS3042", KS 10K, FF
BY-PASS
5 VALVE STS304
FOAM
4 RETURN SHUT OFF STS304
FOAM
3 SUPPLY SHUT OFF STS304
DRAIN
2 VALVE STS304
FOAM
1 STORAGE TANK STS304
NO. PART NAME MATERIAL REMARK
STS304 1
COVER BrC 1
BrC 1
PART NAME MATERIAL REMARKS
PART LIST
°J------------1
FOAM TANK
KS B 6231
MODEL NO. I YS-FT I CODE DESIGN (^aetaaae. KISHL>
Kg/cmLG / AHB.T
PRESSURE/TEMP WORKING PRESSURE HYDRO.
TEST PRESSURE R.T/P.W.H.T Kg/crf.G
DATE I 20 . .I /NO
Liter
YS-
?±ISIA)
YOOK SONG FIRE SOLUTION CO., LTD. A) ¥41 031)672-9961-3
'
200
220
D E TA I L " O P E R AT I N G P L AT E "
NOTES
ja
VOLUME CALCULATION SHEET STRENGTH CALCULATION SHEET
FOAM TANK
1) Applied Codes KS B 6231
9) P W H T N/A
= 4.934 ms
PROUCT NAME CALCULATION
Specialist
0SHINWHA Fire Specialist
DESIGN DATA
r | 600 | | 15 PIPE
16 EARTH LUG
SPPS38
STS304
26B
16-t
18t |18L 18-t 17 LIFTING PAD SB410 212-t
18 SLIDING PLATE SB410 118-t
19 WEB PLATE SB410 2 18t
20 NAME P. BRCKET SS400 12, 3t
21 BRACKET SS400 2100x50x1 t CHANNEL
22 BLADDER BUNA N
11, 2-t 2800 GAL
RUBBER
23 WATER INLET V/V SCPHa 1 2B BALL VALVE
24 SAFETY VALVE SCPHa 111/4B BALL VALVE
25 LEVEL GAUGE TUBI TEPHRDI 11 3/4 B
26 m\> me A105 1 IB BALL VALVE
27 FOAM OUTLET V/V SCPHa 1 2B BALL VALVE
28 WfeLINL A105 1 IB BALL VALVE
UUNULN1 HA 1L
29 A105 1 IB BALL VALVE
FILL8.DRAIN V/V
30 WATER VENT V/V A105 1 IB BALL VALVE
31 FILL CUP STS304 165x25 REDUCER
32 CHECK VALVE SCPHa 1 2B
33 CONCENT, VENT V/' ' A105 1 IB BALL VALVE
PART
PROUCT NAME FOAM LIST
TANK (11000 LITER)
DESIGN
CHECKD APPR VIEW 3RD
CONCENTRATE CONTROLLER DETAIL
DWG.
DATENO 2002.5.15MODEL
YSFT-11000-1 REVISION SCALE
NC YS-FTHPP-1100C
NO