Building Drift – Do You Check It?

Posted by Sam Hensen on January 16, 2013

[Simpson Strong-Tie note: Sam Hensen is the Simpson Strong-Tie Engineering Manager for the
Southeast U.S. and the latest blogger for the Structural Engineering Blog. For more on Sam, see his
bio here.]
Just as bending and shear checks performed on gravity loaded beams do not ensure that the beam
will comply with required deflection limitations, adherence to allowable shears and aspect ratio
limits on shearwalls does not mean the structure will comply with required drift limitations. Shearwalls
that are too flexible may prevent the structure from meeting drift limitations even if the shearwall design
has adequate strength.

Seismic
For seismic load applications, section 12.12.1 of ASCE7-10 states that the design story drift of the
structure shall not exceed the allowable drift listed in table 12.12-1. For light-frame buildings, the
maximum permitted drift is 2.5% of the story height. This limitation is put in place not merely for
serviceability reasons, but is an inherent effect of current seismic design provisions that is required to
be checked to ensure life safety.

Current seismic design provisions do not use the Maximum Considered Earthquake (MCE) response,
but instead design procedures are in place to allow for a much smaller seismic force to be utilized
based on the ability of the lateral resisting system to absorb and dampen the energy during the seismic
event. This process requires the structure to deflect under each cycle of loading, but not deflect
enough for a collapse to occur, so this method relies heavily on ductility inherent in the chosen lateral
resisting system. More ductile systems can undergo larger deflections when loaded and the benefit is
a lower seismic design force. A simple steel frame and yield curve is shown below to further clarify the
definition of ductility.

Ductility Graph
An increase in the lateral resisting system ductility means a lessened seismic design force for the
structure (see graph below). On a separate note, the reliance on ductility for seismic design is one
reason seismic detailing and limitations must be followed even when wind controls the design. Take a
look at Paul’s previous blog post, Ignore Seismic Requirements When Wind Controls?

Strength versus Ductility Graph

Okay, back to our original discussion. Since the amount of deflection the lateral system will undergo is
not just a serviceability issue, the required deflection check is even more critical than for gravity loaded
systems due to P-Delta effects. Although deflection checks including P-Delta effects are included in
most structural analysis software, this design check is often omitted in structures analyzed by hand.

Wind
Traditionally, for high wind design, we used the actual pressures the building is expected to
experience. The building was expected to perform well not just for life safety, but also to sustain
minimal cosmetic damage and protect the contents and belongings. Currently ASCE7-10 requires all
building envelope openings be protected from flying debris in wind-borne debris regions, allowing the
designer to use a much smaller internal pressure (3x less than when not protecting the openings.)

This measure was put in place in ASCE7-05 and was a result of losses realized when the building
envelope is penetrated during the wind event and significant damage occurring from water intrusion.

One of the most popular methods used to protect openings is to use impact-resistant glazing systems.
There are racking limitations for this type of opening protection in order for them to work properly and
maintain their structural integrity. In my opinion, this issue is addressed in section 4.1.3 of the Special
Design Provisions for Wind and Seismic (SDPWS). It states, “Deformation of connections within and
between structural elements shall be considered in design such that the deformation of each element
and connection comprising the lateral force-resisting system is compatible with the deformations of the
other lateral force-resisting elements and connections and with the overall system.”
The only way for a design to be in conformance with these wind or seismic requirements is for the
designer to check building drift and ensure that the components within the lateral force-resisting
system are all compatible and do not exceed the allowable drift. If they are not compatible or have
excessive drift, then additional considerations must be made, just as we would increase the depth of a
beam to comply with serviceability deflection requirements.