Improvements
Submittal Transmittal
Detailed by Each Transmittal
Remarks
Item # Reg # Rev # Spec Sec Sub Sec Description Type Action
0001 02590 0 28 31 00 1.7 C. Equipment List Product Data
(JV2)
0002 02592 0 28 31 00 1.7 E. Permits, Licenses, and Certificates Certifications
(JV2)
0003 03222 0 28 31 00 1.4 Product Data Product Data
Reviewers
REVIEWED APPROVED
REJECTED
4509 Freidrich Lane. Suite 150 Austin, TX 78744 ph: 512.447.3800 fax: 512.447.3811 Lic #20939
Date Submitted: 05/05/2014
4509 Freidrich Lane. Suite 150 Austin, TX 78744 ph: 512.447.3800 fax: 512.447.3811 Lic #20939
NEW FIRE ALARM SYSTEM
SUBMITTAL FOR:
CONTRACTED WITH:
BERGELECTRIC CORPORATION
4509 FRIEDRICH LN, #105
AUSTIN, TEXAS
78744
PROJECT# 47-000XXX
PERMIT # 2014-XXXXXX BP
SUBMITTED BY:
TABLE OF CONTENTS
All data, design, and concepts contained herein are for the expressed purpose of the owner's use only, and is not
intended for duplication or disbursement to any other parties without the expressed written consent of Firetrol Protection
Systems. Firetrol makes no claim that the fire alarm system proposed herein complies with all applicable requirements of
the Americans with Disabilities Act (ADA) of 1991. Firetrol recommends consultation with federal authorities to obtain final
approval of the fire alarm system.
AUSTIN PUBLIC LIBRARY
Fire Alarm System
AUSTIN PUBLIC LIBRARY
Fire Alarm System
EQUIPMENT LIST
EQUIPMENT LIST
BEAM DETECTORS
2 EST EC-50R REFLECTIVE BEAM SMOKE DETECTOR
2 EST ECLLT TEST STATION
DUCT-SMOKE DETECTORS
21 EST SIGA-SD ADDRESSABLE DUCT-SMOKE DETECTOR
21 EST SD-T60 60” SAMPLING TUBES
AUSTIN PUBLIC LIBRARY
Fire Alarm System
EQUIPMENT LIST
INPUT MODULE
1 EST SIGA-CT1 ADDRESSABLE SINGLE INPUT MODULE
134 EST SIGA-CT2 ADDRESSABLE DUAL INPUT MODULE
OUTPUT MODULE
40 EST SIGA-CC1 ADDRESSABLE SINGLE INPUT SIGNAL MODULE
ISOLATION MODULE
24 EST SIGA-IM ADDRESSABLE ISOLATOR MODULE
RELAYS
92 EST MR101C MULTI-VOLTAGE RELAY
5 EST PAM-1 MULTI-VOLTAGE CONTROL RELAY
SPEAKERS
55 EST GC-S7 CEILING MOUNT, SPEAKER STROBE – WHITE
40 EST G4-S7 WALL MOUNT, SPEAKER STROBE – WHITE
SPEAKER/STROBES
70 EST GC-S7VM 70V CEILING MOUNT, MULTI-CANDELA SPEAKER STROBE
- WHITE
100 EST G4-S7VM 70V WALL MOUNT, MULTI-CANDELA SPEAKER STROBE
- WHITE
53 EST WG4WF-SVMHC 70V WALL MOUNT, WEATHERPROOF MULTI-CANDELA SPEAKER
STROBE - WHITE
AUSTIN PUBLIC LIBRARY
Fire Alarm System
EQUIPMENT LIST
WIRING
Per NEC #760
~ TBD FT. 14/2 FIRE ALARM CABLE 14AWG 2-CONDUCTOR COPPER WIRE W/RED
JACKET - NOTIFICATION APPLIANCE CIRCUITS
~ TBD FT. 16/2 FIRE ALARM CABLE 16AWG 2-CONDUCTOR COPPER WIRE W/GREEN
JACKET – SIGNALING LINE CIRCUITS
~ TBD FT. 16/2 FIRE ALARM CABLE 16AWG 2-CONDUCTOR COPPER WIRE
W/WHITE JACKET – SPEAKER CIRCUITS
~TBD FT. 14/2 FIRE ALARM CABLE 14/2AWG 2-CONDUCTOR COPPER WIRE W/YELLOW
JACKET – 24VDC CIRCUITS
~TBD FT. 16/2-OAS FIRE ALARM CABLE 16AWG 2-CONDUCTOR COPPER WIRE OVERALL
SHIELDED W/ORANGE JACKET – RS-485 COMMUNICATION CIRCUITS
AUSTIN PUBLIC LIBRARY
Fire Alarm System
BEAM DETECTORS
1 EST EC-50R REFLECTIVE BEAM SMOKE DETECTOR
1 EST ECLLT TEST STATION
DUCT-SMOKE DETECTORS
1 EST SIGA-SD ADDRESSABLE DUCT-SMOKE DETECTOR
1 EST SD-T60 60” SAMPLING TUBES
The top layer of the LRMs is referred to as the user interface layer. The availability of eight different channels opens a number of new
This layer is made up of the Main Display Interface module and simultaneous notification possibilities:
a system of generic control/display modules. Any control/dis- 1) Live voice page for MNEC or fire-related instructions;
play module can mount on any LRM. This maximizes flexibility of
2) Emergency floor evacuation/notification message;
design for custom systems. The inner and outer doors finish and
secure the enclosure. 3) Alert message on floors above and below the emergency;
4) Stairwell evacuation reinforcement message;
A single panel can support up to 2,500 addressable points,
provide 28 amps @ 24 Vdc, provide access control for up to 124 5) Elevator cab information messages;
doors, and still have room for future expansion. If a single panel is 6) Lobby message instructing occupants to exit the building;
not large enough or you need to distribute functionality throughout 7) Concourse instructions to occupants not to enter the lobby;
the project, then you can network up to 64 panels together!
8) Other instructions to areas not directly affected by the emer-
gency.
Networking/Communications Any combination of the eight audio channels can be automatically
The EST3 Life Safety Network uses a multi-priority peer-to-peer directed to any or all areas of the building, with total manual over-
token ring protocol. The protocol gives EST3 the exceptionally ride as required. Eight channel capability assures that one mes-
fast alarm response time of less than three seconds across the sage is never interrupted in order to process another, a common
network, virtually independent of the total number of nodes. The fault with two-channel systems. This eliminates any chance of
EST3 token ring network configuration also affords long distances confusing the occupants with conflicting messages.
between panels. The distance between any three panels on #18 Survivability is also an integral part of EST3’s digitized audio
AWG (1.0 mm²) is 5,000 ft (1,523m) for both network control and system. Default audio messages are continuously transmitted to
digital audio signals. Supporting a maximum of 64 panels on a all network amplifiers by the ASU. These messages provide audio
network, the total network length can be in excess of 160000 ft supervision for the digital audio chain, and act as a default signal
(48768m). Network and audio communication are via RS-485 if the network data circuit fails or should message control infor-
serial ports. Each two-wire circuit supports Class A (Style 7) or mation fail to reach the ASU. If the audio data circuit fails, each
Class B (Style 4) wiring configurations. Fiber optic media is also amplifier generates a 1KHz temporal (3-3-3) tone that is transmit-
available. ted during an alarm. In the event of an amplifier failure, a backup
As an indication of the high level of system integration, off-premise audio amplifier is automatically substituted for the failed amplifier
communications is handled by the Modcom modem communica- in the cabinet, restoring audio capability. In the unlikely event of
tor module. This module provides the Digital Alarm Communicator multiple amplifier failures, the backup amp replaces the amplifier
Transmitter (DACT) function, sending system status signals for up actively processing the highest priority message in the cabinet.
to 255 accounts to up to 80 different central monitoring stations When messages are no longer directed to a failed amplifier such
and/or commercial paging carriers. The Modcom also acts as a as when a high priority page message ends, the backup amp is
V.32bis 14.4K-baud modem for uploading and downloading of dynamically reassigned to the next highest priority failed amplifier
system access control data remotely via the telephone network. actively processing messages
EST3 Central
Processor Unit
3-CPU3, 3-RS485A, 3-RS485B,
3-RS232 EN54-2:1997+A1
and EN54-
4:1997+A1:2002+A2
pending.
Power Power
J11
J10
J11
J10
Central
exceptional response times over the network, less than three Processor L L L L L
seconds. Unit
R R R R R
Module
Each 3-CPU3 provides slots at the back for mounting Network, 3-CPU3 M M M M M
and RS-232, cards. Removable terminal blocks on the 3-CPU3
support connection of network and audio data wiring. On board
common relays also terminate at the 3-CPU3 terminals. To aid Data
in trouble shooting and service, status LEDs monitor local rail,
Maximum resistance between any 3 panels 90 Ohms
network, RS232 and audio data communications.
Maximum capacitance between any 3 panels 0.3 µF
The Network Communications card mounts to the back of the Maximum distance between any 3 panels
5,000 ft. (1,524 m)
Central Processor Unit. The 3-RS485A card provides a Class A via RS485
(Style 7) or Class B (Style 4) circuit for network communications
Capacitance, entire network
signals and support for a Class B (Style 4) or Class A (Style 7 - Maximum Accumulative Capacitance
dual Style 4) circuit for the digitized audio signals. The 3-RS485B
Wire Size 38.4K Baud 19.2K Baud
card provides a Class B (Style 4) or Class A (Style 7) circuit for
18 AWG 1.4 µF 2.8 µF
network communications signals and a second Class B (Style 4)
16 AWG 1.8 µF 3.6 µF
circuit for the digitized audio signals. Network messages received
14 AWG 2.1 µF 4.2 µF
by the Network Communications card are re-transmitted to the
next network node. Re-transmission maximizes the wire run
lengths between nodes. With 64 nodes miles of network length is Audio
possible. Fail safe mechanisms built into the card direct connect Maximum resistance between any 3 panels 90 Ohms
the data input and output ports should the network card or its Maximum capacitance between any 3 panels 0.09 µF
related Central Processor fail. Network communications may be Maximum distance between any 3 panels
5,000 ft. (1,524 m)
configured via copper or fiber media using the 3-FIBMB. via copper RS485
Engineering Specification
It must be possible to support a single stand alone node or up
to 64 nodes communicating on a peer-to-peer token ring proto-
col network. Network and digitized audio wiring shall be run in a
[choose one: Class A (Style 7) or Class B (Style 4)] configuration.
Network alarm response from alarm input to signal activation must
be under 3 seconds. All field wiring must be to removable terminal
blocks. Status LEDs must be provided for communications of net-
work and internal rail communications. Inter-node communication
speed must be programmable. Internal rail communications speed
must be programmable.
Notes
1. Maximum #14 AWG (1.5 mm2) wire;
minimum #18 AWG (0.75 mm2).
3-CPU(1)(3) Module
3-CPU(1)(3) Module
NC C NO NO C N/A NC NO C NC
To/From next panel
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
DB9 FEMALE
(REAR VIEW)
PIN 9
(5) COM
(3) TXD PORT #2(isolated)
TO PRINTER OR REMOTE
Network Data Riser
(2) RXD
PIN 1
COMMAND SYSTEM,
PLUG PIN #
PIN FUNCTION
OR
DB25 FEMALE
(REAR VIEW)
PIN 13 PIN 25
PIN 13 PIN 25
DB25 FEMALE
(REAR VIEW)
PORT #1
(7) COM
ISOLATED PORT
TO PRINTER OR REMOTE
COMMAND SYSTEM.
(3) RXD
(2) TXD
PIN 14
PIN 1
utcfireandsecurity.com
Ordering Information
© 2010 UTC Fire & Security.
All rights reserved. Catalog Ship Wt.
Description
Number lb (kg)
3-CPU3 Central Processor Unit Module 0.7lb (0.32kg)
0.33lb
3-RS485A Network Communications Card, Class A (Style 7)
(0.15kg)
One Class A/B network data circuit and one Class B audio data 0.33lb
3-RS485B
circuit (0.15kg)
0.33lb
3-RS232 RS-232 Communication Card
(0.15kg)
CPU doors with filler plates. Order separately, one required per CPU 0.25lb
3-CPUDR
where no LCD display is installed. (0.11kg)
05-18-11
In the system status window (top line), the display shows the time
and the status of active and disabled points.
The “Selected Alarm” window, lines 2, 3, 4 automatically display
Located below the general status LEDs are four, LED / Switch the first active event of the highest priority if the user has not taken
common controls. The versatility of EST3 allows system design- control of the system. Once the emergency user takes control, this
ers to define the features as affecting a domain (defined group of window displays user message selections.
nodes) or as global (affects all nodes) across the network. This The system events window of the display shows system event
feature is very useful when configuring systems with multiple build- information. In the example above, the display shows the alarm
ings on one network. As an example, operating the reset in one queue as indicated by the window header and the reversed text
building may have adverse effect in other buildings. With EST3, on the bottom two lines.
having operational differences between buildings on the same
network is not a problem. The queue shows the chronological number of the event (0001
is the first alarm event) followed by the event type (Zone Active).
Pressing Reset starts the system’s reset operation. The yellow EST3 supports over 60 event type messages from which system
LED has three flash rates during reset. The LED flashes fast during designers choose. The second line of each event is the custom
the smoke power down phase of reset, flashes slow during the re- programmable location message, which has space for 40 char-
start phase, and turns on steady for the restoral phase. The Reset acters.
LED turns off when the system is normal.
Pressing Alarm Silence turns off all Notification Appliance Circuits
defined as audible. The yellow LED turns on when silence is active
via the Alarm Silence switch or via alarm silence software timers.
Pressing Panel Silence turns off the system’s internal audible
signal. The yellow LED turns on when panel silence is active. The Most Recent Event window shows the last highest priority
Pressing Drill turns on the drill LED and all signals sound evacua- event in the system (a pull station in this example). This window is
tion. Drill does not activate city tie connections. Auxiliary relays will always displayed and updated automatically by the system. Here
not activate unless programmed to do so with drill. the emergency user can monitor the progress of a fire.
13:35:07 02/17/2003
When EST3 is configured for a local mode system viewing the
subsequent alarm messages is easy, just press the NEXT key.
The next message scrolls into the selected alarm window. The
One line for event number, type, status
One line (40 characters) for location
last highest priority event always remains in view. No matter what
queue the user selects for viewing, the LCD always displays the
most recent alarm. A new alarm event resounds the panel audible
signal and appears immediately on display without overwriting
information the user selected for view
The last two lines on the display make up the status window. This
window shows the total number of active events by queue type:
Alarm, Supervisory, Trouble, and Monitor. The number below each
event is the number of active events existing in each queue.
Alarm History Count: 0000
TROUBLE
N
C
N
O
C
ALARM
N
-
A
N
C
N
O
SUP
C N
C
TB1
The device with the lowest address displays in the first window.
If multiple devices are active, each one is available for viewing by
using the arrow associated Previous or Next keys and scrolling Ribbon cable
through the device list. J1
utcfireandsecurity.com
05-18-11
Signature Driver
Controller Modules
3-SSDC1, 3-SDDC1, 3-SDC1
EN54-2:1997+A1: 2006
and EN54-4:1997+2002
+A2 : 2006
detects an alarm, specialized circuitry will make the node aware of + Power
6
Circuit #1
the alarm condition. The 3-CPU(1/3) will communicate the alarm 1 2 3 4 5 6 7 8 9 10
condition to the rest of the network. Having multiple redundant To TB1 on 3-SDDC1 Module
3-SDDC1
SIGNATURE
a green LED on the detector flashes. Normal green LED activity is CONTROLLER
MODULE
not disturbing to building occupants, but can be quickly spotted To TB2 on 3-SDDC1 Module
TB2
device data to the “Expected” site specific program data. If any Wiring Notes + + Power
6
map fault. Through the 3-CPU3’s RS-232 port a graphical map of 2. All wiring supervised and power limited. TB1
3-SDDC1
loop, including branches (T-Taps) and all of the physical attributes 4 Class A wiring.
DRIVER
CONTROLLER
associated with the device. This diagnostic information is unparal- 5 Class B wiring.
MODULE
leled in the fire detection industry and vital for keeping accurate
TB2
the module.
During installation a common problem with analog/ addressable
+ +
SDC #2 Smoke
systems is locating ground faults. The 3-SSDC1 and 3-SDDC1 Power
6
duplicate addresses, which are also very difficult for most systems
to locate.
Ordering Information
Catalog Shipping
Description
Number Wt. lb (kg)
Single Signature Driver Controller. Comes with one 3-SDC1 Device Card.
3-SSDC1 0.5 (0.23)
Mounts to Local Rail. Add suffex “-E” for EN54 complient versions.
Dual Signature Driver Controller. Comes with two 3-SDC1s.
3-SDDC1 0.5 (0.23)
Mounts to Local Rail. Add suffex “-E” for EN54 complient versions.
3-SDC1 Signature Device Card - upgrades a 3-SSDC1 to a 3-SDDC1 0.25 (0.11)
3-FP Filler Plate, order separately when no LED or LED/Switch module installed. 0.1 (0.05)
05-18-11
Monitor
Module
EST3 Power
Supplies
3-PPS/M series, 3-BPS/M series,
3-BBC/M series Power
Supply
EN54-2:1997+A1
and EN54-4:1997+A1:2002+A2
pending
Power supplies mount to the back of the chassis units or wall- • Automatic load testing of batteries
boxes. The associated power supply monitor module mounts on
the local rail providing system power distribution and mounting
space for any control display module. Access to auxiliary power is
via easily accessible terminal blocks located on the power sup-
ply monitor module. Each power supply produces 7 Amps of
filtered and regulated power. With four power supplies located in
an enclosure (one primary and three booster power supplies) 28
amps of current is available for local rail modules, control display
modules and the eight auxiliary 3.5 amp power outputs (two per
supply).
L
Battery leads are electronically short circuit protected. If a short
R
occurs in the battery leads the charger automatically disables itself
and causes a trouble. The system will constantly look to see if
M
J9
the short has cleared. If the short clears the system automatically
J8
J11
J10
restores.
During operation on standby batteries, battery voltage is constant-
ly monitored. A trouble is reported if the battery voltage falls below
a specified value. J8
J9
J11
J10
J10
J9
J11
J9
J8
J11
Power
J10
Power Distribution
Module
PowerL
Supply (EN-54 only) SupplyR
M
J9
J8
J11
J10
Power
24Vdc * 24Vdc * 24Vdc * 24Vdc *
Supply
2 x 3.5A 2 x 3.5A 2 x 3.5A 2 x 3.5A
Monitoring
4 3 2 1 4 3 2 1 4 3 2 1 4 3 2 1
* Nominal Voltage
Specifications
3-PPS/M & 3-PPS/M-230 & 3-PPS/M-230-E &
Catalog Number 3-BPS/M 3-BPS/M-230 3-BPS/M-230-E
3-BBC/M 3-BBC/M-230 3-BBC/M-230-E
Agency Approvals UL, ULC U L, ULC UL, ULC UL, ULC LPCB EN54*, CE EN54*
Input Voltage 120 Vac (+10%, -15%), 50-60 Hz 230 Vac (+10%, -15%), 50-60 Hz
Brownout Level < or = 102 Vac 96 Vac < or = 195 Vac 184 Vac < or = 195 Vac 188 Vac
3-PPS/M-230 3-PPS/M-230-E
3-PPS/M included
included with included with
with 3-CPU3 current
3-CPU3 current 3-CPU3 current
Current Alarm 50mA Alarm: 50 mA Alarm: 50 mA
Requirements 3-BBC/M Standby 50mA Standby: 50 mA Standby: 50 mA
3-BBC/M-230 3-BBC/M-230-E
Alarm: 70 mA
Alarm: 70 mA Alarm: 70 mA
Standby: 70 mA
Standby: 70 mA Standby: 70 mA
Input Current 3.0 A 1.5 A
Total Output Current Special Applications: 7.0 Amps
Battery Charging 65 AH Sealed 65 AH Sealed 30 AH Sealed
None None None
Capacity Lead-Acid Lead-Acid Lead-Acid
Low Battery Trouble 24 Vdc 22.5 Vdc
Deep Discharge
19.5 Vdc 20.0 Vdc
Cutoff
1 LRM Space +
Mounting 1 LRM space, 1 LRM space,
3-PPS: 2 footprints
Requirements 1 chassis footprint 1 chassis footprint
3-BBC: 1 footprint
Output Voltage 24 Vdc Nominal
Auxiliary Output
Two sources of 3.5 Amps each taken from total output current
Current
Auxiliary Output
18 AWG to 12 AWG (1 mm² to 2.5 mm²)
Terminal Capacity
Output Protection Electronic power limiting & heat sink temperature
Ground Fault
< 10K Ohms
Detection
Latin America
T 305 593 4301
F 305 593 4300
utcfireandsecurity.com
05-18-11
Audio and
Telephone
Masters
3-ASU series
PAGE TO
engineering office
Page to EVAC selects all amplifiers cur- 1 calls connected
ALERT
page delivery.
PHONE
ULI/ULC Listed
47K ohm EOL Resistor
J2 J3 J4
BIN
AIN CIN
J6
AOUT
DIN
J5 J7
BOUT
J9
J8
10 9
J1
J10
J11
8 7 6 5 4 3 2 1
ALL CALL
Page to
Evac
Page to
To Signature
Alert
Data Circuit
All Call
Minus
COUT DOUT
To Phones
Page by
Phone
J8 J9 J9
J8
J11
J10
10 9
NC C NO NO C N/A NC NO C NC
CC1
TROUBLE ALARM SUP 8 7 6 5 4 3 2 1
3-ASU/4 has Chassis, Audio Source Unit, To next panel MAIN PROCESSOR MODULE To Signature
3-CPU Module Data Circuit
Paging Common Control and rail space 3-CPU3
Telephone Riser
for four Local Rail Modules. Mounts in Connect to TB2 on 3-CPU Module
Twisted Shielded Pair
lobby enclosure.
Connect Shield to
Earth Ground only
at the panel. Maintain
shield continuity.
1 14 TB1
TX RX
J1
TB1
J2 J3 J4 Dashed Wires Required
BIN
AIN CIN
AOUT
J5
J6
DIN
J7
BOUT
for Class 'A' Wiring Only
J2 J1 J2 J1
Audio Source Unit
J8 J9
Control Panel
From previous panel
3-CPU Module
J4
1234
Mass Notification
Key-Out
3-REMICA
or
READY TO
PAGE
CONNECT REVIEW PENDING
0 call(s) pending
ACK
Audio-Out 3-3REMICP
ALL CALL EMERGENCY TELEPHONE
(Shielded)
To CPU Module
Page to
Evac
TB2 - Audio A IN
Page to
Alert
All Call
To MN-FVPN or AUX
Minus
Page by
Phone
Engineering Specification
The audio system shall provide eight simultaneous and distinct System amplifiers must be distributed zoned type. Centrally banked
audio channels. These shall consist of a minimum of: Local Page, systems are not acceptable. The circuit must carry a minimum rating
Emergency Communication, Multiple Evacuation, Alert, Auxiliary, of 3.5 Amps for operating 24 Vdc signals.
and General Signaling. Channels shall support hierarchical opera- The system shall provide fully integrated fire fighters’ telephone
tion and be controllable from system programming. The audio system that shall provide 2-way communication between the fire
system also provides Elevator, Stairwell and Auxiliary signaling. alarm control panel and any fire fighters’ telephone station. <<The
Systems that cause signaling devices to go silent while performing Audio Source Unit and Firefighters Telephone shall be installed so
any signaling functions will not be accepted. that a seismic component Importance Factor of 1.5 is achieved.>>
The system must provide operation to 25Vrms or 70.7Vrms speak- The system shall include an alphanumeric user display and controls.
ers. The system must provide as a minimum the following paging When a telephone is activated, a call-in buzzer shall sound, and the
common controls and indicators: Ready to page LED, VU display of location of the phone shall be shown on the alphanumeric display.
paging output level, single switch function for paging to all — Alert The display shall be capable of bilingual operation, displaying Eng-
zones, Evacuation zones, and areas not programmed for signaling. lish, Dutch, Finnish, French, German, Italian, Portuguese or Spanish
The system must provide high quality analog to digital conversion messages.
of paging sources. Digital transmission of paging must be provided The incoming call shall be selected by activating a single button. All
between system nodes. The analog sources must be sampled and subsequent telephone call locations shall be displayed in full text.
converted to digital with a sampling rate no less than 9600 samples The system shall display all incoming calls, all connected phone(s)
per second. It must be possible to transmit signal sources (Alert, on the alphanumeric display. The system shall be configured so that
Alarm, Page, etc.) together over a single pair of wires between nodes. page messages may be issued from any firefighter’s telephone con-
nected to the system, as directed by the emergency operator.
Ordering Information
Ship
Catalog
Description Wt. lb.
Number
(kg)
3-ASU/FT 1 Audio Source Unit with Local Microphone and Firefighters Telephone. 20 (9.1)
3-ASU/4 1 Audio Source Unit w/Local Microphone. Provides four local rail spaces. 15 (6.8)
3-ASU 1 Audio Source Unit w/Local Microphone. Inner door filler plate 15 (6.8)
3-FTCU 1 Firefighters Telephone Control Unit inner door filler plate. 15 (6.8)
Audio Source Unit Memory Expansion. Provides 100 minutes of
3-ASUMX/100 0.5 (.23)
message time.
3-FTEQ Seismic hardening kit for 3-ASU/FT or 3-FTCU telephone handset 2
RFK1 Ferrite Clamp Kit required for EN-54 compliance .25 (.11)
3-LKE UK English Label Kit .25 (.11)
3-LKF French Label Kit .25 (.11)
3-LKR Russian Label Kit .25 (.11)
3-LKS Spanish Label Kit .25 (.11)
1. Add “-CC” for City of Chicago
2. For earthquake anchorage, including detailed mounting weights and center of gravity detail, please refer to
Seismic Application Guide 3101676. Approval of panel anchorage to site structure may require local AHJ,
structural, or civil engineer review.
05-18-11
EST3 Central
Processor Unit
3-CPU3, 3-RS485A, 3-RS485B,
3-RS232 EN54-2:1997+A1
and EN54-
4:1997+A1:2002+A2
pending.
Power Power
J11
J10
J11
J10
Central
exceptional response times over the network, less than three Processor L L L L L
seconds. Unit
R R R R R
Module
Each 3-CPU3 provides slots at the back for mounting Network, 3-CPU3 M M M M M
and RS-232, cards. Removable terminal blocks on the 3-CPU3
support connection of network and audio data wiring. On board
common relays also terminate at the 3-CPU3 terminals. To aid Data
in trouble shooting and service, status LEDs monitor local rail,
Maximum resistance between any 3 panels 90 Ohms
network, RS232 and audio data communications.
Maximum capacitance between any 3 panels 0.3 µF
The Network Communications card mounts to the back of the Maximum distance between any 3 panels
5,000 ft. (1,524 m)
Central Processor Unit. The 3-RS485A card provides a Class A via RS485
(Style 7) or Class B (Style 4) circuit for network communications
Capacitance, entire network
signals and support for a Class B (Style 4) or Class A (Style 7 - Maximum Accumulative Capacitance
dual Style 4) circuit for the digitized audio signals. The 3-RS485B
Wire Size 38.4K Baud 19.2K Baud
card provides a Class B (Style 4) or Class A (Style 7) circuit for
18 AWG 1.4 µF 2.8 µF
network communications signals and a second Class B (Style 4)
16 AWG 1.8 µF 3.6 µF
circuit for the digitized audio signals. Network messages received
14 AWG 2.1 µF 4.2 µF
by the Network Communications card are re-transmitted to the
next network node. Re-transmission maximizes the wire run
lengths between nodes. With 64 nodes miles of network length is Audio
possible. Fail safe mechanisms built into the card direct connect Maximum resistance between any 3 panels 90 Ohms
the data input and output ports should the network card or its Maximum capacitance between any 3 panels 0.09 µF
related Central Processor fail. Network communications may be Maximum distance between any 3 panels
5,000 ft. (1,524 m)
configured via copper or fiber media using the 3-FIBMB. via copper RS485
Engineering Specification
It must be possible to support a single stand alone node or up
to 64 nodes communicating on a peer-to-peer token ring proto-
col network. Network and digitized audio wiring shall be run in a
[choose one: Class A (Style 7) or Class B (Style 4)] configuration.
Network alarm response from alarm input to signal activation must
be under 3 seconds. All field wiring must be to removable terminal
blocks. Status LEDs must be provided for communications of net-
work and internal rail communications. Inter-node communication
speed must be programmable. Internal rail communications speed
must be programmable.
Notes
1. Maximum #14 AWG (1.5 mm2) wire;
minimum #18 AWG (0.75 mm2).
3-CPU(1)(3) Module
3-CPU(1)(3) Module
NC C NO NO C N/A NC NO C NC
To/From next panel
20 19 18 17 16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1
DB9 FEMALE
(REAR VIEW)
PIN 9
(5) COM
(3) TXD PORT #2(isolated)
TO PRINTER OR REMOTE
Network Data Riser
(2) RXD
PIN 1
COMMAND SYSTEM,
PLUG PIN #
PIN FUNCTION
OR
DB25 FEMALE
(REAR VIEW)
PIN 13 PIN 25
PIN 13 PIN 25
DB25 FEMALE
(REAR VIEW)
PORT #1
(7) COM
ISOLATED PORT
TO PRINTER OR REMOTE
COMMAND SYSTEM.
(3) RXD
(2) TXD
PIN 14
PIN 1
utcfireandsecurity.com
Ordering Information
© 2010 UTC Fire & Security.
All rights reserved. Catalog Ship Wt.
Description
Number lb (kg)
3-CPU3 Central Processor Unit Module 0.7lb (0.32kg)
0.33lb
3-RS485A Network Communications Card, Class A (Style 7)
(0.15kg)
One Class A/B network data circuit and one Class B audio data 0.33lb
3-RS485B
circuit (0.15kg)
0.33lb
3-RS232 RS-232 Communication Card
(0.15kg)
CPU doors with filler plates. Order separately, one required per CPU 0.25lb
3-CPUDR
where no LCD display is installed. (0.11kg)
05-18-11
Control Display
Modules
3-LDSM, 3-24x series, 3-12xx series,
3-6/3S1xxx series
Alarm Main
Electrical
Electrical Room Trouble Room
EVAC SHELTER
5th Floor Message Message
EVAC AMBER
5th Floor Strobe Strobe
3-12/S1GY 12 groups green/ yellow Zone Page select with Trouble Annunciation 2 mA base
3-12/S1RY of two w/ red/yellow 12 Alarm and Trouble Annunciation with enable/disable + 1.5 mA per
3-12/S2Y switch yellow/ yellow Supervisory and Trouble Annunciation with enable/disable active LED
ON OPEN D
A
AUTO AUTO M
P
E
OFF CLOSE R
2mA base
Green /Yellow 123 On-Auto-Off fan and Open-Auto-Close Damper Control with
3-4/3SGYWR 4 LEDs + 1.5mA
and White/Red switches Trouble and Normal LED indicators
per active LED
green/yellow /
3-6/3S1G2Y Six On-Auto-Off fan and Open-Auto-Close Damper Control 2 mA base
6 groups of yellow
groups of + 1.5 mA per
3 w/switch green/yellow /
3-6/3S1GYR three Page and Evacuation select with zone trouble active LED
red
Notes:
1) All Control Display Modules are UL and ULC listed.
2) All Control Display Modules mount over one Local Rail Module.
If no local rail module exists the 3-LDSM mounts to local rail
and supports one control display module.
Latin America
T 305 593 4301
F 305 593 4300
utcfireandsecurity.com
05-18-11
Zoned Audio
Amplifiers
3-ZA20A, 3-ZA20B,
3-ZA40A, 3-ZA40B, 3-ZA95
3-ZA95 shown
audio channels. These shall consist of a minimum of: Local Page, Not available on 3-ZA95
Class A circuits only
limited, and wired in a <Class A (Style Z)> <Class B (Style Y)> Field wiring identical
to amplifier #1
Field wiring
identical to
KHz temporal tone generator which shall operate in the event Legend
signal primary audio signals are lost and the amplifier is instructed
UL/ULC Listed 15KW EOL
- - For Class B circuits only
+ +
multiple zoned amplifiers with a common backup amplifier. AUDIO NOTIFICATION APPLIANCE CIRCUIT
Specifications
3-ZA20A 3-ZA20B 3-ZA40A 3-ZA40B 3-ZA95
Agency Listing UL, ULC, CE
Environmental 0°C - 49°C (32°F - 120°F) 93% RH, Non-condensing
Frequency Response 400Hz to 4KHz @ +/- 3dB
Output Voltage 25 VRMS or 70 VRMS
THD (distortion) < 7%
Wire Size 18 to 12 AWG (1.0 to 2.5 mm²)
Internal Tone
1KHz Temporal (3-3-3) Tone (evacuation); 20 PPM (alert)
Generator
SIGA-CC1/2 Support 10 Units, Maximum
62mA for 20 and 40 watt amps;
Standby Current
64mA for the 3-ZA95 watt amp
Alarm Current 1120mA 1120mA 2480mA 2480mA 5540mA
Pwr. Ltd. Audio Output Class A or B Class A or B Class A or B
Class B (Style Y) Class B (Style Y)
Wiring Configuration (Style Z or Y) (Style Z or Y) (Style Z or Y)
15K Ohms 15K Ohms
EOL Resistor 15K Ohms in Class B 15K Ohms in Class B 15K Ohms in Class B
Pwr. Ltd. 24 Vdc NAC Class A or B Class B Class A or B Class B
Wiring Configuration (Style Z or Y) (Style Y) (Style Z or Y) (Style Y)
Line Resistance, Max.* 50 Ohms, Max. 50 Ohms, Max. 50 Ohms, Max. 50 Ohms, Max. N/A
EOL Resistor Line N/A 15 K Ohms N/A 15K Ohms
Capacitance, Max 0.33µF 0.33µF 0.33µF 0.33µF
Space Requirements 1 LRM Space 2 LRM Spaces
India
T : +91 80 4344 2000
F : +91 80 4344 2050
Australia
T +61 3 9239 1200
F +61 3 9239 1299
Europe
T +32 2 725 11 20
F +32 2 721 86 13
Latin America
T 305 593 4301
F 305 593 4300
utcfireandsecurity.com
05-18-11
Hinged Bracket
Filler plate
(ordered separately)
Module
Modem
Communicator
3-MODCOM, 3-MODCOMP
tion of calls in progress by the line seizure relays. In the event that
both lines are busy, the module seizes line one. GREEN
TIP
4 5 (GREEN)
3 6
A fixed DACT testing time can be set at an off-hour, e.g. 2:00am, RJ31X
8 PIN MODULAR
TO PHONE LINE #2
(WIRED SAME AS
again minimizing interruptions and phone line costs. The call time RED 2
1 8
7 CONNECTOR FOR
PHONE LINE #1
PHONE LINE #1)
is programmable, and allows testing of the DACT with the central PREMISES
PHONES 3
4 5
6
RJ31X
8 PIN MODULAR
station. 2 7
CONNECTOR FOR
PHONE LINE #2
1 8
The Modcom series also has the ability to detect Type 1, Type
2 and Type 3 distinctive ringing patterns, permitting it to share 1
its phone lines with other devices and still have a unique phone NO T-TAPS
PERMITTED
number for incoming modem calls. 7 Ft.
(2.13 M) 2
Multiple Modcoms per Network Notes:
Multiple Modcoms can be installed in a single cabinet or located 1 Connect Line 1 and Line 2 to RJ31X or RJ38X
LINE 1 LINE 2
Receivers Tested
Format Manufacturer Model Receiver Card
4/2 and 3/1 Ademco 685 685-1 or 685-8
FBI (Fire Burglary Instruments) CP220
Osborne-Hoffman OH2000
Radionics D6600
Silent Knight 9000 9032
Sur-Gard MLR2, SG-SLR
MCDI TLR, TLR+
Contact ID Ademco 685 685-8
Osborne-Hoffman OH2000
Sur-Gard MLR2, SG-SLR
Radionics D6600
Silent Knight 9000 9032
MCDI TLR, TLR+
SIA DCS Sur-Gard MLR2, SG-SLR
Note 1:
The EST3 is modularly listed under the following standards:
UL 864 categories: UOJZ, UOXX, UUKL and SYZV, UL 294 category ALVY, UL 609 category AOTX, UL 636 category ANET, UL 1076 category APOU, UL 365 category
APAW, UL 1610 category AMCX, UL 1635 category AMCX
ULC-S527, ULC-S301, ULC-S302, ULC-S303, ULC-S306, ULC/ORD-C1076 and ULC/ORD-C693
Please refer to EST3 Installation and Service Manual for complete system requirements.
Ordering Information
Catalog Ship Wt.
Description
Number lb (kg)
3-MODCOM Modem/Dialer (DACT) version 0.5 (0.23)
Modem/Dialer (DACT) w/TAP Pager
3-MODCOMP 0.5 (0.23)
Protocol
Filler Plate, order separately when no LED
3-FP 0.1 (0.05)
or LED/Switch module installed.
U.S.
T 888-378-2329
F 866-503-3996
Canada
Chubb Edwards
T 519 376 2430
F 519 376 7258
Southeast Asia
T : +65 6391 9300
F : +65 6391 9306
India
T : +91 80 4344 2000
F : +91 80 4344 2050
Australia
T +61 3 9239 1200
F +61 3 9239 1299
Europe
T +32 2 725 11 20
F +32 2 721 86 13
Latin America
T 305 593 4301
F 305 593 4300
utcfireandsecurity.com
05-18-11
EST3
Cabinets and
Chassis
3-CAB series, 3-RCC Series
equipment in locations where esthetics are not paramount, like ALL KNOCKOUTS
FOR 3/4" CONDUIT
(15.2 cm)
electrical closets. You can have optional display modules used for
(1.9 cm)
system diagnostics display mounted behind the front door. These OUTER DOOR
2 in
21 in (53.3 cm) 5.64 in
(14.3 cm)
4.4 in
(11.2 cm)
(5.1 cm)
display modules will not be visible with the door closed. Remote
closet cabinets are surface mounting and come in sizes providing
space for one to three chassis with room for standby batteries. A
Chassis *
1.3 in
(3.3 cm)
BATTERY AREA
DO NOT INSTALL CONDUIT
[3RCC.CDR]
.625 in
(1.6 cm)
Ordering Information
Catalog Equipment Ship Wt.
Description Battery Space
Number Mounting Space lb. (Kg)
Chassis Assemblies
Takes one chassis space in wallbox, provides space for 7 local rail modules, up to two power supplies, and a ½ footprint
3-CHAS7 8.4 (3.8)
module.
3-ASU** Takes one chassis space in wallbox, provides an audio source unit /w microphone and an inner door filler plate. 15 (6.8)
3-ASU/4** Takes one chassis space in wallbox, provides an audio source unit /w microphone and four local rail module spaces. 15 (6.8)
3-ASU/FT** Takes one chassis space in wallbox, provides an audio source unit /w microphone and Firefighters Telephone 20 (9.1)
3-FTCU** Takes one chassis space in wallbox, provides Firefighters Telephone Control unit and inner door filler plate. 15 (6.8)
MN-BRKT1 Takes one chassis space in wallbox, provides mounting for MNEC interface equipment 4.0 (1.8)
FSB-BRKT Mounting bracket for FSB-PC communications bridge. Allows FSB-PC to mount on the side of a Chass7 1.0 (0.45)
more...
Notes:
1. All lobby enclosures, wallboxes and doors have a textured gray enamel finish; UL 365 category APAW, UL 1610 category AMCX, UL 1635 category AMCX
outer doors are available in red by adding the suffix “R” to the catalog number, i.e. ULC-S527, ULC-S301, ULC-S302, ULC-S303, ULC-S306, ULC/ORD-C1076,
3-CAB7DR. ULC/ORD-C693
2. Remote closet cabinets will support 65 AH batteries with the use of the 3-BATS Please refer to EST3 Installation and Service Manual for complete system require-
Battery Shelf, which reduces the enclosure’s chassis capacity by one chassis. ments.
3. The EST3 is modularly listed under the following standards: * EN54-2:1997+A1 and EN54-4:1997+A1:2002+A2 pending
UL 864 categories: UOJZ, UOXX, UUKL and SYZV, UL 2572, UL 294 category
ALVY, UL 609 category AOTX, UL 636 category ANET, UL 1076 category APOU, ** Add “-CC” for City of Chicago.
Europe
T +32 2 725 11 20
F +32 2 721 86 13
Latin America
T 305 593 4301
F 305 593 4300
utcfireandsecurity.com
05-18-11
Overview Application
The PT-1 series printers are high speed, 9-pin dot matrix type The PT-1S (serial, RS-232 interface) is used when connecting to
which use standard, continuous tractor feed computer paper. The the CM1(N), CM2N, FCCD, 2-MCM or 3-CPU1. The PT-1P (Paral-
PT-1 series printers are used to permanently record Life Safety lel interface) is used when the printer is connected to the VDU-3,
System changes of state. All printed entries contain the date, time, CCA-1/4/8 or the CGP-1/4/8.
event type and a user defined message for each printed event.
The printer is required in proprietary type systems. In local, auxilia-
ry or remote station systems the printer is ancillary and is optional.
The printer must be backed up by a UPS in a proprietary system. Installation
Printer paper may be fed from the rear or bottom of the printer. The printer comes from the factory with all DIP switches and oper-
ating modes setup for proper operation with the system. The baud
rate in some instances may have to be adjusted to provide reliable
transmission over long distances. When configuring a system to
Standard Features meet the requirements of proprietary, the printer must be located
• High speed, bi-directional printing adjacent to the Fire Command Center.
• Serial (model PT-1S) or parallel (model PT-1P) interface When the printer is located greater than 50 ft (15.2 m) from the
• Front panel setup Fire Command Center, Short Haul Modems (model SHM-M1 or
SHM-F1) may be used. Short Haul Modems will allow distances
• Supports modems for remote installation up to 5 miles (8 km) @ 2400 Baud. When Short Haul Modems are
• Supports fiber optics module used the printer is considered ancillary and the connection is not
supervised.
• LED Status indicators
When the SHM modules are used with the CM1(N) or CM2N an
• RS-232 direct cable IOP3A module must be used to properly power the modules. The
• Printer self-test mode IOP3A may be located on the inside of the Fire Command Center
enclosure.
Canada
Chubb Edwards
T 519 376 2430
Connection Diagram
F 519 376 7258
Southeast Asia
T : +65 6391 9300
F : +65 6391 9306
India
T : +91 80 4344 2000
F : +91 80 4344 2050
Australia
T +61 3 9239 1200
F +61 3 9239 1299
Europe
T +32 2 725 11 20
F +32 2 721 86 13
Latin America
T 305 593 4301
F 305 593 4300 Specifications
utcfireandsecurity.com Print Speed 232 cps
Voltage 120 Vac, ±10% 220/240 Vac, ±10%
© 2010 UTC Fire & Security. Power rating 48VA
All rights reserved.
Frequency 50/60 Hz
MTBF 4000 Hrs @ 25% duty cycle
Size 14.2 x 10.8 x 3.2 inches 36.1 x 27.4 x 8.1 cm
Weight 9.9 lbs (4.5 kg)
Agency Listings UL, ULC, MEA, CSFM
Operating Environment Temperature: 32° - 120°F (0° - 49°C). Humidity: 85% non-condensing
Ordering Information
Model P/N Description
PT-1S 360038 Serial Printer
PT-1P 360039 Parallel Printer
PT-1S/220 360070 Serial Printer-220/240 Vac
PT-1P/220 360071 Parallel Printer-220/240 Vac
Sealed Lead-Acid
Batteries
Overview Application
Rechargeable sealed lead-acid batteries are ideal for use as a When multiple power supplies are provided, each power supply’s
secondary (standby) power source as defined by NFPA 72. Their battery requirements should be calculated individually. Consult
low maintenance and high energy density make them ideal for fire the specific system manual to determine battery capacity require-
alarm signaling applications. ments.
Safety Information
Standard Features Due to a battery’s low internal resistance and high power density, high levels of short
circuit current can develop across battery terminals. Put on protective eye covering
• Rechargeable and remove all jewelry before working on batteries. Do not rest tools or cables on the
• Non-spillable battery, and only use insulated tools. Follow all manufacturers installation instructions
and diagrams when installing or maintaining batteries.
• Non-hazardous
• Low maintenance
• High energy density
U.S.
T 888-378-2329 Ordering Information
F 866-503-3996
Catalog Number Description Shipping Weight, lb (kg)
Canada 12V1A2 1.2 Ah Sealed Lead Acid Battery - 12 Vdc 1.25 (0.57)
Chubb Edwards
12V4A 4.5 Ah Sealed Lead Acid Battery - 12 Vdc 5 (2.27)
T 519 376 2430
F 519 376 7258 12V6A5 7.2 Ah Sealed Lead Acid Battery - 12 Vdc 6 (2.72)
6V8A 8 Ah Sealed Lead Acid Battery - 6 Vdc 4 (1.81)
Southeast Asia 6V10A 12 Ah Sealed Lead Acid Battery - 6 Vdc 5 (2.27)
T : +65 6391 9300
F : +65 6391 9306
12V10A 11 Ah Sealed Lead Acid Battery - 12 Vdc 10 (4.45)
12V17A 18 Ah Sealed Lead Acid Battery - 12 Vdc 13 (5.90)
India 12V24A 26 Ah Sealed Lead Acid Battery - 12 Vdc 20 (9.07)
T : +91 80 4344 2000 12V40A 40 Ah Sealed Lead Acid Battery - 12 Vdc 32 (14.51)
F : +91 80 4344 2050
12V50A 50 Ah Sealed Lead Acid Battery - 12 Vdc 40 (18.14)
Australia 12V65A 65 Ah Sealed Lead Acid Battery - 12 Vdc 49 (22.23)
T +61 3 9239 1200
F +61 3 9239 1299
Europe
T +32 2 725 11 20
F +32 2 721 86 13
Latin America
T 305 593 4301
F 305 593 4300
utcfireandsecurity.com
05-18-11
EST3 Remote
Annunciators
3-ANNCPU3, 3-LCDANN, 3-6ANN,
3-10ANN, 3-EVxxx, 3-4ANN
EN54-2:1997+A1 and
EN54-4:1997+A1:2002+A2
pending
NETWORK A
NETWORK B
24 VDC
24 VDC
SPARE
1 Power limited
circuit Graphic Annunciator
1 2 3 4 5 6 7 8 9 10
To TB1 on 3-ANNCPU3
NOTES:
1. All wiring except earth Wire Specifications
TX RX
RX TX
TX RX
RX TX
TX RX
RX TX
TX RX
Specifications
Catalog Number 3-ANNCPU3 3-ANNSM 3-LCD 3-LCDXL1
Agency Listings UL, ULC, FM, CE, LPCB EN54* pending.
Mounts over 3-ANNCPU
Mounting Space Two Spaces One Space Mounts over 3-ANNCPU
plus two spaces.
Communication Format RS-485 N/A N/A N/A
Current @ 24 Vdc
Standby 144 mA 10mA 40mA 48mA
Alarm 144 mA 10mA 42mA 50mA
Wiring Termination Plug in terminal strip
Twisted Pair 18-14 AWG
Wiring Size
(0.75-1.5 mm²) N/A
5000 ft (1524m)
Max. Wire Distance
between any 3 panels
Relative Humidity 93% non condensing at 90° F (32° C)
Temperature Rating 0-49° C (32 - 120° F)
Wiring Styles Class A or Class B
Note: For a complete list of EST3 annunciator display and control modules please refer to Edwards literature sheet part number 85010-
0055.
* EN54-2:1997+A1 and EN54-4:1997+A1:2002+A2 pending
Engineering Specification
The Life Safety system shall incorporate annunciation of Alarm, units. The LCD interface must provide the ability to display custom
Supervisory, Trouble and Monitor operations. Annunciation must event messages of a minimum of 40 characters. The LCD must
be through the use of both LED display strips complete with a provide the emergency user, hands free viewing of the first and
means to custom label each LED as to its function. Where ap- last highest priority event. The last highest priority event must
plicable control switches must be provided. Switches with LEDs always display and update automatically. System events must
must provide positive feed back to the operator of remote equip- automatically be placed in queues. It shall be possible to view
ment status. An LCD display with basic common control LEDs specific event types separately. Having to scroll through a mixed
and switches shall be provided. The Common Control Switches list of events types is not acceptable. The total number of active
and LEDs provided as minimum will be: Reset switch and LED, events by type must be displayed. It must be possible to custom-
Alarm Silence switch and LED, Panel Silence switch and LED, Drill ize the designations of all user interface LEDs and switches for
switch and LED. It must be possible to add additional common local language requirements. It must be possible to route system
controls as required though the use of modular display / control event messages to specific annunciator locations.
Page 2 of 4 D ATA S H E E T 85010-0069
Not to be used for installation purposes. Issue 10
Dimensions
6.12 in
Semiflush Mount (15.55 cm) Surface Mount
2.75 in 2.75 in
(6.99 cm) (6.99 cm)
0.46 in (1.17 cm)
7.60 in 7.60 in
(19.31 cm) (19.31 cm)
TOP TOP
4ANN/B(-S)
13.19 in. 12.1 in. 13.19 in.
(33.5 cm) (30.7 cm) (33.5 cm)
6ANN/B(-S)
13.19 in. 12.1 in. 13.19 in.
(33.5 cm) (30.7 cm) (33.5 cm)
10ANN/B(-S)
12.1 in. 13.19 in. 12.1 in.
(30.7 cm) (33.5 cm) (30.7 cm)
Liquid Crystal
Display Module
3-LCD MEA
S
CHINA
EN54-2:1997+A1
and EN54-
4:1997+A1:2002+A2
pending
Event Queues
L
Central R
Processor M Fire Fault Disable Monitor
Unit
3-CPU1
For EN54 compliance, EST3 configures for remote proprietary
system operation. This requires that every event must be acknowl-
edged by viewing them before the internal buzzer will silence. The
priority order is Fire, Fault, Disable, Monitor. EN54-2:1997+A1 and
EN54-4:1997+A1:2002+A2 approval is pending.
Ordering Information
Catalog Number Description Shipping Weight, lb. (kg)
3-LCD Liquid Crystal Display Module .8 (.36)
3-LKE UK English Label Kit .25 (.11)
3-LKF French Label Kit .25 (.11)
3-LKR Russian Label Kit .25 (.11)
3-LKS Spanish Label Kit .25 (.11)
05-18-11
Remote
Microphones
3-REMICA, 3-REMICP
3-REMICP 3-REMICA
Canada
1.8 KOhm EOL if not connected
Chubb Edwards to another remote microphone
T 519 376 2430 TB1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20
F 519 376 7258
Southeast Asia
T : +65 6391 9300
F : +65 6391 9306 Engineering Specifications
India Remote paging microphones shall be provided at the locations specified on the drawings.
T : +91 80 4344 2000 Each remote microphone shall provide a dynamic Push-to-Talk microphone, Page level
F : +91 80 4344 2050 meter, Local Page Active LED, Remote Page Active LED, and Trouble LED. Selection of
Australia
paging areas shall be provided using Control Display Modules, which can be programmed
T +61 3 9239 1200 as required for each paging application. The system shall support up to 63 remote micro-
F +61 3 9239 1299 phones.
Europe
T +32 2 725 11 20 Technical Specifications
F +32 2 721 86 13
Installation
Latin America 3-REMICA Takes up two spaces in the 3-ANN series of annunciator cabinets.
T 305 593 4301 3-REMICP Remote microphone in chassis for use in CAB series cabinets.
F 305 593 4300 Input Power 21 to 27 VDC Current: 64 mA
utcfireandsecurity.com Microphone Dynamic, PTT
Audio Output 1 VRMS into 1K Ohms
© 2010 UTC Fire & Security. Audio Input 1 VRMS into 1K Ohms
All rights reserved.
Frequency Response 100 - 4,000 Hz
Supervision Audio Key (PTT) 1 KHz Tone Pulse DC for opens and shorts
Wiring
Maximum Resistance 210 ohms max. from output of last cascaded remote microphone
to 3-ASU remote microphone input
Wire Type Audio = Twisted-shielded pair, 14 - 26 AWG
Key (PTT) = Twisted pair, 14 - 26 AWG
Page level meter, Local Page Active LED, Remote Page Active LED,
Indicators
Trouble LED
Agency Listings UL, ULC
Operating Environment 32°F (0°C) to 120°F (49°C), 93% RH Non-condensing
Ordering Information
Catalog Ship Wt.
Description
Number lb (kg)
3-REMICA Remote microphone for use in 3-ANN series annunciator cabinets 15 (6.8)
3-REMICP Remote microphone in chassis for use in CAB series cabinets 15 (6.8)
Chassis, with space for a 3-REMICP or 3-ASU and four local rail
3-CHASS4 8.5 (3.9)
modules, for use in CAB series cabinets
05-18-11
Input Modules
SIGA-CT1, SIGA-CT1HT,
SIGA-CT2, SIGA-MCT2
SIGA-CT1/2
SIGA-MCT2
MEA
S
CHINA
Application Notes
Available
6-32
The Signature Series intelligent analog-addressable system from Self-tapping
Edwards Security is an entire family of multi-sensor detectors and screws
NOTES
UL/ULC Listed UL/ULC Listed
47KW EOL Input 2 Input 1
47KW EOL
4
3
2
1
Green LED (Normal)
This module will not operate without electrical power. As fires fre- Red LED (Active)
TB15
safeguards with your local fire protection specialist. No connections or jumper settings
required for MCT2.
SIGA-MCT2
Compatibility
The Signature Series modules are compatible only with EST’s
Signature Loop Controller.
Europe
T +32 2 725 11 20
F +32 2 721 86 13
Ordering Information
Catalog Ship Wt.
Latin America Description
Number lbs (kg)
T 305 593 4301
F 305 593 4300 SIGA-CT1 Single Input Module — UL/ULC Listed 0.4 (0.15)
SIGA-CT1HT Single Input Module High Temperature Operation UL/ULC Listed 0.4 (0.15)
utcfireandsecurity.com SIGA-CT2 Dual Input Module — UL/ULC Listed 0.4 (0.15)
© 2010 UTC Fire & Security.
SIGA-MCT2 Dual Input Plug-in (UIO) Module — UL, ULC Listed 0.1 (0.05)
All rights reserved.
Related Equipment
27193-11 Surface Mount Box - Red, 1-gang 1.0 (0.6)
27193-16 Surface Mount Box - White, 1-gang 1.0 (0.6)
Universal Input-Output Module Board w/Riser Inputs
SIGA-UIO2R 0.32 (0.15)
— Two Module Positions
Universal Input-Output Module Board w/Riser Inputs
SIGA-UIO6R 0.62 (0.28)
— Six Module Positions
SIGA-UIO6 Universal Input-Output Module Board — Six Module Positions 0.56 (0.25)
Multifunction Fire Cabinet — Red, supports Signature Module
MFC-A 7.0 (3.1)
Mounting Plates
Transponder Mounting Bracket (allows for mounting
SIGA-MB4 0.4 (0.15)
two 1-gang modules in a 2-gang box)
SIGA-MP1 Signature Module Mounting Plate, 1 footprint 1.5 (0.70)
SIGA-MP2 Signature Module Mounting Plate, 1/2 footprint 0.5 (0.23)
SIGA-MP2L Signature Module Mounting Plate, 1/2 extended footprint 1.02 (0.46)
05-18-11
Control Display
Modules
3-LDSM, 3-24x series, 3-12xx series,
3-6/3S1xxx series
Alarm Main
Electrical
Electrical Room Trouble Room
EVAC SHELTER
5th Floor Message Message
EVAC AMBER
5th Floor Strobe Strobe
3-12/S1GY 12 groups green/ yellow Zone Page select with Trouble Annunciation 2 mA base
3-12/S1RY of two w/ red/yellow 12 Alarm and Trouble Annunciation with enable/disable + 1.5 mA per
3-12/S2Y switch yellow/ yellow Supervisory and Trouble Annunciation with enable/disable active LED
ON OPEN D
A
AUTO AUTO M
P
E
OFF CLOSE R
2mA base
Green /Yellow 123 On-Auto-Off fan and Open-Auto-Close Damper Control with
3-4/3SGYWR 4 LEDs + 1.5mA
and White/Red switches Trouble and Normal LED indicators
per active LED
green/yellow /
3-6/3S1G2Y Six On-Auto-Off fan and Open-Auto-Close Damper Control 2 mA base
6 groups of yellow
groups of + 1.5 mA per
3 w/switch green/yellow /
3-6/3S1GYR three Page and Evacuation select with zone trouble active LED
red
Notes:
1) All Control Display Modules are UL and ULC listed.
2) All Control Display Modules mount over one Local Rail Module.
If no local rail module exists the 3-LDSM mounts to local rail
and supports one control display module.
Latin America
T 305 593 4301
F 305 593 4300
utcfireandsecurity.com
05-18-11
Graphic Annunciator
EV Series Graphic Annunciators
FSCS Series Smoke Control Stations
1-1/4(32)
Fig. 3
Mounting Hole and Knockout Locations
MAXIMUM
A B C AA BB D E
For Use With ... WALLBOX FINISH TRIM RECOMMENDED
in(mm) in(mm) in(mm) in(mm) in(mm) # OF LED'S in(mm) in(mm)
EV1 and FSCS-1 EV1B TEXT, BLACK 24 (610) 18 (458) 3.5 (89) EV1T 26 (660) 20 (508) 40 17.5(445) 10.5 (267)
EV2 and FSCS-2 EV2B TEXT, BLACK 24 (610) 24 (610) 3.5 (89) EV2T 26 (660) 26 (660) 72 17.5(445) 15.75 (400)
EV3 and FSCS-3 EV3B TEXT, BLACK 24 (610) 36 (915) 3.5 (89) EV3T 26 (660) 38 (965) 100 17.5(445) 26.25 (667)
EV4 and FSCS-4 EV4B TEXT, BLACK 36 (914) 48 (1219) 3.5 (89) EV4T 38 (965) 50 (1270) 120 30 (762) 40 (1016)
Graphic Display
Separate Hinged
Outer Door
Wallbox
Mounting Rails
Mounting Instructions:
Optional Surface Mounting - Ref. Fig. 1
Feature Module
c/w Pushbuttons 1. Hold wallbox in level and upright position against the wall.
and LED's 2. Use the mounting holes located in the rear panel to mark the hole positions.
(See Fig. 3)
The top of the wallbox should be no greater than 80" (2032) from the finished floor.
3. Drill the mounting holes. Secure the wallbox using suitable fasteners (By Others).
Optional
Semi-Flush Mounting - Ref. Fig. 2
Semi-Flush Trim
1. Plan wall cutout according to wallbox size. (MIN. DEPTH 3 1/2" (89))
Provide mounting supports for each side of wallbox.
2. Hold the wallbox in a level position.
24(610) x 36(915)
IMPORTANT: Be sure the front of the wallbox is flush to the finished wall surface.
(Shown) 3. Secure the wallbox in position using suitable fasteners (By Others).
4. Install Optional Trim to the wallbox using mounting hardware provided.
All wall boxes and trim kits are fabricated of 16 gauge cold rolled steel
General Notes:
finished in textured black baked enamel.
1. Install in accordance with National and Local Installation Standards.
1 2 3 4 5 6
LED
E PLACEMENT
AREA
BB B
BP1 or Features
1 1
Optional Features
Location with
3-EVRMF
Typical Typical
A B C TRIM AA BB recommended D E
Wallbox Finish recommended
# of switches
IN(mm) IN(mm) IN(mm) IN(mm) IN(mm) # of LEDs (FSCS Series Only) IN(mm) IN(mm)
EV3B TEXT. BLACK 24(610) 36(915) 3.5(89) EV3T 26(660) 38(965) 100 132 17.5(445) 15.75(400)
Driver Board
Mounting
Extrusion/
Chassis These drawings are for information
purposes only and are subject to change
LED Matrix Board
without notice. Consult the relevant instal-
Hinged LED/GRAPHIC Mounting
lation sheet for details.
Graphic Display
Notes:
Optional
2. Mounting Space in 3-EVRMF for
Feature Plate
(1) 3-ANNCPU3 with a 3-LCD and up
or to 4 Control/Display Modules or
BP1 up to 6 Control/Display Modules.
Optional
Flush Trim
Separate Hinged
3. No Driver Modules can mount on the
Outer Door rails behind the Module Mounting Frame.
Optional 3-EVRMF
Module Mounting
Frame
(7 EIA Panel spaces high)
Battery Shelf
CBA-BTS
3-EVRMF Optional
Module Mounting Frame
(7 EIA panel spaces high)
TOP TOP
Mounting Bolt
Knockout
Fig. 4
4.5 Optional
Battery Shelf
CBA-BT5
3.0 (76)
Knockout Battery also fits
in bottom of box
Fig. 1
Optional Features
Location with RSAN-6
A B C Trim AA BB Typical D E
Wallbox Finish Recommended
IN(mm) IN(mm) IN(mm) IN(mm) IN(mm) # of LEDs IN(mm) IN(mm)
EV3B TEXT. BLACK 24(610) 36(915) 3.5(89) EV3T 26(660) 38(965) 100 17.5(445) 15.75(400)
Driver Board
Mounting
Extrusion/
Chassis
Wallbox
Mounting Rails
Optional
Feature Plate
& BP1 Separate Hinged
Outer Door
or
BP2
Optional
Semi-Flush Trim
Notes:
1. No Driver Modules can mount on the rails behind
the Module Mounting Frame.
2. Mounting space in RSAN-6 for [1] SMDN(-C) with
up to 4 SAN modules or up to 6 SAN modules.
Optional
Module Mounting
Frame
(6 EIA Panel spaces high)
Remote Booster
Power Supplies
BPS6A, BPS10A
MEA
476-91-E
Vol.13
Side View
diagnostic LEDs: one for each NAC fault, one for battery fault, one Front View
for ground fault, and one for AC power.
The unique dual-input activation circuits of the BPS can be acti-
vated by any voltage from 6 to 45 VDC (filtered-regulated) or 11
D1 D6
to 33 Vdc (full-wave rectified, unfiltered). The first input circuit can
Side View
be configured to activate 1-4 of the four possible outputs. The
second input circuit can be configured to control circuits 3 and 4. All knockouts
When outputs are configured for auxiliary operation, these circuits for 3/4 in conduit
can be configured to stay on or automatically deactivate 30 sec- (1.9 cm)
onds after AC power is lost. This feature makes these circuits ideal
for door holder applications. The BPS also has a separate 200
mA 24 Vdc output that can be used to power internal activation
modules.
D1 D2 D3 D4 D5 D6
BPS NACs can be configured for a 3-3-3 temporal or continuous
output. California temporal rate outputs are also available on cer- 17.0 in 3.5 in 13.0 in 6.5 in 3.375 in 12.0 in
tain models. This makes the BPS ideal for applications requiring (43.2 cm) (8.9 cm) (33.0 cm) (16.5 cm) (8.6 cm) (30.4 cm)
signaling rates that are not available from the main system.
In addition to the internally generated signal rates, the BPS can
also be configured to follow the coded signal rate of the main Wire routing
system NACs. This allows for the seamless expansion of existing
NACs.
The BPS enclosure has mounting brackets for up to three Signa-
ture modules to the right of the circuit board.
Engineering Specification
Supply, where needed, Edwards BPS Series Booster Power Sup-
plies (BPS) that are interconnected to and supervised by the main
system. The BPS shall function as a stand-alone auxiliary power
supply with its own fully-supervised battery compliment. The BPS
battery compliment shall be sized to match the requirements of
the main system. The BPS shall be capable of supervising and
charging batteries having the capacity of 24 ampere-hours for
Mass Notification/Emergency Communication (MNEC), life safety
and security applications, and the capacity of 65 ampere-hours for
access control applications.
<<The BPS shall be capable of installation for a seismic com-
ponent Importance Factor of 1.5.>> The BPS shall provide a
minimum of four independent, fully supervised Class B circuits
that can be field configurable for notification appliance circuits or
auxiliary 24 Vdc power circuits. BPS NACs shall be convertible to
a minimum of two Class A NACs. Each BPS output circuit shall Notes
be rated at 3 amperes at 24 Vdc. Each output circuit shall be 1. Maintain 1/4-inch (6 mm) spacing between power-limited and nonpower-limited
wiring or use type FPL, FPLR, or FPLP cable per NEC.
provided with automatically restoring overcurrent protection. The [2] Power-limited and supervised when not configured as auxiliary power. Non-
BPS shall be operable from the main system NAC and/or Edwards supervised when configured as auxiliary power.
Signature Series control modules. BPS NACs shall be configurable [3] Source must be power-limited. Source determines supervision.
for continuous, 3-3-3 temporal or optionally, California rate. Fault 4. When using larger batteries, make sure to position the battery terminals towards
conditions on the BPS shall not impede operation of main sys- the door.
tem NAC. The BPS shall be provided with ground fault detection
circuitry and a separate AC fail relay.
Sense 1 Input
Sense 2 Input
NAC output #1
Existing NAC end-of-line resistors are not required to be Fire Alarm NAC output #2
installed at the booster’s terminals. This allows multiple Control Panel NAC output #3
boosters to be driven from a single NAC circuit without the NAC output #4
need for special configurations.
Booster Power
Supply
+
NAC1/ UL listed NAC1/ UL listed
AUX1 EOL 15 kÙ AUX1 EOL 15 KW
NAC2/
+
+
NAC2/
Notification appliance circuit (NAC) AUX2 Notification appliance circuit (NAC)
AUX2
UL listed
+
UL listed
+
NAC3/ NAC3/
AUX3 EOL 15 kÙ AUX3 EOL 15 KW
+
+
NAC4/ NAC4/
AUX4 AUX4
+
TB5
Continuous Continuous
+
+
IN IN
Sense 1 COM Sense 1 COM
OUT + OUT EOL 47 K
+
IN IN
Sense 2 COM EOL 47 kÙ 10 9 Sense 2 COM
OUT OUT EOL 47 K
CC1(S) module [1][3]
NO NO + +
Trouble COM 8765 4 321 Trouble COM
10 9 10 9
NC NC
TB2
+ + +
TB2 CC1(S) module CC1(S) module
Data in from Data out to 8765 4 321 8765 4 321
CT1 previous device
module [4] next device
or Signature [1] [1]
+ + + +
controller
Data in from previous + + *The Booster supports AC Power fail delay [3]
Data out to of three hours via its trouble contact when
device or Signature
next device dip switch SW2-6 is on. All other troubles
controller
are reported to supervising module or panel
without delay via Sense inputs.
TB1 24 V 12 V
EOL
+
NAC2/
AUX2
+
NAC3/
AUX3
+
NAC4/
AUX4
Control panel BPS [1]
Card reader Card reader Card reader
controller controller controller
+ + + + +
To next
device
[1] Disable the BPS’s ground fault jumper (JP3) or end
Ordering Information
Catalog Description Shipping
Number Wt. lb (kg)
BPS6A 6.5 Amp Booster Power Supply 13 ( 5.9)
BPS6AC 6.5 Amp Booster Power Supply (ULC) 13 ( 5.9)
BPS6A/230 6.5 Amp Booster Power Supply (220V) 13 ( 5.9)
BPS6CAA 6.5 Amp Booster Power Supply with California rate 13 ( 5.9)
BPS10A 10 Amp Booster Power Supply 13 ( 5.9)
BPS10AC 10 Amp Booster Power Supply (ULC) 13 ( 5.9)
BPS10A/230 10 Amp Booster Power Supply (220V) 13 ( 5.9)
BPS10CAA 10 Amp Booster Power Supply with California rate 13 ( 5.9)
1. Requires installation of sepa-
rate battery cabinet. Related Equipment
2. BPS supports batteries greater 12V6A5 7.2 Amp Hour Battery, two required 3.4 (1.6)
than 24 Amp hours for access
control applications only.
12V10A 10 Amp Hour Battery, two required 9.5 (4.3)
3. For earthquake anchorage, 3-TAMP Tamper switch
including detailed mounting BC-1EQ Seismic Kit for BC-1. Order BC-1 separately. See note 3.
weights and center of gravity BPSEQ Seismic kit for BPS6A or BPS10 Booster Power Supplies. See
detail, refer to Seismic Applica- note 3
tion Guide 3101676. Approval
of panel anchorage to site BC-1 Battery Cabinet (up to 2 - 40 Amp Hour Batteries) 58 (26.4)
structure may require local BC-2 Battery Cabinet (up to 2 - 17 Amp Hour Batteries) 19 (8.6)
AHJ, structural or civil engineer 12V17A 18 Amp Hour Battery, two required (see note 1) 13 ( 5.9)
review.
12V24A 24 Amp Hour Battery, two required (see note 1) 20 (9.07)
12V40A 40 Amp Hour Battery, two required (see notes 1, 2) 32 (14.5)
12V50A 50 Amp Hour Battery, two required (see notes 1, 2) 40 (18.14)
12V65A 65 Amp Hour Battery, two required (see notes 1, 2) 49 (22.2)
04-05-12
101
96
Approx Final Charge 0.07 (70 mA)
Current (2.45 v/c Cycle)
Terminal Type Type A / (G optional)
Self Discharge 9 months @ 21°C
Case Material ABS – Gray* or Black
Due to changes in the manufacturing processes, specifications may change without notice.
*Gray option is Flame Retardant ABS.
Actual Wattage / Ampere Capacity at Various Discharge Times (Volt per Cell @ 25°C)
Cut Off Voltage
Time
5 Min. 10 min. 15 min. 30 min. 45 min. 60 min.
1.75 v/c W 45.4 30.77 23.28 12.9 10.31 8.07
25°C A 25.94 17.58 13.3 7.37 5.89 4.61
1.67 v/c W 47.76 31.4 23.9 13.09 10.04 8.07
25°C A 28.6 18.8 14.31 7.84 6.01 4.83
1.60 v/c W 49.28 31.52 24.0 13.3 9.3 7.79
25°C A 30.8 19.7 15.0 8.31 5.81 4.87
Synchronization
Output Module
SIGA-CC1S, MCC1S
MEA
Patented
Personality Codes
The operation of the SIGA-CC1S is determined by their sub-type
code or “Personality Code”. The code is selected by the installer SIGA-MCC1S: mount the UIOxR motherboard inside a suitable
depending upon the desired application and is downloaded from Edwards enclosure with screws and washers provided. Plug the
the loop controller. module into any available position on the motherboard and secure
Personality Code 5: Signal Power or Audio Evacuation (sin- the module to the motherboard with the captive screws. Wiring
gle riser). Configures the module for use as a Class B Audible/ connections are made to the terminals on the motherboard (see
Visible Signal power (24 Vdc polarized) or Audio Evacuation (25 wiring diagram). UIOxR motherboard terminals are suited for #12
or 70 VRMS) power selector. The ring-tone generator is disabled. to #18 AWG (2.5 mm2 to 0.75 mm2) wire size.
The output circuit is monitored for open or shorted wiring. If a UIO Motherboard
short exists, the control panel inhibits the activation of the audible/ 6-32
visible signal circuit to prevent connection to the power circuit. Self-tapping
screws
Personality Code 6: Telephone with ring-tone (single riser).
Configures the module for use as a Telephone power selector.
When a telephone handset is plugged into its jack or lifted from its Plug-in (UIO) Captive
Module screws
hook, the module generates its own Ring-Tone signal. A separate
ring-tone circuit is not needed. The module sends this signal to
the control panel to indicate that an off-hook condition is present.
When the system operator responds to the call, the ring-tone #6 Flat washers
signal is disabled.
Cabinet or electrical enclosure
Personality Code 25: Visual Signal Synchronization. This
personality code configures the module to provide synchronization
of fire alarm signals across multiple zones. It functions as a signal
power (24 Vdc) riser selector. The output wiring is monitored for Electronic Addressing
open circuits and short circuits. A short circuit will cause the fire
The loop controller electronically addresses each module saving
alarm control panel to inhibit the activation of the audible/visual
valuable time during system commissioning. Setting complicated
signal circuit so the riser is not connected to the wiring fault.
switches or dials is not required. Each module has its own unique
serial number stored in its “on-board memory”. The loop control-
ler identifies each device on the loop and assigns a “soft” address
Warnings & Cautions to each serial number. If desired, the modules can be addressed
using the SIGA-PRO Signature Program/Service Tool.
This module will not operate without electrical power. As fires fre-
quently cause power interruption, we suggest you discuss further
safeguards with your fire protection specialist.
Testing & Maintenance
Edwards recommends that these modules be installed according The module’s automatic self-diagnosis identifies when it is defec-
to latest recognized edition of national and local fire alarm codes. tive and causes a trouble message. The user-friendly maintenance
program shows the current state of each module and other perti-
nent messages. Single modules may be turned off (de-activated)
Compatibility temporarily, from the control panel.
The Synchronization Output Module is compatible with EST’s Sig- Scheduled maintenance (Regular or Selected) for proper system
nature Loop Controller operating under EST3 version 2.0 or higher, operation should be planned to meet the requirements of the
and QuickStart Signature Loop Intelligent Controller. Authority Having Jurisdiction (AHJ). Refer to current NFPA 72 and
ULC CAN/ULC 536 standards.
Personality Enhanced Integrity and Genesis Devices Personality Enhanced Integrity and Genesis Devices
Code 25 Code 25
UL/ULC Listed UL/ULC Listed
47KW EOL 47KW EOL
1 23 4
UIO(R) series motherboard
473387352
8 7 6 5 4 3 2 1
Data Out
+
MCC1S
-
CAT NO.
4
TB1 3
2
1
Green LED (Normal) TB15
Riser out (+) Red LED (Active)
To next device
Riser out (-) 1 23 4
Riser in (+) -
From control panel Data out (+) Riser 1 In +
- Riser 1 Out
To next device or EOL resistor. +
Riser in (-) Data out (-)
Data in (+)
From Signature Controller
or Previous Device
Data in (-)
NAC1/ UL listed
AUX1 EOL 15 KW
NAC2/
+
NAC3/
AUX3 EOL 15 KW
+
NAC4/
AUX4
200 mA AUX
TB5
Continuous
+
IN
Sense 1 COM
OUT EOL 47 K
+
IN
Sense 2 COM
OUT EOL 47 K
NO + +
Trouble COM
10 9 10 9
NC
TB2 CC1(S) module CC1(S) module
8765 4 321 8765 4 321
[1] [1]
+ + + +
[3]
Related Equipment
27193-21 Surface Mount Box - Red, 2-gang 2 (1.2)
27193-26 Surface Mount Box - White, 2-gang 2 (1.2)
Universal Input-Output Module Board w/Riser Inputs
SIGA-UIO2R 0.32 (0.15)
- Two Module Positions
Universal Input-Output Module Board w/Riser Inputs
SIGA-UIO6R 0.62 (0.28)
- Six Module Positions
SIGA-UIO6 Universal Input-Output Module Board - Six Module Positions 0.56 (0.25)
235196P Bi-polar Transient Protector 0.01 (0.05)
Multifunction Fire Cabinet - Red,
MFC-A 7.0 (3.1)
supports Signature Module Mounting Plates
SIGA-MP1 Signature Module Mounting Plate, 1 footprint 1.5 (0.70)
SIGA-MP2 Signature Module Mounting Plate, 1/2 footprint 0.5 (0.23)
SIGA-MP2L Signature Module Mounting Plate, 1/2 extended footprint 1.02 (0.46)
05-20-11
Intelligent Smoke
Detector with
Optional
CO Sensor
SIGA2-PS, SIGA2-PCOS
Like all Signature Series detectors, the SIGA2-P(CO)S is an intel- • Ground fault detection by module
ligent device that gathers analog information from its smoke and • Up to 250 devices per loop
CO sensor (if present), converting this data into digital signals. To
make an alarm decision, the detector’s on-board microprocessor • Two levels of environmental compensation
measures and analyzes sensor readings and compares this infor- • Two levels of dirty detector warning
mation to historical data. Digital filters remove signal patterns that
are not typical of fires, thus virtually eliminating unwanted alarms. • Twenty pre-alarm settings
• Five sensitivity settings
The SIGA2-PCOS includes an advanced carbon monoxide sensor
and daughterboard. When the electrochemical cell reaches its end • Non-volatile memory
of life after approximately six years, the detector signals a trouble
• Electronic addressing
condition to the control panel. The sensor/daughterboard module
is field-replaceable. • Environmental compensation
• Identification of dirty or defective detectors
• Automatic day/night sensitivity adjustment
• Bicolor (green/red) status LED
• Standard, relay, fault isolator, and audible mounting bases
- a short on the line causes all iso- 5. To next SIGA-AB4GT sounder base or EOL relay.
lators to open within 23 msec 6. SLC_OUT to next intelligent addressable device.
- at 10 msec intervals, 7. SLC_IN from intelligent addressable controller or previous device.
beginning on one side 8. From SIGA-TCDR Temporal Pattern Generator or previous SIGA-AB4GT
of the Class A sounder base.
circuit nearest the loop
controller, the isolators
close to provide the
next isolator down the
line with power Term Description Audible Detector Base, SIGA-AB4G
1 Not Used
- when the isolator next to 2 DATA IN/OUT (+) This base is designed for use where localized or group alarm sig-
the short closes, reopens within 10 msec.
3 DATA IN (-)
4 Not Used
naling is required. When the detector senses an alarm condition,
5 Not Used the audible base emits a local alarm signal. The optional SIGA-CRR
The process repeats beginning on the 6 DATA OUT (-) Polarity Reversal Relay can be used for sounding to other audible
other side of the loop controller. 7 Not Used
bases on the same 24 Vdc circuit.
Southeast Asia
T : +65 6391 9300
F : +65 6391 9306 Specifications
India SIGA2-PS SIGA2-PCOS
T : +91 80 4344 2000 Normal operating current 45 µA 70 µA
F : +91 80 4344 2050 Alarm current 18 mA 18 mA
Australia
Standalone alarm current 45 µA 70 µA
T +61 3 9239 1200 Operating voltage 15.20 to 19.95 VDC
F +61 3 9239 1299 Air velocity 0 to 4,000 ft./min (0 to 20 m/s).
Construction High impact engineering polymer
Europe
T +32 2 725 11 20 Wall mounting Maximum 12 in (305 mm) from ceiling
F +32 2 721 86 13 Mounting Plug-in
Shipping weight 0.44 lb. (164 g)
Latin America
Compatible bases See Ordering Information
T 305 593 4301
F 305 593 4300 Operating environment 32 to 120°F (0 to 49°C), 0 to 93% RH, noncondensing
Storage temperature −4 to 140°F (−20 to 60°C)
utcfireandsecurity.com Environmental compensation Automatic
© 2010 UTC Fire & Security.
All rights reserved.
Ordering Information
Catalog Ship Wt.
Description
Number lbs (kg)
SIGA2-PS Intelligent Photoelectric Detector 0.4 (0.16)
SIGA2-PCOS Intelligent Photoelectric Detector with carbon monoxide sensor 0.4 (0.16)
Intelligent Photoelectric Detector with carbon monoxide sensor
SIGA2-PCOS-CA 0.4 (0.16)
(for use in Canadian markets only).
Accessories
SIGA-SB Detector Mounting Base - Standard
SIGA-SB4 4-inch Detector Mounting Base c/w Trim Skirt
SIGA-RB Detector Mounting Base w/Relay
SIGA-RB4 4-inch Detector Mounting Base w/Relay, c/w Trim Skirt 0.2 (.09)
SIGA-IB Detector Mounting Base w/Fault Isolator
SIGA-IB4 4-inch Detector Mounting Base w/ Fault Isolator, c/w Trim Skirt
SIGA-LED Remote Alarm LED (not for EN54 applications)
SIGA-AB4G Audible (Sounder) Base for Fire Detectors 0.3 (0.15)
SIGA-AB4GT Audible (Sounder) Base for CO and Fire Detectors 0.3 (0.15)
SIGA-TCDR Temporal Pattern Generator 0.3 (0.15)
SIGA-TS4 Trim Skirt (supplied with 4-inch bases) 0.1 (.04)
2-SPRC1* Replacement Smoke Chamber (for SIGA2-PS detectors) 0.1 (.04)
2-SPRC2* Replacement Smoke Chamber (for SIGA2-PCOS detectors) 0.1 (.04)
2-CORPL* Replacement CO Sensor 0.1 (.04)
*Release pending.
05-18-11
Intelligent Heat
Detectors with
Optional
CO Sensors
SIGA2-HFS, SIGA2-HRS, SIGA2-HCOS
Installation Accessories
Installation Detector mounting bases have wiring terminals that are acces-
Signature Series detectors
mount to North American sible from the “room-side” after mounting the base to the electrical
1 box. The bases mount to North American 1-gang boxes and to
1-gang boxes, 3-1/2 inch
3½ inch or 4 inch octagon boxes, 1½ inches (38 mm) deep. They
or 4 inch octagon boxes, 2 also mount to European BESA and 1-gang boxes with 60.3 mm
and to 4 inch square electri- fixing centers. The SIGA-SB4, SIGA-RB4, and SIGA-IB4 mount to
cal boxes 1-1/2 inches (38 North American 4 inch sq. electrical boxes in addition to the above
mm) deep. They mount to boxes. They include the SIGA-TS4 Trim Skirt which is used to
European BESA and 1-gang cover the “mounting ears” on the base. The SIGA-AB4G mounts
boxes with 60.3 mm fixing 1. Tamper-resist lever arm on base to a 4” square box only.
centers. See mounting base (Break off to disable.)
installation and wiring for 2. Access slot for tamper-resist mechanism
more information.
The user-friendly maintenance program shows the current state Remote LED SIGA-LED - The remote LED connects to the
of each detector and other pertinent messages. Single detectors SIGA-SB or SIGA-SB4 Standard Base only. It features a North
may be turned off temporarily from the control panel. Availability American size 1-gang plastic faceplate with a white finish and red
of maintenance features is dependent on the fire alarm system alarm LED.
used. When the CO sensor’s electrochemical cell reaches its end SIGA-TS4 Trim Skirt - Supplied with 4 inch bases, it can also
of life, the detector signals a trouble condition to the control panel. be ordered separately to use with the other bases to help hide
The sensor/daughterboard module is field-replaceable. Scheduled surface imperfections not covered by the smaller bases.
maintenance (Regular or Selected) for proper detector operation
SIGA-AB4G and SIGA-AB4GT - These sounder bases are de-
should be planned to meet the requirements of the Authority Hav- signed for use where localized or group alarm signaling is required.
ing Jurisdiction (AHJ). Refer to current NFPA 72, NFPA 720, and The SIGA-AB4G is compatible with Signature Series smoke and
ULC CAN/ULC 536 standards. heat detectors. The SIGA-AB4GT sounder base, when used with
the SIGA-TCDR Temporal Pattern Generator module, adds an
audible output function to any Signature Series detector, including
Compatibility fire and CO detectors.
SIGA2-PS detectors are compatible only with the Signature Loop
Controller.
Volume setting
Relay Detector Base, SIGA-RB, SIGA-RB4
Tone setting
Default = High volume Default = Temporal pattern
Cut for low volume Cut for steady tone
This base includes a relay. Nor-
mally open or closed operation
DATA- DATA- DATA+
SIG+ SIG- OUT IN IN/OUT
V.2 only). The relay base does not Relay and Audible Bases operate as follows:
Term Description
support the SIGA-LED Remote 1 Normally Open
LED. CONTACT RATING 2 DATA IN/OUT (+) - at system power-up or reset, the relay is de-energized
1.0 Amp @ 30 VDC 3 Common - when a detector is installed in the base with the power
(Pilot Duty) 4 DATA IN (-)
5 Not Used on, the relay energizes for four seconds, then de-energizes
6 Normally-Closed
7 DATA OUT (-)
- when a detector is removed from a base with the power on,
the relay is de-energized
- when the detector enters the alarm state, the relay is energized.
Ordering Information
Catalog Ship Wt.
Description
Number lbs (kg)
SIGA2-HRS Intelligent rate-of-rise heat detector 0.4 (0.16)
SIGA2-HFS Intelligent fixed temperature heat detector 0.4 (0.16)
SIGA2-HCOS Intelligent fixed temperature heat detector with CO sensor 0.4 (0.16)
Intelligent fixed temperature heat detector with CO sensor
SIGA2-HCOS-CA 0.4 (0.16)
(for use in Canadian markets only)
Accessories
SIGA-SB Detector Mounting Base - Standard
SIGA-SB4 4-inch Detector Mounting Base c/w Trim Skirt
SIGA-RB Detector Mounting Base w/Relay
SIGA-RB4 4-inch Detector Mounting Base w/Relay, c/w Trim Skirt 0.2 (.09)
SIGA-IB Detector Mounting Base w/Fault Isolator
SIGA-IB4 4-inch Detector Mounting Base w/ Fault Isolator, c/w Trim Skirt
SIGA-LED Remote Alarm LED (not for EN54 applications)
SIGA-AB4G Audible (Sounder) Base for Fire Detectors 0.3 (0.15)
SIGA-AB4GT Audible (Sounder) Base for CO and Fire Detectors 0.3 (0.15)
SIGA-TCDR Temporal Pattern Generator 0.3 (0.15)
SIGA-TS4 Trim Skirt (supplied with 4-inch bases) 0.1 (.04)
2-CORPL* Replacement CO Sensor 0.1 (.04)
*Release pending.
05-18-11
EC-50R/-100R Reflector
MEA
Test Station
Overview Operation
The EC-50R/-100R comprises a transmitter and receiver in a Alarm Threshold: Alarm thresholds of 25%, 35% and 50%
single enclosure and is usually installed between 19 inches and obscuration can be selected to suit the environment, with 25%
24 inches below the ceiling. The transmitter emits an invisible the most sensitive setting. The factory default setting is 35 percent
infrared light beam that is reflected via a prism mounted directly and is used for most typical applications. If the received infrared
opposite and with a clear line of sight. The reflected infrared light signal reduces to below the selected threshold for approximately
is detected by the receiver and analyzed. Smoke in the beam path 10 seconds, the fire relay is activated.
will reduce the received infrared light proportionally to the density
Fire Alarm: There are two modes to the operation of the fire
of the smoke. The detector analyzes this attenuation or obscura-
relay. Auto reset mode will reset the fire relay 5 seconds after the
tion of light and acts accordingly. Detectors are typically mounted
received infrared signal has recovered to a level above the Alarm
within ±30 feet (9.14 m) of a potential fire source. Consult your
threshold. Latching mode holds the fire relay active indefinitely
Authority Having Jurisdiction for spacing requirements specific to
after an Alarm condition has occurred. To clear the latched mode,
your locality.
power must be removed from the Detector for a minimum of 5
seconds.
Trouble Alarm: If the infrared beam is obscured rapidly to a level
Standard Features of 90% or greater for approximately 10 seconds, the Trouble relay
• Coverage: 50R range 15 -160 ft (4.6 - 48.8 m); is activated. Typical causes of trouble include an object being
100R range 160- 330 ft (48.8 - 100 m) placed in the beam path, transmitter failure, loss of the prism, or
• Microprocessor controlled sudden misalignment of the detector. The Trouble relay will reset
within 2 seconds of the trouble being cleared.
• Automatic drift compensation
Automatic Gain Control (AGC): The Detector monitors long
• Simple alignment term degradation of signal strength caused by component aging
• Selectable alarm thresholds or build up of dirt on optical surfaces. By comparing the received
infrared signal against a standard every 15 minutes, the detec-
• 24 Vdc operating voltage tor automatically compensates for signal differences of less than
• Latching or non-latching operation 0.7dB/hour. When the detector is showing AGC fault, detector is
still capable of generating an alarm, and will display both Alarm
• Low current consumption
and Trouble indications.
• Optional Ground Level Test Station
(102 mm)
reflector placed at the opposite end of the detection zone. The
4”
reflector.
signal is reflected back to the receiver where it is analyzed for fire
and trouble. The EC-50R/-100R must be positioned correctly to
4"
Single
(102 mm)
minimize the detection time. The maximum lateral distance either reflector
side of the beam is found to be typically 30 feet (9.1 m) for satis-
factory detection under flat ceilings, providing a total area cover- 8" (204 mm) 0.34"
(10 mm)
0.34"
(10 mm)
age of 19,800 square feet (60 feet x 330 feet), or 1844 square EC-100R detectors should be
metres (18.3 x 100.6 m). mounted between 160 and 330 feet
(102 mm)
(102 mm)
4”
4”
Smoke stratification may be overcome by mounting multiple beam (48.8 and 100.6 m) from a group of
4" 4"
(102 mm) (102 mm)
beam below the heat layer and into the smoke layer. (102 mm)
(102 mm)
4”
4”
Detection time will be longer in a building with a peaked roof if a
fire occurs at the fringes of the protected area. If in doubt conduct 4"
(102 mm)
4"
(102 mm)
Detector Spacing
Single Detector Ceiling Multiple Detectors
19 to 24 inches L
C L
C
(483 to 610 mm)
(209.55 mm)
8.25"
Zone Wiring
POWER
SUPPLY
Zone Wiring
10.2 to 30 Volts DC (RED)
EC-50R/-100R 0V (BLACK)
Trouble Relay
COM (WHITE)
4.5"
End of Line Resistor (114.3 mm)
NC (GREEN)
Test Station
Ground Level Test Station 2.75" (69.85 mm) 1.5" (38.1 mm)
COMMON
CONN. 8-WAY CONNECTOR
8 CONNECTIONS
WHITE
7
BLUE TEST
B
YELLOW
A
YELLOW
RUN
BLACK
EC-50R / EC-100R
BLUE
CABLE ASSY.
RED
APPROX 3 FT.
GROUND LEVEL C B A
TEST STATION Ø 0.2
TO BE LOCATED D FIXING HOLES
0.5" (12.7 mm)
WITHIN 330 FT. OF GROUND LEVEL
THE JUNCTION BOX. TEST STATION (LLT)
0.34"
Reflector (10 mm)
Detector Installation
Install the detector to a secure surface not subject to movement or
vibration. Use the template provided to mark and install four fixing
points. Secure the rear mounting plate to the four fixing points
through the keyholes on the plate.
When installing the detector on a wall supported with wood studs,
(102 mm)
4"
(102 mm)
Intelligent Duct
Smoke Detector
SIGA-SD
MEA
has reached its limit, the duct smoke detector signals a trouble 3.08 in (7.82 cm)
1.60 in
(4.06 cm)
condition.
The SIGA-SD also uses differential sensing to prevent gradual
environmental changes from triggering unwanted alarms. A rapid
change in environmental conditions, such as smoke from a fire,
causes the detector to signal an alarm state, but dust and debris
accumulated over time does not change alarm sensitivity.
Each Signature Series SuperDuct detector contains a microproc-
essor that performs comprehensive self-diagnostics and stores
the results in nonvolatile memory. Stored results include details 2.28 in
(5.78 cm)
such as hours of operation, last maintenance date, and number
of alarms and troubles. This information can be retrieved and
reviewed when desired.
sensor, its wiring connections, sample and exhaust tubes, and the
smoke chamber itself.
Air enters the detector’s sensing chamber through a sampling
tube (ordered separately) that extends into the duct and is directed
back into the ventilation system through an exhaust tube (in- 1.90 in
(4.83 cm)
cluded). The difference in air pressure between the two tubes pulls
the sampled air through the sensing chamber. When a sufficient
amount of smoke is detected in the sensing chamber, the detector
initiates an alarm.
1.38 in 5.40 in
(3.51 cm) (13.72 cm)
Thin
gasket
Thick
gasket
Coupling
Duct Detector
SD-PH
Sampling tube Protective
(ordered separately) Housing
Plug
Mounting
Rear View
HVAC duct
Airflow
Hinged
Detector Cover
Housing
air tube
Housing Detector
air tube conduit holes
Sampling
tube
The SD-PH is easy to install and service. The hinged and transpar-
ent cover provides ready access to the detector, while keeping its
status indicators visible at all times.
#10 sheet metal screw (2X) Note: The SD-PH Protective Housing is weatherized against out-
door air, but it is not intended for direct outdoor exposure.
Wiring
Auxiliary
equipment
SIGA-LED [1]
Alarm
[1] No more than one remote test station
or LED indicator can be connected to or
the detector at the same time. Wiring 1
17 16 15 is unsupervised. Maximum wire Alarm
resistance is 10 ohms per wire. 2 SD-TRK
Test or
SD-TRM [1]
3
14 13 12 11 10 9 8 7
Power indicator
Alarm indicator
Ordering Information
Catalog Number Description Ship Wt., lb. (kg)
SIGA-SD Intelligent SuperDuct Detector 2.4 (1.1)
Accessories
SD-T8 8-inch sampling tube 0.5 (0.2)
SD-T18 18-inch sampling tube 1.5 (0.7)
SD-T24 24-inch sampling tube 2.7 (1.2)
SD-T36 36-inch sampling tube 3.0 (1.4)
SD-T42 42-inch sampling tube 3.5 (1.6)
SD-T60 60-inch sampling tube 5.8 (2.6)
SD-T78 78-inch sampling tube 7.5 (3.4)
SD-T120 120-inch sampling tube 11.5 (5.2)
SD-PH Protective housing for high humidity environments 5.5 (2.5)
SIGA-LED Remote alarm LED 1.0 (0.5)
SD-TRM Remote test station, magnetic 1.0 (0.5)
SD-TRK Remote test station, keyed 1.0 (0.5)
SD-VTK Air velocity test kit (stoppers only, etc) 1.0 (0.5)
SD-GSK Cover gasket kit 0.5 (0.2)
SD-MAG Test magnet kit 0.5 (0.2)
SIGA-SDPCB Replacement PCB/Signature sensor kit 1.0 (0.5)
05-18-11
Manual Pull
Stations
SIGA-270, SIGA-270P,
SIGA-278 MEA
Patented
SIGA-270 SERIES
SIGA-278
Compatibility
Signature Series manual stations are compatible only with EST’s
Signature Loop Controller.
Cover Release
Screw
Comp atible
Electrical Box
with ½-inch
raised covers
Back
Plate
Toggle
Switch
MAL
NOR
Latin America
Ordering Information
T 305 593 4301
F 305 593 4300 Ship
Catalog Wt. lbs
utcfireandsecurity.com Number Description (kg)
SIGA-270 One Stage Fire Alarm Station, English Markings - UL/ULC Listed
© 2010 UTC Fire & Security.
All rights reserved.
SIGC-270F One Stage Fire Alarm Station, French Markings - ULC Listed
SIGC-270B One Stage Fire Alarm Station, French/English Markings - ULC Listed
Two Stage (Presignal) Fire Alarm Station, English Markings - UL/ULC
SIGA-270P
Listed 1 (0.5)
SIGC- Two Stage (Presignal) Fire Alarm Station, French/English Markings
270PB - ULC Listed
Double Action (One Stage) Fire Alarm Station, English Markings
SIGA-278
- UL/ULC Listed
Accessories
32997 GA Key w/Tag - for pre-signal station (CANADA ONLY)
276-K2 GA Key - for pre-signal station (USA ONLY)
276-K1 Station Reset Key, Supplied with all Key Reset Stations
0.1 (.05)
27165 12 Glass Rods - for SIGA-270 series (CANADA ONLY)
270-GLR 20 Glass Rods - for SIGA-270 series (USA ONLY)
276-GLR 20 Glass Rods - for SIGA-278 series
276B-RSB Surface Mount Box, Red - for SIGA pull stations 1 (0.6)
05-18-11
Input Modules
SIGA-CT1, SIGA-CT1HT,
SIGA-CT2, SIGA-MCT2
SIGA-CT1/2
SIGA-MCT2
MEA
S
CHINA
Application Notes
Available
6-32
The Signature Series intelligent analog-addressable system from Self-tapping
Edwards Security is an entire family of multi-sensor detectors and screws
NOTES
UL/ULC Listed UL/ULC Listed
47KW EOL Input 2 Input 1
47KW EOL
4
3
2
1
Green LED (Normal)
This module will not operate without electrical power. As fires fre- Red LED (Active)
TB15
safeguards with your local fire protection specialist. No connections or jumper settings
required for MCT2.
SIGA-MCT2
Compatibility
The Signature Series modules are compatible only with EST’s
Signature Loop Controller.
Europe
T +32 2 725 11 20
F +32 2 721 86 13
Ordering Information
Catalog Ship Wt.
Latin America Description
Number lbs (kg)
T 305 593 4301
F 305 593 4300 SIGA-CT1 Single Input Module — UL/ULC Listed 0.4 (0.15)
SIGA-CT1HT Single Input Module High Temperature Operation UL/ULC Listed 0.4 (0.15)
utcfireandsecurity.com SIGA-CT2 Dual Input Module — UL/ULC Listed 0.4 (0.15)
© 2010 UTC Fire & Security.
SIGA-MCT2 Dual Input Plug-in (UIO) Module — UL, ULC Listed 0.1 (0.05)
All rights reserved.
Related Equipment
27193-11 Surface Mount Box - Red, 1-gang 1.0 (0.6)
27193-16 Surface Mount Box - White, 1-gang 1.0 (0.6)
Universal Input-Output Module Board w/Riser Inputs
SIGA-UIO2R 0.32 (0.15)
— Two Module Positions
Universal Input-Output Module Board w/Riser Inputs
SIGA-UIO6R 0.62 (0.28)
— Six Module Positions
SIGA-UIO6 Universal Input-Output Module Board — Six Module Positions 0.56 (0.25)
Multifunction Fire Cabinet — Red, supports Signature Module
MFC-A 7.0 (3.1)
Mounting Plates
Transponder Mounting Bracket (allows for mounting
SIGA-MB4 0.4 (0.15)
two 1-gang modules in a 2-gang box)
SIGA-MP1 Signature Module Mounting Plate, 1 footprint 1.5 (0.70)
SIGA-MP2 Signature Module Mounting Plate, 1/2 footprint 0.5 (0.23)
SIGA-MP2L Signature Module Mounting Plate, 1/2 extended footprint 1.02 (0.46)
05-18-11
Signal Modules
SIGA-CC1, SIGA-MCC1,
MEA
SIGA-CC2 & SIGA-MCC2 S
CHINA
Application Notes
Available
SIGA-CC
SIGA-MCC
1 2
Notes 4 8 UIO(R) series motherboard
8 9
MCC2
Data Out
5 All wiring power limited and supervised. If the input source 4
3 Riser 2 Out
is non-power limited, then maintain spacing of 1/4 inch or 2
1 Riser 2 In
use FPL, FPLP, FPLR or equivalent in accordance with NEC. Green LED (Normal) TB15
Red LED (Active)
6 The SIGA-UIO6 does not come with TB8 through TB13. UIOR series motherboard individual
Riser 1 connection. Install the
8
jumpers between adjacent modules
7 Supervised and power-limited. 1 23 4 that use the same riser.
Riser 1 In Riser 1 Out
8 Supervised and power-limited when connected to a power-
limited source. If the source is nonpower-limited, maintain
a space of 1/4 inch from power-limited wiring or use FPL,
SIGA-MCC2
FPLP, FPLR, or an equivalent in accordance with the Na-
tional Electrical Code. Maximum Output Load
9 The input for this riser is common to all modules. 24Vdc 25V 70V
Signals Audio Audio
2A 50W 35W
TB7
CAT NO.
MCC1
Data Out
6 The SIGA-UIO6 does not come with TB8 through TB13. 4 No connections required for
3
2 MCC1. Other modules may
7 Supervised and power-limited. 1 require connections.
Green LED (Normal) TB15
8 If the source is nonpower-limited, maintain a space of Red LED (Active)
UIOR series motherboard individual
1/4 inch from power-limited wiring or use FPL, FPLP, 1 23 4 Riser 1 connection. Install the
FPLR, or an equivalent in accordance with the National 6 8 jumpers between adjacent
modules that use the same riser.
Electrical Code. Riser 1 In Riser 1 Out
Related Equipment
27193-21 Surface Mount Box - Red, 2-gang 2 (1.2)
27193-26 Surface Mount Box - White, 2-gang 2 (1.2)
Universal Input-Output Module Board w/Riser Inputs - Two Module
SIGA-UIO2R 0.32 (0.15)
Positions
Universal Input-Output Module Board w/Riser Inputs - Six Module
SIGA-UIO6R 0.62 (0.28)
Positions
SIGA-UIO6 Universal Input-Output Module Board - Six Module Positions 0.56 (0.25)
235196P Bi-polar Transient Protector 0.01 (0.05)
Accessories
Multifunction Fire Cabinet - Red, supports Signature
MFC-A 7.0 (3.1)
Module Mounting Plates
SIGA-MP1 Signature Module Mounting Plate, 1 footprint 1.5 (0.70)
SIGA-MP2 Signature Module Mounting Plate, 1/2 footprint 0.5 (0.23)
SIGA-MP2L Signature Module Mounting Plate, 1/2 extended footprint 1.02 (0.46)
05-18-11
Control Relay
Modules
SIGA-CR, SIGA-MCR, SIGA-
CRR, SIGA-MCRR
MEA
SIGA-CR
SIGA-MCR
M
Compatibility
The Signature Series modules are compatible only with EST's
ALAR
FIRE DULE
MO
Status LEDs
Signature Loop Controller.
LED viewing ports
#6 Flat washers
Notes
1 Refer to Signature Loop Controller Installation Sheet
for wiring specifications.
2 NFPA 72 requires that the SIGA-CR/SIGA-MCR be
installed in the same room as the device it is control-
ling. This requirement may not apply in all markets.
Check with your local AHJ for details.
3 The SIGA-UIO6R and the SIGA-UIO2R do not come
SIGA-CR Control Relay with TB14.
4 The SIGA-UIO6 does not come with TB8 through
TB13.
4
3
2
Green LED (Normal) 1
Red LED (Active) TB15
1 23 4
4
No connections required for
MCR. Other modules may
require connections.
Listed 24 VDC + 1
Nominal Power 2
Supply
- 1
2 2 2
2
1 2
3 3
CT1
CR CRR 3
SIGA-CRR
Signature +
DATA
Controller
- 3
3 Optional CR
for disabling/disconnecting
sounder base
SIGA-MCRR
SIGA-CRR Schematic SIGA-MCRR Schematic
SIGA-CRR Schematic
11
1
DATA (-) IN
Audible required for
10
2
Bases supevision
SIG +
SIG -
9
4
8
7
6
5
7 8 7
Signature
Notes Data Data Out
Circuit
1 Refer to the Signature controller installation sheet for For normal operation CT1
wiring. 8
For General Fire
Alarm Operation
2 One Pair of Wires (24 Vdc power). UL/ULC Listed 4 3 2 1
24 Vdc power
or
3 One Pair of Wires (Signature Data). supply
473387359
CAT NO.
MCRR
MCRR
9 Maximum #12 AWG (2.5 mm² ) wire; Minimum #18 1 No connections required for
TB15
AWG (0.75 mm² ). Green LED (Normal) MCRR. Other modules may
Red LED (Active) 1 23 4 1 23 4 require connections.
10 End-of-Line Relay must monitor and report power
supply trouble to control panel. 6 6
Optional MCRR
11 Class B Data wiring may be “T-tapped.” or MCR for
No connections required for MCRR. Other
disabling/disconnecting
an audible base. modules may require connections.
Ordering Information
Ship Weight - lbs
Catalog Number Description
(kg)
SIGA-CR Control Relay Module (Standard Mount) 0.4 (0.15)
SIGA-MCR Control Relay Module (UIO Mount) 0.18 (0.08)
SIGA-CRR Polarity Reversal Relay Module (Standard Mount) 0.4 (0.15)
SIGA-MCRR Polarity Reversal Relay Module (UIO Mount) 0.18 (0.08)
Related Equipment
27193-11 Surface Mount Box - Red, 1-gang 1 (0.6)
27193-16 Surface Mount Box - White, 1-gang 1 (0.6)
SIGA-UIO2R Universal Input-Output Module Board w/Riser Inputs - Two Module Positions 0.32 (0.15)
SIGA-UIO6R Universal Input-Output Module Board w/Riser Inputs - Six Module Positions 0.62 (0.28)
SIGA-UIO6 Universal Input-Output Module Board - Six Module Positions 0.56 (0.25)
SIGA-AB4G Audible (Sounder) Detector Base 0.3 (0.15)
Accessories
MFC-A Multifunction Fire Cabinet - Red, supports Signature Module Mounting Plates 7.0 (3.1)
SIGA-MB4 Transponder Mounting Bracket (allows for mounting two 1-gang modules in a 2-gang box) 0.4 (0.15)
SIGA-MP1 Signature Module Mounting Plate, 1 footprint 1.5 (0.70)
SIGA-MP2 Signature Module Mounting Plate, 1/2 footprint 0.5 (0.23)
SIGA-MP2L Signature Module Mounting Plate, 1/2 extended footprint 1.02 (0.46)
Isolator Module
SIGA-IM
MEA
S
CHINA
Application Notes
Patented Available
SHORT
CIRCUIT
This part is removed
Typical Wiring and Installation from the circuit
The SIGA-IM module mounts to North American 2-1/2 inch (64 mm)
deep 2-gang boxes and 1-1/2 inch (38 mm) deep 4 inch square
boxes with 2 gang covers and SIGA-MP mounting plates. The
module will accept #18 AWG (0.75mm2), #16 (1.0mm2), #14 AWG
Typical Class A Configuration
(1.50mm2), and #12 AWG (2.50mm2) wire sizes. Note: Sizes #16 Data Out Data Return with Class B T-Taps
AWG (1.0mm2) and #18 AWG (0.75mm2) are preferred for ease Signature Loop Controller
of installation. See Signature Loop Controller catalog sheet for
detailed wiring requirement specifications.
Edwards recommends that this module be installed according to
latest recognized edition of national and local fire alarm codes.
Green LED
(normal - flashing)
TB1
4 3 5
1
For maximum wire resistance, refer to the appropriate
manufacturer’s documentation.
2 Max. #12 AWG (2.5mm²)wire.
3
Refer to Signature Loop Controller Installation Sheet for
wiring specifications.
4 This module should be used only with Class A wiring.
5 Maximum circuit resistance between isolators is 6 ohms.
6 All wiring is power-limited and supervised.
U.S.
T 888-378-2329
F 866-503-3996
Canada
Chubb Edwards
T 519 376 2430
F 519 376 7258
Southeast Asia
T : +65 6391 9300
F : +65 6391 9306
India
T : +91 80 4344 2000
F : +91 80 4344 2050
Australia
T +61 3 9239 1200
F +61 3 9239 1299
Europe
T +32 2 725 11 20
F +32 2 721 86 13
Latin America
T 305 593 4301
F 305 593 4300
utcfireandsecurity.com
05-18-11
‘SNAP
APART”
Multi-Voltage
SEAMS MR-101/C, MR-201/C
Control Relays
MR-100 & MR-200 Series MR-104/T
LED
VIEWING
HOLES
MR-101/T
MR-104/C, MR-204/C
These devices are ideal for applications where local contacts are • Available in dustproof metal enclosures with LED viewing port
required for system status, remote contacts for control of electri- • Track mounting hardware to facilitate installation in standard
cal loads and general purpose switching. They are suitable for cabinets
use with HVAC Temperature Control, Fire Alarm, Security, Energy
Management, and Lighting Control Systems. • UL recognized relays rated at 10 million mechanical operations
• ULI listed as control unit accessory
U.S.
T 888-378-2329
F 866-503-3996
Canada
Chubb Edwards
T 519 376 2430
F 519 376 7258
Southeast Asia
T : +65 6391 9300
F : +65 6391 9306
India
T : +91 80 4344 2000
F : +91 80 4344 2050
Australia
T +61 3 9239 1200
F +61 3 9239 1299
Europe
T +32 2 725 11 20 MR-101 (MR-104) MR-201 (MR-204)
F +32 2 721 86 13
Latin America
T 305 593 4301
Specifications
F 305 593 4300 Power Requirements
utcfireandsecurity.com MR-101 Position 15 mA @ 24 Vac, 24 Vdc, 115 Vac, 230 Vac
MR-201 Position 35 mA @ 24 Vac, 24 Vdc, 115 Vac, 230 Vac
© 2010 UTC Fire & Security. Relays
All rights reserved.
MR-101 UL Recognized SPDT
MR-201 UL Recognized SPDT
Enclosure 18 ga. CRS, plated with 1/2 in conduit knockouts (top and bottom)
Contact Rating 10 Amps @ 115 Vac
Ambient Temperature -58°F to 185°F (-50°C to 85°C)
Approvals UL Listed control unit accessory
Dimensions
MR-101/T and MR-201/T 3.0 H x 2.125 W x 1.5 D in (76 H x 54 W x 38 D mm)
MR-104/T and MR-204/T 3.0 H x 8.5 W x 1.5 D in (76 H x 216 W x 38 D mm)
MR-101/C and MR-
6.125 H x 3.25 W x 2.5 D in (156mm H x 83mm W x 64 D mm)
201/C
MR-104/C and MR-
6.125 H x 9.5 W x 2.5 D in (156 H x 241 W x 64 D mm)
204/C
Ordering Information
Model Description
MR-101/T Single SPDT relay with LED and track mounting hardware
MR-101/C Single SPDT relay with LED mounted in metal enclosure
MR-104/T Four-position SPDT relay with LEDs and track mounting hardware
MR-104/C Four-position SPDT relay with LEDs mounted in metal enclosure
MR-201/T Single DPDT relay with LED and track mounting hardware
MR-201/C Single DPDT relay with LED mounted in metal enclosure
MR-204/T Four-position DPDT realy with LEDs and track mounting hardware
MR-204/C Four-position DPDT relay with LEDs mounted in metal enclosure
05-18-11
Multi-Voltage
Control Relay
Model PAM-1
Canada
Chubb Edwards
T 519 376 2430 Ordering Information
F 519 376 7258
Model Description
Southeast Asia Single SPDT relay with LED double-sided adhesive tape, mounting screw and 6 in (150 mm)
T : +65 6391 9300 PAM-1
leads.
F : +65 6391 9306
India
T : +91 80 4344 2000
F : +91 80 4344 2050
Australia
T +61 3 9239 1200
F +61 3 9239 1299
Europe
T +32 2 725 11 20
F +32 2 721 86 13
Latin America
T 305 593 4301
F 305 593 4300
utcfireandsecurity.com
05-18-11
Control Relay
Modules
SIGA-CR, SIGA-MCR, SIGA-
CRR, SIGA-MCRR
MEA
SIGA-CR
SIGA-MCR
M
Compatibility
The Signature Series modules are compatible only with EST's
ALAR
FIRE DULE
MO
Status LEDs
Signature Loop Controller.
LED viewing ports
#6 Flat washers
Notes
1 Refer to Signature Loop Controller Installation Sheet
for wiring specifications.
2 NFPA 72 requires that the SIGA-CR/SIGA-MCR be
installed in the same room as the device it is control-
ling. This requirement may not apply in all markets.
Check with your local AHJ for details.
3 The SIGA-UIO6R and the SIGA-UIO2R do not come
SIGA-CR Control Relay with TB14.
4 The SIGA-UIO6 does not come with TB8 through
TB13.
4
3
2
Green LED (Normal) 1
Red LED (Active) TB15
1 23 4
4
No connections required for
MCR. Other modules may
require connections.
Listed 24 VDC + 1
Nominal Power 2
Supply
- 1
2 2 2
2
1 2
3 3
CT1
CR CRR 3
SIGA-CRR
Signature +
DATA
Controller
- 3
3 Optional CR
for disabling/disconnecting
sounder base
SIGA-MCRR
SIGA-CRR Schematic SIGA-MCRR Schematic
SIGA-CRR Schematic
11
1
DATA (-) IN
Audible required for
10
2
Bases supevision
SIG +
SIG -
9
4
8
7
6
5
7 8 7
Signature
Notes Data Data Out
Circuit
1 Refer to the Signature controller installation sheet for For normal operation CT1
wiring. 8
For General Fire
Alarm Operation
2 One Pair of Wires (24 Vdc power). UL/ULC Listed 4 3 2 1
24 Vdc power
or
3 One Pair of Wires (Signature Data). supply
473387359
CAT NO.
MCRR
MCRR
9 Maximum #12 AWG (2.5 mm² ) wire; Minimum #18 1 No connections required for
TB15
AWG (0.75 mm² ). Green LED (Normal) MCRR. Other modules may
Red LED (Active) 1 23 4 1 23 4 require connections.
10 End-of-Line Relay must monitor and report power
supply trouble to control panel. 6 6
Optional MCRR
11 Class B Data wiring may be “T-tapped.” or MCR for
No connections required for MCRR. Other
disabling/disconnecting
an audible base. modules may require connections.
Ordering Information
Ship Weight - lbs
Catalog Number Description
(kg)
SIGA-CR Control Relay Module (Standard Mount) 0.4 (0.15)
SIGA-MCR Control Relay Module (UIO Mount) 0.18 (0.08)
SIGA-CRR Polarity Reversal Relay Module (Standard Mount) 0.4 (0.15)
SIGA-MCRR Polarity Reversal Relay Module (UIO Mount) 0.18 (0.08)
Related Equipment
27193-11 Surface Mount Box - Red, 1-gang 1 (0.6)
27193-16 Surface Mount Box - White, 1-gang 1 (0.6)
SIGA-UIO2R Universal Input-Output Module Board w/Riser Inputs - Two Module Positions 0.32 (0.15)
SIGA-UIO6R Universal Input-Output Module Board w/Riser Inputs - Six Module Positions 0.62 (0.28)
SIGA-UIO6 Universal Input-Output Module Board - Six Module Positions 0.56 (0.25)
SIGA-AB4G Audible (Sounder) Detector Base 0.3 (0.15)
Accessories
MFC-A Multifunction Fire Cabinet - Red, supports Signature Module Mounting Plates 7.0 (3.1)
SIGA-MB4 Transponder Mounting Bracket (allows for mounting two 1-gang modules in a 2-gang box) 0.4 (0.15)
SIGA-MP1 Signature Module Mounting Plate, 1 footprint 1.5 (0.70)
SIGA-MP2 Signature Module Mounting Plate, 1/2 footprint 0.5 (0.23)
SIGA-MP2L Signature Module Mounting Plate, 1/2 extended footprint 1.02 (0.46)
Input Modules
SIGA-CT1, SIGA-CT1HT,
SIGA-CT2, SIGA-MCT2
SIGA-CT1/2
SIGA-MCT2
MEA
S
CHINA
Application Notes
Available
6-32
The Signature Series intelligent analog-addressable system from Self-tapping
Edwards Security is an entire family of multi-sensor detectors and screws
NOTES
UL/ULC Listed UL/ULC Listed
47KW EOL Input 2 Input 1
47KW EOL
4
3
2
1
Green LED (Normal)
This module will not operate without electrical power. As fires fre- Red LED (Active)
TB15
safeguards with your local fire protection specialist. No connections or jumper settings
required for MCT2.
SIGA-MCT2
Compatibility
The Signature Series modules are compatible only with EST’s
Signature Loop Controller.
Europe
T +32 2 725 11 20
F +32 2 721 86 13
Ordering Information
Catalog Ship Wt.
Latin America Description
Number lbs (kg)
T 305 593 4301
F 305 593 4300 SIGA-CT1 Single Input Module — UL/ULC Listed 0.4 (0.15)
SIGA-CT1HT Single Input Module High Temperature Operation UL/ULC Listed 0.4 (0.15)
utcfireandsecurity.com SIGA-CT2 Dual Input Module — UL/ULC Listed 0.4 (0.15)
© 2010 UTC Fire & Security.
SIGA-MCT2 Dual Input Plug-in (UIO) Module — UL, ULC Listed 0.1 (0.05)
All rights reserved.
Related Equipment
27193-11 Surface Mount Box - Red, 1-gang 1.0 (0.6)
27193-16 Surface Mount Box - White, 1-gang 1.0 (0.6)
Universal Input-Output Module Board w/Riser Inputs
SIGA-UIO2R 0.32 (0.15)
— Two Module Positions
Universal Input-Output Module Board w/Riser Inputs
SIGA-UIO6R 0.62 (0.28)
— Six Module Positions
SIGA-UIO6 Universal Input-Output Module Board — Six Module Positions 0.56 (0.25)
Multifunction Fire Cabinet — Red, supports Signature Module
MFC-A 7.0 (3.1)
Mounting Plates
Transponder Mounting Bracket (allows for mounting
SIGA-MB4 0.4 (0.15)
two 1-gang modules in a 2-gang box)
SIGA-MP1 Signature Module Mounting Plate, 1 footprint 1.5 (0.70)
SIGA-MP2 Signature Module Mounting Plate, 1/2 footprint 0.5 (0.23)
SIGA-MP2L Signature Module Mounting Plate, 1/2 extended footprint 1.02 (0.46)
05-18-11
Output Module
Motherboards
SIGA-UIO2R, SIGA-UIO6R,
SIGA-UIO2R
Compatibility
Signature Series Universal Input/Output Module Boards are com-
patible only with SIGA-“M” Series I/O Modules, which require a
Signature Data Controller.
SIGA-UIO2R SIGA-UIO6R
3 Module Input/Output Wiring
Refer to individual module installation sheet for wiring details.
Module Input/Output Wiring UIO2R
1 2 3 4 1 2 3 4
1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 UIO6R
TB1 TB2
TB1
TB2
TB3
TB6
TB4
TB5
Data In
TB7 Data In
Signature 4 TB15 TB7
3
Data 4 Signature
4
2 Common input/output 3
Circuit 1 3
Data TB15
2 bus for M series 2 Input/Output Bus 2
1 Circuit 4
Data Out modules 1 3 Common to all
5 2
1 M series
Data Out modules (maximum
TB8 TB9 current is 8 Amps)
1 2 3 4 1 2 3 4
Jumpers connect common
TB11
TB8
TB9
TB10
TB13
TB12
inputs/outputs between 1
Module Input/Output Wiring modules Jumpers connect 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4
common inputs
3 5 outputs between
Notes modules. Module Input/Output Wiring (maximum current is 8 Amps)
Refer to individual module installation sheet for wiring details.
2) Not all modules use the SIGA-UIO2R terminals for the same
SIGA-UIO6
functions. Module Input/Output Wiring
Refer to individual module installation sheet for wiring details.
3 Refer to individual SIGA-M series installation sheets for jumper
settings and wiring information. Installations with multiple 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4 UIO6
SIGA-UIO motherboards or enclosures (which include other
TB1
TB2
TB3
TB6
TB4
TB5
TB14 Input/Output Bus 1
wiring) require FPL, FPLR, FPLP, or equivalent NEC-approved Data In 4 Common to all
3
wire for all power limited wiring. Observe the details of supervi- 2
1
M series
modules (maximum
4
sion and power limited versus non-power limited circuits. Refer Signature
Data
3 current is 8 Amps)
2 TB15
to the SIGA-M series installation sheets. Circuit 1 4 Input/Output Bus 2
TB7 3 Common to all
2 M series
4) Do not mix incompatible signals. Data Out 1
modules (maximum
current is 8 Amps)
Europe
T +32 2 725 11 20 Ordering Information
F +32 2 721 86 13
Catalog Ship Wt. - lb
Description
Latin America Number (kg)
T 305 593 4301 Universal Input-Output Module Board w/Riser Inputs
F 305 593 4300 SIGA-UIO2R 0.32 (0.15)
- Two Module Positions
utcfireandsecurity.com Universal Input-Output Module Board w/Riser Inputs
SIGA-UIO6R 0.62 (0.28)
- Six Module Positions
© 2010 UTC Fire & Security. Universal Input-Output Module Board
All rights reserved. SIGA-UIO6 0.56 (0.25)
- Six Module Positions
UL listed cabinet for mounting UIO motherboards, red with
MFC-A white “FIRE” 8 inch H X 14 inch W X 3.5 inch D (203 mmH 7.0 (3.1)
X 356 mm W X 89 mm D)
05-18-11
Multi-Voltage
Control Relay
Model PAM-1
Canada
Chubb Edwards
T 519 376 2430 Ordering Information
F 519 376 7258
Model Description
Southeast Asia Single SPDT relay with LED double-sided adhesive tape, mounting screw and 6 in (150 mm)
T : +65 6391 9300 PAM-1
leads.
F : +65 6391 9306
India
T : +91 80 4344 2000
F : +91 80 4344 2050
Australia
T +61 3 9239 1200
F +61 3 9239 1299
Europe
T +32 2 725 11 20
F +32 2 721 86 13
Latin America
T 305 593 4301
F 305 593 4300
utcfireandsecurity.com
05-18-11
MEA
Field Configurable
pending
Ceiling Speaker
One or more patents pending.
Genesis Series
1 2
1/2
1/4
MNEC Applications
Genesis MNEC appliances bring the same high-performance life
safety features and unobtrusive design to mass notification ap-
plications. Available with optional ALERT housing labels, they are
ideal for applications that require differentiation between life safety
and mass notification alerts.
12 11 10 9 8 7 6 5 4 3 2 1 0 1 2 3 4 5 6 7 8 9 10 11 12
90°
82 88 88 82 Wattage switch Indicator
1/4
89 89
83 83
-75° 93 93 75°
84 96 84 Wiring
-60°
5ft (1.5m)
Radius 60° Field wiring terminals accommodate #18 to #12 AWG (0.75 mm²
to 2.5 mm²) wiring.
87 87
-45° 45°
90
10ft (3.05m)
-30° Radius 30°
-15° 15°
0°
Dimensions
6.8" dia.
(173 mm)
1.0"
(25 mm)
Specifications
Textured UV stabilized, color impregnated engineered plastic. Exceeds 94V-0 UL flammability rating. Red and white models
Housing
available.
Wire connections Screw terminals: polarized inputs for speaker, #18 to #12 AWG (0.75 mm² to 2.5 mm²) wire size
Flush mount to North American 4-inch square electrical box, 2-1/8 (54 mm) inches deep,
Mounting
or 960A-4RF round flush box. No extension ring required. Suitable for indoor wall or ceiling applications.
Operating environment Indoor: 32-120° F (0-49° C) ambient temperature; 0-93% relative humidity.
Agency listings/approvals Meets or exceeds UL1480 Fifth Edition, ULC-S541, and CSFM (FM and MEA pending).
Input/Operating Voltage 25 Vrms (Model S2) or 70 Vrms (Model S7).
Speaker frequency response: 250-13,000 Hz. Optimized for voice intelligibility. 4-inch (102mm) mylar cone, sealed back
Speaker Cone
construction, rated for 8 watts, 8 ohm voice coil.
Ordering Information
All speakers include field-selectable ¼, ½, 1, or 2 watt taps
Model Housing Marking Speaker Ship Wt. White Field Configurable
Ceiling Speakers may be
Life safety Appliances (c/w running man icon screen printed on housing) ordered with or without
GC-S2 White None optional FIRE marking.
GCF-S2 White FIRE 25 Volt Red speakers come with
GCFR-S2 Red FIRE 1.62 lb. FIRE marking. MNEC
GC-S7 White None (0.73 kg.) speakers are available with
GCF-S7 White FIRE 70 Volt white housing and optional
GCFR-S7 Red FIRE ALERT marking.
U.S.
T 888-378-2329
F 866-503-3996
Canada
Chubb Edwards
T 519 376 2430
F 519 376 7258
Southeast Asia
T : +65 6391 9300
F : +65 6391 9306
India
T : +91 80 4344 2000
F : +91 80 4344 2050
Australia
T +61 3 9239 1200
F +61 3 9239 1299
Europe
T +32 2 725 11 20
F +32 2 721 86 13
Latin America
T 305 593 4301
F 305 593 4300
utcfireandsecurity.com
05-18-11
Genesis Speakers
and Strobes
Genesis G4 Series MEA
PENDING
Patents pending
All models are intended for indoor wall mounted applications only.
Speakers and speaker-strobes are flush mounted to a North- JP1
15
1
Bottom View
pean 100 mm square box. Signals may be surface mounted to a Candela switch Wattage switch
2. ECS/MNS Applications
(54 125"
m)
mm
) Genesis ECS/MNS appliances bring the same high-performance life
7m
5"
(12 safety features and unobtrusive design to mass notification appli-
cations. Standard models are available with clear or amber lenses
and optional ALERT housing labels, they are ideal for applications
that require differentiation between life safety and mass notifica-
Grounding plate tion alerts. Appliances with red, green or blue lenses are available.
Contact Edwards Customer Service for details.
6.5" (165 mm)
Optional Color-matched
Surface mount box
-15 -10
-5
0
5 10 15
Amber UL 1971* 88 cd 60 cd 24 cd 12 cd
-20 20
-30
-25 25
30 Clear UL 1971 110 cd 75 cd 30 cd 15 cd
-35 35
-40 40
-45 45 * Equivalent Rating
-50 50
Wiring
-55 55
-60 60
-65 65
-70 70
Field wiring is connected to Genesis signals with terminals that ac-
commodate #18 to #12 AWG (0.75 mm² to 2.5 mm²) wiring.
-75 75
-80 80
-85 85
-90 90
0
0
90
90
80
50
50
80
70
40
30
20
10
10
20
30
40
70
100
100
60
60
95
85
75
65
55
45
35
25
15
15
25
35
45
55
65
75
85
95
Minium UL required candela light output
Specifications
Genesis Speakers and Speaker-Strobes
Housing Red or white textured UV stabilized, color impregnated engineered plastic.
Dimensions Height: 6.5” (165 mm). Width: 5” (127 mm). Depth to wall: 1” (25 mm).
Mounting Flush: North-American 4” square box, 2 1/8” (54 mm) deep.
(indoor wall mount only) Surface: model G4B (white) or G4RB (red) surface mount box.
Screw terminals: separate polarized inputs for speaker and strobe, #18 to #12 AWG (0.75 mm² to 2.5 mm²) wire
Wire Connections
size
Operating environment 32-120° F (0-49° C) ambient temperature; 0-93% relative humidity.
UL 1971, UL 1638, UL 1480, ULC S526, ULC S541, CSFM, MEA (FM pending)
Agency Listings
(All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule.)
Speakers
Input/Operating Volts 25 VRMS or 70 VRMS. See ordering information.
Speaker Taps/Output* 2 W = 89 dBA; 1 W = 86 dBA; ½ W = 83 dBA; ¼ W = 80 dBA
Speaker frequency response: 250 to 5,000 Hz.
Speaker Cone
Optimized for voice intelligibility. 4-inch (102mm) mylar cone, sealed back construction.
Strobes
UL 1971, ULC S526: selectable 15 cd, 30 cd, 75 cd, or 110 cd output
Clear Strobe Output Rating UL 1971: 15 cd (fixed 15/75 cd models)
UL 1638, ULCS526: 75 cd (fixed 15/75 cd models)
Amber Strobe Output Rating UL 1638: 13 (D), 26 (C), 65 (B), 95 (A)
Strobe Operating Voltage 16 - 33 Vdc Regulated, 16-33 V Full wave rectified (UL Voltage Designations “Regulated 24” and “24 fwr”)
Strobe Flash Rate One flash per second.
All strobes: one flash per second (fps) within 200 milliseconds over 30 minutes on common circuit.
Strobe Flash Synchronization All strobes: Synchronization source required to comply with UL 1971 synchronization standard.
Temporal setting (private mode only): synchronized to temporal output on the same circuit.
SIGA-CC1S, SIGA-MCC1S, SIGA-CC2A, SIGA-MCC2A, G1M-RM
Synchronization Sources
BPS6A, BPS10A, APS6A, APS10A, iO64, iO500, Fireshield Plus 3, 5 and 10 zone.
Strobe Lens Material Polycarbonate
* Measured in reverberant room using 400-4,000 Hz band limited pink noise per UL 1480.
Detection & alarm since 1872 Model Housing Marking Lens Strobe Speaker Ship Wt.
U.S. Life safety Appliances (c/w running man icon screen printed on housing)
T 888 378 2329 G4-S2 White None
F 866 503 3996
G4R-S2 Red None
Canada G4F-S2 White FIRE
Selectable
Chubb Edwards G4RF-S2 Red FIRE
T 519 376 2430 15, 30, 75, or 25 Volt
G4-S2VM White None
F 519 376 7258 110 cd
G4R-S2VM Red None
Southeast Asia G4F-S2VM White FIRE
T : +65 6391 9300 G4RF-S2VM Red FIRE
F : +65 6391 9306
G4-S7 White None 1.5 lbs.
Clear
India G4R-S7 Red None (0.68 kg)
T : +91 80 4344 2000 G4F-S7 White FIRE
F : +91 80 4344 2050 Selectable
G4RF-S7 Red FIRE
15, 30, 75, or
G4-S7VM White None
Australia 110 cd 70 Volt
T +61 3 9239 1200 G4R-S7VM Red None
F +61 3 9239 1299 G4F-S7VM White FIRE
G4RF-S7VM Red FIRE
Europe
T +32 2 725 11 20 G4F-S7V1575 White FIRE
15/75 cd¹
F +32 2 721 86 13 G4RF-S7V1575 Red FIRE
Accessories
G1M-RM Synchronization Output Module (1-gang) 0.2 (0.1)
SIGA-CC1S Intelligent Synchronization Output Module (2-gang) 0.5 (0.23)
SIGA-MCC1S Synchronization Output Module (Plug-in UIO) 0.18 (0.08)
G4B Surface mount box, white 0.7 (0.32)
G4RB Surface mount box, red 0.7 (0.32) 05-18-11
Field Configurable
Ceiling Speaker
-strobes
Genesis Series
MEA
Speaker Application
The suggested sound pressure level for each signaling zone used
with alert or alarm signals is a minimum of 15 dB above the aver-
age ambient sound level or 5 dB above the maximum sound level
having a duration of at least 60 seconds, whichever is greater. This
is measured 5 feet (1.5 m) above the floor.
Doubling the distance from the signal to the ear will theoretically
cause a 6 dB reduction in the received sound pressure level. The
Installation and Mounting
actual effect depends on the acoustic properties of materials in All models are intended for
the space. Doubling the power output of a device (e.g.: a speaker indoor ceiling or wall applica-
from 1 W to 2 W) will increase the sound pressure level by 3 tions only. Speaker-strobes
dBA. A 3 dBA difference represents a barely noticeable change in are mounted to a flush
volume. North-American 4" square
electrical box, 21/8" (54 mm)
Combination audible/visual signals must be installed in accor- deep.
dance with guidelines established for strobes.
Genesis ceiling speaker-
strobes simply unlatch and
ECS/MNS Applications hinge down to open. This
Genesis ECS/MNS appliances bring the same high-performance life gains access to mounting screws
safety features and unobtrusive design to mass notification applica- and the selectable candela wattage BOX
tions. Available as standard units with clear or amber lenses with tap switches. The shallow depth of
optional ALERT markings, thy are ideal for applications that require Genesis devices leaves ample room 11/16" STROBE
differentiation between life safety and ECS/MNS signals. Units are
Center of Box
0.60"(15 mm)
Field Configuration Candela switch Wattage switch
Genesis ceiling speaker-
strobes may be set for ¼, ½,
1/4
95
2
15
89 89
83 83
-75° 93 93 75°
-75° 75°
84 96 84
5ft (1.5m)
-60° Radius 60°
87 87 -60° 60°
-45° 45°
-45° 45°
Percent of UL
90
rating versus
10ft (3.05m)
-30° Radius 30°
-30° 30°
angle
-15° 15°
0° -15° 15°
0°
Measured at 2 watts setting in anechoic chamber
Angle
Horizontal and vertical outputs reflect the same pattern.
Current Draw
Notes
UL Nameplate Rating UL Nameplate Rating (high cd output mod-
1. Light output switch settings for UL 1971 listed
els)
models are selectable by numeric candela
See "15" or "30" or "75" or "B" "95" or "A" "95" or "115" or "150" or "177" or value. ECS/MNS appliances are selectable by
note 1 "D" "C" "D" "C" "B" "A" A, B, C, or D designations.
RMS RMS RMS RMS RMS RMS RMS RMS 2. Current values are shown in mA.
Specifications
Housing Textured UV stabilized, color impregnated engineered Strobe
plastic. Exceeds 94V-0 UL flammability rating. Red and
Strobe out- UL 1971, UL 1638, ULC S526: selectable 15/30/75/95
white models available.
put rating cd (VM models) and 95/115/150/177 cd (VMH models)
Mounting Flush mount to North American 4-inch square electrical
Strobe GC-S2VM/-S7VM series speaker-strobes: non-coded,
box, 2-1/8 (54 mm) inches deep, or 960A-4RF round
operating filtered 16-33 Vdc or unfiltered 16-33 Vdc FWR
flush box. No extension ring required. Suitable for indoor
voltage
wall or ceiling applications.
Strobe flash GC-S2VM/-S7VM series speaker-strobes: one flash per
Wire con- Screw terminals: polarized inputs for speaker, #18 to #12
rate second synchronized with optional G1M Genesis Signal
nections AWG (0.75 mm² to 2.5 mm²) wire size
Master indefinitely within 10 milliseconds. Temporal set-
Operating Indoor: 32-120° F (0-49° C) ambient temperature; 0-93% ting (private mode only): synchronized to temporal output
environment relative humidity. of Genesis audible signals on same circuit
Agency Meets ULC-S541, year 2004 UL requirements for Synchroni- Meets or exceeds UL 1971 requirements. Maximum
listings/ standards UL1638 and UL1971, FM, MEA, CSFM, and zation allowed resistance between any two devices is 20 Ohms.
approvals complies with UL1480 Fifth Edition. All speaker-strobes Refer to specifications for the synchronization control
comply with ADA Code of Federal Regulation Chapter module, this strobe, and the control panel to determine
28 Part 36 Final Rule. allowed wire resistance.
Speaker SIGA-CC1S, SIGA-MCC1S, SIGA-CC2A, SIGA-MCC2A,
Synchro-
G1M-RM
Input/Oper- 25 Vrms (Model GC-S2VM) or 70 Vrms (Model GC- nization
BPS6A, BPS10A, APS6A, APS10A, iO64, iO500,
ating Volts S7VM). Sources
Fireshield Plus 3, 5 and 10 zone.
Lens Optical grade polycarbonate
Hous- Mark-
Model Lens Strobe Speaker Ship Wt.
Detection & alarm since 1872 ing ing
U.S. Life safety Appliances (c/w running man icon screen printed on housing)
T 888 378 2329 GC-S2VM White None Selectable
F 866 503 3996
GCF-S2VM White FIRE 15, 30, 75, or 95 cd
Canada GC-S2VMH White None Selectable High Output 25 Volt
Chubb Edwards 95, 115, 150,
GCF-S2VMH White FIRE
T 519 376 2430 or 177 cd
F 519 376 7258 2.25 lb.
GC-S7VM White None Clear
Selectable (1.0 kg.)
Southeast Asia GCF-S7VM White FIRE
15, 30, 75, or 95 cd
T : +65 6391 9300 GCFR-S7VM Red FIRE
70 Volt
F : +65 6391 9306 GC-S7VMH White None Selectable High Output
95, 115, 150,
India GCF-S7VMH White FIRE
or 177 cd
T : +91 80 4344 2000
F : +91 80 4344 2050
ECS/MNS Appliances (no running man icon on housing)
Australia GCWA-S2VMA ALERT Amber
T +61 3 9239 1200 GCWA-S2VMC ALERT Clear Selectable
F +61 3 9239 1299 A, B, C or D
GCWN-S2VMA NONE Amber
Europe GCWN-S2VMC None Clear
25 Volt
T +32 2 725 11 20 GCWA-S2VMHA ALERT Amber
F +32 2 721 86 13 GCWA-S2VMHC ALERT Clear Selectable High Output
GCWN-S2VMHA None Amber A, B, C or D
Latin America
T 305 593 4301 GCWN-S2VMHC None Clear 2.25 lb.
White
F 305 593 4300 GCWA-S7VMA ALERT Amber (1.0 kg.)
GCWA-S7VMC ALERT Clear Selectable
utcfireandsecurity.com
GCWN-S7VMA None Amber A, B, C or D
© 2010 UTC Fire & Security. GCWN-S7VMC None Clear
All rights reserved.
70 Volt
GCWA-S7VMHA ALERT Amber
GCWA-S7VMHC ALERT Clear Selectable High Output
GCWN-S7VMHA None Amber A, B, C or D
GCWN-S7VMHC None Clear
05-18-11
Genesis Speakers
and Strobes
Genesis G4 Series MEA
PENDING
Patents pending
All models are intended for indoor wall mounted applications only.
Speakers and speaker-strobes are flush mounted to a North- JP1
15
1
Bottom View
pean 100 mm square box. Signals may be surface mounted to a Candela switch Wattage switch
2. ECS/MNS Applications
(54 125"
m)
mm
) Genesis ECS/MNS appliances bring the same high-performance life
7m
5"
(12 safety features and unobtrusive design to mass notification appli-
cations. Standard models are available with clear or amber lenses
and optional ALERT housing labels, they are ideal for applications
that require differentiation between life safety and mass notifica-
Grounding plate tion alerts. Appliances with red, green or blue lenses are available.
Contact Edwards Customer Service for details.
6.5" (165 mm)
Optional Color-matched
Surface mount box
-15 -10
-5
0
5 10 15
Amber UL 1971* 88 cd 60 cd 24 cd 12 cd
-20 20
-30
-25 25
30 Clear UL 1971 110 cd 75 cd 30 cd 15 cd
-35 35
-40 40
-45 45 * Equivalent Rating
-50 50
Wiring
-55 55
-60 60
-65 65
-70 70
Field wiring is connected to Genesis signals with terminals that ac-
commodate #18 to #12 AWG (0.75 mm² to 2.5 mm²) wiring.
-75 75
-80 80
-85 85
-90 90
0
0
90
90
80
50
50
80
70
40
30
20
10
10
20
30
40
70
100
100
60
60
95
85
75
65
55
45
35
25
15
15
25
35
45
55
65
75
85
95
Minium UL required candela light output
Specifications
Genesis Speakers and Speaker-Strobes
Housing Red or white textured UV stabilized, color impregnated engineered plastic.
Dimensions Height: 6.5” (165 mm). Width: 5” (127 mm). Depth to wall: 1” (25 mm).
Mounting Flush: North-American 4” square box, 2 1/8” (54 mm) deep.
(indoor wall mount only) Surface: model G4B (white) or G4RB (red) surface mount box.
Screw terminals: separate polarized inputs for speaker and strobe, #18 to #12 AWG (0.75 mm² to 2.5 mm²) wire
Wire Connections
size
Operating environment 32-120° F (0-49° C) ambient temperature; 0-93% relative humidity.
UL 1971, UL 1638, UL 1480, ULC S526, ULC S541, CSFM, MEA (FM pending)
Agency Listings
(All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule.)
Speakers
Input/Operating Volts 25 VRMS or 70 VRMS. See ordering information.
Speaker Taps/Output* 2 W = 89 dBA; 1 W = 86 dBA; ½ W = 83 dBA; ¼ W = 80 dBA
Speaker frequency response: 250 to 5,000 Hz.
Speaker Cone
Optimized for voice intelligibility. 4-inch (102mm) mylar cone, sealed back construction.
Strobes
UL 1971, ULC S526: selectable 15 cd, 30 cd, 75 cd, or 110 cd output
Clear Strobe Output Rating UL 1971: 15 cd (fixed 15/75 cd models)
UL 1638, ULCS526: 75 cd (fixed 15/75 cd models)
Amber Strobe Output Rating UL 1638: 13 (D), 26 (C), 65 (B), 95 (A)
Strobe Operating Voltage 16 - 33 Vdc Regulated, 16-33 V Full wave rectified (UL Voltage Designations “Regulated 24” and “24 fwr”)
Strobe Flash Rate One flash per second.
All strobes: one flash per second (fps) within 200 milliseconds over 30 minutes on common circuit.
Strobe Flash Synchronization All strobes: Synchronization source required to comply with UL 1971 synchronization standard.
Temporal setting (private mode only): synchronized to temporal output on the same circuit.
SIGA-CC1S, SIGA-MCC1S, SIGA-CC2A, SIGA-MCC2A, G1M-RM
Synchronization Sources
BPS6A, BPS10A, APS6A, APS10A, iO64, iO500, Fireshield Plus 3, 5 and 10 zone.
Strobe Lens Material Polycarbonate
* Measured in reverberant room using 400-4,000 Hz band limited pink noise per UL 1480.
Detection & alarm since 1872 Model Housing Marking Lens Strobe Speaker Ship Wt.
U.S. Life safety Appliances (c/w running man icon screen printed on housing)
T 888 378 2329 G4-S2 White None
F 866 503 3996
G4R-S2 Red None
Canada G4F-S2 White FIRE
Selectable
Chubb Edwards G4RF-S2 Red FIRE
T 519 376 2430 15, 30, 75, or 25 Volt
G4-S2VM White None
F 519 376 7258 110 cd
G4R-S2VM Red None
Southeast Asia G4F-S2VM White FIRE
T : +65 6391 9300 G4RF-S2VM Red FIRE
F : +65 6391 9306
G4-S7 White None 1.5 lbs.
Clear
India G4R-S7 Red None (0.68 kg)
T : +91 80 4344 2000 G4F-S7 White FIRE
F : +91 80 4344 2050 Selectable
G4RF-S7 Red FIRE
15, 30, 75, or
G4-S7VM White None
Australia 110 cd 70 Volt
T +61 3 9239 1200 G4R-S7VM Red None
F +61 3 9239 1299 G4F-S7VM White FIRE
G4RF-S7VM Red FIRE
Europe
T +32 2 725 11 20 G4F-S7V1575 White FIRE
15/75 cd¹
F +32 2 721 86 13 G4RF-S7V1575 Red FIRE
Accessories
G1M-RM Synchronization Output Module (1-gang) 0.2 (0.1)
SIGA-CC1S Intelligent Synchronization Output Module (2-gang) 0.5 (0.23)
SIGA-MCC1S Synchronization Output Module (Plug-in UIO) 0.18 (0.08)
G4B Surface mount box, white 0.7 (0.32)
G4RB Surface mount box, red 0.7 (0.32) 05-18-11
Outdoor Rated
Speakers and
Strobes
Genesis WG4 Series
Patents pending
These appliances are suitable for indoor and outdoor applications, • Field-configurable temporal strobe output option
and are ideal for challenging conditions such as parking garages • Clear and amber lenses available
and process areas. They are listed for mounting on the ceiling or
the wall, and thanks to an ingenious full backplane sealing gasket, • Fully-compatible with Genesis synchronization protocols
can be installed to recessed (in-the-pour/block) electrical boxes. • Standard and high-output strobe intensities
WG4 signals also mount to suitable surface boxes served by race-
• Speaker only and Speaker/Strobe appliance options
ways. Optional color-matched trim skirts provide a clean, finished
appearance. All appliance wiring is accomplished room-side for
easy installation.
WG4 Series appliances feature highly intelligible and efficient
mylar-cone loudspeakers. These are dual-voltage (25.2V or
70.7V), and have field-selectable output taps ranging from 80.8
dBA to 90.0 dBA. The multi-candela strobes are available with
clear or amber lenses and in two output categories – standard and
high-output. They are precision-timed to meet UL 1971 synchro-
nization standards, and field-configurable for one of four candela
intensities. Wattage and candela settings are viewable even after
installation through an innovative sealed viewport display.
-65 65
SIGA-CC1S, SIGA-MCC1S, SIGA-CC2A,
Compatible strobe -70 70
SIGA-MCC2A, G1M-RM, BPS6A, BPS10A,
synchronization -75 75
APS6A, APS10A, 3X-SFS1, iO64, iO500, -80 80
sources
Fireshield Plus 3, 5 and 10 zone. -85 85
-90 90
0
0
90
90
80
50
50
80
100
70
40
30
20
10
10
20
30
40
70
60
60
100
95
85
75
65
55
45
35
25
15
15
25
35
45
55
65
75
85
95
Compatible Wet: Model 449 (WG4 trim skirt recommended)
electrical boxes Dry: 4" square by 1-1/2" deep box when used UL off-axis candela requirements as a percent of the UL rated output
without a trim skirt. When trim skirt is used,
box must be 4" square by 2-1/8" deep.
Operating environment Wet Strobe Switch Position
Temperature -31 to 151 °F (-35 to 66 °C) Indoor rating
Relative humidity 0 to 95% noncondensing per UL 1971 (candela) A B C D
Lens Clear 87 70 29 15
Sound level output (dBA) Standard Color
Output Amber* 62 59 25 13
Wattage Switch Position 25 V 70 V
Models VDC 319 167 144 106
2W T 90.0 89.7
(-SVMx) Current
1W X 87.1 86.9
FWR 386 347 178 120
½W Y 84.0 83.9
¼W Z 80.8 80.8 Lens Clear 161 147 123 102
dBA = Decibels, A-weighted. High Color
Output Amber* 130 125 101 84
UL 1480: Sound level output at 10 ft. (3.05 m) measured in a reverberant
room using 400 to 4,000 Hz band-limited pink noise. Models VDC 495 494 390 324
(-SVMHx) Current
FWR 646 607 487 412
Field wiring is connected to Genesis signals with terminals that ac- Strobe Switch Position
commodate #18 to #12 AWG (0.75 mm² to 2.5 mm²) wiring. Outdoor rating
per UL 1638 (candela) A B C D
Lens Clear 35 28 12 6
Standard Color
Output Amber* 25 24 10 5
Models VDC 319 167 144 106
(-SVMx) Current
FWR 386 347 178 120
Lens Clear 65 60 50 41
High Color
Output Amber* 52 51 41 34
Models VDC 495 494 390 324
(-SVMHx) Current
FWR 646 607 487 412
* UL 1971 Equivalent candela value
Accessories
WG4WTS Surface Skirt for Genesis WG4 appliance family, white.
WG4RTS Surface Skirt for Genesis WG4 appliance family, red.
WG4GSKT Replacement Mounting Gasket
449 Surface mount box, outdoor rated
08-08-11
Field Configurable
Ceiling Strobes
Genesis Series
MEA
Pending
One or more patents pending.
-75° 75°
Genesis ceiling strobes simply unlatch and twist to open. This -30° 30°
gains access to mounting screws and the selectable candela -15° 15°
switch. The shallow depth of Genesis devices leaves ample room
0°
Angle
behind the signal for extra wiring. Once installed with the cover in Horizontal and vertical outputs reflect the same pattern.
place, no mounting screws are visible.
Field Configuration
Depending on the model, Genesis ceiling
speaker-strobes have multi-candela output Candela switch
(see ordering information). The output
setting is changed by simply opening the
95
device and sliding the switch to the desired
75
30
setting. The strobe does not have to be 15
Wiring
Field wiring terminals accommodate #18 to #12 AWG (0.75 mm² WARNING: These devices will not operate without electrical power. As fires frequently
cause power interruptions, we suggest you discuss further safeguards with your
to 2.5 mm²) wiring. Strobes are interconnected with a single pair of local fire protection specialist.
wires as shown below.
Light output setting, standard models Light output setting, high output models
Typical “15” or ”D” “30” or ”C” “75” or ”B” “95” or ”A” “95” or ”D” “115” or ”C” “150” or ”B” “177” or ”A”
Current RMS RMS RMS RMS RMS RMS RMS RMS
16 Vdc 94 140 273 325 333 392 499 551
20 Vdc 74 108 205 244 259 303 378 429
24 Vdc 63 90 168 194 212 245 306 342
33 Vdc 48 70 124 139 155 180 211 236
16 Vfwr 126 187 368 403 484 570 673 724
20 Vfwr 108 156 281 333 380 438 537 604
24 Vfwr 97 139 240 270 318 361 434 484
33 Vfwr 89 119 197 214 245 269 308 338
Specifications
Textured UV stabilized, color impregnated engineered plastic. Exceeds 94V-0 UL flammability rating. Red and white models
Housing
available.
Lens Optical grade polycarbonate (clear).
Flush mount to North American 4-inch square electrical box, 2-1/8 (54 mm) inches deep. No extension ring required.
Mounting
Suitable for indoor wall or ceiling applications.
Wire Connections Screw terminals: #18 to #12 AWG (0.75 mm² to 2.5 mm²) wire size.
Operating Voltage Regulated 16 to 33 Vdc, 16 to 33 Vfwr.
Operating environment Indoor: 32-120° F (0-49° C) ambient temperature; 0-93% relative humidity.
Meets or exceeds year 2004 UL requirements for standards UL1638 and UL1971 and Canadian requirements for
Agency listings/approvals standards CAN/ULC S526-02 and CAN/ULC S524-01. All models comply with ADA Code of Federal Regulation Chapter
28 Part 36 Final Rule. CSFM, MEA. FM pending.
Strobe output rating UL 1971, UL 1638, ULC S526: selectable 15/30/75/95 cd (GC-VM) and 95/115/150/177 cd (GC-VMH)
GC-VM series strobes: non-coded, filtered 16-33 Vdc
Strobe operating voltage
or unfiltered 16-33 Vdc FWR.
GC-VM series strobes: one flash per second synchronized with optional G1M Genesis Signal Master indefinitely within 10
Strobe flash rate milliseconds. Temporal setting (private mode only): synchronized to temporal output of Genesis audible signals on same
circuit.
Meets or exceeds UL 1971 requirements. Maximum allowed resistance between any two devices is 20 Ohms. Refer
Synchronization to specifications for the synchronization control module, this strobe, and the control panel to determine allowed wire
resistance.
SIGA-CC1S, SIGA-MCC1S, SIGA-CC2A, SIGA-MCC2A, G1M-RM
Synchronization Sources BPS6A, BPS10A, APS6A, APS10A, iO64, iO500, Fireshield Plus 3, 5 and 10 zone.
Add G1M for G1-CVM &G1-HDVM devices only.
utcfireandsecurity.com
05-18-11
Field Configurable
Horns and
Strobes Pending
Temporal Steady
Setting Steady Steady
16 Vdc 81.4 85.5 91.4 94.2 -75° 75°
Temporal/ Temporal/
Setting Temporal Steady
Steady Steady -30° 30°
-30° 30°
-15° 15°
0°
Specifications
Housing Red or white textured UV stabilized, color impregnated engineered plastic. Exceeds 94V-0 UL flammability rating.
Lens Optical grade polycarbonate (clear)
Strobes and horn-strobes are for wall-mount installation only. Horn-only models may be ceiling- or wall-mounted.
Mounting Flush mount: 2½ inch (64 mm) deep one-gang box
(indoor only) Surface mount: Model 27193 surface mount box, wiremold box, or equivalent surface-mount box
With optional trim plate: One-gang, two-gang, four-inch square, octagonal, or European single-gang box
Wire connections Screw terminals: single input for both horn and strobe. #18 to #12 AWG (0.75 mm² to 2.5 mm²) wire size
Operating environment Indoor only: 32-120°F (0-49°C) ambient temperature. 93% relative humidity
UL 1971, UL 1638, UL 464, ULC S525, ULC S526, CSFM, CE, FCC, MEA.
Agency listings/approvals
(All models comply with ADA Code of Federal Regulation Chapter 28 Part 36 Final Rule.)
Signal: 4-1/2” x 2-3/4” x 13/16” (113 mm x 68 mm x 21 mm)
Dimensions (HxWxD)
Trimplate: 5” (127 mm); Height – 5-7/8” (149 mm); Depth – ½” (13 mm)
G1-HD series temporal-tone horns: non-coded, filtered 16-33 Vdc or unfiltered 16-33 Vdc FWR (or coded when horn
set to steady tone)
G1-HDVM series temporal-tone horn-strobes: non-coded, filtered 16-33 Vdc or unfiltered 16-33 Vdc FWR (or coded
Operating voltage
(audible NAC only) when used with optional G1M Genesis Signal Master)
G1-VM series strobes: non-coded, filtered 16 - 33 Vdc or unfiltered 16-33 Vdc FWR
G1-P series steady-tone horns: coded or non-coded, filtered 20-31 Vdc or unfiltered 20-27 Vfwr
UL 1971, UL 1638, ULC S526: selectable 15 cd, 30 cd, 75 cd, or 110 cd output
Strobe output rating UL 1971: 15 cd (fixed 15/75 cd models)
UL 1638, ULCS526: 75 cd (fixed 15/75 cd models)
G1-VM strobes and G1-HDVM series temporal-tone horn-strobes: one flash per second synchronized with optional
Strobe flash rate G1M Genesis Signal Master indefinitely within 10 milliseconds. Temporal setting (private mode only): synchronized to
temporal output of horns on same circuit
SIGA-CC1S, SIGA-MCC1S, SIGA-CC2A, SIGA-MCC2A, G1M-RM
Synchronization Sources BPS6A, BPS10A, APS6A, APS10A, iO64, iO500, Fireshield Plus 3, 5 and 10 zone.
Add G1M for G1-CVM &G1-HDVM devices only.
G1-HD temporal-tone horns and G1-HDVM series temporal-tone horn-strobes: temporal rate synchronized with optional
Horn pulse rate
G1M Genesis Signal Master indefinitely within 10 milliseconds. G1-P steady-tone horns: continuous, steady tone only
Temporal audible pattern ½ sec ON, ½ sec OFF, ½ sec ON, ½ sec OFF, ½ sec ON, 1½ sec OFF, then repeat cycle
Ordering Information
Model Housing Marking Lens Strobe Horn Ship Wt. lbs (kg)
Fire Alarm Appliances (c/w running man icon screen printed on housing)
G1-VM White None Clear Selectable 15, 30, 75, or 110 cd Strobe only 0.25 (0.11)
G1F-HD White FIRE Clear Horn only Selectable high/low dB 0.25 (0.11)
G1F-HDV1575 White FIRE Clear 15/75 cd¹ Temporal hi/lo dB-24V 0.25 (0.11)
G1F-HDVM White FIRE Clear Selectable 15, 30, 75, or 110 cd Selectable high/low dB 0.25 (0.11)
G1F-P White FIRE Clear Steady Horn (not compatible with Genesis Signal Master) 0.25 (0.11)
G1F-V1575 White FIRE Clear 15/75 cd¹ Strobe only 0.25 (0.11)
G1F-VM White FIRE Clear Selectable 15, 30, 75, or 110 cd Strobe only 0.25 (0.11)
G1-HD White None Clear Horn only Selectable high/low dB 0.25 (0.11)
G1-HDVM White None Clear Selectable 15, 30, 75, or 110 cd Selectable high/low dB 0.25 (0.11)
G1-P White None Clear Steady Horn (not compatible with Genesis Signal Master) 0.25 (0.11)
G1RF-HD Red FIRE Clear Horn only Selectable high/low dB 0.25 (0.11)
G1RF-HDV1575 Red FIRE Clear 15/75 cd¹ Temporal hi/lo dB-24V 0.25 (0.11)
G1RF-HDVM Red FIRE Clear Selectable 15, 30, 75, or 110 cd Selectable high/low dB 0.25 (0.11)
G1RF-P Red FIRE Clear Steady Horn (not compatible with Genesis Signal Master) 0.25 (0.11)
G1RF-V1575 Red FIRE Clear 15/75 cd¹ Strobe only 0.25 (0.11)
G1RF-VM Red FIRE Clear Selectable 15, 30, 75, or 110 cd Strobe only 0.25 (0.11)
G1R-HD Red None Clear Horn only Selectable high/low dB 0.25 (0.11)
G1R-HDVM Red None Clear Selectable 15, 30, 75, or 110 cd Selectable high/low dB 0.25 (0.11)
G1R-P Red None Clear Steady Horn (not compatible with Genesis Signal Master) 0.25 (0.11)
G1R-VM Red None Clear Selectable 15, 30, 75, or 110 cd Strobe only 0.25 (0.11)
Trim Plates
G1T White None Genesis Trim Plate (for two-gang or 4” square boxes) 0.15 (0.7)
G1RT Red None Genesis Trim Plate (for two-gang or 4” square boxes) 0.15 (0.7)
G1T-FIRE White FIRE Genesis Trim Plate (for two-gang or 4” square boxes) 0.15 (0.7)
G1RT-FIRE Red FIRE Genesis Trim Plate (for two-gang or 4” square boxes) 0.15 (0.7)
G1WT-ALERT White ALERT Genesis Trim Plate (for two-gang or 4” square boxes) 0.15 (0.7)
Surface Boxes
27193-16 White N/A One-gang surface mount box 1 (0.4)
27193-11 Red N/A One-gang surface mount box 1 (0.4)
¹ These 15/75 cd models provide fixed output and are not multi-candela devices. The 15 cd output component complies with UL1971, while the 75 cd
output component complies with UL 1638.
U.S.
T 888 378 2329
F 866 503 3996
Canada
Chubb Edwards
T 519 376 2430
F 519 376 7258
Southeast Asia
T : +65 6391 9300
F : +65 6391 9306
India
T : +91 80 4344 2000
F : +91 80 4344 2050
Australia
T +61 3 9239 1200
F +61 3 9239 1299
Europe
T +32 2 725 11 20
F +32 2 721 86 13
Latin America
T 305 593 4301
F 305 593 4300
utcfireandsecurity.com
05-18-11
Overview
Edwards fire alarm telephones are rugged communications de-
vices for emergency use. Enclosed keylocked telephone stations Frontplate – Non-Break Glass
comprise three separately ordered components: the handset • Flush or surface mount models
assembly, the frontplate, and the wallbox. Depending on how the • Red powdercoat finish
phones are wired, they are supervised for three or four state op- • Locking door, concealed hinges
eration. Frontplates are available with either metal or break glass
6831-4 • Metal insert
6831-2
insterts.
MEA approved warden stations feature doors with magnetic Wallbox
latches and one-state handsets with armoured cords. Warden sta- • Red powdercoat finish
tions mount to 6832-1 wallboxes. • Flush or surface mount
• For use with 6831 series front plates
Portable handsets plug into one-gang receptacles. Handsets are
• Flush or surface mount
available in black or red. The TCS-6 cabinet provides storage for
up to six handsets. 6832-1
Handset Assembly
Application • Red ABS plastic handset
Firefighters’ telephones are typically installed in corridors, lob- 6830-1 • 60 inch (1500 mm) coiled cord set
bies, mechanical rooms, stairways, or other stategic locations. 6830-4 • Supervised wiring
6830-5A
When lifted from its cradle, or plugged into a suitable wall jack, the 6830-6A • For use with 6831 series front plates
handset activates audible and visible signals at the control panel. 6830-5A4 • Four-state models available
6830-6A4
There, the operator needs only to lift the handset off the cradle to
respond to the current call. Other firefighters’ telephones may be
selected at the control panel to join the conversation. 6833-4 Portable Handsets and Receptacle
• Black or red ABS plastic handset
• 60 inch (1500 mm) coiled cord set
• Supervised wiring
• Stainless-steel one-gang faceplate
6830-3
TCS-6 Handset Storage Cabinet 6700-0061
• Flush or surface mount receptacle
(handsets not included) • Four-state models available
5¼" ¾” or 1” Conduit
4¼" ¾” or 1” Conduit
(133 mm) (133 mm) Top and/or bottom
Top and/or bottom
TELEPHONE TELEPHONE
FOR EMERGENCY FOR EMERGENCY
USE ONLY USE ONLY
16”
14" 14" 14"
(405 mm)
(356 mm) (356 mm) (356 mm)
Frontplate
Frontplate
1¼" 1¼"
8½" (32 mm) 8½" (32 mm)
(216 mm) (216 mm)
3½" 3½"
10½” (89 mm) (89 mm)
(267 mm)
Surface Mounting
Flush Mounting
Flush Mounting Surface Mounting
Assembly 4¼"
(133 mm)
¾” or 1” Conduit
Top and/or bottom
TELEPHONE
FOR EMERGENCY
USE ONLY
14" 14"
(356 mm) (356 mm)
E
ON CY
PH GEN
LE
TE MERNLY
RE O
FO USE
Wallbox
Frontplate
Telephone
Handset
1¼"
8½" (32 mm)Frontplate
(216 mm)
3½"
(89 mm)
Surface Mounting Edwards recommends that these fire alarm communication devices always
be installed in accordance with the latest recognized editions of national
and local fire alarm codes.
1 1
2 2
3 3
EOL EOL
4 4
[4] 5
[4] 5
[5] [5]
24 Vdc 6 24 Vdc 6
7 7
24 Vdc 8 24 Vdc 8
UL/ULC listed Control relay module to operate TB1 UL/ULC listed Control relay module to operate TB1
power supply Telephone in Use indicator light. power supply Telephone in Use indicator light.
Notes
[1] Use jacketed, twisted, shielded pair [4] Connect the shields to chassis ground in the control panel
[2] 14 to 22 AWG (2.08 to 0.33 sq mm) [5] Telephone in Use indicator light (NY versions only)
[3] Max. line impedance: 50 Ohms, 25 Ohms per line Three-state operation does not comply with UL 864 ninth edition.
Note that the riser polarities for differ between three-state and four-state operation.
Warden Stations
Four-state Remote Telephone Warden Station - Flush.
12 lb
6830-NY-F4 Handset station for use with 6832-1 backbox. Hinged flush UL, MEA
(5.4kg)
door with magnetic latch. Handset includes armored cord.
Four-state Remote Telephone Warden Station - Surface.
Handset station for use with 6832-1 backbox. Hinged 12 lb
Detection & alarm since 1872 6830-NY-S4 UL, MEA
surface door with magnetic latch. Handset includes armored (5.4kg)
U.S. cord.
T 888-378-2329
F 866-503-3996 Fixed Telephone Handsets (order frontplates and wallboxes separately)
Four-state Telephone Handset Assembly - Red, 60” 6 lb
Canada 6830-4 UL, MEA
Chubb Edwards (1500mm) Coiled Cord. (2.7kg)
T 519 376 2430 Four-state Telephone Handset Assembly - Red, 60” 6 lb
6830-5A-4 UL, MEA
F 519 376 7258 (1500mm) Coiled Cord, Push-to-talk button. (2.7kg)
Four-state Telephone Handset Assembly - Red, 60” 7 lb
Southeast Asia 6830-6A-4 UL, MEA
(1500mm) Armored Cord, Push-to-talk button. (3.1kg)
T : +65 6391 9300
F : +65 6391 9306
Portable Telephone Handsets
India Four-state Portable Telephone Handset Receptacle 1-gang UL,
T : +91 80 4344 2000 .22 lb
6833-4 Stainless-steel Faceplate for use with 6830-3 or 6700- MEA,
F : +91 80 4344 2050 (0.1kg)
0061. CSFM
Australia UL,
Portable Telephone Handset - Black c/w 60” (1500mm) 1.1 lb
T +61 3 9239 1200 6830-3 MEA,
Coiled Cord. (0.5kg)
F +61 3 9239 1299 CSFM
Portable Telephone Handset - Red c/w 60” (1500mm) 1.1 lb
Europe 6700-0061 UL, MEA
Coiled Cord. (0.5kg)
T +32 2 725 11 20
F +32 2 721 86 13
Frontplates
Latin America Frontplate - Flush Mount, Red Finish, Break Glass Type c/w 1.32 lb
T 305 593 4301 6831-1
2 keys. 16” (405 mm) H x 10-1/2” (267 mm) W. (0.6kg)
F 305 593 4300
Frontplate - Flush Mount, Red Finish, Non-Break Glass Type 1.32 lb
6831-2
utcfireandsecurity.com c/w 2 keys. 16” (405 mm ) H x 10-1/2” (267 mm) W. (0.6kg)
Frontplate - Surface Mount Red Finish, Break Glass Type See 1.1 lb
© 2010 UTC Fire & Security. 6831-3
c/w 2 keys. 14” (356 mm) H x 8-1/2” (216 mm) W. Note 1 (0.5kg)
All rights reserved.
Frontplate - Surface Mounting Red Finish, Non-Break Glass 1.1 lb
6831-4
Type c/w 2 keys. 14” (356 mm) H x 8-1/2” (216 mm) W. (0.5kg)
PP46137- Replacement Break Glass Insert - for use in 6831-1 and 1.1 lb
0067 6831-3. (0.5kg)
Wallboxes
Wallbox - Flush or Surface mount, Red finish. 14” (356mm) See 1.54 lb
6832-1
H x 8-1/2” (216mm) W x 3½” (89mm) D. Note 1 (0.7kg)
Portable handset storage cabinet. Surface mount c/w
keylock. Red finish with white lettering: “Emergency 12 lb
TCS-6 N/A
Telephone Handsets”. 15½” (394 mm ) H x 24-1/8” (613 mm) (5.4kg)
W x 4”(102) D.
Note 1: Agency listings for these components are included under the handset assemblies or warden stations
they are installed with.
05-18-11
SPECIFICATION SHEET
100 Bradley Parkway • Blauvelt, NY 10913 TAPPAN Spec. G60004.1
Phone: 1-800-WIRE-911 • Fax: 1-845-353-9315 Update 1.3 5/11/2012
Tappan Wire & Cable Inc. provides information and specifications on an “as is” basis. Information in specifications described herein are subject to error
and/or omission, and subject to change without notice. Although we make all efforts possible to ensure the accuracy and timeliness of the information,
Tappan Wire & Cable, will not be held liable for any damages whatsoever, even if advised of the possibility of such damages, arising from the use, or
inability to use, the information or specifications herein. Please refer to our “Website Use Policy”, listed on our website, www.tappanwire.com, under the
Sales Support Section for full details, or contact your Tappan Representative. This drawing may contain patented or proprietary information. It is the
property of Tappan Wire and must not be used in any way detrimental to Tappan Wire. Acceptance by signature of this drawing will be considered as an
agreement of and acceptance of the foregoing.
SPECIFICATION SHEET
100 Bradley Parkway • Blauvelt, NY 10913 TAPPAN Spec. G50032.1
Phone: 1-800-WIRE-911 • Fax: 1-845-353-9315 Update 1.3 5/11/2012
Tappan Wire & Cable Inc. provides information and specifications on an “as is” basis. Information in specifications described herein are subject to error
and/or omission, and subject to change without notice. Although we make all efforts possible to ensure the accuracy and timeliness of the information,
Tappan Wire & Cable, will not be held liable for any damages whatsoever, even if advised of the possibility of such damages, arising from the use, or
inability to use, the information or specifications herein. Please refer to our “Website Use Policy”, listed on our website, www.tappanwire.com, under the
Sales Support Section for full details, or contact your Tappan Representative. This drawing may contain patented or proprietary information. It is the
property of Tappan Wire and must not be used in any way detrimental to Tappan Wire. Acceptance by signature of this drawing will be considered as an
agreement of and acceptance of the foregoing.
SPECIFICATION SHEET
100 Bradley Parkway • Blauvelt, NY 10913 TAPPAN Spec. G50013.1
Phone: 1-800-WIRE-911 • Fax: 1-845-353-9315 Update 1.3 5/10/2012
Tappan Wire & Cable Inc. provides information and specifications on an “as is” basis. Information in specifications described herein are subject to error
and/or omission, and subject to change without notice. Although we make all efforts possible to ensure the accuracy and timeliness of the information,
Tappan Wire & Cable, will not be held liable for any damages whatsoever, even if advised of the possibility of such damages, arising from the use, or
inability to use, the information or specifications herein. Please refer to our “Website Use Policy”, listed on our website, www.tappanwire.com, under the
Sales Support Section for full details, or contact your Tappan Representative. This drawing may contain patented or proprietary information. It is the
property of Tappan Wire and must not be used in any way detrimental to Tappan Wire. Acceptance by signature of this drawing will be considered as an
agreement of and acceptance of the foregoing.