Spread footing verification


Input data
Settings
USA - Safety factor
Materials and standards
Concrete structures : ACI 318-11
Settlement
Analysis method : Analysis using oedometric modulus
Restriction of influence zone : by percentage of Sigma,Or
Coeff. of restriction of influence zone : 10.0 [%]
Spread Footing
Analysis for drained conditions : NCMA
Verification methodology : Safety factors (ASD)
Safety factors
Permanent design situation
Safety factor for vertical bearing capacity : SFv = 2.00 [–]
Safety factor for sliding resistance : SFh = 1.50 [–]
Basic soil parameters
jef cef g gsu d
No. Name Pattern
[°] [kPa] [kN/m3] [kN/m3] [°]

1 agua 80.00 1.00 0.10 0.00 80.00

All soils are considered as cohesionless for at rest pressure analysis.

Soil parameters
agua
Unit weight : g = 0.10 kN/m3
Angle of internal friction : jef = 80.00 °
Cohesion of soil : cef = 1.00 kPa
Oedometric modulus : Eoed = 1.00 MPa
Saturated unit weight : gsat = 0.10 kN/m3

Foundation
Foundation type: strip footing
Depth from original ground surface hz = 5.30 m
Depth of footing bottom d = 0.00 m
Foundation thickness t = 0.60 m
Incl. of finished grade s1 = 0.00 °
Incl. of footing bottom s2 = 21.25 °
Unit weight of soil above foundation = 0.10 kN/m3

Geometry of structure
Foundation type: strip footing
Overall strip footing length = 3.05 m
Strip footing width (x) = 1.80 m
Column width in the direction of x = 0.10 m
Volume of strip footing = 1.08 m3/m
Inserted loading is considered per unit length of continuous footing span.

1
[GeoStructural Analysis - Cantilever Wall | version 5.16.13.0 | Copyright © 2013 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]
danny

Material of structure
Unit weight g = 24.00 kN/m3
Analysis of concrete structures carried out according to the standard ACI 318-11.

Concrete : Concrete ACI


Compressive strength fc' = 21.00 MPa
Tensile-bending strength fr = 2.85 MPa
Elasticity modulus Ecm = 21689.22 MPa
Longitudinal steel : A616/60
Tensile strength fy = 420.00 MPa
Transverse steel: A615/40
Tensile strength fy = 275.79 MPa
Geological profile and assigned soils
Layer
No. Assigned soil Pattern
[m]

1 5.30 agua

2 - agua

Load
Load N My Hx
No. Name Type
new change [kN/m] [kNm/m] [kN/m]
1 YES LC 1 Service 85.47 56.88 0.00
2 YES LC 2 Design 85.47 56.88 0.00
Global settings
Analysis type : analysis for drained conditions

Settings of the stage of construction


Design situation : permanent

Verification No. 1
Load case verification
ex ey s Rd Utilization
Name Is satisfied
[m] [m] [kPa] [kPa] [%]
LC 2 -0.51 0.00 143.04 5374303522.68 0.00 Yes
Analysis carried out for the load case No. 2. (LC 2)

Computed self weight of strip foundation G = 25.92 kN/m


Computed weight of overburden Z = 0.00 kN/m
Vertical bearing capacity check
Shape of contact stress : rectangle

Parameters of slip surface below foundation:


Depth of slip surface zsp = 5.39 m
Length of slip surface lsp = 21.73 m
Design bearing capacity of found.soil Rd = 5374303522.68 kPa
Extreme contact stress s = 143.04 kPa

Factor of safety = 37571894.77 > 2.00

2
[GeoStructural Analysis - Cantilever Wall | version 5.16.13.0 | Copyright © 2013 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]
danny

Bearing capacity in the vertical direction is SATISFACTORY

Horizontal bearing capacity check


Earth resistance: 1/2 pass., 1/2 at rest
Design magnitude of earth resistance Spd = 0.00 kN
Friction angle foundation-footing bottom y = 80.00 °
Cohesion foundation-footing bottom a = 1.00 kPa
Horizontal bearing capacity Rdh = 632.52 kN
Extreme horizontal force H = 0.00 kN

Factor of safety = 1000.00 > 1.50


Bearing capacity in the horizontal direction is SATISFACTORY

Bearing capacity of foundation is SATISFACTORY

Verification No. 1
Settlement and rotation of foundation - input data
Analysis carried out with automatic selection of the most unfavourable load cases.
Analysis carried out with accounting for coefficient k1 (influence of foundation depth).
Stress at the footing bottom is not considered.

Computed self weight of strip foundation G = 25.92 kN/m


Computed weight of overburden Z = 0.00 kN/m
Settlement of mid point of longitudinal edge = 112.2 mm
Settlement of mid point of transverse edge 1 = 169.6 mm
Settlement of mid point of transverse edge 2 = 64.4 mm
(1-max.compressed edge; 2-min.compressed edge)

Settlement and rotation of foundation - results

Foundation stiffness:
Computed weighted average modulus of deformation Edef = 0.95 MPa
Foundation in the longitudinal direction is rigid (k=848.21)
Foundation in the direction of width is rigid (k=4946.76)

Overall settlement and rotation of foundation:


Foundation settlement = 140.8 mm
Depth of influence zone = 23.62 m
Rotation in direction of width = 58.430 (tan*1000)

Dimensioning No. 1
Analysis carried out with automatic selection of the most unfavourable load cases.

Verification of longitudinal reinforcement of foundation in the direction of x


Bar number = 5
Number of bars = 5
Reinforcement cover = 50.0 mm
Cross-section width = 1.00 m
Cross-section depth = 0.60 m
Reinforcement ratio r = 0.18 % > 0.18 % = rmin
Position of neutral axis c = 0.03 m < 0.23 m = cmax
Ultimate moment fMn = 198.43 kNm > 41.23 kNm = Mu

3
[GeoStructural Analysis - Cantilever Wall | version 5.16.13.0 | Copyright © 2013 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]
danny

Cross-section is SATISFACTORY.

Spread footing for punching shear failure check


Verification for punching shear has not been performed due to shape of the critical cross-section.

Name : Dimensioning Stage : 1; Dimensioning : 1

Plan: Punching shear - critical cross-section:


B
Loading area
1.00 transmitted by RC through shear

A A critical cross-section
length: 2.00m
B
1.80

Section A-A: Section B-B:

0.60

5 no. diam. 5,
length 1.70m, concrete cover 40.0mm

4
[GeoStructural Analysis - Cantilever Wall | version 5.16.13.0 | Copyright © 2013 Fine spol. s r.o. All Rights Reserved | www.finesoftware.eu]