Вы находитесь на странице: 1из 8

Securing power

Mitigation of voltage collapses in large urban grids


by means of SVC

ROLF GRÜNBAUM, PETER LUNDBERG, BJÖRN THORVALDSSON years has meant that grid companies can no longer rely on
– Recent blackouts in Europe as well as the United States generators for reactive power, ie, transmission suppliers may
have focused attention on the importance of a secure and have to provide their own var (volt-ampere reactive). The fast
reliable supply of power to homes, public institutions and and adequate supply of reactive power is required to main-
industry. It is now recognized that a significant number of tain stable voltages, especially when high percentages of
grids are plagued by underinvestment, exacerbated by the induction motor loads, such as those created by air condi-
uncertainty of roles and rules within the electricity supply tioners in urban areas, are dominant in the grid and during
industry brought about by deregulation. For instance, the system faults. SVCs (static var compensators) are a solution
unbundling of power generation and transmission in recent well adapted to meet the challenges in question.

Securing power 49
degree. If the reactive power supply is
1 Voltage variation at a load busbar as a
limited, the increased loading on the line function of loading with and without SVC
will cause a voltage drop over the sys-
tem. If reactive power is not provided at
this time, the voltage can fall precipitous-
ly. The transmission system can no lon-
ger transfer electrical energy and a sys-

Voltage
tem blackout will follow.

It is apparent that provision of the right


kind of reactive power (with proper dy-
namic characteristics) at the right mo- Power

ment and at the right locations provides With SVC of infinite rating

potent methods to prevent, or at least Uncompensated


With SVC of limited rating
limit, blackouts. This is where ABB’s SVC
can play a critical role.

Fast var, slow var


2 Single-line diagram of generic system
Reactive power can be supplied, not only
by SVC, but also by MSCs (mechanically
switched capacitors). There are, howev-
er, some vital distinctions to be made. IM

While the SVC provides fast vars, an Grid Line Load

MSC is a provider of slow vars. This


means that the MSC is very useful in sit-

A
vital characteristic of the SVC uations where there are no particular re-
3 Load torque and machine torques as
is its ability to provide reactive quirements on dynamic response or fre- functions of speed and machine currents
power in grids for a variety of quent operation, such as steady-state
situations, thereby helping to voltage support to follow 24-hour load
maintain, or, in the most difficult cases, patterns. For more demanding applica- 1

restore stable operating conditions to tions, MSCs fall short, and SVCs (or in-
0.8
deed STATCOMs 1 will be needed.
Torque/current

grids. The article focuses on a current


case where SVCs are used successfully 0.6
for dynamic voltage stabilization in power Dynamic voltage stability
0.4
grids dominated by heavy loads with a The introduction of an SVC at a critical
large percentage of induction motors for load point will serve as a powerful tool 0.2
air conditioning. for dynamic voltage support that will en-
0
hance the stability margin. The ability of 0 0.2 0.4 0.6 0.8 1
SVCs are part of the FACTS (flexible AC an SVC to maintain a constant voltage at Speed (m/s)

transmission systems) family of devices the load point of a certain grid configura- Current

that are applied to power systems for a tion is dependent on the SVC rating and Machine torque
Load torque
variety of tasks, with the aim of improv- the size of the load. This relationship is
ing grid performance. shown in ➔ 1.

A shortage of reactive power is often the Controlling the undervoltages produced


4 SLG close to the load
cause of a voltage collapse in the power by faults and overvoltages produced
grid. Typically reactive power is needed to during light or no-load conditions are
maintain proper voltage levels in a power key features of SVC operation. A gener- SVC
system. However, reactive power cannot ic case is shown in ➔ 2. The load center
– nor should it – travel over long distanc- is fed through a transmission line and
es, because it is associated with power the load consists, to a large extent, of IM

losses as well as voltage gradients. Reac- induction motors (IM), which are sensi- Grid Line Load

tive power should therefore be provided tive to undervoltage situations. In this


where it is needed (ie, at load centers). case both active and reactive power to
the load must be supported through the
Reactive power is consumed by loaded transmission line. Quite apart from the
lines. When a fault occurs in a power ohmic losses this will generate in the Footnote
system, such as a short circuit, the af- system, it will also show up as a variety 1 A STATCOM (static synchronous compensator)
is a power electronics voltage-source converter
fected line is disconnected and the re- of challenges during faults in the sys-
used on alternating current electricity
maining lines pick up the flow. Reactive tem. In the following section, these chal- transmission networks that acts as either a
power is then consumed to an increasing lenges are described. source or sink of reactive power.

50 ABB review 1|10


Undervoltage control pacitors (TSC), and/or fixed capacitors
5 SVC of TCR/TSC/Filter configuration
Undervoltage situations can occur at (FC) tuned to filters. A common design
generator outages or faults in adjacent type is shown in ➔ 5.
feeders. These faults are typically tem-
porary, clearing after 100 to 150 ms. A TCR consists of a fixed reactor in se-
During the fault, the voltage will drop by ries with a bi-directional thyristor valve.
a varying degree. Two main cases of un- TCR reactors are generally of air core
dervoltage can develop: one case during type, glass fiber insulated and epoxy res-
the fault, and the other directly after the in impregnated.
fault has cleared.
A TSC consists of a capacitor bank in
If the SVC is very close to a three-phase series with a bidirectional thyristor valve TCR TSC TSC Filters
fault, it cannot do much to help alleviate and a damping reactor. The reactor also
the voltage drop during the fault. For serves to detune the circuit to avoid par-
more remote faults or for single line-to- allel resonance with the network. The
6 V-I characteristics of SVC
ground (SLG) faults, however, it might thyristor switch acts to connect or dis-
also be possible, to some extent, to sup- connect the capacitor bank for an inte- Voltage (V T)
port the voltage situation in the vicinity of gral number of half cycles of the applied
the SVC since the SVC will continue to voltage. The TSC is not phase controlled,
V max
generate reactive power in the grid dur- which means it does not generate any ΔVLmax

ing the fault. Undervoltage situations are harmonic distortion. ΔV Cmax Vref

especially difficult when the load consists V min

of a large percentage of asynchronous A complete SVC based on TCR and TSC


machines, such as motors for pumps or may be designed in a variety of ways to
air conditioners. The steady-state rela- satisfy a number of criteria in its opera-
tionship between the load torque and the tion on the grid. In addition, slow vars
produced electrical torque as a function can be supplied in the scheme by means
of speed is shown in ➔ 3. of MSC if required. I Cmax I Lmax

Total SVC current


During the fault the asynchronous ma- SVC characteristics
chines will slow, which will affect the sys- An SVC has a steady-state and dynamic
tem when the fault is cleared. In the most voltage-current (V-I) characteristic as
severe cases voltage recovery may be shown in ➔ 6. The SVC current/suscep- A shortage of
prevented in the grid after this kind of tance is varied to regulate the voltage ac-
fault. Assume, for example, that an SLG cording to a slope characteristic. The reactive power
fault occurs close to the load center as
indicated in ➔ 4. With the help of an SVC
slope setting along with other voltage
control equipment is important in the grid.
is often the cause
that dynamically supports the situation It is also important when determining the of a voltage
during the fault by means of reactive pow- voltage at which the SVC will reach the
er generation, the case can be solved. limit of its control range. A large slope set- collapse in the
The SVC will give strong support to the
grid, especially after the fault has cleared.
ting will extend the active control range to
a lower voltage, but at the expense of
power grid.
voltage regulation accuracy. ABB’s SVC can
Overvoltage control
The overvoltage control works in a simi- The voltage at which the SVC neither play a critical role
lar fashion to the undervoltage control, generates nor absorbs reactive power is
but is vital in load-rejection cases, where the reference voltage Vref. This reference
in the provision
sudden loss of loads generates overvolt- voltage can be adjusted within a certain of reactive power
ages due to reactive surplus from the range.
generators, lines and cables in the sys- to prevent or
tem. The control speed of the SVC en- Preventing voltage collapse
ables full support within one fundamental The Saudi Electricity Company of the
limit blackouts.
cycle and the SVC will consume reactive Western region of Saudi Arabia operates
power to limit the voltage in the system. a power transmission system comprising
As soon as the load is back in the system 380 kV overhead (OH) lines and under-
the SVC will return to its original set point ground cables. There are numerous
and support the system once again. 380 kV / 110 kV bulk supply stations,
feeding local 110 kV / 13.8 kV substa-
Static var compensator tions through mostly underground cable
An SVC is based on thyristor-controlled circuits. A simplified form of the grid is
reactors (TCR), thyristor-switched ca- shown in ➔ 7.

Securing power 51
7 Simplified grid of SEC Western region

Umm Lajj

Al Madinah (Medina)
Yanbu‘al
G Bahr SVC

SAUDI ARABIA

Rābigh

Red Sea G

G Al Khurmah
SVC Jiddah (Jeddah)
Makkah (Mecca)
SVC

SUDAN G

Al Lith

Operating conditions in the Saudi power – Voltage collapse situations at peak phase sequence voltage initially drops to
grid are special due to the hot climate, load conditions 0.7 to 0.8 per unit (p.u.). Air-conditioner
with up to 80 percent of the total load induction-motor flux decays and the mo-
consisting of air conditioners. From a grid A comprehensive reactive power plan- tors lose electrical torque. Almost instan-
point of view, air conditioning is a particu- ning study encompassing 380 kV, 110 kV taneously the motors lose speed as the
larly demanding kind of load, with slow and 13.8 kV levels was performed. The transient electrical torque becomes neg-
voltage recovery, motor stalling or even most important conclusions affecting the ative. During the rest of the fault time the
voltage collapse in conjunction with short system planning and operation were: electrical torque oscillates due to the im-
circuits in the transmission or subtrans- – Faster fault clearing, where possible, balance, but with an average value be-
mission network. In the Western region, reduces the dynamic reactive power low the load torque due to the reduced
especially near the Red Sea, and with the requirement. voltage. The loss of speed continues but
major city of Jiddah and the cities of Mak- – AC motor stalling for SLG faults can with a smaller rate of change. At fault
kah and Al Madinah as dominant load be avoided by installing dynamic
centers, grid stability is strained, particu- reactive power support.
larly in summer and during the Hajj pilgrim- – Dynamic reactive power support is SVCs provide a
age. Simulations have shown that the needed only for a short period: during
power system may not survive even SLG the fault and for about 1 s following fast and adequate
faults close to the load center during peak
load conditions. To stabilize the situation,
fault clearing.
– Reactive power support is needed to
supply of reactive
three large SVCs have been installed, with counteract voltage fluctuations due to power to maintain
the explicit purpose of keeping the grid daily load variations.
voltage stable as air conditioners all stable voltages,
around the region are running at full
speed ➔ 7 [1].
The total dynamic reactive power de-
mand was calculated at 3,000 MVAr
especially when
(Megavolt-ampere reactive). Installing large induction
The power system has a few specific five SVCs with a rating – 60 MVAr /
characteristics: + 600 MVAr each (ie, 60 MVAr inductive motor loads, such
– A large difference between minimum
and maximum (annual and daily) load
to 600 MVAr capacitive) at five different
110 kV buses would solve the AC motor-
as those created
– Extremely high concentration of load stalling problem and satisfy the daily by air conditioners,
air-conditioning load load voltage control.
– High impedance 380 kV / 110 kV and are dominant in
110 kV / 13.8 kV power transformers, The first three SVCs at the Al Madinah
to limit short circuit currents South, Faisaliyah and Jamia substations
the grid.
– Somewhat remote generation were taken into service in 2008 and
2009. The remaining two SVCs are still to clearing the motors need to both remag-
These characteristics affect the operation be purchased. Site views of the Faisali- netize and reaccelerate. The resulting
of the system. System performance yah ➔ 8 and Jamia SVCs are shown large active and reactive components in
and operational problems experienced in ➔ 9. the load current give a big voltage drop
were: in the source impedances. A large part of
– Voltage control between peak load Problem definition the impedance is in the 110 kV / 13.8 kV
and off-peak load conditions At an SLG fault in the vicinity of the city power transformers. In case of peak load
– Unacceptable voltage recovery after of Jiddah, on the 380 kV system or di- conditions, the motors will have lost too
faults at medium-load conditions rectly in the 110 kV system, the positive much speed to be able to reaccelerate

52 ABB review 1|10


8 Faisaliyah SVC 9 Jamia SVC

10 Motor speed, torque and 110 kV / 13.8 kV without SVC: 11 Motor speed, torque and 110 kV / 13.8 kV with SVCs: successful
unsuccessful voltage recovery voltage recovery

1.00 1.00
Motor speed

Motor speed
0.99 0.99
(p.u.)

(p.u.)
0.98 0.98

0.97 0.97

TE TM TE TM
1.75 1.75
Torque

Torque
(p.u.)

(p.u.)

-0.50 -0.50

V pos110 V pos14 V pos110 V pos14

1.05 1.05
Voltage

Voltage

0.95 0.95
(p.u.)

(p.u.)

0.85 0.85

0.75 0.75

0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40 0.05 0.10 0.15 0.20 0.25 0.30 0.35 0.40
Time (s) Time (s)
TE = Electrical torque TE = Electrical torque
TM = Mechanical torque TM = Mechanical torque
V pos110 = Positive phase sequence voltage at 110 kV Vpos110 = Positive phase sequence voltage at 110 kV
V pos14 = Positive phase sequence voltage at 13.8 kV V pos14 = Positive phase sequence voltage at 13.8 kV

following fault clearing, and voltage re- The initial drop in speed for the induction after fault clearing in cases where the SVCs
covery is unsuccessful ➔ 10. motors cannot be avoided by SVCs. It will were not operating during the fault.
take 1.5 cycles before the SVCs are fully
Countering motor stalling with SVCs compensating the voltage drop. With suf- Directly at fault clearing, the voltage
The way to prevent the motors from stall- ficiently large SVCs the voltage can be jumps upwards in a step. The reactive
ing is obviously to reduce the voltage supported to such an extent that the mo- current to the motors increases instanta-
drop during the fault and to restore the tors do not continue to lose speed follow- neously. In addition, a large active cur-
voltage as quickly as possible after fault ing the initial drop ➔ 11. A new “stable” rent is needed for reacceleration. In cas-
clearing. Such a task requires a lot of re- operating point is reached. During the fault, es where the voltage at the motors
active power support during a short pe- it is very difficult to increase the voltage to remains severely depressed, the active
riod of time. Voltage support applied the point at which the motors accelerate. It current needed cannot flow and the volt-
close to the motors gives the best re- is important to stop or slow down the age recovery in the system will be slow.
sults. The most efficient locations are in speed drop as quickly as possible. The In the worst case the motors will get
each 110 kV / 13.8 kV distribution sub- sooner it stops the easier it becomes to stuck. By supporting the voltage, a more
station on the 13.8 kV level. This would reaccelerate the system following fault rapid recovery is made.
require installing a very large number of clearing. A shorter response time for the
rather small SVCs. The practical solution SVC means that fewer Mvars are needed. SVC performance
is to install a limited number of large It has been shown in studies that the mo- The three SVCs each have a rating of
SVCs on the 110 kV level. tors are almost impossible to reaccelerate 60 MVAr inductive to 600 MVAr capaci-

Securing power 53
stant of about reaches its limit. This time is essentially
12 SVC single-line diagram
10 ms; the slope is the same irrespective of regulator gain.
the positive phase The TSC valves will switch on at the ap-
Bus 1 110 kV
sequence current propriate point on wave 2 and the TCRs
Bus 2
multiplied by a will cease conducting. The SVC will be
constant. Control fully conducting in 1.5 cycles. The TSC
action is by a PI switch-on time may be longer depending
600 MVA (proportional and on its precondition (charged or dis-
integrating) regula- charged). The most common condition is
tor (in many cases discharged capacitors.
just an I regulator).
It works on the dif- New control for faster voltage recovery
ference between a During a short circuit in the power grid
set voltage and the the positive phase sequence voltage is
actual voltage depressed. The SVC runs fully capaci-
TCR TSC 1 TSC 2
230 MVAr 215 MVAr 215 MVAr modified by the tive. In case of a lightly loaded system, a
3rd, 5th 7th, 11th 3rd, 5th 7th, 11th
61 MVAr 24 MVAr 61 MVAr 24 MVAr slope. The output temporary overvoltage may occur at fault
is a signal that can clearing. The primary reason for the over-
be seen directly as voltage is that the power system cannot
tive power. They are connected to gas- a susceptance order to the main circuit. absorb the reactive power generation
insulated switchgear (GIS) substations Thyristor valves can switch only once per from the SVC. A standard control system
on 110 kV. The nominal voltage on the half cycle and phase. A three-phase has to wait until the voltage has exceed-
SVC medium-voltage bus is 22.5 kV. valve assembly can be modeled by an ed its set voltage before the regulator
There are two TSCs rated at 215 MVAr average time delay. can start reducing the susceptance or-
each, and one TCR rated at der to the main circuit. This inevitably re-
230 MVAr ➔ 12. The harmonic filters rat- Typically, a response in the range of two sults in an overvoltage with a duration of
ed at a total of 170 MVAr are divided into cycles is achievable. This fulfills the re- at least one cycle. In the studied system,
two separate branches. The branches quirement by the
are connected to the MV bus by circuit utility that the re-
breakers. Each filter branch consists of sponse time be no Motors are almost impossible
two double-tuned filters covering the longer than 40 ms
3rd, 5th, 7th and 11th harmonics. in a strong net- to reaccelerate after fault clear-
Speed of response
work. (In Saudi
Arabia, the grid
ing in cases where SVCs were
When it comes to the speed of response frequency is 60 not operating and in those
for an SVC it is important to differentiate cycles, ie, two cy-
between “large signal” and “small signal” cles correspond to cases where they were, fewer
behavior. The large signal response is 33.3 ms.)
when the SVC responds to network faults
Mvars were needed when the
causing a large system voltage change. The stability of the SVC response time was short.
This is typically a line-to-ground fault in control must be
the vicinity of an SVC, or a more distant maintained at varying network strengths. voltages in excess of 1.5 p.u. may occur.
three-phase fault. The small signal re- Typically the short-circuit capacity varies Many SVCs around the world do not run
sponse is for minor changes in the system by a factor of two between the strong in capacitive mode until after fault clear-
voltage such as the effect from tap chang- and weak conditions. The regulator is ing because there were no efficient ways
er action or connection/disconnection of trimmed to give a fast response at the to solve this problem at the time when
a line reactor or a capacitor bank. For the weakest network condition. It is accept- they were installed.
utility-type of SVC, it is mainly the large ed that the SVC will be slower at the
signal speed that is of interest. strongest network. In case the system A simulation of the temporary overvolt-
becomes even weaker, automatic gain- age is shown in ➔ 13. The need to switch
A utility SVC primarily controls the posi- reduction algorithms are activated. the TSC out faster is evident. To improve
tive phase sequence voltage and in some the situation, a new control function was
special cases the negative phase se- The major task for a utility SVC is to developed and implemented in the three
quence voltage. For control, the instan- quickly supply Mvar at severe voltage Saudi SVCs where the TSCs are blocked
taneous voltage measurements have to drops at network faults. The most fre- at the first current-zero crossing follow-
be separated into sequence values and quent fault is a line-to-ground fault. The ing fault clearing. This approach has
the harmonic components in the voltage positive sequence voltage typically drops been shown to be efficient in simulations,
must be removed. Both these actions re- to 0.7 p.u. for a nearby fault and to grad- however real data is still to come. The re-
quire time. As a first approximation, the ually higher values for more remote faults. sults obtained with the new control func-
voltage processing can be seen as a At such a large voltage deviation the SVC tion are shown in ➔ 14.
first-order low-pass filter with a time con- regulator very quickly (in about one cycle)

54 ABB review 1|10


13 Temporary over-voltage: 1.4 p.u. over-voltage; TSC blocking at 14 New TSC blocking function: over-voltage reduced to 1.1 p.u.; TSC
the 4th current zero crossing blocking at the 1st current zero crossing.

1.50 1.50
System voltage

System voltage
(110 kV)

(110 kV)
(p.u.)

(p.u.)
0.70 0.70

7.00 7.00
(p.u.)

(p.u.)
B REF

B REF
0 0

Current TSC1 I ab Current TSC1 Ibc Current TSC1 Iab Current TSC1 I bc
Current TSC1 I ca Current TSC1 Ica
12.5 12.5
TSC 1 phase

TSC 1 phase
currents

currents
(kA)

(kA)
0 0

-12.5 -12.5

0 0.100 0.125 0.150 0.175 0.200 0.225 0 0.100 0.125 0.150 0.175 0.200 0.225
Time (s) Time (s)

15 TFR recording at Faisaliyah SVC 16 TFR recording at Al Madinah South SVC

Ua Ub Ua Ub
Uc Uc
1.5 1.5
(phase voltages) (p.u.)

(phase voltages) (p.u.)


System voltage

System voltage

1.0 1.0
(110 kV)

(110 kV)

0.5 0.5
0.0 0.0
-0.5 -0.5
-1.0 -1.0
-1.5 -1.5

0.1 0.1
(pos. phase seq.) (p.u.)

(pos. phase seq.) (p.u.)


System voltage

System voltage

0.0 0.0
(110 kV)

(110 kV)

-0.1 -0.1
-0.2 -0.2
-0.3 -0.3
-0.4 -0.4

8 8
6 6
4 4
(p.u.)

(p.u.)
B REF

B REF

2 2
0 0
-2 -2

0 0.20 0.25 0.30 0.35 0.40 0 0.20 0.25 0.30 0.35 0.40
Time (s) Time (s)

Securing power 55
Operational experience Operational experience shows that the
17 Saudi SVC project
Three line-to-ground faults were experi- SVCs are efficient in supporting the posi-
Several important conclusions can be drawn enced in the grid system in the summer tive phase sequence voltage during and
from the Saudi SVC project: of 2008, ie, during the peak load season. following SLG faults. The SVC reaction
– Motor stalling or voltage collapse
Two of the faults were in the Jiddah area time is short and the TSCs behave cor-
problems are evident in power systems
with large induction motor loads such as (Faisaliyah) ➔ 15 and one in Al Madi- rectly during the disturbances. Support-
those produced by the frequent use of air nah ➔ 16. ing the positive phase sequence voltage
conditioners. most efficiently means running all SVC
– SVCs provide efficient support for the
The SVC responded quickly to the fault, phases fully capacitive. The disadvan-
positive phase sequence voltage during
faults. The speed of induction motors can and became fully capacitive in 1.5 cycles. tage is that also the fault-free phases
then be maintained at reasonable levels. During the fault, the system voltage was may be raised above the maximum con-
– SVCs must run at a high capacity during constant or even increased slightly. It tinuous voltage. Such a rise could satu-
faults. The quicker the SVC response, the
was noted that the fault-free phase volt- rate the SVC power transformer; howev-
smaller the ratings needed. Very large
ratings are required when the SVCs ages did not drop much after the initial er, this problem did not develop as a
become active only after fault clearing. dip. At fault clearing the faulted phase result of the fault ➔ 17.
– A short time rating is sufficient, ie, only a recovered instantaneously. The SVC re-
few seconds of operation is required.
duced its output somewhat (about Grid stability with fast SVC response
– SVCs are robust and can run during faults
and during fault clearing. 100 MVAr) and ran at 500 MVAr for about Power systems with large induction mo-
– The SVCs must be able to block TSCs four cycles; thereafter it gradually re- tor loads, such as air conditioners, pres-
immediately after fault clearing to prevent duced its output to about 200 MVAr dur- ent a high risk of voltage collapse or mo-
temporary overvoltages during light load
ing the next five cycles. It remained at tor stalling, particularly in conjunction
situations.
– The typical SVC large-signal response this output throughout the recorded pe- with faults. They tend to consume large
time (from zero to full output) is 1.5 cycles riod of 30 s. It is interesting to note that amounts of reactive power, which should
with discharged capacitors. the faulted phase did not fully recover to not be transmitted over large distances,
– The typical SVC small-signal response
its prefault value within the 30 s time pe- since this increases the risk of voltage
time is 2.5 cycles for a strong power
system, resulting in two cycles in the weak riod. drops and causes active power losses.
system without retuning. To maintain voltage stability in such cir-
At the time of the fault, the phase B to cumstances SVCs can be used. To pro-
neutral voltage instantaneously dropped. vide voltage stability in the grid, particu-
The measured positive phase sequence larly in conjunction with fault situations, a
Operational voltage in the SVC dropped with a time fast dynamic response from the SVC is
constant of about 10 ms. This is the time essential. There is typically a trade-off
experience shows needed for phase sequence separation between dynamic response and the Mvar

that the SVCs and harmonic filtering. The voltage regu-


lator went fully capacitive in just a little
rating, ie, an increase in dynamic re-
sponse offers possible savings in Mvar
are efficient in more than one cycle. The time for the ratings while attaining the same favor-
main circuit to run fully capacitive on all able impact on grid stability.
supporting the three phases was 1.5 cycles. The delay

positive phase is due to the sampling effect – each


phase can only start conducting on the
sequence voltage zero crossing of their voltages. The TSCs Rolf Grünbaum
started to conduct with a minimum of Peter Lundberg
during and follow- transients. At fault clearing the TSCs re- Björn Thorvaldsson
mained in service. The currents still con-
ing single-line- tained a minimum of transients.
ABB Power Systems,
Grid Systems/FACTS

to-ground faults. Västerås, Sweden


The fault in Al Madinah was similar to the rolf.grunbaum@se.abb.com
one in Jiddah ➔ 14. The major difference peter.lundberg@se.abb.com
was that the fault in Al Madinah occurred bjorn.thorvaldsson@se.abb.com
at 8:45 a.m., compared with 4:45 a.m. in
the previous case. At this later time the
load in the system was heavier. There Footnote
2 Point on wave is a kind of synchronous
was larger asymmetry during the faults
switching where there is an active choice of
and one of the fault-free phases was de- moment in the cycle when the switching is
pressed, while the third one remained made.
unaffected. The recovery was somewhat
slower and the SVC stayed at full output
for a longer period of time. It should be Reference
[1] Al-Mubarak, A. H., Bamsak, S. M., Thorvaldsson,
noted that full capacity was needed only
B., Halonen, M., Grünbaum, R. (2009, March).
during some tenths of a second. Preventing voltage collapse by large SVCs at
power system faults. IEEE PSCE, Seattle, WA.

56 ABB review 1|10

Вам также может понравиться