Ringmaster
Medium Voltage Distribution
schneider-electric.com/mv-distribution
General contents
Presentation 3
Remote control 87
Installation drawings 93
Overview 4
Description 5
Switchgear description 6
Applications 7
Protection
Time Fuse Link (TFL) 13
VIP protection relays
Product advantages
Simple, clear operation combined with compact size, high functionality and
reliability extends the applications of the Ringmaster range.
Reduced risk
Fully certified internal arc design in accordance with latest international standards.
Indoor/outdoor design
No need for expensive switchrooms.
Self-powered protection
Not reliant on costly battery chargers.
Compact
Reduced dimensions, gives reduced civil costs.
Virtually maintenance free
Low lifetime costs.
Modular design
Quick, simple & easy to install.
Proven quality
Assured consistent quality.
ISO 9001 quality certification.
Environmental
Manufacture to ISO 14001 environmental standards.
Direct mounting to transformer
No cable connection needed thus cost saving in term of cable
and cable connection when directly mounted to transformers
Plug in motor
Directly mountable to a pre-wired live RMU on site, in less than 1 min.
SCADA compatible with Remote Terminal Unit (RTU):
Easergy T300
High performance
Switch rated up to 5000 numbers mechanical operations.
A multitude of configurations
A variety of different panel
types are available for each unit
within the range, together with a
PE57064
number of optional accessories
PE57061
enabling Ringmaster to satisfy
the most complex system
specification.
electrical operation
• Interlocked MV cable test access (no need to remove
PE57065
cable terminations or use loose earthing devices)
• Type C bushing offers flexibility of wide choice of
3rd party screened & unscreened termination
system
Free standing,
non-extensible, top entry,
cable connected ring main unit.
• Agriculture
• Factory
• Private residential
• Public residential.
• Automotive
• Food and beverage
• Pharmaceuticals
• Construction materials
• Waste management.
• Conveyors
• Packaging
• Materials handling
• Hoisting.
Key markets
PE58315
• Electricity distribution
• Water
• Rail
• Airports
• Seaports
• Defence
• Gas
• Telecommunications
• Road.
Principal customers
in the electric power market
PE58316
network
Ringmaster is a range of MV switchgear with a genuine IP 54 design to maximise
resistance to the toughest environment:
• Dust
• Pollution
• Humidity.
Cost effective and simple
• The IP54 degree of protection of the Ringmaster’s housing makes it possible
to be used in the most aggressive environment. No consideration needs to be
taken for an external enclosure, saving cost compared to traditional solutions.
• A virtually maintenance free design is achieved having all MV contacts housed
in a sealed for life IP67 SF6 gas filled enclosure.
• Underground handling in narrow tunnels and lifts is simplified by compact
dimensions and light weight.
from our comprehensive range. Flexibility of tailored configurations are available from the wide range of
Schneider Electric products which include:
• Transformers from 315 kVA to 2000 kVA (up to 5 MVA for special applications)
This provides customers with • Extensible and non-extensible Ringmaster MV switchgear
a convenient single source • LV SAIF and shielded fusegear from 800 A to 3200 A
• LV acb and mccb pillars up to 3200 A
package substation with • Automation and monitoring systems
minimum time and costs. • Tailor made enclosures can be mounted on the transformer underbase to provide
single lift complete installation.
Cost savings are achieved by reducing the foundation area requirement due to
the direct coupling which requires minimum cabling and reduced maintenance.
PE58324
The Ringmaster switchboards comply with the requirements of the following standards and regulations:
Description IEC standard IEC classes EN standard
Switchboard IEC 62271-200 LSC partition class PM EN 62271-200
IEC 62271-1 Continuity of service of the cable EN 62271-1
connection and fuse
compartments: LSC2A (1)
Behaviour in the event of internal faults IEC 62271-200 EN 62271-200
Earthing switch IEC 62271-102 E2 EN 62271-102
Ring switch IEC 62271-103 M1, E3(1), C1
Circuit-breaker IEC 62271-100 M1, E2 EN 62271-100
Current transformer IEC 60044-1 EN 60044-1
Voltage transformer IEC 60044-2 EN 60044-2
Voltage presence indicators IEC 61958 EN 61958
Voltage detection systems IEC 61243-5 EN 61243-5
Protection against accidental contact, foreign bodies and IEC 60529 EN 60529 1
ingress of water
Installation HD 637 S
Operation of the electrical equipment EN 50110
TFL protection
An effective low cost option without compromising reliability.
CT operated trip coils (with TFL) provides phase overcurrent and earth fault inverse
time protection, the characteristic being given by a Time Fuse Link (TFL).
This option is suitable for transformer protection up to 1600 kVA.
DE60245-1
• Low cost
• Fast clearance of LV faults
• Simple to replace
• Proven protection to EA standards
• Fast tripping for MV earth faults
• Improved discrimination with LV fuse
Principle of operation
The current transformer feeds a trip coil that is normally shunted by a time fuse link.
In the event of a fault the fuse ruptures, diverting all the fault current through the trip
coil, tripping the breaker. A residually connected trip coil provides instantaneous
earth fault protection.
General
Transformer
use
protection
protection
VIP 40 VIP 45 VIP 400
Phase overcurrent (ANSI 50-51) b b b
Standard
Earth fault phase (ANSI 51N) (sum of current method)
b b
High sensitivity (earth fault CTs)
Thermal overload (ANSI 49) b
Cold load pick-up
Measurement functions
VIP 40/45
Phase current b b b
Earth current b b
PM100578
PM105713
EM100103
Home page
Monitoring / Data / Status
Diagnostic / Events
DE40901EN
Schneider Electric offers you a complete solution, including:
• Easergy T300 telecontrol interface,
• Switchgear that is adapted for telecontrol.
HV/MV
MV ring
Communication network
Network control centre
Nota:
Please consult us for other SCADA platforms, PACiS, OaSys. (1) SAIDI: System Average Interruption Duration Index
C
Standalone
circuit breaker
6 630 A Need more information?
S Stand-alone switch 16 16 kA If your requirements are not listed, please contact your local Schneider Electric
N Non-Extensible 21 21 kA representative at:
www.schneider-electric.com/b2b/en/support/
E Extensible
MU Metering unit
The Ringmaster catalogue allows easy selection and Electronic catalogue requests
specification, based on a broad range of worldwide
applications. Included in this publication is: Electronic copies of this selection guide are available free of charge upon request.
• panel type specifications For this, and other MV literature, please email your full contact details to Email:
• details of optional accessories MVSwitchgearGB@schneider-electric.com
• schematic diagrams
• Installation drawings.
Selection Matrix
T1 - TFL T2 - VIP400
T5 - Glass TFL T3 - VIP40
T4 - VIP45
Options
Accessories selection
Characteristics
22
Electrical and Mechanical
Characteristics of Ringmaster
Rated voltage (Ur) kV 12 13.8
Rated frequency (fr) Hz 50/60 50/60
Rated lightning impulse withstand voltage (Up) kV 75 95
Rated power frequency withstand voltage (Ud) kV 28 38
Rated current
Ring switches (Ir) A 630 630
Circuit breaker (Ir) A 200/630 200/630
Ring switch rated short time withstand, 3 s (Ik) kA 16 21
Ring switch earth short time withstand, 3 s (Ik) kA 16 21
Ring switch peak making current (Ip) kA 40 52.5
Ring switch earth peak making current (Ip) kA 40 52.5
Circuit breaker short time withstand, 3 s (Ik) kA 16 21
Ciruit breaker earth short time withstand, 3 s (Ik) kA 16 21
Circuit breaker peak making current (Ip) kA 40 53
Circuit breaker earth peak making current (Ip) kA 40 53
Internal arc withstand - gas enclosure (1 s) kA 21 (A-FLR) 21 (A-FLR)*
Internal arc withstand - cable box (1 s) kA 13.1(AF)**
Number of operating cycles
Mechanical: ring switch (main) 5000 5000
ring switch 5000 5000
ring switch (earth) 1000 1000
circuit breaker (main) 2000 2000
circuit breaker (earth) 1000 1000
circuit breaker (at rated short circuit breaking 11 10
current)
SF6 gas
Pressure bar G 0.35 0.55
Weight (RN2d/RN6d) g 516 592
Weight (RE2d) g 612 703
Transformer ratings
See table on Time Fuse Link - page13
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
DE60181
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Accessories Integral ring switch cable test facility
CB, LH, RH motor kits Cable
LH, RH ring switch indication 1NO 1NC earth On 1NO Bottom entry up to 1 x 3C 300 mm2
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/ Bottom entry up to 3 x 1C 630 mm2
DC
VPIS indication
Inverted cable boxes (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code Rating
RN2d-T1/16 16 kA, 12 kV, 75 kV BIL
[*] 21kA (AF) - Please consult us.
RN2d-T1/21 21 kA, 13.8 kV, 95 kV BIL [**] 21kA (AF) - Please consult us.
Self powered IDMT overcurrent and earth fault relay, VIP 400. In accordance with
IEC 60255 and BS142
Protection CT’s - 200/1 A class X
• Setting range:
--Overcurrent: 20-200 A
--Earth fault: 2-160 A
Transformer ratings
See table on Time Fuse Link - page 13
Environment
Indoor/outdoor
IP54
DE60185
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 21kA 1s IAC class A-FLR for gas enclosure *
Internal arc 13.1kA 1s IAC class AF for cable boxes **
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Multi voltage shunt trip coil 20-48 V DC - 110-250 V AC/DC
VPIS indication
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Accessories Test facility
CB LH, RH motor kits Integral ring switch cable test facility
LH, RH ring switch indication 1NO 1NC earth On 1NO
Inverted cable boxes (indoor only) Cable
Transformer mounting kit
Bottom entry up to 1 x 3C 300 mm2
Freestanding tee-off cable box Bottom entry up to 3 x 1C 630 mm2
Order information
Code Rating
RN2d-T2/16 16 kA, 12 kV, 75 kV BIL
RN2d-T2/21 21 kA, 13.8 kV, 95 kV BIL
[*] 21kA (AF) - Please consult us.
[**] 21kA (AF) - Please consult us.
MV transformer protection
Environment
Indoor/outdoor
IP54
DE60182
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 21kA 1s IAC class A-FLR for gas enclosure *
Internal arc 13.1kA 1s IAC class AF for cable boxes **
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Accessories Integral ring switch cable test facility
CB, LH, RH motor kit
LH, RH ring switch indication 1NO 1NC earth On 1NO Cable
Multi voltage shunt trip coil Bottom entry up to 1 x 3C 300 mm2
20-48 V DC - 110-250 V AC/DC Bottom entry up to 3 x 1C 630 mm2
VPIS indication
Inverted cable box (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code Rating
RN2d-T3/16 16 kA, 12 kV, 75 kV BIL
RN2d-T3/21 21 kA, 13.8 kV, 95 kV BIL [*] 21kA (AF) - Please consult us.
[**] 21kA (AF) - Please consult us.
MV transformer protection
Protection & control - CB
DE60180
Environment
DE60183
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 21kA 1s IAC class A-FLR for gas enclosure *
Internal arc 13.1kA 1s IAC class AF for cable boxes **
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
Accessories CB earth position selected 1NO
CB, LH, RH motor kits CB earth ON, 1NO
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil Test facility
20-48 V DC - 110-250 V AC/DC Integral ring switch cable test facility
VPIS indication
Inverted cable boxes (indoor only) Cable
Transformer mounting kit Bottom entry up to 1 x 3C 300 mm2
Freestanding tee-off cable box Bottom entry up to 3 x 1C 630 mm2
Order information
Code Rating
RN2d-T4/16 16 kA, 12 kV, 75 kV BIL
RN2d-T4/21 21 kA, 13.8 kV, 95 kV BIL [*] 21kA (AF) - Please consult us.
[**] 21kA (AF) - Please consult us.
Overcurrent and earth fault protection using CT operated trip coils with provision for
time fuse links (glass fuse link)
Protection CT’s - 100/50/5 A class X
Transformer ratings
See table on Time Fuse Link - page13
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
DE60184
Operating mechanism
Independent manual
Standard features
Ring cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch cable test facility
Cable
Accessories
Bottom entry up to 1 x 3C 300 mm2
CB, LH, RH motor kits
Bottom entry up to 3 x 1C 630 mm2
LH, RH ring switch indication 1NO 1NC earth On 1NO
Multi voltage shunt trip coil
20-48 V DC - 110-250 V AC/DC
VPIS indication
Inverted cable boxes (indoor only)
Transformer mounting kit
Freestanding tee off cable box
Order information
Code Rating
RN2d-T5/16 16 kA, 12 kV, 75 kV BIL
[*] 21kA (AF) - Please consult us.
RN2d-T5/21 21 kA, 13.8 kV, 95 kV BIL
[**] 21kA (AF) - Please consult us.
Self powered IDMT overcurrent and earth fault relay, VIP 400. In accordance with
IEC 60255 and BS142
Protection CT’s - 800/400/1 A class X
• Setting range: 800/1 A ratio
--Overcurrent: 80-800 A
--Earth fault: 8-640 A
• Setting range: 400/1 A
--Overcurrent: 40-400 A
--Earth fault: 4-320 A
Environment
Indoor/outdoor
IP54
DE60186
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 21kA 1s IAC class A-FLR for gas enclosure *
Internal arc 13.1kA 1s IAC class AF for cable boxes **
Normal current rating 630 A/630 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Circuit breaker earth switch 16/21 kA
Ring cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Provision for motorised mechanism LH/RH ring switch and circuit breaker with plug
interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Order information
Code Rating
RN6d-T1/16 16 kA, 12 kV, 75 kV BIL
RN6d-T1/21 21 kA, 13.8 kV, 95 kV BIL [*] 21kA (AF) - Please consult us.
[**] 21kA (AF) - Please consult us.
Overcurrent and earth fault protection using CT operated trip coils with provision for
time fuse links.
Protection CT’s - 100/50/5 A class X
Transformer ratings
See table on Time Fuse Link - page 13
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 21kA 1s IAC class A-FLR for gas enclosure *
Internal arc 13.1kA 1s IAC class AF for cable boxes **
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
DE60187
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Extensible (RHS)
Provision for motorised mechanism LH/RH ring switch with plug interface
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Test facility
Integral ring switch test facility
CB, LH, RH motor kits
LH, RH ring switch indication 1NO 1NC earth On 1NO Cable
Multi voltage shunt trip coil Bottom entry up to 1 x 3C 300 mm2
20-48 V DC - 110-250 V AC/DC Bottom entry up to 3 x 1C 630 mm2
VPIS indication
Integral circuit breaker test facility Accessories
Inverted cable boxes LH, CB (indoor only)
Transformer mounting kit
Freestanding tee-off cable box
Order information
Code Rating
RE2d-T1/16 16 kA, 12 kV, 75 kV BIL
RE2d-T1/21 21 kA, 13.8 kV, 95 kV BIL
[*] 21kA (AF) - Please consult us.
[**] 21kA (AF) - Please consult us.
Self powered IDMT overcurrent and earth fault relay, VIP 400. In accordance with
IEC 60255 and BS 142.
Protection CT’s - 200/1 A class X
• Setting range:
--Overcurrent: 20-200 A
--Earth fault: 2-160 A
Transformer ratings
See table on Time Fuse Link - page13
Documents
Installation drawing ref: RMINST-22
Schematic drawing ref: RMSCH-03
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
DE60188
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Extensible (RHS)
Provision for motorised mechanism LH/RH ring switch
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Accessories Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB, LH, RH motor kits
CB earth position selected 1NO
LH, RH ring switch indication 1NO 1NC
CB earth ON, 1NO
Multi voltage shunt trip coil
20-48 V DC - 110-250 V AC/DC Test facility
VPIS indication
Inverted cable box LH CB (indoor only) Integral ring switch test facility
Transformer mounting kit
Cable
Freestanding tee-off cable box
Bottom entry up to 1 x 3C 300 mm2
Order information Bottom entry up to 3 x 1C 630 mm2
Code Rating
RE2d-T2/16 16 kA, 12 kV, 75 kV BIL
RE2d-T2/21 21 kA, 13.8 kV, 95 kV BIL [*] 21kA (AF) - Please consult us.
[**] 21kA (AF) - Please consult us.
MV transformer protection
Protection & control - CB
DE60211
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 21kA 1s IAC class A-FLR for gas enclosure *
Internal arc 13.1kA 1s IAC class AF for cable boxes **
DE60189
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Extensible (RHS)
Provision for motorised mechanism LH/RH ring switch
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 1NC
CB earth position selected 1NO
CB earth ON, 1NO
Accessories
CB, LH, RH motor kit Test facility
LH, RH ring switch indication 1NO 1NC Integral ring switch test facility
Multi voltage shunt trip coil
20-48 V DC - 110-250 V AC/DC Cable
VPIS indication
Bottom entry up to 1 x 3C 300 mm2
Inverted cable boxes LH, CB (indoor only)
Bottom entry up to 3 x 1C 630 mm2
Transformer mounting kit
Freestanding tee-off cable box
Or der information
Code Rating
RE2d-T3/16 16 kA, 12 kV, 75 kV BIL
[*] 21kA (AF) - Please consult us.
RE2d-T3/21 21 kA, 13.8 kV, 95 kV BIL
[**] 21kA (AF) - Please consult us.
MV transformer protection
Protection & control - CB
DE60211
Environment
Indoor/outdoor
IP54
Ratings
DE60190
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 21kA 1s IAC class A-FLR for gas enclosure *
Internal arc 13.1kA 1s IAC class AF for cable boxes **
Normal current rating 630 A/200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Ring switch cable earth switch, 16/21 kA 3 s
Transformer earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Extensible (RHS)
Provision for motorised mechanism LH/RH ring switch
Accessories Indication
CB, LH, RH motor kit Mechanical tripped on fault indicator
LH, RH ring switch indication 1NO 1NC Mechanical ON/OFF indicator
Multi voltage shunt trip coil Mechanical earth/main indicator
20-48 V DC - 110-250 V AC/DC Gas pressure indicator
VPIS indication CB auxiliary contacts 1NO 1NC
Inverted cable boxes LH, CB (indoor only) Earth position selected 1NO
Transformer mounting Earth ON, 1NO
Freestanding tee-off cable box
Test facility
Order information Integral ring switch test facility
Code Rating
Cable
RE2d-T4/16 16 kA, 12 kV, 75 kV BIL
RE2d-T4/21 21 kA, 13.8 kV, 95 kV BIL Bottom entry up to 1 x 3C 300 mm2
Bottom entry up to 3 x 1C 630 mm2
CN2-T1, CN2-T6 45
SN6-S1, SN6-S2 49
MU6d-N** 58
CN2-T9 CN2-T6
VIP 400 TFL
Environment
Indoor / outdoor b b
IP54 b b
Ratings
Normal rated current 200 A b b
12 kV 16 kA 3 seconds 75 kV BIL b b
13.8 kV 21 kA 3 seconds 95 kV BIL O O
Cable earth switch 16 kA 3 seconds b b
Cable earth switch 21 kA 3 seconds O O
Transformer earth switch 3.15 kA 3 seconds b b
Mechanism
Independent manual b b
Protection & control - circuit breaker
CT’s dual ratio - 100/50/5 A class X b
CT’s ratio - 200/1 A class X b
CT’s dual ratio 200/100/1 A 5P20
Overcurrent & earth fault CT operated trip coils b
Time fuse Link O
IDMT overcurrent & earth fault relay - VIP 400 b
IDMT overcurrent and earth fault relay Sepam 10
20 V-250 shunt trip coil b b
Circuit breaker auxiliary switch 1NO 2NC b b
Indication
Mechanical ON/OFF b b
Mechanical EARTH/MAIN b b
VPIS indication (6.6 - 13.8 kV) O O
Auxiliary switch contacts 1NO 2NC b b
Gas pressure indicator b b
Test facility
Integral cable test facility b b
Standard features
Operating handle b b
Transformer earth switch 3.15 kA 3 seconds b b
Cable (see available cable kit accessories)
Bottom entry up 300 mm2 1 x 3C b b
Bottom entry up 630 mm2 3 x 1C b b
Key: b Standard feature O Optional feature
CN2-T9 CN2-T6
Kit no.
VIP 400 TFL
Cable kits
Tee-off cable box v v RMR-F47
Gland plate 1 x 3C O O RMR-A48
Gland plate 3 x 1C O O RMR-A49
Angled gland plates (RMR) O O RMR-A50
Blank aluminium gland plate O O RMR-A52
Brass wiping gland 1 x 3C O O RMR-A10
Brass wiping gland 3 x 1C O O RMR-A11
Tubular gland 1 x 3C O O RMR-A12
Tubular gland 3 x 1C O O RMR-A13
CES5 gland plate 1 x 3C O O RMR-A132
Installation items
Set of padlocks - 6 no O O RMR-A18/6
Anti-vandal fixings, including tool O O RMR-A19
Foundation bolts (not required for transformer mounting) O O RMR-A22
Multicore pilot glands O O RMR-A16
Time Fuse Link (set of 2 - specify rating as table page 133) O RMR-A17
Operational items
Operating handle b b RMR-A23
VPIS indication (6.6-13.8 kV) v v RMR-F108
Neon lamp test unit (including lamp) O O RMR-A24
Neon lamp O O RMR-A81
VAP 6 test unit for VIP 400 O RMR-A202
Mechanical interlocks
Key free, earth on v v RMR-F85
Key free, unit off v v RMR-F86
Transformer earth switch, key free, earth on v v RMR-F110
N. B. specify lock symbol at time of ordering (3 digits max) not
available with motor mechanisms
Order codes
12 kV, 16 kA, 75 kV BIL CN2-T9/16 CN2-T6/16
13.8 kV, 21 kA, 95 kV BIL CN2-T9/21 CN2-T6/21
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Tee-off earth switch, 3.15 kA 3 s
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 2 NC
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Tee-off cable box
Glands and plates
Interlocks
Please refer to accessories list.
Order information
Code Rating
CN2-T9/16 16 kA, 12 kV, 75 kV BIL
CN2-T9/21 21 kA, 13.8 kV, 95 kV BIL
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Transformer earth switch, 16/21 kA 3 s
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
CB auxiliary contacts 1NO 2 NC
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Tee-off cable box
Glands and plates
Interlocks
Please refer to accessories list.
Order information
Code Rating
CN2-T6/16 16 kA, 12 kV, 75 kV BIL
CN2-T6/21 21 kA, 13.8 kV, 95 kV BIL
SN6-S1 SN6-S2
Manual operation Provision for actuator
Environment
Indoor / outdoor b b
IP54 b b
Ratings
Normal rated current 630 A b b
13.8 kV 21 kA 3 seconds 95 kV BIL b b
Cable earth switch 21 kA 3 seconds b b
Transformer earth switch 3.15 kA 3 seconds b b
Mechanism
Independent manual b b
Provision for actuator 24 V DC b
Actuator 24 V DC O
Indication
Mechanical ON/OFF b b
Mechanical EARTH/MAIN b b
VPIS indication (6.6 - 13.8 kV) O O
Auxiliary switch contacts 1NO 2NC b
Phase and earth fault detection CT’s for Easergy T300 O
Provision for EFPI O O
Test facility
Integral cable test facility b b
Standard features
Operating handle b b
Transformer earth switch 3.15 kA 3 seconds b b
Cable (see available cable kit accessories)
Bottom entry up 300 mm2 1 x 3C b b
Bottom entry up 630 mm2 3 x 1C b b
Key: b Standard feature O Optional feature
SN6-S1 SN6-S2
Kit no.
Manual operation Provision for actuator
Cable kits
Tee-off cable box v v RMR-F47
Gland plate 1 x 3C O O RMR-A48
Gland plate 3 x 1C O O RMR-A49
Angled gland plates (RMR) O O RMR-A50
Blank aluminium gland plate O O RMR-A52
Brass wiping gland 1 x 3C O O RMR-A10
Brass wiping gland 3 x 1C O O RMR-A11
Tubular gland 1 x 3C O O RMR-A12
Tubular gland 3 x 1C O O RMR-A13
CES5 gland plate 1 x 3C O O RMR-A132
Installation items
Set of padlocks - 6 no O O RMR-A18/6
Anti-vandal fixings, including tool O O RMR-A19
Foundation bolts (not required for transformer mounting) O O RMR-A22
Multicore pilot glands O O RMR-A16
Operational items
Operating handle b b RMR-A23
VPIS indication (6.6-13.8 kV) v v RMR-F108
Neon lamp test unit (including lamp) O O RMR-A24
Neon lamp O O RMR-A81
Actuator 24 V DC v RMR-F67
Mechanical interlocks
Key free, earth on v RMR-F85
Key free, unit off v RMR-F86
Transformer earth switch, key free, earth on v v RMR-F110
N. B. specify lock symbol at time of ordering (3 digits
max) not available with motor mechanisms
Order codes
13.8 kV, 21 kA, 95 kVBIL SN6-S1/21 SN6-S2/21
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
Switch disconnector
DE60193
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 13.8 kV
Normal rated BIL 95 kV
Operating mechanism
Independent manual
Standard features
Transformer earth switch, 16/21 kA 3 s
Cable earth switch, 21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Tee-off cable box
VPIS indication
Glands and plates
Interlocks
Please refer to accessories list.
Order information
Code Rating
SN6-S1/21 21 kA, 13.8 kV, 95 kV BIL
Switch disconnector
DE60194
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 13.8 kV
Normal rated BIL 95 kV
Operating mechanism
Independent manual
Provision for actuator, 24 V DC
Standard features
Transformer earth switch, 16/21 kA 3 s
Cable earth switch, 21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
Auxiliary contacts 1NO 2NC
Earth selected auxiliary contact 1NO
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Tee-off cable box
Actuator, 24 V DC
VPIS indication
Glands and plates
Please refer to accessories list.
Order information
Code Rating
SN6-S2/21 21 kA, 13.8 kV, 95 kV BIL
Metering transformers
• Metering CT’s L1 & L3 phases
--50/25/5 A
--7.5 VA class 0.5s
• Metering VT ph - ph
--11 kV/110 V 50 VA
--class 0.5
Environment
Indoor/outdoor
IP54
Ratings
Short time withstand 16 kA 1 s
Normal current rating 200 A
Normal rated voltage 12 kV
Normal rated BIL 75 kV
Standard features
Direct coupling between RMU and transformer (optional freestanding cable
connection)
Cable connection
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Cable box
Glands and plates
Installation kits
Please refer to accessories list.
Order information
Code Rating
MU2d-M1/16 16 kA, 12 kV, 75 kV BIL
Metering transformers
• Metering CT’s L1 & L3 phases
--100/50/5 A
--10 VA class 0.5s
• Metering VT ph - ph
--11 kV/110 V 50 VA
--class 0.5
Environment
Indoor/outdoor
IP54
Ratings
Short time withstand 16 kA 1 s
Normal current rating 200 A
Normal rated voltage 12 kV
Normal rated BIL 75 kV
Standard features
Direct coupling between RMU and transformer (optional freestanding cable
connection)
Cable connection
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Cable box
Glands and plates
Installation kits
Please refer to accessories list.
Order information
Code Rating
MU2d-M2/16 16 kA, 12 kV, 75 kV BIL
Metering transformers
• Metering CT’s L1 & L3 phases
--200/100/5 A
--10 VA class 0.5s
• Metering VT ph - ph
--11 kV/110 V 50 VA
--class 0.5
Environment
Indoor/outdoor
IP54
Ratings
Short time withstand 16 kA 1 s
Normal current rating 200 A
Normal rated voltage 12 kV
Normal rated BIL 75 kV
Standard features
Direct coupling between RMU and transformer
(optional freestanding cable connection)
Cable connection
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Cable box
Glands and plates
Installation kits
Please refer to accessories list.
Order information
Code Rating
MU2d-M3/16 16 kA, 12 kV, 75 kV BIL
Metering transformers
• Metering CT’s L1 & L3 phases (16 kA, 12 kV, 75 kV BIL)
10 VA class 0.5s N1/16 N2/16 N3/16 N5/16
400/200/5 A b
600/5 A b
400/5 A b
600/300/5 A b
• Metering VT ph - ph (16 kA, 12 kV, 75 kV BIL)
50 VA class 0.5 N1/16 N2/16 N3/16 N5/16
11 kV/110 V b b b
11 kV/6.6 kV/110 V b
Environment
Indoor/outdoor
IP54
Ratings
Short time withstand 16 kA 1 s
Normal current rating 630 A
Normal rated voltage 12 kV
Normal rated BIL 75 kV
Standard features
Direct coupling between RMU and transformer
(optional freestanding cable connection)
Cable connection
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Cable box
Glands and plates
Installation kits
Please refer to accessories list.
Order information
Code Rating
MU6d-N** 16 kA, 12 kV, 75 kV BIL
(*) See complete titles footer CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2-
T30 T3 T7 T32 T31 T35 T36 T33 T34 T37 T38 T39
Environment
Indoor / outdoor b b b b b b b b b b b b
IP54 b b b b b b b b b b b b
Ratings
Busbars 630 A b b b b b b b b b b b b
Circuit breaker normal rated current 200 A b b b b b b b b b b b b
12 kV 16 kA 3 seconds 75 kV BIL b b b b b b b b b b b b
13.8 kV 21 kA 3 seconds 95 kV BIL O O O O O O O O O O O O
Cable earth switch 16 kA 3 seconds b b b b b b b b b b b b
Cable earth switch 21 kA 3 seconds O O O O O O O O O O O O
Mechanism
Independent manual b b b b b b b b b b b b
Provision for actuator 24 V DC b b b b
Actuator 24 V DC O O O O
Operating handle b b b b b b b b b b b b
Protection system
CT’s dual ratio - 500/200/1 A class x b b
Overcurrent relay - VIP 40 b
CT’s dual ratio - 100/50/5 A class X b
CT’s dual ratio 200/100/1 A 5P20
CT ratio - 200/1 A class X b b b b b b b b b
Overcurrent & earth fault CT operated trip coils b
Overcurrent & earth fault relay VIP 45 b
Time fuse link O
IDMT overcurrent & earth fault relay - VIP 400 b b b b b b b b b
20 V-250 shunt trip coil b b b b b b b b b b b b
Auxiliary switch 1NO 2NC b b b b b b b b b b b b
Metering
CT’s -200/100/5 A 0.5s 10 VA b b b b b b b
VT’s -13.8 kV/110 V 0.5 10 VA 13.8/110 V/110 V 0.5 50 VA 3P 20
VA b b
VT’s -11 kV/110 V 0.5 50 VA b b b
VT’s -6.6 kV/110 V 0.5 50 VA b b
VT’s phase - phase, CT’s L1 & L3 b b b b
VT’s phase - earth, CT’s L1, L2 & L3 b b b
Indication
Mechanical ON/OFF b b b b b b b b b b b b
Mechanical EARTH/MAIN b b b b b b b b b b b b
Cable VPIS indication (6.6 - 13.8 kV) O O O O O O O O O O O O
Auxiliary switch contacts 1NO 2NC b b b b b b b b b b b b
Earth selected auxiliary contacts 1NO b b b b
Test facility
Integral cable test facility b b b b b b b b b b b b
Cable
Bottom entry up to 300 mm2 1 x 3C b b b b b b b b b b b b
Bottom entry up to 630 mm2 3 x 1C b b b b b b b b b b b b
Top entry cables O O O O O O O O O O O O
Key: b Standard feature O Optional feature
(*) Complete titles:
CE2-T30-VIP400 --> CE2-T30/400
CE2-T33/40
(*) See complete titles CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2-
footer Kit no.
T30 T40 T7 T32 T31 T35 T36 T33 T34 T37 T38 T39
Cable kits
Gland plate 1 x 3C O O O O O O O O O O O O RMR-A48
Gland plate 3 x 1C O O O O O O O O O O O O RMR-A49
Angled gland plates (RMR) O O O O O O O O O O O O RMR-A50
Blank aluminium gland plate O O O O O O O O O O O O RMR-A52
Brass wiping gland 1 x 3C O O O O O O O O O O O O RMR-A10
Brass wiping gland 3 x 1C O O O O O O O O O O O O RMR-A11
Tubular gland 1 x 3C O O O O O O O O O O O O RMR-A12
Tubular gland 3 x 1C O O O O O O O O O O O O RMR-A13
CES5 gland plate 1 x 3C O O O O O O O O O O O O RMR-A132
Top entry cables standard panels v v v v v RMR-F93
Top entry cables MU6 only v v v v v v v RMR-F94
Installation items
3 phase busbars 630 A O O O O O RMR-A14
3 phase busbars 630 A O O O O O O O RMR-A78
Busbar end kit O O O O O O O O O O O O RMR-A15
Set of padlocks - 6 no O O O O O O O O O O O O RMR-A18/6
Foundation bolts (not required b b b b b b b b b b b b
for transformer mounting) RMR-A22
(*) See complete CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2-
titles footer Kit no.
T30 T40 T7 T32 T31 T35 T36 T33 T34 T37 T38 T39
Earth fault passage indication (choose provision kit and an EFPI required if not using Easergy T300)
EFPI provision kit,
inside cable box O O O O O O O O O O O O RMR-F30
Bowden STD EFPI
type NB O O O O O O O O O O O O RMR-A277
Bowden LV reset
EFPI type NB1 O O O O O O O O O O O O RMR-A278
Bowden LV reset &
alarm type NB2 O O O O O O O O O O O O RMR-A279
Bowden “RR” EFPI
and CT O O O O O O O O O O O O RMR-A56
Fundamentals ER
“FIND” EFPI and CT O O O O O O O O O O O O RMR-A57
Ancillary items
Tool box O O O O O O O O O O O O RMR-A80
Order code
12 kV, 16 kA, 75 kV BIL CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2-
N/A N/A
T30/16 T3/16 T7/16 T32/16 T31/16 T35/16 T36/16 T33/16 T34/16 T38/16
13.8 kV, 21 kA, 95 kV BIL CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2- CE2-
N/A
T30/21 T3/21 T7/21 T32/21 T31/21 T35/21 T36/21 T33/21 T34/21 T37/21 T39/21
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
VPIS indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
Please refer to accessories list.
Order information
Code Rating
CE2-T30/16 16 kA, 12 kV, 75 kV BIL
CE2-T30/21 21 kA, 13.8 kV, 95 kV BIL
11 kV
Protection & control - CB
Overcurrent and earth fault protection using CT operated trip coils with provision
for time fuse links.
Protection CT’s - 100/50/5 A class X
Shunt trip coil, 20 V DC-250 V AC
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
VPIS indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
Please refer to accessories list.
Order information
Code Rating
CE2-T7/16 16 kA, 12 kV, 75 kV BIL
CE2-T7/21 21 kA, 13.8 kV, 95 kV BIL
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Accessories Anti-reflex operating handle
VPIS indication
Glands and plates Standard features
Interlocks Cable earth switch, 16/21 kA 3 s
Operating handle
Busbar kit Indication
Top entry cables Mechanical tripped on fault flag indicator
Please refer to accessories list. Mechanical ON/OFF indicator
Mechanical earth/main indicator
Order information
Auxiliary contacts,1NO 2NC
Gas pressure indicator
16 kA, 12 kV, CE2- CE2- CE2-
75 kV BIL T40/16 T32/16
N/A
T38/16 Test facility
Integral cable test facility
21 kA, 13.8 kV, CE2- CE2- CE2- Cable
N/A
95 kV BIL T40/21 T32/21 T37/21
Bottom entry up to 300 mm2 1 x 3C
Metering VT Bottom entry up to 630 mm2 3 x 1C
information: b b
Phase to phase
Phase to earth b b
6.6 kV/110 V b
11 kV/110 V (1) b b
13.8 kV/110 V b
(1) Please consult Schneider Electric when ordering
units with 95 kV BIL voltage Tel: +44 (0)113 290 3500
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Provision for actuator, 24 V DC
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Earth selected auxiliary contact1NO
Gas pressure indicator
Test facility
Integral cable test facility
Accessories
Cable
Actuator, 24 V DC
Bottom entry up to 300 mm2 1 x 3C
VPIS indication
Bottom entry up to 630 mm2 3 x 1C
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
Please refer to accessories list.
Order information
Code Rating
CE2-T31/16 16 kA, 12 kV, 75 kV BIL
CE2-T31/21 21 kA, 13.8 kV, 95 kV BIL
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Accessories
Actuator, 24 V DC Operating mechanism
VPIS indication Independent manual
Glands and plates Provision for actuator, 24 V DC
Interlocks
Operating handle Standard features
Busbar kit
Cable earth switch, 16/21 kA 3 s
Top entry cables
Anti-reflex operating handle
Please refer to accessories list.
Indication
Order information
Mechanical tripped on fault indicator
16 kA, 12 kV, Mechanical ON/OFF indicator
75 kV BIL
CE2-T36/16 N/A Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
21 kA, 13.8 kV, Earth selected auxiliary contact1NO
CE2-T36/21 CE2-T39/21
95 kV BIL Gas pressure indicator
Metering VT information:
Phase to phase b Test facility
Integral cable test facility
Phase to earth b
6.6 kV/110 V b Cable
11 kV/110 V (1) Bottom entry up to 300 mm2 1 x 3C
13.8 kV/110 V b Bottom entry up to 630 mm2 3 x 1C
General arrangement RMINST-02 RMINST-02
drawing Page 96 Page 96
Schematic diagram RMSCH-20 RMSCH-36
Page 124 Page 130
(1) Please consult Schneider Electric when ordering
units with 95 kV BIL voltage
Tel: +44 (0)113 290 3500
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Actuator, 24 V DC
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Accessories Earth selected auxiliary contact1NO
VPIS indication Gas pressure indicator
Glands and plates
Interlocks Test facility
Operating handle Integral cable test facility
Busbar kit
Top entry cables Cable
Please refer to accessories list. Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Order information
Code Rating
CE2-T35/16 16 kA, 12 kV, 75 kV BIL
CE2-T35/21 21 kA, 13.8 kV, 95 kV BIL
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator
Test facility
Integral cable test facilities
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
VPIS indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
Please refer to accessories list.
Order information
Code Rating
CE2-T33/16 16 kA, 12 kV, 75 kV BIL
CE2-T33/21 21 kA, 13.8 kV, 95 kV BIL
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 200 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Gas pressure indicator
Test facility
Integral cable test facilities
Cable
Accessories Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
VPIS indication
Glands and plates
Interlocks
Operating handle
Busbar kit
Top entry cables
Please refer to accessories list.
Order information
Code Rating
CE2-T34/16 16 kA, 12 kV, 75 kV BIL
CE2-T34/21 21 kA, 13.8 kV, 95 kV BIL
(*) See complete titles footer CE6- CE6- CE6- CE6- CE6- CE6- CE6- CE6- CE6-
T30 T33 T39 T31 T34 T35 T36 T38 T37
Environment
Indoor / outdoor b b b b b b b b b
IP54 b b b b b b b b b
Ratings
Busbars 630 A b b b b b b b b b
Circuit breaker normal rated current 630 A b b b b b b b b b
12 kV 16 kA 3 seconds 75 kV BIL b b b b b b b b b
13.8 kV 21 kA 3 seconds 95 kV BIL O O O O O O O O O
Cable earth switch 16 kA 3 seconds b b b b b b b b b
Cable earth switch 21 kA 3 seconds O O O O O O O O O
Mechanism
Independent manual b b b b b b b b b
Provision for actuator 24 V DC b b b b
Actuator 24 V DC O O O O
Operating handle b b b b b b b b b
Protection system
CT ratio - 800/1 A class X b b b b b b b b b
CT dual ratio 800/400/1 A 5P20
IDMT overcurrent & earth fault relay - VIP 400 b b b b b b b b b
20 V-250 V shunt trip coil b b b b b b b b b
Auxiliary switch 1NO 2NC b b b b b b b b b
Metering
CT’s - 400/200/5 A 0.5s 10 VA b b b b b b b
VT’s - 13.8 kV/110 V/110 V/ 0.5 50 VA 3P 20 VA b b
VT’s - 11 V/110 V 0.5 50 VA b b b
VT’s - 6.6 kV/110 V 0.5 50 VA b b
VT’s - phase - phase, CT’s L1 & L3 b b b b
VT’s phase - earth, CT’s L1, L2 & L3 b b b
Indication
Mechanical ON/OFF b b b b b b b b b
Mechanical EARTH/MAIN b b b b b b b b b
Cable VPIS indication (6.6 - 13.8 kV) O O O O O O O O O
Auxiliary switch contacts 1NO 2NC b b b b b b b b b
Indication CT 600/5 A 5 VA CLS 1 L2 ph b b b b b b b b b
Ammeter 0-600 A b b b b b b b b b
Earth selected auxiliary contacts 1NO b b b
Gas pressure indicator b b b b b b b b b
Test facility
Integral cable test facility b b b b b b b b b
Cable
Bottom entry up to 300 mm2 1 x 3C b b b b b b b b b
Bottom entry up to 630 mm2 3 x 1C b b b b b b b b b
Top entry cables O O O O O O O O O
Key: b Standard feature O Optional feature
(*) Complete titles:
CE6-T30-VIP400 --> CE6-T30/400
(*) See complete titles footer CE6- CE6- CE6- CE6- CE6- CE6- CE6- CE6- CE6- Kit no.
T30 T33 T39 T31 T34 T35 T36 T38 T37
Cable kits
Gland plate 1 x 3C O O O O O O O O O RMR-A48
Gland plate 3 x 1C O O O O O O O O O RMR-A49
Angled gland plates (RMR) O O O O O O O O O RMR-A50
Blank aluminium gland plate O O O O O O O O O RMR-A52
Brass wiping gland 1 x 3C O O O O O O O O O RMR-A10
Brass wiping gland 3 x 1C O O O O O O O O O RMR-A11
Tubular gland 1 x 3C O O O O O O O O O RMR-A12
Tubular gland 3 x 1C O O O O O O O O O RMR-A13
CES5 gland plate 1 x 3C O O O O O O O O O RMR-A132
Top entry cables standard panels v v RMR-F93
Top entry cables MU6 only v v v v v v v RMR-F94
Installation items
3 phase busbars 630 A O O RMR-A14
3 phase busbars 630 A O O O O O O O RMR-A78
Busbar end kit O O O O O O O O O RMR-A15
Set of padlocks - 6 no O O O O O O O O O RMR-A18/6
Foundation bolts (not required for b b b b b b b b b RMR-A22
transformer mounting)
Multicore pilot glands O O O O O O O O O RMR-A16
Operational items
Operating handle b b b b b b b b b RMR-A23
Cable VPIS indication (6.6 - 13.8 kV) v v v v v v v v v RMR-A108
Neon lamp test unit (including lamp) O O O O O O O O O RMR-A24
Neon lamp O O O O O O O O O RMR-A81
Actuator 24 V DC v v v v RMR-F67
Polarity conversion kit (1) v v v v RMR-F391
Mechanical interlocks
Key free, EARTH ON v v v v v RMR-F85
Key free, MAIN OFF v v v v v RMR-F86
N. B. specify lock symbol at time of ordering ( 3 digits max) not available with motor mechanisms
Earth fault passage indication (choose provision kit and an EFPI required if not using Easergy T200E)
EFPI provision kit, inside cable box O O O O O O O O O RMR-F30
Bowden STD EFPI type NB O O O O O O O O O RMR-A277
Bowden LV reset EFPI type NB1 O O O O O O O O O RMR-A278
Bowden LV reset & alarm type NB2 O O O O O O O O O RMR-A279
Bowden “RR” EFPI and CT O O O O O O O O O RMR-A56
Fundamentals ER “FIND” EFPI and CT O O O O O O O O O RMR-A57
Ancillary items
Tool box O O O O O O O O O RMR-A80
Order code
12 kV, 16 kA, 75 kV BIL CE6- CE6- CE6- CE6- CE6- CE6- N/A N/A CE6-
T4/16 T5/16 T6/16 T8/16 T9/16 T10/16 T24/16
13.8 kV, 21 kA, 95 kV BIL CE6- CE6- CE6- CE6- CE6- CE6- CE6- CE6- N/A
T4/21 T5/21 T6/21 T8/21 T9/21 T10/21 T22/21 T23/21
Key: b Standard feature v Factory fitted accessory O Loose accessory, assembled on site
(1) Only required when unit is used with RE2d ring main units and automation.
(*) Complete titles:
CE6-T30-VIP400 --> CE6-T30/400
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Ammeter 0-600 A
Indication CT L2 ph - 600/5 A class 1.0, 5 VA
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300 mm2 1 x 3C
Accessories Bottom entry up to 630 mm2 3 x 1C
VPIS indication
Glands and plates
Interlocks
Busbar kit
Top entry cables
Please refer to accessories list.
Order information
Code Rating
CE6-T30/16 16 kA, 12 kV, 75 kV BIL
CE6-T30/21 21 kA, 13.8 kV, 95 kV BIL
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Accessories Independent manual
Actuator, 24 V DC
VPIS indication Standard features
Glands and plates Cable earth switch, 16/21 kA 3 s
Interlocks Anti-reflex operating handle
Busbar kit
Top entry cables Indication
Please refer to accessories list. Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Order information Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
16 kA, 12 kV, CE6- CE6- CE6- Ammeter 0-600 A
N/A
75 kV BIL T 33/16 T39/16 T37/16 Indication CT L2 ph - 600/5 A class 1.0, 5 VA
Gas pressure indicator
21 kA,
CE6- CE6- CE6-
13.8 kV, N/A Test facility
T33/21 T39/21 T36/21
95 kV BIL
b b Integral cable test facility
Metering VT
information:
Phase to phase Cable
Bottom entry up to 300 mm2 1 x 3C
Phase to earth b b
Bottom entry up to 630 mm2 3 x 1C
6.6 kV/110 V b
11 kV/110 V (1) b b
13.8 kV/110 V b
(1) Please consult Schneider Electric when ordering
units with 95 kV BIL voltage
Tel: +44 (0)113 290 3500
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Provision for actuator, 24 V DC
Standard features
Cable earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Earth selected auxiliary contact1NO
Ammeter 0-600 A
Indication CT L2 ph - 600/5 A class 1.0, 5 VA
Gas pressure indicator
Test facility
Integral cable test facility
Accessories
Actuator, 24 V DC Cable
VPIS indication Bottom entry up to 300 mm2 1 x 3C
Glands and plates Bottom entry up to 630 mm2 3 x 1C
Interlocks
Busbar kit
Top entry cables
Please refer to accessories list.
Order information
Code Rating
CE6-T31/16 16 kA, 12 kV, 75 kV BIL
CE6-T31/21 21 kA, 13.8 kV, 95 kV BIL
Circuit breaker, metering Extensible circuit breaker
and switches
630 A
CE6-T**
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 12/13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
Accessories Cable earth switch, 16/21 kA 3 s
VPIS indication Anti-reflex operating handle
Glands and plates
Indication
Interlocks
Busbar kit Mechanical tripped on fault flag indicator
Top entry cables Mechanical ON/OFF indicator
Please refer to accessories list. Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Order information Earth selected auxiliary contacts
Ammeter 0-600 A
16 kA, CE6- CE6- N/A Indication CT L2 ph- 600/5 A class 1.0, 5 VA
12 kV, 75 kV BIL T34/16 T35/16 Gas pressure indicator
Switch disconnector
DE60201
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 13.8 kV
Normal rated BIL 95 kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 21 kA 3 s
Anti-reflex operating handles
Indication
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
VPIS indication
Glands and plates
Interlocks
Busbar kit
Top entry cables
Please refer to accessories list.
Order information
Code Rating
SE6-S1/21 21 kA, 13.8 kV, 95 kVBIL
Switch disconnector
DE60202
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 13.8 kV
Normal rated BIL 95 kV
Operating mechanism
Independent manual
Provision for actuator, 24 V DC
Standard features
Cable earth switch, 21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2NC
Earth selected auxiliary contact 1NO
Gas pressure indicator
Test facility
Integral cable test facility
Cable
Bottom entry up to 300 mm2 1 x 3C
Bottom entry up to 630 mm2 3 x 1C
Accessories
Actuator, 24 V DC
VPIS indication
Glands and plates
Interlocks
Busbar kit
Top entry cables
Please refer to accessories list.
Order information
Code Rating
SE6-S2/21 21 kA, 13.8 kV, 95 kV BIL
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 13.8 kV
Normal rated BIL 95 kV
Operating mechanism
Independent manual
Standard features
Cable earth switch, 21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical earth/main indicator
Gas pressure indicator
Test facility
N/A
Cable
N/A
Accessories
Interlocks
Busbar kit
Please refer to accessories list.
Order information
Code Rating
SE6-E1/21 21 kA, 13.8 kV, 95 kV BIL
CE6-B10
CE6-B9
SE6-B1 Bus-section manual
Bus-section manual
Bus-section manual Metering
Metering
Provision for actuator
Environment
Indoor / outdoor b b b
IP54 b b b
Ratings
Busbars 630 A b b b
Circuit breaker normal rated current 630 A b b
Switch normal rated current 630 A b
12 kV 16 kA 3 seconds 75 kV BIL b b
13.8 kV 21 kA 3 seconds 95 kV BIL b O O
RH busbar earth switch 16 kA 3 seconds b b
RH busbar earth switch 21 kA 3 seconds b O O
Mechanism
Independent manual b b b
Provision for actuator 24 V DC b
Actuator 24 V DC O
Operating handle b b b
Protection system
CT ratio - 800/1 A class X b b
IDMT overcurrent & earth fault relay - VIP 400 b b
20- 250 V shunt trip coil b b
Auxiliary switch1NO 2 NC b b
Metering
CT’s - 400/200/5 A 0.5s 10 VA b b
VT’s - 11 kA/110 V 0.5 50 VA b b
VT’s phase - phase, CT’s L1 & L3 b b
Indication
Mechanical ON/OFF b b b
Mechanical EARTH/MAIN b b b
Earth selected auxiliary contact1NO b
RH busbar VPIS indication O O O
Auxiliary switch contacts1NO 2NC b b
Indication CT 600/5 A 5 VA CLS 1 L2 phase b b
Ammeter 0-600 A b b
Gas pressure indicator b b b
Integral test facility
RH busbar earthing b b b
LH busbar earthing ( using SE6-E1) O O O
Key: b Standard feature O Optional feature
CE6-B10
CE6-B9 Bus-section
SE6-B1
Bus-section manual Kit no.
Bus-section Metering
manual
manual Provision for
Metering
actuator
Installation items
3 phase busbars 630 A RMR-A14
3 phase busbars 630 A (Joggle metering) v v v RMR-A79
3 phase busbars 630 A double width (metering) v v v RMR-A78
Set of padlocks - XX no O O O RMR-A18/6
Busbar end kit (1 end kit required per switchboard) O O O RMR-A15
Foundation bolts (not required for transformer mounting) b b b RMR-A22
Bus-section disconnector
DE60204
Environment
Indoor/outdoor
IP54
Ratings
Busbars 630 A
Short time withstand 21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 13.8 kV
Normal rated BIL 95 kV
Operating mechanism
Independent manual
Standard features
RH busbar earth switch, 21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Gas pressure indicator
Test facility
Integral RH busbar test facility
Cable
N/A
Accessories
VPIS indication
Interlocks
Busbars
Please refer to accessories list.
Order information
Code Rating
SE6-B1/21 21 kA, 13.8 kV, 95 kV BIL
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Standard features
RH busbar earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Ammeter 0-600 A
Indication CT L2 ph- 600/5 A class 1.0 5 VA
Gas pressure indicator
Order information
Code Rating
CE6-B9/16 16 kA, 12 kV, 75 kV BIL
CE6-B9/21 21 kA, 13.8 kV, 95 kV BIL
Ratings
Busbars 630 A
Short time withstand 16/21 kA 3 s
Internal arc 16/21 kA 1 s IAC class AF, A-FLR available on gas enclosure only
Normal current rating 630 A
Normal rated voltage 13.8 kV
Normal rated BIL 75/95 kV
Operating mechanism
Independent manual
Provision for actuator, 24 V DC
Standard features
RH busbar earth switch, 16/21 kA 3 s
Anti-reflex operating handle
Indication
Mechanical tripped on fault flag indicator
Mechanical ON/OFF indicator
Mechanical earth/main indicator
Auxiliary contacts,1NO 2 NC
Earth selected auxiliary contacts1NO
Accessories Ammeter 0-600 A
Actuator, 24 V DC Indication CT L2 ph- 600/5 A class 1.0 5 VA
VPIS indication Gas pressure indicator
Interlocks
Busbars Test facility
Integral RH busbar test facility
Please refer to accessories list.
Cable
Order information
N/A
Code Rating
CE6-B10/16 16 kA, 12 kV, 75 kV BIL
CE6-B10/21 21 kA, 13.8 kV, 95 kV BIL
Telecontrol cabinet
Easergy T300 - General description 88
Easergy T300 - OVR 89
Easergy T300 - OVR - Datasheet 89
Information presented in
front panel of modules is Ready-to-use Panel Solution
visible through a window,
• A ready to use panel catalog is available off-the-shelf for fast
without opening the door.
delivery and installation.
T300_closed
Note :
For further details on Easergy T300, please refer:
T300 Catalog ref NRJED314621EN
T300_OVR
Outdoor Vertical version
1 Power Supply PS50
1 Front Head Unit HU250
1 to 4 modules Switch Controller SC150 Opened door contact
(option)
Connected internally to a
digital input and enables
remote indication of the
door status (open/
closed)
1 LV150 module
T300-OVR Characteristics
• Dimensions • Mounting:
Basic enclosure: –– Wall mounting - vertically
L380 x H600 x P275 mm –– The enclosure can be attached to the
• Weight: 40 kg Ringmaster using the standard T300 fixing kit
Order code:
(Please contact us)
Typical switchboard 94
Extensible units 95
Non-extensible unit 98
799
Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions or contact Schneider Electric
799
Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions or contact Schneider Electric.
799
Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions or contact Schneider Electric.
799
Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric.
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions or contact Schneider Electric.
Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric Tel: +44 (0)113 290 3500
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions Ref: SE 6251 or contact Schneider Electric
Tel: +44 (0)113 290 3500
1209
747
779
374
878
Extensible
Bushing Cover
1955
LH ring switch RH ring switch
cable box cable box
1510
575
1320
439
Concrete plinth
(Depth as required)
EXTENSIBLE
510
PLINTH
Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric.
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions or contact Schneider Electric.
Note: for installation where overpressure relief of the equipment is required please contact
Schneider Electric
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions or contact Schneider Electric.
Note: for civil engineering and recommendations for internal arc clearances please consult
our installation and maintenance instructions or contact Schneider Electric.
Schematic legends
106
Specification
RN2d-T2 200/1 A
Legends Class X
RN2d-T3 500/200/1 A
EPS earth position selected auxiliary Class X
MR mechanism reset switch RN2d-T4 500/200/1 A
RL1 close relay Class X
CE2-T33 200/1 A
Class X
Symbols
CE2-T34 200/1 A
Class X
DE60269
Note:
Please contact Schneider Electric for schematics not covered in this catalogue
DE59820
RMD-F507 RMD-F328 RMD-F363
L1 L2 L3
DE59821
RMD-F507 RMD-F365 (F581 and F582)
RMD-F368
RMD-F581
RMD-F582
L1
L2
L3
PROVISION FOR
SHUNT TRIP COIL
89L 52 89R
VIP 40
IDMT RELAY
MITOP COIL K8 51
-
ITC D
K7 +
L1
CLASS: 5P25
E
L2
L3
L4 40
COMMON
a 52 L1 41
CLOSE IND.
b 52 L3 42
OPEN IND. INDICATION
1 EPS L5 43
E.P.S. IND.
1 ES L7 44
E.S. CLOSE IND.
89L 52 89R
VIP 400
IDMT RELAY
51
MITOP COIL K8
-
ITC D
K7 +
L1
CLASS: 5P25
E
L2
L3
L4 40 COMMON
52
a
L1 41 CLOSE IND.
52
b
L3 42 OPEN IND.
INDICATION
EPS
1
L5 43 E.P.S. IND.
ES
1
L7 44 E.S. CLOSE IND.
89L 52 89R
VIP 45
IDMT RELAY
51
MITOP COIL K8
-
ITC D
K7 +
L1
CLASS: 5P25
E
L2
L3
L4 40
COMMON
52
a
L1 41
CLOSE IND.
52
b
L3 42
OPEN IND. INDICATION
EPS
1
L5 43
E.P.S. IND.
ES
1
L7 44
E.S. CLOSE IND.
89L 52 89R
VIP 45
IDMT RELAY
MITOP COIL K8 51
-
ITC
K7 + D
L1
CLASS: 5P25
L2 E
L3
L4 40
COMMON
52
a
L1 41
CLOSE IND.
52
b
L3 42
OPEN IND. INDICATION
EPS
1
L5 43
E.P.S. IND.
ES
1
L7 44
E.S. CLOSE IND.
L1 L3
L1 L2 L3
L1 L2 L3
52
52/c K3 1
K5 COMMON
STC SHUNT
2 TRIP
K2 110-250V AC/DC COIL
K4 3
20-48V DC
VIP 400
IDMT RELAY
51
MITOP COIL K8
-
ITC
K7 D
+
L1
CLASS: 5P25 L2 E
L3
S1 D131 21 D131
P1 REMOVE LINK
22
RATIO: 600/5A FOR REMOTE
BURDEN: 5VA L2 A
INDICATION
CLASS: 1.0 S2 D130 23 D170
P2
D190 24 D170
11
L11
52/b 12
L9
13
L7 SPARE
AUXILIARY
52/b 14 CONTACTS
L5
15
L3
52/a 16
L1
52
K5 52/c K3 1
COMMON
STC SHUNT
2 TRIP
K2 110-250V AC/DC COIL
3
K4 20-48V DC
VIP 40
IDMT RELAY
51
MITOP COIL K8
-
ITC
K7 +
D
L1
CLASS: 5P25
L2
E
L3
L11 11
52/b L9 12
L7 13 SPARE
AUXILIARY
52/b L5 14
CONTACTS
L3 15
52/a L1 16
52
K5 52/c K3 1
COMMON
STC SHUNT
2 TRIP
K2 110-250V AC/DC COIL
3
K4 20-48V DC
VIP 40
IDMT RELAY
51
MITOP COIL K8
-
ITC
K7 +
D
L1
CLASS: 5P25
L2
E
L3
L11 11
52/b L9 12
L7 13 SPARE
AUXILIARY
52/b L5 14
CONTACTS
L3 15
52/a L1 16
52
52/c K3 1
K5 COMMON
STC SHUNT
2 TRIP
K2 110-250V AC/DC COIL
K4 3
20-48V DC
VIP 400
IDMT RELAY
51
MITOP COIL K8
-
ITC
K7 +
D
L1
L2
CLASS: 5P25 E
L3
11
L11
52/b L9 12
L7 13 SPARE
AUXILIARY
52/b L5 14 CONTACTS
L3 15
52/a L1 16
K11 25
K9 26
+ 24V DC
MR/1 RL1/2 RL2 RL2/1 X
K15 K23 K22 27 SUPPLY
-
EPS/1 52/b K20 28
K13 COMMON ACTUATOR
K10 29
52/b RL2/2 RL1 RL1/1 OPEN
K21 K25
RL1/4 K12 30
CLOSE
K17
RL1/3 L13 31
EARTH
M K19 EPS/2 L15 32 POSITION
RL2/4 SELECTED
RL2/3
52
52/c K3 1
K5 COMMON
STC
SHUNT
2 TRIP
K2 110-250V AC/DC COIL
K4 3
20-48V DC
VIP 400
IDMT RELAY
51
MITOP COIL K8
-
ITC
D
K7 +
L1
CLASS: 5P25 L2 E
L3
D131 21 D131
RATIO: 600/5A P1 REMOVE LINK
22
S1
BURDEN: 5VA FOR REMOTE
L2 A
INDICATION
CLASS: 1.0 S2 D130 23 D170
P2
D190 24 D170
K11 25
11
L11
26
RL1/2 X K9 + 24V DC 52/b 12
MR/1 RL2 RL2/1 L9
K15 K23 K22 27
- SUPPLY
52/b L7 13 SPARE
EPS/1 K13 K20 28
COMMON AUXILIARY
ACTUATOR 52/b 14
RL2/2 K10 29
OPEN L5 CONTACTS
52/b RL1 RL1/1
K21 K25 L3 15
RL1/4 K12 30
CLOSE 52/a
K17 L1 16
M RL1/3 L13 31
EARTH
K19 EPS/2 L15 32 POSITION
RL2/4 SELECTED
RL2/3
L1 L2 L3 Easergy T300
L1 L2 L3 Easergy T300
Accessories description
MV substation remote monitoring unit - Flair 200C
Voltage indicator and relay - VD23
128
Fault passage indicators - Flair 21D and 22D
Motorization
Other accessories
VD23
• Voltage presence/absence indication via LED
• Settings by front pushbuttons and LCD
--thresholds, delays and smart parameters
--display of all settings on LCD.
• Auto-adaptation of the nominal system voltage
• Check on voltage status.
Advanced settings
All the combinations can be set with microswitches on the rear of the device.
L1 The use of two relays provides safety backup operation for each combination
L2
L3 6 microswitches: 1: Ph-N voltage(V) / Ph-Ph voltage(U)
VD23 1 2 3 4 5 6 2: Direct / inverse action on output relays
DM100060
Flair 21D The detector checks the 3 phases for current variations (di/dt).
A time delay of 70 s is applied for fault confirmation by the upstream
protective device.
• Automatic mode for adjustment-free calibration of detection thresholds
• Manual mode for special override settings:
--Flair 21D: 6 detection thresholds from 40 to 160 A, via microswitches
--Flair 22D (configurable via the front panel keypad):
-- Type A from 20 to 200 A, in 10 A increments
-- Type B from 5 to 30 A in 5 A increments and 30 to 200 A in 10 A.
• Inrush function: prevents unnecessary detection in the event of load switch-on.
PE57784
Test
Reset
L1
• The load current is displayed continuously
L2
L3 A
I max.
• When a fault is detected, the faulty phase is indicated
• Use the buttons on the front panel to scroll through settings and measurements.
Esc
Easergy
Flair 22D
Selection table
EMS58352 Flair 21D Flair 22D
Power supply Self-powered b b
Sensors
Dual-powered b (1)
The Flair 21D, 22D range uses an integrated detection Detection Overcurrent b b
system composed of indicators Earth-fault b b
and dedicated CTs. Display Ammeter b b
Integrated sensors are normally placed around (4 digit LCD) Maximeter b b
the bushings. Split CTs can be placed around cables Options SCADA interface (relay) b b
for retrofit purposes.
External lamp b b
Connection diagrams
External reset b
Extended setting (keypad) b
L3 Communication 2-voltage output relays
L2 Serial communication port
L1
(1) By lithium battery
DM100048
Flair 22D
Reset Indication Standard applications
Flair 21D Maintenance-free, adjustment-free fault detector
Flair 22D Fault detector for networks with very low load current (< 2 A)
with possibility
of manual adjustments.
DSC0456
Accessories
Schneider Electric are able to
provide a number These are dispatched either:
• Fitted to the unit within the works - these are accessories that are either too bulky,
of accessories to enhance the or need testing prior to despatchie; tee-off cable box
basic unit specifications. These • Loose, boxed, for you to assemble on site. These items are either those that need
to be supplied loose to ease installation: ie a gland plate, or test equipment.
accessories are detailed within
the panel type specifications
RMD-A14/A15/A78/A79
Busbar assemblies
• Each kit comprises a three phase set of busbars, 630 A
• Specify at time of ordering:
--1 off RMD-A15 - end panel kit, plus busbar kits
--Quantity required = No. of panels - 1
RMD-A15 Note: Different busbar kits are required for metering units and bus-sections
DE60270
RMD-A15
RMD-A14 RMD-A78 RMD-A79 Busbars are dispatched loose.
RMD-A17
Time Fuse Links
• 2 off time fuse links for overcurrent protection
Order code Rating
RMD-A17/3 3 amp
RMD-A17/5 5 amp
RMD-A17/7 7.5 amp
RMD-A17/10 10 amp
RMD-A17/12 12.5 amp
DE60245-1
RMD-A17/15 15 amp
799
Order form
138
Guide Metering & Bus section
www.schneider-electric.com
AMTED399086EN
ART45334