Supervisor de Temperatura para Transformadores com

Óleo TS

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


1
Supervisor de Temperatura para Transformadores com
Óleo TS

SUMÁRIO

1 ASSISTÊNCIA TÉCNICA .................................................................................. 3

2 HISTÓRICO DE REVISÕES............................................................................... 3

3 PROTOCOLO MODBUS RTU ............................................................................. 4

4 PROTOCOLO DNP 3.0 .................................................................................... 9

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


2
Supervisor de Temperatura para Transformadores com
Óleo TS

1 Assistência Técnica
As informações deste documento permitem que todas as leituras, seleções e comandos do
TS sejam efetuados por meio da porta de comunicação serial RS485 (opcional). Estão disponíveis
os protocolos Modbus RTU e DNP3.0 nível 1.

Para obter assistência técnica para o TS ou qualquer outro produto Treetech, entre em
contato através do endereço abaixo:

Treetech Sistemas Digitais Ltda. – Assistência Técnica


Rua José Alvim, 100 – Salas 03 e 04 – Centro
Atibaia – São Paulo – Brasil
CEP: 12.940-800
CNPJ: 74.211.970/0002-53
IE: 190.159.742.110
TEL: +55 (11) 2410-1190 x201
FAX: +55 (11) 2410-1190 x702
Email: suporte.tecnico@treetech.com.br
Site: http://www.treetech.com.br

2 Histórico de Revisões
Revisão Data Descrição Feito por
João Victor
1.00 31/07/2015 Emissão Inicial
Miranda
João Victor
1.10 03/11/2015 Atualização para o firmware 1.13
Miranda

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


3
Supervisor de Temperatura para Transformadores com
Óleo TS

3 Protocolo Modbus RTU

Protocolo: Modbus
Modo: RTU (binário)
Taxa de transmissão: 4.800, 9.600, 19.200 ou 38.400, 57.600 ou 115.200bps
Bits de dados: 8
Bits de parada: 2
Paridade: Nenhuma
Tipo de variável de memória: Holding Registers
03 (Leitura, em blocos ou individualmente)

Comandos implementados: 06 (Escrita em um único registrador)

16 (Escrita em um bloco de registradores)


Base de Endereçamento: Base 1 (PLC Address): O endereço dos dados inicia em 1
Aplicável à versão de firmware: 1.13

Mapa de Registradores TS (Versão 1.13)


Registrador Bit Descrição Faixa de Medição ou Estado Passo Escrita ou Leitura

01 - Parâmetro -55...200 1 E/L


ALMO
02 - Parâmetro -55...200 1 E/L
DSLO
03 - Parâmetro 0...20 0,1 E/L
RDSO
04 - Parâmetro -55...200 1 E/L
ALME
05 - Parâmetro DSLE -55...200 1 E/L
06 - Parâmetro RDSE 0...20 0,1 E/L
07 - Parâmetro IDI 0= Português 1 E/L
1= Inglês
2= Espanhol
08 - Parâmetro RTDS 1...3 1 E/L
09 - Parâmetro DISP 0= Fixo 1 E/L
1= rolagem
2= Máxima
10 - Parâmetro ALO 0...4 1 E/L
11 - Parâmetro DSO 0...4 1 E/L
12 - Parâmetro ALE 0...4 1 E/L
13 - Parâmetro DSE 0...4 - E/L
14 0 Parâmetro RL1 0 = Normal - E/L
1 = Invertido
1 Parâmetro RL2 0 = Normal - E/L
1 = Invertido
2 Parâmetro RL3 0 = Normal - E/L
1 = Invertido
3 Parâmetro RL4 0 = Normal - E/L
1 = Invertido

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


4
Supervisor de Temperatura para Transformadores com
Óleo TS
15 - Parâmetro 0= Óleo 1 E/L
VSAN 1= Enrol.
2= RTD2
3= RTD3
4= Máxima
16 - Parâmetro FSAN 0= 0-1mA 1 E/L
1= 0-5mA
2= 0-10mA
3= 0-20mA
4= 4-20mA
17 - Parâmetro FESA -55...200 1 E/L
18 - Parâmetro IESA -55...200 1 E/L
19 - Parâmetro GEO -50...50 1 E/L
20 - Parâmetro TE 1...999 1 E/L
21 - Parâmetro HS+ 0...20 0,1 E/L
22 - Parâmetro HS* 1...1,50 0,01 E/L
23 - Parâmetro 2*M 0=1.6 - E/L
1=1.8
2=2.0
24 - Parâmetro CNT 0...99,98 0,01 E/L
25 - Parâmetro CNS 0...10 0,01 E/L
26 - Parâmetro RF1 -55...200 1 E/L
27 - Parâmetro RF2 -55...200 1 E/L
28 - Parâmetro HIS 0...9 - E/L
29 - Parâmetro ALT 0 = desligado 1 E/L
1 = ligado
30 - Parâmetro CV1 10...200 1 E/L
31 - Parâmetro CV2 10...200 - E/L
32 - Parâmetro HIC 1...9 1 E/L
33 - Parâmetro EVH 0...23 1 E/L
34 Parâmetro EVM 0...59
35 - Parâmetro TEV 1...100 1 E/L
36 - Parâmetro 1...20 1 E/L
HLOG
37 - Parâmetro 1...120 1 E/L
TLOG
38 - Parâmetro 0= Sem ação - E/L
RLOG 1=Resetar log
39 - Parâmetro MES 1...12 - E/L
40 - Parâmetro DIA 1...31 - E/L
41 - Parâmetro ANO 05...99 - E/L
42 - Parâmetro 0..23 - E/L
HORA
43 - Parâmetro MIN 0...59 - E/L
44 - Modo de 0=automático - E/L
operação do 1 =manual
grupo de
resfriamento
RF1
45 - Modo de 0=automático - E/L
operação do 1 =manual
grupo de

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


5
Supervisor de Temperatura para Transformadores com
Óleo TS
resfriamento
RF2
46 - Reset memória 0=off - E/L
de erros 1=reset
47 - Parâmetro TCR1 0=óleo - E/L
1=enrolamento
48 - Parâmetro TCR2 0=óleo - E/L
1=enrolamento
49 - Parâmetro ATIV 0=off - E/L
1=on
2=automático
50 - Parâmetro VIDA 1…60 1 E/L
51 - Parâmetro BALI -999…999 1 E/L
52 - Parâmetro ABAL 0…999 1 E/L
53 - Parâmetro 0…200 1 E/L
LMAX
54 - Parâmetro 0…200 1 E/L
LMIN
55 - Parâmetro KP 0…9,999 0,001 E/L
56 - Parâmetro KI 0…9,999 0,001 E/L
57 - Parâmetro KD 0…9,999 0,001 E/L
58…69 - Reservado - - E/L
1001 - Temperatura -55...200 0,1 L
óleo
1002 - Temperatura -55...200 0,1 L
enrolamento
1003 - Temperatura -55...200 0,1 L
RTD2
1004 - Temperatura -55...200 0,1 L
RTD3
1005 - Temperatura -55...200 0,1 L
máxima
atingida pelo
óleo
1006 - Temperatura -55...200 0,1 L
máxima
atingida pelo
enrolamento
1007 - Temperatura -55...200 0,1 L
máxima
atingida pelo
RTD2
1008 - Temperatura -55...200 0,1 L
máxima
atingida pelo
RTD3
1009 - Gradiente Final -55...55 0,01 L
de Temperatura
(GFN)
1010 - Percentual de 0...100 0,1 L
carga (%)
1011 - Corrente lida 0...10 0,01 L
nosecundário do
TC (AMP)

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


6
Supervisor de Temperatura para Transformadores com
Óleo TS
1012 - Corrente do 0...99,98 0,01 L
transformador
(kA)
1013 0 Estado do Relé 0 = desligado - L
da R.F.1 1 = ligado
1 Estado do Relé 0 = desligado - L
da R.F.2 1 = ligado
2 Estado do Relé 0 = desligado - L
de 1 = ligado
Autodiagnóstico
4 Estado do Relé 1 0 = desligado - L
1 = ligado
5 Estado do Relé 2 0 = desligado - L
1 = ligado
6 Estado do Relé 3 0 = desligado - L
1 = ligado
7 Estado do Relé 4 0 = desligado - L
1 = ligado
1014 - Variável de * - L
erros
1015 0 Opcional RTDs 0 =não disp. - L
adicionais 1 =disponível
1 Opcional Saída 0 =não disp. - L
Analógica 1 =disponível
2 Opcional 0 =não disp. - L
Comunicação 1 =disponível
Serial RS485
3 Não utilizado - - L
4 Opcional 0 =não disp. - L
Memória de 1 =disponível
Massa
5 Opcional Pré- 0 =não disp. - L
resfriamento 1 =disponível
6 Opcional 0 =não disp. - L
Exercício de 1 =disponível
ventiladores
7 Não utilizado - - L
1016 0 Alarme 0= não atuado - L
temperatura do 1= atuado
enrolamento
1 Alarme 0= não atuado - L
temperatura do 1= atuado
óleo
2 Desligamento 0= não atuado - L
temperatura do 1= atuado
enrolamento
3 Desligamento 0= não atuado - L
temperatura do 1= atuado
óleo
4 Não utilizado - - L
5 Não utilizado - - L
6 Não utilizado - - L
7 Não utilizado - - L
1017 - Ponteiro do LOG 2000...16384 - L
1018 - Reservado - - L

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


7
Supervisor de Temperatura para Transformadores com
Óleo TS
1019 - Memória de - L
autodiagnóstico
1020 - Valor de carga - L
em relação ao
parâmetro
CMIN
1021 - Valor novo para - L
acionamento do
primeiro estágio
1022 - Balanço de vida Em dias na tela de consulta, - L
– parte alta em segundos no registrador
1023 - Balanço de vida Em dias na tela de consulta, - L
- parte baixa em segundos no registrador
1024 - Reservado -
1025 - Número de série - L
1
1026 - Número de série - L
2
1027 - Tempo de - L
retardo para
desligamento
de enrolamento
1028 - Tempo de - L
retardo para
desligamento
de óleo

Observações:
* O valor informado corresponde ao mesmo código de erro apresentado no display do TS em
formato hexadecimal.

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


8
Supervisor de Temperatura para Transformadores com
Óleo TS

4 Protocolo DNP 3.0

DNP V3.0
DEVICE PROFILE DOCUMENT

This document is accompanied by table 1, Supported DNP 3.0 Objects, Function Codes, and

Qualifiers, and table 2, Point List.

Vendor Name: TreeTech Sistemas Digitais

Device Name: Supervisor de Temperatura TS

Highest DNP Level Supported: Device Function:

For Requests: Level 1 Master Remote

For Responses: ______

Notable Objects, functions, and/or qualifiers supported in addition to highest DNP Levels Supported:

 Reads of Binary Inputs (Object 01, Variation 01, Qualifier 00, 01 and 06)

 Reads of 16-bit Analog Inputs (Object 30, Variation 04, Qualifier 00, 01 and 06)

GENERAL INFORMATION:

Maximum Data Link Frame Size (octets): Maximum Application Frame Size (octets):

Transmitted: 292 Transmitted: 500

Received: (must be 292) Received: 200

Maximum Data Link Re-tries: Maximum Application Layer Re-tries:

None None

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


9
Supervisor de Temperatura para Transformadores com
Óleo TS

Fixed at ___ Configurable, range ___ to ___

Configurable, range 0 to 255 (Fixed is not permitted)

Requires Data Link Layer Confirmation:

Never

Always

Sometimes If Sometimes, when? ______________________________

Configurable as: __________________________________________

Requires Application Layer Confirmation:

Never

Always (Not recommended)

When reporting Event Data (Slave devices only)

When sending mult-fragment responses (Slave devices only)

Sometimes: If ‘Sometimes’, when? __________________________________________

Configurable: If ‘Configurable’, how? _________________________________________

Timeouts while waiting for:

Fixed at _____ Variable Configurable*


Data link confirm: None

Complete Appl. Fragment: None Fixed at _____ Variable Configurable*

Application Confirm: None Fixed at _____ Variable Configurable*

Complete Appl. Response: None


Fixed at _____ Variable Configurable*
Others: ______________________________________________________________________

*Attach explanation if ‘Variable’ or ‘Configurable’ was checked for any timeout

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


10
Supervisor de Temperatura para Transformadores com
Óleo TS

Sends/Executes Control Operations:

WRITE Binary Outputs: Never Always Sometimes Configurable


SELECT/OPERATE: Never Always Sometimes Configurable
DIRECT OPERATE: Never Always Sometimes Configurable

DIRECT OPERATE-No ACK: Never Always Sometimes Configurable

Count > 1: Never Sometimes Configurable


Always
Pulse On: Never Sometimes Configurable
Always
Pulse Off: Never Sometimes Configurable
Always
Sometimes Configurable
Latch On: Never Always
Sometimes Configurable
Latch Off: Never Always

Queue: Never Sometimes Configurable


Always
Clear Queue: Never Always Sometimes Configurable

Attach explanation if 'Sometimes' or 'Configurable' was checked for any operation.

FILL OUT THE FOLLOWING ITEM FOR MASTER DEVICES ONLY:

Expects Binary Input Change Events:

Either time-tagged or non-time-tagged for a single event.

Both time-tagged and non-time-tagged for a single event.

Configurable (Attach explanation)


FILL OUT THE FOLLOWING ITEMS FOR REMOTE DEVICES ONLY:

Default Status Object/Variation: Default Analog Object/Variation:

No Status objects reported No Analog objects reported

Configurable (attach explanation) Configurable (attach explanation)

Default Static Object_____________ Default Static Object______________

Default Static Variation __________ Default Static Variation ___________

Default Event Object_____________ Default Event Object______________

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


11
Supervisor de Temperatura para Transformadores com
Óleo TS

Default Event Variation __________ Default Event Variation ___________

Point-by-point list attached Point-by-point list attached

Default Counter Object/Variation: Counters Roll Over at:

No Counters reported No Counters Reported

Configurable (attach explanation) Configurable (attach explanation)

Default Static Object____________ 16 Bits

Default Static Variation__________ 32 Bits

Default Event Object____________ Other Value _________

Default Event Variation _________ Point-by-point list attached

Point-by-point list attached

Default Frozen Counter Object/Variation: Counters frozen by means of:

No Frozen Counters reported No Frozen Counters reported

Configurable (attach explanation) Remote device time based

Default Static Object____________ Fixed time

Default Static Variation__________ Configurable; range _____ to _____

Default Event Object____________ Master Request (see implementation table)

Default Event Variation __________ Both

Point-by-point list attached

Analog Deadbands: Configuring Analog Deadbands:

Fixed Not Applicable

Configurable: ____ Configuration Software

Per Point Using Object 34 from the master station

Per Analog Type Both configuration software and Object 34

Global

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


12
Supervisor de Temperatura para Transformadores com
Óleo TS

Are the updated deadband values preserved through a device reset:

YES

NO

The number of multiple objects allowed in a single read request message:

Number of multiple objects allowed: 3

Ability to DISABLE/ENABLE DNP database points: IIN 1-6 Device Trouble Bit:

Not Applicable Never used


Per point Reason for setting:
Per object

Global

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


13
Supervisor de Temperatura para Transformadores com
Óleo TS

Time Sync Information:

Time Sync Period:

Never

Fixed at ______ seconds

Configurable, range ______ to _______ seconds

Only at IED startup

a) Maximum time base drift over a 10 minute interval: _________ ms

b) Maximum Internal Time Reference Error when set via DNP: _________ ms

c) Maximum Delay Measurement error: _________ ms

d) Maximum Response time: _________ ms

e) Event data time-tag error – if different than ( c ) :

Binary Input Change Events _________ ms


Counter Change Events __________ ms
Frozen Counter Change Events __________ ms

Analog Change Events __________ ms

Frozen Analog Change Events __________ ms

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


14
Supervisor de Temperatura para Transformadores com
Óleo TS

Sends/Executes Digital Control Operations:

SELECT/OPERATE* Never Always Sometimes Configurable

DIRECT OPERATE* Never Always Sometimes Configurable

DIRECT OPERATE – NO ACK* Never Always Sometimes Configurable

*Attach explanation if ‘Sometimes’ or ‘Configurable’ was checked for any operation.

*To support control operations and conform to the Subset Definitions, either ‘Always’ or ‘Configurable’ must
be selected.

Count > 1 Never Always Sometimes Configurable

Pulse On Never Always Sometimes Configurable

Pulse Off Never Always Sometimes Configurable

Latch On Never Always Sometimes Configurable

Latch Off Never Always Sometimes Configurable

Trip/Close Never Always Sometimes Configurable

Raise/Lower Never Always Sometimes Configurable

Queue Never Always Sometimes Configurable

Clear Queue Never Always Sometimes Configurable

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


15
Supervisor de Temperatura para Transformadores com
Óleo TS

Sends/Executes Analog Control Operations:

SELECT/OPERATE* Never Always Sometimes Configurable

DIRECT OPERATE* Never Always Sometimes Configurable

DIRECT OPERATE – NO ACK* Never Always Sometimes Configurable

*Attach explanation if ‘Sometimes’ or ‘Configurable’ was checked for any operation.

*To support control operations and conform to the Subset Definitions, either ‘Always’ or ‘Configurable’ must
be selected.

Queue Never Always Sometimes Configurable

Clear Queue Never Always Sometimes Configurable

The maximum number of objects supported in a single control request for objects 12 and 41.

Number of objects allowed for object 12: 1

Number of objects allowed for object 41: 1

Control Points per address:


Do all indices support the same control codes:

Configurable
YES – Controls codes 3 and 4
1 control point per address
NO – attached points list stating configuration
2 control points per address ability and supported control codes per point or group
of points

Maximum Select/Execute Delay Time: Ability for REMOTE/LOCAL control mode:

Not Applicable Not Applicable

Fixed at _____ seconds Per point

Configurable, range ______ to ______ seconds Per object

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


16
Supervisor de Temperatura para Transformadores com
Óleo TS

Global

Sends Unsolicited Responses: Sends Static Data in Unsolicited Responses:

Never Never

Configurable (attach explanation) When Device Restarts

Only certain objects When Status Flags Change

Sometimes (attach explanation)

*No other options permitted.

ENABLE/DISABLE Unsolicited: Minimum number of events and/or minimum time


before transmission of an unsolicited message.

Not Supported

Configurable # of events:__________

Function codes 20,21 supported min. amount of time(msec) :___________

Assign Class Function code supported: Is the Event Buffer size configurable:

NO NO fixed size: _______

YES YES: range: _________to_________

Per Object

Per Point Configurable Per Class buffer:

Configurable

NO

YES

Are the updated ENABLE/DISABLE unsolicited settings Are the updated Assign Class settings saved through a
saved through a device reset: device reset:

YES YES

NO NO

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


17
Supervisor de Temperatura para Transformadores com
Óleo TS

Supports Collision Avoidance:

Never

Always (attach explanation)

Configurable (attach explanation)

Source Address Filtering:

Not Supported

Configurable (attach explanation)

Supports Multi-drop communications: Yes No

Sends Multi-Fragment Responses: Yes No

Tabela 1: Supported DNP 3.0 Objects, Function Codes, and Qualifiers

REQUESTS RESPONSES
OBJECTS
(slave will parse) (master must parse)

Function Qualifier Function Qualifier


Object Variation Description
Codes Codes(hex) Codes Codes(hex)

01 02 Binary Input with flag 01 00, 06 00, 129 00, 01

10 02 Binary Output 01, 02 00, 06 00, 129 00, 01

12 01 Control Relay Output Block 05, 06 17, 28 00, 129 Echo

30 02 16 bit Analog Input with flag 01 06 00, 129 00, 01

40 02 16 bit Analog Output Status 01 06 00, 129 00, 01

41 02 16-bit Analog Output Block 05, 06 17, 28 00, 129 Echo

50 01 Time and Date – Absolute time 01, 02 07 01, 02 07

60 01 Class 0 Data 01 06 129 00, 01

60 02 Class 1 Data 01 06 129 00, 01

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


18
Supervisor de Temperatura para Transformadores com
Óleo TS

60 03 Class 2 Data 01 06 129 00, 01

60 04 Class 3 Data 01 06 129 00, 01

80 01 Internal Indications 02 00, index=7 129 -

- - Cold Restart 13 - 129 -

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


19
Supervisor de Temperatura para Transformadores com
Óleo TS

Table 2: Point List

Default Static / Event


Description Index Variation Scale Point Name
Object Var. Description

Binary output 0…2 12 01 No status Reservado

Modo de operação do Relé


Binary output 3 12 01 No status - programável 1. 0=Normal /
1=Invertido

Modo de operação do Relé


Binary output 4 12 01 No status - programável 2. 0=Normal /
1=Invertido

Modo de operação do Relé


Binary output 5 12 01 No status - programável 3. 0=Normal /
1=Invertido

Modo de operação do Relé


Binary output 6 12 01 No status - programável 4. 0=Normal /
1=Invertido

Binary output 7 12 01 No status - Reservado

Parâmetro ALT. 0=Desliga / 1=


Binary output 8 12 01 No status -
Liga

Binary output 9…15 12 01 No status - Reservado

Modo de operação do grupo RF1


Binary output 16 12 01 No status -
0=Automático / 1=Manual

Binary output 17…23 12 01 No status - Reservado

Modo de operação do grupo RF2


Binary output 24 12 01 No status -
0=Automático / 1=Manual

Binary output 25…31 12 01 No status - Reservado

Binary output 32 12 01 No status - Reset Memória de erros

Binary output 33…39 12 01 No status - Reservado

Binary output 40 12 01 No status - Reset temperatura máxima óleo

Reset temperatura máxima


Binary output 41 12 01 No status -
Enrolamento

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


20
Supervisor de Temperatura para Transformadores com
Óleo TS

Binary output 42 12 01 No status - Reset temperatura máxima RTD2

Binary output 43 12 01 No status - Reset temperatura máxima RTD3

Analog output
0 41 02 16-bit - Parâmetro ALMO
block

Analog output
1 41 02 16-bit - Parâmetro DSLO
block

Analog output
2 41 02 16-bit 1x10 Parâmetro RDSO
block

Analog output
3 41 02 16-bit - Parâmetro ALME
block

Analog output
4 41 02 16-bit - Parâmetro DSLE
block

Analog output
5 41 02 16-bit 1x10 Parâmetro RDSE
block

Parâmetro IDI

Analog output 0= Português


6 41 02 16-bit -
block 1= Inglês

2= Espanhol

Analog output
7 41 02 16-bit - Parâmetro RTDS
block

Parâmetro DISP

Analog output 0= Fixo


8 41 02 16-bit -
block 1= rolagem

2= Máxima

Analog output
9 41 02 16-bit - Parâmetro ALO
block

Analog output
10 41 02 16-bit - Parâmetro DSO
block

Analog output
11 41 02 16-bit - Parâmetro ALE
block

Analog output
12 41 02 16-bit - Parâmetro DSE
block

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


21
Supervisor de Temperatura para Transformadores com
Óleo TS

Parâmetro VSAN

0= Óleo

Analog output 1= Enrolamento


13 41 02 16-bit -
block 2= RTD2

3= RTD3

4= Máxima

Parâmetro FSAN

0= 0-1mA

Analog output 1= 0-5mA


14 41 02 16-bit -
block 2= 0-10mA

3= 0-20mA

4= 4-20mA

Analog output
15 41 02 16-bit - Parâmetro FESA
block

Analog output
16 41 02 16-bit - Parâmetro IESA
block

Analog output
17 41 02 16-bit 1x10 Parâmetro GEO
block

Analog output
18 41 02 16-bit - Parâmetro TE
block

Analog output
19 41 02 16-bit 1x10 Parâmetro HS+
block

Analog output
20 41 02 16-bit 1x100 Parâmetro HS*
block

Parâmetro 2*M

Analog output 0=1.6


21 41 02 16-bit -
block 1=1.8

2=2.0

Analog output
22 41 02 16-bit 1x100 Parâmetro CNT
block

Analog output
23 41 02 16-bit 1x100 Parâmetro CNS
block

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


22
Supervisor de Temperatura para Transformadores com
Óleo TS

Analog output
24 41 02 16-bit - Parâmetro RF1
block

Analog output
25 41 02 16-bit - Parâmetro RF2
block

Analog output
26 41 02 16-bit - Parâmetro HIS
block

Analog output
27 41 02 16-bit - Parâmetro CV1
block

Analog output
28 41 02 16-bit - Parâmetro CV2
block

Analog output
29 41 02 16-bit - Parâmetro HIC
block

Analog output
30 41 02 16-bit - Parâmetro EVH
block

Analog output
31 41 02 16-bit - Parâmetro EVM
block

Analog output
32 41 02 16-bit - Parâmetro TEV
block

Analog output
33 41 02 16-bit - Parâmetro HLOG
block

Analog output
34 41 02 16-bit - Parâmetro TLOG
block

Parâmetro RLOG
Analog output
35 41 02 16-bit - 0= Sem ação
block
1=Resetar log

Analog output
36 41 02 16-bit - Parâmetro MES
block

Analog output
37 41 02 16-bit - Parâmetro DIA
block

Analog output
38 41 02 16-bit - Parâmetro ANO
block

Analog output
39 41 02 16-bit - Parâmetro HORA
block

Analog output
40 41 02 16-bit - Parâmetro MIN
block

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


23
Supervisor de Temperatura para Transformadores com
Óleo TS

Analog output
41 41 02 16-bit - Parâmetro TCR1
block

Analog output
42 41 02 16-bit - Parâmetro TCR2
block

Analog output
43 41 02 16-bit - Parâmetro ATIV
block

Analog output
44 41 02 16-bit - Parâmetro VIDA
block

Analog output
45 41 02 16-bit - Parâmetro BALI
block

Analog output
46 41 02 16-bit - Parâmetro ABAL
block

Analog output
47 41 02 16-bit - Parâmetro LMAX
block

Analog output
48 41 02 16-bit - Parâmetro LMIN
block

Analog output
49 41 02 16-bit - Parâmetro KP
block

Analog output
50 41 02 16-bit - Parâmetro KI
block

Analog output
51 41 02 16-bit - Parâmetro KD
block

Analog output
52 41 02 16-bit - Parâmetro CMIN
block

Analog output
53…58 41 02 16-bit - Reservado
block

Analog output
59 41 02 16-bit - Parâmetro PWD
block

Analog output
60 41 02 16-bit - Parâmetro LINT
block

Analog output
61 41 02 16-bit - Parâmetro STEP
block

Analog output
62 41 02 16-bit - Parâmetro TREF
block

Analog output
63 41 02 16-bit - Parâmetro VREF
block

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


24
Supervisor de Temperatura para Transformadores com
Óleo TS

Analog output
64 41 02 16-bit - Parâmetro HLV
block

Analog input 0 30 04 Without flag 1x10 Temperatura óleo

Analog input 1 30 04 Without flag 1x10 Temperatura enrolamento

Analog input 2 30 04 Without flag 1x10 Temperatura RTD2

Analog input 3 30 04 Without flag 1x10 Temperatura RTD3

Temperatura máxima atingida


Analog input 4 30 04 Without flag 1x10
pelo óleo

Temperatura máxima atingida


Analog input 5 30 04 Without flag 1x10
pelo enrolamento

Temperatura máxima atingida


Analog input 6 30 04 Without flag 1x10
pelo RTD2

Temperatura máxima atingida


Analog input 7 30 04 Without flag 1x10
pelo RTD3

Gradiente Final de Temperatura


Analog input 8 30 04 Without flag 1x100
GFN

Analog input 9 30 04 Without flag 1x10 Percentual de carga

Analog input 10 30 04 Without flag 1x100 Corrente lida no TC (A)

Analog input 11 30 04 Without flag 1x100 Corrente do transformador (kA)

Analog input 12 30 04 Without flag 1x100 Memória de erro

Analog input 13 30 04 Without flag 1x100 Ponteiro do Log

Analog input 14 30 04 Without flag 1x100 Reservado

Temperatura final do setpoint do


Analog input 15 30 04 Without flag 1x100
primeiro estágio de resfriamento

Analog input 16 30 04 Without flag 1x100 Balanço de vida

Analog input 17 30 04 Without flag 1x100 Balanço de vida

Analog input 18 30 04 Without flag 1x100 Reservado

Analog input 19 30 04 Without flag 1x100 Reservado

Analog input 20 30 04 Without flag 1x100 Número de série 1

Analog input 21 30 04 Without flag 1x100 Número de série 2

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


25
Supervisor de Temperatura para Transformadores com
Óleo TS

Analog input 22 30 04 Without flag 1x100 Versão de firmware

Tempo de retardo de
Analog input 23 30 04 Without flag 1x100
desligamento de enrolamento

Tempo de retardo de
Analog input 24 30 04 Without flag 1x100
desligamento de óleo

Binary input 0 01 01 No status - Estado do Relé da R.F.1*

Binary input 1 01 01 No status - Estado do Relé da R.F.2*

Estado do Relé de
Binary input 2 01 01 No status -
Autodiagnóstico*

Binary input 3 01 01 No status - Estado do Relé programável 1*

Binary input 4 01 01 No status - Estado do Relé de programável


2*
Binary input 5 01 01 No status - Estado do Relé programável 3*

Estado do Relé de programável


Binary input 6 01 01 No status -
4*

Binary input 8 01 01 No status - Erro de EEPROM*

Binary input 11 01 01 No status - Erro de overflow nas medições*

Binary input 12 01 01 No status - Não utilizado

Binary input 13 01 01 No status - Erro de leitura do TC externo*

Binary input 14 01 01 No status - Erro de leitura do AD*

Binary input 15 01 01 No status - Erro de salto na leitura de RTD’s*

Binary input 16 01 01 No status - Erro de calibração RTD1*

Binary input 17 01 01 No status - Erro de calibração RTD2*

Binary input 18 01 01 No status - Erro de calibração RTD3*

Binary input 19 01 01 No status - Não utilizado

Binary input 20 01 01 No status - Erro de leitura RTD1*

Binary input 21 01 01 No status - Erro de leitura RTD2*

Binary input 22 01 01 No status - Erro de leitura RTD3*

Binary input 23 01 01 No status - Não utilizado

Binary input 24 01 01 No status - Opcional RTDs adicionais*

Binary input 25 01 01 No status - Opcional Saída Analógica*

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


26
Supervisor de Temperatura para Transformadores com
Óleo TS

Binary input 26 01 01 No status - Opcional Porta Serial RS485*

Binary input 27 01 01 No status - Não utilizado

Binary input 28 01 01 No status - Opcional Memória de Massa*

Binary input 29 01 01 No status - Opcional Pré-resfriamento*

Opcional Exercício de
Binary input 30 01 01 No status -
ventiladores*

Binary input 31 01 01 No status - Opcional PID

Binary input 32 01 01 No status - Alarme de enrolamento

Binary input 33 01 01 No status - Alarme de óleo

Binary input 34 01 01 No status - Desligamento de enrolamento

Binary input 35 01 01 No status - Desligamento de óleo

Alarme por envelhecimento


Binary input 36 01 01 No status -
acumulado

Binary input 37...39 01 01 No status - Reservado

Binary input 40 01 01 No status - Erro de EEPROM**

Binary input 41...42 01 01 No status - Reservado

Binary input 43 01 01 No status - Erro de overflow nas medições**

Binary input 44 01 01 No status - Reservado

Binary input 45 01 01 No status - Erro de leitura do TC externo**

Binary input 46 01 01 No status - Erro de leitura do AD**

Erro de salto na leitura de


Binary input 47 01 01 No status -
RTD’s**

Binary input 48 01 01 No status - Erro de calibração RTD1**

Binary input 49 01 01 No status - Erro de calibração RTD2**

Binary input 50 01 01 No status - Erro de calibração RTD3**

Binary input 51 01 01 No status - Não utilizado

Binary input 52 01 01 No status - Erro de leitura RTD1**

Binary input 53 01 01 No status - Erro de leitura RTD2**

Binary input 54 01 01 No status - Erro de leitura RTD3**

Binary input 55 01 01 No status - Não utilizado

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


27
Supervisor de Temperatura para Transformadores com
Óleo TS

Binary input 56 01 01 No status - Ativo energizado

* Os itens marcados com um asterisco (*) estão disponíveis no objeto Class 1

** Encontrados na memória de erros do equipamento

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


28
Supervisor de Temperatura para Transformadores com
Óleo TS

BRASIL
Treetech Sistemas Digitais Ltda
Praça Claudino Alves, 141, Centro
CEP 12.940-000 - Atibaia/SP
+ 55 11 2410-1190
comercial@treetech.com.br
www.treetech.com.br

REPRESENTANTES/ DISTRIBUIDORES INTERNACIONAIS

AMÉRICA DO SUL AMÉRICA DO NORTE OCEANIA

CHILE - Santiago ESTADOS UNIDOS DA AMÉRICA - Portland AUSTRÁLIA/NOVA ZELÂNDIA - Melbourne


INMOHA TechSales Martec Asset Solutions
+56 2531-7986 +1 503 345 9710 +61 (0)430 149 665
felix.morales.h@gmail.com terry@techsales-nw.com selwyn.braver@martecassetsolutions.com.au

PARAGUAI - Asunción MÉXICO - Hidalgo EUROPA


Enertec MCT
+595 21 214 814 +52 779 796 4286 PORTUGAL - Linda a Velha
paraguay@treetech.com.br jgchirino@monitoreoycontrol.com Trafotech
+351 214 146 740
PERU - Lima ÁSIA trafotech@trafotech.pt
Logytec
+511 452 3111 ÍNDIA - Raipur NORUEGA - Hokksund
ventas@logytec.com.pe Global Technology EB Elektro
+91 98261 22000 +47 31 01 37 00
COLÔMBIA - Medellín info@global-technology.in simen.andreassen@eb-elektro.no
Enersafe S.A
+57 4 604 32 72
daniel.restrepo@enersafe.com.co

Protocolo de Comunicação – TS | PC-032 | 03/11/2015 | Revisão: 1.10


29

Вам также может понравиться