Вы находитесь на странице: 1из 6

providing insights for today’s hvac system designer

Engineers Newsletter volume 40 –3

Minimum Outdoor Airflow Using the IAQ Procedure

ANSI/ASHRAE Standard 62.1-20104 3 Determine the emission rate for each


Past Engineers Newsletters1 and includes three alternative procedures for pollutant from each identified source.
ASHRAE Journal articles2,3 have
discussed compliance with the determining minimum outdoor airflow 4 Specify a concentration limit for each
requirements of the Ventilation Rate (OA) rates: the ventilation rate
Procedure (VRP) because most pollutant.
procedure (VRP), the indoor air quality
engineers use it, most building codes
base minimum outdoor airflow procedure (IAQP), and the natural 5 Specify the design limit for perceived
requirements on it, and several energy ventilation procedure (NVP). IAQ in terms of the minimum
labeling programs and building rating percentage of occupants or visitors
systems require compliance with it.
The VRP prescribes minimum zone-level expressing satisfaction with the air
This newsletter, however, describes OA rates and procedures to find system- quality in the completed building.
compliance with the Indoor Air Quality level OA intake rates. The IAQP allows
Procedure (IAQP) requirements. 6 Using mass balance calculations,
compliance based on contaminant
Although this procedure is not widely determine the minimum breathing zone
used because it requires significant
concentrations and perceived air quality,
OA rate necessary to meet the specified
judgment on the part of the designer, i.e., based on performance criteria. The
concentration limits for each pollutant.
nevertheless it deserves a detailed NVP prescribes minimum outdoor air
discussion. openings (not OA rates) for natural 7 Find the OA rate required to meet the
(passive) ventilation; in most cases, the perceived IAQ limit by conducting a
NVP must be used in conjunction with subjective evaluation in the completed
either the VRP or the IAQP, since building or by establishing that the
mechanical ventilation must be available current zone design meets the criteria
whenever passive ventilation is for a “substantially similar zone”
undesirable or ineffective. wherein a successful subjective
evaluation has been conducted.
8 For each zone, find the minimum
Summary of the IAQP breathing zone OA rate—the largest OA
rate among those determined by mass
To find the minimum required breathing balance for each pollutant or the OA rate
zone OA rate for each zone using the IAQP, determined by subjective
the following steps must be completed evaluation—whichever is greater.
(see inset p.3): 9 Finally, find system-level OA intake flow
1 Identify all contaminants-of-concern based on the breathing zone OA rate
and mixtures-of-concern for the zone.* found for each zone.
For simplicity we’ll refer to all of these
as “pollutants.” Standard 62.1 allows designers to apply the
IAQP in some zones within a system, and
2 Identify both indoor and outdoor the VRP in other zones, and it requires
sources for each pollutant. designers to document design assumptions
and calculations, but here we focus on the
nine steps listed.

* Although Section 6.3.1 seems to require identification of either contaminants-of-concern OR mixtures-of-concern,


most designers logically interpret this as a requirement to identify all contaminants- AND mixtures-of-concern.

© 2011 Trane, a business of Ingersoll Rand. All rights reserved. 1


Identify contaminants and mixtures Gaseous contaminants are either Many contaminants must be considered
of concern. For designers, identifying organic or inorganic. Like particles, both as individual contaminants of
all pollutants to be considered for a gases originate both indoors and concern and as constituents of one or
given design represents the first and outdoors. more mixtures. Formaldehyde, for
most important set of judgments. example, should be considered as an
Since the ASHRAE Handbook5 Mixtures of concern are either source individual contaminant (since it is a
classifies indoor pollutants as either related or impact-related. Source known carcinogen) and as a constituent
particulate matter or gaseous mixtures (such as diesel exhaust or of one or more impact mixtures (since it
contaminants, designers must tobacco smoke) comprise a wide range has a pungent odor and impacts the
consider both when identifying of contaminants, often both particles respiratory system).
contaminants of concern, and they and gases, which originate from known
must consider mixtures as well to sources or processes. Impact mixtures Both indoor and outdoor pollutants must
comply with the standard.  comprise a set of particles or gases be considered. Although lists of some
(See Table 1.) known to impact the same human organ potential outdoor pollutants6 and some
or system, such as the eyes, the potential indoor pollutants7 exist, no
Particulate matter includes inert respiratory system or the nervous complete and widely accepted list of
particles, biological particles and liquid system. Standard 62.1 doesn't currently pollutants exists—such a list would vary
droplets. There are many sources of make this distinction between source widely from one project to the next.
particles. Most inert particles and liquid and impact mixtures, although it Even if a comprehensive pollutant list
particles originate outdoors. Biological probably should in the future. existed, the designer would be required
particles originate both indoors and to judge which pollutants apply for each
outdoors. specific zone in each building project.

Table 1. Indoor pollutants


Pollutant category Type Examples Example sources Impact
particulate matter solid dust (less than 100 µm) wind, volcanoes, grinding, demolition, burning asthma, nose and throat irritation, lung
fuels, unpaved roads and so on damage
bioaerosols living things, including viruses, bacteria, fungi, allergies, asthma, various diseases,
mites, plants and insects including tuberculosis, Legionnaire’s
disease, and influenza
liquid mist cooling towers evaporation may increase concentration
of bioaerosols
fog condensation evaporation may increase concentration
of bioaerosols and very small particles
gaseous inorganic ammonia cleaning products respiratory irritant
contaminants
ozone electrostatic appliances, printers, copiers, outdoor reduced lung function, asthma, eye
air irritation
carbon monoxide incomplete combustion, outdoor air respiratory system damage
radon soil lung cancer
organic formaldehyde building materials, adhesives, insulation eye, nose, and throat irritation, asthma,
respiratory symptoms
benzene burning, automobile exhaust, some glues, paints, cancer
and detergents
other volatile organic compounds people, processes, cleaning products odor, wide range of physical symptoms
(VOC)
mixtures source mixtures smoke burning organic material see particulate matter
tobacco smoke burning tobacco cancer; see particulate matter
diesel exhaust diesel fuel combustion cancer; see particulate matter, inorganic
and organic gases
smog products of combustion see ozone and particulate matter
impact mixtures** example constituents: multiple sources respiratory system impact
acetaldehyde, acrolein,
ammonia, etc.
example constituents: arsenic, nervous system impact
benzene, carbon disulfide, etc.
example constituents: benzene, reproductive system impact
butadiene, carbon disulfide, etc.
**Example impact-mixture categories based on Office of Environmental Health Hazard Assessment (OEHHA) table (see www.oehha.org/air/allrels.html)

2 Trane Engineers Newsletter volume 40–3 providing insights for today’s HVAC system designer
It's clear that the most important step in Establish target concentrations. For IAQP requirements
the IAQP—establishing the individual each contaminant and each mixture, an 
contaminants, source mixtures and acceptable concentration and exposure- 6.3 Indoor Air Quality (IAQ) Procedure.
Breathing zone outdoor airflow (Vbz) and/or
impact mixtures of concern—is not easy time limit must be established. Designers system outdoor air intake flow (Vot) shall be
and requires considerable designer must cite a cognizant authority (see inset) determined in accordance with Sections 6.3.1
judgment and therefore, risk. as the source for these limits. Acceptable through 6.3.5.
limits for individual contaminants vary
6.3.1 Contaminant Sources. Contaminants
Sources of contaminants. Having among cognizant authorities, so each
or mixtures of concern for purposes of the
established a list of pollutants, the next designer must judge which authority to design shall be identified. For each
step is to identify both indoor and outdoor rely upon. contaminant or mixture of concern, indoor
sources (occupants and materials) and
sources of each. Possible indoor sources
ASHRAE Handbook8 states that there are outdoor sources shall be identified, and the
include people, furnishings, wall emission rate for each contaminant of concern
coverings, paints, adhesives, ceiling tiles, “no established exposure guidelines” for
from each source shall be determined.
carpet and so on. Possible outdoor inert particles in nonindustrial indoor
sources include the outdoor air in general environments, so designers tend to rely 6.3.2 Contaminant Concentration. For
on the outdoor air limits for particulate each contaminant of concern, a concentration
(see inset p. 4), motor vehicles, limit and its corresponding exposure period
dumpsters, cooling towers and so on. matter established by the Environmental
and an appropriate reference to a cognizant
Protection Agency (EPA) National Ambient
authority shall be specified.
Each identified source can contribute one Air Quality Standards (NAAQS). Some
or more contaminant, source mixture or biological particles cause diseases such as 6.3.3 Perceived Indoor Air Quality. The
tuberculosis, so specific exposure limits design level of indoor air acceptability shall be
impact mixture (or constituent). Although
have been recommended by the National specified in terms of the percentage of
some pollutant emissions data have been building occupants and/or visitors expressing
established for some indoor products, Institute for Occupational Safety and satisfaction with perceived IAQ.
laboratory measurements are often Health (NIOSH) and others.
required to determine the pollutants 6.3.4 Design Approach. Zone and system
Exposure limits have been established for outdoor airflow rates shall be the larger of
emitted from specific products. those determined in accordance with Section
many individual gases by various
6.3.4.1 and either 6.3.4.2 or 6.3.4.3, based
Since there are so many potential authorities, including NIOSH and the
on emission rates, concentration limits, and
pollutants, identifying even the major American Council of Industrial Hygienists other relevant design parameters (e.g., air
sources for each requires a great deal of (ACGIH). cleaning efficiencies and supply airflow rates).
judgment and is inexact at best. So, like
Neither source-mixtures nor impact- 6.3.4.1 Mass Balance Analysis. Using a
pollutant identification, source steady-state or dynamic mass-balance
identification poses a risk for designers. mixtures of concern have been addressed
analysis, determine the minimum outdoor
directly. Cognizant authorities are not too airflow rates required to achieve the
concerned with concentration limits for concentration limits specified in Section 6.3.2
Source strength. With a list of all most source mixtures—it's much easier to for each contaminant or mixture of concern
identified sources for each pollutant, simply keep such mixtures out of the within each zone served by the system.
source strengths must be determined. All building. However, ACGIH has established
sources for each pollutant must be 6.3.4.2 Subjective Evaluation. Using a
a method to limit impact-mixture subjective occupant evaluation conducted in
evaluated so that the total emission rate concentrations based on the threshold the completed building, determine the
can be determined to support mass limit value (TLV) of the mixture minimum outdoor airflow rates required to
balance calculations. For instance, if constituents. TLVs have been established achieve the level of acceptability specified in
formaldehyde has been identified as a Section 6.3.3 within each zone served by the
for many gaseous constituents of impact- system.
contaminant of concern as well as a mixtures, so it is often possible for
constituent of an impact mixture, the designers to determine valid mixture- 6.3.4.3 Similar Zone. The minimum outdoor
formaldehyde emission rate from all related limits. airflow rates shall be no less than those found
potential sources must be determined to in accordance with Section 6.3.4.2 for a
find the total emission rate in the zone. substantially similar zone (i.e., in a zone with
identical contaminants of concern,
Emission rates for various contaminants concentration limits, air cleaning efficiency,
from some products have been and specified level of acceptability; and with
established, but for most contaminant Cognizant authority similar contaminant sources and emission
sources, source strengths must be rates).
determined using appropriate materials- Standard 62.1 defines cognizant authority
as "an agency or organization that has the 6.3.5 Combined IAQ Procedure and
laboratory testing. This can be expensive Ventilation Rate Procedure. The IAQ
expertise and jurisdiction to establish and
and time-consuming. regulate concentration limits for airborne procedure in conjunction with the Ventilation
contaminants; or an agency or Rate Procedure may be applied to a zone or
And remember, contaminant sources organization that is recognized as system. In this case, the Ventilation Rate
include people and their activities, so authoritative and has the scope and Procedure shall be used to determine the
expertise to establish guidelines, limit required zone minimum outdoor airflow, and
emission rates for people-related the IAQ Procedure shall be used to determine
values, or concentration levels for airborne
pollutants must always be considered. contaminants." the additional outdoor air or air cleaning
necessary to achieve the concentration limits
of the contaminants of concern.

3 Trane Engineers Newsletter volume 40–3 providing insights for today’s HVAC system designer
Some designers use the IAQP while have been or will be established, so Most designers using the IAQP don't
ignoring mixtures altogether. But designers must either prohibit smoking or address mixtures—they simply focus
remember, established limits (TLVs) for establish OA rates for ETS zones using an on the concentration limits for specific
many constituents of impact mixtures alternate approach. (Neither the VRP nor contaminants, and assume that they
do exist, so they can be used to satisfy the IAQP can be used to find minimum need only introduce the OA needed for
the additivity analysis (see inset) for OA rates for ETS zones.) the “worst case” contaminant.
specific impact mixtures. Additivity adjustments aren’t made in
Perceived IAQ. A minimum target level spite of clear advice to do so in
If established limits from a cognizant for perceived IAQ must be specified. For Informative Appendix B. (The VRP, on
authority cannot be referenced for all example, the designer might specify that the other hand, is based on the
building contaminants and impact at least 70 percent of visitors to a zone principle of adding OA rates for odors
mixture constituents, then compliance must express satisfaction with the air and irritants from two major sources,
with the IAQP isn’t possible. For quality, or that at least 90 percent of occupants and the building itself.) By
instance, no acceptable limits for occupants must express satisfaction. ignoring the additive nature of impact-
environmental tobacco smoke (ETS) Setting this target too high may require mixtures, the IAQP often results in
higher OA rates or more filtration for the inappropriately low OA rates.
Impact mixture "additivity."
zone. Setting it too low may lead to
Remember, many studies in office
According to Informative Appendix B, unacceptably low satisfaction levels—and
buildings show that the effective OA
contaminants that act on (impact) the how many building operators want even
same organ systems should be
rate must be between 15 to 20 cfm per
10 percent of the occupants complaining
analyzed, and outdoor air should be person as prescribed by the VRP. It
about odor? Again, setting a perceived
provided so that the sum of seems like good practice to find the
concentration ratios for the "impact
IAQ minimum satisfaction target places a
minimum breathing zone OA rate
mixture" does not exceed 1.0. judgment burden on the designer.
without air cleaning, as a check. If the
When many chemicals are rate without air cleaning is substantially
present in the air, as they almost
Mass balance calculations. With below the VRP rate for the zone, it's
always are in indoor air, then pollutants established, along with likely that a pollutant has been missed
some way of addressing potential sources, source strengths and target or mischaracterized or the additive
additive effects is warranted. The limits, and perhaps air-cleaning
ACGIH guidance on the subject
quality of impact mixtures has been
efficiencies for some pollutants, it's time overlooked. Failure to follow the
instructs that when two or more
substances acting on the "…same for some calculations. The standard Appendix B analysis for mixtures can
organ system are present, their requires mass balance calculations for lead to under-ventilation and
combined effect, rather than that every contaminant of concern identified complaints, which can haunt a building
of either individually, should be for the project, which logically includes
given primary consideration." B-1 design for years.
Information on affected organs is
both individual contaminants and
readily available on the websites constituents of impact mixtures. For For multiple-zone systems, mass
of the cited references for ACGIH, single-zone systems, Appendix D of balance calculations become more
OEHHA and ATSDR. If no Standard 62.1 shows steady-state complicated and usually require the
contradictory information is
equations relating source strength, OA use of spreadsheets or software. Mass
available, the effects of the
different substances "should be rate, air-cleaning efficiency, contaminant
considered as additive." A (or constituent) concentration and so on.
formula is given wherein the These equations can be algebraically What about outdoor air quality?
ratios of the concentrations of manipulated to solve for the minimum OA
each substance with the same Outdoor air introduced into a building
health-related endpoint to the
rate given concentration limits, or for air- can dilute and remove indoor-source
threshold limit value for each cleaning efficiencies given OA rate. pollutants. But since it can also add
substance are added. If the sum outdoor-source pollutants, it must be
of all these ratios exceeds unity, Designers use mass balance equations considered as a potential source. Some
then it is considered that the primarily to find the minimum required outdoor pollutants (such as ozone,
concentration value has been particulate matter, and odors) can be
breathing zone OA rate for each
exceeded. reduced by air cleaning before they
contaminant and for each impact mixture. enter the building, but some (carbon
(Remember source mixtures should be monoxide, for instance) cannot. In any
prevented from entering the building.) case, pollutants from outdoors must be
C1 C2 C Individual contaminants usually have considered both as individual
  n contaminants and as mixtures or
T1 T2 Tn established limits to use in calculations. constituents of mixtures when using the
And while impact mixtures don't have IAQP. But, remember that most indoor
where established limits, they can be pollutants are not present in the
Ci = the airborne concentration of “controlled” to acceptable levels (see outdoor air, so even "dirty" outdoor air
the substance. always dilutes and removes indoor-

insets pp.4-5) based on the concentration
source contaminants. Some amount of
Ti = the threshold limit value of and TLV of individual constituents, and outdoor air is always used for indoor air
that substance. using the “additivity” of concentration quality control.
ratios.

4 Trane Engineers Newsletter volume 40–3 providing insights for today’s HVAC system designer
balance software used to find air- To evaluate visitor satisfaction, a
cleaning efficiencies must be based on group of untrained subjects Impact mixture calculations
the minimum OA rates and procedures enters the zone and renders a
According to the ACGIH, when two or
in Standard 62.1-2004 (or later), since judgment on IAQ acceptability more substances acting on the "… same
both rates and procedures changed within 15 seconds; to evaluate organ system are present, their
significantly in the 2004 version of the occupant satisfaction, the group combined effect, rather than that of
standard. renders a judgment on either individually, should be given
priority." One way to do this is to: (1)
acceptability after spending more
Each IAQP zone in a multiple-zone find the steady-state concentration of
than six minutes in the zone. If each individual constituent, given an
system must be treated individually, the initial zone OA rate results in a OA rate, generation rate, air cleaning
using the contaminant and mixture satisfaction rating below the efficiency, and so on, (2) find the ratio
concentration levels in the primary air target percentage specified, of each constituent concentration to its
supplied to the zone, instead of OA TLV, and (3) add all the ratios together.
action must be taken (e.g., If the ratio sum exceeds 1.0, the
levels. Although local (in the zone) air increase the OA rate, reduce concentration of one (or more) of the
cleaning can be used, central air emissions by replacing some constituents must be lowered by
cleaners located in the air handler are building materials or furnishings, increasing the OA rate, decreasing the
much more common. To find system- generation rate, and/or increasing air
or increase air cleaning for odors).
level outdoor air intake flow while cleaning efficiency for that constituent.
The subjective evaluation must be With one or more new parameters,
accounting for both zone and outdoor repeated and corrective action repeat steps 1 through 3 until the sum
pollutant sources, as well as central air taken until the specified level of of the concentration ratios is less than
cleaning, designers must either derive acceptability is achieved. On the 1.0. This results in an acceptable OA
new equations to find contaminant rate for the impact-mixture being
other hand, if the initial zone OA considered. Of course, these
levels or use analysis software, such as rate results in excessively high calculations must be repeated for each
CONTAM10. The single-zone equations levels of occupant satisfaction, it identified impact-mixture.
in Appendix D do not apply. may be possible to reduce the
zone OA rate, provided the
Subjective evaluation. The mass- subjective evaluation is repeated
balance calculations described above to ensure compliance.
pollutant, and an identical specified
result in a minimum zone OA rate for
b. Alternatively, designers may level of perceived acceptability.
each contaminant or impact mixture.
identify a "substantially similar" Finding a zone with identical air
Each zone requires the highest of
zone in a previously constructed cleaning efficiency might be the
these rates to ensure acceptable
building that was successfully most difficult part because no
"objective" IAQ. But any minimum OA
evaluated using the subjective widely accepted rating method yet
rate must also ensure acceptable
evaluation approach described exists for comparing gaseous air-
"perceived" IAQ in terms of occupant or
above. The OA rate used in the cleaner efficiency for specific
visitor satisfaction. This requires a
similar zone establishes the contaminants or impact mixture
subjective evaluation of air quality
minimum OA rate needed to constituents.
using either of two approaches:
satisfy the subjective evaluation
The minimum zone OA rate determined
a. Based on the results of mass- requirement, without actually
using the mass balance calculations
balance calculations, experience, using a group of untrained
must be compared to the rate
knowledge of air cleaning subjects to evaluate perceived IAQ
determined using one of the two
devices, and so on, designers in the "new" zone. Of course,
subjective evaluation approaches. To
may choose to determine an identifying a similar zone can be
comply with the IAQP, the higher of
initial minimum zone OA rate for difficult, especially for zones in
these two values establishes the
design purposes. After one-of-a-kind buildings. A
minimum zone OA rate per the IAQP.
construction and building substantially similar zone has
occupancy, a subjective similar pollutant sources and
evaluation must be conducted in emission rates, similar or identical
each IAQP zone. While the contaminants, source mixtures
standard does not require a and impact mixtures, identical
specific subjective evaluation concentration limits, identical air-
procedure, Informative Appendix cleaning efficiency for each
B describes one such procedure.

5 Trane Engineers Newsletter volume 40–3 providing insights for today’s HVAC system designer
References.

Engineers
Summary
[1] Stanke, D. 2004. "Addendum 62n

Newsletter
Breathes New Life Into ASHRAE 62."
The IAQP is a valid procedure that Engineers Newsletter 33-1. La Crosse,
provides a valid performance-based WI: Trane
alternative to the VRP and has been
[2] Stanke, D. 2005. "Standard 62-2001
LIVE!
successfully applied for some building
Addendum 62n: Single-Path Multiple- Upgrading Existing
ventilation systems, especially where
Zone System Design." ASHRAE Journal
the same building design with 47(1):28-35. Chilled-Water
substantially similar zones is repeated in
multiple locations. However, for one-of-
[3] Stanke, D. 2005. "Standard 62.1-2004 Systems
Designing Dual-Path, Multiple-Zone Now available on-demand
a-kind buildings, the IAQP requires Systems." ASHRAE Journal 47(5):20-31. at www.trane.com/ContinuingEducation
designers to make many difficult
judgments and to perform a subjective [4] American Society of Heating,
Refrigerating and Air Conditioning High-Performance
evaluation in the completed building. In
Engineers, Inc. (ASHRAE) 2010. ANSI/
so doing, the required minimum zone ASHRAE Standard 62.1-2010. Ventilation VAV Systems
OA rate found using the IAQP is likely to for Acceptable Indoor Air Quality. Atlanta, Now available on-demand
vary considerably from one designer to GA: ASHRAE. at www.trane.com/ContinuingEducation
the next, and may be too low in many [5] 2009 ASHRAE Handbook-Fundamentals,
cases due to incomplete evaluation of Chapter 11. Atlanta, GA. ASHRAE
the additive nature of impact mixtures. October 2011
[6] 2009 ASHRAE Handbook- Fundamentals,
Chapter 11: Tables 11,12. Atlanta, GA. Dedicated
For these reasons, many designers are ASHRAE
uncomfortable with this approach.
Outdoor-Air
[7] 2009 ASHRAE Handbook- Fundamentals,
Furthermore, most mechanical codes Chapter 11: Table 10. Atlanta, GA.
Equipment
require a prescriptive procedure based ASHRAE
Contact your local Trane office
on the VRP, and only allow the IAQP as [8] 2009 ASHRAE Handbook-Fundamentals, to register.
an approved code variance. Although Chapter 10: p. 6. Atlanta, GA. ASHRAE
allowed by both ASHRAE Standard [9] User’s Manual: ANSI/ASHRAE Standard
189.1 and LEED 2009 to increase zone 62.1-2010. Atlanta, GA. ASHRAE
OA rates above the VRP minimums, the New On-Demand Courses
[10] CONTAM Multizone Airflow and
IAQP cannot be used to decrease zone Contaminant Transport Analysis Software.
OA rates below the VRP minimum http://www.bfrl.nist.gov/IAQanalysis/
CONTAM/
High performance VAV Systems.
rates.
Variable-air-volume (VAV) systems have
Perhaps more designers will use a been used to provide comfort in a wide
future version of the IAQP when range of building types and climates.
comprehensive, accepted and This ENL will discuss design and control
published data about mixtures, sources, strategies that can significantly reduce
air cleaning and subjective evaluation energy use and ensure proper
are available so designers can make the ventilation in VAV systems.
necessary judgments with more
confidence. But for now, most ASHRAE 62.1: Ventilation Rate
designers continue to use the Procedure. This program covers the
prescriptive VRP to reduce design time, Ventilation Rate Procedure for
cost, and risk. calculating zone and system ventilation
airflow, which still exists in the standard
By Dennis Stanke, staff applications engineer, and today. As a prerequisite to obtain LEED
Jeanne Harshaw, program manager,Trane. You can
find this and previous issues of the Engineers
certification, this program will help
Newsletter at www.trane.com/EN. To comment,  viewers understand the requirements
e-mail us at comfort@trane.com. of the Standard.

Visit www.trane.com/
ContinuingEducation to view courses
or to see a complete list of courses.

Trane, Trane believes the facts and suggestions presented here to be accurate. However, final design and
A business of Ingersoll Rand application decisions are your responsibility. Trane disclaims any responsibility for actions taken on
the material presented.
For more information, contact your local Trane
office or e-mail us at comfort@trane.com

6 Trane Engineers Newsletter volume 40–3 ADM-APN042-EN (September 2011)

Вам также может понравиться