INSPECTION TEST RECORD (ITR) - C

FIRE & GAS DEVICE LOOP TEST I16-C


Project No.
Project Title
Facilities
GENERAL
Platform/ Plant
Name
Sys Number Sys Description
FIRE & GAS DEVICE DATA
Type of Detector Heat Smoke Flam Gas Breakglass Other (To Specify):____
Tag Number Signal Range Manufacturer
Method of
Classifying Authority Model Number
detection
Area Protected EX Protection Serial Number
IP Rating Data Sheet Loop Drawing
COMMISSIONING CHECK OK N/A P/L No

1 Verify completeness of pre-commissioning checksheet I16-B

2 Verify no damage to the Fire & Gas device during transportation (offshore)

3 Verify all cables are secured and no damage

4 Verify the Junction Boxes are secured and no damage

5 Verify the correct electric power supply is connected to the Fire and Gas panel

6 Verify all tools/equipment/test kits for the loop test are available

7 Verify local indication/display (if applicable), are correctly activated upon testing of the loop

8 Verify all theindication/display in FGS Panel are correctly activated upon testing of the loop

Verify the indication/display in DCS (if applicable) are correctly activated upon testing of the
9
loop
Verify the indication/display and actions in Shutdown Systems (if applicable) are correctly
10
activated upon testing of the loop as per cause and effect matrix

11 Verify no dust inside Enclosure /Cabinet / Panel and insulation surfaces are clean.

12 Verify Instruments & its Accessories /Electrical equipment/Panel externally clean.

REFERENCE DRAWINGS
1 Loop Drawings
2 FGS Cause & Effect Matrix (if applicable)
3 Vendor Drawings
OBSERVATION / REMARKS