The DECS-100 is in stock in at Powerdist, thus reducing the lead time to 1-2 days
Extremely Cost effective replacement
Support available around the clock from Australia (details here)
DECS-100’s Built-in Over & Under Excitation limiters to protect the generator from operating outside
its capability
DECS-100’s Built-in Loss of sensing detection is included in the DECS-100, to prevent over voltage
damage following a sensing fuse blown or a bad connection in the sensing circuit
The problem is that upgrading an AVR introduces additional engineering costs. The purpose of this post is to
reduce this cost by providing guidelines for the upgrade process and explaining the differences between the 2
AVRs and provide instructions to bypass the differences. The DECS100 is not an exact like for like
replacement but fortunately the replacement does not require a lot of effort. Some considerations are
necessary when implementing the upgrade:
Mechanical Considerations
The temperature, shock and humidity ratings are similar for both devices so the DECS-100 can withstand
anything the MX321 will.
https://www.powerdist.com.au/replacing-a-stamford-mx321-by-basler-electric-decs-100 1/4
3/24/2019 Replacing a Stamford MX321 by Basler Electric DECS-100 | Generator control and protection systems
NOTE A: If the voltage sensing is A-B-C as shown in the table above, the CT has to be connected on phase
WHITE. If the CT is on another phase, the voltage sensing can be modified to allow for the difference
NOTE B: The set-point adjustment on the DECS-100 is done via either RAISE/LOWER contacts or via a
wet +/-3V biasing signal. On the MX321, this is done using a potentiometer. The easier option is to replace
the old potentiometer by a RAISE/LOWER Switch
NOTE C: The DECS100 doesn’t need a Start/Stop signal. the AVR start to operate as soon as the generator is
started; the voltage will increase as per the soft start settings or the volt/hertz limiter if the generator
frequency increases slower than the soft start.
NOTE D: The additional terminals B1, B3, 52J, 52K, 52L, 52M, VM, VMC of the DECS-100 are for more
functions and can simply be left disconnected if not used.
Generator voltage sensing input: The DECS-100 accepts a wider voltage range than the MX321.
https://www.powerdist.com.au/replacing-a-stamford-mx321-by-basler-electric-decs-100 2/4
3/24/2019 Replacing a Stamford MX321 by Basler Electric DECS-100 | Generator control and protection systems
Soft start:
Droop CT: The DECS100 is fitted with a CT input for parallel control (droop). The secondary CT has to be
specified when ordering with the following style:
Generator Over-voltage protection: The over-voltage protection is available in the DECS100 (set-
point adjustable from 100 to 120% and time delay from 0 to 10s)
Contact output for circuit breaker trip: The terminals AL1 – AL2 (ALARM) on the DECS100 can be used to
trip the generator circuit breaker in some circumstances (Generator over-voltage Field over-voltage Loss of
voltage sensing, Over excitation limiter or Under excitation limiter). The operation of this contact is
programmable.
The only difference is that the DECS-100 maximum output voltage is less than the rating of the MX321. In
most cases the rated voltage is actually less than 63Vdc. If you are not sure, we can double check the ratings
of your exciter.
Setpoint adjustment: On the MX321, the set-point adjustment is done by potentiometer. On the DECS100,
the set-point has to be adjusted by dry contacts: raise / lower or using a biasing signal. The biasing signal
needs to be wet +/-3V. The easier solution is to replace the old potentiometer by a RAISE/LOWER Switch.
Voltage matching function: allow tracking of the bus voltage for quick synchronisation. If required, the
style number has to be “DECS100-X1X”.
Power factor or reactive power regulation modes are available in the DECS100 with the style
“DECS100-BXX”.