Telefono 381-6196
CUADRO N° IE - 4
SUMATORIA
TRAMO POTENCIA POTENCIA CORRIENTE LONGITUD SECCION CAIDA DE TENSION ALIMENTADOR
(kW.) (kW.) DISEÑO CABLE (m) (mm2) PUNTUAL TOTAL
(A) (A) (V) (V)
0 - 1 1.350 1.350 3.77 144 359.00 35 1.30 1.30 3 - 1 x 35 mm2 NYY+1x16mm2 NYY(T)
CUADRO N° 3.2
SUMATORIA
PUNTO POTENCIA POTENCIA CORRIENTE LONGITUD SECCION CAIDA DE TENSION ALIMENTADOR
(kW.) (kW.) DISEÑO CABLE (m) (mm2) PUNTUAL TOTAL
(A) (A) (V) (V)
0.86 0.86
1 2.160 15.120 39.68 144 32.00 35 1.22 2.08 3 - 1 x 35 mm2 NYY+1x16mm2 NYY (N)
2 2.160 12.960 34.01 144 60.00 35 1.96 4.04 3 - 1 x 35 mm2 NYY+1x16mm2 NYY (N)
3 2.160 10.800 28.34 144 29.00 35 0.79 4.83 3 - 1 x 35 mm2 NYY+1x16mm2 NYY (N)
4 2.160 8.640 22.67 94 28.00 16 1.34 6.17 3 - 1 x 16 mm2 NYY+1x16mm2 NYY (N)
5 2.160 6.480 17.01 94 31.00 16 1.11 7.29 3 - 1 x 16 mm2 NYY+1x16mm2 NYY (N)
6 2.160 4.320 11.34 94 35.00 16 0.84 8.12 3 - 1 x 16 mm2 NYY+1x16mm2 NYY (N)
7 2.160 2.160 5.67 94 34.00 16 0.41 8.53 3 - 1 x 16 mm2 NYY+1x16mm2 NYY (N)
CUADRO N° 3.2
SUMATORIA
PUNTO POTENCIA POTENCIA CORRIENTE LONGITUD SECCION CAIDA DE TENSION ALIMENTADOR
(kW.) (kW.) DISEÑO CABLE (m) (mm2) PUNTUAL TOTAL
(A) (A) (V) (V)
0.00 0.00
1 2.160 2.160 5.67 144 53.00 50 0.29 0.29 3 - 1 x 35 mm2 NYY+1x16mm2 NYY (N)
2 2.160 4.320 11.34 144 29.00 35 0.32 0.60 3 - 1 x 35 mm2 NYY+1x16mm2 NYY (N)
3 2.160 6.480 17.01 144 29.00 35 0.47 1.08 3 - 1 x 35 mm2 NYY+1x16mm2 NYY (N)
4 2.160 8.640 22.67 144 29.00 35 0.63 1.71 3 - 1 x 35 mm2 NYY+1x16mm2 NYY (N)
5 2.160 10.800 28.34 144 29.00 35 0.79 2.50 3 - 1 x 35 mm2 NYY+1x16mm2 NYY (N)
6 2.160 12.960 34.01 144 23.00 35 0.75 3.25 3 - 1 x 35 mm2 NYY+1x16mm2 NYY (N)
7 2.160 15.120 39.68 144 51.00 35 1.94 5.20 3 - 1 x 35 mm2 NYY+1x16mm2 NYY (N)
8 2.160 17.280 45.35 144 33.00 35 1.44 6.64 3 - 1 x 35 mm2 NYY+1x16mm2 NYY (N)
9 2.160 19.440 51.02 144 32.00 35 1.57 8.20 3 - 1 x 35 mm2 NYY+1x16mm2 NYY (N)
10 2.160 21.600 56.69 144 32.00 35 1.74 9.95 3 - 1 x 35 mm2 NYY+1x16mm2 NYY (N)
CUADRO N° 3.2
SUMATORIA
PUNTO POTENCIA POTENCIA CORRIENTE LONGITUD SECCION CAIDA DE TENSION ALIMENTADOR
(kW.) (kW.) DISEÑO CABLE (m) (mm2) PUNTUAL TOTAL
(A) (A) (V) (V)
0.00 0.00
1 5.460 5.460 14.33 94 30.00 16 0.86 0.86 3 - 1 x 16 mm2 NYY+1x16mm2 NYY (N)