RT2DB
Excitation and voltage regulation system
for synchronous generators
dry type excitation most severe overload
transformer in this case, conditions of the
or from a permanent generator.
Fully digital. magnet exciter (PMG). If
Parameter settings a PMG is used to supply In the cases where the
done by software. the system, its excitation system takes
Self monitoring frequency should be at its supply voltage from
routines. most 100 Hz. the generator terminals
Maintenance free. it may be necessary to
High reliability. The voltage regulation sustain the excitation
Excellent dynamic is achieved by actuating current during a short
performance. on the field winding of circuit on the generator
Strong construction. the exciter machine. terminals in order to
Several guarantee the actuation
communication For the field flashing of protection relays or
protocols available. auxiliary energy is taken protection selectivity.
from the auxiliary power For that reason the
supply (DC or AC). RT2DB excitation
1) Introduction system can also include
The voltage and current a special circuitry for
The RT2DB excitation regulation, the setpoint sustaining the stator
system was developed generation, the actual current of the generator
for excitation and value measuring, the at a certain level in the
voltage regulation of control of the field case of near short
synchronous generators flashing and shutdown circuit.
equipped with rotating processes, as well as
exciters (brushless or the excitation system
DC exciters). monitoring are fully
digital. These functions
In the case of brushless are carried out by a 32
exciters it will result in a bit processor module,
maintenance free power which is plugged in a
generation system. three-phase fully
controlled converter of
The system can be used the series Simoreg DC
not only in hydro but Master.
also in thermal power
plants, in new projects
or as an excellent 2) Power stage
alternative for Fig. 1: The Simoreg DC
refurbishment of old The current rectification Master converter unit.
regulators. is carried out by the self
cooled Simoreg DC
The RT2DB excitation Master unit. The
system can take the thyristors are protected
necessary energy either by monitored ultra-fast
from the terminals of the fuses. The Simoreg
generator being excited, converter is designed
through a three-phase taking into account the
and HAND) act on the 1. Quick acting
3) Configuration of the same power stage. The excitation current
electronics bumpless channel limiter (field forcing
change-over is carried limiter)
The voltage regulation, out by software. 2. Overexcitation limiter
the control and the 3. Underexcitation
monitoring functions of limiter
the excitation system 3.1) Automatic channel 4. Volt/Herz limiter
are carried out by the 5. Stator current limiter
processor module T400 The automatic channel
plugged in the Simoreg corresponds to the When a limiter
converter. The thyristor automatic voltage intervenes an indication
gating and monitoring regulator (AVR), which signal is released.
are implemented by the compares the generator
converter itself. voltage actual value with The software routines
The power supply for the reference value for the limiters run on
the electronics is taken (voltage setpoint) the T400 module.
in a redundant way from adjusted by the power
the excitation plant operator. The AVR possesses an
transformer and from underordinated
the station battery. The actual values of the excitation current
active and reactive regulator. This
power are measured configuration ensures
directly on the generator the system an excellent
terminals through 3 dynamic behavior and
potential transformers simultaneously allows
with secondary voltages limiting the excitation
of 110, 115 or 120 V as current at its maximum
well as 2 current values.
transformers with
secondary current of 1 A power factor (or
or 5 A. reactive power)
regulator is also
The generator voltage included. This additional
Fig. 2: The generator voltage setpoint is digitally regulator allows the
regulation is carried out by generated and can be generator to operate at
the T400 technological board, adjusted in the range any desired power
which is plugged in the 90% to 110% of the factor regarding its
Simoreg unit.
rated generator voltage capability diagram.
The setpoint value is
There are two regulating
During the operation of digitally generated by
channels: AUTOMATIC
the synchronous the T400 module.
(automatic voltage
generator attention must
regulator) and HAND
be paid to its capability
(field current regulation).
diagram. For this reason
the following limiters act
Both regulating
on the AVR:
channels (AUTOMATIC

3
A bumpless channel The excitation cubicle is
change-over from AVR delivered with
to excitation current provisions both for local
regulator and vice-versa control (from the cubicle
can occur at any time. door) and for remote
control (from a central
This is possible thanks control room).
to the follow-up routine,
which ensures that the In the standard version
selected control channel of this cubicle the local
Fig. 3: By means of the Drive
Monitor parametering follows up the settings operation is carried out
software it is also possible to of the other channel. by means of push
record oscillograms of This way both channels buttons on the cubicle
analogical signals. outputs always the door. Alarms and status
same firing angle for the indications are made by
thyristors, what LED signalizations.
3.2) Hand channel guarantees a bumpless
channel change-over at A man-machine
This control channel any time. interface (MMI) is
corresponds to the optionally available to
excitation current Certain failures make the operation of
regulator. It is extremely involving the AVR cause the system easier. This
useful when performing an automatic change- optional device is
tests on the generator. over to the hand equipped with keyboard
In addition the hand channel. A trip signal is and display (LCD).
channel works as a released if failures occur Through this device
stand-by regulator in the hand channel commands can be
allowing continuing of being selected the hand entered and actual
the operation even at channel. system parameters
failures in the AVR. (excitation current and
voltage, generator
The setpoint of the active and reactive
excitation current power, generator
ranges from about 10% voltage, setpoints etc)
up to 110% of the rated can be read out.
excitation current of the
exciter. By taking an
independent power
supply for the excitation
Fig. 4: The regulation and
system the setpoint control software is user
range stretches from friendly, what makes the
zero to 110%. programming and
understanding very easy.

3.3) Channel switch


over and follow-up 3.4) Operation Fig. 5: In order to make die
control operation easier a man-
machine interface can be

4
additionally ordered. The inverter. The field
figure shows one of the polarity inversion
available models (OP17).
causes thus a very
quick reduction of the
There are two
excitation current
standardized types of
towards zero. About 5 s
MMI: a simple one
after introducing inverter
(OP1S) and a more
operation the controller
comfortable one, which
opens the field
can display alarm
contactor. Since the
messages of the
excitation current at this
excitation system in Fig. 6: With the optional time will have already
clear text with indication module OLM the excitation
system can be connected to reached zero, the main
of the time in which the
a PROFIBUS DP contacts of the field
alarm occurred.
communication link using contactor open at no
optical fiber. load condition, what
The RT2DB cubicle can
increases the lifetime of
be connected to the
the device.
superordinated control 4) Instrumentation and
system by means of operation Additionally the RT2DB
normal cabling because
excitation cubicle is also
all of the input and In the standard version equipped with a linear
output signals are of the system the field discharge resistor.
available on terminal following instruments It is used to dissipate
strips as potential-free are installed on the the stored energy of the
contacts. cubicle door: reset exciter field winding in
push-button, signaling emergency situations,
The optional board LEDs to indicate where inverter operation
CBP2 allows the system operational statuses and cannot be ensured any
to be connected to a grouped alarms and more.
communication network push-buttons to enter
using the PROFIBUS commands for the local The RT2DB excitation
DP protocol. operation. system has a
This communication link
suppressor device in
can be optionally built In the case the optional parallel to its DC output,
using optical fiber. In MMI is ordered neither in order to protect the
this case the optional push-buttons nor thyristors and the field
module OLM has to be signaling LEDs are winding against induced
ordered. supplied. overvoltages.
Other communication
protocols are optionally 5) De-excitation and 6) Mechanical features
available. overvoltage protection
The excitation cubicle
At normal conditions de- has the following
excitation is carried out approximate
by forcing the thyristor dimensions:
bridge to operate as
5
Width: 600 mm be installed in a client’s
Depth: 800 mm existing cubicle saving 8) Optional features
Height: 2200 mm thus the costs of an
additional cubicle. The following devices
The cubicle has only can be additionally
front door. Cables inlet ordered:
and outlet are made
from the bottom. - Man-machine
interface;
The cubicle is - Rotating diode
constructed with 1.9 mm monitoring (for
dick steel sheets. The brushless generators);
supporting frames are - Communication board
made of 2.5 mm dick for PROFIBUS DP link;
steel sheets. - Communication port
for other protocols;
Fig. 7: The Simoreg DC
The cubicle wiring uses - Redundancy in the
Master converter includes the
self extinguishing electronics for controlling and power stage (in this
copper conductors monitoring the fully controlled case two automatic
insulated for 750V. three-phase rectifier bridge. channels are supplied,
All conductors have each one with its own
identification rings at rectifier bridge, i.e. two
both ends. independent Simoreg
DC Master units are
Each one of the devices supplied);
has identification tags - Compounding circuitry
with the device symbol for sustaining the
according to the generator current during
electrical diagrams. near short circuit.
Each device can be
easily accessed.

The protection degree is


IP41.

7) Optional frame
assembly

As an economical
alternative all the low
voltage parts of the Fig. 8: As an economical
RT2DB excitation solution the RT2DB excitation
system can also be supplied
system can be supplied
on a steel sheet to be housed
assembled on a steel in a client’s existing cubicle.
sheet (frame) sized 800
x 1200 mm (see Fig. 8).
This way the system can
6
Fig. 9: General diagram of the RT2DB excitation system

7
General technical data of the RT2DB digital excitation system
Maximum excitation current Up to 20 A DC
Maximum ceiling voltage Up to 600 V DC
Voltage for control and interfacing From station battery
Auxiliary voltage for field flashing Power plant auxiliary power supply (AC or DC); current
consumption: 2 A typ. during max 10 s (depends on
generator data).
Connection to potential transformers 3 x PT’s; secondary voltage: 110, 115 or 120 V (“V
connection” is allowed ); power consumption: 10 VA per
phase.
Connection to current transformers 2 x CT’s; secondary current: 1 or 5 A; power
consumption: 10 VA per phase.
Regulator Fully digital; double channel configuration: Auto
Channel (AVR) and Hand Channel (excitation current
regulator).
Limiters · Quick acting excitation current limiter
· Overexcitation limiter
· Underexcitation limiter
· Stator current limiter
· V/Hz limiter
Power supply for the regulator Redundant configuration: from the excitation
electronics transformer and from the station battery.
Setpoint range · Generator voltage: 90% ... 110% (typical)
· Excitation current: 10% ... 110%
Rectifier Fully controlled thyristor bridge (6 pulses), self cooled,
continuous DC output current: 30 A DC.
Power requirements from the station Interfacing and control circuits: max. 100 W
battery Regulator redundant power supply: max. 250 W
Dimensions 600 x 800 x 2200 mm (W x D x H)
Approximate weight 300 kg
Protection degree of the cubicle IP 41
Finish color Grey Munsell N6.5 or according to customer’s
specifications.
Dimensions of the steel sheet in the 791 x 1200 mm
case of frame assembly
Standard interfaces Conventional wiring (potential-free contacts)
Output signals (4 ... 20 mA) for remote · Excitation current
indication · Voltage setpoint

For more information please contact:

Siemens Ltda.
Rua Werner Siemens, 111
05069-900 Lapa São Paulo, SP
Tel: (11) 3833-4052 / 4106 / 4098 FAX: (11) 3833-4189
Internet: www.siemens.com.br/excitacao

E-mails: sebastiao.carpi@siemens.com
jorge.humberto@siemens.com

Issue: July 2006