Summary
The project developed Industrias de Hule Galgo SA DE CV is a design and calculation of
interior lighting for the auditorium José Suárez.
In this project the design, features, regulations and calculations of the lighting and electrification
of Joseph Suarez Auditorium, located in Industrias de Hule Galgo SA DE C.V. This project is
equipped with an explanatory report containing the processes used in the design and
calculation of the installation, and the final results of the same.
So attached to the memory, all results obtained through an annex of calculations are justified,
in addition to the budget, and the representation of the final results by means of drawings and
diagrams.
For the design of interior lighting systems analytical or mathematical method is used both as
assisted by lighting design software DIALux. Both methods are discussed.
It concluded with the analysis that the simulation program DIALux is a very useful tool lighting
studies in order to have an analysis of the lamps prior to installation and thus ensure that they
meet an established standard.
This study was limited to 4 types of lighting, the most common powers used and manufacturers
mostly found in the country.
In case proposed international and national standards, taking as variables, the type of
luminaire, power operation, mounting height, separation and distributing them throughout the
auditor.
1
INTRODUCCIÓN
Las instalaciones eléctricas son la base para el uso de la electricidad por parte del
hombre de forma directa. Las técnicas han ido progresando a lo largo de la historia
para poder ampliar los usos de las instalaciones de una forma más segura y cómoda.
Una instalación eléctrica obliga al ingeniero diseñador a consultar multitud de
reglamentos, manuales y normas para enfocar la tarea desde una posición lo más
óptima posible. En ocasiones tener diferentes fuentes de información, para conseguir
un diseño apropiado, puede conducir a conflictos o interpretaciones erróneas.
Abordar todos los puntos para la electrificación de un edificio que estará dedicado a
conferencias, desde la acometida de la compañía en media tensión y puesta a tierra
del edificio, hasta los estudios de eficiencia energética de la iluminación que tendremos
en las diferentes salas.
Se comenta cuáles son los objetivos del proyecto. Seguidamente, se desarrolla una
memoria descriptiva; los cálculos justificativos; se adjuntarán anexos de materiales
especificados y se citará la bibliografía que ha sido necesaria para la realización del
documento. Finalmente, se presentará el presupuesto que costaría llevar a cabo la
obra, y los planos necesarios para su seguimiento y ejecución. La mayoría de los
diseños de iluminación son prácticamente empíricos, hechos más por costumbre y
basados en la experiencia, que por alguna norma o regla establecida para la labor
requerida, por lo que con este trabajo se busca hacer los diseños de iluminación. Toda
edificación en la cual se ha de realizar algún tipo de actividad, ya sea laboral o
cotidiana, requiere de un ambiente que cuente con un buen nivel de iluminación para
optimizar el rendimiento, la productividad, la seguridad y el confort al momento de
ejecutar dichas actividades. Anteriormente las instalaciones de iluminación no eran
diseñadas teniendo en cuenta diversos factores que alteran el efecto lumínico de las
fuentes de luz de una u otra manera y tampoco existían reglamentos o
especificaciones que deberían cumplir éstos diseños, provocando así que las
instalaciones de iluminación fueran mal diseñadas y no garantizaban los niveles de
iluminancia requeridos para cada tipo de espacio y actividad a realizar.
Los sistemas de iluminación presentan buenas oportunidades de implementar
soluciones de eficiencia energética. Debido a que estás son aplicadas localmente y
normalmente no es necesario intervenir mayormente las instalaciones eléctricas.
En la actualidad todas las lámparas incandescentes, fluorescentes compactas y tubos
fluorescentes comercializados en nuestro país deben contar con una etiqueta de
eficiencia energética, cuyo objetivo otorgar una herramienta de decisión, basada en la
eficiencia en el uso de energía, para optar por alguna tipo de tecnología u otra.
La calidad del alumbrado influye de manera directa en el rendimiento visual,
concentración, seguridad y bienestar del ser humano en el trabajo. Por lo tanto el
alumbrado debe ser diseñado de modo que cumpla con las condiciones particulares
de cada caso.
La iluminación artificial nos permite realizar actividades en lugares obscuros donde la
luz de día no alcanza a llegar y que la luz emitida por la luna durante la noche no es
suficiente para llevar a cabo actividades nocturnas.
2
ANTECEDENTES
INDUSTRIAS DE HULE GALGO S.A. DE C.V. es una empresa que se ha consolidado como
líder nacional en la fabricación de una amplia gama de productos de hule, para diferentes
aplicaciones.
En 1982 Galgo inaugura en Tula de Allende Hidalgo, una moderna planta para la elaboración
de materiales para la renovación de neumáticos, en las que además de ampliar su capacidad
de producción de hule añade la elaboración de materiales utilizados en el proceso de
renovación, tales como camel back, cemento, pinturas y hules cojín.
Objetivo General
Tener la información para planificar, calcular y presupuestar la instalación eléctrica de baja
tensión en el Auditorio José Suárez en la empresa industrias de Hule Galgo S.A. de C.V.
Objetivos Específicos
Diseño de la iluminación del interior del edificio.
Diseño de la Instalación Eléctrica.
Estudio económico del costo de la instalación.
3
Justificación
En el proyecto se han tenido en cuenta factores: sociales, administrativos, ecológicos,
estéticos y en base al encargo realizado. En general, se pueden fijar una serie de criterios
básicos que se han tenido en cuenta en la red de alumbrado para el Auditorio José Suárez.
Garantizar un suministro suficiente para las necesidades previstas. Vías peatonales con
escaso tráfico rodado y comercio prácticamente nulo. Por lo que se establece una iluminación
media de 20 lux.
Primar la total seguridad en el servicio de alumbrado y un mantenimiento mínimo. Para lo que
se proyecta una distribución de redes aéreas ramificadas donde todas las conexiones o
derivaciones y elementos auxiliares se situarán por encima del nivel del suelo, en la propia
luminaria. La distribución será trifásica con neutro común para las fases y protegidos en tablero
por diferenciales trifásicos.
Se instalarán luminarias con TECNOLOGÍA LED para conseguir un ahorro energético
considerable y elevamos la vida de la luminaria en relación con las luminarias de lámparas de
descarga utilizadas.
Permitir una fácil orientación. Para lo cual se ha calculado una uniformidad global de la
luminancia.
Proporcionar una iluminación suficiente, una fiabilidad visual y que ofrezca la máxima
seguridad. Mediante los reguladores de flujo se consigue que se mantenga una uniformidad
en la iluminación, constantemente aun cuando reducimos el consumo, algo que no se consigue
con al apagado alternativo proporcionando un aspecto atractivo.
4
CAPÍTULO 1. MARCO TEÓRICO
1.1 LA ELECTRICIDAD
La electricidad es un conjunto de fenómenos físicos referentes a los efectos producidos
por las cargas eléctricas tanto en reposo como en movimiento. Fue Benjamín Franklin quien
denominó a los dos tipos de cargas, positiva y negativa; dedujo que cuando una carga se
produce, siempre otra de magnitud idéntica pero de carga opuesta se crearía.
La electricidad puede definirse como el movimiento de cargas eléctricas llamadas
electrones. Los átomos de la materia contienen electrones, que son partículas con cargas
negativas. Los electrones se mueven alrededor del núcleo de su átomo, el cual contiene
partículas cargadas positivamente llamadas protones.
Normalmente las cargas positivas y las negativas se encuentran en equilibrio en la
materia. Cuando los electrones se mueven de su posición normal en los átomos, se observan
efectos eléctricos.
1.2 COMPONENTES DE LAS INSTALACIONES ELÉCTRICAS
Para la realización física de una instalación eléctrica se emplea una gran cantidad de
equipo y material eléctrico.
Cualquier persona que se detenga a observar una instalación eléctrica podrá notar que
existen varios elementos, algunos visibles o accesibles y otros no.
El conjunto de elementos que intervienen desde el punto de alimentación o acometida
de la compañía suministradora (CFE) hasta el último punto de una casa habitación, comercio,
bodega o industria en donde se requiere el servicio eléctrico, constituye lo que se conoce como
los componentes de la instalación eléctrica.
En el tema anterior se mencionó que un circuito eléctrico está constituido en su forma
más elemental por una fuente de voltaje o de alimentación, los conductores que alimentan la
carga y los dispositivos de control o apagadores. De estos elementos se puede desglosar el
resto de los componentes de una instalación eléctrica práctica, ya que, por ejemplo, los
conductores eléctricos normalmente van dentro de tubos metálicos o de PVC que se conocen
genéricamente como tubos (conduit); los apagadores se encuentran montados sobre cajas,
las lámparas se alimentan de cajas metálicas similares a las usadas en los apagadores y
también en los contactos; y asociados a estos elementos se tienen otros componentes
menores, así como toda una técnica de selección y montaje.
1. Los elementos que estudiaremos brevemente son:
2. Conductores eléctricos.
3. Interruptores.
4. Fusibles.
5. Centros de carga.
6. Contactos y apagadores.
7. Lámparas.
8. Canalizaciones y accesorios.
5
Por otra parte, todos los elementos usados en las instalaciones eléctricas deben cumplir
con ciertos requisitos, no sólo técnicos, también de uso y presentación, para lo cual deben
acatar las disposiciones que establece la Norma Oficial de Instalaciones Eléctricas NOM-001-
SEDE.
Todos estos elementos se identifican en un plano o diagrama eléctrico por medio de
símbolos. A continuación haremos una breve descripción de estos elementos y al final del
tema ilustraremos el punto de los diagramas y planos eléctricos con su simbología.
1.3 CONDUCTORES ELÉCTRICOS
Los alambres y cables que se emplean en casas habitación, comercios, bodegas, etc.,
se conocen en el argot de los conductores eléctricos como cables para la industria de la
construcción.
Estos cables para la industria de la construcción en baja tensión están formados por los
siguientes elementos:
Componentes de las instalaciones eléctricas
El conductor eléctrico, que es el elemento por el que circula la corriente eléctrica: es de
cobre suave y puede tener diferentes flexibilidades:
Rígida: Conductor formado por un alambre.
Semiflexible: Conductor formado por un cable (cableado clase B o C).
Flexible: Conductor eléctrico formado por un cordón (clase I en adelante).
6
Una cubierta externa, cuya función es la de proteger al cable de factores externos
(golpes, abrasión, etc.) y ambientales (lluvia, polvo, rayos solares, etc.). Normalmente está
cubierta externa es de poli cloruró de vinilo (PVC) y se aplica en cables multi-conductores.
7
1.4 Conductor eléctrico
Son cuatro los factores que deben ser considerados en la selección de los conductores:
material, flexibilidad, forma y dimensiones.
Material
Los materiales más usados como conductores eléctricos son el cobre y el aluminio,
aunque el primero es superior en características eléctricas y mecánicas (la conductividad del
aluminio es aproximadamente el 60% de la del cobre y su esfuerzo de tensión a la ruptura, el
40%). Las características de bajo peso del aluminio han dado lugar a un amplio uso de este
metal en la fabricación de los cables aislados y desnudos.
En la siguiente tabla se muestran en forma general las propiedades de los conductores
de cobre suave y de aluminio 3/4 de duro.
8
Características Cobre suave Aluminio ¾ duro
Flexibilidad
Acorde con los requerimientos de una instalación en particular, las normas de productos
clasifican la flexibilidad de los conductores en clases de cableado, combinando diferentes
diámetros de alambres y el número de éstos.
9
Figura 1. 3 Flexibilidad de los Conductores.
Forma
1.5 INTERRUPTORES
10
Para nuestro caso consideraremos como sobrecargas todos aquellos valores de
corriente que excedan a la corriente nominal de los equipos, pero sin exceder un 500%.
El cortocircuito es una condición en la que la corriente de un equipo o sistema se eleva
a valores muy superiores al valor nominal. Para nuestro caso se considera cortocircuito a todo
valor de corriente que excede el 500% de la nominal.
Línea. Se da el nombre de línea al conductor o conjunto de conductores en los cuales
hay presencia de voltaje y pueden alimentar un equipo eléctrico.
Carga. Se conoce como carga al aparato o conjunto de aparatos conectados a la línea,
que consumirán energía eléctrica.
Polos y fases. Para un interruptor, se conoce como número de polos a la cantidad de
pares conductores línea-carga que llegan a dicho interruptor.
11
Circuito alimentador. Refiriéndonos a tableros y centros de carga, el circuito alimentador
o línea de alimentación será aquel circuito que le proporciona la energía eléctrica al tablero.
Circuito derivado. Se da ese nombre a cada uno de los circuitos que alimentan el
tablero a través de cada uno de sus interruptores, los cuales también reciben el nombre de
derivados.
Fases, hilos y número de polos. Cuando a un tablero lo alimenta una línea de corriente
o dos, se dice que es de una fase, siendo en estos dos casos absolutamente necesaria la
conexión del hilo neutro.
Cuando al tablero llegan las tres líneas de corriente, se dice que es de tres fases.
El número de hilos en el tablero queda definido por la suma de cables de línea y neutro
que lo alimentan, teniéndose las siguientes combinaciones.
Una fase, tres hilos.
Tres fases, tres hilos.
Tres fases, cuatro hilos.
Tipos de montaje
12
La alimentación del tablero se realiza a través de un interruptor termo magnético que
forma parte integral de él y le brinda medio de protección y conexión general.
1.8 CANALIZACIONES
Las canalizaciones eléctricas sirven para proporcionar protección mecánica a los
conductores, ya que los aísla físicamente y confina cualquier problema de calor o chispas
producidas por falla de aislamiento.
Existe una gran variedad de medios para contener a los conductores eléctricos
conocidos como canalizaciones eléctricas; algunas son de uso común y otras se usan en
aplicaciones específicas. Algunos de estos medios son los tubos (conduit, con sus variedades
constructivas y de material), ductos, charolas y electro-ductos.
1.9 Tubos (conduit) metálicos
Los tubos (conduit) metálicos, dependiendo del tipo usado, se pueden instalar en
exteriores e interiores, en áreas secas o húmedas. Los tubos (conduit) rígidos constituyen, de
hecho, el sistema de canalización más comúnmente usado, porque prácticamente se puede
utilizar en todo tipo de atmósferas y para todas las aplicaciones.
13
En ambientes corrosivos, adicionalmente se debe tener cuidado de proteger los tubos
con pintura anticorrosiva, ya que la presentación normal de estos tubos es galvanizada.
Los tipos más usados son:
Tubo (conduit) metálico rígido (pared gruesa). Este tipo de tubo (conduit) se
suministra en tramos de 3 m de longitud, en acero o aluminio, y se encuentra disponible en
diámetros desde 13 mm (1/2‖) hasta 152,4 mm (6‖). Cada extremo del tubo se proporciona
con rosca y uno de ellos tiene un coplee.
Tubo metálico de pared delgada (rígido ligero). Estos tubos son similares a los de
pared gruesa, pero tienen la pared interna mucho más delgada. Se fabrican en diámetros de
hasta 102 mm (4‖). Se pueden usar en instalaciones visibles u ocultas, embebido en concreto
o embutido en mampostería, pero en lugares secos no expuestos a humedad o ambientes
corrosivos. Estos tubos no tienen sus extremos roscados y tampoco usan los mismos
conectores que los tubos metálicos anteriormente citados. Los conectores de este tipo de
tubería son atornillados.
Tubo (conduit) metálico flexible. Este es un tubo hecho de cinta metálica engargolada
(en forma helicoidal), sin ningún recubrimiento. Hay otro tubo metálico que tiene una cubierta
exterior de un material no metálico que se aplica sobre el tubo para que sea hermético a los
líquidos. Este tipo de tubo (conduit) es útil cuando se hacen instalaciones en áreas donde se
dificultan los dobleces con tubo (conduit) metálico, o bien en lugares donde existen vibraciones
mecánicas que puedan afectar las uniones rígidas de las instalaciones. Este tubo se fabrica
con un diámetro mínimo de 13 mm (1/2‖) y un diámetro máximo de 102 mm (4‖).
14
Figura 1. 7 Tipos de Tubo Conduit.
15
1.12 INCANDESCENCIA
Es la forma o proceso de producir luz por radiación térmica, normalmente en esta técnica,
el filamento de incandescencia de una lámpara es calentado debido a la acción de un campo
eléctrico lo que produce una gran cantidad de calor que traerá consigo la radiación de energía
en forma de ondas las que se propagan en línea recta. Si se eleva el voltaje aplicado a la
lámpara se eleva la temperatura del filamento y la energía radiante aumentará rápidamente.
Las lámparas incandescentes presentan por lo general un rendimiento muy bajo, debido
a que aproximadamente el 90 % de la energía radiada es invisible.
1.13 LUMINISCENCIA
La luminiscencia comprende todos los métodos de producción de luz distintos de la
incandescencia, va acompañada o es producida por reacciones químicas y se caracteriza por
una radiación muy selectiva, componiéndose frecuentemente el espectro de solo algunas
franjas coloreadas estrechas y brillantes, alguna de las cuales pueden encontrarse en la región
ultravioleta y ser, por consiguiente, invisibles. Tales espectros sugieren posibilidades
maravillosas en la tarea de producir luz de buen rendimiento.
El gusano de luz, por ejemplo, radia toda su energía en una estrecha banda de longitudes
de onda situada en el centro de la región visible. Es el foco luminoso de mayor rendimiento en
lo que se refiere a obtener la máxima visión con la mínima energía, pero todos los objetos
iluminados por esta luz aparecen amarillo – verdoso o negros.
1.14 SOMBRAS
Puede definirse como diferencia de brillo de las superficies y son indispensables para
observar objetos en tres dimensiones. Es, por consiguiente, buena práctica al proyectar
instalaciones de alumbrado que existan sombras, pero deben ser tenues e iluminadas. Es
también acertado disponer de iluminación artificial que dé las mismas sombras relativas que
proporciona la iluminación con luz diurna.
El grado en el cual deben eliminarse las sombras depende de la naturaleza del trabajo
a efectuar y de la perspectiva deseada. Se considera generalmente que es necesario eliminar
las sombras lo más posible en salas de dibujo y oficinas, y que las sombras densas deben
evitarse siempre.
16
1.15 FLUJO LUMINOSO
El flujo luminoso es la medida de la potencia luminosa percibida. Difiere del flujo radiante,
la medida de la potencia total emitida, en que está ajustada para reflejar la sensibilidad del ojo
humano a diferentes longitudes de onda.
Su unidad de medida en el Sistema Internacional de Unidades es el lumen (lm) y se
define a partir de la unidad básica del SI, la candela (cd).
El flujo luminoso se obtiene ponderando la potencia para cada longitud de onda con la
función de luminosidad, que representa la sensibilidad del ojo en función de la longitud de
onda. El flujo luminoso es, por tanto, la suma ponderada de la potencia en todas las longitudes
de onda del espectro visible.
La radiación fuera del espectro visible no contribuye al flujo luminoso. Así, para cualquier
punto de luz, si representa el flujo luminoso, simboliza la potencia radiante espectral del punto
de luz en cuestión y la función de sensibilidad luminosa.
1.16 Rendimiento luminoso
Rendimiento luminoso (η) es el rendimiento en términos de flujo luminoso (es decir,
iluminación efectiva) que se obtiene de una fuente luminosa que gasta una potencia eléctrica
dada. En unidades del SI, se mide en lumen por vatio.
Suele representarse por el símbolo η.
Se define como el rendimiento luminoso obtenido de un artefacto que gasta un vatio de
potencia y genera un lumen de flujo luminoso.
Puede entenderse este valor en términos de porcentaje de eficiencia. Por ejemplo, un
foco corriente suele emitir un 85% de la energía eléctrica gastada en forma de calor y otras
radiaciones, y un 15% efectivamente en iluminación visible, por lo que es muy ineficiente.
1.17 Reflexión
Cuando una superficie devuelve un rayo de luz que incide sobre ella, se dice que el rayo
es reflejado. La reflexión puede ser de varios tipos, especular, difusa, difusa dirigida o mixta.
17
El factor de reflexión o reflectancia es la relación entre la luz reflejada por una superficie
y la luz incidente en ella. Este factor puede variar considerablemente de acuerdo con la
dirección y la naturaleza de la luz incidente.
En la reflexión especular o normal el ángulo de incidencia es igual al de reflexión, en la
reflexión difusa la incidencia máxima es perpendicular a la superficie independientemente del
ángulo del rayo incidente, en la reflexión difusa dirigida es intermedia entre la especular y la
difusa y, por último, la reflexión mixta es una combinación de la difusa y la especular.
En la siguiente figura se muestran los diferentes tipos de reflexión.
1.18 Deslumbramiento
Consiste en una reacción fotoquímica en la retina, la cual la insensibiliza por un periodo
de tiempo, produciendo molestia y pérdida temporal de la visión.
1.19 Factor de mantenimiento
Factor que se emplea en el cálculo de la iluminación efectiva proporcionada por un
sistema después de un período de tiempo y en condiciones de terminadas como pueden ser
los efectos de la temperatura, el voltaje, la suciedad sobre la superficie de la luminaria.
1.20 Factor de uniformidad general
Relación entre la luminancia mínima y media, de una instalación de alumbrado, su
símbolo es U0 y se mide como un porcentaje.
1.21 Factor de uniformidad longitudinal
Relación entre la luminancia mínima y máxima longitudinal, de una instalación de
alumbrado, su símbolo es UL y se mide como un porcentaje.
18
Como cualquier otro cuerpo incandescente, el cuerpo negro cambia de color a medida
que aumenta su temperatura, adquiriendo al principio, el tono de un rojo sin brillo, para luego
alcanzar el rojo claro, el naranja, el amarillo y finalmente el blanco, el blanco azulado y el azul.
El color, por ejemplo, de la llama de una vela, es similar al de un cuerpo negro calentado
a unos 1.800 K*, y la llama se dice entonces, que tiene una “temperatura de color” de 1.800 K.
Las lámparas incandescentes tienen una temperatura de color comprendida entre los
2.700 y 3.200 K, según el tipo, por lo que su punto de color determinado por las
correspondientes coordenadas queda situado prácticamente sobre la curva del cuerpo negro.
Define sólo color y sólo puede ser aplicada a Fuentes de luz que tengan una gran
semejanza de color con el cuerpo negro.
19
Figura 1. 9 Curva de Temperatura de un Cuerpo Negro.
La iluminancia recibida desde una sola fuente de luz sobre cualquier superficie dada
puede calcularse a partir de los datos de la curva de distribución luminosa de dicha fuente,
esto se puede hacer tomando el ángulo de apertura al cual se quiere medir la intensidad y
buscar el punto de intersección de la curva de distribución con la línea del ángulo que se desea
calcular, luego se aplica la siguiente ecuación, para el cálculo de la intensidad luminosa real.
20
Figura 1. 10 Curva de Distribución Fotométrica.
21
La mejor representación de un haz de luz irregular se obtiene mediante un diagrama de
isocandelas. En él se representa en grados las distancias al eje del haz, tanto horizontal como
verticalmente, y se recoge gran número de lecturas de intensidades luminosas en diferentes
puntos; las curvas que se dibujan unen puntos de igual intensidad luminosa. Los diagramas
de isocandelas que se refieren a haces notablemente dispersos se representan a veces en
proyección semiesférica, gracias a la distribución acimutal de Lambert, en la cual las áreas de
las zonas estudiadas pueden verse con mayor precisión que empleado en coordenadas
rectangulares, de estos diagramas se pueden medir además, el alcance de la luminaria.
22
Figura 1. 12 Diagrama Isolux.
23
1.27 Lámparas fluorescentes
La lámpara fluorescente es una lámpara de descarga en vapor de mercurio de baja
presión, en la cual la luz se produce mediante polvos fluorescentes activados por la energía
ultravioleta de una descarga.
Entre ellas existen varios tonos con una amplia variedad de temperaturas de color e
índices de reproducción cromática, con lo cual cubren una amplia gama de aplicaciones
residenciales e industriales.
24
Figura 1. 15 Lámpara de Vapor de Mercurio.
25
1.30 Lámparas de inducción magnética
Son un tipo de lámparas de descarga, en las cuales se introduce un concepto totalmente
nuevo en la generación de la luz. La característica principal del sistema es que prescinde de
la necesidad de los electrodos para la ionización del gas, en la actualidad existen dos métodos,
los cuales son crear un anillo cerrado de vidrio donde la energía se suministra desde el exterior
por un campo magnético, ionizando el gas dentro del tubo, o colocar un gas a baja presión y
un acoplador de potencia en el cual se encuentre un núcleo cilíndrico de ferrita, para crear un
campo electromagnético dentro del recipiente de descarga que induce una corriente en el gas
provocando su ionización.
26
1.31 Lámparas LED’s
Una Lámpara LED es una lámpara de estado sólido que usa Diodos Emisores de
Luz (LEDs) como fuente luminosa. Debido a que la luz capaz de emitir un LED no es
muy elevada, para alcanzar la intensidad luminosa similar a las otras lámparas existentes
como las incandescentes o las fluorescentes compactas, las lámparas LED están compuestas
por agrupaciones de LED, en mayor o menor número, según la intensidad luminosa que se desee
alcanzar.
Actualmente las lámparas LED se pueden usar para cualquier aplicación comercial,
desde el alumbrado decorativo hasta el de viales y jardines, presentado ciertas ventajas, entre
las que destacan su considerable ahorro energético, bajos costos de mantenimiento, no
contienen mercurio, reducción de emisiones contaminantes y luz dirigida (menos
contaminación visual) y su mayor vida útil, pero también con ciertos inconvenientes como son
su elevado coste inicial, poca disponibilidad de fotometrías, bajos niveles del flujo luminoso y
niveles de iluminación más limitados, entre otros.
27
1.32 Luminarias
Según la norma UNE-EN 60598-1, se define luminaria como el aparato de alumbrado
que reparte, filtra o transforma la luz emitida por una o varias lámparas y que comprende todos
los dispositivos necesarios para el soporte, la fijación y la protección de lámparas, (excluyendo
las propias lámparas) y, en caso necesario, los circuitos auxiliares en combinación con los
medios de conexión con la red de alimentación.
Con independencia de otras definiciones que puedan ser más o menos descriptivas,
podríamos definir la luminaria como un objeto formado por un conjunto de elementos
destinados a proporcionar una adecuada radiación luminosa de origen eléctrico, la
materialización de estos elementos pasa en cada caso por la conjunción entre un buen diseño
formal y una razonable economía de medios.
Al primero corresponde resolver el control luminoso según las necesidades, que es el fin
primordial, un control térmico que haga estable su funcionamiento, y un control eléctrico que
ofrezca las debidas garantías al usuario. Al segundo corresponde prever un producto de
fabricación sólida y eficaz, una relativa sencillez en su instalación y un mínimo mantenimiento
de uso.
Figura 1. 19 Gabinete.
28
CAPÍTULO 2. SUPUESTOS TÉCNICOS
29
CAPÍTULO 3 PROPUESTA DE SOLUCIÓN AL PLANTEAMIENTO DEL
PROBLEMA
El desarrollo de este proyecto se basó en varias etapas, las cuales se detallan a
continuación.
Lectura y comprensión de diversos manuales y libros sobre los sistemas d iluminación,
con el fin de recopilar información sobre los conceptos básicos utilizados en el tema.
Realizar una investigación bibliográfica de las normativas internacionales para los
diseños de iluminación, así como una revisión a los códigos utilizados en el país para
este fin.
Efectuar mediciones de diferentes parámetros en la instalación existente para tener un
panorama del estado de la cuestión, además de en numerar las fallas de los sistemas
existentes.
Utilizar el programa de software libre Dialux para hacer un estudio y análisis de la
iluminación interior con las luminarias elegidas.
3.1 Objetivo
El objetivo del siguiente proyecto es la descripción de las características, condiciones
técnicas y de seguridad que reunirá la instalación para la iluminación del Auditorio José
Suárez y su correspondiente red de distribución de energía eléctrica en baja tensión,
220-127 VCA.
30
3.3 CONDUCCIÓN
Por último indicar que el tipo de conducción será aéreo todo ello se hará, evidentemente,
cumpliendo con todas las normas que afectan a este tipo de instalaciones.
3.4 Normas
La distribución de las luminarias ha sido calculada y decidida teniendo en cuenta:
Tablas de iluminación NOM-013-ENER-2012.
Tablas de iluminación NOM-025-STPS-2012.
31
Tarea Visual del Puesto de Trabajo Área de Trabajo Niveles Mínimos de
Iluminación (luxes)
ensamble simple, trabajo medio en banco y máquina, Talleres: áreas de empaque y ensamble, aulas y
300
inspección simple, empaque y trabajos de oficina. oficinas.
32
3.5 CÁLCULO DE INSTALACIONES DE ALUMBRADO
El cálculo de los niveles de iluminación de una instalación de alumbrado de interiores es
bastante sencillo. A menudo nos bastará con obtener el valor medio del alumbrado general
usando el método de los lúmenes.
3.6 Método de los lúmenes
La finalidad de este método es calcular el valor medio en servicio de la iluminancia en
un local iluminado con alumbrado general. Es muy práctico y fácil de usar, y por ello se utiliza
mucho en la iluminación de interiores cuando la precisión necesaria no es muy alta como
ocurre en la mayoría de los casos.
El proceso a seguir se puede explicar mediante el siguiente diagrama de bloques:
Figura 3. 2 Datos de
Entrada.
33
Determinar el nivel de iluminancia media (Em). Este valor depende del tipo de actividad
a realizar en el local y podemos encontrarlos tabulados en las normas y recomendaciones que
aparecen en la bibliografía.
Altura de las
Tipo de Local
luminarias
34
Locales de altura normal Lo más altas
(oficinas, viviendas, aulas...) posibles
Calcular el índice del local (k) a partir de la geometría de este. En el caso del método
europeo se calcula como:
Sistema de
Índice del local
iluminación
Iluminación directa,
semidirecta,
directa-indirecta y
general difusa
Iluminación
indirecta y
semiindirecta
Tabla 3. 4 Índice del Local.
35
Determinar los coeficientes de reflexión de techo, paredes y suelo. Estos valores se
encuentran normalmente tabulados para los diferentes tipos de materiales, superficies y
acabado. Si no disponemos de ellos, podemos tomarlos de la siguiente tabla.
Lugar Color Factor
de reflexión
( )
Techo Blanco 0.7
o muy claro
claro 0.5
medio 0.3
Paredes claro 0.5
medio 0.3
oscuro 0.1
Suelo claro 0.3
oscuro 0.1
Tabla 3. 5 Coeficiente de Reflexión.
En su defecto podemos tomar 0.5 para el techo, 0.3 para las paredes y 0.1 para el suelo.
Determinar el factor de utilización ( , CU) a partir del índice del local y los factores de
reflexión. Estos valores se encuentran tabulados y los suministran los fabricantes. En las tablas
encontramos para cada tipo de luminaria los factores de iluminación en función de los
coeficientes de reflexión y el índice del local. Si no se pueden obtener los factores por lectura
directa será necesario interpolar.
36
Figura 3. 4 Ejemplo de Factor de Utilización.
Figura 3. 5 Fórmula
para el Flujo Luminoso.
37
Donde:
es el flujo luminoso total
E es la iluminancia media deseada
S es la superficie del plano de trabajo
es el factor de utilización
fm es el factor de mantenimiento
. Figura 3. 6 Fórmula
para el número de
Luminarias
donde N es el número de
luminarias
Figura 3. 7 Distancias entre Luminarias.
38
La distancia máxima de separación entre las luminarias dependerá del ángulo de
apertura del haz de luz y de la altura de las luminarias sobre el plano de trabajo. Veámoslo
mejor con un dibujo:
Como puede verse fácilmente, mientras más abierto sea el haz y mayor la altura de la
luminaria más superficie iluminará aunque será menor el nivel de iluminancia que llegará al
plano de trabajo tal y como dice la ley inversa de los cuadrados. De la misma manera, vemos
que las luminarias próximas a la pared necesitan estar más cerca para iluminarla (normalmente
la mitad de la distancia). Las conclusiones sobre la separación entre las luminarias las
podemos resumir como sigue:
Distancia
Tipo de Altura del
máxima
luminaria local
entre luminarias
intensiva > 10 m e 1.2 h
extensiva 6 - 10 m
Semi e 1.5 h
4-6m
extensiva
extensiva 4m e 1.6 h
distancia pared-luminaria: e/2
Tabla 3. 7 Distancia entre luminarias.
39
Si después de calcular la posición de las luminarias nos encontramos que la distancia
de separación es mayor que la distancia máxima admitida quiere decir que la distribución
luminosa obtenida no es del todo uniforme. Esto puede deberse a que la potencia de las
lámparas escogida sea excesiva. En estos casos conviene rehacer los cálculos probando a
usar lámparas menos potentes, más luminarias o emplear luminarias con menos lámparas.
Figura 3. 9 Fórmula de
iluminación media.
40
3.11.1 Delimitación del nivel de iluminación
La iluminancia o nivel de iluminación de una superficie es la relación que hay entre la
cantidad total de luz (emitida por una fuente de luz) que recibe esa superficie y su área. Los
niveles de iluminación vendrán dados por las características del área a iluminar.
Zona Lux NOM-025
Auditorio (1) 300 Lux
Auditorio (2) 300 Lux
Auditorio (3) 300 Lux
Cocineta (4) 200 Lux
Recibidor (5) 100 Lux
Pasillo (6) 100 Lux
Baño (7) 100 Lux
Tabla 3. 9 Niveles de iluminación en zonas.
41
3.12 Instalación de Iluminación Sección 1.
Se requiere diseñar una instalación de alumbrado para un auditorio de 9.10 m de largo
por 15.02 m de ancho y 4.06 m de altura. Para ello utilizaremos lámparas LED de 60 W de
potencia con un flujo luminoso de 7000 lm. Respecto a las luminarias, cuya tabla del factor de
utilización 0-1, suministradas por el fabricante, se adjuntan a continuación.
Otros datos:
Los coeficientes de reflexión de paredes y techo se considerarán debido a que
los materiales empleados (superficies y estructuras metálicas) tienen coeficientes
de reflexión extremadamente bajos.
Es recomendable que el sistema de iluminación se instale por lo menos a .25 m
del techo.
El nivel de iluminación aconsejado para las actividades que se desarrollan en el
local es de 300 lux en el plano de trabajo.
3.12.1 Cálculos Luminotécnicos
Este es un ejemplo de problema resuelto con el método de los lúmenes. Tenemos un
auditorio que queremos alumbrar con una iluminación homogénea de 300 lx.
3.12.2 Datos Sección #1
Largo 9.10 mts
42
3.12.3 Nivel de iluminancia media
Nos piden 300 lx pero teniendo en cuenta que sólo se trabaja de día y la iluminancia de
la luz solar es de 75 lux, la iluminancia proporcionada por la iluminación será:
Em = 300 - 75 =225 lx
Sistema de
Índice del local
iluminación
Iluminación
directa,
semidirecta,
directa-indirecta
y general difusa
Iluminación
indirecta y
semiindirecta
Tabla 3. 12 Índice del Local Sección #1.
43
3.12.5 Coeficientes de reflexión
Los coeficientes del techo y las paredes se suministran en el enunciado.
Techo Paredes Suelo
Coeficiente de reflexión
70% 70% 50%
Tabla 3. 13 Coeficiente de Reflexión Sección #1.
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
44
.
PARED 0.70
SUELO 0.50
45
Acudimos a la tabla de producto para el cálculo de Coeficiente de Utilización.
Techo 0.70 0.70 0.70 0.50 0
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
Interpolamos
46
3.12.8 Flujo Luminoso Total de la Sección #1
Luminaria 𝟇 𝑬𝒎∗𝑺
𝑻=
𝑪𝒖∗𝑭𝒎
𝟇𝑻 Flujo luminoso (Lúmenes)
Cu Coeficiente de Utilización
Fm Factor de Mantenimiento
Tabla 3. 18 Flujo Luminoso.
𝟇 (𝟐𝟐𝟓𝑳𝒙)(𝟏𝟑𝟔.𝟔𝟖𝟐𝒎𝟐 )
𝑻= =𝟑𝟒𝟔𝟑𝟐.𝟐𝟔𝟑𝟓𝟏 𝑳ú𝒎𝒆𝒏𝒆𝒔
(𝟏.𝟏𝟏)(𝟎.𝟖)
47
3.12.8 Número de Luminarias Necesarias
𝝓𝑻
𝑵=
𝒏 ∗ ∅𝑳
N Número de Luminarias
𝝓𝑻 Flujo Luminoso Total (Lúmenes)
Número de Lámparas por
N
Luminaria
𝝓𝑳 Flujo Luminoso de una Lámpara
Tabla 3. 19 Número de Luminarias.
𝟑𝟒𝟔𝟑𝟐. 𝟐𝟔𝟑𝟓𝟏
𝑵= = 𝟒. 𝟗𝟒 𝑳𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏 ∗ (𝟕, 𝟎𝟎𝟎)
3.12.9 Emplazamiento de las luminarias
Finalmente sólo nos queda distribuir las luminarias sobre la planta del local y comprobar
que la distancia de separación entre ellas es inferior a la máxima admisible. En este caso la
separación máxima viene indicada en las tablas de las luminarias.
𝑵 𝒕𝒐𝒕𝒂𝒍
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝒂𝒏𝒄𝒉𝒐
𝒍𝒂𝒓𝒈𝒐
𝟓
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝟗. 𝟏𝟎 = 𝟏. 𝟕𝟒 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏𝟓. 𝟎𝟐
𝒍𝒂𝒓𝒈𝒐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝑵 𝒂𝒏𝒄𝒉𝒐 ∗ ( )
𝒂𝒏𝒄𝒉𝒐
𝟏𝟓. 𝟎𝟐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝟏. 𝟕𝟒 ∗ ( ) = 𝟐. 𝟖𝟕𝟏𝟗 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟗. 𝟏𝟎
48
Ancho Luminaria
Núm. De Luminarias 2
Separación (m) 9.10/2=4.55 mts
Separación de las paredes (m) 4.55/2=2.275 mts
Tabla 3. 20 Distancia entre Luminarias Ancho Sección #1.
Largo Luminaria
Núm. De Luminarias 3
Separación (m) 15.02/3=5 mts
Separación de las paredes (m) 5/2=2.5 mts
Tabla 3. 21 Distancia entre Luminarias Largo Sección #1.
𝟔 ∗ 𝟕, 𝟎𝟎𝟎 ∗ 𝟏. 𝟏𝟏 ∗ 𝟎. 𝟖
𝑬= = 𝟐𝟕𝟐. 𝟖𝟔𝟔𝟗 𝑳𝒖𝒙
𝟏𝟓. 𝟎𝟐 ∗ 𝟗. 𝟏
49
Distancia
Tipo de Altura del
máxima
luminaria local
entre luminarias
intensiva > 10 m e 1.2 h
extensiva 6 - 10 m
Semi e 1.5 h
4-6m
extensiva
extensiva 4m e 1.6 h
distancia pared-luminaria: e/2
Potencia 60 Watts
Lúmenes 7,000 Lm
50
3.13 Instalación de Iluminación Sección 1.1
Se requiere diseñar una instalación de alumbrado para un auditorio de 9.10 m de largo
por 15.02 m de ancho y 4.06 m de altura. Para ello utilizaremos lámparas LED de 30 W de
potencia con un flujo luminoso de 3500 lm. Respecto a las luminarias, cuya tabla del factor de
utilización 0-1, suministradas por el fabricante, se adjuntan a continuación.
Otros datos:
Los coeficientes de reflexión de paredes y techo se considerarán debido a que
los materiales empleados (superficies y estructuras metálicas) tienen coeficientes
de reflexión extremadamente bajos.
Es recomendable que el sistema de iluminación se instale por lo menos a .25 m
del techo.
El nivel de iluminación aconsejado para las actividades que se desarrollan en el
local es de 300 lux en el plano de trabajo.
3.13.1 Cálculos Luminotécnicos
Este es un ejemplo de problema resuelto con el método de los lúmenes. Tenemos un
auditorio que queremos alumbrar con una iluminación homogénea de 300 lx.
3.13.2 Datos Sección #1.1
Largo 9.10 mts
Em = 300 - 75 =225 lx
51
Tipo de lámpara a colocar. LED.
Sistema de
Índice del local
iluminación
Iluminación
directa,
semidirecta,
directa-indirecta
y general difusa
Iluminación
indirecta y
semiindirecta
Tabla 3. 28 Índice del Local Sección #1.1.
52
3.13.6 Determinación del coeficiente de utilización ( )
A partir de los factores de reflexión y el índice del local se leen en las tablas los factores
de utilización.
Techo 0.70 0.70 0.70 0.50 0
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
53
Figura 3. 11 Coeficientes del Local.
PARED 0.70
SUELO 0.50
54
Acudimos a la tabla de producto para el cálculo de Coeficiente de Utilización.
Techo 0.70 0.70 0.70 0.50 0
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
Interpolamos
55
3.13.8 Flujo Luminoso Total de la Sección #1.1
Luminaria 𝟇 𝑬𝒎∗𝑺
𝑻=
𝑪𝒖∗𝑭𝒎
𝟇𝑻 Flujo luminoso (Lúmenes)
Cu Coeficiente de Utilización
Fm Factor de Mantenimiento
Tabla 3. 34 Flujo Luminoso.
𝟇 (𝟐𝟐𝟓𝑳𝒙)(𝟏𝟑𝟔.𝟔𝟖𝟐𝒎𝟐 )
𝑻= =𝟑𝟒𝟔𝟑𝟐.𝟐𝟔𝟑𝟓𝟏 𝑳ú𝒎𝒆𝒏𝒆𝒔
(𝟏.𝟏𝟏)(𝟎.𝟖)
56
3.13.9 Número de Luminarias Necesarias
𝝓𝑻
𝑵=
𝒏 ∗ ∅𝑳
N Número de Luminarias
𝝓𝑻 Flujo Luminoso Total (Lúmenes)
Número de Lámparas por
N
Luminaria
𝝓𝑳 Flujo Luminoso de una Lámpara
Tabla 3. 35 Número de Luminarias.
𝟑𝟒𝟔𝟑𝟐. 𝟐𝟔𝟑𝟓𝟏
𝑵= = 𝟗. 𝟖𝟗 𝑳𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏 ∗ (𝟑𝟓𝟎𝟎)
3.13.10 Emplazamiento de las luminarias
Finalmente sólo nos queda distribuir las luminarias sobre la planta del local y comprobar
que la distancia de separación entre ellas es inferior a la máxima admisible. En este caso la
separación máxima viene indicada en las tablas de las luminarias.
𝑵 𝒕𝒐𝒕𝒂𝒍
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝒂𝒏𝒄𝒉𝒐
𝒍𝒂𝒓𝒈𝒐
𝟏𝟎
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝟗. 𝟏𝟎 = 𝟐. 𝟒𝟔 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏𝟓. 𝟎𝟐
𝒍𝒂𝒓𝒈𝒐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝑵 𝒂𝒏𝒄𝒉𝒐 ∗ ( )
𝒂𝒏𝒄𝒉𝒐
𝟏𝟓. 𝟎𝟐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝟐. 𝟒𝟔 ∗ ( ) = 𝟒 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟗. 𝟏𝟎
57
Ancho Luminaria
Núm. De Luminarias 3
Separación (m) 9.1/3=3 mts
Separación de las paredes (m) 3/2=1.5 mts
Tabla 3. 36 Distancia entre Luminarias Ancho Sección #1.1
Largo Luminaria
Núm. De Luminarias 4
Separación (m) 15.02/4=3.755 mts
Separación de las paredes (m) 3.755/2=1.8775 mts
Tabla 3. 37 Distancia entre Luminarias Largo Sección #1.1.
𝟏𝟐 ∗ 𝟑𝟓𝟎𝟎 ∗ 𝟏. 𝟏𝟏 ∗ 𝟎. 𝟖
𝑬= = 𝟐𝟕𝟐 𝑳𝒖𝒙
𝟏𝟓. 𝟎𝟐 ∗ 𝟗. 𝟏𝟎
58
Distancia
Tipo de Altura del
máxima
luminaria local
entre luminarias
intensiva > 10 m e 1.2 h
extensiva 6 - 10 m
Semi e 1.5 h
4-6m
extensiva
extensiva 4m e 1.6 h
distancia pared-luminaria: e/2
Tabla 3. 39 Distancia entre Luminarias Sección #1.1
Potencia 30 Watts
Lúmenes 3500 Lm
59
3.14 Instalación de Iluminación Sección 2.
Se requiere diseñar una instalación de alumbrado para un auditorio de 4.56 m de largo
por 15.02 m de ancho y 5.16 m de altura. Para ello utilizaremos lámparas LED de 60 W de
potencia con un flujo luminoso de 7,000 lm. Respecto a las luminarias, cuya tabla del factor
de utilización 0-1, suministradas por el fabricante, se adjuntan a continuación.
Otros datos:
Los coeficientes de reflexión de paredes y techo se considerarán debido a que
los materiales empleados (superficies y estructuras metálicas) tienen coeficientes
de reflexión extremadamente bajos.
Es recomendable que el sistema de iluminación se instale por lo menos a .25 m
del techo.
El nivel de iluminación aconsejado para las actividades que se desarrollan en el
local es de 300 lux en el plano de trabajo.
3.14.1 Cálculos Luminotécnicos
Este es un ejemplo de problema resuelto con el método de los lúmenes. Tenemos un
auditorio que queremos alumbrar con una iluminación homogénea de 300 lx.
3.14.2 Datos Sección #2
Largo 4.56 mts
60
3.14.3 Nivel de iluminancia media
Nos piden 300 lx pero teniendo en cuenta que sólo se trabaja de día y la iluminancia de
la luz solar es de 75 lux, la iluminancia proporcionada por la iluminación será:
Em = 300 - 75 =225 lx
Sistema de
Índice del local
iluminación
Iluminación
directa,
semidirecta,
directa-indirecta
y general difusa
Iluminación
indirecta y
semiindirecta
Tabla 3. 44 Índice del Local Sección 2.
61
3.14.5 Coeficientes de reflexión
Los coeficientes del techo y las paredes se suministran en el enunciado.
Techo Paredes Suelo
Coeficiente de reflexión
70% 70% 50%
Tabla 3. 45 Coeficiente de Reflexión Sección 2.
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
62
Figura 3. 12 Coeficientes del Local.
PARED 0.70
SUELO 0.50
63
Acudimos a la tabla de producto para el cálculo de Coeficiente de Utilización.
Techo 0.70 0.70 0.70 0.50 0
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
Interpolamos
87 + 104 95.5
𝐶𝑢 = = = 0.955
2 100
64
3.14.8 Flujo Luminoso Total de la Sección #2
Luminaria 𝟇 𝑬𝒎∗𝑺
𝑻=
𝑪𝒖∗𝑭𝒎
𝟇𝑻 Flujo luminoso (Lúmenes)
Cu Coeficiente de Utilización
Fm Factor de Mantenimiento
Tabla 3. 50 Flujo Luminoso.
𝟇 (𝟐𝟐𝟓𝑳𝒙)(𝟔𝟖.𝟒𝟗𝟏𝟐𝒎𝟐 )
𝑻= =𝟐𝟎𝟏𝟕𝟎.𝟖𝟑𝟕𝟕 𝑳ú𝒎𝒆𝒏𝒆𝒔
(𝟎.𝟗𝟓𝟓)(𝟎.𝟖)
65
3.14.9 Número de Luminarias Necesarias
𝝓𝑻
𝑵=
𝒏 ∗ ∅𝑳
N Número de Luminarias
𝝓𝑻 Flujo Luminoso Total (Lúmenes)
Número de Lámparas por
N
Luminaria
𝝓𝑳 Flujo Luminoso de una Lámpara
Tabla 3. 51 Número de Luminarias Sección 2.
𝟐𝟎𝟏𝟕𝟎. 𝟖𝟑𝟕𝟕
𝑵= = 𝟐. 𝟖𝟖 𝑳𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏 ∗ (𝟕, 𝟎𝟎𝟎)
3.14.10 Emplazamiento de las luminarias
Finalmente sólo nos queda distribuir las luminarias sobre la planta del local y comprobar
que la distancia de separación entre ellas es inferior a la máxima admisible. En este caso la
separación máxima viene indicada en las tablas de las luminarias.
𝑵 𝒕𝒐𝒕𝒂𝒍
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝒂𝒏𝒄𝒉𝒐
𝒍𝒂𝒓𝒈𝒐
𝟑
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝟒. 𝟓𝟔 = 𝟎. 𝟗𝟓 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏𝟓. 𝟎𝟐
𝒍𝒂𝒓𝒈𝒐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝑵 𝒂𝒏𝒄𝒉𝒐 ∗ ( )
𝒂𝒏𝒄𝒉𝒐
𝟏𝟓
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝟎. 𝟗𝟓 ∗ ( ) = 𝟑. 𝟏𝟐𝟓 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟒. 𝟓𝟔
66
Ancho Luminaria
Núm. De Luminarias 1
Separación (m) 4.56/1=4.56 mts
Separación de las paredes (m) 4.56/2=2.28 mts
Tabla 3. 52 Distancia entre Luminarias Ancho Sección 2.
Largo Luminaria
Núm. De Luminarias 4
Separación (m) 15.02/4=3.755 mts
Separación de las paredes (m) 3.755/2=1.8775 mts
Tabla 3. 53 Distancia entre Luminarias Largo Sección 2.
𝟒 ∗ 𝟕, 𝟎𝟎𝟎 ∗ 𝟎. 𝟕𝟏 ∗ 𝟎. 𝟖
𝑬= = 𝟐𝟑𝟐. 𝟐𝟎𝟓𝟎 𝑳𝒖𝒙
𝟏𝟓. 𝟎𝟐 ∗ 𝟒. 𝟓𝟔
67
Distancia
Tipo de Altura del
máxima
luminaria local
entre luminarias
intensiva > 10 m e 1.2 h
extensiva 6 - 10 m
Semi e 1.5 h
4-6m
extensiva
extensiva 4m e 1.6 h
distancia pared-luminaria: e/2
Tabla 3. 55 Distancia entre Luminarias Sección 2.
Potencia 60 Watts
Lúmenes 7,000 Lm
68
3.15 Instalación de Iluminación Sección 2.1
Se requiere diseñar una instalación de alumbrado para un auditorio de 4.56 m de largo
por 15.02 m de ancho y 5.16 m de altura. Para ello utilizaremos lámparas LED de 30 W de
potencia con un flujo luminoso de 3500 lm. Respecto a las luminarias, cuya tabla del factor de
utilización 0-1, suministradas por el fabricante, se adjuntan a continuación.
Otros datos:
Los coeficientes de reflexión de paredes y techo se considerarán debido a que
los materiales empleados (superficies y estructuras metálicas) tienen coeficientes
de reflexión extremadamente bajos.
Es recomendable que el sistema de iluminación se instale por lo menos a .25 m
del techo.
El nivel de iluminación aconsejado para las actividades que se desarrollan en el
local es de 300 lux en el plano de trabajo.
3.15.1 Cálculos Luminotécnicos
Este es un ejemplo de problema resuelto con el método de los lúmenes. Tenemos un
auditorio que queremos alumbrar con una iluminación homogénea de 300 lx.
3.15.2 Datos Sección #2.1
Largo 4.56 mts
69
3.15.3 Nivel de iluminancia media
Nos piden 300 lx pero teniendo en cuenta que sólo se trabaja de día y la iluminancia de
la luz solar es de 75 lux, la iluminancia proporcionada por la iluminación será:
Em = 300 - 75 =225 lx
Sistema de
Índice del local
iluminación
Iluminación
directa,
semidirecta,
directa-indirecta
y general difusa
Iluminación
indirecta y
semiindirecta
Tabla 3. 60 Índice del Local Sección 2.1
70
3.15.5 Coeficientes de reflexión
Los coeficientes del techo y las paredes se suministran en el enunciado.
Techo Paredes Suelo
Coeficiente de reflexión
70% 70% 50%
Tabla 3. 61 Coeficiente de Reflexión Sección 2.1
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
71
Figura 3. 13 Coeficientes del Local.
PARED 0.70
SUELO 0.50
72
Acudimos a la tabla de producto para el cálculo de Coeficiente de Utilización.
Techo 0.70 0.70 0.70 0.50 0
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
87 + 104 95.5
𝐶𝑢 = = = 0.955
2 100
73
3.15.8 Flujo Luminoso Total de la Sección #2.1
Luminaria 𝟇 𝑬𝒎∗𝑺
𝑻=
𝑪𝒖∗𝑭𝒎
𝟇𝑻 Flujo luminoso (Lúmenes)
Cu Coeficiente de Utilización
Fm Factor de Mantenimiento
Tabla 3. 66 Flujo Luminoso.
𝟇 (𝟐𝟐𝟓𝑳𝒙)(𝟔𝟖.𝟒𝟗𝟏𝟐𝒎𝟐 )
𝑻= =𝟐𝟎𝟏𝟕𝟎.𝟖𝟑𝟕𝟕 𝑳ú𝒎𝒆𝒏𝒆𝒔
(𝟎.𝟗𝟓𝟓)(𝟎.𝟖)
74
3.15.9 Número de Luminarias Necesarias
𝝓𝑻
𝑵=
𝒏 ∗ ∅𝑳
N Número de Luminarias
𝝓𝑻 Flujo Luminoso Total (Lúmenes)
Número de Lámparas por
N
Luminaria
𝝓𝑳 Flujo Luminoso de una Lámpara
Tabla 3. 67 Número de Luminarias Sección 2.1
𝟐𝟎𝟏𝟕𝟎. 𝟖𝟑𝟕𝟕
𝑵= = 𝟓. 𝟕𝟔𝟑𝟎 𝑳𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏 ∗ (𝟑𝟓𝟎𝟎)
3.15.10 Emplazamiento de las luminarias
Finalmente sólo nos queda distribuir las luminarias sobre la planta del local y comprobar
que la distancia de separación entre ellas es inferior a la máxima admisible. En este caso la
separación máxima viene indicada en las tablas de las luminarias.
𝑵 𝒕𝒐𝒕𝒂𝒍
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝒂𝒏𝒄𝒉𝒐
𝒍𝒂𝒓𝒈𝒐
𝟔
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝟒. 𝟓𝟔 = 𝟏. 𝟑𝟒𝟗𝟔 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏𝟓. 𝟎𝟐
𝒍𝒂𝒓𝒈𝒐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝑵 𝒂𝒏𝒄𝒉𝒐 ∗ ( )
𝒂𝒏𝒄𝒉𝒐
𝟏𝟓. 𝟎𝟐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝟏. 𝟑𝟒𝟗𝟔 ∗ ( ) = 𝟒. 𝟒𝟒𝟓𝟑 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟒. 𝟓𝟔
75
Ancho Luminaria
Núm. De Luminarias 2
Separación (m) 4.56/2=2.28 mts
Separación de las paredes (m) 2.28/2=1.14 mts
Tabla 3. 68 Distancia entre Luminarias Ancho Sección 2.1
Largo Luminaria
Núm. De Luminarias 5
Separación (m) 15.02/5=3 mts
Separación de las paredes (m) 3/2=1.5 mts
Tabla 3. 69 Distancia entre Luminarias Largo Sección 2.1
𝟏𝟎 ∗ 𝟑𝟓𝟎𝟎 ∗ 𝟎. 𝟕𝟏 ∗ 𝟎. 𝟖
𝑬= = 𝟐𝟗𝟎 𝑳𝒖𝒙
𝟏𝟓. 𝟎𝟐 ∗ 𝟒. 𝟓𝟔
76
Distancia
Tipo de Altura del
máxima
luminaria local
entre luminarias
intensiva > 10 m e 1.2 h
extensiva 6 - 10 m
Semi e 1.5 h
4-6m
extensiva
extensiva 4m e 1.6 h
distancia pared-luminaria: e/2
Tabla 3. 71 Distancia entre Luminarias Sección 2.1
Potencia 30 Watts
Lúmenes 3500 Lm
77
3.16 Instalación de Iluminación Sección 3.
Se requiere diseñar una instalación de alumbrado para un auditorio de 6 m de largo por
15.02 m de ancho y 6.25 m de altura. Para ello utilizaremos lámparas LED de 60 W de
potencia con un flujo luminoso de 7,000 lm. Respecto a las luminarias, cuya tabla del factor
de utilización 0-1, suministradas por el fabricante, se adjuntan a continuación.
Otros datos:
Los coeficientes de reflexión de paredes y techo se considerarán debido a que
los materiales empleados (superficies y estructuras metálicas) tienen coeficientes
de reflexión extremadamente bajos.
Es recomendable que el sistema de iluminación se instale por lo menos a .25 m
del techo.
El nivel de iluminación aconsejado para las actividades que se desarrollan en el
local es de 300 lux en el plano de trabajo.
3.16.1 Cálculos Luminotécnicos
Este es un ejemplo de problema resuelto con el método de los lúmenes. Tenemos un
auditorio que queremos alumbrar con una iluminación homogénea de 300 lx.
3.16.2 Datos Sección #3
Largo 6 mts
78
3.16.3 Nivel de iluminancia media
Nos piden 300 lx pero teniendo en cuenta que sólo se trabaja de día y la iluminancia de
la luz solar es de 75 lux, la iluminancia proporcionada por la iluminación será:
Em = 300 - 75 =225 lx
Sistema de
Índice del local
iluminación
Iluminación
directa,
semidirecta,
directa-indirecta
y general difusa
Iluminación
indirecta y
semiindirecta
Tabla 3. 76 Índice del Local Sección 3
79
3.16.5 Coeficientes de reflexión
Los coeficientes del techo y las paredes se suministran en el enunciado.
Techo Paredes Suelo
Coeficiente de reflexión
70% 70% 50%
Tabla 3. 77 Coeficiente de Reflexión Sección 3.
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
80
Figura 3. 14 Coeficientes del Local.
PARED 0.70
SUELO 0.50
81
Acudimos a la tabla de producto para el cálculo de Coeficiente de Utilización.
Techo 0.70 0.70 0.70 0.50 0
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
87 + 104 95.5
𝐶𝑢 = = = 0.955
2 100
82
3.16.8 Flujo Luminoso Total de la Sección #3
Luminaria 𝟇 𝑬𝒎∗𝑺
𝑻=
𝑪𝒖∗𝑭𝒎
𝟇𝑻 Flujo luminoso (Lúmenes)
Cu Coeficiente de Utilización
Fm Factor de Mantenimiento
Tabla 3. 82 Flujo Luminoso.
𝟇 (𝟐𝟐𝟓𝑳𝒙)(𝟗𝟎.𝟏𝟐𝒎𝟐 )
𝑻= =𝟑𝟓𝟔𝟗𝟖.𝟗𝟒𝟑𝟔 𝑳ú𝒎𝒆𝒏𝒆𝒔
(𝟎.𝟕𝟏)(𝟎.𝟖)
83
3.16.9 Número de Luminarias Necesarias
𝝓𝑻
𝑵=
𝒏 ∗ ∅𝑳
N Número de Luminarias
𝝓𝑻 Flujo Luminoso Total (Lúmenes)
Número de Lámparas por
N
Luminaria
𝝓𝑳 Flujo Luminoso de una Lámpara
Tabla 3. 83 Número de Luminarias.
𝟑𝟓𝟔𝟗𝟖. 𝟗𝟒𝟑𝟔
𝑵= = 𝟓 𝑳𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏 ∗ (𝟕, 𝟎𝟎𝟎)
3.16.10 Emplazamiento de las luminarias
Finalmente sólo nos queda distribuir las luminarias sobre la planta del local y comprobar
que la distancia de separación entre ellas es inferior a la máxima admisible. En este caso la
separación máxima viene indicada en las tablas de las luminarias.
𝑵 𝒕𝒐𝒕𝒂𝒍
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝒂𝒏𝒄𝒉𝒐
𝒍𝒂𝒓𝒈𝒐
𝟓
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝟔 = 𝟏. 𝟒𝟏𝟑𝟐 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏𝟓. 𝟎𝟐
𝒍𝒂𝒓𝒈𝒐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝑵 𝒂𝒏𝒄𝒉𝒐 ∗ ( )
𝒂𝒏𝒄𝒉𝒐
𝟏𝟓. 𝟎𝟐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝟏. 𝟒𝟏𝟑𝟐 ∗ ( ) = 𝟑. 𝟓𝟑 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟔
84
Ancho Luminaria
Núm. De Luminarias 2
Separación (m) 6/2=3 mts
Separación de las paredes (m) 3/2=1.5 mts
Tabla 3. 84 Distancia entre Luminarias Ancho Sección 3.
Largo Luminaria
Núm. De Luminarias 4
Separación (m) 15.02/4=3.755 mts
Separación de las paredes (m) 3.755/2=1.8775 mts
Tabla 3. 85 Distancia entre Luminarias Largo Sección 3
𝟖 ∗ 𝟕, 𝟎𝟎𝟎 ∗ 𝟎. 𝟕𝟏 ∗ 𝟎. 𝟖
𝑬= = 𝟑𝟓𝟐. 𝟗𝟓𝟏𝟔 𝑳𝒖𝒙
𝟏𝟓. 𝟎𝟐 ∗ 𝟔
85
Distancia
Tipo de Altura del
máxima
luminaria local
entre luminarias
Entensiva > 10 m e 1.2 h
Extensiva 6 - 10 m
Semi e 1.5 h
4-6m
extensiva
extensiva 4m e 1.6 h
distancia pared-luminaria: e/2
Tabla 3. 87 Distancia entre Luminarias Sección 3.
Potencia 60 Watts
Lúmenes 7,000 Lm
86
3.17 Instalación de Iluminación Sección 3.1
Se requiere diseñar una instalación de alumbrado para un auditorio de 6 m de largo por
15.02 m de ancho y 6.25 m de altura. Para ello utilizaremos lámparas LED de 30 W de
potencia con un flujo luminoso de 3500 lm. Respecto a las luminarias, cuya tabla del factor de
utilización 0-1, suministradas por el fabricante, se adjuntan a continuación.
Otros datos:
Los coeficientes de reflexión de paredes y techo se considerarán debido a que
los materiales empleados (superficies y estructuras metálicas) tienen coeficientes
de reflexión extremadamente bajos.
Es recomendable que el sistema de iluminación se instale por lo menos a .25 m
del techo.
El nivel de iluminación aconsejado para las actividades que se desarrollan en el
local es de 300 lux en el plano de trabajo.
3.17.1 Cálculos Luminotécnicos
Este es un ejemplo de problema resuelto con el método de los lúmenes. Tenemos un
auditorio que queremos alumbrar con una iluminación homogénea de 300 lx.
3.17.2 Datos Sección #3.1
Largo 6 mts
87
3.17.3 Nivel de iluminancia media
Nos piden 300 lx pero teniendo en cuenta que sólo se trabaja de día y la iluminancia de
la luz solar es de 75 lux, la iluminancia proporcionada por la iluminación será:
Em = 300 - 75 =225 lx
Sistema de
Índice del local
iluminación
Iluminación
directa,
semidirecta,
directa-indirecta
y general difusa
Iluminación
indirecta y
semiindirecta
Tabla 3. 92 Índice del Local Sección 3.1
88
3.17.5 Coeficientes de reflexión
Los coeficientes del techo y las paredes se suministran en el enunciado.
Techo Paredes Suelo
Coeficiente de reflexión
70% 70% 50%
Tabla 3. 93 Coeficiente de Reflexión Sección 3.1
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
89
Figura 3. 15 Coeficientes del Local.
PARED 0.70
SUELO 0.50
90
Acudimos a la tabla de producto para el cálculo de Coeficiente de Utilización.
Techo 0.70 0.70 0.70 0.50 0
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
87 + 104 95.5
𝐶𝑢 = = = 0.955
2 100
91
3.17.8 Flujo Luminoso Total de la Sección #3.1
Luminaria 𝟇 𝑬𝒎∗𝑺
𝑻=
𝑪𝒖∗𝑭𝒎
𝟇𝑻 Flujo luminoso (Lúmenes)
Cu Coeficiente de Utilización
Fm Factor de Mantenimiento
Tabla 3. 98 Flujo Luminoso.
𝟇 (𝟐𝟐𝟓𝑳𝒙)(𝟗𝟎.𝟏𝟐𝒎𝟐 )
𝑻= =𝟑𝟓𝟔𝟗𝟖.𝟗𝟒𝟑𝟔 𝑳ú𝒎𝒆𝒏𝒆𝒔
(𝟎.𝟕𝟏)(𝟎.𝟖)
92
3.17.9 Número de Luminarias Necesarias
𝝓𝑻
𝑵=
𝒏 ∗ ∅𝑳
N Número de Luminarias
𝝓𝑻 Flujo Luminoso Total (Lúmenes)
Número de Lámparas por
N
Luminaria
𝝓𝑳 Flujo Luminoso de una Lámpara
Tabla 3. 99 Número de Luminarias.
𝟑𝟓𝟔𝟗𝟖. 𝟗𝟒𝟑𝟔
𝑵= = 𝟏𝟎 𝑳𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏 ∗ (𝟑𝟓𝟎𝟎)
3.17.10 Emplazamiento de las luminarias
Finalmente sólo nos queda distribuir las luminarias sobre la planta del local y comprobar
que la distancia de separación entre ellas es inferior a la máxima admisible. En este caso la
separación máxima viene indicada en las tablas de las luminarias.
𝑵 𝒕𝒐𝒕𝒂𝒍
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝒂𝒏𝒄𝒉𝒐
𝒍𝒂𝒓𝒈𝒐
𝟏𝟎
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝟔 = 𝟐 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏𝟓. 𝟎𝟐
𝒍𝒂𝒓𝒈𝒐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝑵 𝒂𝒏𝒄𝒉𝒐 ∗ ( )
𝒂𝒏𝒄𝒉𝒐
𝟏𝟓. 𝟎𝟐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝟐 ∗ ( ) = 𝟓 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟔
93
Ancho Luminaria
Núm. De Luminarias 2
Separación (m) 6/2=3 mts
Separación de las paredes (m) 3/2=1.5 mts
Tabla 3. 100 Distancia entre Luminarias Ancho Sección 3.1
Largo Luminaria
Núm. De Luminarias 5
Separación (m) 15.02/4=3 mts
Separación de las paredes (m) 3/2=1.5 mts
Tabla 3. 101 Distancia entre Luminarias Largo Sección 3.1
𝟏𝟎 ∗ 𝟑𝟓𝟎𝟎 ∗ 𝟎. 𝟕𝟏 ∗ 𝟎. 𝟖
𝑬= = 𝟐𝟐𝟎. 𝟔𝟎 𝑳𝒖𝒙
𝟏𝟓. 𝟎𝟐 ∗ 𝟔
94
Distancia
Tipo de Altura del
máxima
luminaria local
entre luminarias
Entensiva > 10 m e 1.2 h
Extensiva 6 - 10 m
Semi e 1.5 h
4-6m
extensiva
extensiva 4m e 1.6 h
distancia pared-luminaria: e/2
Tabla 3. 103 Distancia entre Luminarias Sección 3.1
Potencia 30 Watts
Lúmenes 3500 Lm
H= 6 Mts E= 3 Mts
e 1.5 h= 6 Mts*1.5=9 Mts ACEPTABLE
Tabla 3. 105 Separación Sección 3 Aceptable.
95
3.18 Instalación de Iluminación Sección 4
Se requiere diseñar una instalación de alumbrado para un auditorio de 3 m de largo por
2.68 m de ancho y 2.66 m de altura. Para ello utilizaremos lámparas LED de 23 W de
potencia con un flujo luminoso de 1700 lm. Respecto a las luminarias, cuya tabla del factor de
utilización 0-1, suministradas por el fabricante, se adjuntan a continuación.
Otros datos:
Los coeficientes de reflexión de paredes y techo se considerarán debido a que
los materiales empleados (superficies y estructuras metálicas) tienen coeficientes
de reflexión extremadamente bajos.
Es recomendable que el sistema de iluminación se instale por lo menos a .25 m
del techo.
El nivel de iluminación aconsejado para las actividades que se desarrollan en el
local es de 200 lux en el plano de trabajo.
3.18.1 Cálculos Luminotécnicos
Este es un ejemplo de problema resuelto con el método de los lúmenes. Tenemos una
cocina que queremos alumbrar con una iluminación homogénea de 200 lx.
3.18.2 Datos Sección #4
Largo 3 mts
96
3.18.3 Nivel de iluminancia media
Nos piden 200 lx pero teniendo en cuenta que sólo se trabaja de día y la iluminancia de
la luz solar es de 75 lux, la iluminancia proporcionada por la iluminación será:
Em = 200 - 75 =125 lx
Sistema de
Índice del local
iluminación
Iluminación
directa,
semidirecta,
directa-indirecta
y general difusa
Iluminación
indirecta y
semiindirecta
Tabla 3. 108 Índice del Local Sección 4
97
3.18.5 Coeficientes de reflexión
Los coeficientes del techo y las paredes se suministran en el enunciado.
Techo Paredes Suelo
Coeficiente de reflexión
70% 70% 50%
Tabla 3. 109 Coeficiente de Reflexión Sección 4
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
98
Figura 3. 16 Coeficientes del Local.
PARED 0.70
SUELO 0.50
99
Acudimos a la tabla de producto para el cálculo de Coeficiente de Utilización.
Techo 0.70 0.70 0.70 0.50 0
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
87
𝐶𝑢 = = 0.87
100
100
3.18.8 Flujo Luminoso Total de la Sección #4
Luminaria 𝟇 𝑬𝒎∗𝑺
𝑻=
𝑪𝒖∗𝑭𝒎
𝟇𝑻 Flujo luminoso (Lúmenes)
Cu Coeficiente de Utilización
Fm Factor de Mantenimiento
Tabla 3. 114 Flujo Luminoso.
𝟇 (𝟏𝟐𝟓𝑳𝒙)(𝟖.𝟎𝟒𝒎𝟐 )
𝑻= =𝟐𝟎𝟗𝟑.𝟕𝟓 𝑳ú𝒎𝒆𝒏𝒆𝒔
(𝟎.𝟔)(𝟎.𝟖)
101
3.18.9 Número de Luminarias Necesarias
𝝓𝑻
𝑵=
𝒏 ∗ ∅𝑳
N Número de Luminarias
𝝓𝑻 Flujo Luminoso Total (Lúmenes)
Número de Lámparas por
N
Luminaria
𝝓𝑳 Flujo Luminoso de una Lámpara
Tabla 3. 115 Número de Luminarias.
𝟐𝟎𝟗𝟑. 𝟕𝟓
𝑵= = 𝟏. 𝟐𝟑 𝑳𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏 ∗ (𝟏𝟕𝟎𝟎)
3.18.10 Emplazamiento de las luminarias
Finalmente sólo nos queda distribuir las luminarias sobre la planta del local y comprobar
que la distancia de separación entre ellas es inferior a la máxima admisible. En este caso la
separación máxima viene indicada en las tablas de las luminarias.
𝑵 𝒕𝒐𝒕𝒂𝒍
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝒂𝒏𝒄𝒉𝒐
𝒍𝒂𝒓𝒈𝒐
𝟏. 𝟐𝟑
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝟐. 𝟔𝟖 = 𝟏. 𝟎𝟒 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟑
𝒍𝒂𝒓𝒈𝒐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝑵 𝒂𝒏𝒄𝒉𝒐 ∗ ( )
𝒂𝒏𝒄𝒉𝒐
𝟑
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝟏. 𝟎𝟒 ∗ ( ) = 𝟏. 𝟏𝟔 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟐. 𝟔𝟖
102
Ancho Luminaria
Núm. De Luminarias 1
Separación (m) 2.68/1=2.68 mts
Separación de las paredes (m) 2.68/2=1.34 mts
Tabla 3. 116 Distancia entre Luminarias Ancho Sección 4
Largo Luminaria
Núm. De Luminarias 1
Separación (m) 3/1=3 mts
Separación de las paredes (m) 3/2=1.5 mts
Tabla 3. 117 Distancia entre Luminarias Largo Sección 4
𝟏𝟕𝟎𝟎 ∗ 𝟎. 𝟔 ∗ 𝟎. 𝟖
𝑬= = 𝟏𝟎𝟏. 𝟒𝟗 𝑳𝒖𝒙
𝟐. 𝟔𝟖 ∗ 𝟑
103
Distancia
Tipo de Altura del
máxima
luminaria local
entre luminarias
Entensiva > 10 m e 1.2 h
Extensiva 6 - 10 m
Semi e 1.5 h
4-6m
extensiva
extensiva 4m e 1.6 h
distancia pared-luminaria: e/2
Tabla 3. 119 Distancia entre Luminarias Sección 4
Potencia 23 Watts
Lúmenes 1700 Lm
104
3.19 Instalación de Iluminación Sección 4.1
Se requiere diseñar una instalación de alumbrado para un auditorio de 3 m de largo por
2.68 m de ancho y 2.66 m de altura. Para ello utilizaremos lámparas LED de 36 W de
potencia con un flujo luminoso de 2870 lm. Respecto a las luminarias, cuya tabla del factor de
utilización 0-1, suministradas por el fabricante, se adjuntan a continuación.
Otros datos:
Los coeficientes de reflexión de paredes y techo se considerarán debido a que
los materiales empleados (superficies y estructuras metálicas) tienen coeficientes
de reflexión extremadamente bajos.
Es recomendable que el sistema de iluminación se instale por lo menos a .25 m
del techo.
El nivel de iluminación aconsejado para las actividades que se desarrollan en el
local es de 200 lux en el plano de trabajo.
3.19.1 Cálculos Luminotécnicos
Este es un ejemplo de problema resuelto con el método de los lúmenes. Tenemos una
cocineta que queremos alumbrar con una iluminación homogénea de 200 lx.
3.19.2 Datos Sección #4.1
Largo 3 mts
105
3.19.3 Nivel de iluminancia media
Nos piden 200 lx pero teniendo en cuenta que sólo se trabaja de día y la iluminancia de
la luz solar es de 75 lux, la iluminancia proporcionada por la iluminación será:
Em = 200 - 75 =125 lx
Sistema de
Índice del local
iluminación
Iluminación
directa,
semidirecta,
directa-indirecta
y general difusa
Iluminación
indirecta y
semiindirecta
Tabla 3. 124 Índice del Local Sección 4.1
106
3.19.5 Coeficientes de reflexión
Los coeficientes del techo y las paredes se suministran en el enunciado.
Techo Paredes Suelo
Coeficiente de reflexión
70% 70% 50%
Tabla 3. 125 Coeficiente de Reflexión Sección 4
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
107
Figura 3. 17Coeficientes del Local.
PARED 0.70
SUELO 0.50
108
Acudimos a la tabla de producto para el cálculo de Coeficiente de Utilización.
Techo 0.70 0.70 0.70 0.50 0
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
87
𝐶𝑢 = = 0.87
100
109
3.19.8 Flujo Luminoso Total de la Sección #4.1
Luminaria 𝟇 𝑬𝒎∗𝑺
𝑻=
𝑪𝒖∗𝑭𝒎
𝟇𝑻 Flujo luminoso (Lúmenes)
Cu Coeficiente de Utilización
Fm Factor de Mantenimiento
Tabla 3. 130 Flujo Luminoso.
𝟇 (𝟏𝟐𝟓𝑳𝒙)(𝟖.𝟎𝟒𝒎𝟐 )
𝑻= =𝟐𝟎𝟗𝟑.𝟕𝟓 𝑳ú𝒎𝒆𝒏𝒆𝒔
(𝟎.𝟔)(𝟎.𝟖)
110
3.19.9 Número de Luminarias Necesarias
𝝓𝑻
𝑵=
𝒏 ∗ ∅𝑳
N Número de Luminarias
𝝓𝑻 Flujo Luminoso Total (Lúmenes)
Número de Lámparas por
N
Luminaria
𝝓𝑳 Flujo Luminoso de una Lámpara
Tabla 3. 131 Número de Luminarias.
𝟐𝟎𝟗𝟑. 𝟕𝟓
𝑵= = 𝟏 𝑳𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏 ∗ (𝟐𝟖𝟕𝟎)
3.19.10 Emplazamiento de las luminarias
Finalmente sólo nos queda distribuir las luminarias sobre la planta del local y comprobar
que la distancia de separación entre ellas es inferior a la máxima admisible. En este caso la
separación máxima viene indicada en las tablas de las luminarias.
𝑵 𝒕𝒐𝒕𝒂𝒍
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝒂𝒏𝒄𝒉𝒐
𝒍𝒂𝒓𝒈𝒐
𝟏
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝟐. 𝟔𝟖 = 𝟎. 𝟗𝟒 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟑
𝒍𝒂𝒓𝒈𝒐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝑵 𝒂𝒏𝒄𝒉𝒐 ∗ ( )
𝒂𝒏𝒄𝒉𝒐
𝟑
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝟎. 𝟗𝟒 ∗ ( ) = 𝟏. 𝟎𝟓 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟐. 𝟔𝟖
111
Ancho Luminaria
Núm. De Luminarias 1
Separación (m) 2.68/1=2.68 mts
Separación de las paredes (m) 2.68/2=1.34 mts
Tabla 3. 132 Distancia entre Luminarias Ancho Sección 4.1
Largo Luminaria
Núm. De Luminarias 1
Separación (m) 3/1=3 mts
Separación de las paredes (m) 3/2=1.5 mts
Tabla 3. 133 Distancia entre Luminarias Largo Sección 4.1
𝟐𝟖𝟕𝟎 ∗ 𝟎. 𝟔 ∗ 𝟎. 𝟖
𝑬= = 𝟏𝟕𝟏. 𝟑𝟒𝟑𝟐 𝑳𝒖𝒙
𝟐. 𝟔𝟖 ∗ 𝟑
112
Distancia
Tipo de Altura del
máxima
luminaria local
entre luminarias
Entensiva > 10 m e 1.2 h
Extensiva 6 - 10 m
Semi e 1.5 h
4-6m
extensiva
extensiva 4m e 1.6 h
distancia pared-luminaria: e/2
Tabla 3. 135 Distancia entre Luminarias Sección 4.1
Potencia 36 Watts
Lúmenes 2870 Lm
113
3.20 Instalación de Iluminación Sección 5
Se requiere diseñar una instalación de alumbrado para un auditorio de 3.63 m de largo
por 1.05 m de ancho y 2.66 m de altura. Para ello utilizaremos lámparas LED de 4 W de
potencia con un flujo luminoso de 270 lm. Respecto a las luminarias, cuya tabla del factor de
utilización 0-1, suministradas por el fabricante, se adjuntan a continuación.
Otros datos:
Los coeficientes de reflexión de paredes y techo se considerarán debido a que
los materiales empleados (superficies y estructuras metálicas) tienen coeficientes
de reflexión extremadamente bajos.
Es recomendable que el sistema de iluminación se instale por lo menos a .25 m
del techo.
El nivel de iluminación aconsejado para las actividades que se desarrollan en el
local es de 100 lux en el plano de trabajo.
3.20.1 Cálculos Luminotécnicos
Este es un ejemplo de problema resuelto con el método de los lúmenes. Tenemos un
recibidor que queremos alumbrar con una iluminación homogénea de 100 lx.
3.20.2 Datos Sección #5
Largo 3.63 mts
114
3.20.3 Nivel de iluminancia media
Nos piden 100 lx
Em = 100 lx
Sistema de
Índice del local
iluminación
Iluminación
directa,
semidirecta,
directa-indirecta
y general difusa
Iluminación
indirecta y
semiindirecta
Tabla 3. 140 Índice del Local Sección 5
115
3.20.5 Coeficientes de reflexión
Los coeficientes del techo y las paredes se suministran en el enunciado.
Techo Paredes Suelo
Coeficiente de reflexión
70% 70% 50%
Tabla 3. 141 Coeficiente de Reflexión Sección 5
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
116
Figura 3. 18 Coeficientes del Local.
PARED 0.70
SUELO 0.50
117
Acudimos a la tabla de producto para el cálculo de Coeficiente de Utilización.
Techo 0.70 0.70 0.70 0.50 0
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
87
𝐶𝑢 = = 0.87
100
118
3.20.8 Flujo Luminoso Total de la Sección #5
Luminaria 𝟇 𝑬𝒎∗𝑺
𝑻=
𝑪𝒖∗𝑭𝒎
𝟇𝑻 Flujo luminoso (Lúmenes)
Cu Coeficiente de Utilización
Fm Factor de Mantenimiento
Tabla 3. 146 Flujo Luminoso.
𝟇 (𝟏𝟎𝟎𝑳𝒙)(𝟑.𝟖𝟏𝟏𝟓𝒎𝟐 )
𝑻= =𝟕𝟗𝟒.𝟎𝟔𝟐𝟓 𝑳ú𝒎𝒆𝒏𝒆𝒔
(𝟎.𝟔)(𝟎.𝟖)
119
3.20.9 Número de Luminarias Necesarias
𝝓𝑻
𝑵=
𝒏 ∗ ∅𝑳
N Número de Luminarias
𝝓𝑻 Flujo Luminoso Total (Lúmenes)
Número de Lámparas por
N
Luminaria
𝝓𝑳 Flujo Luminoso de una Lámpara
Tabla 3. 147 Número de Luminarias.
𝟕𝟗𝟒. 𝟎𝟔𝟐𝟓
𝑵= = 𝟐. 𝟗𝟒 𝑳𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏 ∗ (𝟐𝟕𝟎)
3.20.10 Emplazamiento de las luminarias
Finalmente sólo nos queda distribuir las luminarias sobre la planta del local y comprobar
que la distancia de separación entre ellas es inferior a la máxima admisible. En este caso la
separación máxima viene indicada en las tablas de las luminarias.
𝑵 𝒕𝒐𝒕𝒂𝒍
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝒂𝒏𝒄𝒉𝒐
𝒍𝒂𝒓𝒈𝒐
𝟐. 𝟗𝟒
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝟏. 𝟎𝟓 = 𝟏 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟑. 𝟔𝟑
𝒍𝒂𝒓𝒈𝒐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝑵 𝒂𝒏𝒄𝒉𝒐 ∗ ( )
𝒂𝒏𝒄𝒉𝒐
𝟑. 𝟔𝟑
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝟏 ∗ ( ) = 𝟑. 𝟒𝟓 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏. 𝟎𝟓
120
Ancho Luminaria
Núm. De Luminarias 1
Separación (m) 1.05/1=1.05 mts
Separación de las paredes (m) 1.05/2=0.525 mts
Tabla 3. 148 Distancia entre Luminarias Ancho Sección 5
Largo Luminaria
Núm. De Luminarias 3
Separación (m) 3.63/3=1.21 mts
Separación de las paredes (m) 1.21/2=0.605 mts
Tabla 3. 149 Distancia entre Luminarias Largo Sección 5
𝟑 ∗ 𝟐𝟕𝟎 ∗ 𝟎. 𝟔 ∗ 𝟎. 𝟖
𝑬= = 𝟏𝟎𝟐 𝑳𝒖𝒙
𝟏. 𝟎𝟓 ∗ 𝟑. 𝟔𝟑
121
Distancia
Tipo de Altura del
máxima
luminaria local
entre luminarias
Entensiva > 10 m e 1.2 h
Extensiva 6 - 10 m
Semi e 1.5 h
4-6m
extensiva
extensiva 4m e 1.6 h
distancia pared-luminaria: e/2
Tabla 3. 151 Distancia entre Luminarias Sección 5
Potencia 4 Watts
Lúmenes 270 Lm
122
3.21 Instalación de Iluminación Sección 5.1
Se requiere diseñar una instalación de alumbrado para un auditorio de 3.63 m de largo
por 1.05 m de ancho y 2.66 m de altura. Para ello utilizaremos lámparas LED de 5 W de
potencia con un flujo luminoso de 250 lm. Respecto a las luminarias, cuya tabla del factor de
utilización 0-1, suministradas por el fabricante, se adjuntan a continuación.
Otros datos:
Los coeficientes de reflexión de paredes y techo se considerarán debido a que
los materiales empleados (superficies y estructuras metálicas) tienen coeficientes
de reflexión extremadamente bajos.
Es recomendable que el sistema de iluminación se instale por lo menos a .25 m
del techo.
El nivel de iluminación aconsejado para las actividades que se desarrollan en el
local es de 100 lux en el plano de trabajo.
3.21.1 Cálculos Luminotécnicos
Este es un ejemplo de problema resuelto con el método de los lúmenes. Tenemos un
recibidor que queremos alumbrar con una iluminación homogénea de 100 lx.
3.21.2 Datos Sección #5.1
Largo 3.63 mts
123
3.21.3 Nivel de iluminancia media
Nos piden 100 lx
Em = 100 lx
Sistema de
Índice del local
iluminación
Iluminación
directa,
semidirecta,
directa-indirecta
y general difusa
Iluminación
indirecta y
semiindirecta
Tabla 3. 156 Índice del Local Sección 5.1
124
3.21.5 Coeficientes de reflexión
Los coeficientes del techo y las paredes se suministran en el enunciado.
Techo Paredes Suelo
Coeficiente de reflexión
70% 70% 50%
Tabla 3. 157 Coeficiente de Reflexión Sección 5.1
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
125
Figura 3. 19 Coeficientes del Local.
PARED 0.70
SUELO 0.50
126
Acudimos a la tabla de producto para el cálculo de Coeficiente de Utilización.
Techo 0.70 0.70 0.70 0.50 0
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
87
𝐶𝑢 = = 0.87
100
127
3.21.8 Flujo Luminoso Total de la Sección #5.1
Luminaria 𝟇 𝑬𝒎∗𝑺
𝑻=
𝑪𝒖∗𝑭𝒎
𝟇𝑻 Flujo luminoso (Lúmenes)
Cu Coeficiente de Utilización
Fm Factor de Mantenimiento
Tabla 3. 162 Flujo Luminoso.
𝟇 (𝟏𝟎𝟎𝑳𝒙)(𝟑.𝟖𝟏𝟏𝟓𝒎𝟐 )
𝑻= =𝟕𝟗𝟒.𝟎𝟔𝟐𝟓 𝑳ú𝒎𝒆𝒏𝒆𝒔
(𝟎.𝟔)(𝟎.𝟖)
128
3.21.9 Número de Luminarias Necesarias
𝝓𝑻
𝑵=
𝒏 ∗ ∅𝑳
N Número de Luminarias
𝝓𝑻 Flujo Luminoso Total (Lúmenes)
Número de Lámparas por
N
Luminaria
𝝓𝑳 Flujo Luminoso de una Lámpara
Tabla 3. 163 Número de Luminarias.
𝟕𝟗𝟒. 𝟎𝟔𝟐𝟓
𝑵= = 𝟑. 𝟏𝟕 𝑳𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏 ∗ (𝟐𝟓𝟎)
3.21.10 Emplazamiento de las luminarias
Finalmente sólo nos queda distribuir las luminarias sobre la planta del local y comprobar
que la distancia de separación entre ellas es inferior a la máxima admisible. En este caso la
separación máxima viene indicada en las tablas de las luminarias.
𝑵 𝒕𝒐𝒕𝒂𝒍
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝒂𝒏𝒄𝒉𝒐
𝒍𝒂𝒓𝒈𝒐
𝟑. 𝟏𝟕
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝟏. 𝟎𝟓 = 𝟏 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟑. 𝟔𝟑
𝒍𝒂𝒓𝒈𝒐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝑵 𝒂𝒏𝒄𝒉𝒐 ∗ ( )
𝒂𝒏𝒄𝒉𝒐
𝟑. 𝟔𝟑
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝟏 ∗ ( ) = 𝟑. 𝟒𝟓 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏. 𝟎𝟓
129
Ancho Luminaria
Núm. De Luminarias 1
Separación (m) 1.05/1=1.05 mts
Separación de las paredes (m) 1.05/2=0.525 mts
Tabla 3. 164 Distancia entre Luminarias Ancho Sección 5.1
Largo Luminaria
Núm. De Luminarias 4
Separación (m) 3.63/4=0.90 mts
Separación de las paredes (m) 0.90/2=0.45 mts
Tabla 3. 165 Distancia entre Luminarias Largo Sección 5.1
𝟒 ∗ 𝟐𝟓𝟎 ∗ 𝟎. 𝟔 ∗ 𝟎. 𝟖
𝑬= = 𝟏𝟐𝟓. 𝟗𝟑 𝑳𝒖𝒙
𝟏. 𝟎𝟓 ∗ 𝟑. 𝟔𝟑
130
Distancia
Tipo de Altura del
máxima
luminaria local
entre luminarias
Entensiva > 10 m e 1.2 h
Extensiva 6 - 10 m
Semi e 1.5 h
4-6m
extensiva
extensiva 4m e 1.6 h
distancia pared-luminaria: e/2
Tabla 3. 167 Distancia entre Luminarias Sección 5.1
Potencia 5 Watts
Lúmenes 250 Lm
131
3.22 Instalación de Iluminación Sección 6
Se requiere diseñar una instalación de alumbrado para un auditorio de 2.86 m de largo
por 1.34 m de ancho y 2.66 m de altura. Para ello utilizaremos lámparas LED de 4 W de
potencia con un flujo luminoso de 270 lm. Respecto a las luminarias, cuya tabla del factor de
utilización 0-1, suministradas por el fabricante, se adjuntan a continuación.
Otros datos:
Los coeficientes de reflexión de paredes y techo se considerarán debido a que
los materiales empleados (superficies y estructuras metálicas) tienen coeficientes
de reflexión extremadamente bajos.
Es recomendable que el sistema de iluminación se instale por lo menos a .25 m
del techo.
El nivel de iluminación aconsejado para las actividades que se desarrollan en el
local es de 100 lux en el plano de trabajo.
3.22.1 Cálculos Luminotécnicos
Este es un ejemplo de problema resuelto con el método de los lúmenes. Tenemos un
recibidor que queremos alumbrar con una iluminación homogénea de 100 lx.
3.22.2 Datos Sección #6
Largo 2.86 mts
132
3.22.3 Nivel de iluminancia media
Nos piden 100 lx
Em = 100 lx
Sistema de
Índice del local
iluminación
Iluminación
directa,
semidirecta,
directa-indirecta
y general difusa
Iluminación
indirecta y
semiindirecta
Tabla 3. 172 Índice del Local Sección 6
133
3.22.5 Coeficientes de reflexión
Los coeficientes del techo y las paredes se suministran en el enunciado.
Techo Paredes Suelo
Coeficiente de reflexión
70% 70% 50%
Tabla 3. 173 Coeficiente de Reflexión Sección 6
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
134
Figura 3. 20 Coeficientes del Local.
PARED 0.70
SUELO 0.50
135
Acudimos a la tabla de producto para el cálculo de Coeficiente de Utilización.
Techo 0.70 0.70 0.70 0.50 0
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
87
𝐶𝑢 = = 0.87
100
136
3.22.8 Flujo Luminoso Total de la Sección #6
Luminaria 𝟇 𝑬𝒎∗𝑺
𝑻=
𝑪𝒖∗𝑭𝒎
𝟇𝑻 Flujo luminoso (Lúmenes)
Cu Coeficiente de Utilización
Fm Factor de Mantenimiento
Tabla 3. 178 Flujo Luminoso.
𝟇 (𝟏𝟎𝟎𝑳𝒙)(𝟑.𝟖𝟑𝟐𝟒𝒎𝟐 )
𝑻= =𝟕𝟗𝟖.𝟒𝟏𝟔𝟔 𝑳ú𝒎𝒆𝒏𝒆𝒔
(𝟎.𝟔)(𝟎.𝟖)
137
3.22.9 Número de Luminarias Necesarias
𝝓𝑻
𝑵=
𝒏 ∗ ∅𝑳
N Número de Luminarias
𝝓𝑻 Flujo Luminoso Total (Lúmenes)
Número de Lámparas por
N
Luminaria
𝝓𝑳 Flujo Luminoso de una Lámpara
Tabla 3. 179 Número de Luminarias.
𝟕𝟗𝟖. 𝟒𝟏𝟔𝟔
𝑵= = 𝟐. 𝟗𝟓 𝑳𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏 ∗ (𝟐𝟕𝟎)
3.22.10 Emplazamiento de las luminarias
Finalmente sólo nos queda distribuir las luminarias sobre la planta del local y comprobar
que la distancia de separación entre ellas es inferior a la máxima admisible. En este caso la
separación máxima viene indicada en las tablas de las luminarias.
𝑵 𝒕𝒐𝒕𝒂𝒍
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝒂𝒏𝒄𝒉𝒐
𝒍𝒂𝒓𝒈𝒐
𝟐. 𝟗𝟓
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝟏. 𝟑𝟒 = 𝟏. 𝟏𝟕𝟓𝟔 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟐. 𝟖𝟔
𝒍𝒂𝒓𝒈𝒐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝑵 𝒂𝒏𝒄𝒉𝒐 ∗ ( )
𝒂𝒏𝒄𝒉𝒐
𝟐. 𝟖𝟔
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝟏. 𝟏𝟕𝟓𝟔 ∗ ( ) = 𝟐. 𝟓𝟎 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏. 𝟑𝟐
138
Ancho Luminaria
Núm. De Luminarias 1
Separación (m) 1.34/1=1.34 mts
Separación de las paredes (m) 1.34/2=0.0.67 mts
Tabla 3. 180 Distancia entre Luminarias Ancho Sección 6
Largo Luminaria
Núm. De Luminarias 3
Separación (m) 2.86/3=0.95 mts
Separación de las paredes (m) 0.95/2=0.476 mts
Tabla 3. 181 Distancia entre Luminarias Largo Sección 6
𝟑 ∗ 𝟐𝟕𝟎 ∗ 𝟎. 𝟔 ∗ 𝟎. 𝟖
𝑬= = 𝟏𝟎𝟏 𝑳𝒖𝒙
𝟏. 𝟑𝟒 ∗ 𝟐. 𝟖𝟔
139
Distancia
Tipo de Altura del
máxima
luminaria local
entre luminarias
Entensiva > 10 m e 1.2 h
Extensiva 6 - 10 m
Semi e 1.5 h
4-6m
extensiva
extensiva 4m e 1.6 h
distancia pared-luminaria: e/2
Tabla 3. 183 Distancia entre Luminarias Sección 6
Potencia 4 Watts
Lúmenes 270 Lm
140
3.23 Instalación de Iluminación Sección 6.1
Se requiere diseñar una instalación de alumbrado para un auditorio de 2.86 m de largo
por 1.34 m de ancho y 2.66 m de altura. Para ello utilizaremos lámparas LED de 5 W de
potencia con un flujo luminoso de 250 lm. Respecto a las luminarias, cuya tabla del factor de
utilización 0-1, suministradas por el fabricante, se adjuntan a continuación.
Otros datos:
Los coeficientes de reflexión de paredes y techo se considerarán debido a que
los materiales empleados (superficies y estructuras metálicas) tienen coeficientes
de reflexión extremadamente bajos.
Es recomendable que el sistema de iluminación se instale por lo menos a .25 m
del techo.
El nivel de iluminación aconsejado para las actividades que se desarrollan en el
local es de 100 lux en el plano de trabajo.
3.23.1 Cálculos Luminotécnicos
Este es un ejemplo de problema resuelto con el método de los lúmenes. Tenemos un
recibidor que queremos alumbrar con una iluminación homogénea de 100 lx.
3.23.2 Datos Sección #6.1
Largo 2.86 mts
141
3.23.3 Nivel de iluminancia media
Nos piden 100 lx
Em = 100 lx
Sistema de
Índice del local
iluminación
Iluminación
directa,
semidirecta,
directa-indirecta
y general difusa
Iluminación
indirecta y
semiindirecta
Tabla 3. 188 Índice del Local Sección 6.1
142
3.23.5 Coeficientes de reflexión
Los coeficientes del techo y las paredes se suministran en el enunciado.
Techo Paredes Suelo
Coeficiente de reflexión
70% 70% 50%
Tabla 3. 189 Coeficiente de Reflexión Sección 6.1
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
143
Figura 3. 21 Coeficientes del Local.
PARED 0.70
SUELO 0.50
144
Acudimos a la tabla de producto para el cálculo de Coeficiente de Utilización.
Techo 0.70 0.70 0.70 0.50 0
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
87
𝐶𝑢 = = 0.87
100
145
3.23.8 Flujo Luminoso Total de la Sección #6.1
Luminaria 𝟇 𝑬𝒎∗𝑺
𝑻=
𝑪𝒖∗𝑭𝒎
𝟇𝑻 Flujo luminoso (Lúmenes)
Cu Coeficiente de Utilización
Fm Factor de Mantenimiento
Tabla 3. 194 Flujo Luminoso.
𝟇 (𝟏𝟎𝟎𝑳𝒙)(𝟑.𝟖𝟑𝟐𝟒𝒎𝟐 )
𝑻= =𝟕𝟗𝟖.𝟒𝟏𝟔𝟔 𝑳ú𝒎𝒆𝒏𝒆𝒔
(𝟎.𝟔)(𝟎.𝟖)
146
3.23.9 Número de Luminarias Necesarias
𝝓𝑻
𝑵=
𝒏 ∗ ∅𝑳
N Número de Luminarias
𝝓𝑻 Flujo Luminoso Total (Lúmenes)
Número de Lámparas por
N
Luminaria
𝝓𝑳 Flujo Luminoso de una Lámpara
Tabla 3. 195 Número de Luminarias.
𝟕𝟗𝟖. 𝟒𝟏𝟔𝟔
𝑵= = 𝟑. 𝟏𝟗 𝑳𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏 ∗ (𝟐𝟓𝟎)
3.23.10 Emplazamiento de las luminarias
Finalmente sólo nos queda distribuir las luminarias sobre la planta del local y comprobar
que la distancia de separación entre ellas es inferior a la máxima admisible. En este caso la
separación máxima viene indicada en las tablas de las luminarias.
𝑵 𝒕𝒐𝒕𝒂𝒍
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝒂𝒏𝒄𝒉𝒐
𝒍𝒂𝒓𝒈𝒐
𝟑. 𝟏𝟗
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝟏. 𝟑𝟒 = 𝟏. 𝟐𝟐 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟐. 𝟖𝟔
𝒍𝒂𝒓𝒈𝒐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝑵 𝒂𝒏𝒄𝒉𝒐 ∗ ( )
𝒂𝒏𝒄𝒉𝒐
𝟐. 𝟖𝟔
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝟏. 𝟐𝟐 ∗ ( ) = 𝟐. 𝟔𝟎 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏. 𝟑𝟒
147
Ancho Luminaria
Núm. De Luminarias 1
Separación (m) 1.34/1=1.34 mts
Separación de las paredes (m) 1.34/2=0.67 mts
Tabla 3. 196 Distancia entre Luminarias Ancho Sección 6.1
Largo Luminaria
Núm. De Luminarias 4
Separación (m) 2.86/4=0.715 mts
Separación de las paredes (m) 0.715/2=0.3575 mts
Tabla 3. 197 Distancia entre Luminarias Largo Sección 6.1
𝟒 ∗ 𝟐𝟓𝟎 ∗ 𝟎. 𝟔 ∗ 𝟎. 𝟖
𝑬= = 𝟏𝟐𝟓. 𝟐𝟒𝟕𝟖 𝑳𝒖𝒙
𝟏. 𝟎𝟓 ∗ 𝟑. 𝟔𝟑
148
Distancia
Tipo de Altura del
máxima
luminaria local
entre luminarias
Entensiva > 10 m e 1.2 h
Extensiva 6 - 10 m
Semi e 1.5 h
4-6m
extensiva
extensiva 4m e 1.6 h
distancia pared-luminaria: e/2
Tabla 3. 199 Distancia entre Luminarias Sección 6.1
Potencia 5 Watts
Lúmenes 250 Lm
149
3.24 Instalación de Iluminación Sección 7
Se requiere diseñar una instalación de alumbrado para un auditorio de 1.28 m de largo
por 0.71 m de ancho y 2.66 m de altura. Para ello utilizaremos lámparas LED de 1 W de
potencia con un flujo luminoso de 36 lm. Respecto a las luminarias, cuya tabla del factor de
utilización 0-1, suministradas por el fabricante, se adjuntan a continuación.
Otros datos:
Los coeficientes de reflexión de paredes y techo se considerarán debido a que
los materiales empleados (superficies y estructuras metálicas) tienen coeficientes
de reflexión extremadamente bajos.
Es recomendable que el sistema de iluminación se instale por lo menos a .25 m
del techo.
El nivel de iluminación aconsejado para las actividades que se desarrollan en el
local es de 50 lux en el plano de trabajo.
3.24.1 Cálculos Luminotécnicos
Este es un ejemplo de problema resuelto con el método de los lúmenes. Tenemos un
recibidor que queremos alumbrar con una iluminación homogénea de 50 lx.
3.24.2 Datos Sección #7
Largo 1.28 mts
150
3.24.3 Nivel de iluminancia media
Nos piden 50 lx para alumbrar las casetas que contengan el baño.
Em = 50 lx
Sistema de
Índice del local
iluminación
Iluminación
directa,
semidirecta,
directa-indirecta
y general difusa
Iluminación
indirecta y
semiindirecta
Tabla 3. 204 Índice del Local Sección 7
151
3.24.5 Coeficientes de reflexión
Los coeficientes del techo y las paredes se suministran en el enunciado.
Techo Paredes Suelo
Coeficiente de reflexión
70% 70% 50%
Tabla 3. 205 Coeficiente de Reflexión Sección 7
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
152
Figura 3. 22 Coeficientes del Local.
PARED 0.70
SUELO 0.50
153
Acudimos a la tabla de producto para el cálculo de Coeficiente de Utilización.
Techo 0.70 0.70 0.70 0.50 0
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
87
𝐶𝑢 = = 0.87
100
154
3.24.8 Flujo Luminoso Total de la Sección #7
Luminaria 𝟇 𝑬𝒎∗𝑺
𝑻=
𝑪𝒖∗𝑭𝒎
𝟇𝑻 Flujo luminoso (Lúmenes)
Cu Coeficiente de Utilización
Fm Factor de Mantenimiento
Tabla 3. 210 Flujo Luminoso.
𝟇 (𝟓𝟎𝑳𝒙)(𝟎.𝟗𝟎𝒎𝟐 )
𝑻= =𝟗𝟑.𝟕𝟓 𝑳ú𝒎𝒆𝒏𝒆𝒔
(𝟎.𝟔)(𝟎.𝟖)
155
3.24.9 Número de Luminarias Necesarias
𝝓𝑻
𝑵=
𝒏 ∗ ∅𝑳
N Número de Luminarias
𝝓𝑻 Flujo Luminoso Total (Lúmenes)
Número de Lámparas por
N
Luminaria
𝝓𝑳 Flujo Luminoso de una Lámpara
Tabla 3. 211 Número de Luminarias.
𝟗𝟑. 𝟕𝟓
𝑵= = 𝟐. 𝟔𝟎 𝑳𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏 ∗ (𝟑𝟔)
3.24.10 Emplazamiento de las luminarias
Finalmente sólo nos queda distribuir las luminarias sobre la planta del local y comprobar
que la distancia de separación entre ellas es inferior a la máxima admisible. En este caso la
separación máxima viene indicada en las tablas de las luminarias.
𝑵 𝒕𝒐𝒕𝒂𝒍
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝒂𝒏𝒄𝒉𝒐
𝒍𝒂𝒓𝒈𝒐
𝟐. 𝟔𝟎
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝟎. 𝟕𝟏 = 𝟏. 𝟐 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏. 𝟐𝟖
𝒍𝒂𝒓𝒈𝒐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝑵 𝒂𝒏𝒄𝒉𝒐 ∗ ( )
𝒂𝒏𝒄𝒉𝒐
𝟏. 𝟐𝟖
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝟏. 𝟐𝟎 ∗ ( ) = 𝟐. 𝟏𝟔 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟎. 𝟕𝟏
156
Ancho Luminaria
Núm. De Luminarias 1
Separación (m) 0.71/1=0.71 mts
Separación de las paredes (m) 0.71/2=0.355mts
Tabla 3. 212 Distancia entre Luminarias Ancho Sección 7
Largo Luminaria
Núm. De Luminarias 3
Separación (m) 1.28/3=0.42 mts
Separación de las paredes (m) 0.42/2=0.21 mts
Tabla 3. 213 Distancia entre Luminarias Largo Sección 7
𝟑 ∗ 𝟑𝟔 ∗ 𝟎. 𝟔 ∗ 𝟎. 𝟖
𝑬= = 𝟏𝟎𝟐 𝑳𝒖𝒙
𝟏. 𝟐𝟖 ∗ 𝟎. 𝟕𝟏
157
Distancia
Tipo de Altura del
máxima
luminaria local
entre luminarias
Entensiva > 10 m e 1.2 h
Extensiva 6 - 10 m
Semi e 1.5 h
4-6m
extensiva
extensiva 4m e 1.6 h
distancia pared-luminaria: e/2
Tabla 3. 215 Distancia entre Luminarias Sección 7
Potencia 1 Watts
Lúmenes 36 Lm
158
3.25 Instalación de Iluminación Sección 7.1
Se requiere diseñar una instalación de alumbrado para un auditorio de 1.28 m de largo
por 0.71 m de ancho y 2.66 m de altura. Para ello utilizaremos lámparas LED de 2.8 W de
potencia con un flujo luminoso de 240 lm. Respecto a las luminarias, cuya tabla del factor de
utilización 0-1, suministradas por el fabricante, se adjuntan a continuación.
Otros datos:
Los coeficientes de reflexión de paredes y techo se considerarán debido a que
los materiales empleados (superficies y estructuras metálicas) tienen coeficientes
de reflexión extremadamente bajos.
Es recomendable que el sistema de iluminación se instale por lo menos a .25 m
del techo.
El nivel de iluminación aconsejado para las actividades que se desarrollan en el
local es de 50 lux en el plano de trabajo.
3.25.1 Cálculos Luminotécnicos
Este es un ejemplo de problema resuelto con el método de los lúmenes. Tenemos un
recibidor que queremos alumbrar con una iluminación homogénea de 50 lx.
3.25.2 Datos Sección #7.1
Largo 1.28 mts
159
3.25.3 Nivel de iluminancia media
Nos piden 50 lx para alumbrar las casetas que contengan el baño.
Em = 50 lx
Sistema de
Índice del local
iluminación
Iluminación
directa,
semidirecta,
directa-indirecta
y general difusa
Iluminación
indirecta y
semiindirecta
Tabla 3. 220 Índice del Local Sección 7.1
160
3.25.5 Coeficientes de reflexión
Los coeficientes del techo y las paredes se suministran en el enunciado.
Techo Paredes Suelo
Coeficiente de reflexión
70% 70% 50%
Tabla 3. 221 Coeficiente de Reflexión Sección 7.1
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
161
Figura 3. 23Coeficientes del Local.
PARED 0.70
SUELO 0.50
162
Acudimos a la tabla de producto para el cálculo de Coeficiente de Utilización.
Techo 0.70 0.70 0.70 0.50 0
Índice del
Local
K 0.6 87 69 62 61 59
K 1.0 104 83 76 74 71
K 1.5 118 93 88 84 81
87
𝐶𝑢 = = 0.87
100
163
3.25.8 Flujo Luminoso Total de la Sección #7.1
Luminaria 𝟇 𝑬𝒎∗𝑺
𝑻=
𝑪𝒖∗𝑭𝒎
𝟇𝑻 Flujo luminoso (Lúmenes)
Cu Coeficiente de Utilización
Fm Factor de Mantenimiento
Tabla 3. 226 Flujo Luminoso.
𝟇 (𝟓𝟎𝑳𝒙)(𝟎.𝟗𝟎𝒎𝟐 )
𝑻= =𝟗𝟑.𝟕𝟓 𝑳ú𝒎𝒆𝒏𝒆𝒔
(𝟎.𝟔)(𝟎.𝟖)
164
3.25.9 Número de Luminarias Necesarias
𝝓𝑻
𝑵=
𝒏 ∗ ∅𝑳
N Número de Luminarias
𝝓𝑻 Flujo Luminoso Total (Lúmenes)
Número de Lámparas por
N
Luminaria
𝝓𝑳 Flujo Luminoso de una Lámpara
Tabla 3. 227 Número de Luminarias.
𝟗𝟑. 𝟕𝟓
𝑵= = 𝟎. 𝟒 𝑳𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏 ∗ (𝟐𝟒𝟎)
3.24.10 Emplazamiento de las luminarias
Finalmente sólo nos queda distribuir las luminarias sobre la planta del local y comprobar
que la distancia de separación entre ellas es inferior a la máxima admisible. En este caso la
separación máxima viene indicada en las tablas de las luminarias.
𝑵 𝒕𝒐𝒕𝒂𝒍
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝒂𝒏𝒄𝒉𝒐
𝒍𝒂𝒓𝒈𝒐
𝟎. 𝟒
𝑵 𝒂𝒏𝒄𝒉𝒐 = √ ∗ 𝟎. 𝟕𝟏 = 𝟎. 𝟒𝟕 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟏. 𝟐𝟖
𝒍𝒂𝒓𝒈𝒐
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝑵 𝒂𝒏𝒄𝒉𝒐 ∗ ( )
𝒂𝒏𝒄𝒉𝒐
𝟏. 𝟐𝟖
𝑵 𝒍𝒂𝒓𝒈𝒐 = 𝟎. 𝟒𝟕 ∗ ( ) = 𝟎. 𝟖𝟒 𝒍𝒖𝒎𝒊𝒏𝒂𝒓𝒊𝒂𝒔
𝟎. 𝟕𝟏
165
Ancho Luminaria
Núm. De Luminarias 1
Separación (m) 0.71/1=0.71 mts
Separación de las paredes (m) 0.71/2=0.355mts
Tabla 3. 228 Distancia entre Luminarias Ancho Sección 7.1
Largo Luminaria
Núm. De Luminarias 1
Separación (m) 1.28/1=1.28 mts
Separación de las paredes (m) 1.28/2=0.64 mts
Tabla 3. 229 Distancia entre Luminarias Largo Sección 7.1
𝟐𝟒𝟎 ∗ 𝟎. 𝟔 ∗ 𝟎. 𝟖
𝑬= = 𝟏𝟐𝟔. 𝟕𝟔 𝑳𝒖𝒙
𝟏. 𝟐𝟖 ∗ 𝟎. 𝟕𝟏
166
Distancia
Tipo de Altura del
máxima
luminaria local
entre luminarias
Entensiva > 10 m e 1.2 h
Extensiva 6 - 10 m
Semi e 1.5 h
4-6m
extensiva
extensiva 4m e 1.6 h
distancia pared-luminaria: e/2
Tabla 3. 231 Distancia entre Luminarias Sección 7.1
Lúmenes 240 Lm
167
3.26 Distribución de las luminarias
Las luminarias, se han distribuido sobre la zona a iluminar de la forma más uniforme u
homogénea posible, teniendo también en cuenta el factor estético de la instalación. El resumen
de la distribución es la siguiente:
Zona Luminaria # De Luminarias Potencia Inst.
M2300S MAGG
1 23w
Cocineta (4) 23w 1700Lm
SQ5SSD MAGG
3 12w
Recibidor (5) 4w 270Lm
SQ5SSD MAGG
6 24w
Pasillo (6) 4w 270Lm
CRICKET MAGG
18 18w
Baño (7) 1W 36Lm
168
# De Luminarias Potencia Inst.
46 1157 w
M3600 S MAGG
Cocineta 1 36
(4.1) 36w 2870Lm
FLASH C REDONDO
6 16.8w
Baño (7.1) 2.8w 240Lm
169
# De Luminarias Potencia Inst.
51 1072.8w
Teniendo en cuenta todos estos factores se empieza a realizar los cálculos necesarios.
Primero que nada se tiene que medir las dimensiones donde se desea colocar
iluminación exterior, dicha iluminación rodea al auditorio José Suárez.
170
3.28 Plano Cartesiano de la zona exterior #1 a iluminar
171
3.29 Cálculo del Área Exterior 1.
0.16 12.03 20.48
Á𝑟𝑒𝑎 = ∫ 𝑓 (𝑥 )𝑑𝑥 + ∫ 𝑔 (𝑥 )𝑑𝑥 + ∫ 𝑞 (𝑥)𝑑𝑥 ( 1)
0 0.16 12.03
Si se tienen varias funciones sumándose o restándose entre ellas, simplemente hay que
integrar de manera independiente a cada una.
La presente tiene por objeto justificar el cálculo del área de las sección exterior #1. Para
realizar los cálculos he empleado integrales, los cuales posteriormente han sido analizados,
comprobados.
𝑌2 − 𝑌1
𝑌 − 𝑌1 = (𝑋 − 𝑋1) ( 2)
𝑋2 − 𝑋1
Sean (x1, y1) y (x2, y2) dos puntos de una recta. En base a estos dos puntos conocidos
de una recta, es posible determinar su ecuación
4.71 − 0
𝑌−0= (𝑋 − 0)
0.16 − 0
471 ( 3)
𝑓(𝑥) = (𝑋)
16
4.24 − 4.71
𝑌 − 4.71 = (𝑋 − 0.16) ( 4)
12.03 − 0.16
172
47
𝑌 − 4.71 = − (𝑋 − 0.16)
1187
47 188
− (−0.16) =
1187 29675
47
− (𝑥)
1187
188
+ 4.71 = 4.7163
29675
47
𝑔 (𝑥 ) = − (𝑥) + 4.7163
1187
0 − 9.02
𝑌 − 9.02 = (𝑋 − 12.03)
20.48 − 12.03
902
𝑌 − 9.02 = − (𝑋 − 0.16)
845
902
− (−12.03) = 12.8414
845
902 ( 5)
− (𝑥)
845
902
𝑔 (𝑥 ) = − (𝑥) + 21.8614
845
173
Fórmula 1. 6 Fórmula a Integrar.
Si se tienen varias funciones sumándose o restándose entre ellas, simplemente hay que
integrar de manera independiente a cada una.
𝟎.𝟏𝟔
𝟒𝟕𝟏
∫ 𝑿 𝒅𝒙
𝟎 𝟏𝟔
𝟎.𝟏𝟔
𝟒𝟕𝟏
∫ 𝟏𝟔 𝑿𝟐 = [𝟒𝟕𝟏 𝑿𝟐 ]
𝟎 𝟐 𝟑𝟐
𝟒𝟕𝟏 𝟒𝟕𝟏 ( 7)
[ (𝟎. 𝟏𝟔)𝟐 ] − [ (𝟎)𝟐 ]
𝟑𝟐 𝟑𝟐
𝟒𝟕𝟏 𝟐
𝒎
𝟏𝟐𝟓𝟎
174
12.03
47
∫ − (𝑥) + 4.7163 𝑑𝑥
0.16 1187
47 2 47 2
[− 𝑥 + 4.7163] = − 𝑥 + 4.7163𝑥
1187 2374
2
47 47
[− (12.03)2 + 4.7163(12.03)] − [− (0.16)2 + 4.7163(0.16)] ( 8)
2374 2374
376
[−2.8651 + 56.7370] − (− + 0.7560)
741875
[53.8719] − [0.7565]
53.1154𝑚 2
902 2 451 2
[− 𝑥 + 21.8614] = − 𝑥 + 21.8614𝑥
845 845
2
451 451 ( 9)
[− (20.48)2 + 21.8614(20.48)] − [− (12.03)2 + 21.8614(12.03)]
845 845
[223.8598] − [185.7511]
38.1087𝑚 2
175
471 2
Á𝑟𝑒𝑎 = 𝑚 + 53.1154 𝑚 2 + 38.1087𝑚 2 = 91.6009 𝑚 2 ( 10)
1250
Ahora se procede a restarle el área donde se encuentra una parte del auditorio
15.46 m
2.29 m
¿
1.97 m
0.47 m
176
0.47 + 1.97 + 2.0252
𝑆𝑒𝑚𝑖𝑝𝑒𝑟í𝑚𝑒𝑡𝑟𝑜 = = 2.2326 ( 13)
2
= 0.4629𝑚 2
177
3.30 Cálculo del Área Exterior 2
20.48 m
7.67 m
Ahora se le tiene que restar el área en la cual se encuentra parte del auditorio.
5.90 m
1.16 m
Figura 3. 28 Triángulo 1.
178
15.34 m
1.78 m
16.50 m
15.34 m
4m
Figura 3. 30 Cálculo triángulo 2.
4 + 16.50 + 15.34
𝑆𝑒𝑚𝑖𝑝𝑒𝑟í𝑚𝑒𝑡𝑟𝑜 = = 17.92𝑚 ( 19)
2
179
Á𝑟𝑒𝑎 𝑟𝑒𝑎𝑙 𝑒𝑥𝑡𝑒𝑟𝑖𝑜𝑟 2 = (157.0816𝑚 2 ) − (60.8906𝑚 2 ) = 96.191𝑚 2 ( 22)
Teniendo en cuenta todos estos factores se empieza a realizar los cálculos necesarios.
Tipo de lámpara a colocar. LED.
Potencia (W) 75 watts.
Flujo Luminoso 6,500 Lm.
Tipo de luminaria. CITI80
Voltaje (V) 100-305 volts.
Altura de montaje 6.20 metros.
Marca MAGG
Tabla 3. 238 Especificaciones de la lámpara exterior.
180
Altura del poste 6.20 metros.
181
20,000 ≤ ΦL < 40,000 10 ≤ H < 12
ΦL ≥ 40,000 ≥12
Según la Tabla 3.241 para un flujo luminoso de 6,500 Lm emitidos por la lámpara le
corresponde una altura de entre 6 y 8 metros de colocación de la luminaria.
Por motivos económicos se podría escoger un poste de 6 metros de altura.
Unilateral ≤1
Según la Tabla 3.242 aconseja una disposición unilateral ya que al dividir el ancho de la
calzada entre la altura de montaje encontramos un valor menor a 1.
Como las avenidas se encuentran con poco tráfico podemos pensar que la instalación
no se ensuciará demasiado pero también podemos suponer que las lámparas no se limpiaran
182
con mucha frecuencia. Por lo tanto adoptando una posición conservadora se asignara el valor
de una luminaria cerrada en un ambiente medio. Ver Tabla 3.243 Factor de Mantenimiento.
Factor de Mantenimiento Fm
183
3.36 Cálculo del factor de utilización para lámparas de 75 W de
LED.
3.36.1Factor de utilización de la calzada.
𝐴1 3.64 𝑚
= = 0.5870 = 𝜼 = 𝟎. 𝟏
ℎ 6.20 𝑚
𝐴2 2𝑚
= = 0.3225 = 𝜼 = 𝟎. 𝟎𝟖
ℎ 6.20 𝑚
184
3.36.2 Calculando la distancia de iluminación
Se ocupa la siguiente fórmula
𝜂 ∗ 𝐹𝑚 ∗ 𝛷𝐿
𝑑=
𝐸𝑚 ∗ 𝐴
Siendo
d = Distancia a iluminar o distancia entre luminarias, distancia entre postes.
𝐹𝑚 = Factor de Mantenimiento.
𝐸𝑚 =Iluminación Media.
ΦL = Flujo luminoso de la lámpara.
A = Largo de la calzada.
Sustituyendo los valores en la fórmula.
0.18 ∗ 0.80 ∗ 6,500𝐿𝑚
𝑑= = 8.3 𝑚𝑒𝑡𝑟𝑜𝑠.
20 𝐿𝑢𝑥 ∗ 5.64𝑚
Por lo tanto la distancia que puede iluminar cada lámpara es de 8.3 metros al igual que
la distancia que cada poste debe de estar uno de otro.
Se calcula la iluminación media de la calzada para comprobar el dato obtenido
anteriormente empleando la siguiente fórmula.
𝜂 ∗ 𝛷𝐿 ∗ 𝐹𝑚
𝐸𝑚 =
𝐴∗𝑑
Siendo
d = Distancia a iluminar, o distancia entre luminarias, distancia entre postes.
𝐹𝑚 = Factor de Mantenimiento.
𝐸𝑚 =Iluminación Media.
ΦL = Flujo luminoso de la lámpara. A = Largo de la calzada.
185
Sustituyendo los valores en la fórmula.
𝐴1 4.64 𝑚
= = 0.7483 = 𝜼 = 𝟎. 𝟐𝟎
ℎ 6.2 𝑚
𝐴2 3𝑚
= = 0.5 = 𝜼 = 𝟎. 𝟏
ℎ 6.2 𝑚
𝜂 ∗ 𝛷𝐿 ∗ 𝐹𝑚
𝐸𝑚 =
𝐴∗𝑑
Siendo
𝐹𝑚 = Factor de Mantenimiento.
𝐸𝑚 =Iluminación Media.
186
Sustituyendo los valores en la fórmula.
𝐴1 4.64 𝑚
= = 0.7483 = 𝜼 = 𝟎. 𝟐𝟑
ℎ 6.20 𝑚
𝐴2 3.64𝑚
= = 0.5870 = 𝜼 = 𝟎. 𝟐
ℎ 6.2 𝑚
𝛈= 𝜂1 − 𝜂2 = 0.23 − 0.2 = 0.03
Como la inter distancia entre luminarias es conocida, el valor de la iluminación media en
la acera contraria es de.
𝜂 ∗ 𝛷𝐿 ∗ 𝐹𝑚
𝐸𝑚 =
𝐴∗𝑑
Siendo
d = Distancia a iluminar, o distancia entre luminarias, distancia entre postes.
𝐹𝑚 = Factor de Mantenimiento.
𝐸𝑚 =Iluminación Media.
ΦL = Flujo luminoso de la lámpara. A = Largo de la acera.
187
Sustituyendo los valores en la fórmula.
𝐴1 3𝑚
= = 0.4838 = 𝜼 = 𝟎. 𝟏𝟒
ℎ 6.2 𝑚
𝐴2 2𝑚
= = 0.3225 = 𝜼 = 𝟎. 𝟏𝟎
ℎ 6.2 𝑚
𝜂 ∗ 𝛷𝐿 ∗ 𝐹𝑚
𝐸𝑚 =
𝐴∗𝑑
Siendo
𝐹𝑚 = Factor de Mantenimiento.
𝐸𝑚 =Iluminación Media.
188
Sustituyendo los valores en la fórmula.
Proyector 400 w
189
Calculando el calibre del conductor por corriente.
Fórmula:
𝐾𝑤 ∙ 1000
𝐼=
√3 ∙ 𝐸𝐹 ∙ 𝐹. 𝑃
Siendo:
I= Corriente en amperes.
Sustituyendo en la formula.
(7.582 𝐾𝑤)(1000)
𝐼=
(√3)(220 𝑉𝐶𝐴)(0.90)
𝐼 = 22.1084 𝐴𝑚𝑝𝑒𝑟𝑒𝑠
Ahora bien dado que la instalación eléctrica de alumbrado exterior para las avenidas del
auditorio es de una distancia considerable se debe de realizar el cálculo del calibre del
conductor de alimentación a las luminarias por el método de caída de tensión.
190
La circulación de corriente a través de los conductores, ocasiona una pérdida de potencia
transportada por el cable, y una caída de tensión o diferencia entre las tensiones en el origen
y extremo de la canalización.
Esta caída de tensión debe ser inferior a los límites marcados por el Reglamento en cada
parte de la instalación, con el objeto de garantizar el funcionamiento de los receptores
alimentados por el cable. Este criterio suele ser determinante cuando las líneas son de larga
longitud por ejemplo en derivaciones individuales que alimenten a los últimos pisos en un
edificio de cierta altura o en instalaciones de alumbrado exterior.
3.37.1 CÁLCULO POR CAÍDA DE TENSIÓN
𝑒=𝐼∙𝑅
𝑉
𝑅=
𝐼
𝑒 = (220 𝑉𝐶𝐴)(0.03)
𝑒 = 6.6 𝑉𝐶𝐴
6.6 𝑉𝐶𝐴
𝑅=
27.6355 𝐴𝑚𝑝𝑒𝑟𝑒𝑠
𝑅 = 0.2388232527 Ω/20mts
𝑅 = 2 Ω/𝐾𝑚
191
Tabla 3. 245 Ampacidad de conductores eléctricos de cobre.
192
RESISTENCIA ÓHMICA Y PESO DE LOS CONDUCTORES
14 8.28 27 23
ALAMBRES
12 5.21 40 35
10 3.28 56 50
8 2.06 99 91
14 8.45 30 25
12 5.31 43 38
10 3.35 63 60
8 2.06 105 98
193
3.38 CÁLCULO DE LA CANALIZACIÓN ELÉCTRICA.
Cálculo de la tubería conduit.
Por lo tanto se escoge este último calibre de conductor por la larga distancia hasta donde
tiene que alimentar.
893 Kg/Km
0.893 Kg/m
Se colocará un cable cordón uso rudo con un diámetro exterior nominal de 25.3 mm.
(25.3 𝑚𝑚)2
𝐴= 𝜋
4
𝐴 = 502.7255 𝑚𝑚2
El área total del conductor cordón uso rudo tetra filar 4x8 AWG es de 502.7255 mm2.
Según la tabla 3.247 Sección transversal de tubería conduit cédula 20. Se necesita una
tubería conduit de 1 ½” pulgada de diámetro. Ya que al 40% de su capacidad puede alojar
530 𝑚𝑚 2.
194
Tuberias Conduit
½ 13 195 78 58.5 39
195
Figura 3. 32 Especificaciones técnicas del conductor de cobre.
196
Figura 3. 33 Cordón uso rudo.
197
3.39 CÁLCULO DEL INTERRUPTOR GENERAL PARA LA
ALIMENTACIÓN DEL TABLERO DE ALUMBRADO
Potencia total instalada: 7582 w=7.582 KW
(7.582 𝐾𝑤)(1000)
𝐼=
(√3)(220 𝑉𝐶𝐴)(0.90)
𝐼 = 22.10 𝐴𝑚𝑝
Interruptor de 30 Amperes.
3.40 CÁLCULO DEL INTERRUPTORES DERIVADOS PARA LA
DEL TABLERO DE ALUMBRADO
Se dispondrán de 46 luminarias para el auditorio las cuales cada una tiene una potencia
de 75 watts, sabemos que un circuito derivado para alumbrado no debería de rebasar los 1500
watts de potencia instalada, en nuestro caso podemos plantear dos opciones las cuales son
las siguientes.
Nosotros optaremos por la primera opción ya que el auditorio en una parte de la tarde
se llega a ocupar la iluminación para la finalización de algunas conferencias, entonces si
llegara a ocurrir una falla en un grupo importante de luminarias los obreros se vería retrasados
para continuar con sus labores, así la instalación será más flexible con el usuario.
198
3.41 Cálculo de circuitos derivados
Área Potencia
Auditorio 1 360w
Auditorio 2 240w
Auditorio 3 480w
Proyector 400 w
𝟎. 𝟑𝟔 ∗ 𝟏𝟎𝟎𝟎
𝐀𝐮𝐝𝐢𝐭𝐨𝐫𝐢𝐨 𝟏 (𝐈) = = 𝟑. 𝟏𝟒𝟗𝟔 𝑨𝒎𝒑𝒆𝒓𝒆𝒔
𝟏𝟐𝟕 ∗ 𝟎. 𝟗
𝟎. 𝟐𝟒 ∗ 𝟏𝟎𝟎𝟎
𝐀𝐮𝐝𝐢𝐭𝐨𝐫𝐢𝐨 𝟐 (𝐈) = = 𝟐. 𝟎𝟗𝟗𝟕 𝑨𝒎𝒑𝒆𝒓𝒆𝒔
𝟏𝟐𝟕 ∗ 𝟎. 𝟗
𝟎. 𝟒𝟖 ∗ 𝟏𝟎𝟎𝟎
𝐀𝐮𝐝𝐢𝐭𝐨𝐫𝐢𝐨 𝟑 (𝐈) = = 𝟒. 𝟏𝟗𝟗𝟒 𝑨𝒎𝒑𝒆𝒓𝒆𝒔
𝟏𝟐𝟕 ∗ 𝟎. 𝟗
199
𝟎𝟒 ∗ 𝟏𝟎𝟎𝟎
𝐏𝐫𝐨𝐲𝐞𝐜𝐭𝐨𝐫 (𝐈) = = 𝟑. 𝟓 𝑨𝒎𝒑𝒆𝒓𝒆𝒔
𝟏𝟐𝟕 ∗ 𝟎. 𝟗
𝟎. 𝟓𝟐𝟓 ∗ 𝟏𝟎𝟎𝟎
𝐋á𝐦𝐩𝐚𝐫𝐚𝐬 𝐞𝐱𝐭𝐞𝐫𝐢𝐨𝐫𝐞𝐬 (𝐈) = = 𝟒. 𝟓𝟗𝟑𝟏 𝑨𝒎𝒑𝒆𝒓𝒆𝒔
𝟏𝟐𝟕 ∗ 𝟎. 𝟗
𝟏. 𝟐𝟓𝟎 ∗ 𝟏𝟎𝟎𝟎
𝐂𝐨𝐧𝐭𝐚𝐜𝐭𝐨𝐬 𝐋𝐚𝐩𝐭𝐨𝐩 𝟏 (𝐈) = = 𝟏𝟎. 𝟗𝟑𝟔𝟏 𝑨𝒎𝒑𝒆𝒓𝒆𝒔
𝟏𝟐𝟕 ∗ 𝟎. 𝟗
𝟏. 𝟐𝟓𝟎 ∗ 𝟏𝟎𝟎𝟎
𝐂𝐨𝐧𝐭𝐚𝐜𝐭𝐨𝐬 𝐋𝐚𝐩𝐭𝐨𝐩 𝟐 (𝐈) = = 𝟏𝟎. 𝟗𝟑𝟔𝟏 𝑨𝒎𝒑𝒆𝒓𝒆𝒔
𝟏𝟐𝟕 ∗ 𝟎. 𝟗
𝟏. 𝟓 ∗ 𝟏𝟎𝟎𝟎
𝐂𝐨𝐧𝐭𝐚𝐜𝐭𝐨𝐬 𝐄𝐪𝐮𝐢𝐩𝐨𝐬 𝟏 (𝐈) = = 𝟏𝟑. 𝟏𝟐𝟑𝟑 𝑨𝒎𝒑𝒆𝒓𝒆𝒔
𝟏𝟐𝟕 ∗ 𝟎. 𝟗
𝟏. 𝟓 ∗ 𝟏𝟎𝟎𝟎
𝐂𝐨𝐧𝐭𝐚𝐜𝐭𝐨𝐬 𝐄𝐪𝐮𝐢𝐩𝐨𝐬 𝟐 (𝐈) = = 𝟏𝟑. 𝟏𝟐𝟑𝟑 𝑨𝒎𝒑𝒆𝒓𝒆𝒔
𝟏𝟐𝟕 ∗ 𝟎. 𝟗
200
Capítulo 4 Análisis Costo-Beneficio
La electricidad es sin lugar a dudas la forma de energía que ofrece más ventajas para
su transportación y distribución.
Esto la ha convertido en uno de los servicios más importantes para la sociedad y como
tal se espera que esté disponible para cualquiera que lo solicite.
La justificación del uso de la relación costo-beneficio como criterio para selección de
alternativas se estudia para instalaciones con parámetros luminotécnicos de diseño
recomendados, distintos grados de protección mecánica y polución.
Para la determinación de cuáles son los problemas más importantes en la instalación
eléctrica de alumbrado exterior, se recurre al diagrama de Pareto.
El diagrama de Pareto está basado en la ―ley 80-20‖ o de ―los pocos vitales y muchos
triviales‖, enunciada por el economista italiano Vilfredo Pareto a principios de siglo.
Aplicando este mismo principio, cuando dividimos las causas que explican un problema
en la organización, nos daremos cuenta generalmente de que sólo con unos pocos factores
se explica la mayor parte del efecto. Esto nos permite focalizar los esfuerzos en esas causas
principales.
4.1 UTILIDAD DEL DIAGRAMA DE PARETO
El diagrama de Pareto se revela especialmente útil cuando se trata de:
a) Mostrar la importancia relativa de las diversas causas identificadas para un
determinado efecto o problema, en los casos en que éste sea el resultado de la contribución
de varias causas o factores.
b) Determinar los factores clave (o los más importantes) que incluyen en un determinado
efecto o problema.
c) Decidir sobre qué aspectos (los “pocos vitales”) trabajar de manera inmediata.
201
CAUSAS DEFECTOS
Ahora nos disponemos a ordenar los factores de mayor a menor, por supuesto que va
en función de la magnitud de cada uno de ellos.
El porcentaje acumulado para cada uno de los factores se obtiene sumando los
porcentajes de los factores anteriores de la lista más el porcentaje del propio factor del que se
trate.
202
Núm. De
Núm. De
Causas defectos % Total % Acumulado
defectos
acumulados
Circuitos
sobrecargados por
falta de identificación 130 130 30.0925 % 30.0925 %
de fases
alimentadoras.
Lámparas
100 230 23.1481 % 53.2406 %
deterioradas.
Conductores
100 330 23.1481 % 76.3887 %
aterrizados a tierra.
Poco mantenimiento
28 358 6.4814 % 82.8701 %
a las luminarias.
Registros eléctricos
25 383 5.7870 % 88.6571 %
sin coladera.
Encendido con
relevadores de 20 403 4.6296 % 93.2867 %
tiempo.
Relleno total de la
15 418 3.4722 % 96.7589 %
tubería conduit.
Fosa de aceite de
transformadores con 13 431 3% 99.7589 %
fugas.
Colocación de
hidrante cerca de
registro eléctrico y 1 432 0.2314 % 100 %
tablero de control de
alumbrado.
203
% Lámparas deterioradas. = (100 / 432) x 100 = 23.1481%
% Conductores aterrizados a tierra. = (100 / 209) x 100 = 23.1481%
% Poco mantenimiento a las luminarias. = (28 / 432) x 100 = 6.4814%
% Registros eléctricos sin coladera. = (25 / 432) x 100 = 5.7870%
% Encendido con relevadores de tiempo. = (20 / 432) x 100 = 4.6296 %
% Relleno total de la tubería conduit. = (15/ 432) x 100 = 3.4222 %
% Fosa de aceite de transformadores con fugas. = (13/ 432) x 100 = 3%
% Colocación de hidrante cerca de registro eléctrico y tablero de control de alumbrado.
. = (1 / 432) x 100 =0.2314 %
Dibujar dos ejes verticales y un eje horizontal. Situar en el eje vertical izquierdo la
magnitud de cada factor. La escala del eje está comprendida entre cero y la magnitud total de
los factores. En el derecho se representan el porcentaje acumulado de los factores, por tanto,
la escala es de cero a 100. El punto que representa a 100 en el eje derecho está alineado con
el que muestra la magnitud total de los factores detectados en el eje izquierdo. Por último, el
eje horizontal muestra los factores empezando por el de mayor importancia.
140
120
96 99 100
Núm. de defectos.
100 88 93
82
76
80
53
60
40 30
20 Núm. De defectos
130100100 28 25 20 15 13 1
0 % Acumulado
Como conclusión, se puede decir que esta técnica facilita la selección de los puntos
débiles donde debemos focalizar los esfuerzos de mejora. Del mismo modo que se puede
utilizar el diagrama de Pareto para determinar cuáles son las principales causas de un
problema.
204
En el gráfico obtenido se observa que un 20% de los factores (circuitos sobrecargados
por falta de identificación de fases, lámparas deterioradas y conductores aterrizados a tierra)
representan aproximadamente un 80% de los defectos, por lo tanto centrándose la empresa
solo en estos 3 factores reduciría en un 80% el número de defectos.
A continuación se muestra una tabla que representa la lista de costos para la nueva
instalación eléctrica que proveerá de alimentación eléctrica a las luminarias del auditorio.
205
Zona Luminaria # De Luminarias Marca
SQ5SSD MAGG
3
Recibidor (5) 4w 270Lm
SQ5SSD MAGG
6
Pasillo (6) 4w 270Lm
CRICKET MAGG
18
Baño (7) 1W 36Lm
206
# De
Zona Luminaria P/U Total
Luminarias
M2300S MAGG
1
Cocineta (4) 23w 1700Lm
SQ5SSD MAGG
3
Recibidor (5) 4w 270Lm
SQ5SSD MAGG
6
Pasillo (6) 4w 270Lm
CRICKET MAGG
18
Baño (7) 1W 36Lm
207
Una iluminación inadecuada en el centro de trabajo puedo originar fatiga ocular,
cansancio, dolor de cabeza, estrés y accidentes. El trabajo con poca luz daña la vista, también
cambios bruscos de luz pueden ser peligrosos, pues ciegan temporalmente, mientras el ojo se
adapta a la nueva iluminación.
Uno de los grandes beneficios que brinda la luz blanca es una mejor reproducción de
color y un ambiente mucho más agradable a todos los que transitan por lugares exteriores.
La luz blanca permite con mucha más facilidad reconocer personas, vehículos y detalles,
lo que inhibe actos de vandalismo.
La luz natural es fundamental para nuestras vidas, pero de noche dependemos de la
iluminación artificial para iluminar nuestro mundo. La luz blanca de alta calidad brinda una serie
de beneficios cuando la comparamos con la luz amarilla tradicional. Además de ahorrar
energía, los ambientes están mejor iluminados.
Con la implementación de este proyecto se pretende brindar confiabilidad al auditorio,
para evitar accidentes y actos de vandalismo.
Promoviendo la seguridad, comodidad y confort para el tráfico vehicular y peatonal
proporcionándole una adecuada visibilidad durante los días nublados, de niebla y las noches.
Algunos de los beneficios de la correcta iluminación externa influyen en una reacción
colectiva e individual en la empresa, tales como:
Incrementar la seguridad individual y colectiva en las vías.
Incrementar el atractivo de las vías interiores de la empresa.
Ofrece mayor protección a los obreros y propiedades de los daños.
Proporciona confort y tranquilidad.
Da mayor sentido de seguridad ya que contribuye a detener o disminuir las
acciones vandálicas.
208
CAPÍTULO 5 CONCLUSIONES Y RECOMENDACIONES
Los cálculos luminotécnicos basándome en las normas de iluminación en los centros
de trabajo, pero para esto necesitaba conocer algunos datos como son:
Ancho de la calzada.
Ancho de la acera.
Altura de colocación de la luminaria.
Una vez que obtuve estos datos simplemente consulte algunos catálogos de
iluminación para así conocer los lúmenes emitidos por distintos tipos de lámparas y
potencias diferentes escogiendo la mejor opción.
Para la realización de los cálculos se emplearon tres tipos de lámparas como lo
son:
Led.
Encontrando un nivel de iluminación adecuado con forme a las normas.
Estos mismos cálculos se realizaron con las diferentes tipos de lámparas
encontrando niveles de iluminación adecuados.
Una vez realizado los cálculos luminotécnicos, se realizó los cálculos para el
calibre del conductor de alimentación a las lámparas, para determinar el calibre se
realizó por los métodos de corriente y caída de tensión.
Con el desarrollo teórico y con la implementación de este proyecto, tengo la
satisfacción y me quedo con todo el aprendizaje obtenido.
De las cosas más importantes al realizar este proyecto, fue todo ese aprendizaje
obtenido, ya que fue necesario aplicar todas esas teorías y conocimientos de
instalaciones eléctricas y luminotecnia, para poder elaborar los cálculos necesarios
para realizar la selección, instalación y colocación de las nuevas luminarias, para el
alumbrado.
Desarrollar las habilidades y destrezas para poder aplicar todos aquellos
conocimientos y cálculos elaborados, con el fin de alcanzar el resultado plasmado en
un papel, físicamente al momento de la implementación del proyecto.
La realización de la instalación para el alumbrado de las vialidades, me queda
como experiencia, ya que no es lo mismo trabajar con tinta y papel, al realizar todo un
proceso en un área de trabajo, ya que estando en una industria todo cambia; ahí ya
no es como en el salón de clases eso es la vida real, no existe espacio para errores ya
que un error puede costar la vida o un gasto monetario mayor.
El entorno escolar no se compara en lo absoluto con el de trabajo, la enseñanza
en un salón de clases solo es teóricamente, pero en el trabajo todo es prácticamente,
y el poder tener la oportunidad de estar en un empresa como lo es IDHG S.A. DE
C.V., me hace darme cuenta que la teoría y la práctica van de la mano hacia el
camino del aprendizaje; y muchas veces es más ocupada la enseñanza empírica que
la teórica.
209
Anexos
210
Anexo III Lámpara LED exterior.
211
Anexo V Lámpara LED baño.
212
GLOSARIO
Adaptación visual. Es la capacidad visual que permite regular la intensidad de la
respuesta en función de la magnitud del estímulo visual.
Aislamiento. Material no conductor que se utiliza en un conductor para separar los
materiales conductores de un circuito. Material no conductor que se utiliza en la fabricación de
cables aislados.
Amperio (A). Unidad que expresa el flujo de una corriente eléctrica. Un amperio es la
corriente que produce una diferencia de tensión de un voltio en una resistencia de un ohmio;
Una corriente eléctrica que circula a una velocidad de un culombio por segundo.
Balastro. Elemento que limita la corriente a lámparas de descarga como tubos
fluorescentes y halogenuros metálicos. Es parte del llamado equipo de la luminaria, tiene un
consumo que va del 3 al 30% de la potencia de la lámpara. Los hay electrónicos y
ferromagnéticos.
Calibración .Ajuste de un dispositivo de forma que su salida se encuentre dentro de un
rango específico para determinados valores de entrada.
Candela. Unidad fotométrica internacional, basada en la radiación de un cuerpo negro
a la temperatura de solidificación del platino. Dicha radiación, por centímetro cuadrado,
equivale a 60 candelas.
Conductividad. Capacidad de un conductor de transportar electricidad, normalmente
expresada como porcentaje de la conductividad de un conductor del mismo tamaño de cobre
suave
Conductor. Cable o combinación de cables adecuados para transportar una corriente
eléctrica. Los conductores pueden estar aislados o desnudos. 2) Todo material que permite a
los electrones fluir a través de él.
Corriente alterna (AC). Corriente de electrones en la que la magnitud y el sentido varían
cíclicamente. Es la corriente de servicio que nos suministran las compañías eléctricas.
Corriente continua (CC). Flujo continuo de electrones entre dos puntos a través de un
conductor. Es el tipo de corriente que se utiliza en electrónica, el LED funciona con corriente
continua, así que necesita algún elemento que sea capaz de rectificar la tensión de red y limitar
la corriente para tener un consumo estable.
Curva de distribución de la luz. Es un diagrama donde se representa la intensidad
luminosa de una fuente de luz. Se obtiene al realizar mediciones de esta intensidad desde
todos los ángulos alrededor de la citada fuente.
Permite determinar magnitudes como la eficiencia, eficacia, flujo luminoso total emitido,
altura de montaje recomendada y criterio de espaciamiento de una fuente de luz.
Dialux. Software gratuito desarrollado por la compañía alemana DIAL. Es el programa
de cálculo luminotécnico más extendido en Europa. Tiene competidores, como el Relux, o el
Aidolux, este último desarrollado en España.
Flujo luminoso. Es el flujo radiante emitido dentro del espectro visible, y además,
ponderado por la curva de sensibilidad relativa.
Fotometría. Es la ciencia de la medición de la luz, en términos de su brillo percibido por
el ojo humano.
Grado de protección (IP). Estándar internacional que certifica el nivel de protección
frente a elementos ambientales que posee un producto. Desde impedir la entrada de insectos,
partículas y polvo, hasta la capacidad de sumergirse en agua sin sufrir daños
213
Grado de protección (K). Estándar internacional que certifica el nivel de protección
frente a agresiones mecánicas que posee un producto.
214
BIBLIOGRAFÍA
Enríquez Harper, G., (2009), ABC de las instalaciones eléctricas industriales, México,
Limusa S.A. de C.V.
Silva Bijit, L., (2006), Redes eléctricas, México, Prentice Hall/Pearson.
Lima Velasco, J. I., (2009), Diseño y cálculo de instalaciones eléctricas, México, Éxodo.
Enríquez Harper, G., (2006), Guía práctica para el cálculo de instalaciones eléctricas,
México, Limusa S.A. de C.V.
Enríquez Harper, G., (2006), Guía para el diseño de instalaciones eléctricas,
residenciales, industriales y comerciales., México, Limusa S.A. de C.V.
Cabral C, (2003), Manual de iluminación. Lisboa, INATEL.
Bavister S., (2001), Técnicas de iluminación. Barcelona, Omega Roto Visión.
Urraca Piñeiro, J.I.(1988). Tratado de Alumbrado Público. Ed Donostiarra.
Chapa Carreón, J. (1990). Manual de instalaciones de alumbrado y fotometría. Editorial
Limusa.
215