Вы находитесь на странице: 1из 1

Date 1/15/2019 Kruger Ventilation Industries Pte Ltd

Company - No. 17 Tuas Avenue 10


Attention - Singapore 639141
Project -
Reference Tel: +65 6861 1577 Fax: +65 6861 3577
Email: mktg@krugerasia.com

Fan Selection 1200

Fan Type rpm

Unit FSA900/TM (I)


20%
Operating Conditions Ducted
Air Volume 21,400 m³/h 1000 30% 62.7%

60%
Static Pressure 300 Pa 40%

50%
Velocity Pressure 52 Pa
500
Total Pressure 352 Pa
Outlet Velocity 9.26 m/s 800
Fan Total Efficiency 61.6 %
50%
Fan Static Efficiency 52.6 % 450

Fan Speed 312 rpm


Air Temperature 20 °C
600
Altitude 0m 400

Fan Absorbed Power 3.39 kW 40%

Motor Selection
Recommended Motor D132M (4.00 kW) 350

400
Motor Speed 960 rpm
Service Factor 0% 312

30%
Operating Limits
Max. Absorbed Power 15.00 kW
250

Max. Fan Speed 650 rpm 200

Temperature (Min-Max) -20° to 100°C 200


15.0 kW

0.750 kW 11.0 kW
0.370 0.550
kW kW 1.10 kW
7.50 kW
5.50 kW
1.50 kW 4.00 kW
3.00 kW
2.20 kW

0
0 10000 20000 30000 40000 50000 60000
Q - Volume Flow (m³/h)

Hz 63 125 250 500 1k 2k 4k 8k Overall


Lwi(Lin) 88 81 82 84 80 74 68 63 91 dB
Lwi(A) 62 65 73 81 80 75 69 62 84 dB(A)
Lpi(A) 52 54 63 70 69 65 59 51 74 dB(A)
* Sound data is for the inlet side * Sound Pressure Level 1.5m, Room Conditions

Version: 1.17.11.801 (Database: 30) (CLT) Date: 1/15/2019 Time: 2:12 PM