Академический Документы
Профессиональный Документы
Культура Документы
1 PRESENTATION...........................................................................................................4
1.1 MAIN FEATURES OF DEGO III..................................................................................4
1.2 BASIC FUNCTIONS OF DEGO III ...............................................................................5
1.2.1 General .............................................................................................................5
1.2.2 Parameterization ..............................................................................................5
1.2.3 I/O And Communication Ports .........................................................................5
1.2.4 Commissioning .................................................................................................5
1.2.5 Environment......................................................................................................6
1.2.6 Hardware Design..............................................................................................7
1.2.6.1 I/O Configuration...................................................................................................... 9
1.2.7 Disposition Of The LEDs ................................................................................14
1.2.8 Disposition Of The Program Jumpers ............................................................15
1.2.9 Terminal Layout..............................................................................................19
1.2.10 Disposition of terminals - General configuration...........................................20
1.2.11 Disposition of terminals, “BASIC” Single Engine Propulsion (ASAC X00) ..21
1.2.12 Power Amplifier..............................................................................................22
1.2.13 Display unit - Local Reset...............................................................................23
1.2.13.1 Software Presentation Mode............................................................................... 24
1.2.13.2 Normal Display Mode ........................................................................................ 24
1.2.13.3 Actuator Adjustment Mode ................................................................................ 24
1.2.14 Integrated Alarm System And Fault Logger ...................................................24
1.2.15 Alarm list ........................................................................................................25
1.3 DESCRIPTION OF THE BASIC GOVERNOR FUNCTIONS ..............................................28
1.3.1 Speed Setting...................................................................................................28
1.3.2 Speed Sensing .................................................................................................29
1.3.3 Start Function .................................................................................................29
1.3.4 Normal And Slow Mode Speed Control ..........................................................30
1.3.5 P-Gain ............................................................................................................30
1.3.5.1 Speed And Load Dependant Gain........................................................................... 31
1.3.5.2 Zone Amplifier........................................................................................................ 31
1.3.6 Integrator........................................................................................................31
1.3.7 D-Function......................................................................................................32
1.3.8 Torque Limit ...................................................................................................32
1.3.9 Smoke Limit ....................................................................................................33
1.3.10 Integrator Limit ..............................................................................................34
1.3.11 Overshoot Amplification .................................................................................34
1.3.12 State Machine .................................................................................................35
1.3.13 Fuel Admission Control Loops .......................................................................35
1.3.14 Fuel Servo - Functions....................................................................................36
1.3.15 Fuel Servo - External Arrangement................................................................36
1.4 THE SINGLE ENGINE PROPULSION APPLICATION ......................................................39
1.5 TWIN ENGINE PROPULSION APPLICATION..................................................................40
1.5.1 Master / slave operation. ................................................................................41
1.5.2 Serial communication between the governor Control Units (RS 485)............42
1.5.3 Unit identification system. ..............................................................................42
1.5.4 Load balance setting.......................................................................................43
1.5.5 Loading – unloading.......................................................................................44
1.5.5.1 Loading on time. ..................................................................................................... 44
1.5.5.2 Un-loading. ............................................................................................................. 44
1.5.5.3 Bypass..................................................................................................................... 45
1.5.6 Order declutch. ...............................................................................................45
1.5.7 Alarms for twin engine application.................................................................46
1.5.8 Disposition of terminals, “BASIC” Dual Engine Propulsion (ASAC X00) ....47
1.6 GENERATOR APPLICATION.......................................................................................48
1.6.1 Droop operation. ............................................................................................48
1.6.1.1 Droop operation with feedforward.......................................................................... 48
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 2
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
Approvals:
Revision History:
1 Presentation.
The DEGO III Governor System is a fully electronic speed control unit intended for a
wide range of Diesel engine types and applications. The governor has all the
traditional governor functions (propulsion, power generation, shaft generators,
parallel function, etc.). As in most modern computer systems, the software is
developed in portable (ANSI) C code. The microprocessor used for the system is
optimised to run C code. The governor design takes advantage of a number of new
control algorithms. Paired with modern control architecture this makes the control
system more efficient and easier to commission and use.
• The analog control includes two controllers (actuator position control and speed
control) ensuring a smooth control while maintaining the governor
responsiveness in case of critical situations such as sudden loss of load or
overspeed.
• The discrete control part is also rule-based. The state changes (including
alarms) are logged and stored in memory. All state-changes can be displayed
(printed out) in plain English. This feature leads to short commissioning
procedures and removes one of the most common reasons for commissioning
errors.
• The governor setup is fully under software control. Each configuration can be
created and copied using a standard PC.
• The I/O system is protected in order to comply with the European EMC rules.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 5
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
1.2.1 General
The governor system is programmed prior to delivery with the specific engine and
application data using the diesel engine specification and the application
specification. Further parameter settings and modifications can be made during
commissioning by means of a common PC connected via the serial interface.
The governor system can be parameterised via a standard PC, connected through
the serial communication link. The parameterisation is done via the DEGO III
Commissioning AID running under Windows (version 3.X, 9X, NT). Help functions
are available on-line. The set-ups for most common diesel engines are available in
the engine database. If several governor units are interconnected, any of them can
be programmed from the serial port of any unit.
The application program can be stored either in a flash PROM (inside the
microprocessor) or in an external EPROM (selected with program jumper). The
parameters for engine and application are stored in an Electrically Erasable PROM
(EEPROM).
1.2.3 I/O And Communication Ports
The digital input order signals from superior control units shall have the level of +24
VDC. Analogue input signals are in the range 4-20 mA or 0-10V the 0 and 100%
scaling can be selected in the aid.
Two serial ports are available: one interfaced with RS232 or RS485 (com1) and the
second interfaced with RS485 (com2). The com2 interface is the communication
between the governors in case of twin engine or generator application.
A PC can be connected to any of them using the RS 232. (Com 1)
In case the RS 485 (also com1) are all connected together and a modem is used, all
units can be reached by the PC without changing the connection.
The commissioning procedures such as tests and consistency checks, are made
using the Commissioning Aid installed in a PC. See chapter 2.
Normally an engine file for the actual engine is available. This forms the starting point
for further tuning of the parameters.
During commissioning all relevant parameters are displayed on-line in the DEGO III
Commissioning Aid. All parameters can be saved on a file for storage or print out.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 6
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
• Self test
• Consistency check (check that different parameters do not contradict each other)
• All relevant signals are displayed in digital, analogue, graphical or time-log form.
1.2.5 Environment
Low power and high power actuators are available with several possible AC/DC
power supplies. The actuator range is from 70 to 400 Nm.
The governor is designed for engine room environment. A superior control unit can
act either via conventional I/O or/and via a RS485/RS232 serial link. A common PC
(486 or higher) can be used for supervision and parameter reading.
The Digital signals have 24VDC level and the analog interfaces are 0-10 or 4-20mA
signals. The analog output is only for mA. Full scaling on analog signals is possible.
The engine speed is measured by means of pulses from two standard proximity
switches sensing a toothed wheel, for example the flywheel. Optional 4 proximity
speed switches can be used.
The charge air pressure input is intended for a 4-20 mA or 0-10V signal from a
standard pressure transmitter.
The generator power is measured using a single phase voltage and single phase
current signal (generator and shaft generator applications).
The supplies for the control electronics and for each actuator are galvanically
separated from each other and isolated from ground. Consequently, earth fault
monitoring is possible.
For the main actuator power circuit (actuator 2) an integrated earth fault detection
circuit is provided
In multi-engine plants, each governor can be galvanically insulated from each other
(different power supplies). The interconnection between the governors takes place
via one, or two redundant, multidrop RS485 bus(es). Galvanic isolation between the
24 Volt main supply and the 5 Volt processor related supply is done by dc/dc
converter. The zero volt reference of the 5 volt processor supply is grounded, this
means that the RS 485 bus(es) are not Galvanic isolated from the ground.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 7
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
PC MONITOR
SUPERIOR
CONTROL
SYSTEM
24 Vdc
RS485
RS485 (OPTION)
QHFQ 4X0
Ch 1 Ch 2 24 VDC SUPPLY
OTHER
DEGO III CONTROL POWER UNIT
CONTROL SUPERIOR SYSTEM
UNIT
(HARD WIRED)
UNIT
POWER SUPPLY
RS232
ACTUATOR
REMOVABLE TERMINAL
(FUTURE OPTION)
MODEM
VOLTAGE
PHASE R-S
PICKUPS CURRENT
PHASE T
CIRCUIT BREAKER
DISTANCE
POSITION
CONNECTION
MODEM PRESSURE CLUTCH
TRANSMITTER POSITION
PC AID
PC AID
Both the control circuits and the power amplifier for the fuel servo are
accommodated in the cabinet. Therefore, the wiring is reduced to a minimum.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 8
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
Power
+5V supply
0V earth
RS485
External connections
24V
supply
The terminal board is located on the bottom part of the cabinet, whereas the
microprocessor board is mounted on the door (on the mounting plate, the capacitors
and chokes for the power amplifier(s) are located).
For the power connection, an isolating switch (no fuse) is provided for each power
amplifier.
The QHFQ 552 is designed for save “generator” operation with a minimum of
interference with a PMS. It carries the same components as the QHFQ 100 series
but an extra interface board was needed to obtain the same functions, and wiring
connections, as the successfully predecessor the QHFD 552. This interface board,
QHFQ 220, have more connections to avoid bubble wire in one terminal, relays for
external indication and double pole filters for generator / busbar voltages / current
filtering. The QHFQ 552 remains running in isochronous with loadsharing without any
connection of the PMS.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 9
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
AC Power Amplifier
Display for status and alarm
DC Power Amplifier
Microprocessor board
EMC filters
Supply Switch
and connection
Power Ampl. 2
Supply Switch
and connection
Power Ampl. 1
Capacitor fo the DC
supply line
• Analog I/O
The analog inputs include 3 fixed connected signals and 5 signals that are accessible
from the terminals.
Three analog outputs are available for external use. Signal range 4-20mA.
Two additional analog outputs are actuator set values controlling the power amplifier
internally. Alternatively, these outputs can produce a 60-160mA PWM signal suitable
for Woodward actuators.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 10
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
Act 1
Act 2
Actuator 1 set value AO1
Actuator 2 set value AO2
SW Selectable AO3
SW Selectable AO4
SW Selectable AO5
X2 X8
X1 X7
Legend:
AI4 and AI5 are programmed on the terminal board. The default functions are shown
without brackets in the table below.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 11
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
• Analog inputs
With the AIS (Analogue Input Selection) jumpers, different inputs can be selected.
• Analog outputs
Outputs AO 2-4 are defined in the DEGO III Commissioning Aid from a choice of
output signals.
• Digital I/O
24 digital inputs (DI) and 9 digital outputs (DO) are controlled by the software. Some
of the functions are logically interconnected by hard-wired logic, e. g. watchdog,
actuator monitoring etc.
With the DIS (Digital Input Selection) jumpers, different inputs can be selected.
• Digital inputs
• Digital outputs
Light emitting diodes (LED's) are provided both on the processor board and on the
terminal board. The layout is shown in fig. 5 and 6.
ALARM RESET
+15V
+5V
-15V
The disposition of the jumpers on the circuit boards is shown in Figure 7 and 8.
The program jumpers are located on both the terminal board and the processor
board.
Dedicated programming jumpers adapt the analog inputs for current or voltage
signal. Other jumpers adapt the supply voltage for different type of speed setting and
actuator position feedback transducers.
Four sets of jumpers (T1-T4) are determining the division factor for the speed pickup
signals. Three jumpers on the processor board select between normal analog input
mode and AC input mode. The later are for generator applications. A detailed
description of the disposition of the jumpers can be found on the cover plates inside
the cubicle.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 16
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
FLASH T4
MD2 x1 2 3 4 5
ID
T3
x1 2 3 4 5
T2
SUPCPU x1 2 3 4 5
T1
x1 2 3 4 5
AO4CP
AO3CP AO5CP
CPURES
SS/ LS
BV 50/60 AI4DC
AI3DC
S2 S3 S5 S6 GV 50/60 GC 50/60 AI2DC
A2T XA
XC XF
XB XD 1 2 XE 1 2
DISEL A1S A1C
AISEL
3 1
1 5 EF1 EF2 EF3 EF4
9 7
A2S A2C
A2PCI AI5CI
A1PCI AI8CI
A2P24 IFB 1
Pull-up Pull-down A1P24 IFB 2
SSS Tacho 4
Tacho 3
Tacho 2
AI6ACI Tacho 1
J1 J2
X2 X4 X6 X8
X1 X3 X5 X7
Potentiometer Function
A1S Set actuator 1 speed in MANUAL, Clockwise increase the speed
A2S Set actuator 2 speed in MANUAL, Clockwise increase the speed
A1C Current measurement scaling actuator 1
A2C Current measurement scaling actuator 1
A2T Temperature alarm limit, actuator 2 driver.
SSS Adjustable voltage for teminal X2:1 ( nomally for speedset)
The electrical connections of the DEGO III units are via plug-in terminals. All
terminals except those for the communication are located on the terminal board as
seen in figure below.
XA
XB
X3 XC XD XE
XF
X2 X4 X6 X8
Two power amplifier versions are used: DC or AC supplied, both with DC output for
brush type servo motors. The amplifier is a servo for actuator speed. Thus, the
actuator position control is via a speed control.
When the actuator is exposed to a sudden high load, the current is first rising to the
double maximum continuos current for 2 sec. Thereafter the current is reduced to
the pre-set value. The purpose is to boost acceleration and to enable the actuator to
overcome temporary friction in the fuel pumps or in the fuel rack.
The features of the power amplifier can be adjusted using DIP switches placed under
the cover plate.
Important:
Do not change the factory settings. If for instance a spare amplifier must be set up
use the tables below and follow the instructions in the chapter - Commissioning.
LED for status indikation GREEN= OK
RED=Blocked
ON
1 2 3 4 10 2 1
Potentiometers DIP Switches P1 Control signals 1 2 3 4
LOOP GAIN
The potentiometers placed on the top of the power amplifier have the following
functions:
Potmeter Function
P1 Loop gain
P2 Current limit (for the steady state condition)
P3 Reference in gain. Set in MAX. pos. The gain is adjusted in the
governor software.
P4 Test alt. Offset. Adjust until same speed in both directions in MANUAL
1.2.13 Display unit - Local Reset
An ALARM RESET button connected in parallel with the digital input is located in the
lower right corner. When depressed, no longer active alarms are deleted.
Activated in 10 sec at power up or when the microprocessor reset switch (under the
cover) is depressed twice.
Normal Display Mode is always displayed when power is on and no other mode is
active.
The contrast is adjusted with a potentiometer located under the cover in the upper
left corner. It can be reached from the upper left side.
If mode Start Fuel at Internal Manual and Reset is chosen in the engine set-up, the
fuel rack can be set to start fuel at engine standstill by depressing the RESET button.
1.2.14 Integrated Alarm System And Fault Logger
The individual alarms are identified on line 4 in the integrated LCD display. 18
numbered alarms are listed.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 25
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
Each alarm can have four states. They are identified in the presentation with a prefix
as follows:
[Blank] = No alarm
1 Press Tran OoR = Active, unacknowledged alarm
1*Press Tran OoR = Active acknowledged alarm
1$Press Tran OoR = No longer active unacknowledged alarm
Also the Commissioning Aid or a hand terminal (future option) displays the individual
alarms.
alarm is prevailing and a new alarm is activated, the contact is closing for 1 sec
and then opening again.
Each alarm channel has a two-colour LED. Green in normal condition and red at
alarm state.
The alarm contacts are of opto-coupler type. The principal diagram is shown below:
PTC
Unipolar
100 Ohm
The analog speed setting signal is monitored for interruption. If the current drops
below the adjusted level ( default 2mA), I/D mode is automatically engaged and the
speed setting is frozen on the value at the moment of interruption. A timer for
disconnection of the "freezing" ensures that temporary recoveries (bad contact) are
not taken as a restored connection.
The analog signal is calibrated using the DEGO III Commissioning Aid (window
"Calibration of Analogue Inputs") to match the electronics.
Voltage input or current input can be selected with programming jumpers. See
chapter 1.2.8.
The speedsetting signal is passing a ramp before entering the comparison point in
order to avoid sudden changes.
4-20mA or
0-10V
Analog SCALING RAMP
signal
500 Ohm
To Speed
Increase
control
Decrease
I/D mode
OUT OF RANGE
MONITOR
Alarm
Four independent inputs for speed sensing are provided, channels 1 to 4. Channel 1
and 2 are normally used for the engine speed. Channel 3 is used for the generator
and channel 4 for the propeller in a multi-channel tacho application.
Each channel can be programmed for either NPN or PNP pick-ups with
programming jumpers on the terminal board. See also figure below. Each channel
can be monitored by a green LED. The four channels have independent, short circuit
proof power supplies for the pick ups.
PULL-DOWN PULL-UP
+24V 0V
X:3
+15V
1 PTC
E+
PULSE 2
TRANSM.
C
E- 0V 0V
0V
3
0V
+15V 0V ISOLATED
TERMINAL BOARD PROCESSOR BOARD PART
Channel 1 has a software speed filter designed to filter out irregularities over one
engine turn and still not cause delays at speed changes. In case of malfunction of
channel 1, the filter is automatically switched over to channel 2.
1.3.3 Start Function
The start function ensures a fixed start fuel to the engine during the start program or
at engine reversal. The following parameters can be set in the window Speed
Intervals and Start Program Settings in the DEGO III Commissioning Aid:
Dead Speed The speed value at which the application of fuel takes place
[RPM]
Normal Start Speed The speed value at which the fixed fuel is interrupted and the
normal speed control takes over [RPM]
Heavy Start Speed The speed value at which the fixed fuel is interrupted and the
controller takes over when input X4:8 Bypass limit is
activated [RPM]
Normal Start Fuel The value of the fuel applied between dead speed and start
speed [%]
Heavy Start Fuel The value of the fuel applied between dead speed and start
speed when input X4:8 Bypass limit is activated [%]
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 30
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
Start fuel at Stop Checking this box causes the actuator to give start fuel as
Release: soon as the stop order is released
Start fuel at Reset Checking this box causes the actuator to give start fuel s
soon as the reset order is activated
SPEED FUEL
Engine Speed
SPEED
Dead Speed
Normal Start Speed
Heavy Start Speed
A PID controller structure with fuzzified zone amplifiers is utilised for the normal and
slow mode speed controller.
ENGINE
SPEED SET P- P-
P O-SHOOT
GAIN ZONE
+ TORQUE,
-
ENGINE
D-GAIN D SMOKE FUEL SET
SPEED
LIMIT
I-GAIN I I-LIMIT
1.3.5 P-Gain
The basic adjustment and monitoring of the P-gain is done with the DEGO III
Commissioning Aid in the window Speed Control Loop.
The Slow mode gives a more smooth action of the fuel rack at the cost of a larger
speed variation around the set-point.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 31
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
In the DEGO III Commissioning Aid window P-Gain Amplifier, the P-gain can be
made dependant on both engine speed and -load.
100%
C urve valid at 100% speed
50%
C urve valid at actu al sp eed
0 Fuel
50% 100%
In the DEGO III Commissioning Aid window P-Zone Amplifier the width of the low
gain band can be adjusted for Normal- and Slow Mode respectively.
The P gain is reduced when the speed deviation is zero or near zero.
P Gain
Normal Mode
Slow Mode
Speed Error
Low gain band
1.3.6 Integrator
The basic integrator time constant is set with the Commissioning Aid in window
Speed Control Loop where also the influence from the integrator is shown.
The integrator characteristics are dynamically adjusted by the fuel rack position as
well as the speed. The relationships between engine load, engine speed and
integrator time are set via the DEGO III Commissioning Aid, window Speed Control
Loop.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 32
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
100%
C urve valid at 100% speed
50%
C urve valid at actu al sp eed
0 Fuel
50% 100%
1.3.7 D-Function
D -P art
100%
C urve valid at 100% sp eed
50%
C urve valid at actual speed
0 Fuel
50% 100%
The torque limit is calculated from the current engine speed and current fuel set
information read by the governor.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 33
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
One curve is available for normal operation and one for bypass*). The curves are
graphically set up in the DEGO III Commissioning Aid, window Torque and Integrator
Limit. In this window also a third curve is configured, Integrator limit.
*) Bypass implies increasing of the normal limit value to a separately selected curve.
FUEL
C u r v e v a lid a t b y p a s s
100%
C u r v e tr im h a n d le s
50%
C u r v e v a lid a t n o r m a l m o d e
A c tu a l v a lu e
0 SPEED
50% 100%
Smoke limit is generated as a function of the measured scavenging air pressure and
the current fuel position information. The purpose is to limit the fuel admission to
burn the fuel efficiently with the air available.
One curve is available for normal operation and one for bypass. The curves are
graphically set up in the DEGO III Commissioning Aid, window Smoke Limit.
The input for the charging air transducer is a 4-20mA/0-10V signal. The pressure
scaling of the transducer can be set in window Engine Properties of the DEGO III
Commissioning Aid.
In case the pressure signal is interrupted, an alarm is released and the smoke limit
function is inhibited. The same delay function as described in section Speed Setting.
Speed Setting is preventing an irregular behaviour of the limiter in case of a bad
contact.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 34
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
FU E L
50%
C urve valid at n orm al m ode
Actual Fuel V alue
0 S cav air
2 4.0 B ar
The Integrator Limit curve in the Torque Limit window serves the purpose to stabilise
the engine at very low speed and load when the engine tends to become unstable
due to low inertia.
Since the integrator limit can be set to vary with the speed, the recommendation is to
set the integrator limit to reduce fuel to zero at speeds higher than appr.50%. This
setting ensures prompt fuel reduction to zero at loss of load at high speeds.
I-VALUE
INTEGRATOR BLOCKED
SPEED
The Overshoot Amplification function is an aid to avoid overspeed. When the speed
raises above the nominal speed, the P-gain can be set to increase progressively to a
high value.
The relation Speed - P-gain can be set in the window Over-shoot Amplification in the
DEGO III Commissioning Aid.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 35
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
P -G A IN
100% SPEED
O V E R S P E E D T R IP
The governor has distinct modes of operations (states). These depend on the actual
engine speed, command input states, air pressure etc.
The actual state is displayed in the LCD panel as well as in the yellow information
row in the DEGO III Commissioning Aid. The changes are logged in the event log.
Each state can be set up with its own set of control parameters to optimise the
control in every situation.
1.3.13 Fuel Admission Control Loops
The controllers are of PD type. The actuator forms the integrator function.
ACTUATOR
SET-POINT
OFFSET
FUEL
TRANSM SCALING P
SIGNAL ACTUATOR
CONTROL
SIGNAL
ACTUATOR 0V
D
SPEED
The fuel error after the comparison point is amplified and fed to a summation
amplifier. The actuator speed signal (from the tacho) is amplified and with reversed
sign fed to the same summation amplifier as above (acts as a damping).
The resulting error is amplified, limited and provided with a dead zone. In order to
provide an output signal symmetrical around zero, an adjustable offset is applied.
The signal is fed via an analog output to the power amplifier .
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 36
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
The fuel servo is a four quadrant drive for brush type DC motors with tacho. It is
designed to match the ABB actuators ASAC 20, ASAC 70, ASAC 200 and ASAC
400. The governor is able to control two independent actuators.
The power amplifier is integrated into the control box. All control signals are brought
via a ribbon cable to the terminal board. Inputs for max. and min. position limit
switches are provided.
Manual intervention is made in the MANUAL mode. The servo is then changed to an
open-loop control. The actuator is controlled by increase/decrease pushbuttons.
MANUAL mode is also activated at engine standstill and at critical faults in the fuel
servo loop (slow speed application).
The function principle for the fuel servo loop is presented in the picture below.
INCR.
DECR. MANUAL
TACHO FEEDBACK
+10V
GAIN
POSITION
ADAPT.
TRANSMITTER
CIRCUIT
0V
BRAKE
• DC supplied 24-56V
• AC supplied 110-130V
The DC supplied servo is fed via an isolating switch and a reservoir capacitor, both
are integrated in the governor unit. The reservoir capacitor is ensuring a correct
switching of the PWM signal as well as absorbing the excess voltage at braking of
the actuator.
The AC supplied servo has an integrated rectifier and a shunt resistor. At braking, if
the voltage on the internal DC bus exceeds the max. limit (185V), the shunt resistor
switches in to avoid trip of the amplifier due to over-voltage.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 37
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
It is important that the peak value of the AC supply is below this voltage. If not, the
shunt resistor will burn out.
An appropriate fuse is required in the source end of the supply cable. See further in
Chapter 3 Installation.
In series with the actuator motor, two paralleled mH chokes are inserted. They
smooth out the steep gradients originating from the PWM modulation.
The servo using the current output is wired in accordance with figure 21. Please note
that the control coil is supplied from an external 24V source in series with a 33Ohm
ballast resistor.
If the actuator is lacking a fuel feedback sensor, an internal feedback feature can be
utilised by inserting program jumpers IFB 1 and/or IFB 2.
TERMINAL BOARD
EARTH POWER
FAULT
AMPLIFIER 1
DETECT.
0V POWER GROUND
4700 u F
250mH
MOTOR +
+ 250mH
SERVO
MOTOR
-
MOTOR -
TERMINAL BOARD
EARTH
FAULT
DETECT.
POWER
AMPLIFIER 2
110-130VAC
HIGH VOLTAGE
POWER EMC FILTER
SUPPLY AC -SUPPLY
0V
GROUND
250 mH
MOTOR +
+ 250 mH
SERVO
MOTOR
-
MOTOR -
GROUND
CONTROL
UNIT
33 Ohm LOAD
0-200 mA
+24 V
CONTROL SIGNAL
IFB 1 (2)
FUEL POS. SIGNAL
20 Ohm
0V
0V
• Sulzer engines
• Mitsubishi engines
The DEGO III governor is adapted for all three types. The required engine data is
stored in separate files available from the menu in the Commissioning Aid.
The normally used actuators are ASAC 200 and ASAC 400. The governor control
unit contains an AC supplied power amplifier. For the smaller sizes however, the
ASAC 70 is often sufficient.
• Sulzer engines
• Mitsubishi engines
The DEGO III governor is adapted for all three types. The required engine data is
stored in separate files available from the File menu in the Commissioning Aid.
The normally used actuators are ASAC 200 and ASAC 400. The governor control
unit contains an AC supplied power amplifier. For the smaller sizes however, the
ASAC 70 is often sufficient.
In case none -or only one clutch is engaged, both engines are operated as in a single
engine application.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 41
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
The output from the speed control loop is called fuel set point.
This fuel set point will be linked to both fuel control loops, se picture below.
This means that from the slave governor only the fuel control loop is active PID
controller.
All limit functions (Torque, Smoke, External and Load Balance) are individual for
each engine. See picture below.
As can be seen from above picture, the output from the speed control loop is
controlling both fuel loops in case both clutches are engaged.
“The output from the speed control loop is called “Fuel Set”
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 42
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
1.5.2 Serial communication between the governor Control Units (RS 485).
• The serial communication is needed to send a number of signals between the
Mater and Slave unit to realize the parallel operation.
In case the serial communication is lost, the units will automatically change from the
master/slave mode to speed control mode with speed droop.
Due to the speed droop the engines are load-sharing without communication.
Remarks:
1. The load-sharing is depending from equal parameter setting of both speed
control loops (PID) settings.
2. The performance and accuracy of the load sharing is less.
3. The speed setting have to be the same for both sides.
4. The speed-droop setting have to be set between 4 and 10% and equal.
The ID number for the Port engine is by default “#1” and for the Stbd engine “#2”.
No other settings of the ID switches are allowed in the Twin Engine application.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 43
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
Two modes of load balance can be chosen in the Commissioning Aid window
System Configuration, Options as follows:
Fix setting: (Example: Potentiometer set on 60% for stbd engine, in this case the
load is equal for both engines up to 60%, above 60% the stbd engine load
remains the same and the added load will be carried by the port engine only.
This mode is suitable for running in overhauled engines.
• Proportional setting: In this mode both engines are sharing the load in the set
proportion over the whole load range.
• The load set potentiometer is always connected to the ID1 unit, default Port
engine.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 44
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
1.5.5.2 Un-loading.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 45
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
Un-loading is activated via a digital input, When the signal is removed the unloading
reverts to loading. By activating another digital input, the bypass function is
activated.
The engine remains at the lowest adjusted load until the engine is clutched out or un-
loading is cancelled..
1.5.5.3 Bypass
By activating a digital input, the bypass function is activated. The following
parameters are then altered:
• Loading up time
• Unloading time
• Speed ramp
• Torque limit
• Smoke limit
When the Unload program is ended a digital output “declutch” becomes active.
This signal is normally connected to the “clutch logic’s” that gives finally the decluch
order.
If the pith is not reduced manually when one engine is unloaded, the remaining
engine takes excessive load. The analogue output Available Load on the governor
can be connected to the pitch control system with the purpose to reduce the pitch.
The individual alarms are identified on line 4 in the integrated LCD display. 18
numbered alarms are listed.
Each alarm can have four states. They are identified in the presentation with a prefix
as follows:
[Blank] = No alarm
1 Press Tran OoR = Active, unacknowledged alarm
1*Press Tran OoR = Active acknowledged alarm
1$Press Tran OoR = No longer active unacknowledged alarm
Note: Normally the torque or smoke limits are not applied in the generator set-up,
and set to limit the maximum allowed fuel. If needed they can be adjusted and will
work accordingly.
1.6.1 Droop operation.
ABB will call the droopmode also basic droopmode, this due to the fact that also
droopmode with electrical power measurement exists. This power measurement is
used as a feedforward signal and improves the response.
In basic droop operation the speed setting will decrease with the load of the engine.
Basic speeddroop is without the electrical load measurement as regulating signal.
For basic speeddroop there is no communication between the governor units
needed.
The amount of droop can be adjusted. Typical 4% is sufficient.
Droop mode will be automatically activated in case of a malfunction of the serial
communication (com2) between the units.
The power measurement acts directly on the fuel setpoint as a feed forward. This
regulation method gives a very quick responding. Since the power measuring system
is matched to the fuel servo, the PID part is acting only for small error compensation
in speed and load errors.
Isochronous operation is only possible when the serial communication between the
units is working. If the communication is interrupted, either partly or as a whole, the
affected units are set in (Basic) Droop Mode.
When there is a need to run parallel with non-ABB DEGO III governors, isochronous
mode is normally not suitable. Droop Mode is to prefer instead.
In cases there is a difference between the loadset point and the actual average load
at the time the load control is switched on, a ramp will smoothly transfer the load to
the required loadset point.
The same for canceling the loadcontrol order, after the loadcontrol order is switched
off, the governor stays internally in loadcontrol until the load reaches the same level
as the average load line. Ones this is reached, loadcontrol will be canceled.
The average load is constantly monitored. In case there is a risk for either overload,
or reverse power. The load setpoint(s) for the units(s) in load control is (are)
automatically modified in such a way, that a critical situation is avoided.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 50
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
1.6.3.1 Loading.
As soon the generator breaker is closed, the generator will ramp up to the average
load of the other connected generator(s). As soon as the average load is reached the
generator switches over to the required mode. For this automatic loading, the
generator voltage and current measurement is needed. Two ramp curves are
available. The second curve is valid when the Bypass input is activated.
When the electrical power measurement breaks down, the system can not made any
corrections anymore and the error can grow to 10%.
1.6.3.2 Unloading.
An unload request is usually ordered from the corresponding external input.
2 ramp curves are available. The second ramp is normally set to a short time-base to
unload the engine quickly when Bypass is ordered.
Unloading persists until the minimum load according to the curve is reached, typical
10%
The minimum load is maintained until either the MSB is tripped, or the unload order
is cancelled. In this later case, loading according to the corresponding curve is
resumed.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 51
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
To enable the communication, all units must be given a unique identification number
(1-7). This is made on switch S1, at the right upper corner of the process board.
1.6.6 Speedsetting.
The speedsetting can be either inc/dec or analogue (V or mA).
When the DI is not activated assigned or left open, analogue speedsetting is active.
For inc/dec speed setting the rate of change can be adjusted in the commissioning
aid, a bypass time ramp can be switched on by a DI.
In case of analogue speedsetting failure, automatically the inc/dec speedsetting gets
active.
The speedsetting used for isochronous running can be optional fixed, in this case the
analogue input will be ignored and the speedsetting can not be changed. This is
useful for generator version.
The I/D speedsetting can be optional selected to be true as long the CB isn’t
engaged. Many times synchronization is done by inc/dec signals.
When the CB gets engaged, the system switch over to analogue speedsetting or
fixed speed as long the external I/D order isn’t given.
The minimum speed for I/D mode is normally given by the Start program’s start
speed. Optional (most used) can be chosen for the Low limit value as be given for
the calibration of signals. (I.e. 3V = 50 Rpm, this 50 Rpm is now the lowest limit that
can be reached by I/D signals)
The individual alarms are identified on line 4 in the integrated LCD display. 18
numbered alarms are listed.
Each alarm can have four states. They are identified in the presentation with a prefix
as follows:
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 52
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
[Blank] = No alarm
1 Press Tran OoR = Active, unacknowledged alarm
1*Press Tran OoR = Active acknowledged alarm
1$Press Tran OoR = No longer active unacknowledged alarm
27 Pow Meas Err 27 Pow Meas Err Power measurement error Non Critical
Gen. volt or current interrupt
14 Inter Comm. failure 14 Inter comm failure The inter-communication is lost. Non Critical
RS485 / com 2
15 CB wire break 15 CB wire break Fuel / electric power not Non Critical
corresponding together.
29 AnLdSet Oor 29 AnLdSet Oor The load setting potentiometer Non Critical
or the connections are
interrupted or shorted.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 53
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
* The input can be programmed to replace input X2:2 at confirmed load control.
** The input / output can be programmed to other signals.
*** Un = 18-32 Vdc
The following additional features are provided with the QHFQ 55X unit.
♦ Extra terminals for external use. (doubling to avoid 2 wires in 1 terminal)
♦ Better filtering for the generator voltage / current and the busbar voltage.
Strong harmonics due the electrical propulsion motors.
These filters can be switched on/off and are default adjusted for 50/60 Hz, to
be selected by jumpers,
♦ Relays for memory the latest state in load control.
At lost of PMS, the latest control state maintain.
♦ Fixed I/O arrangement.
As this is a standard concept, the functions are always the same.
In case all commands from a superior control system goes to zero (microprocessor
stall), the governor cluster will remain running as per last order.
This means:
• The unit runs, unless externally given, in isochronous mode.
• As long the CB is open the speedsetting follows the I/D orders. At start of
cancellation of idle speed, the I/D mode gets active after the nominal speed
is reached. (iso speed)
• Isochronous running mode is default when no external orders are given.
• The speed setting in isochronous mode is generated internally in the
governor. ( fixed by the program or by internal analogue supply)
• The unload function is memory backed-up. Puls signals unload on and
unload off are used.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 56
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
• Idle speed at digital 1-signal. This signal is not required from the superior
control. Blocked when the circuit breaker is closed.
• Load control mode by digital 1-order.
• The loadsetpoint can be analogue or by I/D signals.
• I/D loadsetppoint mode by digital 1-order, else analogue loadsetpoint.
• Automatically tracking to avoid “reverse power” or “overload trip”. The load
set point is override internally in cases the isochronous generator(s) are
running to low or too high in load. Tracking values programmable.
• The speed droop mode can be activated at the emergency control.
• Speedsetting in speed droop mode is by increase/decrease orders
The cyclo converter Propulsion Drive causes strong harmonics on the ship’s grid. In
order to enable correct voltage and current measurement, are filters for suppressing
of distortion in the measuring signals provided.
On the interfaceboard is standard a dubble pole filter, this filter needs to be trimmed /
jumpered for 50/60Hz.
1.7.4 Extra hardware.
In order to obtain the additional functionality required for the Diesel Electric
Propulsion application, a special interface board is designed.
This board (QHFQ 220) has special 2 pole filters for the measuring circuits of the
busbar voltage as well as for the generator voltage and current.
Jumpers and trimmers are applied to select 50 or 60 Hz as nominal frequency.
Relays are added as a memory for the last status of the loading on/off order.
The terminal numbering is made the same as for the QHFD 552A units.
Option 48 isn’t listed in the Option window, it will be found in the generator
configuration window.
Not all options are free of charge, some options have to be purchased. Ones the
option is ordered, a unique number will be supplied by ABB to release this optional
function. If 3 options are ordered, 3 passwords are given.
The (QHFQ 210) identity serial number of the microprocessor board is needed to
order the options.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 58
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
The option can be selected from the System Configuration box. To activate one of
these functions, you need to give the corresponding password number.
Reference list, check here if the option is working for your application.
Single engine Twin engine Generator Free option. Included in option module
1 Y N QSOFT OPT2
2 Y N QSOFT OPT3
3 Y N QSOFT OPT4
4 Y Y Y N QSOFT OPT6
5 Y Y Y N QSOFT OPT5
6 Y Y Y Y
7 Y Y N Not available yet
8 Y Y N QSOFT OPT1
9 Y Y Y
10 Y Y N Not available yet
20 Y Y N QSOFT OPT7
21 Y Y Y Y
22 Y Y
23 Y N QSOFT OPT8
40 Y Y
41 Y Y Y Y
42 Y Y Y Y
43 Y Y
44 Y Y
45 Y Y
46 Y Y
47 Y Y
48 Y N QSOFT OPT9
49 Y N Not available yet
50 Y N QSOFT OPT7
51 Y N Not available yet
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 59
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
1.8.3.1 Introduction.
To reduce pollution and saving lubrication oil, engine designers have reduced the
cylinder lubrication. In steady state condition, the cylinder lubrication is sufficient.
However during acceleration and other load variations a specified amount of cylinder
lubrication oil is added in order to avoid extra wear.
The digital terminal output can be selected by the aid. Typical 24V / 60mA
1.8.3.3 Function.
There are 3 low pass filters of the first order to detect the need of switching on the
output. When the level of the 3rd filer exceeds the limit, the output becomes active.
The output stays active for at least the adjusted time.
The value of the filters can easily be monitored by the built- in recorder.
1.8.4.1 Introduction
The engine builder specifies the dual fuel function and adaptation of the software
may be necessary.
The DEGO III has as standard the possibility to install a second (GAS / VIT) actuator
driver. This driver can control either one of the ABB actuators from 70 to 400 NM or
any other DC PM-motor servo with the corresponding data.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 60
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
In case there will be no motorised servo fitted, a 4-20mA output signal is available to
control the customer’s gas control PLC, or any other separate actuator control
equipment.
In case of the M/V Navion Viking, the DEGO III only gives a fuel setpoint to a
sophisticated gas control unit.
This setpoint is the PID regulator output, after the Torque and Smoke limits.
The fuel oil is limited to a minimum level (≈6%) to avoid misfiring, all other fuel
needed to accelerate or maintain the speed will be given by the gas actuator.
The DEGO III has a 4-20mA output to control the gas actuator PLC system. Which
one of the three outputs that shall have this function is selected from the AO
selection box in a window in the DEGO III Commissioning Aid. A password is needed
to do this.
The analogue Fuel limit input can also be selected from the AI configuration box. The
scaling can be selected freely, but it is logical to set 100% = 16.8mA.
The fuel oil can be limited with a 4-20mA input signal to a programmed minimum
level. Wire break will be detected and generate an alarm.
4-20mA 4-20mA=100%-0%
PILOT
FUEL
CONTROL
LIMIT POSITION SERVO
SPEED SETTING
P-GAIN POWER AMPLIFIER
ZONE
P-GAIN
M P-GAIN
RAMP I
D-GAIN POWER
FUNCTION N
+ STAGE
- D-GAIN
I-GAIN
I-GAIN
I/D CURRENT
MODE TRACKING CONTROL
SLOW ADAPTATION
MODE
MAX FUEL
LIMITS
MANUAL
TORQUE SMOKE ACTUATOR
SPEED
SUMMA
SPEED MEASURING FUNCTION
+
ACTIVATIO ACTUATOR
N
WEIGHTIN SPEED
G MANUAL BRAKE
<6%
>1 POS
FILTE FILTE FILTE FILTE
R R R R MONITOR
INTERNAL
FREQUENCY FREQUENCY FREQUENCY FREQUENCY FAILURE ALARM
CONVERTER CONVERTER CONVERTER CONVERTER T
To MAN/B&W
INC. MANUAL MBD Complex Controller
PRESS. 4-20mA = 0-100% Fuelset
PULSE TRANSM.
PICKUPS DEC.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 61
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
1.8.5.1 Introduction
A diesel engine plant including flexible couplings is liable to resonance problems. If a
severe resonance appears within the normal speed range, the corresponding speed
is defined as critical speed. Running at this speed must be avoided and the speed
setting is normally not possible to set within this area.
If the system has a low resonance frequency (about 2-3 Hz) the governor tries to
compensate for the speed variation, however the frequency is too high and instability
will be the result.
It may even happen that the governor amplifies the amplitude of the resonance and
makes the control almost impossible.
The DEGO III governor has 4 speed measuring channels for frequency pickups. The
speed signals shall be picked up the main masses of the plant. The MVT function will
sum the individually scaled signals.
Since masses located on each sides of an elastic part (e.g. an elastic coupling) in the
shafting system are in anti-phase, a summation of the speed signals will create a
smooth speed signal. The influence of each signal can be adjusted
individually.
1.8.5.3 Clutches
It is essential that the involved masses are included in the active system. If a mass
can be clutched out, the signal from that mass shall be contributing only when the
clutch is closed. A position switch connected to a digital input in the governor
arranges this condition. The position switch is often a pressure switch in the clutch,
and the switching level must be adjusted to indicate a safe connection of the mass to
the system. There are two digital inputs specially assigned for this purpose.
At parallel running, the system consists of two engines with one MVT function in
each governor. According to the Master-Slave concept, only the master is controlling
the plant. However, the speed signals for each side are measured only in the
corresponding governor. To include all signals into one measured mean value, the
interconnection via the bus is utilised.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 62
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
The MCT function includes a monitoring function of the coupling. By using two
channels to measure the momentary speed deviation across the coupling, the
dynamic torsion is calculated and thus a value of the stress is obtained. This value is
compared to a pre-set alarm limit to initiate an alarm.
Normally one of these pickups is included in the speed measuring system and the
other is used only for this monitoring function.
1.8.6 I/D low limit = AI low point else start program speed.
In case the increase / decrease signals will be used to control the speed, there will
be a selected minimum speed. This can be :
a) the low limit as used for scaling the analogue speedset input.
In the example the minimum speed is 43 Rpm without bypass and 50 Rpm with
bypass.
1.8.7 Shaft Generator Control
Will be implemented on customer’s request.
1.8.8.1 Introduction
This function prevents the engine from running in a critical speed range that can give
damage to the engine or plant. Only one critical speed range can be adjusted.
The critical speed range can be made active over the complete speed range.
1.8.8.2 Input
The input is the speedset signal, both increase / decrease (digital speedset) and the
analogue speedset are valid for this function.
ABB MARINE ROTTERDAM.
Title : User's Manual. Document no.: 3BNM005401D101 Sheet : 63
Name : DEGO III, Governor unit. Rev : G
Subject : Presentation. Date : 02-11-07
1.8.8.3 Function
The internal speedset signal will be stopped on the border of the critical speed range
when the external speedset is set inside the critical speed range. The speedset (and
speed) remains on the border until the speedset is moved passed the critical speed
range. The internal speed ramp (normal ramp time) will then pass over the critical
area fast.
An alarm is generated when the speed stays more than 30 seconds within the critical
area. This alarm is also active when sailing in manual mode.
Up to 6 adjustable knee-points can be used to limit the fuel in respect to the rpm.
As the engine speed is measured very fast, irregularities within the revolution can be
detected. Especially at periodical disturbances, as for example misfiring, the
amplitude of the vibration at certain conditions could be dangerous.