Вы находитесь на странице: 1из 1

Chapter: 01 Cylinders Page: 1 of 1

Engineering data sheet


Sheet No.: Cylinders UL-FM

Cylinders w. INERGEN
Burst disc
General
This datasheet covers the following articles:
200624-60 Cylinder 80-300 M25 UL
200615-60 Cylinder 50-300 M25 UL
200616-60 Cylinder 80-200 W24 UL

< H2
200610-60 Cylinder 50-200 W24 UL
Complete cylinder w. INERGEN and hand wheel valve for Fire Eater
INERGEN fire extinguishing systems approved by UL & FM.

H1
For other cylinders see Ci-Cylinders.
t
Numbers in the name after Cylinder is:
First number: Water volume of the cylinder

H
Second number: Pressure in bar @15°C
Specifications
See table next page for complete list.
Heights:
H1 = H +100mm
H2 ≤ H +170mm
Material: Steel 34CrMo4
Colour: EN 1089/3
Cylinder: Red (RAL 3000)
Shoulder: Green (RAL 6018)
Standard & approval:
TPED EC1999/36 EN1964-2, π D
Installation
Cylinders must be fixed firmly to wall or floor with suitable brackets.
For installations with nozzles directly at the discharge valve the brackets must be able to support the force
during discharge.
Hand wheel valve must be opened after installation of discharge valve.
Maintenance
Recertification (testing) every 10 years, or as per local authorities having jurisdiction.

Item Valve INERGEN Capacity Pressure Dimensions Mass


@ 15°C @ 21°C @ 15°C @ 21°C Diam. Wall Height Filled
Thread Kg M3 M3 Bar Bar mm mm2 mm < Kg

200624 80-300 M25×1.5 33.1 22.9 23.3 300 310.5 267 7.4 1780 140
200615 50-300 M25×1.5 20.7 14.3 14.6 300 310.5 229 6.2 1515 85
200616 80-200 W24.32 23.8 16.5 16.8 200 206.5 267 7.4 1780 135
200610 50-200 W24.32 14.9 10.3 10.5 200 206.5 229 6.2 1470 70

Document: Cylinders UL-FM.docx Text


1
2
Category: Id: MK 3
UL & FM Ci system Rev:2011.11.17 4
5
6
Vølundsvej 17 7
DK- 3400 Hillerød
Tel +45 7022 2769 8
Fax +45 7023 2769 9