Electrical Apparatus
NAMEPLATE
Laser-scribed
anodized
aluminum.
COOLING
RADIATORS
Detachable, bolt-on
radiators with valves
are available.
BASE
Suitable for skidding,
rolling and jacking. GROUND PADS
Non-corrosive, stainless
steel ground pads on
the front and rear.
CONTROL BOX
Weather-resistant, dust-proof, DRAIN/FILTERING VALVE
NEMA-rated control box for The combination drain and
controls and alarm contacts. filtering valve contains a
fluid sampling device.
Figure 2.
Secondary unit substation transformer with standard features and optional accessories.
2
210-15
3
Primary or Secondary Unit
with 65° C temperature rise
750 840 862 965
65° C Rise 65° C Rise 1000 1120 1150 1288
OA OA/FA
1500 1680 1725 1932
500 575 2000 2240 2300 2576
750 862 +12%
2500 2800 3125 3500
+15%
1000 1150 3750 4200 4687 5250
1500
2000
1725
2300
5000
7500
5600
8400
6750
9375
7000
10500
10000 11200 12500 14000
4687
2500 3125
3750
5000 +25% 6250
12500
7500 9375 TABLE 5
10000 Insulation Test Levels
kV Class Induced Test kV BIL Applied Test
180 or 400 Hz-7200 Cycle Distribution Power 60 Hz (kV)
TABLE 2
Percent Impedance Voltage1 1.2 30 45 10
2.5 45 60 15
kV BIL Low Voltage 5.0 60 75 19
8.7 TWICE 75 95 26
Class < 2400 V ≥ 2400 V
2 3
15.0 RATED 95 110 34
45-150 5.75 6.50 25.0 (Grd Y Only) VOLTAGE 125 150 40
200 7.25 7.00 25.0 150 150 50
250 7.75 7.50 34.5 (Grd Y Only) 125 150 50
34.5 150 200 70
1
The standard tolerance is ± 7.5%.
2
Option for 6.75% is available. 46.0 200 250 95
3
Option for 5.50% is available.
TABLE 6
TABLE 3 Temperature Rise Ratings 0 - 3300 feet (0-1000 meters)
Audible Sound Levels
Standard Optional
Self-cooled, NEMA Average
Two Winding Unit Rating 65° C 55/65° C
kVA Rating dB, OA dB, FA Ambient Temperature Max. 40° C 40° C
Ambient Temperature 24 Hour Av. 30° C 30° C
500 56 67 Temperature Rise Winding1 65° C 55° C
501-700 57 67 Temperature Rise Hotspot 80° C 65° C
701-1000 58 67
1001-1500 60 67 1
Average Rise by resistance. Refer to NEMA Standards TRI; ANSI Standard C57.12.00.
1501-2000 61 67 Note: Derate kVA by 0.4% for each 100 M (330 ft.) that the altitude is above 1000 M (3300 ft.).
2001-2500 62 67
2501-3000 63 67
3001-4000 64 67
4001-5000 65 67
5001-6000 66 68
6001-7500 67 70
7501-10000 68 71
4
210-15
TABLE 7
Oil Filled – Aluminum Windings 55/65°C Rise1
Base Dimensions Drawing Dimensions Approx.
(in.) (in.) Total
C kVA Gallons Weight (Ibs.)
Width Depth A B C D Of Fluid (With Fluid)
H3 X3 500 51 35 69 50 40 59 335 6,300
X2 750 56 36 69 55 36 56 355 7,300
D H2
X1
1000 58 36 69 57 42 62 370 8,200
H1 X0
1500 54 36 78 53 54 75 400 9,800
2000 57 38 78 56 55 109 455 12,000
2500 68 40 78 67 50 99 595 14,680
>2500 * Consult Factory Representative
1
Weights, gallons of fluid and dimensions are for reference only, and not for construction. Please contact
Cooper Power Systems for exact dimensions.
TOP VIEW
TABLE 8
8"
R-Temp® Filled – Aluminum Windings 55/65°C Rise1
Base Dimensions Drawing Dimensions Approx.
(in.) (in.) Total
kVA Gallons Weight (Ibs.)
Width Depth A B C D Of Fluid (With Fluid)
500 51 35 69 50 40 59 325 6,300
A
750 56 36 69 55 42 62 355 7,600
55" 55"
1000 58 36 69 57 42 84 375 8,400
1500 56 36 78 55 62 83 425 10,800
2000 60 40 78 59 56 111 530 13,500
2500 68 40 78 67 58 115 620 16,300
>2500 * Consult Factory Representative
B
1
Weights, gallons of fluid and dimensions are for reference only, and not for construction. Please contact
ELEVATION Cooper Power Systems for exact dimensions.
Figure 3.
High-voltage left (Segment 2) shown. TABLE 9
High-voltage right (segment 4) also Oil Filled – Copper Windings 55/65°C Rise1
available. Base Dimensions Drawing Dimensions Approx.
(in.) (in.) Total
kVA Gallons Weight (Ibs.)
Width Depth A B C D Of Fluid (With Fluid)
500 51 34 69 50 39 59 320 5,500
750 55 38 69 54 39 60 375 7,500
1000 59 38 69 58 45 66 390 8,750
3 1500 51 40 78 50 56 78 435 11,000
2000 59 38 78 58 57 113 475 13,250
2 4 2500 59 38 78 58 57 113 500 14,500
>2500 * Consult Factory Representative
1
1 Weights, gallons of fluid and dimensions are for reference only, and not for construction. Please contact
Cooper Power Systems for exact dimensions.
5
Primary or Secondary Unit
38"
34" 2" (TYP.)
38"
34" 2" (Typ.)
10.5" BUSHINGS 8"
CL
9" BUSHINGS 8"
18" 20"
CL 15" 10.5"
9"
40"
42" 44"
10.5"
4" Ø 0.50" 9" 9" 9" 9"
12 HOLES
10.5"
Figure 7.
Flange.
38.3"
10"
BUSHING 38.3"
CL
34"
24" 24"
34"
BUSHING
CL
18" FRONT VIEW
10"
(with Lift-Off Front Panel)
22"
FRONT VIEW
18"
(with Lift-Off Front Panel)
Figure 5. 22"
Air terminal chamber-bottom entry.
Figure 8.
Air terminal chamber-top entry.
38.3"
38.3"
10"
BUSHING
CL
24 "
BUSHING
CL
55"
55"
FRONT VIEW
18" (with Lift-Off Front Panel)
22"
Figure 9.
Full length cabinet-top entry.
6
210-15
CONSTRUCTION Transformer tanks are pressure-tested ester-based fluid. Envirotemp FR3 fluid
to withstand 7 psig without permanent offers the advantage of a seed oil-based
Core distortion and 15 psig without rupture. dielectric coolant with food grade
The three-legged, step-lap mitered additives, in addition to increased fire
Tank Finish safety when compared to mineral oil.
core construction is manufactured
using a high-quality cutting machine. An advanced multi-stage finishing R-Temp and Envirotemp FR3 fluid
For maximum efficiency, cores are process exceeds ANSI C57.12.28 can be used in a substation trans-
precisely stacked, virtually eliminating standards. The eight-state pretreatment former next to buildings or inside
gaps in the corner joints. process assures coating adhesion buildings with suitable containment
and retards corrosion. It converts tank provisions.
Five-legged wound core or shell-type surfaces to a nonmetallic, water
triplex designs are used for wye-wye insoluble iron phosphate coating. SUBSTATION VFI
connected transformers, and other TRANSFORMER
special transformer designs. The three-step, epoxy primer (E-coat)
provides a barrier against moisture, salt The VFI transformer combines a con-
Cores are manufactured with preci- and corrosives. The electrostatically- ventional Cooper Power Systems dis-
sion cut, burr-free, grain-oriented sili- applied, oven-cured polyester power tribution transformer with the proven
con steel. Many grades of core steel coat (P-coat) enhances resistance to Kyle Vacuum Fault Interrupter (VFI).
are available for optimizing core loss abrasion and impact. A urethane final This combination provides both volt-
efficiency. coat seals and adds ultraviolet age transformation and transformer
protection. overcurrent protection in one space
Coils saving, money saving package.
Substation transformers feature a Vacuum Processing The substation VFI transformer with
rectangular coil configuration with Transformers are dried and filled with transformer protection protects the
wire-wound, high-voltage primaries filtered insulating fluid under vacuum, transformer and provides proper coor-
and sheet-wound secondaries. The while secondary windings are ener- dination with upstream protective
design minimizes axial stress devel- gized. Coils are heated to drive out devices. When a transformer fault or
oped by short circuits and provides moisture, ensuring maximum penetra- overload condition occurs, the VFI
for magnetic balancing of tap tion of fluid into the coil insulation breaker trips and isolates the trans-
connections. system. Special attention to moisture former.
Coils are wound using the highest removal is the major reason for The three-phase VFI breaker has
quality winding machines providing Cooper’s track record of superior independent single-phase initiation,
exacting tension control and conduc- reliability and service life. but is three-phase mechanically
tor placement for superior short-circuit gang-tripped. A trip signal on any
strength and maximum efficiency. Cooling System
phase will open all three phases. This
Extra mechanical strength is provided Oil-Air (OA) cooling is provided with feature eliminates single-phasing of
by diamond pattern, epoxy coated transformers rated 500 kVA. A choice three-phase loads. It also enables the
paper insulation, used throughout the of OA-FFA (Future Forced Air) or VFI breaker to be used as a three-
coil, with additional epoxy at heavy OA-FA (Forced Air) cooling is provided phase loadbreak switch. Because the
stress points. The diamond pattern with units rated 750 kVA and above. VFI breaker is resettable, restoring
distribution of the epoxy and carefully Insulating Fluid three-phase service is faster and
arranged ducts, provide a network of easier.
passages through which cooling fluid Cooper Power Systems transformers
can freely circulate. are available with standard electrical R-TRAN™ FM APPROVED
grade mineral insulating oil or other TRANSFORMER
Coil assemblies are heat-cured under dielectric coolants manufactured by
calculated hydraulic pressure to Cooper Power Systems’ R-Tran
Cooper Power Systems. The highly
ensure performance against short-cir- Transformer is FM Approved for
refined oil is tested and degassed to
cuit forces. indoor locations. Factory Mutual
assure a chemically inert product with Research Corporation’s approval of
Core and Coil Assemblies minimal acid ions. Special additives the R-Tran transformer line makes it
minimize oxygen absorption and
Substation transformer core and coil easy to comply and verify compliance
inhibit oxidation. To ensure high
assemblies are braced with heavy with the 1996 National Electrical
dielectric strength, the oil is retested
heavy steel end plates to prevent the Code (NEC®) section 450-23, Less-
for dryness and dielectric strength,
rectangular coil from distorting under Flammable Liquid-Filled Transformer
refiltered, heated, dried, and stored
fault conditions. Plates are clamped in Requirements for both indoor and
under vacuum before being added to
place using presses, and welded or outdoor locations.
the completed transformer. R-Temp
bolted to form a solid core and coil fluid, manufactured by Cooper Power
assembly. Systems under strict quality control for
optimum transformer cooling charac-
Tanks teristics, provides higher dielectric
Transformer tanks are designed for strength than mineral oil. The special
high strength, and ease of handling, formulation is less flammable as
installation, and maintenance. Tanks defined by the National Electric Safety
are welded using precision-cut, hot- Code, as well as non-toxic and
rolled, pickled and oiled steel. They biodegradable. Envirotemp® FR3 fluid,
are sealed to protect the insulating the fluid used in Envirotran® trans-
fluid and other internal components. formers is a fire resistant, natural
7