Вы находитесь на странице: 1из 10

Preliminary Test for CAG14:

STEP:-1
Double click on “CAG14/34”
STEP:-2
Double click on “50N” or “Copy of 50N”
STEP:-3
Pickup Test:
Macro Type: LRAMPI
Relay setting: P.S. = 0.2
Double click on “pickup test” LRAMPI
STEP:-4
Now, click on “RUN” button

Same test repeat on various frequencies from 47Hz to 52Hz


STEP:-5
Pickup Test:
Macro Type: TIMEI
Relay setting: P.S. = 0.2
Double click on “Time test” TIMEI
STEP:-6
Now, click on “RUN” button & see actual operating time of relay
Preliminary test for FAC:
STEP:-1
Double click on “FAC”
STEP:-2
Double click on “64R” for FAC14 (Single element)
STEP:-3
Pickup Test:
Macro Type: LRAMPV
Relay setting: P.S. = 15V
Double click on “pickup test” LRAMPV
STEP:-4
Now, click on “RUN” button & see actual operating value of relay

Same test repeat on various frequencies like 60Hz, 55Hz & 45 Hz etc.