One of the most important applications used by any power The substation environment is usually characterized by a high level
utility is protection of high voltage power lines. Protection of electromagnetic fields caused by high voltages and currents
relays, which provide the protection functionality for power in power lines. Specially during fault conditions the same can
lines, need to exchange information in order to ensure correct rise significantly and disturb communications channels based on
operation. The utility's captive communications network is copper wires. So it is recommended to use a complete optical
normally used to provide reliable communications channels interconnection from relay to relay via fibre optical multiplex equip-
for protection applications. Such communications channels ment using the IEEE C37.94 protocol.
demand highest availability and performance figures, espe-
cially for differential protection applications which require The IEEE C37.94 standard defines the communication of protec-
very low and symmetrical end-to-end delay times. tion equipment (protections relays) with communications equip-
ment inside a substation using optical fibers. Accordingly no
Transmitting protection relay data channels via communication additional extern converters are required anymore. This standard
network instead of direct relay connection using dedicated fibres is already implemented by many protection relay manufactur-
has the big advantage of complete supervision of the data chan- ers around the world. ABB’s latest relay series REx670 and the
nel and the possibility for redundant channel routing. Beside this teleprotection equipment NSD570 support this standard as well.
it also saves fibres, which are valuable assets. Supervision of the The OPTIF module (OPtical Teleprotection InterFace) extends the
data channel and redundant channel routing allow to significantly FOX515/512 platform with IEEE C37.94 interfaces while ensuring
increase the availability of protection applications. compatibility with the traditional ABB SFC protocol used by legacy
ABB protection relays.
FOX515 multi-service multiplexer
HV power line
Utility communication
e.g. STM-1 or STM-4
4x 4x
Voice Voice
All-optical interconnection
General
Designed for FOX515/512, P-BUS access
Number of ports Maximum 4 ports per OPTIF
module
Optical ports All optical ports require SFP for:
– 850 nm (multimode) or
– 1,310 nm (single-mode)
Operation mode IEEE C37.94 or ABB TPE
Module width 1 mechanical slot in FOX515
Environmental conditions According to FOX515 specification
Configuration tool UCST release R8B SP02 or higher
Maintenance – Local and remote test loops
available
– Performance monitoring
Typical 1+1 switchover ≤ 25 ms
time
Standard compliance IEEE C37.94
MTTF > 60 years
Interfaces
Interface type IEEE C37.94 ABB type Ethernet
Max port number 4 4 1
Type of port (Connector) Optical SFP (LC-PC) Optical SFP (LC-PC) Electrical RJ45 or optical SFP
Framing complying to ANSI/IEEE C37.94 ABB SFC protocol 10/100 BaseT or 100 Base-FX
N x 64 kbit/s (N = 1 ... 12)
N x 64 kbit/s (N = 1 ... 3) N x 64 kbit/s (N = 1 ... 30)
Data transmission 64 kbits/s – 768 kbit/s or
[Ch1, Ch2, RemAlm] or 2,048 kbit/s
2,048 kbit/s transparent
Transmission bit rate 2,048 kbit/s optical 4,096 kbit/s optical ---
Signal bit rate 2,048 kbit/s (electrical) 2,048 kbit/s (electrical) ---
Optical line coding NRZ MCMI ---
SFP transceivers
The optical parameters are subject to the selected SFP transceiver module. The following table shows the characteristics of the SFP
transceiver modules approved for these applications:
Maximum distance
2 km 30 ... 50 km
(depending on total link attenuation)
© ABB Switzerland Ltd. May 2015 The right to modifications or deviations due to technical progress is reserved.
SFP SFP Transceiver 1310 nm, single-mode 1KHW001872R0001*
Optical cables: multimode
V9YE Duplex LC to ST, outside cabinet, 10 m 1KHW027541R0100
V9YF Duplex LC to LC cable, outside cabinet, 10 m 1KHW027542R0100
V9YG Duplex LC to LC cable, inside cabinet, 2 m 1KHW027543R0020
Optical cable: single-mode
V9KZ Duplex LC - FC/PC cable, outside cabinet, 10 m 1KHW027499R0100
V9KX Duplex LC - LC cable, outside cabinet, 10 m 1KHW027497R0100
V9KW Duplex LC - FC/PC cable, inside cabinet, 2 m 1KHW027496R0020
V9KU Duplex LC - LC cable, inside cabinet, 2 m 1KHW027494R0020
Electric cables: ethernet
Optical
connector SFP with
SDH network
NSD570 LC-connector
REL316 Patch
REL551 panel
REL561 Optical
connector
OPTIF FOX515
FOX6Plus
Substation
Substation relay & telecom cabinet
www.abb.com/communicationnetworks