Вы находитесь на странице: 1из 1

Domae Residual current devices

Type AC
4500 A, Curve C
Earth leakage protection

&HUWL¿HGFRPSOLDQW,(&
Functions
b The single-phase RCBO residual current device carries out:
v protection of persons against direct and indirect contacts,
v FRPSOHWHSURWHFWLRQRI¿QDOFLUFXLWV RYHUFXUUHQWVDQGLQVXODWLRQIDXOWV 
v safety device to switch both of active and neutral.
b Overload, short circuit and earth fault currents are indicated by location of the
handle in the OFF position.
b A push-test button "T" is positioned on the front of the device for testing that
product is operational.
DB407746-35

1P+N
Residual current devices
Type Rating (In) 30 mA
6 DOM12520
DB406496

10 DOM12521
16 DOM12522
20 DOM12523
25 DOM12524
32 DOM12525
Width in 9-mm modules 2

Additional feature
According to IEC 61009-1
5DWHGUHVLGXDOEUHDNLQJDQGPDNLQJFDSDFLW\ ,ǻP 4500 A
Breaking capacity (Icn)
Ph/N 230 V AC 4500 A

Additional characteristics
Minimum operating voltage of test button 187 V AC
(QGXUDQFH 2& Electrical 10,000 cycles
Mechanical 20,000 cycles
Operating temperature -25°C to +55°C
Storage temperature -30°C to +70°C

Dimensions (mm) Connection


DB406495
DB406007

70 Type Tightening Copper cables


5.5 44 20 torque Rigid Flexible
18 14 mm
DB122945

DB122946

6.0 mm
19
PZ2

45 L and N upstream 2 N.m 1 to 16 mm2 1 to 16 mm2


93
L and N downstream 2 N.m 1 to 10 mm2 1 to 10 mm2
PZ2
11 mm
4 6.0 mm

Note: for any case, isolate power before installation. Wire neutral
prior to installing active.
Weight (g)
Type RCBO
1P+N 136

4 Version : 1.1 17/05/2016 CR902002E