Eg Measurements SERVICE MANUAL MCGG 01 Series Overcurrent relay for phase and earth faults contents DESCRIPTION SEPTLNGS INSTALLATION commtssTONTNe MAINTENANCE 6 PROBLEM ANALYSIS Page 3 DESCRIPTION Overcurrent relay type NOGG provides a choice of four inverse tine and three definite cime ranges by switehed selection, and is available in the Following uodels: MODEL NUMBER oDEL. yoce 12 Single pole phase fault Single pole earth fault Mose 21 Single pole phase fault with Instantaneous element Single pole earth fault with Instantaneous eleaent Moco 31 J pole phase fault Mose 41 2 pole phase fault plus earth fault 5 Moce 51 2 pole phase fault with instantaneous elemeat plus earth faule Meoe 61 3 pole phase fault with {astantaneous elenent ‘The rated current of the relay (Jy) is either 1 Aup or 5 Amp and appears on the nodule rating card. 2. SETTINGS The relay settings are determined by positioning miniature evitches on the relay front panel. If the relay is ficted with an instantaneous element, there vill be two groups of svitehes, the time/current setting ewicches positioned above the instantaneous elesent switches. Note: An MGC 41 or 51 can be treated as two separate relays, with separate settings for phase and earthfault elements.