Вы находитесь на странице: 1из 4

Communication Networks

OPTIF for FOX515/512


IEEE C37.94 communication interface

One of the most important applications used by any power The substation environment is usually characterized by a high level
utility is protection of high voltage power lines. Protection of electromagnetic fields caused by high voltages and currents
relays, which provide the protection functionality for power in power lines. Specially during fault conditions the same can
lines, need to exchange information in order to ensure correct rise significantly and disturb communications channels based on
operation. The utility's captive communications network is copper wires. So it is recommended to use a complete optical
normally used to provide reliable communications channels interconnection from relay to relay via fibre optical multiplex equip-
for protection applications. Such communications channels ment using the IEEE C37.94 protocol.
demand highest availability and performance figures, espe-
cially for differential protection applications which require The IEEE C37.94 standard defines the communication of protec-
very low and symmetrical end-to-end delay times. tion equipment (protections relays) with communications equip-
ment inside a substation using optical fibers. Accordingly no
Transmitting protection relay data channels via communication additional extern converters are required anymore. This standard
network instead of direct relay connection using dedicated fibres is already implemented by many protection relay manufactur-
has the big advantage of complete supervision of the data chan- ers around the world. ABB’s latest relay series REx670 and the
nel and the possibility for redundant channel routing. Beside this teleprotection equipment NSD570 support this standard as well.
it also saves fibres, which are valuable assets. Supervision of the The OPTIF module (OPtical Teleprotection InterFace) extends the
data channel and redundant channel routing allow to significantly FOX515/512 platform with IEEE C37.94 interfaces while ensuring
increase the availability of protection applications. compatibility with the traditional ABB SFC protocol used by legacy
ABB protection relays.
FOX515 multi-service multiplexer

Applications with OPTIF Main features


FOX515 collects all utility specific signals and transmits the – Fully supporting ANSI/IEEE C37.94 (64 – 768 kbit/s pay load)
same through Wide Area Networks (WAN) using fibre optical – 4 ports individually configurable for:
or copper interfaces. Therefore the FOX515 provides standard – IEEE C37.94 on 850 nm multi mode fiber
data interfaces and utility specific interfaces such as the – ABB’s proprietary SFC protocol on 1,310 nm single-mode
OPTIF module which provides up to four ports for differential fiber
protection signal transmission. – All 4 optical ports using SFPs, supporting multimode and
single-mode fibers depending on selected type of interface
OPTIF architecture – 1 Ethernet port configurable as
The OPTIF is part of a large complement of interface modules – electrical port 10/100 BaseT (RJ45), or
which can be plugged into a FOX515 shelf. Like all FOX515 – optical port when equipped with SFP
modules OPTIF is – Transmission delay time:
– powered from the FOX515 shelf Fully symmetrical bidirectional communication on normal
– configured by UCST and operation and also in protected mode (working and protect-
– supervised by FOXMAN management system ing path)
4 optical ports equipped with SFPs on the front allow indi- – Fully integrated in FOX515/512 platform (1 mechanical slot)
vidual configuration to support either
– ANSI/IEEE C37.94 standard or For connections based on ABB’s SFC protocol, SFPs for
– ABB’s traditional SFC protocol single-mode fibers on 1,310 nm are required. This solu-
Additionally an Ethernet port is provided, compatible with tion has been successfully implemented for many years in
DATAx and ETER1/LAWA4 module substations around the world together with ABB’s protection
relays REL316, REL551, REL561 or teleprotection equipment
Symmetric transmission delay NSD570 (G1LO-interface).
Differential protection relays usually calculate the delay times of the
data channel by a round trip delay measurement. Therefore asym- In addition to these four optical dual-use ports, one additional
metrical delay times can not be detected and lead to the possibility port is added on the module operating as an Ethernet port
of wrong trips. with optical or electrical interface:
– 10/100 BaseT (RJ45), electrical port or optical port when
OPTIF solves this problem by ensuring the same data routing equipped with a suitable SFP
for the transmit and receive paths. In case of redundant channel
configuration, OPTIF ensures symmetrical protection switching for Management System
differential protection data channels. This ensures equal delay The FOX515 with a variety of services are managed centrally
times on transmit and receive paths under all circumstances by UCST/FOXMAN management system. Utilities save cost
and therefore avoids the possibility for false tripping of the and accelerate the circuit provisioning process with only one
protection relay due to asymmetrical delay times. element manager for all service types.

HV power line

FOX515 with OPTIF module FOX515 with OPTIF module

Utility communication
e.g. STM-1 or STM-4

4x 4x
Voice Voice

IEEE Data Data IEEE


RED
RED C37.94 C37.94 RED

Substation "A" Substation "B"

All-optical interconnection

2 | OPTIF for FOX515/512


Technical data

General
Designed for FOX515/512, P-BUS access
Number of ports Maximum 4 ports per OPTIF
module
Optical ports All optical ports require SFP for:
– 850 nm (multimode) or
– 1,310 nm (single-mode)
Operation mode IEEE C37.94 or ABB TPE
Module width 1 mechanical slot in FOX515
Environmental conditions According to FOX515 specification
Configuration tool UCST release R8B SP02 or higher
Maintenance – Local and remote test loops
available
– Performance monitoring
Typical 1+1 switchover ≤ 25 ms
time
Standard compliance IEEE C37.94
MTTF > 60 years

Interfaces
Interface type IEEE C37.94 ABB type Ethernet
Max port number 4 4 1
Type of port (Connector) Optical SFP (LC-PC) Optical SFP (LC-PC) Electrical RJ45 or optical SFP
Framing complying to ANSI/IEEE C37.94 ABB SFC protocol 10/100 BaseT or 100 Base-FX
N x 64 kbit/s (N = 1 ... 12)
N x 64 kbit/s (N = 1 ... 3) N x 64 kbit/s (N = 1 ... 30)
Data transmission 64 kbits/s – 768 kbit/s or
[Ch1, Ch2, RemAlm] or 2,048 kbit/s
2,048 kbit/s transparent
Transmission bit rate 2,048 kbit/s optical 4,096 kbit/s optical ---
Signal bit rate 2,048 kbit/s (electrical) 2,048 kbit/s (electrical) ---
Optical line coding NRZ MCMI ---

SFP transceivers
The optical parameters are subject to the selected SFP transceiver module. The following table shows the characteristics of the SFP
transceiver modules approved for these applications:

Optical parameters IEEE C37.94 compliant ABB SFC protocol


Application example RED670 REL316, REL551, REL561
NSD570/G1LOa NSD570/G1LO
Wavelength 850 nm 1,310 nm
Fiber type Multimode Single-mode
-19 - 11 dBm (62.5μm)
Optical output power (Tx) -15 ... -8 dBm
-23 - 9 dBm (50μm)
Max allowed optical input power -3 dBm -3 dBm
13 dBm (62.5μm)
Optical power budget, min 19 dB
11 dBm (50μm)

Receiver sensitivity -32 dBm -34 dBm

Maximum distance
2 km 30 ... 50 km
(depending on total link attenuation)

OPTIF for FOX515/512 | 3


OPTIF ordering information

Type Despription Order number


OPTIF Optical Teleprotection Interface 1KHW001797R0001
SFP SFP Transceiver 850 nm, multimode 1KHW001871R0005

© ABB Switzerland Ltd. May 2015 The right to modifications or deviations due to technical progress is reserved.
SFP SFP Transceiver 1310 nm, single-mode 1KHW001872R0001*
Optical cables: multimode
V9YE Duplex LC to ST, outside cabinet, 10 m 1KHW027541R0100
V9YF Duplex LC to LC cable, outside cabinet, 10 m 1KHW027542R0100
V9YG Duplex LC to LC cable, inside cabinet, 2 m 1KHW027543R0020
Optical cable: single-mode
V9KZ Duplex LC - FC/PC cable, outside cabinet, 10 m 1KHW027499R0100
V9KX Duplex LC - LC cable, outside cabinet, 10 m 1KHW027497R0100
V9KW Duplex LC - FC/PC cable, inside cabinet, 2 m 1KHW027496R0020
V9KU Duplex LC - LC cable, inside cabinet, 2 m 1KHW027494R0020
Electric cables: ethernet

1KHA - 001 122 - SEN 1000 - 03.15 - Printed in Switzerland


LAN_1.005 Ethernet 1:1 cable, 3 m 1KHW027456R0030
LAN_X.006 Ethernet crossover cable, 3 m 1KHW027457R0030
* SFP Transceiver modules are also suited for 100 Base-FX Ethernet applications.
Other lengths available on request.

3rd party Fiber pair Max. 4 ports

RED 670 (up to 2 km)


ABB SFC IEEE C37.94

Optical
connector SFP with
SDH network
NSD570 LC-connector

REL316 Patch
REL551 panel
REL561 Optical
connector
OPTIF FOX515
FOX6Plus

Relay cabinet Telecom cabinet

Substation
Substation relay & telecom cabinet

For more information please contact: List of abbreviations

MCMI Modified Code Mark Inversion


ABB Switzerland Ltd.
Power Systems NRZ Non Return to Zero
Bruggerstrasse 72 SFC Secure Frame Concept
5400 Baden, Switzerland SFP Small Form Pluggable
Phone: +41 58 585 77 44
UCST Configuration Toll for
Fax: +41 58 585 55 77
FOX515/512
E-Mail: communication.networks@ch.abb.com

www.abb.com/communicationnetworks

Вам также может понравиться