Академический Документы
Профессиональный Документы
Культура Документы
Cooling Towers
INTRODUCTION COOLING TOWER PSYCHROMETRICS
The purpose of this section is to provide a basic understand- Psychrometry is the study of cooling by evaporation. Maxi-
ing of the design and operation of a cooling tower. A cooling mum evaporation takes place when water, in the form of tiny
tower allows water to be cooled by ambient air through evapo- droplets, is exposed to the maximum air flow for the longest pos-
ration. sible time. The process of evaporation through removal of latent
FIG. 11-1
Nomenclature
DEFINITIONS OF WORDS AND Capacity: The amount of water that a cooling tower will cool
through a specified range, at a specified approach and wet-
PHRASES USED IN COOLING TOWERS bulb temperature.
Air inlet: Opening in a cooling tower through which air enters. Cell: Smallest tower subdivision which can function as an inde-
Sometimes referred to as the louvered face on induced draft pendent unit with regard to air and water flow; it is bounded
towers. by either exterior walls or partition walls. Each cell may have
Air power: The power output developed by a fan in moving a one or more fans and one or more distribution systems.
given air rate against a given resistance. Circulation rate: Actual water flow rate through a given
Air rate: Mass flow of dry air per square foot of cross-sectional tower.
area in the tower’s heat transfer region per hour. Cold water temperature: Temperature of the water leaving
Air velocity: Velocity of air-vapor mixture through a specific the collection basin, exclusive of any temperature effects
region of the tower (i.e. the fan). incurred by the addition of makeup and/or the removal of
blowdown.
Ambient wet-bulb temperature: The wet-bulb temperature
of the air encompassing a cooling tower, not including any Collection basin: Chamber below and integral with the tower
temperature contribution by the tower itself. Generally mea- where water is transiently collected and directed to the sump
sured upwind of a tower, in a number of locations sufficient or pump suction line.
to account for all extraneous sources of heat. Counterflow: Air flow direction through the fill is countercur-
Approach: Difference between the cold water temperature and rent to that of the falling water.
the entering wet-bulb temperature. Crossflow: Air flow direction through the fill is essentially per-
Blowdown: Water discharged from the system to control con- pendicular to that of the falling water.
centrations of salt or other impurities in the circulating wa- Distribution basin: Shallow pan-type elevated basin used to
ter. distribute hot water over the tower fill by means of orifices in
the basin floor. Application is normally limited to crossflow
towers.
11-1
Double-flow: A crossflow cooling tower where two opposed fill Louvers: Blade or passage type assemblies installed at the air
banks are served by a common air plenum. inlet face of a cooling tower to control water splashout and/or
Drift: Circulating water loss from the tower as liquid droplets promote uniform air flow through the fill. In the case of film-
entrained in the exhaust air stream. Units percent of circu- type crossflow fill, they may be integrally molded to the fill
lating water rate or gpm. [For more precise work, an L/G sheets.
parameter is used, and drift becomes kilograms of water per Makeup: Water added to the circulating water system to re-
million kilograms of exhaust air (ppmw).] place water lost by evaporation, drift, windage, blowdown,
Drift eliminators: An assembly of baffles or labyrinth pas- and leakage.
sages through which the air passes prior to its exit from the Natural draft: Refers to the movement of air through a cool-
tower, for the purpose of removing entrained water droplets ing tower purely by natural means. Typically, by the driving
from the exhaust air. force of a density differential.
Dry-bulb temperature: The temperature of the entering or Net effect volume: That portion of the total structural volume
ambient air adjacent to the cooling tower as measured with within which the circulating water is in intimate contact
a dry-bulb thermometer. with the flowing air.
Evaporation loss: Water evaporated from the circulating wa- Performance factor: Variable used in determining perfor-
ter into the air stream in the cooling process. mance characteristics in cooling towers.
Fan cylinder: Cylindrical or venturi-shaped structure in Psychrometer: An instrument incorporating both a dry-bulb
which a propeller fan operates. Sometimes referred to as a and a wet-bulb thermometer, by which simultaneous dry-
fan “stack” on larger towers. bulb and wet-bulb temperature readings can be taken.
Fan deck: Surface enclosing the top of an induced draft cool- Range: Difference between the hot water temperature and the
ing tower, exclusive of the distribution basins on a crossflow cold water temperature.
tower. Recirculation: Describes a condition in which a portion of the
Fan pitch: The angle which the blades of a propeller fan make tower’s discharge air re-enters the air inlets along with the
with the plane of rotation, measured at a prescribed point on fresh air. Its effect is an elevation of the average entering
each blade. wet-bulb temperatures compared to the ambient.
Fill: That portion of a cooling tower which constitutes its pri- Water rate: Mass flow of water per square foot of fill plan area
mary heat transfer surface. Sometimes referred to as “pack- of the cooling tower per hour.
ing.” Wet-bulb temperature: the temperature of the entering or
Forced draft: Refers to the movement of air under pressure ambient air adjacent to the cooling tower as measured with
through a cooling tower. Fans of forced draft towers are lo- a wet-bulb thermometer.
cated at the air inlets to “force” air through the tower. Wet-Bulb thermometer: A thermometer whose bulb is en-
Hot water temperature: Temperature of circulating water cased within a wetted wick.
entering the cooling tower’s distribution system. Windage: Water lost from the tower because of the effects of
Induced draft: Refers to the movement of air through a cool- wind.
ing tower by means of an induced partial vacuum. Fans of in- Wind load: The load imposed upon a structure by a wind blow-
duced draft towers are located at the air discharges to “draw” ing against its surface.
air through the tower.
Liquid-to-gas ratio: A ratio of the total mass flows of wa-
ter and dry air in a cooling tower. (See Air Rate and Water
Rate)
heat allows the water to be cooled below the ambient dry-bulb tower. Water cannot be cooled below the wet-bulb temperature
temperature. The dry air enters the cooling tower and begins by evaporation. The air entering the tower at a temperature of
to gain moisture and enthalpy in an effort to reach equilibrium 24°C and 100% relative humidity has a 24°C “wet-bulb” tem-
with the water. The water may be cooled 8°C or more while the perature. The wet-bulb temperature is usually measured using
air mass dry-bulb temperature may increase only slightly. A a sling psychrometer. Wet bulb and dry bulb data for various
psychrometric chart (Fig. 11-2) may be used to illustrate the locations around the world are shown in Figs. 11-3a and 11-3b.
relationships between wet- and dry-bulb temperatures. All no-
menclature is indicated in Fig. 11-1. Types of Cooling Systems
Wet-bulb Temperature Cooling water is circulated through equipment to absorb
and carry away heat. The basic cooling systems are shown in
The basis for thermal design of an evaporative type cool- Fig. 11-4. The open recirculating system is the most common
ing tower is the wet-bulb temperature of the air entering the for industrial plants.
11-2
FIG. 11-2
Psychrometric Chart
11-3
FIG. 11-3a
Dry Bulb/Wet Bulb Temperature Data2
11-4
FIG. 11-3a (Cont’d)
Dry Bulb/Wet Bulb Temperature Data2
11-5
FIG. 11-3a (Cont’d)
Dry Bulb/Wet Bulb Temperature Data2
The dry bulb and wet bulb temperatures represent values which have been equalled or exceeded by 5% of the total hours during the months of June through Sep-
tember in the northern hemisphere and the months December through March in the southern hemisphere.
The data for Canadian stations are based on the month of July only.
Adapted to SI with permission of the American Society of Heating, Refrigerating and Air-Conditioning
Engineers, Atlanta, Georgia, from the 1993 ASHRAE Handbook—Fundamentals.
11-6
FIG. 11-3b
Dry Bulb/Wet Bulb Temperature Data2
11-7
FIG. 11-3b (Cont’d)
Dry Bulb/Wet Bulb Temperature Data2
The dry bulb and wet bulb temperatures represent values which have been equalled or exceeded by 5% of the total hours during the months of June through Sep-
tember in the northern hemisphere and the months December through March in the southern hemisphere.
The data for Canadian stations are based on the month of July only.
Adapted to SI with permission of the American Society of Heating, Refrigerating and Air-Conditioning
Engineers, Atlanta, Georgia, from the 1993 ASHRAE Handbook—Fundamentals.
11-8
The open recirculating system routes cooled water through Tower Location
the heat-exchange equipment. Effluent warm water then is
cooled by contact with air in a cooling tower. The cooling ef- Local heat sources upwind of the cooling tower can elevate
fect is produced by evaporation of a portion of the circulating the wet-bulb temperature of the air entering the tower. Inter-
water, and this evaporation causes the dissolved solids in the ference occurs when a portion of the saturated air upwind of
water to become concentrated. Water lost by evaporation must the tower contaminates the ambient air of a downwind tower.
be replaced by makeup water. But water lost through entrain- Drift and condensed water can cause corrosion problems with
ment of droplets in the circulating air (windage or drift) tends downwind equipment.
to limit the degree of concentration since the entrained droplets
also contain dissolved solids. Windage loss varies with the type PERFORMANCE CHARACTERISTICS
of tower.
The performance characteristics of various types of tow-
Typical windage losses, expressed as percentages of the ers will vary with height, fill configuration, and flow arrange-
total system water circulation rate, for different evaporative ment — crossflow or counterflow; however, these factors have
equipment are as follows: been taken into consideration in preparation of the Performance
Characteristic Nomograph Fig. 11-5. When accurate character-
Spray ponds 1.0 to 5.0% istics of a specific tower are required, the cooling tower manu-
Atmospheric-draft towers 0.3 to 1.0% facturer should be consulted.
FIG. 11-4
Cooling System Characteristics
11-9
Example 11-1 — Effect of Varying WB Temperature on Cold Water Tempera-
ture (CWT).
What is new CWT when WB changes from 25° to 15° with m3/h and range
remaining constant?
Enter Nomograph at 30° CWT, go horizontally to 25° WB, then vertically
down to 15° WB, read new CWT of 24°.
Example 11-3 — Effect of Varying Water Circulating Rate and Heat Load on
Cold Water Temperature.
What is new CWT when water circulation is changed from 200 m3/h to
300 m3/h (50% change in heat load at constant Range). Varying water rate,
particularly over wide ranges, may require modifications to the distribution
system. Enter Nomograph at 30° CWT, go horizontally to 25° WB, vertically
to 10° R, horizontally to Performance Factor of 1.8. Obtain new PF by multi-
plying (1.8) (300/200) = 2.7, then enter Nomograph at PF of 2.7, go horizon-
tally to 10° R, vertically down to 25° WB, read new CWT 33.2°.
11-10
Example 11-4 — Effect of Varying WB Temperature, Range, and Water Cir-
culating Rate on Cold Water Temperature.
What is new CWT when the WB changes from 25° to 15°, R changes from
10° to 12.5°, m3/h changes from 200 to 250 (25% change in heat load.) En-
ter Nomograph at 30° CWT, go horizontally to 25° WB, vertically to 10° R,
horizontally read PF 1.8 then multiply (1.8) (250/200) = 2.25 (new PF). Enter
Nomograph at PF = 2.25, go horizontally to 12.5° R, vertically down to 15°
WB, read 27.5° new CWT.
Performance tests on a cooling tower should be done in ac- ample 11-5), m3/h could be increased from 250 to (250) (1.053)
cordance with the Cooling Tower Institute (CTI) Acceptance = 263 m3/h.
Test Code and the American Society of Mechanical Engineers
(ASME) test code. Example 11-7 — Calculate the concentrations and blowdown
rate for the following cooling tower:
Examples Circulation Rate = 2000 m3/h
The use of the Nomograph is illustrated by the following Water Temperature Drop Through Tower = 10°C
examples covering typical changes in operating conditions.
Type of Tower = Mechanical Induced Draft
Assume a cooling tower is operating at known conditions of:
Blowdown Rate = 4.0 m3/h, or 0.2% of circulation rate
Flow = 200 m3/h
Therefore:
Hot Water = 40°C
Evaporation Loss = 1.8% (1% for each 5.5°C temperature
Cold Water = 30°C drop)
Wet Bulb = 25°C (all rates are based on a percent of circulation rate)
This is commonly referred to as 40-30-25 or 10° Range Windage Loss = 0.3% (maximum for mechanical draft tower,
(40° – 30°) and 5° Approach (30° – 25°). p. 11-2)
Example 11-6 — The correction factor shown in Example 11-5 Number of E+B
could also be used to increase m3/h instead of decreasing CWT, Concentrations
(cycles) = B
as was done in Example 11-5. In Example 11-4, we developed
a new CWT of 27.5° when circulating 250 m3/h at 12.5° R and 1.8 + (0.2 + 0.3)
15° WB. If motor kW is increased from 30 to 35 under these = = 4.6
(0.2 + 0.3)
conditions with PF correction factor = 1.053 (as shown in Ex-
11-11
FIG. 11-5
Performance Characteristic Nomograph
11-12
If the resultant concentrations are excessive and a desired con- Mechanical Draft Towers
centration of 4.0 is required, what must the blowdown rate be?
Fans are used to move the air through the mechanical draft
E tower. The performance of the tower has a greater stability
B =
Cycles – 1 because it is affected by fewer psychrometric variables. The
fans provide a means of regulating the air flow. Mechanical
1.8 draft towers are characterized as either forced draft or induced
= = 0.6%
4.0 – 1 draft.
The windage component of B is 0.3%, therefore the blowdown Forced draft towers (Fig. 11-6) — The fan is located on
rate required would be 0.6 – 0.3 = 0.3% or the air stream entering the tower. This tower is characterized
(2000 m3/h) (0.003) = 6.0 m3/h by high air entrance velocities and low exit velocities, therefore,
the towers are susceptible to recirculation thus having a lower
performance stability. The fans can also be subject to icing un-
CONCENTRATION CYCLES der conditions of low ambient temperature and high humidity.
The concentration of compounds occurring in circulating
Induced draft towers (Fig. 11-7a and 11-7b) — The fan
water systems that can cause scaling or corrosion of equipment
is located on the air stream leaving the tower. This causes air
must be controlled at a desirable level. This concentration level,
exit velocities which are three to four times higher than their
developed on each system, is based on the quality of makeup
air entrance velocities. This improves the heat dispersion and
water and the water treating chemicals used to control corro-
reduces the potential for recirculation. Induced draft towers re-
sion or scaling. The concentration is usually reported as concen-
quire about one kw of input for every 18 000 m3/h of air.3
tration cycles and refers to the number of times the compounds
in the makeup water are concentrated in the blowdown water.
FIG. 11-7a
For example, if the concentration in the makeup water were
125 mg/kg and the concentration of the blowdown were 500, Mechanical Induced Draft Counterflow Tower
the concentration cycles would be 500/125 or 4 cycles. The com-
pounds are concentrated by the loss of water through evapora- Air
tion and windage. The evaporation loss in a cooling tower is cal- Out
culated from the ratio of specific heat to the heat of vaporation.
The specific heat of water is 4.186 kJ/(kg • °C) and the heat of Fan
vaporation is 2326 kJ/kg. The ratio 4.186/2326 = 0.0018/°C indi-
cates that 0.18% evaporation occurs for every degree of cooling
taking place across the tower.
FIG. 11-6
FIG. 11-7b
Mechanical Forced Draft Counterflow Tower
Mechanical Induced Draft Cross Flow Tower
Air Air
Water Out Out
Sprays
Fan
Air
In
Water
In
Air Air
In In
Water Water
Fan Out Out
11-13
Coil shed towers (Fig. 11-8) — This application exists in ENVIRONMENTAL
many older cooling towers. The atmospheric coils or sections
are located in the basin of the cooling tower. The sections are Environmental factors should be considered when choosing
cooled by flooding the surface of the coils with cold water. Rea- whether or not to use a cooling tower. Areas to consider would
sons for discontinued use were scaling problems, poor tempera- include:
ture control, and construction costs. This type tower can exist 1. Leakage to the atmosphere (VOC, CO2)
both as mechanical or natural draft.
2. Particulate matter (mist eliminators)
Natural Draft Towers
3. Tower blowdown (disposal well, treatment, release to
Atmospheric spray towers (Fig. 11-9) — Cooling towers surface waters, evaporation ponds)
of this type are dependent upon atmospheric conditions. No me-
chanical devices are used to move the air. They are used when These issues are discussed further in Section 18 — Utilities.
small sizes are required and when low performance can be tol-
erated. BASIN
Hyperbolic natural draft towers (Fig. 11-10) — These The cooling tower basin design should take into consider-
towers are extremely dependable and predictable in their ation the suction requirements for the water circulation pump.
thermal performance. A chimney or stack is used to induce air This is discussed in more detail in the “Submergence” section
movement through the tower. under the title “Net Positive Suction Head” in Section 12 —
Pumps and Hydraulic Turbines.
FIG. 11-10
Coils Hyperbolic Natural Draft Tower
Air
Water Outlet
Outlet
FIG. 11-9
Atmospheric Spray Tower
Air Outlet
Water Inlet
Distribution
System
Hot
Water
Inlet
Air
Air In Air In Inlet
Water Outlet
Water Outlet
Cold Water
Collection Basin
11-14
FIG. 11-11
Properties of Saturated Air1
11-15
REFERENCES AND BIBLIOGRAPHY 3. Evans, Frank L., Jr., “Equipment Design Handbook for Refin-
eries and Chemical Plants,” 2nd ed., Gulf Publishing Company,
1. American Society of Heating, Refrigerating and Air-Condition- Houston, Texas.
ing Engineers, “ASHRAE Handbook—Fundamentals,” Table 1,
Chapter 6, Atlanta, Georgia. 4. Maulbetsch, John S. and DeFilippo, Michael N., “Performance, Cost
and Environmental Effects of Saltwater Cooling Towers.”
2. American Society of Heating, Refrigerating and Air-Condition-
ing Engineers, “ASHRAE Handbook—Fundamentals,” Tables 1,
2 and 3, Chapter 24, Atlanta, Georgia.
11-16