Вы находитесь на странице: 1из 6

CLIENT M/S GUJARAT ENERGY TRANSMISSION CORPORATION LTD.

PROJECT 400/220/66kV PANCHAM (FEDRA) GIS SUBSTATION


LOA REF. NO. CE(Projects)/SE(Proj)/V/400kV GIS/4352,4353,4357 Dtd.16.11.2017
CONTRACTOR M/s GODREJ & BOYCE MFG CO LTD.
TITLE DESIGN CALCULATION- SINGLE BUSDUCT FOUNDATION
DRG. NO. SVP010050 -PAC-C-DES-203a
REVISION 0
PREPARED BY DDP
CHECKED BY IK
APPROVED BY IK
DATE 07.02.19

0 FOR APPROVAL 07.02.19


REVISION DESCRIPTION DATE
Foundation support reaction for C02 bay

Load Point Load Case FX (kN) FY (kN) FZ (kN) MX (kN-m) MY (kN-m) MZ (kN-m) MX + Fy MY+Fx
LC 1 0 0 -12 0 0 0 0 0
LC 2 9 1 -3 2 -16 0 3 -7
LC 3 0 0 0 0 0 0 0 0
LC 4 -2 0 1 1 2 0 1 0
LC 5 0 -13 0 -46 0 0 -59 0
217
LC 6 0 0 1 0 0 0 0 0
LC 7 0 0 0 0 0 0 0 0
LC 8 -5 0 3 1 6 0 1 1
LC 9 0 -18 0 -59 0 0 -77 0
LC 10 0 0 -14 0 0 0 0 0

9 1 3 2
-5 -18 -14 -59
DOC:
GODREJ BOYCE LTD DESIGN OF FOOTING
REV : R0

DESIGN OF BI-AXIAL ISOLATED RCC FOOTING (IS 456, 2000)


LOADS FROM ANALYSIS - SUPPORT REACTIONS FOR INDIVIDUAL FOOTING

Load (T) Moments (T.M)


Load Case MX( @X ) MY( @Y)
P TM TM
217
LC11 -0.612 0.000 0.00
LC12 -0.714 0.204 -0.357
LC13 -0.765 -2.854 -0.357
LC14 -0.714 0.153 -0.357
LC15 -0.765 0.153 -0.357
LC16 -0.897 0.204 -0.306
LC17 -1.417 0.173 -0.336
LC18 -1.050 -3.77 -0.36
LC19 -1.478 -1.417 -0.357
1.478

COLUMN/PEDESTAL
Depth of footing from NGL = 1
Length (l, dim. || Z axis ) = 450 mm
global
Breadth (b, dim. || X axis) = 450 mm
Y
Height of pedestal = 0.8 m Breadth 2 m

FOOTING global
global
Foot length (L, dim. || X axis) = 1.4 m X
X
Foot Breadth (B, dim. || Y axis) = 2 m
Thickness of footing (t) = 200 mm global
Clear cover to Reinforcement = 50 mm Y
Main bar dia of footing = 12 mm
Effective depth of footing = 144 mm Length 1.4 m
Selfweight of the footing = 1.40 T Footing Dimensions
Area of Footing(A) = 2.80 m2
Sect mod of foot about X axis (Xz) = 0.93 m3
Sec mod of foot about Y axis (Yx) = 0.65 m3
MATERIALS OF CONSTRUCTION
2
Grade of concrete fck = 25 N/mm
2
Grade of steel fy = 500 N/mm

Safe NET bearing pressure = 5 T/m2


Safe gross bearing pr. = 7.85 T/m2 (net pr. + depth of foot * soil unit wt)
Factor of overstressing 1.25
Unit wt of soil = 1.6 T/m3
Weight of soil retained above foot = 3.32 T

CALCULATION OF PRESSURES
P (T) Moments (T.M) Soil
Pmax Pmin Actual /
Load Case (Incl self wt overstress
(T/m2) (T/m2) Allowable
+ soil wt MX(@X) My(@Y) Factor
217
LC11 5.34 0.000 0.000 1 1.91 1.91 0.29
LC12 5.44 0.204 0.357 1 2.71 1.18 0.34
LC13 5.49 2.854 0.357 1 5.56 -1.64 0.71
LC14 5.44 0.153 0.357 1 2.65 1.23 0.34
LC15 5.49 0.153 0.357 1.25 2.67 1.25 0.34
LC16 5.62 0.204 0.306 1.25 2.69 1.32 0.34
LC17 6.14 0.173 0.336 1.25 2.89 1.49 0.37
LC18 5.77 3.772 0.357 1.25 6.65 -2.52 0.85
LC19 6.20 1.417 0.357 1.25 4.28 0.15 0.55

5.34 3.77 OK 0.85

Maximum bearing pressure = 6.65 T/m


2 P M y M x
2
 
Minimum bearing pressure = -2.52 T/m A Zy Zx
Hence footing is safe against max gross bearing pr.

FOR DESIGN OF FOOTINGS


Maximum effective soil pressure pe max 6.65
2
( Pu/Area+ Muz/Zz + Mux/Zx) - Psoil - Pconc = 4.96 T/m
Design of footing is done using above maximum effective soil pressure
F.O.S against overturning = 5.77 x 2 / 2
= 3.77

= 1.53 > 1.5 SAFE

F.O.S against sliding = 5.77 x 0.6


1.835
= 1.89 > 1.5 SAFE

Maximum overhang = 2.00 - 0.45


2.00
= 0.775 m

2
Maximum bending moment = 4.96 x 0.775 = 1.49 tm
2
Factored maximum moment = 1.50 x 1.5
= 2.22 tm
Effective depth d = 120 mm

Mu/bd2 = 21784794 = 1.51 N/mm2


2
1000 x 120
% steel = 0.375 %
Minimum % steel = 0.12 %
2
Ast required = 449.48 mm

Assume diameter of bars as = 10 mm


centre to centre spacing = 150 mm OK
2
Ast provided = 523.5 mm
Hence provide 10 mm @ 150 mm c/c at Bottom
10 mm @ 250 mm c/c at Top
Check for shear:-
one way shear
Maximum shear at a distance "d" from the face of the column

Overhang from the face of the column = 0.775 - 0.12


= 0.655 m
Shear force = 4.96 x 0.655
= 3.25 t

Factored Shear force Vu = 3.25 x 1.50 = 4.875 t

Maximum shear stress Tv = 48753 = 0.41 N/mm2


1000 x 120
For pt '= 0.44
b factor = 6.65
Permissible shear stress = t c = 0.46 N/mm2 SAFE

Two way shear


Critrical section at d/2 from face of pedestal = 60 mm
Perimeter for fractured pyramid = 2 * (B1+d+L1+d) = 4920 mm
Area of fractured pyramid = (B1+d) * (L1+d) = 1.1457 m2

Punching shear = V = (A-Pyramid Area) * P Max = ( 2.80 - 1.15 ) x 4.96


= 8.209 Ton
Eff depth at critical section = 120 mm

Shear stress = Vu / (Perimeter * Min Depth) = 0.21 N/MM2

Allowable shear stress = 0.25 * SQRT(Fck) = 1.25 N/MM2 HENCE SAFE


Design of Pedestal
Pedestal size = 0.45 x 0.45 m
Vertical load on each pedestal = 1.478 t

self weight of pedestal = 0.45 x 0.45 x 1.25 x 2.5


= 0.63 t

Total vertical load = 1.478 + 0.63 = 2.11 t

shear at plinth level = 0.50 t

Moment at the base of the pedestal = 0.50 x( 1.25 - 0.2 )


= 0.53 tm
0.25

1.0

0.2

2.00
Factored Total vertical load = 2.11 x 1.5 = 3.17 T
Factored Moment at the base of the pedestal =( 3.17 + 0.53 ) x 1.5 = 5.54 Tm

COMPRESSION WITH BENDING Pu/fck b d = 0.0063 Mu/fck b d2 = 0.0000

lef = 1.1 x 2 = 2.10 m


lef / D = 4.67 < 12 Short Column

Total Moment = 5.54 + 0.00 = 5.54 Tm

Since Load is is very less only minimum reinforcement as per cl. 26.5.3(b) of IS 456 will be required.

Concrete area required to resist direct vertical load= 3.17 x 10000


0.36 x 25.00
= 3518.16 mm2

Minimum Ast required = 0.8 % of the concrete area required to resist direct vertical load

= 0.80 x 3518.2 = 28.15 mm2


100.00
Provide longitudinal reinforcement of 8 nos 12 dia

Ast Provided = 904.32 mm2


Spacing between reinforcement = 185.00 < 300 OK
Design for lateral ties :
Spacing of lateral ties shall be least of the following :-

I) Least lateral dimn of column = 450.00 mm


ii) 16 x dia of longitudinal reinf = 16.00 x 12 = 192.00 mm
iii) 48 x dia of transverse reinforcement= 48.00 x 8 = 384.00 mm

Provide 8 Dia Links at 190 c/c