DCDU-01

The Direct Current Distribution Unit-01 (DCDU-01) supplies DC power to each component in
the cabinet.

Panel

Figure 1 shows the panel of the DCDU-01.


Figure 1 Panel of the DCDU-01

Functions

The DCDU-01 has the following functions:


  Supports one -48 V DC inputs

  Supports ten -48 V DC outputs


 One 25 A output to the SPARE2 port
 Nine 12 A outputs to other ports

 Supplies power to only the BBU3900, RFUs, and fan box in the cabinet, but not
external devices

Ports

Table 1 describes the ports, terminals, and power switches on the panel of the DCDU-01.

Table 1 Ports, terminals, and power switches on the panel of the DCDU-01

Port Label Connector Description

Power input NEG(-) OT terminal Negative input wiring


wiring terminals terminal

RTN(+) Positive input wiring


terminal

Power output SPARE2, SPARE1, Parallel terminal Providing 10 power


port BBU, FAN, and RFU5 outputs to the modules
to RFU0 such as the BBU3900,
RFUs, and fan box
Table 1 Ports, terminals, and power switches on the panel of the DCDU-01

Port Label Connector Description

Power switch SPARE2, SPARE1, - Powering on or powering


BBU, FAN, and RFU5 off the modules such as
to RFU0 the BBU3900, RFUs, and
fan box

DCDU-03
Configured with MCBs of different specifications, the DCDU-03 can be classified into DCDU-
03A, DCDU-03B, and DCDU-03C. The three types of DCDU-03 have the same appearance,
engineering specifications, and ports.

Appearance

Figure 1 shows the DCDU-03.


Figure 1 DCDU-03

Engineering Specifications

Table 1 describes the engineering specifications of the DCDU-03.

Table 1 Engineering specifications of the DCDU-03

Item Specification

Weight ≤ 4 kg

Dimensions (width x height x depth) 442 mm x 42 mm x 200 mm

Functions

The Direct Current Distribution Unit (DCDU-03) provides the following functions:
 Provides nine -48 V DC outputs to meet multiple power distribution requirements in
scenarios of distributed and separated base stations through different MCB
configurations
 Provides surge protections through the built-in DC surge protection board

 Provides surge protection alarm signals and reporting the surge protection alarms in
time
Table 2 describes the DC power distribution functions of the DCDU-03.

Table 2 DC power distribution functions of the DCDU-03

DCDU Type DC Output Power MCB MCB Application


Terminal consumptio Specificatio Quantity Scenario
n devices n

DCDU-03A LOAD0 Temperature 12 A 1 Transmission


control cabinet
system

LOAD1 to Transmission 4 A 8
LOAD8 devices of the
operator

DCDU-03B LOAD0 to RRU 20 A 6 GSM


LOAD5 distributed
base station
LOAD6 to BBU and the 12 A 3
LOAD8 transmission
devices of the
operator

DCDU-03C LOAD0 to RRU 12 A 6 WCDMA or


LOAD5 WiMax
distributed
LOAD6 BBU 12 A 1 base station

LOAD7 and Transmission 6 A 2


LOAD8 devices of the
operator

Ports

Figure 2 shows the ports on the panel of the DCDU-03.


Figure 2 Ports on the panel of the DCDU-03
 Figure 2 takes the DCDU-03A for example.
Table 3 describes the ports on the panel of the DCDU-03.

Table 3 Ports on the panel of the DCDU-03

Port Specification Cross-Sectional Area (Unit: Remarks


mm2)

DC input Supporting M6  DCDU-03A:6 -


terminal 2-hole OT  DCDU-03B,DCDU-
terminal
03C:25

DC LOAD0 to 2.5  Three rows of


output LOAD8 (from wiring terminals for
terminal left to right) outputs: NEG(-),
RTN(+), and PGND,
where, the last three
pairs of the PGND
wiring terminals
support the grounding
of the M4 2-hole OT
terminals, as shown in
the red boxes in
Figure 2
 Supporting the
output power cable
with a maximum
cross-sectional area of
6 mm2

Surge Supporting 2- - 2-pin cord end terminal not


protectio pin cord end distinguished from different
n alarm terminal polarities
wiring
terminal
DCDU-04
The DCDU-04 provides DC power to the BTS3900 or other base stations.

Structure

For the position of the DCDU-04, see Structure of the PS4890. Figure 1 shows the structure
of the DCDU-04.
Figure 1 Structure of the DCDU-04

Engineering Specifications

Table 1 describes the engineering specifications of the DCDU-04.

Table 1 Engineering specifications of the DCDU-04

Item Specification

Weight 3 kg

Dimensions (Width x Height x Depth) 442 mm x 42 mm x 140 mm

Functions

The DCDU-04 is used for DC power distribution. All the input and output power cables are
connected on the front panel. The DCDU-04 has the following functions:
 Supports two DC power outputs at a maximum current of 80 A respectively, which can
provide power supply to BTS3900 or other base stations.
 Provides the temperature alarm of the battery through the built-in HPMI (Hert Power
and environment Monitoring Interface unit).

Port

Figure 2 describes the ports on the panel of the DCDU-04.


Figure 2 Ports on the panel of the DCDU-04
Figure 3 shows the HPMI.
Figure 3 HPMI

Table 2 describes the ports on the panel of the DCDU-04.

Table 2 Ports on the panel of the DCDU-04

Port Label Function

DC output LOAD0 and Providing two output DC power at a maximum current of


terminals LOAD1 80 A.

HPMI TO PMU DB50 Transferring the monitoring signals of the PMU

A:1.2.3.4 Transmitting two Boolean signals

B:1.2.3.4 Receiving two Boolean signals

C:1.2.3.4  1.2: receiving one Boolean signals


 3.4: detecting the fuse alarm signals

Gate Receiving the door status alarm signals

D:1.2.3.4  1.2: receiving the AC surge protection alarm


signals
 3.4: receiving the DC surge protection alarm
signals

Bat1 Tmp Receiving the battery temperature monitoring signals

E:1.2.3.4 Receiving two Boolean signals


Table 2 Ports on the panel of the DCDU-04

Port Label Function

Smoke Receiving the smoke alarm signals

Water Receiving the water immersion alarm signals

Tem Humi Receiving the temperature and humidity alarm signals

Bat2 Tmp Providing the standby port for the input of the battery
temperature monitoring signals

DCDU-11A
The direct current distribution unit-11A (DCDU-11A) is a 1 U high module, supplying DC
power to components in the cabinet.

Exterior

Figure 1 shows a DCDU-11A.


Figure 1 DCDU-11A

Function

The DCDU-11A performs the following functions:


 Supports one -48 V DC input of 160 A or two -48 V DC inputs of 80 A

 Supports ten -48 V DC outputs of 25 A

 Supplies power to the RFUs and fan assembly in the cabinet, but not to any external
equipment
Table 1 lists the DC power distribution functions of the DCDU-11A.

Table 1 DC power distribution functions of the DCDU-11A

DC Output Equipment Circuit Breaker Circuit breaker


Terminal Specifications

LOAD0 to RFU0 to RFU5 25 A SW0 to SW5


LOAD5
Table 1 DC power distribution functions of the DCDU-11A

DC Output Equipment Circuit Breaker Circuit breaker


Terminal Specifications

LOAD6 Fan assembly 25 A SW6

LOAD7 to Reserved for external 25 A SW7 to SW9


LOAD9 equipment

Ports

Figure 2 shows the ports on the panel of the DCDU-11A.


Figure 2 Ports on the panel of the DCDU-11A

Table 2 Ports on the panel of the DCDU-11A

Item Port Type Label Connector Description


and Cable

1 Power input NEG(-) Two M6 one- Negative power input


wiring hole OT wiring terminal
terminal terminals and
RTN(+) cables with Positive power input
the maximum wiring terminal
cross-
sectional area
of 25 mm2

2 Circuit SW0 to SW9 - The circuit breakers SW0


breaker to SW9 control the ports
LOAD0 to LOAD9
respectively, controlling
the power supplies to the
RFUs, fan assembly, and
Table 2 Ports on the panel of the DCDU-11A

Item Port Type Label Connector Description


and Cable

other components.

3 Power LOAD0 to Figure 3 For details about DC


output port LOAD9 shows an output specifications, see
easy power Table 1.
receptacle
(pressfit type)
connector
used for any
port from
LOAD0 to
LOAD9. The
connector is
applicable to a
cable with the
maximum
cross-
sectional area
of 4 mm2.
Figure 3 Tool-less female connector (pressfit type)

DCDU-11B and DCDU-11C


The DCDU-11B and DCDU-11C are 1 U-high direct current distribution units, which supply
power to each component in the cabinet. They have the same exterior, engineering
specifications, and ports but different circuit breaker specifications and usage scenarios.

Exterior

Figure 1 and Figure 2 show the front and rear views of a DCDU-11B/DCDU-11C respectively.
Figure 1 Front view of the DCDU-11B/DCDU-11C
Figure 2 Rear view of the DCDU-11B/DCDU-11C

NOTE:
The DCDU-11C does not use the equipotential connection point and ground point. The
DCDU-11B uses the equipotential connection point or ground point only in one of the
following scenarios:
 Scenario 1: The DCDU-11B is placed in an open rack and is connected to the ground
bar of the open rack by using the equipotential connection point near the mounting ears.
 Scenario 2: The DCDU-11B is mounted on a wall to serve as an independent power
distribution device, which is connected to the ground bar in the equipment room by using
the ground point at the rear of the DCDU-11B.

Function

The DCDU-11B/DCDU-11C provides ten -48 V DC outputs. Different circuit breaker


configurations can meet power distribution requirements for a distributed or outdoor macro
base station.
Table 1 lists the DC power distribution functions of the DCDU-11B/DCDU-11C.
Table 1 DC power distribution functions of the DCDU-11B/DCDU-11C

DCDU DC Equipment Circuit Circuit Description


Type Output Breaker Breaker
Terminal Specification
s

DCDU-11B LOAD0 to RRU0 to RRU5 25 A SW0 to Distributed or


LOAD5 SW5 mini base
station
LOAD6 BBU or transmission 25 A SW6
equipment

LOAD7 BBU or transmission 25 A SW7


equipment

LOAD8 EMUA or 25 A SW8


transmission
equipment

LOAD9 Fan assembly 25 A SW9

DCDU-11C LOAD0 Transmission 6A SW0 -48 V outdoor


equipment macro base
station or
LOAD1 Transmission 6A SW1 transmission
equipment cabinet

LOAD2 Transmission 12 A SW2


equipment

LOAD3 Transmission 12 A SW3


equipment

LOAD4 Transmission 25 A SW4


equipment

LOAD5 Transmission 25 A SW5


equipment

LOAD6 BBU or transmission 25 A SW6


equipment

LOAD7 BBU or transmission 25 A SW7


equipment

LOAD8 EMUA or 25 A SW8


transmission
equipment

LOAD9 Fan assembly 25 A SW9


Ports

Figure 3 shows the ports on the panel of the DCDU-11B/DCDU-11C.


Figure 3 Ports on the panel of the DCDU-11B/DCDU-11C

Table 2 describes specifications of the ports on the panel of the DCDU-11B/DCDU-11C.

Table 2 Specifications of the ports on the panel of the DCDU-11B/DCDU-11C

SN Port Label Terminal and Cable Description

(1) DC input NEG(-) M6 one-hole OT Negative power input wiring


terminal terminal (two wires) terminal
and a maximum
RTN(+) cross-sectional area Positive power input wiring
of 25 mm2, default terminal
cross-sectional area
of 16 mm2.

(2) DC output LOAD0 to DCDU-11B: For details about DC output


terminal LOAD9  Figure 4 specifications, see Table 1.
shows an easy
power
receptacle
(pressfit type)
connector
adapting to
LOAD0 to
LOAD5
terminals. The
maximum cross-
sectional area is
10 mm2.
 Figure 5
shows an easy
power
receptacle
Table 2 Specifications of the ports on the panel of the DCDU-11B/DCDU-11C

SN Port Label Terminal and Cable Description

(pressfit type)
connector
adapting to
LOAD6 to
LOAD9
terminals. The
maximum cross-
sectional area is
4 mm2.
DCDU-11C: Figure 5
shows an easy power
receptacle (pressfit
type) connector
adapting to LOAD0 to
LOAD9 terminals. The
maximum cross-
sectional area is 4
mm2.

(3) Circuit SW0 to SW9 - The circuit breakers SW0 to


breaker SW9 control the ports LOAD0
to LOAD9 respectively,
controlling the power supplies
to the BBU, fan assembly, and
transmission equipment.

Figure 4 Easy power receptacle (pressfit type) connector (1)

Figure 5 Easy power receptacle (pressfit type) connector (2)


Technical Specifications

Table 3 describes the technical specifications of the DCDU-11B and DCDU-11C.

Table 3 Technical Specifications of the DCDU-11B and DCDU-11C

Item Specification

Dimension (H x W x D) The DCDU-11B/DCDU-11C is 1 U (44.45


mm or 1.75 in.) high and can be installed in a
19 inch cabinet or rack. Its dimensions are
as follows:
 42 mm x 442 mm x 220 mm (1.65 in.
x 17.4 in. x 8.66 in.) (without mounting
ears)
 42 mm x 482.6 mm x 220 mm (1.65
in. x 19 in. x 8.66 in.) (with mounting
ears)

Surge protection specifications of ports on -48 V DC port, differential mode: 10kA


DCDU-11B or DCDU-11C (8/20μs)

-48 V DC port, common mode: 20kA


(8/20μs)

DCDU-12A
A direct current distribution unit-12A (DCDU-12A) is 1 U high and
provides DC power for all components in the cabinet.

Exterior
Figure 4-17 shows a DCDU-12A.
Figure 4-17 Front view of a DCDU-12A

(1) DC input (2) DC output (3) Spare fuse (4) Grounding


terminal terminal box point

Functions
The DCDU-12A provides ten -48 V DC outputs using same fuse
configurations to meet the power distribution requirements of the
RFC.
Table 4-12 describes the DC power distribution functions of the DCDU-
12A.
Table 4-12 DC power distribution functions of the DCDU-12A
DCDU Type DC Output Power- Specification
Terminal Consuming of the Fuse
Device

DCDU-12A LOAD0 to LOAD5 RFU 0 to RFU 5 30 A

LOAD6 FAN

LOAD7 Reserved

LOAD8 Reserved

LOAD9 Reserved

Ports
Figure 4-18 shows the ports on the DCDU-12A panel.
Figure 4-18 Ports on the DCDU-12A panel

Table 4-13 shows the terminals and switches on the DCDU-12A panel.
Table 4-13 Terminals and switches on the DCDU-12A panel
No. Port

(1) DC input terminals

(2) Fuse block


No. Port

(3) DC output terminals

(4) Spare fuse box


Figure 4-19 Exterior of an EPC4 connector

Technical Specifications
Table 4-14 lists the technical specifications of a DCDU-12A.
Table 4-14 Technical specifications of a DCDU-12A
Item Specifications

Dimensions (H x W x D) The DCDU-12A is 1 U high and can be


installed in a 19-inch cabinet or
rack. Its dimensions are as follows:
 42 mm x 442 mm x 65 mm (1.65
in. x 17.4 in. x 2.56 in.)
(without mounting ears)
 42 mm x 482.6 mm x 65 mm
(1.65 in. x 19 in. x 2.56 in.)
(with mounting ears)

Surge protection specifications -48 V DC power port, 10 kA (8/20


μs) differential mode

-48 V DC power port, 20kA (8/20 μs)


common mode

DCDU-12B
A direct current distribution unit-12B (DCDU-12B) is 1 U high and
provides DC power for all components in the cabinet.

Exterior
Figure 4-20 and Figure 4-21 show exterior of a DCDU-12B.
Figure 4-20 Front view of a DCDU-12B

(1) DC input (2) DC output (3) Spare fuse (4) Ground


terminal terminal box point
Figure 4-21 Rear view of a DCDU-12B

(1) Ground point

NOTE:
The DCDU-12B uses the equipotential connection point and ground point in the
following scenarios:
 Scenario 1: The DCDU-12B is installed on an open subrack. An equipotential
cable connects the equipotential connection point near the mounting ear of
the DCDU-12B to the ground bar of the open rack.
 Scenario 2: The DCDU-12B is installed on a wall as a standalone power
distribution device. The ground point at the rear of the DCDU-12B is
connected to the ground bar in the cabinet.

Functions
The DCDU-12B provides ten -48 V DC outputs using same fuse
configurations to meet the power distribution requirements of
different distributed base stations.
Table 4-15 describes the DC power distribution functions of the DCDU-
12B.
Table 4-15 DC power distribution functions of the DCDU-12B
DCDU Type DC output Power- Specificati Remarks
ports Consuming on of the
Device Fuse

DCDU-12B LOAD0 to RRU0 to RRU5 30 A  BTS3900


LOAD5
 BTS3900A
LOAD6 BBU or  DBS3900
transmission  Mini NodeB
device

LOAD7 BBU or
transmission
DCDU Type DC output Power- Specificati Remarks
ports Consuming on of the
Device Fuse

device

LOAD8 EMUA or
transmission
device

LOAD9 Fan assembly

NOTE:
It is recommended that the power output terminals on the DCDU-12B be connected as
follows:
 The LOAD0 to LOAD5 terminals are connected to cables with a cross-sectional
area of 3.3mm2 (0.005 in.2) to 10mm2 (0.015 in.2) to provide power for RRU 0
to RRU 5.
 The LOAD6 to LOAD8 terminals are connected to cables with a cross-sectional
area of 1.5mm2 (0.002 in.2) to 4mm2(0.006 in.2) to provide power for RRU 6
to RRU 8.
 The LOAD9 terminal is reserved.

Ports
Figure 4-22 shows the ports on the DCDU-12B panel.
Figure 4-22 Ports on the DCDU-12B panel

Table 4-16 shows the terminals and switches on the DCDU-12B panel.
Table 4-16 Terminals and switches on the DCDU-12B panel
No. Port

(1) DC input terminals

(2) Fuse block


No. Port

(3) DC output ports

(4) Spare fuse box

NOTE:
Fuse blocks and DC output terminals are jointly called fuse terminal blocks.
Figure 4-23 Exterior of an EPC5 connector

Figure 4-24 Exterior of an EPC4 connector

Technical Specifications
Table 4-17 lists the technical specifications of a DCDU-12B.
Table 4-17 Technical specifications of a DCDU-12B
Item Specifications

Dimensions (H x W x D) The DCDU-12B is 1 U high and can be


installed in a 19-inch cabinet or
rack. Its dimensions are as follows:
 42 mm x 442 mm x 65 mm (1.65
in. x 17.4 in. x 2.56 in.)
(without mounting ears)
 42 mm x 482.6 mm x 65 mm
(1.65 in. x 19 in. x 2.56 in.)
(with mounting ears)

Surge Protection Specifications -48 V DC power port, 10 kA (8/20


μs) differential mode
Item Specifications

-48 V DC power port, 20 kA (8/20


μs) common mode

DCDU-12C
A direct current distribution unit-12C (DCDU-12C) is 1 U high and
provides DC power input for all components in the cabinet.

Exterior
Figure 4-25 shows the DCDU-12C.
Figure 4-25 Front view of a DCDU-12C

(1) DC input (2) DC output (3) Spare fuse (4) Ground


terminal terminal box point

Functions
The DCDU-12C provides ten -48 V DC outputs using same fuse
configurations to meet the power distribution requirements of
distributed and separated base stations
Table 4-18 describes the DC power distribution functions of a DCDU-
12C.
Table 4-18 DC power distribution functions of a DCDU-12C
DCDU Type DC output Power- Specificati Remarks
ports Consuming on of the
Device Fuse

DCDU-12C LOAD0 Transmission 30 A  BTS3900A


device (-48 V)
 Transmissi
LOAD1 Transmission
on cabinet
device

LOAD2 Transmission
device

LOAD3 Transmission
device

LOAD4 Transmission
device
DCDU Type DC output Power- Specificati Remarks
ports Consuming on of the
Device Fuse

LOAD5 Transmission
device

LOAD6 BBU or
transmission
device

LOAD7 BBU or
transmission
device

LOAD8 EMUA or
transmission
device

LOAD9 Fan assembly

Ports
Figure 4-26 shows the ports on the DCDU-12C panel.
Figure 4-26 Ports on the DCDU-12C panel

Table 4-19 describes the ports on the DCDU-12C panel.


Table 4-19 Ports on the DCDU-12C panel
No. Port

(1) DC input terminals

(2) Fuse block


No. Port

(3) DC output ports

(4) Spare fuse box

NOTE:
Fuse blocks and DC output terminals are jointly called fuse terminal blocks.
Figure 4-27 Exterior of an EPC4 connector

Technical Specifications
Table 4-20 lists the technical specifications of a DCDU-12C.
Table 4-20 Technical specifications of a DCDU-12C
Item Specifications

Dimensions (H x W x D) The DCDU-12C is 1 U high and can be


installed in a 19-inch cabinet or
rack. Its dimensions are as follows:
 42 mm x 442 mm x 65 mm (1.65
in. x 17.4 in. x 2.56 in.)
(without mounting ears)
 42 mm x 482.6 mm x 65 mm
(1.65 in. x 19 in. x 2.56 in.)
(with mounting ears)

Surge Protection Specifications -48 V DC power port, 10 kA (8/20


μs) differential mode

-48 V DC power port, 20 kA (8/20


μs) common mode