Академический Документы
Профессиональный Документы
Культура Документы
INTRODUCTION
The Institution of Electrical Engineers (lEE) guide (BS 7671) is used to assist in
design and installation of electrical services. Engineers follow the guide closely to
provide safe and efficient electrical systems in buildings.
The supply or intake cable may enter the building through an underground duct or
via an overhead supply.
An underground supply is preferred since all of the electrical service is hidden.
The supply cable is terminated in the area board’s fused sealing chamber which
should be sited in a dry accessible position. From the sealing chamber the supply
passes through the meter, which records the electricity consumed in units of
kilowatt/hours, to the consumer unit which has a switch controlling the supply to
the circuit breakers or circuit fuses.
These fuses are a protection against excess current or overload of the circuit since
when overloading occurs, the fuse or circuit breaker will isolate the circuit from the
source of the problem.
The consumer unit should be fitted close to the point of service entry and from here
the service is divided into a number of sub-circuits. It is normal in a domestic
installation to separate power circuits and lighting circuits so that if a fault occurs
then not all socket outlets or lights are isolated.
Sometimes an external cabinet is used for easy meter reading. This is located in an
outside wall as shown below.
EXTERNAL CABINET
POWER CIRCUITS
When deciding on the number of circuits for a house, a useful rule is; one power
circuit for every 100m2 of floor area. In larger houses this means that two circuits
can be used for power socket outlets, in a two-storey house this would be one
circuit for upstairs and one for downstairs. In some larger houses a separate power
circuit is also installed for the garage / utility area.
In all domestic installations a separate power circuit is required for the cooker since
the electrical demand is likely to be high. The immersion heater in the hot water
cylinder can also be supplied from a separate circuit since a 3kW load is quite high.
Ring circuits are used as a safe and economic method of distribution of electricity
to socket outlets.
Many consumer unit manufacturers produce 8 way and 12 way units.
The drawing below shows the layout of conduit and conductors for a ring circuit in
a small building. Steel or plastic conduit is used in the walls to protect cables from
mechanical damage. The conduit is buried in the wall behind the plaster. This
means that the wall will be tracked to accommodate the circular or oval 20mm
diameter conduit.
The earth conductor may not be covered but the live and neutral are each
separately coated in a PVC covering. The three conductors (L,N & E) can be
covered in an outer covering of PVC to form PVC/PVC Twin and Earth. The
typical size of conductors for a ring circuit for domestic use is 2.5 mm2, this is the
cross sectional area of the conductor. The conductors are pulled through the conduit
after it is installed by a ‘fish’ wire.
Another method of installing a ring circuit may be to distribute the conductors
horizontally under the floor instead of above the ceiling. This reduces the length
of conduit buried in the wall. If a solid cement floor is constructed then the
conductors would need to be protected by galvanised steel conduit. If a suspended
timber floor is constructed then a PVC/PVC cable could be clipped to wooden floor
joists. This is the method adopted for two-storey houses, for an upstairs ring circuit.
The consumer's mains equipment is normally fixed close to the point at which the
supply cable enters the building. To meet the requirements of the IEE Regulations
it must provide:
Protection against electric shock is provided by insulating and placing live parts out
of reach in suitable enclosures, earthing and bonding metal work and
providing fuses or circuit breakers so that the supply is automatically disconnected
under fault conditions. To provide overcorrect protection it is necessary to provide
a device which will disconnect the supply automatically before the overload current
can cause a rise in temperature which would damage the installation. A fuse or
miniature circuit breaker (MCB) would meet this requirement.
In practice it is the aim to bring the Electrical supply to the appliance with as small
a loss of voltage through the conductor as possible. This means that the wiring must
have the smallest resistance that is economical.