Estimate for Construction of Central Workshop for IIT Bhubaneswar at Argul, Khurda, Odisha
Supplying and filling in plinth with Jamuna sand under floors, including watering, ramming,
9 2.27 consolidating and dressing complete. cum 345 910.25 314036.25
Surface dressing of the ground including removing vegetation and inequalities not exceeding 15 cm
10 2.28
deep and disposal of rubbish, lead upto 50 m and lift upto 1.5 m.
2.28.1 All kinds of soil 100 sqm 0.00
11 2.29 Ploughing the existing ground to a depth of 15 cm to 25 cm and watering the same.
2.29.1 All kinds of soil 100 sqm 0.00
Felling trees of the girth (measured at a height of 1 m above ground level), including cutting of
12 2.33 trunks and branches, removing the roots and stacking of serviceable material and disposal of
unserviceable material.
2.33.1 Beyond 30 cm girth upto and including 60 cm girth each 5.0 196.70 983.50
2.33.2 Beyond 60 cm girth upto and including 120 cm girth each 2.0 871.10 1742.20
2.33.3 Beyond 120 cm girth upto and including 240 cm girth each 1.0 4029.05 4029.05
2.33.4 Above 240 cm girth each 1.0 8080.45 8080.45
Supplying chemical emulsion in sealed containers including delivery as specified.
13 2.34
2.34.1 Chlorpyriphos/ Lindane emulsifiable concentrate of 20% litre 3510.00 185.95 652684.50
Rate Diluting and injecting chemical emulsion for PRE/POST CONSTRUCTIONAL anti-termite
14
Analysis treatment (excluding the cost of chemical emulsion) :
Along external wall where the apron is not provided using chemical emulsion @ 7.5 litres / Sqm of the
(i) vertical surface of the substructure to a depth of 300 mm including excavation channel along the wall
& rodding etc. complete:
With Chlorpyriphos/ Lindane E.C. 20% with 1% concentration Metre 351.00 13.82 4850.82
Treatment of soil under floors using chemical emulsion @ one litre per hole, 300 mm apart including
Rate
15 making 12 mm diameter holes and channels etc. complete as per specification and as per the
Analysis
direction of engineer-in-charge.
(i) With Chlorpyriphos/Lindane E.C. 20% with 1% concentration Sqm 2717.00 76.21 207062.57
TOTAL FOR SUB HEAD - I 4174117.06 211913.39
Applying a coat of residual petroleum bitumen of grade of VG-10 of approved quality using 1.7 kg per
4 4.13 square metre on damp proof course after cleaning the surface with brushes and finally with a piece of sqm 75.00 132.00 9900.00
cloth lightly soaked in kerosene oil.
Making plinth protection 50 mm thick of cement concrete 1:3:6 (1 cement:3 coarse sand : 6 graded
5 4.17 stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, Sqm 239.1 419.30 100257.1458
well rammed and consolidated and grouted with fine sand, including finishing the top
Extra for addition of synthetic Polyester triangular fibre of length 12mm,effective diameter 10-40
Per Bag
microns and specific gravity of 1.34 to 1.40 in cement. concrete/RCC/Flooring/water retaining
6 4.18 of 50 kg 2636.0 53.00 139708.00
structures by using Per Bag of 125gms of synthetic Polyester triangular fibre for 50 Kg cement used
of cement
50 Kg of as per directions of Engineer-in-Charge.(For water retaining structures only)
TOTAL FOR SUB HEAD II 3693811.30 0.00
Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and
5 5.22.A
binding all complete up to Above plinth level
5.22.A.6 Thermo-Mechanically Treated bars. Kg 104400.00 68.10 7109640.00
Smooth finishing of the exposed surface of R.C.C. work with 6 mm thick cement mortar 1:3 (1
6 5.23 Sqm 342.00 134.70 46067.40
Cement : 3 fine sand)
7 5.30 Add for plaster drip course/ groove in plastered surface or moulding to R.C.C. projections. meter 315.50 30.75 9701.63
Providing and laying in position machine batched and machine mixed design mix M-25 grade cement
concrete for reinforced cement concrete work, using cement content as per approved design mix,
including pumping of concrete to site of laying but excluding the cost of centering, shuttering,
8 5.33 finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to
accelerate, retard setting of concrete, improve workability without impairing strength and durability
as per direction of Engineer-in-charge. (Note :- Cement content considered in this item is @ 330
kg/cum. Excess/ less cement used as per design mix is payable/recoverable separately).
Providing and fixing 1mm thick M.S. sheet door with frame of 40x40x6mm angle iron and 3mm M.S.
2 10.5 gusset plates at the junctions and corners, all necessary fittings complete, including applying a
priming coat of approved steel primer.
10.5.1 Using M.S. angels 40x40x6 mm for diagonal braces. sqm 3.15 3073.85 9682.63
Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked
together through their entire length and jointed together at the end by end locks, mounted on
specially designed pipe shaft with brackets, side guides and arrangements for inside and outside
3 10.6
locking with push and pull operation complete, including the cost of providing and fixing necessary
27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming
to IS: 4454 -part 1 and M.S. top cover of required thickness for rolling shutters.
10.6.1 80x1.25mm M.S. laths with 1.25 mm thick top cover. sqm 30.71 2142.10 65789.25
4 10.7 Providing and fixing ball bearing for rolling shutters. each 8.00 438.95 3511.60
5 10.8 Extra for providing mechanical device chain and crank operation for operating rolling shutters.
6 10.8.1 Exceeding 10.00 sqm and upto 16.80 sqm in the area. sqm 30.71 724.85 22261.96
Providing and fixing pressed steel door frames conforming to IS: 4351 manufactured from
commercial mild steel sheet of 1.60 mm thickness including hinges, jamb, lock jamb, bead and if
required angle threshold of mild steel angle of section 50x25mm, or base ties of 1.60 mm pressed
7 10.14
mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges,
2.5mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a
coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge:
10.14.3 Profile E
10.14.3.2 Fixing with carbon steel galvanised dash fastener of required dia and size (to be paid for separately). Mtr 31.9 415.90 13267.21
Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including
8 10.16 cutting, hoisting, fixing in position and applying a priming coat of approved steel primer, including
welding and bolted with special shaped washers etc. complete.
10.16.1 Hot finished welded type tubes Kg 24342.89 102.90 2504883.38
Providing and fixing M.S. fan clamp type I or II of 16 mm dia M.S. bar bent to shape with hooked
9 10.17 ends in R.C.C. slabs, beams during laying including painting the exposed portion of loop, all as per Each 82.0 124.45 10204.90
standard design complete.
10 10.20 Providing and fixing bolts including nuts and washers complete. kg 1217.14 98.25 119584.45
Steel work welded in built up sections/ framed work including cutting, hoisting, fixing in position and
11 10.25
applying a priming coat of approved steel primer using structural steel etc. as required.
10.25.2 In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. Kg 19350.00 90.10 1743435.00
Providing and fixing carbon steel galvanised ( minimum coating 5 micron) dash fastener of 10 mm
dia double threaded 6.8 grade (yield strength
12 10.27
480 N/mm2), counter sunk head, comprising of 10 m dia polyamide PA 6 grade sleeve, including
drilling of hole in frame , concrete/ masonry, etc.as per direction of Engineer-in-charge
10.27.3 10 x 120 mm each 360.00 86.75 31230.00
10.27.4 10 x 140 mm each 240.00 97.80 23472.00
10.27.5 10 x 160 mm each 160.00 119.60 19136.00
Providing and fixing stainless steel ( Grade 304) railing made of Hollow tubes, channels, plates etc.
including Knock down, grinding, buffing, polishing and making curvature (wherever required) and
fitting the same with necessary stainless steel nuts and bolts complete i/c fixing the railing with
necessary accessories & stainless steel dash fasteners , stainless steel bolts etc., of required size, on
13 10.28 Kg 307.10 619.40 190215.49
the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-
charge.( for payment purpose only weight of stainless steel members shall be considered excluding
fixing accessories such as nuts, bolts, fasteners etc.) Note:- This item shalll be of Knock down
arragement having no welding and assemble it as to fixing at site.
Providing and fixing precoated galvanised iron profile sheets (size, shape and pitch of corrugation as
approved by Engineer-in-charge) 0.50 mm (+ 0.05 %) total coated thickness with zinc coating 120
grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns epoxy primer on both side of the
sheet and polyester top coat 15-18 microns. Sheet should have protective guard film of 25 microns
14 12.50 minimum to avoid scratches during transportation and should be supplied in single length upto 12 Sqm 434.70 622.00 270383.40
metre or as desired by Engineer- in-charge. The sheet shall be fixed using self drilling /self tapping
screws of size (5.5x 55 mm) with EPDM seal, complete upto any pitch in horizontal/ vertical or curved
surfaces, excluding the cost of purlins, rafters and trusses and including cutting to size and shape
wherever required.
Providing and fixing precoated galvanised steel sheet roofing accessories 0.50 mm (+ 0.05 %) total
coated thickness, Zinc coating 120 grams per sqm as per IS: 277, in 240 mpa steel grade, 5-7 microns
15 12.51
epoxy primer on both side of the sheet and polyester top coat 15-18 microns using self drilling/ self
tapping screws complete :
12.51.2 Flashings/ Aprons.( Upto 600 mm) Mtr 35.20 609.05 21438.56
12.51.6 Gutter .(600 mm over all girth) Mtr 35.20 815.00 28688.00
TOTAL FOR SUB HEAD V 5241985.18 0.00
Providing and fixing copper pins 7.5 cm long 6 mm diameter for securing adjacent stones in stone
2 7.27 Each 80.00 31.75 2540.00
wall lining in cement mortar 1:2 (1cement : 2 coarse sand) including making the necessary chases.
Providing and fixing 18mm thick gang saw cut mirror polished premoulded and prepolished) machine
cut for kitchen platforms, vanity counters, window sills , facias and similar locations of required size
of approved shade, colour and texture laid over 20mm thick base cement mortar 1:4 (1 cement : 4
3 8.2
coarse sand) with joints treated with white cement, mixed with matching pigment, epoxy touch ups,
including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at
all levels.
8.2.2 Granite of any colour and shade
8.2.2.2 Area of slab over 0.50 Sqm Sqm 9.50 3907.40 37120.30
Providing edge moulding to 18mm thick marble/Granite stone counters, Vanities etc. including
4 8.3 machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-
in-Charge.
8.3.2 Granite Works `Mtr 13.00 230.55 2997.15
Extra for fixing marble /granite stone over and above corresponding basic item, in facia and drops of
5 8.4 Mtr 13.00 247.40 3216.20
width upto 150 mm with epoxy resin based adhesive including cleaning etc. complete.
Extra for providing opening of required size & shape for wash basins/ kitchen sink in kitchen
6 8.5 platform, vanity counters and similar location in marble/Granite/stone work including necessary Each 12.00 386.60 4639.20
holes for pillar taps etc. including moulding, rubbing and polishing of cut edges etc. complete.
Providing and fixing stone slab table rubbed, edges rounded and polished of size 75x50 cm deep and
1.8 cm thick fixed in urinal partitions by cutting a chase of appropriate width with chase cutter and
7 8.10
embedding the stone in the chase with epoxy grout or with cement concrete 1:2:4 (1 cement : 2 coarse
sand : 4 graded stone aggregate 6mm nominal size) as per direction of Engineer-in-charge
8.10.2 Granite Stone of approved shade. Sqm 2.450 3263.50 7995.58
Cement concrete flooring 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate) finished with a
8 11.3 floating coat of neat cement including cement slurry, but excluding the cost of nosing of steps etc.
complete.
11.3.1 40mm thick with 20mm nominal size stone aggregate. Sqm 25.00 353.35 8833.75
Cement plaster skirting (up to 30 cm height) with cement mortar 1:3 (1 cement : 3 coarse sand)
9 11.6
finished with a floating coat of neat cement.
11.6.1 18 mm thick. sqm 2.50 377.25 943.13
10 11.13 Providing and fixing glass strips in joints of terrazo/ cement concrete floors. Mtr 48.00 50.05 2402.40
11.13.1 40 mm wide and 4 mm thick.
Kota stone slab flooring over 20 mm (average) thick base laid over and jointed with grey cement
11 11.26 slurry mixed with pigment to match the shade of the slab including rubbing and polishing complete
with base of cement mortar 1 : 4 (1 cement : 4 coarse sand) :
11.26.1 25 mm thick Sqm 2566.51 1141.40 2929412.13
Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average)
12 11.27 thick cement mortar 1:3 (1 cement 3coarse sand) and jointed with grey cement slurry mixed with Sqm 98.84 1191.25 117738.98
pigment to match the shade of the slabs, including rubbing and polishing complete.
13 11.31 Extra for pre finished nosing in treads of steps of Kota stone/ sand stone slab. Metre 66.60 75.80 5048.28
14 11.32 Extra for Kota stone/ sand stone in treads of steps and risers using single length up to 1.05 metre . sqm 120.60 16.90 2038.14
Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS : 15622 (thickness to be
specified by the manufacturer ) of approved make in all colours, shades except burgundy, bottle
15 11.36 green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados Sqm 282.46 836.65 236320.58
over 12 mm thick bed of cement Mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement
slurry @ 3.3kg per sqm including pointing in white cement mixed with pigment of matching shade
complete.
Providing and laying rectified Glazed Ceramic floor tiles 300x300 mm or more (thickness to be
specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in all
16 11.40 colours, shades, except White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick Cement Mortar 1:4 Sqm 68.22 1009.60 68876.58
(1 Cement : 4 Coarse sand) including pointing the joints with white cement and matching pigments
etc., complete.
Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the
manufacturer) with water absorption's less than 0.08%and conforming to IS : 15622 of approved
17 11.41
make in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand)
including grouting the joints with white cement and matching pigments etc., complete.
11.41.2 Size of tile 600x600 mm Sqm 31.88 1405.95 44818.87
Providing and laying Vitrified tiles in different sizes (thickness to be specified by the manufacturer),
with water absorption less than 0.08%and conforming to IS: 15622, of approved brand &
18 11.47 manufacturer in all colours and shade in skirting, riser of steps, laid with cement based high polymer
modified quick set tile adhesive (water based) conforming to IS: 15477, in average 6 mm thickness,
including grouting of joints(Payment for grouting of joints to be made separately).
11.47.2 Size of tile 600x600 mm Sqm 2.76 1630.20 4501.80
Laying water bound macadam sub-base with brick aggregate and blinding material, earth etc.
19 16.5 including screening, sorting and spreading to template and consolidation with light power road-roller
etc. complete.(payment for brick aggregate and moorum etc. to be made separately)
16.5.1 Over burnt (Jhama) brick aggregate 120 mm to 40 mm. Cum 214.50 328.60 70484.70
16.5.2 Over burnt (Jhama) brick aggregate 90 mm to 45 mm. Cum 214.50 328.60 70484.70
Supplying, stacking and Spreading 6 mm thick red bajri, watering and rolling complete including
20 16.6
preparation of the surface and rolling.
16.6.1 With road roller/ hand roller. Sqm 2862.88 14.90 42656.97
TOTAL FOR SUB HEAD VI 3671689.18 0.00
Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded
built up standard tubular sections/appropriate Z sections and other sections of approved make
conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including
necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM
2 21.1
rubber/neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and
jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing /
paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the
directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) :
21.1.1 For fixed portion
Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868,
21.1.1.1 Kg 1546.26 348.50 538869.94
Minimum anodic coating of grade AC 15)
For shutters of doors, windows & ventilators including providing and fixing hinges/ pivots and
21.1.2 making provision for fixing of fittings wherever required including the cost of EPDM rubber /
neoprene gasket required (Fittings shall be paid for separately).
Anodised aluminium (anodised transparent or dyed to required shade according to IS: 1868,
21.1.2.1 kg 4638.77 405.90 1882874.96
Minimum anodic coating of grade AC 15)
Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with
3 21.3 EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of
engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):
21.3.1 With float glass panes of 4.0 mm thickness Sqm 4.50 828.75 3729.38
21.3.2 With float glass panes of 8.0 mm thickness Sqm 38.6 1338.40 51603.35
Filling the gap in between aluminium frame & adjacent RCC/ Brick/ Stone work by providing
4 21.8 weather silicon sealant over backer rod of approved quality as per architectural drawings and
direction of Engineer-in-charge complete.
21.8.1 Upto 5mm depth and 5 mm width Rmt 525.63 88.75 46649.66
Providing and fixing anodised aluminium (anodised transparent or dyed to required shade according
to IS: 1868. Minimum anodic coating of grade AC 15) sub frame work for windows and ventilators
5 21.14 with extruded built up standard tubular sections of approved make conforming to IS: 733 and IS: Kg 1703.04 312.20 531689.46
1285, fixed with dash fastener of required dia and size (Dash fastener to be paid for separately).
(Aluminium section 50x25*3.2)
Providing and fixing aluminium casement/sliding windows fastener of required length for
6 21.15
aluminium windows with necessary screws etc. complete.
21.15.1 Anodized (AC 15) aluminium Each 318.00 54.00 17172.00
Providing and fixing anodised aluminium grill /louver (anodised transparent or dyed to required
shade according to IS: 1868 with minimum anodic coating of grade AC 15) of approved
design/pattern, with approved standard section and fixed to the existing window frame with C.P
7 21.17 brass/ stainless steel screws @ 200mm centre to centre, including cutting the grill to proper opening Kg 721.1 403.35 290850.64
size for fixing and operation of handles and fixing approved anodised aluminium standard section
around the opening, all complete as per requirement and direction of Engineer-in-charge. (Only
weight of grill to be measured for payment).
Providing and fixing 12 mm thick frameless toughened glass door shutter of approved brand and
manufacture, including providing and fixing top & bottom pivot & spring type fixing arrangement
8 21.18 and making necessary holes etc. for fixing required door fittings, all complete as per direction of sqm 21.42 4746.25 101664.68
Engineer-in-charge (Door handle, lock and stopper etc.to be paid separately).
Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying
cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of
slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound@ 0.253 kg/sqm. This
9 22.5 layer will be allowed to air cure for 4 hours. b)Second layer of slurry of cement @ 0.242 kg/sqm mixed sqm 68.2 283.10 19313.55
with waterproofing cement compound @ 0.126 kg/sqm. This layer will be allowed to air cure for 4
hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment
and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry.
Providing and laying water proofing treatment on roofs of slabs by applying cement slurry mixed
with water proofing cement compound consisting of applying: a) after surface preparation, first layer
of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound@ 0.253 kg/sqm. b)
laying second layer of Fibre glass cloth when the first layer is still green. Overlaps of joints of fibre
cloth should not be less than 10 cm. c) third layer of 1.5 mm thickness consisting of slurry of cement
10 22.6 Sqm 28.0 390.35 10929.80
@ 1.289 kg/sqm mixed with water proofing cement compound@ 0.670 kg/sqm and coarse sand @ 1.289
kg/sqm. This will be allowed to air cure for 4 hours followed by water curing for 48 hours. The entire
treatment will be taken upto 30cm on parapet wall and tucked into groove in parapet all around. d)
fourth and final layer of brick tiling with cement mortar (which will be paid for separately For the
purpose of measurement the entire treated surface will be measured.
Providing and fixing partition upto ceiling height consisting of G.I. frame and required board
including providing and fixing of frame work made of special section power pressed/ roll form G.I.
sheet with zinc coating of 120gms/sqm(both side inclusive), consisting of floor and ceiling channel
50mmwide having equal flanges of 32 mm and 0.50 mm thick, fixed to the floor and ceiling at the
spacing of 610 mm centre to centre with dash fastener of 12.5mm dia meter 50 mm length or suitable
anchor fastener or metal screws with nylon plugs and the studs 48 mm wide having one flange of 34
mm and other flange 36 mm and 0.50 mm thick fixed vertically within flanges of floor and ceiling
channel and placed at a spacing of 610mm centre to centre by 6 mm dia bolts and nuts, including
12 9.105 fixing of studs along both ends of partition fixed flush to wall with suitable anchor fastener or metal
screws with nylon plugs at spacing of 450 mm centre to centre, and fixing of boards to both side of
framework by 25 mm long dry wall screws on studs, floor and ceiling channels at the spacing of 300
mm centre to centre. The boards are to be fixed to the framework with joints staggered to avoid
through cracks, M.S. fixing channel of 99mm width (0.9 mm thick having two flanges of 9.5 mm each)
to be provided at the horizontal joints of two boards, fixed to the studs using metal to metal flathead
screws, including jointing and finishing to a flush finish with recommended jointing compound,
jointing tape, angle beads at corner (25mm x 25 mm x 0.5 mm), joint finisher and two coats of primer
suitable for board as per manufacture's specification and direction of engineer in charge all complete.
75 mm overall thickness partition with 12.5 mm thick double skin fire rated board conforming to IS:
9.105.1 Sqm 460.5 1325.65 610461.83
2095: part I.
Providing and fixing factory made P.V.C. door frame of size 50x47mm with a wall thickness of 5mm,
made out of extruded 5mm rigid PVC foam sheet, mitred at corners and joined with 2 Nos. of 150mm
long brackets of 15x15mmM.S. square tube, the vertical door frame profiles to be reinforced
13 9.119 Mtr 77.88 458.95 35743.03
with19x19mm M.S. square tube of 19 gauge, EPDM rubber gasket weather seal to be provided
through out the frame. The door frame to be fixed to the wall using M.S. screws of 65/100mm size,
complete as per manufacturers specification and direction of Engineer-in-Charge.
Providing and fixing factory made panel PVC door shutter consisting of frame made out of M.S. tubes
of 19 gauge thickness and size of 19mm x 19mm for styles and 15x15mm for top & bottom rails. M.S.
frame shall have a coat of steel primers of approved make and manufacture . M.S. frame covered
with5mm thick heat moulded PVC 'C' channel of size 30mm thickness, 70mmwidth out of which
50mm shall be flat and 20mm shall be tapered in 45degreeangle on both side forming styles; and
5mm thick, 95mm wide PVC sheet out of which 75mm shall be flat and 20mm shall be tapered in 45
degree on the inner side to form top and bottom rail and 115mm wide PVC sheet out of which 75mm
14 9.120 shall be flat and 20mm shall be tapered on both sides to form lock rail. Top, bottom and lock rails
shall be provided both side of the panel.10mm (5mm x 2 ) thick, 20mm wide cross PVC sheet be
provided as gap insert for top rail & bottom rail. paneling of 5mm thick both side PVC sheet to be
fitted in the M.S. frame welded/ sealed to the styles & rails with 7mm(5mm+2mm) thick x 15mm
wide PVC sheet beading on inner side, and joined together with solvent cement adhesive. An
additional 5mm thick PVC strip of20mm width is to be stuck on the interior side of the 'C' Channel
using PVC solvent adhesive etc. complete as per direction of Engineer-in-charge. Manufacturer’s
specification & drawing
9.120.1 30 mm thick plain PVC door shutters. Sqm 27.72 2749.60 76218.91
TOTAL FOR SUB HEAD - X 1132875.463 0
Painting runway/taxi track/apron marking with adequate no. of coats to give uniform finish with
6 16.47 road marking paint of superior make as approved by the Engineer-in-charge i/c cleaning the surface
of all dirt, scales, oil, grease and other foreign material etc. and lining out complete.
16.47.1 New work (Two or more coats) Sqm 72.2 109.30 7885.995
Providing, laying and making kerb channel 30cm wide and 50mm thick with cement concrete 1:3:6 (1
cement: 3 coarse sand:6 graded stone aggregate20mm nominal size) over 75mm bed of dry brick
7 16.63 Sqm 225.0 354.20 79695.00
ballast 40 mm nominal size well rammed and consolidated and grouted with fine sand including
finishing the top smooth etc. complete and as per direction of Engineer-in-charge.
Providing and laying 60mm thick factory made cement concrete interlocking paver block of M -30
grade made by block making machine with strong vibratory compaction, of approved size, design &
8 16.68 Sqm 240.0 602.20 144528.0
shape, laid in required colour and pattern over and including 50mm thick compacted bed of fine sand,
filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge.
Providing and laying at or near ground level factory made kerb stone of M-25 grade cement concrete
in position to the required line, level and curvature, jointed with cement mortar 1:3 (1 cement: 3
coarse sand) including making joints with or without grooves (thickness of joints except at sharp
9 16.69 Cum 102.5 5295.90 542829.75
curve shall not to more than 5mm), including making drainage opening wherever required complete
etc. as per direction of Engineer-in-charge (length of finished kerb edging shall be measured for
payment). (Precast C.C. kerb stone shall be approved by Engineer-in-charge).
Providing and laying C.C. pavement of mix M-25 with ready mixed concrete from batching plant. The
ready mixed concrete shall be laid and finished with screed board vibrator , vacuum dewatering
process and finally finished by floating, brooming with wire brush etc. complete as per specifications
10 16.75 Cum 426.0 6848.85 2917610.1
and directions of Engineer-in-charge. (The panel shuttering work shall be paid for separately).(Note:-
Cement content considered in this item is @ 330 kg/cum. Excess/less cement used as per design mix
is payable/ recoverable separately).
Providing and erecting 2.00 metre high temporary barricading at site as per drawing/ direction of
Engineer-in-Charge which includes writing and painting, arrangement for traffic diversion such as
traffic signals during construction at site for day and night, glow lamps, reflective signs, marking,
flags, caution tape as directed by the Engineer-in-Charge. The barricading provided shall be retained
in position at site continuously i/c shifting of barricading from one location to another location as
11 16.81 many times as required during the execution of the entire work till its completion. Rate include its Mtr 250.0 0.00
maintenance for damages, painting, all incidentals, labour materials, equipments and works
required to execute the job. The barricading shall not be removed without prior approval of Engineer-
in-Charge. (Note :- One time payment shall be made for providing barricading from start of work till
completion of work i/c shifting. The barricading provided shall remain to be the property of the
contractor on completion of the work).
Providing and placing in position 100 mm thick factory made machine batched &
machine mixed Precast RCC Rectangular Covers on drains of footpath of various
sizes, of M-25 grade cement concrete for RCC work, including cost of centering,
shuttering, reinforcement of 8 mm dia TMT bars of Fe 500 grade @ maximum 100mm
12 16.93 c/c on both ways , neat cement punning on finished surface, properly encased on all Sqm 15.0 2090.30 31354.50
edges with 1.6 mm thick , 100 mm wide MS sheet duly painted over priming coat ,
reinforcement to be welded at edges with MS sheet and providing 2 Nos. 12 mm dia
bar for hooks etc i/c cost of cartage, all leads & lift, handling at site etc. all complete as per direction
of Engineer-in-Charge.
Providing & laying Selection no. 1 grass turf with earth 50mm to 60mm thickness on existing ground
prepared with proper level and ramming with required tools wooden and than rolling the surface
13 23.2.34 sqm 165.0 0.00
with light roller make the surface smoothen and light watering the same, as per direction of officer in
charge
TOTAL SUB HEAD XI -ROAD WORKS 4859089.63 0.00
Providing and fixing tiled false ceiling of approved materials of size 595x595 mm in true horizontal
level suspended on inter locking metal grid of hot dipped galvanized steel sections ( galvanized @
120gsm/sqm, both side inclusive) consisting of main "T" runner with suitably spaced joints to get
required length and of size 24x38mmmade from 0.30mm thick (minimum) sheet, spaced at 1200mm
center to center and cross "T" of size 24x25mm made of 0.30mm thick(minimum) sheet, 1200mm long
spaced between main "T" at 600mmcenter to center to form a grid of 1200x600 mm and secondary
cross T of length 600mm and size 24x25mm made of 0.30 mm thick(minimum) sheet to be
interlocked at middle of the 1200x600mm panel to form grids of 600x600mm and wall angle of size
24x24x0.3 mm and laying false ceiling tiles of approved texture in the grid including, wherever,
1 12.52 required, cutting/making, opening for services like diffusers, grills, light fittings, fixtures, smoke
detectors etc. Main "T" runners to be suspended from ceiling using GI slotted cleats of size 27 x 37 x
25 x1.6x mm fixed to ceiling with 12.5 mm dia and 50 mm long dash fasteners,4mm GI adjustable
rods with galvanised butterfly level clips of size 85 x30 x 0.8 mm spaced at 1200mm center to center
along main T, bottom exposed width of 24 mm of all T-sections shall be pre-painted with polyester
paint, all complete at all heights as per specifications drawings and as directed by Engineer-in-
charge.12.52.1 GI Metal Ceiling Lay in plain Tegular edge Global white color tiles of size 595x595
mm, and 0.5mm thick with 8mmdrop; made of G I sheet having galvanizing of 100 gms/sqm(both
sides inclusive) and electro statically polyester powder coated of thickness 60 microns (minimum),
including factory painted after bending.
GI Metal Ceiling Lay in perforated Tegular edge global white color tiles of size 595x595 mm and
0.5mm thick with 8mmdrop; made of GI sheet having galvanizing of 100 gms/sqm(both sides
12.52.2 inclusive) and 20% perforation area with 1.8mmdia holes and having NRC (Noise Reduction Sqm 2110.65 1673.50 3532172.78
Coefficient ) of0.5, electro statically polyester powder coated of thickness60 microns (minimum),
including factory painted after bending and perforation, and backed with a black Glass fiber
acoustical fleece.
Providing and laying roof insulation with 40 mm thick impervious sprayed, closed cell free Rigid
Polyurethane foam over deck insulation conforming to IS - 12432 Pt. III (density of foam being 40-45
kg/ cum), over a coat of polyurethane primer applied @ 6-8 sqm per litre, laying 400 G polythene
2 12.56 sheet over PUF spray and providing a wearing course of 40 mm thick cement screed 1: 2 : 4 (1 cement Sqm 2476.80 1167.20 2890920.96
: 2 coarse sand : 4 stone aggregate 20 mm nominal size) in chequered rough finish, in panels of 2.5 m
x 2.5 m and embedding with 24 G wire netting and sealing the joints with polymerized mastic, all
complete as per direction of Engineer-in-Charge.
Providing and supplying aluminium extruded tubular and other aluminium sections as per the
architectural drawings and approved shop drawings , the aluminium quality as per grade 6063 T5 or
2 26.1 T6 as per BS 1474,including super durable powder coating of 60-80 microns conforming to AAMA Kg 625.15 338.25 211456.99
2604 of required colour and shade as approved by the Engineer-in-Charge ,Weight of Aluminium=1.0
Sqm=6.5 Kg
Designing, fabricating, testing, protection, installing and fixing in position semi (grid) unitized
3 26.2 system of structural glazing (with open joints) for linear as well as curvilinear portions of the
building for all heights and all levels including:
:(a) Structural analysis, design and preparation of shop drawings for the specified design loads
conforming to IS 875 part III (the system must passed the proof test at 1.5 times design wind
pressure without any failure), including functional design of the aluminum sections for fixing glazing
panels of various thicknesses, aluminium cleats, sleeves and splice plates etc. gaskets, screws,
toggles, nuts, bolts, clamps etc., structural and weather silicone sealants, flashings, fire stop (barrier)-
cum-smoke seals, microwave cured EPDM gaskets for water tightness, pressure equalisation &
drainage and protection against fire hazard including
(b) Fabricating and supplying serrated M.S. hot dip galvanised /Aluminium alloy of 6005 T5 brackets
of required sizes, sections and profiles etc. to accommodate 3 Dimentional movement for achieving
perfect verticality and proper fixing of structural glazing system with the RCC/ masonry/structural
steel framework of building structure, using stainless steel anchor fasteners/ bolts, nylon seperator to
prevent bimetallic contacts with nuts and washers etc. of stainless steel grade 316, of the required
capacity and in required numbers.
(c) Providing and filling, two part pump filled, structural silicone sealant and one part weather
silicone sealant compatible with the structural silicone sealant of required bite size in a clean and
controlled factory / work shop environment , including double sided spacer tape, setting blocks and
backer rod, all of approved grade,brand and manufacturer, as per the approved sealant design,
within and all around the perimeter for holding glass
.(d) Providing and fixing in position flashings of solid aluminium sheet 1 mm thick and of sizes,
shapes and profiles, as required as per the site conditions, to seal the gap between the building
structure and all its interfaces with curtain glazing to make it watertight
(e) Making provision for drainage of moisture/ water that enters the curtain glazing system to make
it watertight, by incorporating principles of pressure equalization, providing suitable gutter
profilesat bottom (if required), making necessary holes of required sizes and of required numbers etc.
complete This item includes cost of all inputs of designing, labour for fabricating and installation of
aluminium grid, installation of glazed units, T&P,scaffolding and other incidental charges including
wastages etc.,enabling temporary structures and services, cranes or cradles etc. as described above
and as specified. The item includes the cost of getting all the structural and functional design
checked and all the shop drawings vetted by the Principals of the structural glazing system.The item
also includes the cost of all mock ups at site, cost of all samples of the individual components for
testing in an approved laboratory, field tests on the assembled working structural glazing as
specified, cleaning and protection till the handing over of the building for occupation. In the end, the
Contractor shall provide a water tight structural glazing having all the performancecharacteristics
etc. all complete as required, as per the Architectural drawings, as per item description, as specified,
as per the approved shop drawings and as directed by the Engineer-in-Charge.
Note:- 1. The cost of providing extruded aluminium frames, shadow boxes, extruded aluminium
section capping for fixing in the grooves of the curtain glazing and vermin proof stainless steel wire
mesh shall be paid for separately under relevant items under this subhead. However, for the purpose
of payment, only the actual area of structural glazing (including width of grooves ) on the external
face shall be measured in sqm. up to two decimal places.
Providing and supplying Spandrel Glass Panels comprising of 6 mm thick heat strengthened
monolithic float glass of approved colour and shade with reflective soft coating on surface # 2 of
approved colour and shade so as to match the colour and shade of the IGUs in the vision panels etc.
,all complete for the required performances as the vision panels etc. ,all complete for the required
performances as specified, as per the Architectural drawings, as per the approved shop drawings, as
specified, and as directed by the Engineer- in- Charge. For payment, only the actual area of glass on
5 26.6 face # 1 of the glass panels (but excluding the area of grooves and weather silicone sealant) provided Sqm 2.45 2997.25 7343.26
and fixed in position, shall be measured in sqm.(Payment for fixing of Spandrel Glass Panels in the
curtain glazing is included in cost of relevent Item*). (i) Coloured tinted float glass 6mm thick
substrate with reflective soft coating on face # 2, + 12mm Airgap + 6mm Heat Strengthened clear
Glass of approved make having properties as visible Light transmittance (VLT) of 25 to 35 %, Light
reflection internal 10 to 15%, light reflection external 10 to 20 %, shading coefficient (0.25- 0.28) and
U value of 3.0 to 3.3 W/m2 degree K etc.
Designing, fabricating, testing, installing and fixing in position Curtain Wall with Aluminium
Composite Panel Cladding, with open grooves for linear as well as curvilinear portions of the
building, for all heights and all levels etc. including:
a) Structural analysis & design and preparation of shop drawings for pressure equalisation or rain
screen principle as required, proper drainage of water to make it watertight including checking of all
the structural and functional design.
b) Providing, fabricating and supplying and fixing panels of aluminium composite panel cladding in
7 26.7 Sqm 110.00 3775.30 415283.00
pan shape in metalic colour of approved shades made out of 4mm thick aluminium composite panel
material consisting of 3mm thick FR grade mineral core sandwiched between two Aluminium
sheets (each 0.5mm thick). The aluminium composite panel cladding sheet shall be coil coated, with
Kynar 500 based PVDF / Lumiflon based fluoropolymer resin coating of approved colour and shade
on face # 1 and polymer (Service) coating on face # 2 as specified using stainless steel screws, nuts,
bolts, washers, cleats, weather silicone sealant, backer rods etc.
c) The fastening brackets of Aluminium alloy 6005 T5 / MS with Hot Dip Galvanised with serrations
and serrated washers to arrest the wind load movement, fasteners, SS 316 Pins and anchor bolts of
approved make in SS 316, Nylon separators to prevent bi-metallic contacts all complete required to
perform as per specification and drawing The item includes cost of all material & labour component,
the cost of all mock ups at site, cost of all samples of the individual components for testing in an
approved laboratory, field tests on the assembled working curtain wall with aluminium composite
panel cladding, cleaning and protection of the curtain wall with aluminium composite panel
cladding till the handing over of the building for occupation. Base frame work for ACP cladding is
payable under the relevant aluminium item.s The Contractor shall provide curtain wall with
aluminium composite panel cladding, having all the performance characteristics all complete , as
per the Architectural drawings, as per item description, as specified, as per the approved shop
drawings and as directed by the Engineer-in-Charge. However, for the purpose of payment, only the
actual area on the external face of the curtain wall with Aluminum Composite Panel Cladding
(including width of groove) shall be measured in sqm. up to two decimal places.
Supply and installation of 20mm thick Terracotta tiles made entirely from natural raw materials
derived from a sustainable source with superior finish, high strength, low maintenance , tested safety
, colour fast, highly resistant to all kinds of weather conditions , fire resistant with density 2.0-2.4
g/sqcm, dry weight 46 kg /sqm, elasticity .305 x 105 as per ISO 17561, water abrasion value 3%,
Rate collapsible strength > 7*104N, anti fire performance grade A , thermal shock stability with no crack
1 Sqm 1198.50 7274.61 8718620.085
Analysis and burst after 10 times testing JC/T 1080-2008, sound proofing with reduce noise over 9 db ,
thermal conductivity 0.264 W/m@K, Wind pressure performance Positive 5.0 KPa, Negative 5.0 KPa
GB/T 21086-2007, Seismic performance over 10 grade GB/T 18575\GB5011, Acid resistant .
Installation up to 10.0 Mtr height withAluminium clip holder C channel, Angle,box section ,self
drilling screw,anchor fastenr as per structural design all complete. as approved by Architect..
Rate
2 Extra for Teracota tile works in Beige Colour . Sqm 1198.50 39.62 47484.57
Analysis
EPDM Rubbergard Membrane.Water proofing :-Horizontal area: Providing and laying a layer of
200 gsm Geotextile is loose laid on Lean concrete substrate. The geotextile membrane must be
overlapped for 75mm. The overlapping joint may be secured by Stitching or Bonding Adhesive or hot
air gun as convenient to the waterproofing applicator. EPDM Rubbergard : Prividing & Laying 1.1
mm EPDM membrane confirming to above mentioned technical values is loose laid over the
Rate
3 geotextile layer. The width of EPDM sheet should be minimum 9 meter or large as possible to
Analysis
minimize the number of joints. Adjacent sheet shall be laid in similar fashion with an overlap of
minimum 100 mm . Min 75mm wide rubber polymers butyl splice tape having 100% solid content
together with synthetic-rubber polymer primer having 16-18% solids, Specific Gravity 0.793 and
Flash point-17.8 degree centigrade, should be used to make watertight QuickSeam between 2 EPDM
membranes.
Vertical wall:The surface of wall shall be smooth, hard , dry and free from dust before applying
treatment. 1.1mm thick EPDM Rubbergard confirming to above standards is fully bonded to the RCC
substrate using FM approved solvent based Neoprene Bonding adhesive. having following
parameters : A blend of Polychloroprene and SBR rubbers Solvents: A blend of Acetone, Hexane,
Toluene and Xylene; Viscosity: 3,300-3,800 cps, with R.V.F. #3 spindle @ 10 rpm,Weight/Gallon:6.6-
7.4 lb/gal, Specific Gravity: 0.7909-0.8868; V.O.C. Content: 5.282 lb/gal (633 g/L). All the insertions
shall be treated with uncured EPDM. The treatment to be terminated atleast at the height of 300mm Sqm 2476.80 762.82 1889352.58
above the roof floor level using termination bar and appropriate fasteners. Water block sealant
should be used on top edge behind membrane and lap sealant should be applied on the edges of
termination detail.
Uncured EPDM flashing material factory laminated to splice tape should be used to flash inside and
outside corners, pipes, drain outlets, scuppers and other penetrations or unusually shaped
walls/details where the use of cured membrane flashing is not practical.
Rate Providing and fixing Stain finished Stainless Steel tower bolts Round (barrel type) with necessary
4
Analysis screws etc. complete :
1.0 300i10 mm Each 288.00 390.52 112469.76
2.0 200x10 mm Each 24.00 262.81 6307.44
Providing and fixing stainless steel grade 304 wire gauge with 0.5 mm dia. Wire and 1.4 mm wide
aperture with matching Aluminium beading in aluminium door, window, ventilator shutters and
Rate
15 partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings sqm 183.64 1311.32 240810.80
Analysis
and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic
item):
Providing and fixing double glazed hermetically sealed glazing in aluminium windows, ventilators
and partition etc. with 6 mm thick Tempered glass both side(SKN 440Saint Gobain India & Exceed
Rate
16 Green Vision Asahi india glass), having 12 mm air gap, including providing EPDM gasket, perforated sqm 229.76 5109.68 1174000.08
Analysis
aluminium spacers, desiccants, sealant (Both primary and secondary sealant) etc. as per
specifications, drawings and direction of Engineer-in-charge complete.
Rate Providing and fixing Romanhuse blinds non blockout with chain Mechanism all complete
17 Sqm 235.40 1974.36 464764.34
Analysis Make.Vista,Hunter Duglus,fabindia
Providing and laying M-20 grade foam concrete filling in sunken portion of W.C. & kitchen/Terrace
Rate
18 with approved quality of foam concrete including pumping of concrete to site of laying but excluding Cum 272.45 4388.46 1195635.93
Analysis
the cost of centering, shuttering.as per direction of Engineer-in-charge.
Providing and laying a average 40 mm thick additional cement screed concrete 1: 2 : 4 (1 cement : 2
Rate
19 coarse sand : 4stone aggregate 20 mm nominal size) so as to provide slope in the roof at all heights Cum 99.07 0.00
Analysis
and levels etc. complete.
Rate Extra Providing and Double Charge vitrified floor/wall tiles in different sizes (thickness to be specified by
20 Sqm 34.64 154.81 5362.54
Analysis the manufacturer)
TOTAL NON SCHEDULE ITEMS 0.00 15218141.98
2 SUB HEAD - II - (SOIL, WASTE, RAIN WATER AND VENT PIPES) 350852.30 373669.82
Providing and fixing white vitreous china flat back half stall urinal of size
580x380x350 mm with white PVC automatic flushing cistern, with fittings,
standard size C.P. brass flush pipe, spreaders with unions and clamps (all
1 17.5
in C.P. brass) with waste fitting as per IS : 2556, C.I. trap with outlet
grating and other couplings in C.P. brass, including painting of fittings and
cutting and making good the walls and floors wherever required
17.5.1 Single half stall urinal with 5 litre P.V.C. automatic flushing cistern Each 6 6591.10 39546.60
Providing and fixing 900 x 600mm beveled edge mirror of superior glass (of
2 M.R approved quality) complete with 6 mm thick hard board ground fixed to wooden Each 12 1403.59 16843.08
cleats with C.P. brass screws and washers complete.
3 17.34 Providing and fixing toilet paper holder.
17.34.1 C.P. brass Each 6 415.90 2495.40
Providing and fixing white vitreous china extended wall mounting water
closet of size 780x370x690 mm of approved shape including providing &
4 17.78 fixing white vitreous china cistern with dual flush fitting, of flushing Each 6 10100.90 60605.40
capacity 3 litre/6 litre (adjustable to 4 litre/8 litres), including seat cover,
and cistern fittings, nuts, bolts and gasket etc complete
5 18.21 Providing and fixing uplasticised PVC connection pipe with brass unions
18.21.2 45 cm length
18.21.2.1 15 mm dia nominal bore Each 25 68.60 1715.00
Providing and fixing C.P. brass long body bib cock of approved quality
6 18.51
conforming to IS standards and weighing not less than 690 gms.
18.51.1 15 mm nominal bore Each 2 610.65 1221.30
Providing, fixing, testing and commissioning of star white colour vitreous china
below / over counter Oval Wash Basin / circular basin (Size 560 x 410 mm) with
7 M.R. CP brass waste assembly complete including CI / MS brackets duly painted, Each 12 3562.82 42753.84
cutting and making good the walls floors wherever jaquar make cat.no. FLS-
WHT-0401 ,ALD-709 or equivalent
Providing and fixing CP brass bottle trap with wall connection pipe for wash
8 M.R.
basins and urinals. Jaquar make cat. ALD-769L250x190 or EQUIVALENT
(i) 32 mm dia Each 18 1369.49 24650.82
Providing and fixing C.P. brass towel ring with C.P. brass wall brackets & C.P
9 M.R. brass screws complete as required. Jaquar make cat. ACN-1121BN or Each 10 754.74 7547.40
EQUIVALENT
Providing and fixing C.P. brass liquid soap container with C.P. brass lid and
brackets fixed to wall with wooden cleats and C.P. brass screws, including
10 M.R. Each 10 1031.15 10311.50
cutting and making good the walls wherever required. Jaquar make cat. ACN-
1135N or EQUIVALENT
Providing and fixing CP brass twin coat hooks fixed on toilet door/wall with CP
11 M.R. Each 6 490.00 2940.00
brass screws. Jaquar Make Cat. No ACN-1161N or EQUIVALENT
Supplying, Fixing , testing & commissioning of two way CP brass Bib Cock with CP
brass stop cock and ABS Heath Faucet (complete with hook and flexible SS tube
12 M.R. Nos. 6 2610.64 15663.84
min. Length 1.0 m) as required. Jaquar Make Cat. No. VGP-81041 , ALD-CHR-
583 , LYR-38083 or EQUIVALENT
Providing, fixing, testing & commissioning of C.P. brass eurometic self closing
13 M.R. Nos. 12 1722.18 20666.16
pillar tap. Jaquar Make Cat. No. 031] or EQUIVALENT
(i) WITH 50 LPH RO System with 60 ltr HTP Storage tank Each 2 81375.88 162751.76
50 Lph RO System including with, RAW WATER PUMP, MICRON
FILTER, MEMBRANE HOUSING, Membrane Boosting Pump, RO
(ii) Each 2 39902.68 79805.36
Membranes, CONTROL INSTRUMENTS, SKID Hanging with Pressure
tank of capacity of 60 Ltr.
Providing and fixing adjustable type wash basin for handicap toilet
15 M.R. complete with brackets, tracks, waste pipes and other accessories complete Each 2 47920.37 95840.74
as required. [Presalit -Commander Make Cat. No. R4140]
Providing and fixing 2 Nos. support arms and backrest to mounted on the
16 M.R. track (vertically and laterally) for handicap toilet complete as required. Each 2 102250.23 204500.46
[Presalit -Commander Make Cat. No. R 3548 XXX & 6533]
Providing and fixing raised toilet seat with cover for handicap toilet
17 M.R. Each 2 37829.61 75659.22
[Presalit -Commander Make Cat. No. R34000]
Providing and fixing ABS alloy steel grab bar. [Presalit -Commander Make
18 M.R. Each 6 9378.20 56269.20
Cat. No. RT 100 XXX]
TOTAL FOR SUB HEAD-I 105583.70 816203.38
Providing and fixing bend of required degree with access door, insertion
5 17. 38
rubber washer 3 mm thick, bolts and nuts complete.
17.38.1 100 mm
17.38.1.2 Sand cast iron S&S as per IS-3989 Each 21 385.70 8099.70
17.38.2 75 mm
17.38.2.2 Sand cast iron S&S as per IS-3989 Each 2 318.50 637.00
Providing and fixing single equal plain junction of required degree with
8 17. 43
access door, insertion rubber washer 3mm thick, bolts and nuts complete.
17.43.1 100x100x100mm
17.43.1.2 sand cast iron S&S as per IS-3989 Each 20 623.80 12476.00
17.43.2 75x75x75mm
17.43.2.2 sand cast iron S&S as per IS-3989 Each 5 472.95 2364.75
9 17. 44 Providing and fixing single equal plain junction of required degree
17.44.1 100x100x100mm
17.44.1.2 sand cast iron S&S as per IS-3989 Each 12 576.20 6914.40
17.44.2 75x75x75mm
17.44.2.2 sand cast iron S&S as per IS-3989 Each 5 405.60 2028.00
Providing and fixing single unequal junction of required degree with access
10 17. 47
door, insertion rubber washer 3mm thick, bolts and nuts complete.
17. 47.1 100x100x75mm
17.47.1.2 sand cast iron S&S as per IS-3989 Each 5 792.20 3961.00
Providing lead caulked joints to sand cast iron /centrifugally cast (spun)
13 17. 58
iron pipes and fittings of diameter:
17.58.1 100 mm Each 128 243.75 31200.00
17.58.2 75 mm Each 50 205.30 10265.00
Providing and fixing M.S. stays and clamps for sand cast iron /
14 17. 59
centrifugally cast (spun) iron pipes of diameter :
17.59.1 100 mm Each 10 68.60 686.00
Providing and fixing trap of self cleansing design with screwed down or
15 17.60 hinged grating with or without vent arm complete, including cost of cutting
and making good the walls and floors: (F.T. + U.T.)
17.60.1.1 100 mm inlet and 100 mm outlet (Sand cast iron S&S as per IS: 3989 Each 14 982.55 13755.70
Painting sand cast iron / centrifugally cast (spun) iron soil, waste vent
16 17.65 pipes and fittings with paint of any colour such as chocolate, grey, or buff
etc. over a coat of primer (of approved quality) for new work:
17.65.1 100 mm diameter pipe Metre 102 38.65 3942.30
17.65.2 75 mm diameter pipe Metre 25 29.50 737.50
Providing and fixing G.I. (class-C) pipes and fittings conforming to IS: 1239
clamps and hinges including cutting chases and holes and making good the
17 18.10
walls and ceiling for waste pipes from wash basins, urinals kitchen sink
and equipment waste connections
18.10.5 40 mm nominal bore Metre 28 425.65 11918.20
18.10.6 50 mm nominal bore Metre 36 527.20 18979.20
Providing & fixing 100mm x 50mm G.I. waste with reducing elbow &
19 M.R. nipple cutting chases, the floor / slab, repairs complete as required and Each 6 1227.69 7366.14
connection to GI / CI waste pipe. JINDAL OR EQUIVALENT
Providing and fixing G.I. EXTENSION PIECE for 100 mm dia floor trap
formed out of main pipe (Type A) with multiple side inlets, suitable for
various dia pipes, side connections, including all fixtures and fittings as per
22 M.R. Each 14 1256.41 17589.74
site conditions and as per standard details and water tight sealing of joints
and area surrounding the grating and as directed. Jayna OR
EQUIVALENT
Providing and fixing clean out plug comprising of GI socket caulked to pipe
and cast brass plug with suitable inlet key for opening male threaded joint
23 M.R.
with GI class 'C' pipe & socket. Including lead caulked to CI pipes complete
as required.Jayna OR EQUIVALENT
(i) 100 mm dia Each 8 411.03 3288.24
Providing and fixing cleaning eye on horizontal CI soil & waste pipes of 300
mm long GI medium class pipe with one plain end lead caulked in to the
collar of CI pipe and the other end with flange which in covered by
24 M.R.
neoprene rubber gasket and blank flange, complete with nuts, bolts etc and
hot dip galvanization after fabrication to the satisfaction of Engineer in
Charge GMGR OR EQUIVALENT
(i) 100 dia Each 5 936.03 4680.15
TOTAL FOR SUB HEAD-II 350852.30 373669.82
Providing and fixing G.I. pipes complete with G.I. fittings and clamps, i/c
3 18.10
cutting and making good the walls etc.
Internal work - Exposed on wall
18.10.1 15 mm dia nominal bore Metre 5 215.10 1075.50
18.10.2 20 mm dia nominal bore Metre 5 249.30 1246.50
18.10.3 25 mm dia nominal bore Metre 5 304.15 1520.75
18.10.4 32 mm dia nominal bore Metre 115 343.20 39468.00
18.10.5 40 mm dia nominal bore Metre 70 425.65 29795.50
18.10.6 50 mm dia nominal bore Metre 25 527.20 13180.00
M.R. 65 mm dia nominal bore Metre 15 742.18 11132.70
M.R. 80 mm dia nominal bore Metre 10 936.92 9369.20
M.R. 100 mm dia nominal bore Metre 5 1313.85 6569.25
Painting G.I. pipes and fittings with synthetic enamel white paint with two
4 18.38 coats over a ready mixed priming coat, both of approved quality for new
work :
18.38.1 15 mm dia nominal bore Metre 5 9.60 48.00
18.38.2 20 mm dia nominal bore Metre 5 11.35 56.75
18.38.3 25 mm dia nominal bore Metre 5 14.95 74.75
18.38.4 32 mm dia nominal bore Metre 115 17.70 2035.50
18.38.5 40 mm dia nominal bore Metre 70 21.00 1470.00
18.38.6 50 mm dia nominal bore Metre 25 24.75 618.75
Derived Rate
65 mm dia nominal bore Metre 15 29.71 445.65
from 18.38.6
Derived Rate
80 mm dia nominal bore Metre 10 33.56 335.60
from 18.38.6
Derived Rate
100 mm dia nominal bore Metre 5 41.28 206.40
from 18.38.6
Derived Rate
150 mm dia nominal bore Metre 5 56.45 282.25
from 18.38.6
Providing and fixing C.P. brass angle valve for basin mixer and geyser
5 18.53
points of approved quality conforming to IS:8931 a) 15 mm nominal bore
18.53.1 15 mm nominal bore Each 25 507.70 12692.50
Providing & fixing full way lever operated forged brass ball valve of brass
body with forged brass hard chrome plated steel ball tested to a pressure
8 M.R.
not less than 10 Kg / sqcm with threaded / flanged joints complete with
nuts, bolts, gaskets, washers ZOLOTO OR EQUIVALENT
(i) 15 mm dia. Each 1 287.18 287.18
(ii) 20 mm dia. Each 1 376.03 376.03
(iii) 25 mm dia. Each 1 566.28 566.28
(iv) 32 mm dia. Each 12 944.10 11329.20
(v) 40 mm dia. Each 1 1304.87 1304.87
Providing and fixing Butter fly valve with nitrile seat and stainless steel
stem with lever operation and cast iron body in powder coated finish,
9 M.R. suitable for test pressure of 10Kg/sq.mm) with flanges, gaskets and
necessary pad locking arrangement complet ZOLOTO OR
EQUIVALENT
(i) 65 mm dia. Each 2 2012.95 4025.90
(ii) 80 mm dia. Each 2 2247.18 4494.36
(iii) 100 mm dia. Each 1 2951.67 2951.67
TOTAL FOR SUB HEAD-III 185464.15 96184.47
Extra over for item no. 1.1 excavating trenches for pipes, cables etc. in all
3 2.11 kinds of soil for depth exceeding 1.5 m, but not exceeding 3 m. (Rate is over Metre 60 283.28 16996.80
corresponding basic item for depth up to 1.5 metre)
Providing, laying and jointing glazed stoneware pipes class SP-1 with stiff
4 19.1 mixture of cement mortar in the proportion of 1:1 (1 cement : 1 fine sand)
including testing of joints etc. complete:
19.1.1 100 mm dia S.W. pipe Metre 10 206.55 2065.50
19.1.2 150 mm dia S.W. pipe Metre 10 314.35 3143.50
19.1.4 250 mm dia S.W. pipe Metre 60 696.50 41790.00
Providing and fixing square-mouth S.W. gully trap class SP-1 complete
with C.I. grating brick masonry chamber with water tight C.I. cover with
7 19.4
frame of 300 x300 mm size (inside) the weight of cover to be not less than
4.50 kg and frame to be not less than 2.70 kg as per standard design:
19.4.1 100x100 mm size P type
With common burnt clay F.P.S. (non modular) bricks of class designation
19.4.1.1 Each 4 1571.25 6285.00
7.5
Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with
8 19.6 collars jointed with stiff mixture of cement mortar in the proportion of 1:2
(1 cement : 2 fine sand) including testing of joints etc. complete.
Inside size 90 x 80 cm and 45 cm deep including C.I. cover with frame (light
19.7.1 duty) 455 x 610 mm internal dimensions total weight of cover and frame to
be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg)
19.7.1.1 With F.P.S. bricks with class designation 75 Each 15 8507.00 127605.00
Inside size 120 x 90 cm and 90 cm deep including C.I. cover with frame
19.7.2 (medium duty) 500 mm internal diameter, total weight of cover and frame
to be not less than 116 kg (weight of cover 58 kg and weight of frame 58 kg)
19.7.2.1 With F.P.S. bricks with class designation 75 Each 5 18304.45 91522.25
Providing and filling sand of grading zone V or coarser grade alround the
6 18.41
G.I. pipes in external work.
18.41.3 25 mm dia nominal bore Metre 10 69.05 690.50
18.41.4 32 mm dia nominal bore Metre 25 70.85 1771.25
Providing, fixing, joints and testing in position the following UPVC Pipe
conferming to IS:4985 of 6kg sqcm for garden irrigation system cut to
2 MR
required length pipe to be laid below level in trenches up to required depth,
including excavation in all kind SFMC OR EQUIVALENT
(i) 32 mm OD metre 10 218.08 2180.80
(ii) 75 mm OD metre 100 419.10 41910.00
(iii) 90 mm OD metre 15 467.56 7013.40
(iv) 110 mm OD metre 10 685.64 6856.40
The above installation shall be complete with sump pump lifting assembly,
ready made electro – galvanized MS lifting chain, GI pipe header complete
with discharge manifold, flanges, tee, elbow etc. complete including GI pipe
upto the top of sump and including GI union. Header shall be sized for
both pump working under delivery velocity of 1.5 m/sec.
Capacity of 45 lpm against a total head of 50 m (solid handling 5-8 mm)
(Domestic water transfer from UGT to OHT) (1 Working + 1 Stand by) (SS Set 1 54801.91 54801.91
Body and SS Impeller and shaft)
Capacity of 25 lpm against a total head of 50m (solid handling 5-8 mm)
(Flushing water transfer from UGT to OHT) (1 Working + 1 Stand by) (SS Set 1 54801.91 54801.91
Body and SS Impeller and shaft)
To indicate 5 levels of water in all tanks through a control panel with LEDs
To start the pumps in a cyclic order.
The system shall be complete to ensure automatic quotation of pump in
accordance to water level in respective tanks.
The Contractor will include all the over head tanks and all the pumps as
Set 2 19216.79 38433.58
required for level control in this item
TOTAL CARRIED TO SUMMARY 148037.40
1 LT PANEL
Design, fabrication, supplying, assembling, erecting, connecting, testing and commissioning of
dust,damp and vermin proof free floor standing sheet steel enclosed non-drawout moduler type LT
Panel, fabricated out of suitable sized angle iron and flats, base channel and covered with 2.0mm thick
CRCA sheet, duly painted complete with earth bus, aluminium bus bar, numbering & sign writing,
interconnection & including the cost of connection through bus bar / copper conductor flexible
connection with necessary interlocking with existing panel as shown in drawing as per specification and
mounted with the followings. Trafo and DG incomers alongwith buscoupler shall be colour coded
compartment.The Panel shall have IP-54 rating of form-4.
A INCOMING:
1 Nos. 250amps, 415V 4P MCCB '25ka' with overcurrent and short circuit TM release.
i) 1 Set of three phase R,Y,B, ON indicating lamps, along with 2A SP MCB backup protection.
B BUSBAR:
Three phase and neutral Aluminium extensible type busbars rated at 415V, 315 amps capacity insulated
with heat shrinkable coloured PVC sleeves.
C OUTGOINGS:
Following rated 415V, MCCB's with overcurrent and short circuit releases, all indication, front operating
handle & door interlock with Multifunction Meter with Volt, Amp and KWH etc. complete with RS Port in
all respects as mentioned in specifications and as required. For each outgoing:
100A, FP, 25KA, MCCB manually operated - 4 No.(1 for light power panel + ODU + VENTILATION +1
iii)
spare)
63A, FP, 25KA, MCCB manually operated - 6 No. ( 1 No. For Lift Panel + 1 No. For Fire Fighting Panel
v) 1 Set 447411.17 0.00 447411.17
+ 1 external lighting + 1 UPS + 1 No. Euipment panel +1 spare )
B BUSBAR:
Three phase and neutral Aluminium extensible type busbars rated at 415V, 160 amps capacity insulated
with heat shrinkable coloured PVC sleeves.
C OUTGOINGS:
Following rated 415V, MCCB's with overcurrent and short circuit releases, all indication, front operating
handle & door interlock with Multifunction Meter with Volt, Amp and KWH etc. complete with RS Port in
all respects as mentioned in specifications and as required. For each outgoing:
Outgoing:-
All outgoing feeders shall be provided with On indicating lamp with 2 A SP MCB protection
a) 4 Nos. 63A 4P MCB with 10kA Breaking Capacity ( 3 Nos. for power DB +1 Spare)
3 UPS PANEL
Supplying, Installation, Testing and Commissioning of dust, damp and vermin proof free floor standing /
wall mounted factory built sheet steel enclosed modular construction extendable panel, suitable for
operation on 415 + 10% volts, 50 Hz AC 3 phase 4 wire system fabricated out of suitable sized square
tubular section and covered with 2.0mm thick CRCA sheet, hinged doors of 1.6mm thick CRCA sheet,
duly painted complete with aluminium bus bars, interconnection with solid copper conductor wires /
aluminium strips, neutral links, earth bus etc. necessary metering protections & indications and mounted
with the following as per drawing and technical specifications attached etc. complete as required.
INCOMING :
1 No. of 63 Amp 4P MCCB of 25 kA Breaking capacity with On Indicating Lamp with 2A SP MCB back-
up.
BUSBAR:
100 Amp. 4P Al. Bus Bar
OUTGOING
63A 4P MCB of 10kA Breaking Capacity - 2 Nos. 1 Set 30162.81 0.00 30162.81
4 EQUIPMENT PANEL
Supplying, Installation, Testing and Commissioning of dust, damp and vermin proof free floor standing /
wall mounted factory built sheet steel enclosed modular construction extendable panel, suitable for
operation on 415 + 10% volts, 50 Hz AC 3 phase 4 wire system fabricated out of suitable sized square
tubular section and covered with 2.0mm thick CRCA sheet, hinged doors of 1.6mm thick CRCA sheet,
duly painted complete with aluminium bus bars, interconnection with solid copper conductor wires /
aluminium strips, neutral links, earth bus etc. necessary metering protections & indications and mounted
with the following as per drawing and technical specifications attached etc. complete as required.
INCOMING :
1 No. of 63Amp 4P MCCB of 25 kA Breaking capacity with On Indicating Lamp with 2A SP MCB back-
up.
BUSBAR:
100 Amp. 4P Al. Bus Bar
OUTGOING
63A 4P MCB of 10kA Breaking Capacity - 6 Nos. 1 Set 46500.63 0.00 46500.63
Supply, Installation, Testing and Commissioning of (3 phase IN & 3 phase OUT) UPS system suitable for
input and output parameters strictly as per specifications. The system shall be provided in powder coated
fan cooled enclosure painted in colour as per specifications. The system shall be suitable for normal,
1 MR emergency, recharge, by-pass and maintenance mode. The system be expandable in such a manner
that addition of another module of similar capacity can double the system output with common by-pass.
inverter shall have own batteries with 15 minute battery back-up. System shall have a voltage range of
380V to 450V
1.1 10 KVA UPS described as above 1 Each 391548.49 0.00 391548.49
SUB HEAD - III- LT CABLES , RACE WAYS , CABEL TRAYS & EARTHING
Supply, laying, testing and commissioning of 1.1 kv grade XLPE insulated PVC sheathed steel
armoured alluminium stranded conductor ISI marked LT Cables in trenches/ ducts/ through RCC pipes
under roads/ on cable trays of following sizes, complete all as specified (as per CPWD specifications for
1 MR
External Electrical works), i/c clamping, dressing, earth work digging, sand filling, bricks protection, back
filling etc. as required & approved by Engineer's Incharge. (Tagging to be provided with aluminium strips
on both the ends as approved).
Supplying and making end termination with double brass compression gland and aluminium lugs for
2 9.1 following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as
required.
2.1 9.1.21 3.5 core X35 Sq.mm 2 Set 270.00 540.00 0.00
Supplying and installing following size of perforated pre-painted M.S. cable trays with perforation not
3 4.1 more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S.
suspenders including bolts & nuts, painting suspenders etc as required.
3.1 4.1.4 300 mm width X 50 mm depth X 1.6 mm thickness 50 Mtr 789.00 39450.00 0.00
3.2 4.1.2 150 mm width X 50 mm depth X 1.6 mm thickness 50 Mtr 520.00 26000.00 0.00
Supply, installation & testing of advance maintenance free Chemical Gel Earthing of Dual Pipe
Technology (GI) of 3mtr long 80mm dia of outer shell (MS) with the 50mm dia of inner shell (MS) of 80-
100 microns galvanized earth electrode filled with highly conducting metallic compounds with the
permanent sealings at both the ends with the lead terminal of 50 x 10mm size at the top along with 50
4 MR Kgs of chemical mixture of Resistance Lowering Grounding Minerals. The loss on ignition by mass of the 4 Set 19720.25 0.00 78881.00
chemical compound shall be less than 20%. The chemical compound should be tested and certified by
any International accredited and BIS (Bureau of Indian Standards) accredited laboratory. The earth
electrode shall be duly tested & certified by CPRI (Central Power Research Institute), Govt of India. The
chemical earth electrode manufacturer shall be an ISO 9001: 2008 & ISO 14001: 2004 certified
organization. The Earth pit should be covered with heavy duty polyplastic weather proof chamber.
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including
6 5.11 80 Mtr. 421.00 33680.00 0.00
connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
7 5.15 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. 120 Mtr. 142.00 17040.00 0.00
Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including
8 5.10 50 Mtr. 1082.00 54100.00 0.00
connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required.
9 5.14 Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. 30 Mtr. 856.00 25680.00 0.00
Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing along with existing
10 5.18 250 Mtr. 23.00 5750.00 0.00
surface/ recessed conduit/ submain wiring/ cable as required.
Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated
copper conductor single core cable in surface / recessed medium class PVC conduit, with modular
1 1.10.1 380 Point 518.00 196840.00 0.00
switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper
conductor single core cable etc. as required.
Wiring for light/ power plug with 2X4 sq. mm FRLS PVC insulated copper conductor single core cable in
2 1.12 surface/ recessed medium class PVC conduit alongwith 1 No. 4 sq. mm FRLS PVC insulated copper 550 Metre 162.00 89100.00 0.00
conductor single core cable for loop earthing as required.
Wiring for light/ power plug with 4X4 sq. mm FRLS PVC insulated copper conductor single core cable in
3 1.13 surface/ recessed medium class PVC conduit alongwith 2 Nos. 4 sq. mm FRLS PVC insulated copper 80 Metre 275.00 22000.00 0.00
conductor single core cable for loop earthing as required.
4.2 1.14.2 2 x 2.5 sq. mm + 1 x 2.5 sq. mm earth wire 150 Metre 131.00 19650.00 0.00
4.3 1.14.4 2 X 6 sq. mm + 1 X 6 sq. mm earth wire 50 Metre 221.00 11050.00 0.00
4.4 1.14.10 4 X 10 sq. mm + 2 X 6 sq. mm earth wire 90 Metre 597.00 53730.00 0.00
4.4 1.14.11 4 X 16 sq. mm + 2 X 6 sq. mm earth wire 30 Metre 883.00 26490.00 0.00
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess,
5 1.31 including providing and fixing 3 pin 5/6 A modular socket outlet and 5/6 A modular switch, connections 24 Each 303.00 7272.00 0.00
etc. as required.
Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess,
6 1.32 including providing and fixing 6 pin 5/6 A & 15/16 A modular socket outlet and 15/16 A modular switch, 67 Each 395.00 26465.00 0.00
connections etc. as required.
Supplying and fixing of following sizes of medium class PVC conduit along with accessories in
9 1.21 surface/recess including cutting the wall and making good the same in case of recessed conduit as
required.
9.1 1.21.1 20 mm 350 Metre 53.00 18550.00 0.00
Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding
10 1.26 10 Each 23.00 230.00 0.00
modular plate as required
Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB
distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A, tinned copper
1 2.5
bus bar, common neutral link, earth bar, din bar for mounting MCBs (but without MCBs and incomer) as
required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.)
1.1 2.5.6 12 way (4+36), Double door 1 Each 7165.00 7165.00 0.00
Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V,
2 2.3 on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar,
interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator)
2.1 2.3.3 12 way, Double door 1 Each 1151.00 1151.00 0.00
Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for
3 2.10 inductive load of following poles in the existing MCB DB complete with connections, testing and
commissioning etc. as required.
3.1 2.10.1 Single Pole 94 Each 169.00 15886.00 0.00
Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with
4 2.13
connections, testing and commissioning etc. as required.
4.1 2.13.2 63 amps 3 Each 670.00 2010.00 0.00
Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current
5 2.14 circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with
connections, testing and commissioning etc. as required.
5.1 2.14.2 40 amps 13 Each 1714.00 22282.00 0.00
6 2.11 Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required. 10 Each 7.00 70.00 0.00
Supplying of the following light fixtures complete with housing, reflectors, all accessories i.e. copper
1 wound Electronic ballast, HPF condensers, starters, holders, hanging/fixing arrangements etc. complete
as required
1200mm CEILING FAN (Make Havells ES-50 Premium 5 or Anchor Pansonic STILER PLUS ISI & 5
1.1 MR 107 Nos. 1984.23 0.00 212312.61
STAR or equivalent Crompton, Orient, Usha)
300 mm SWEEP EXHAUST FAN (1400 RPM) (Make Havells Turbo Force SP or equivalent Crompton,
1.2 MR 4 Nos. 3014.49 0.00 12057.96
Orient, Usha)
40W LED LIGHT (Make Panasonic PBTM04406 or Bajaj BLRB 218W LED XE TUBE + BATTEN
1.4 MR 191 Nos. 2110.77 0.00 403157.07
4500Lm or Equivalent Philips, Wipro)
1X18W LED LIGHT (Make Panasonic PDLM03207 or Bajaj BGSLO 18W LED SURFACE RD or
1.6 MR 25 Nos. 1219.62 0.00 30490.50
Equivalent Philips, Wipro)
1x40W LED LIGHT (Make Panasonic PBLM01367 or Bajaj BLRB 218W LED XE TUBE + BATTEN
1.7 MR 4 Nos. 2110.77 0.00 8443.08
4500Lm or Equivalent Philips, Wipro)
1X18W LED TUBE LIGHT (Make Panasonic PTUM02187 or Bajaj BLRB 118 LED XE or Equivalent
1.8 MR 2 Nos. 421.79 0.00 843.58
Philips, Wipro)
10W MIRROR LIGHT (Make Panasonic PBTMO1107 or Bajaj BCLN 10W LED or Equivalent Philips,
1.9 MR 12 Nos. 262.95 0.00 3155.40
Wipro)
10W BULKHEAD (Make Panasonic PBHM01107 or Bajaj BIBWP 10W LED or Equivalent Philips,
1.10 MR 1 Nos. 769.10 0.00 769.10
Wipro)
Installation, testing and commissioning of ceiling fan, including wiring the down rods of standard length
2 1.44 109 Nos. 95.00 10355.00 0.00
(upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable etc. as required.
Installation of exhaust fan in the existing opening, including making good the damage, connection,
3 1.50
testing, commissioning etc. as required.
3.1 1.50.1 Upto 450 mm sweep 4 Nos. 204.00 816.00 0.00
Installation, testing and commissioning of pre-wired, fluorescent fitting / compact fluorescent fitting of all
4 1.41 types, complete with all accessories and tube/lamp etc. directly on ceiling/ wall, including connections 271 Nos. 91.00 24661.00 0.00
with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC
1 1.53
conduit as required.
1.1 1.53.1 1 run of cable 180 Metre 33.00 5940.00 0.00
Supplying and drawing following pair, 0.5 sq.mm FRLS PVC insulated copper conductor, unarmoured
2 1.18
telephone cable in the existing surface / recessed steel / PVC conduit as required.
2.1 1.18.2 2 Pair 240 Metre 18.00 4320.00 0.00
Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated,
3 1.19 shielded with fine tinned copper braid and protected with PVC sheath in the existing surface / recessed 25 Metre 28.00 700.00 0.00
steel / PVC conduit as required.
Supplying and fixing following modular switch / socket on the existing modular plate & switch box
5
including connections but excluding modular plate etc. as required.
5.1 1.24.7 TV antenna socket outlet 1 Each 94.00 94.00 0.00
5.3 MR Socket for RJ 45 Jack for Cat - 6 Cable 6 Each 507.95 0.00 3047.70
Supplying and Fixing following sizes / modules , GI box along with modular base & cover plate for
6
modular switches in recess etc as required.
6.1 1.27.1 1 or 2 Module (75mmX75mm) 15 Each 166.00 2490.00 0.00
Supply, erection, testing and commissioning of following tap off / splitter as per specification in 1.6mm
7 MR
thick CRCA sheet steel enclosure for CATV system.
7.1 MR 4 way splitter box 1 Each 237.82 0.00 237.82
Supplying and fixing of following sizes of steel conduit along with accessories in surface / recess
8 1.20 including painting in case of surface conduit, or cutting the wall and making good the same in case of
recessed conduit as required.
8.1 1.20.1 20 mm 50 Metre 121.00 6050.00 0.00
Supply, assembly, erection, connecting, testing & commissioning of LT weather proof dust and vermin
proof (IP-65), outdoor feeder pillar, fabricated out of suitable sized angle iron and flats and covered with
3mm thick CRCA sheet steel including canopy, duly stove enamel painted, both sides (front and rear)
openable with locking arrangement, rubber gasket cable glands, etc. Bakelite phase separators and bus
1 bar supports including RCC 1:2:4 (1 cement: 2 coarse sand : 4 graded stone aggregate 20mm nominal
size) foundation, 450 mm deep and 150 mm above the ground. The feeder pillars shall be complete with
3 phase and neutral bus bars of capacities as described below and moulded case circuit breakers
(MCCBs) with adjustable overload relay, copper FRLS control wiring with 1.5sq.mm, complete in all
respects as per specifications as required.
INCOMING:-
OUTGOING:-
a) 70 AMP. TP CONTACTOR WITH NO/ NC CONTACTS -1 set.
b) 24 HOUR TIMER - 1 set.
c) 20A 4P MCB (10ka) - 5 nos.
d) 16A DP MCB (10ka) - 2 nos.
e) 63A 4P MCB (10ka) - 1 no.
16 AMP. SWITCH & SOCKET - 1 no. with in the feeder pillar.
M.R. External Lighting Feeder Pillar as above 1 Set 74149.72 0.00 74149.72
Supply of standard 6.0 metre high (above ground) hot dip galvanized (grading of galvenisation average
70 micron or better as per IS2629 or equivalent) octagonal pole, as per IS 875 Part-3, with stiffeners,
chain, allen bolt, single arm bracket one metre long, foundation bolt, anchor plate, template, nut and
washers galvanized, factory finish base plate of size 250 x 250 x 12 mm etc complete as required. The
2 MR 15 Nos 14918.97 0.00 223784.55
pole shall be made of 3 mm thickness sheet with tolerance of +/- 5%. The column shall also be provided
with flush door at the bottom with proper strengthening to the cutout of the door opening, a junction/
looping box with Heavy duty 3 phase, 32 Amp connector with 16A DP MCB including all accessories
complete as required. (make & model will be selected by the client).
Supply of solar power Street Lighting Fixture complete with 7.5 meter long Octaganol GI poles as per
approved makes and as per standard design. The luminaire shall be of aluminium die cast construction
3 MR
with minimum IP65 protection with inter-connection copper cable from solar panel to battery, to controller
and to luminaire etc as required.
The storage capacity of the battery should be sufficient to run the full load for 18 hours on rainy/ heavy
cloudy days.The unit should also have an additional AC charging arrangement to charge the batteries in
case of very long heavy cloudy days
A junction chamber of size 300mm/ 100mm with cable termination arrangement connector block and 1
No. 10 Amp SPMCB shall be provided. The street light fixture shall be 1 x 70 watt capacity with LED
bulbs of white colour of 1 watt each. the fixture shall be complete with control gear for auto switching
ON, switching OFF supplementary power charging in case of non availability of solar power on very long
heavy cloudy days etc. as required. The solar panel shall be of sufficient capacity to charge the sealed
maintenance free battery of minimum 160 AH capacity. The RCC pedestral shall be made of 1:2:4 ratio
as required.
The column shall be smooth surface finished degreased, derusted, primary coated, cavity sealed and
painted with PU based self curing polyurethane based automotive paint. Complete item will be finalised 2 Nos 122932.53 0.00 245865.06
by the client/ consultant.
Receiving, Assembly, Erection, Testing & Commissioning of Street Lighting Fixture complete with
6.0 meter long octagonal GI pole with excavation, back filling,all material, steel reinforcement with cold
twisted bar, PCC with 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)
4 MR & main foundation 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), 15 Nos 4935.90 0.00 74038.50
fixing of 'J' Bolts ('J' bolts provided by other agency) including curing, back filling etc. as required,
including suitable length of 32 mm GI pipe for cable entry size & design of foundation as per standard
design & approved by the consultant/ client etc. as required.
Receiving, Assembly, Erection, Testing & Commissioning of Street Lighting Fixture complete with
7.5 meter long octagonal GI pole with excavation, back filling,all material, steel reinforcement with cold
twisted bar, PCC with 1:3:6 (1 Cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size)
5 MR & main foundation 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), 2 Nos 4935.90 0.00 9871.80
fixing of 'J' Bolts ('J' bolts provided by other agency) including curing, back filling etc. as required,
including suitable length of 32 mm GI pipe for cable entry size & design of foundation as per standard
design & approved by the consultant/ client etc. as required.
Supply of following luminaries (IP-65) with housing made of single piece high pressure die cast
6 alluminium alloy/ as per standards, energy efficient copper ballast, heat resistant toughened flat glass /
cover glare free, pole mounting mechanism etc. (make & model will be approved by the client).
post top fixture (Bajaj cat. LED POLE LIGHT - BAJAJ BRIL 45W LED WH or Panasonic make
6.1 MR 15 Nos 13415.77 0.00 201236.55
APT010404 or equivalent from approved Philips, Panasonic, Wipro makes). pole light.
Parking are to be considered lig
Supply, laying, testing and commissioning of 1.1 kv grade XLPE insulated PVC sheathed steel
armoured alluminium stranded conductor LT Cables including both end termination with lugs & brass
glands in trenches/ ducts/ through RCC pipes under roads of following sizes, complete all as specified
7
(as per CPWD specifications for External Electrical works) including the cost of digging and back filling
the trenches, sand filling, brick covering for protection etc complete as required & approved by
Engineer's Incharge. (Tagging to be provided with aluminium strips on both the ends as approved).
7.1 MR 4 core X 4 Sq.mm (For external Lights) 300 Meter 113.08 0.00 33924.00
8 5.16 Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. 300 Meter 35.00 10500.00 0.00
9 5.15 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. 50 Meter 142.00 7100.00 0.00
Supply, Installation, Testing & Commissioning of ONVIF compliant Outdoor IP67 IK10 Weatherproof and
Vandalproof IP PTZ Camea with 1/3” progressive scan color CMOS image sensor, 3MP, H.264 / Motion-
JPEG - Triple streams, individually configurable, Multiple video profiles support, 2048x1536 at 20fps;
1 MR 1920x1080 at 30/25fps, Auto-iris, Autofocus, 24x Optical zoom and 240x total zoom, 0.03 lux @ F1.6 1 Nos. 238554.55 0.00 238554.55
(Color) 0.01 lux @ F1.6 (B/W), 360° endless pan, 0~92° tilt with auto flip, 128 presets, 4 patrol tour.
Audio-In/Out 1/0, Alarm-In/Out 4/1, SD card Slot, PoE+, CE / FCC / RoHS compliant.
Supply, Installation, Testing & Commissioning of ONVIF compliant Outdoor, Weatherproof (IP66),
Vandalproof (IK10) IP Bullet Camera with 1/3” progressive scan color CMOS image sensor, 3MP,
H.264/Motion-JPEG - Triple streams, individually configurable, Multiple video profiles support. 2048 x
1536 at 20 FPS and 1920 x 1080 at 30/25 FPS, motorized varifocal lens, f3- 9mm, F1.2, auto-iris, auto-
2 MR 4 Nos. 28635.38 0.00 114541.52
focus,Color: 0.3 lux at 50 IRE, F1.2; B/W: 0.01 lux at 50 IRE, F1.2; 0 lux when IR on, IR Distance of
25m, Audio in-/outputs: 1/1, Alarm in-/outputs: 1/1, microSD Card slot, Operating temperature: -10 °C to
50 °C, PoE, CE / FCC / RoHS compliant.
Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC
3 1.53
conduit as required.
3.1 1.53.1 1 run of cable 200 Metre 33.00 6600.00 0.00
Supply, Installation, Testing & Commissioning of 3 Core 1.5Sq Mm power cable in the existing surface /
4 MR 100 Metre 96.92 0.00 9692.00
recessed steel conduit/HDPE pipe as required technical specification.
Supply, Installation, Testing & Commissioning of POE+ Enabled Layer 2 Manageable network switch
with 24 x 10/100/1000 BaseT Copper Port,4 x1000 Base-X Ports (4 x 1000 Base X Ports are Combo
5 MR Shared with 4 x 10/100/1000 Base-T ports) populated with 2 x SM fiber Module plus additional dedicated 1 nos. 315632.61 0.00 315632.61
stacking Ports with stacking bandwidth of 40Gbps or more as required as per technical specification.
Supply, Installation, Testing & Commissioning of 12 port LIU splice box/ tray for field network switched
6 MR complete with fiber splicing, pigtails, Adapters, splicing joints, complete as required as per techncal 1 Nos. 20841.15 0.00 20841.15
specification
Supply, Installation, Testing & Commissioning of 24 port LIU splice box/ tray for Main Control room
7 MR complete with fiber splicing, pigtails, Adapters, splicing joints, complete as required as per technical 1 Nos. 33501.27 0.00 33501.27
specification.
Supply, Installation, Testing & Commissioning of modular furniture for 42U Equipment Server rack of
800x1000 mm Heavy duty, with front lockable Door, Fanr tray, Power distribution , complete as required
8 MR 1 Nos. 76636.52 0.00 76636.52
technical specification.
Supplying and fixing of following sizes of steel conduit along with accessories in surface / recess
9 1.20 including painting in case of surface conduit, or cutting the wall and making good the same in case of
recessed conduit as required.
9.1 1.20.1 20 mm 30 Mtr 121.00 3630.00 0.00
Providing and fixing of lightning conductor finial, made of 25 mm dia 300 mm long, G.I. tube, having
1 6.2 10 Each 369.00 3690.00
single prong at top, with 85 mm dia 6 mm thick G.I. base plate including holes etc. complete as required.
Fixing of lightning conductor finial (single prong) with base plate including holes etc. complete as
2 6.3 10 Each 154.00 1540.00
required.
Jointing copper / G.I. tape (with another copper/ G I tape, base of the finial or any other metallic object)
3 6.4 10 Each 72.00 720.00
by riveting / nut bolting/sweating and soldering etc as required
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor
4 6.7 400 Meter 68.00 27200.00
complete as required. (For horizontal run)
Providing and fixing G.I. tape 20 mm X 3 mm thick on parapet or surface of wall for lightning conductor
5 6.8 60 Meter 98.00 5880.00
complete as required. (For vertical run)
Providing and fixing testing joint, made of 20 mm X 3 mm thick G.I. strip, 125 mm long, with 4 nos. of G.I.
6 6.12 20 Each 71.00 1420.00
bolts, nuts, chuck nuts and spring washers etc. complete as required
TOTAL - 6,64,260.22
TOTAL DSR + MR 664260.22
The cabinet shall be painted with one coat of primer and 2 coats
M.R. 8 Each 9065.00 72520.00
of synthetic enamel paint of approved shade.
Supply & fixing of Co2 type Fire Extinguisher 4.5kg capacity with
Brass forged Screw down / squeeze lever type valve, initial gas
charged as per IS 15222, rubber braided discharge hose & Horn,
2
complete with accessory as per IS:15683 with BIS mark, MTC &
PESO (OLD CCOE) certificate.Wll mounting bracket with screw.
FIRE RATING - 34B
2.1 M.R. 4.5kg capacity cylinder 8 Each 4926.92 39415.36
Incoming
MCCB, TPN, 63 A, 25 KA (with adjustable thermal magnetic
release and (ICS - 25 KA upto 433 V) - 1 No.
Digital Ammeter cum voltmeter (0 - 60 A / 0-500 V ) each
phase,96 mm. sq. CT operated with in built selector switch with 3
Nos. CT's of ratio 60/5 A, 10 VA burden and accuracy of class 1.0
- 1 Set
Phase Indicating coloured LED (RYB) with control fuses - 1 Set
Outgoing
Fully Automatic DOL Starter suitable for Terrace Pump (7.5 HP
capacity) complete with preventer complete with contactors, push
button, indicators LED type Auto/manual selector switch over load
protection, current sensing type single phase preventer push
buttons LED indicators complete with all accessories and wiring
etc. as required - 1 Set
Penal shall be enclosed with M.S. sheet to protect from weather
at terrace.
Terrace fire pump panel as above 1 Set 41843.84 0.00 41843.84
NBCC (I) Ltd.
6
CENTRAL WORKSHOP- Fire Fighting IIT Bhubaneswar
OR SAY 65,73,794.00
NAME OF THE WORK : IIT BHUBNESWAR (SH: SITC AIR CONDITIONING SYSTEM)
All the rates quoted by the contractor shall be complete finished work including cost of all labour, material, scaffolding, finishing as required with tools, plants, lead, lift, taxes,
tollage, octroi, royalties etc. except those specially excluded in the description of the individual items. All works shall be executed as per drawings, specification and
instructions of Site incharge and shall include the supply and installation at site of all the equipment, ancillary materials as specified and all such items what-so-ever which may
be required to fulfill the intent and purpose as laid down in the specification and/or the drawings. All materials shall be as per ISI specification and with IS certification marked
wherever applicable. The material shall be duly approved by Site incharge before incorporation in the actual work.
DETAILED ESTIMATE (CENTRAL WORKSHOP)
DSR Rate Market Rate DSR Amount Market Amount
S. No. DSR 2014 Description Unit Qty.
(Rs.) (Rs.) (Rs.) (Rs.)
1 VRV/VRF UNITS
1.1 Outdoor Unit
1.2 Indoor VRV Units (Nominal Capacity) - Floor Standing Duct Type
5.2 MR 34.9 mm dia with 19mm thick EPDM/nitrile rubber insulation Mtrs. 10 2030.90 20309.00
5.3 MR 28.6 mm dia with 19mm thick EPDM/nitrile rubber insulation Mtrs. 30 1920.51 57615.30
5.4 MR 22.2 mm dia with 19mm thick EPDM/nitrile rubber insulation Mtrs. 190 1811.03 344095.70
5.5 MR 19.1 mm dia with 13mm thick EPDM/nitrile rubber insulation Mtrs. 20 1701.54 34030.80
5.6 MR 15.9 mm dia with 13mm thick EPDM/nitrile rubber insulation Mtrs. 20 1591.15 31823.00
5.7 MR 12.7 mm dia with 13mm thick EPDM/ nitrile rubber insulation Mtrs. 30 1372.18 41165.40
5.8 MR 9.5 mm dia with 13mm thick EPDM/nitrile rubber insulation Mtrs. 210 1042.82 218992.20
6 Drain Piping
Providing & fixing of PVC Pipe complete with fittings, supports as per
specifications and duly insulated with 6/9 mm thickness of closed cell nitrile
rubber as per direction of Engineer-in-charge & specifications enclosed as
reqd.
6.1 MR 50 mm dia with 9 mm thick insulation Mtrs. 10 493.59 4935.90
TOTAL 2410360.42
Outer facing Reinforced aluminum. Kraft and glass veil and inner facing foil -
3.2 MR SQM. 50 1629.74 81487.00
Black glass textile.
Supplying & fixing of powder coated extruded aluminium Supply Air Grills
7 16.15 SQM. 15 7107.00 106605.00
with aluminium volume control dampers as per specifications.
Supply, fixing and commissioning of Fresh/ exhaust air louvers with section
11 MR SQM. 10 6791.79 67917.90
comprising of powder coated Aluminium louvers & bird screen as required.
Supplying, fixing acoustic lining on wall and ceiling of AHU rooms with
50mm thick, density 32 kg/cu.m resin bonded glass fiber insulation friction
fixed in 610mm x 610 mm frame work made of 25 X 50 X50 X 50 X 25 mm
1 16.22 SQM. 70 864.00 60480.00
made out of 0.6mm thick GI sheet U shaped channel and covered with
reinforced fiber glass tissue and finished with 0.80 mm perforated
aluminium sheet etc. complete as required and as per specifications.
1 VENTILATION PANEL
Supplying, of dust, damp and vermin proof free floor mounted, Indoor type
standing factory built sheet steel enclosed modular construction extendable
panel, suitable for operation on 415 ±10% volts, 50 Hz AC 2 phase 4 wire
system fabricated out of suitable sized square tubular section and covered
with CRCA sheet steel of 2mm thick for frame work and covers, 2mm thick
for gland plates i/c cleaning & finishing complete with 7 tank process for
powder coating in approved shade, complete with Aluminium bus bars, inter-
connection with copper conductor wires / aluminium strips, neutral links,
earth bus etc. necessary metering protections & indications and mounted
with the following as per drawing and technical specifications attached etc.
complete as required.
including control wiring with 1.5sqmm. & 2.5sqmm. PVC insulated FRLS
copper conductor S/C cable for voltage & current respectively, cable alleys,
cable gland plates in two half, etc. necessary metering protections &
indications and mounted with the following switch gears as per drawing and
technical specifications etc. complete as required. (Each starter should
have remote control and interlocking facilities including auto manual switch,
NO/NC contacts for control and must have auto manual operation suitable
to take signal from fire alarm panel for automatic operation of fan in case of
fire. All the starters shall have suitable facility to operate with fire sensing
control modules.
Incoming:
Bus Bar :
TPN aluminium extensible type main bus bars of minimum of 160 Amp
capacity and auxiliary bus bar of suitable capacity with heat shrinkable
coloured sleeves and i/c DMC/ SMC bus bars supports at required intervals
complete for cross section, size supports & their spacing etc.
Outgoings:
40Amp TP,10 kA MCB with Fully automatic DOL starter suitable for
operating Upto 7.5 kw motors/fan capacity, complete with contactors,Timer,
overload protection relay, current sensing type single phase preventer, ON
indications, push buttons, auto / manual / off selector switch,other
accessories. complete as required. - 16 sets.
40Amp TP,35 kA MCB - 1 No.
VENTILATION PANEL as above Set 1.00 137065.35 137065.35
Supplying and making cable end termination with brass compression glands
and aluminium lugs including inhibiting compound to be used in each lug,
3 9.1
for the following XLPE aluminium conductor armoured cables of 1.1 KV
grade etc, complete as required.
3.1 9.1.32 4 core X 10 Sq.mm 2 Set 193.00 386.00
4.2 4.1.2 150 mm width X 50 mm depth X 1.6 mm thickness 50 Mtr 520.00 26000.00